The T0-3-8007/E is a voltmeter selector switch designed for flush mounting with a degree of protection IP65, featuring 6 contacts and a maintained switching function for both phase-phase and phase-N configurations. It has a rated uninterrupted current of 20 A and operates within an ambient temperature range of -25 to +50 °C. The switch complies with various international standards including IEC/EN 60947 and is suitable for branch circuits and motor disconnection.

Uploaded by

Ahmed Osman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
56 views5 pages

Eaton DS 095813 T0 3 8007 - E 20190625

The T0-3-8007/E is a voltmeter selector switch designed for flush mounting with a degree of protection IP65, featuring 6 contacts and a maintained switching function for both phase-phase and phase-N configurations. It has a rated uninterrupted current of 20 A and operates within an ambient temperature range of -25 to +50 °C. The switch complies with various international standards including IEC/EN 60947 and is suitable for branch circuits and motor disconnection.

Uploaded by

Ahmed Osman
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

DATASHEET - T0-3-8007/E

Voltmeter selector switches, Contacts: 6, 20 A, 3 x phase-phase, 3 x


phase-N, front plate: Phase/Phase-0-Phase/N, 45 °, maintained, flush
mounting

Part no. T0-3-8007/E


Catalog No. 095813

EL-Nummer 0001456302
(Norway)
Similar to illustration

Delivery program
Product range Control switches

Part group reference T0

Basic function Voltmeter selector switches

with black thumb grip and front plate

Contacts 6

Degree of Protection Front IP65

Design flush mounting

Contact sequence

switching function 3 x phase-phase


3 x phase-N

Switching angle ° 45

Switching performance maintained


With 0 (Off) position

Design number 8007

Front plate no.

front plate Phase/Phase-0-Phase/N

Motor rating AC-23A, 50 - 60 Hz


400 V P kW 5.5

Rated uninterrupted current Iu A 20

Note on rated uninterrupted current !u Rated uninterrupted current Iu is specified for max. cross-section.

Number of contact units contact 3


unit(s)

Technical data
General
Standards IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL
Switch-disconnector according to IEC/EN 60947-3

Climatic proofing Damp heat, constant, to IEC 60068-2-78


Damp heat, cyclic, to IEC 60068-2-30

Ambient temperature

06/25/2019 Eaton 095813 ED2019 V57.0 EN 1/5


Open °C -25 - +50

Enclosed °C -25 - +40

Overvoltage category/pollution degree III/3

Rated impulse withstand voltage Uimp V AC 6000

Mechanical shock resistance g 15

Mounting position As required


Contacts
Electrical characteristics

Rated operational voltage Ue V AC 690

Rated uninterrupted current Iu A 20

Note on rated uninterrupted current !u Rated uninterrupted current Iu is specified for max. cross-section.

Load rating with intermittent operation, class 12

AB 25 % DF x Ie 2

AB 40 % DF x Ie 1.6

AB 60 % DF x Ie 1.3

Short-circuit rating

Fuse A gG/gL 20

Rated short-time withstand current (1 s current) Icw Arms 320

Note on rated short-time withstand current lcw Current for a time of 1 second

Rated conditional short-circuit current Iq kA 6

Switching capacity
cos ϕ rated making capacity as per IEC 60947-3 A 130

Rated breaking capacity cos ϕ to IEC 60947-3 A

230 V A 100

400/415 V A 110

500 V A 80

690 V A 60

Safe isolation to EN 61140

between the contacts V AC 440

Current heat loss per contact at Ie W 0.6

Current heat loss per auxiliary circuit at Ie (AC-15/230 V) CO 0.6

Lifespan, mechanical Operations x 10


6 > 0.4

Maximum operating frequency Operations/h 1200

AC

AC-3

Rating, motor load switch P kW

220 V 230 V P kW 3

230 V Star-delta P kW 5.5

400 V 415 V P kW 5.5

400 V Star-delta P kW 7.5

500 V P kW 5.5

500 V Star-delta P kW 7.5

690 V P kW 4

690 V Star-delta P kW 5.5

Rated operational current motor load switch

230 V Ie A 11.5

230 V star-delta Ie A 20

400V 415 V Ie A 11.5

400 V star-delta Ie A 20

500 V Ie A 9

500 V star-delta Ie A 15.6

690 V Ie A 4.9

690 V star-delta Ie A 8.5

AC-21A

06/25/2019 Eaton 095813 ED2019 V57.0 EN 2/5


Rated operational current switch

440 V Ie A 20

AC-23A

Motor rating AC-23A, 50 - 60 Hz P kW

230 V P kW 3

400 V 415 V P kW 5.5

500 V P kW 7.5

690 V P kW 5.5

Rated operational current motor load switch

230 V Ie A 13.3

400 V 415 V Ie A 13.3

500 V Ie A 13.3

690 V Ie A 7.6

DC

DC-1, Load-break switches L/R = 1 ms

Rated operational current Ie A 10

Voltage per contact pair in series V 60

DC-21A Ie A

Rated operational current Ie A 1

Contacts Quantity 1

DC-23A, motor load switch L/R = 15 ms

24 V

Rated operational current Ie A 10

Contacts Quantity 1

48 V

Rated operational current Ie A 10

Contacts Quantity 2

60 V

Rated operational current Ie A 10

Contacts Quantity 3

120 V

Rated operational current Ie A 5

Contacts Quantity 3

240 V

Rated operational current Ie A 5

Contacts Quantity 5

DC-13, Control switches L/R = 50 ms

Rated operational current Ie A 10

Voltage per contact pair in series V 32

Control circuit reliability at 24 V DC, 10 mA Fault HF -5


< 10 , < 1 fault in 100000 operations
probability
Terminal capacities
Solid or stranded mm
2 1 x (1 - 2,5)
2 x (1 - 2,5)

Flexible with ferrules to DIN 46228 mm


2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)

Terminal screw M3.5

Tightening torque for terminal screw Nm 1


Technical safety parameters:
Notes B10d values as per EN ISO 13849-1, table C1

Rating data for approved types


Contacts

Rated operational voltage Ue V AC 600

Rated uninterrupted current max.

Main conducting paths

General use A 16

06/25/2019 Eaton 095813 ED2019 V57.0 EN 3/5


Auxiliary contacts

General Use IU A 10

Pilot Duty A 600


P 600

Switching capacity

Maximum motor rating

Single-phase

120 V AC HP 0.5

200 V AC HP 1

240 V AC HP 1.5

Three-phase

200 V AC HP 3

240 V AC HP 3

480 V AC HP 7.5

600 V AC HP 7.5

Short Circuit Current Rating SCCR

Basic Rating kA 5

max. Fuse A 50

High fault rating kA 10

max. Fuse A 20, Class J

Terminal capacity

Solid or flexible conductor with ferrule AWG 18 - 14

Terminal screw M3.5

Tightening torque lb-in 8.8

Design verification as per IEC/EN 61439


Technical data for design verification

Rated operational current for specified heat dissipation In A 20

Heat dissipation per pole, current-dependent Pvid W 0.6

Equipment heat dissipation, current-dependent Pvid W 0

Static heat dissipation, non-current-dependent Pvs W 0

Heat dissipation capacity Pdiss W 0

Operating ambient temperature min. °C -25

Operating ambient temperature max. °C 50

IEC/EN 61439 design verification

10.2 Strength of materials and parts

10.2.2 Corrosion resistance Meets the product standard's requirements.

10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.

10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.

10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects

10.2.4 Resistance to ultra-violet (UV) radiation UV resistance only in connection with protective shield.

10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.

10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.

10.2.7 Inscriptions Meets the product standard's requirements.

10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.

10.4 Clearances and creepage distances Meets the product standard's requirements.

10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.

10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.

10.7 Internal electrical circuits and connections Is the panel builder's responsibility.

10.8 Connections for external conductors Is the panel builder's responsibility.

10.9 Insulation properties

10.9.2 Power-frequency electric strength Is the panel builder's responsibility.

10.9.3 Impulse withstand voltage Is the panel builder's responsibility.

10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.

06/25/2019 Eaton 095813 ED2019 V57.0 EN 4/5


10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.

10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.

10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.

10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.

Technical data ETIM 7.0


Low-voltage industrial components (EG000017) / Voltmeter selector switch (EC000911)

Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Volt meter switch ([email protected]
[AKF068013])

Measurement between phases possible Yes

Measuring between phase and N-neutral possible Yes

With 0 (off) position Yes

Device construction Front installation

Modular version No

With control unit Yes

Degree of protection (IP) IP65

Degree of protection (NEMA) 12

Approvals
Product Standards UL 60947-4-1;CSA - C22.2 No. 60947-4-1-14; CSA-C22.2 No. 94; IEC/EN 60947-3; CE
marking

UL File No. E36332

UL Category Control No. NLRV

CSA File No. 12528

CSA Class No. 3211-05

North America Certification UL listed, CSA certified

Suitable for Branch circuits, suitable as motor disconnect

Degree of Protection IEC: IP65; UL/CSA Type 1, 12

Dimensions

② ZFS-... Label mount not included as standard

Assets (links)
Declaration of CE Conformity
00003075
Instruction Leaflets
IL03801020Z2018_05

06/25/2019 Eaton Industries GmbH 5/5


http://www.eaton.eu
© 06/2019 by Eaton Industries GmbH
Eaton 095813 ED2019 V57.0 EN