CMP A2F
CMP A2F
TECHNICAL DATA
CABLE GLAND
Metric NPT NPT Min Max Max Max Size Type
(Metric) Length (NPT) Suffix
16 M16 15.0 - - - 3.2 8.7 24.0 26.4 25.1 16 A2F 1RA PVC04 0.060
20S/16 M20 15.0 1/2” 19.9 3/4” 3.2 8.7 24.0 26.4 25.1 20S16 A2F 1RA PVC04 0.070
20S M20 15.0 1/2” 19.9 3/4” 6.1 11.7 24.0 26.4 25.1 20S A2F 1RA PVC04 0.060
20 M20 15.0 1/2” 19.9 3/4” 6.5 14.0 27.0 29.7 27.2 20 A2F 1RA PVC05 0.070
TYPE
25 M25 15.0 3/4” 20.2 1” 11.1 20.0 36.0 39.6 35.5 25 A2F 1RA PVC09 0.130
32 M32 15.0 1” 25.0 1 1/4” 17.0 26.3 41.0 45.1 34.2 32 A2F 1RA PVC10 0.150
40 M40 15.0 1 1/4” 25.6 1 1/2” 23.5 32.2 50.0 55.0 35.1 40 A2F 1RA PVC13 0.200
50S M50 15.0 1 1/2” 26.1 2” 31.0 38.2 55.0 60.5 32.0 50S A2F 1RA PVC15 0.260
50 M50 15.0 2” 26.9 2 1/2” 35.6 44.0 60.0 66.0 36.3 50 A2F 1RA PVC18 0.270
A2F
63S M63 15.0 2” 26.9 2 1/2” 41.5 49.9 70.5 77.6 33.5 63S A2F 1RA PVC21 0.430
63 M63 15.0 2 1/2” 39.9 3” 47.2 55.9 75.0 82.5 35.8 63 A2F 1RA PVC23 0.400
75S M75 15.0 2 1/2” 39.9 3” 54.0 61.9 80.0 88.0 34.2 75S A2F 1RA PVC24 0.520
75 M75 15.0 3” 41.5 3 1/2” 61.1 67.9 84.0 92.4 40.6 75 A2F 1RA PVC26 0.500
90 M90 24.0 3 1/2” 42.8 4” 66.6 79.9 108.0 118.8 58.3 90 A2F 1RA PVC31 1.600
100 M100 24.0 4” 44.0 4” 76.0 91.0 123.0 135.3 55.2 100 A2F 1RA LSF33 1.780
115 M115 24.0 4” 44.0 5” 86.0 97.9 133.4 146.7 65.2 115 A2F 1RA LSF34 2.670
130 M130 24.0 5” 46.8 - 97.0 114.9 152.4 167.6 73.9 130 A2F 1RA LSF35 3.800
Dimensions are displayed in millimetres unless otherwise stated
CMP Products Limited on its sole responsibility declares that the equipment referred to herein conforms to the requirements of the ATEX Directive 2014/34/EU and the following
standards:-
FI413
IFS 18 5/17
0518
Notified Body: Sira Certification Service, Unit 6, Hawarden Industrial Park, Hawarden, CH5 3US, UK
Tel: +44 191 265 7411 • Fax: +44 1670 715 646
E-Mail: [email protected] • Web: www.cmp-products.com
CSA / cCSAus 2 1/17
www.cmp-products.com Logos shown for illustration purposes only. Please check certification for details
INSTALLATION INSTRUCTIONS FOR CMP CABLE GLAND TYPES A2F 4. Slacken the seal nut (3) to relax the seal (2).
CABLE GLAND COMPONENTS - It is not necessary to dismantled the cable gland any further than illustrated below
1. Entry Item 1 2 3
2. Seal
3. Seal Nut
5. Pass the cable through the gland to the desired position, then tighten the seal nut by hand until resistance is felt (when the seal
contacts the cable). Tighten with a spanner one further turn.
2. Fit the gland into the equipment and fully tighten the entry item (1).
3. Determine the conductor length required to suit the installation and prepare the cable accordingly, removing part of the outer sheath
where required to reveal the insulated conductors.
www.cmp-products.com www.cmp-products.com