0% found this document useful (0 votes)
19 views

CMP A2F

The document provides installation instructions and technical data for the A2F cable gland, which is designed for use in explosive atmospheres with various certifications including ATEX and IECEx. It outlines the necessary installation steps, components, and available accessories, emphasizing that installation should only be performed by a competent person. Additionally, it includes details on the cable gland's ingress protection ratings and temperature ranges for seals.

Uploaded by

melek.kharrat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
19 views

CMP A2F

The document provides installation instructions and technical data for the A2F cable gland, which is designed for use in explosive atmospheres with various certifications including ATEX and IECEx. It outlines the necessary installation steps, components, and available accessories, emphasizing that installation should only be performed by a competent person. Additionally, it includes details on the cable gland's ingress protection ratings and temperature ranges for seals.

Uploaded by

melek.kharrat
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Printed on: 02 October 2017 SCAN FOR INSTALLATION VIDEOS

TECHNICAL DATA

INSTALLATION INSTRUCTIONS FOR


CABLE GLAND TYPE : A2F
INGRESS PROTECTION : IP66, IP67, IP68, NEMA 4X
PROCESS CONTROL SYSTEM : BS EN ISO 9001
ISO/IEC 80079-34:2011
EXPLOSIVE ATMOSPHERES CLASSIFICATION

A2F CABLE GLAND


ATEX CERTIFICATION No : SIRA 13ATEX1068X, SIRA 13ATEX4074X
ATEX CERTIFICATION CODE : II 2G, II 1D Ex d IIC Gb, Ex e IIC Gb, Ex ta IIIC Da
: II 3G Ex nR IIC Gc I M2 Ex d I Mb, Ex e I Mb
IECEx CERTIFICATION No : IECEx SIR 13.0023X
IECEx CERTIFICATION CODE : Ex d IIC Gb, Ex e IIC Gb, Ex nR IIC Gc, Ex ta IIIC Da, Ex d I Mb, Ex e I Mb
CSA CERTIFICATION No : 1211841
CSA CERTIFICATION CODE : Ex d IIC, Ex e II, Ex nR II, Enclosure Type 4X, Class 1, Div. 1, Div. 2, Groups B,C & D
CABLE GLAND FOR USE WITH UNARMOURED AND BRAIDED CABLES IN EXPLOSIVE
INSTALLATION INSTRUCTIONS
Installation should only be performed by a competent person using the correct tools. Spanners shoudl be used for tightening. Read all instructions before beginning installation.
SPECIAL CONDITIONS FOR SAFE USE
ATMOSPHERES
None.
ACCESSORIES
The following accessories are available from CMP Products, as optional extras, to assist with fixing, sealing and earthing:
Locknut, Earth Tag, Serrated Washer, Entry Thread (I.P.) Sealing Washer, Shroud
INCORPORATING EU DECLARATION OF CONFORMITY TO DIRECTIVE [2014/34/EU]
Available Entry Threads Combined Ordering
(Alternate Metric Thread Lengths Available) Overall Cable Across Across
Reference
Diameter Flats Corners Cable
Cable Gland Standard Option Protrusion (*Brass Metric)
Shroud Gland Weight
Size Length
Thread Length Thread Ordering (Kgs)

CABLE GLAND
Metric NPT NPT Min Max Max Max Size Type
(Metric) Length (NPT) Suffix

16 M16 15.0 - - - 3.2 8.7 24.0 26.4 25.1 16 A2F 1RA PVC04 0.060
20S/16 M20 15.0 1/2” 19.9 3/4” 3.2 8.7 24.0 26.4 25.1 20S16 A2F 1RA PVC04 0.070
20S M20 15.0 1/2” 19.9 3/4” 6.1 11.7 24.0 26.4 25.1 20S A2F 1RA PVC04 0.060
20 M20 15.0 1/2” 19.9 3/4” 6.5 14.0 27.0 29.7 27.2 20 A2F 1RA PVC05 0.070

TYPE
25 M25 15.0 3/4” 20.2 1” 11.1 20.0 36.0 39.6 35.5 25 A2F 1RA PVC09 0.130
32 M32 15.0 1” 25.0 1 1/4” 17.0 26.3 41.0 45.1 34.2 32 A2F 1RA PVC10 0.150
40 M40 15.0 1 1/4” 25.6 1 1/2” 23.5 32.2 50.0 55.0 35.1 40 A2F 1RA PVC13 0.200
50S M50 15.0 1 1/2” 26.1 2” 31.0 38.2 55.0 60.5 32.0 50S A2F 1RA PVC15 0.260
50 M50 15.0 2” 26.9 2 1/2” 35.6 44.0 60.0 66.0 36.3 50 A2F 1RA PVC18 0.270

A2F
63S M63 15.0 2” 26.9 2 1/2” 41.5 49.9 70.5 77.6 33.5 63S A2F 1RA PVC21 0.430
63 M63 15.0 2 1/2” 39.9 3” 47.2 55.9 75.0 82.5 35.8 63 A2F 1RA PVC23 0.400
75S M75 15.0 2 1/2” 39.9 3” 54.0 61.9 80.0 88.0 34.2 75S A2F 1RA PVC24 0.520
75 M75 15.0 3” 41.5 3 1/2” 61.1 67.9 84.0 92.4 40.6 75 A2F 1RA PVC26 0.500
90 M90 24.0 3 1/2” 42.8 4” 66.6 79.9 108.0 118.8 58.3 90 A2F 1RA PVC31 1.600
100 M100 24.0 4” 44.0 4” 76.0 91.0 123.0 135.3 55.2 100 A2F 1RA LSF33 1.780
115 M115 24.0 4” 44.0 5” 86.0 97.9 133.4 146.7 65.2 115 A2F 1RA LSF34 2.670
130 M130 24.0 5” 46.8 - 97.0 114.9 152.4 167.6 73.9 130 A2F 1RA LSF35 3.800
Dimensions are displayed in millimetres unless otherwise stated

Note: Standard Seal (Black) Temperature Range = -60°C to +130°C,


High Temperature Seal (Brown) Temperature Range = -60°C to +180°C for High Temperature Seal add ‘HT’ to Ordering Reference after Gland Type e.g. 20SA2FHT1RA.

CMP Products Limited on its sole responsibility declares that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following
standards:-

EN 60079-0:2012, EN 60079-1:2007, EN 60079-7:2007, EN 60079-15:2010, EN 60079-31:2009, BS 6121:1989, EN 62444:2013

David Willcock - Certification Engineer (Authorised Person)


CMP Products Limited, Cramlington, UK, NE23 1WH
24th June 2015

FI413

Certificate Revision Date

IFS 18 5/17

ATEX / IECEx 2 1/17


Glasshouse Street • St. Peters • Newcastle upon Tyne • NE6 1BS

0518
Notified Body: Sira Certification Service, Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, UK
Tel: +44 191 265 7411 • Fax: +44 1670 715 646
E-Mail: [email protected] • Web: www.cmp-products.com
CSA / cCSAus 2 1/17

www.cmp-products.com Logos shown for illustration purposes only. Please check certification for details
INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES A2F 4. Slacken the seal nut (3) to relax the seal (2).

CABLE GLAND COMPONENTS - It is not necessary to dismantled the cable gland any further than illustrated below
1. Entry Item 1 2 3
2. Seal
3. Seal Nut

PLEASE READ ALL INSTRUCTIONS CAREFULLY BEFORE BEGINNING THE INSTALLATION


1. It is not necessary to dismantle the gland any further than illustrated below.

5. Pass the cable through the gland to the desired position, then tighten the seal nut by hand until resistance is felt (when the seal
contacts the cable). Tighten with a spanner one further turn.

2. Fit the gland into the equipment and fully tighten the entry item (1).

3. Determine the conductor length required to suit the installation and prepare the cable accordingly, removing part of the outer sheath
where required to reveal the insulated conductors.

www.cmp-products.com www.cmp-products.com