DATASHEET - T0-3-8007/E
Voltmeter selector switches, Contacts: 6, 20 A, 3 x phase-phase, 3 x
phase-N, front plate: Phase/Phase-0-Phase/N, 45 °, maintained, flush
mounting
Part no. T0-3-8007/E
Catalog No. 095813
EL-Nummer 0001456302
(Norway)
Similar to illustration
Delivery program
Product range Control switches
Part group reference T0
Basic function Voltmeter selector switches
with black thumb grip and front plate
Contacts 6
Degree of Protection Front IP65
Design flush mounting
Contact sequence
switching function 3 x phase-phase
3 x phase-N
Switching angle ° 45
Switching performance maintained
With 0 (Off) position
Design number 8007
Front plate no.
front plate Phase/Phase-0-Phase/N
Motor rating AC-23A, 50 - 60 Hz
400 V P kW 5.5
Rated uninterrupted current Iu A 20
Note on rated uninterrupted current !u Rated uninterrupted current Iu is specified for max. cross-section.
Number of contact units contact 3
unit(s)
Technical data
General
Standards IEC/EN 60947, VDE 0660, IEC/EN 60204, CSA, UL
Switch-disconnector according to IEC/EN 60947-3
Climatic proofing Damp heat, constant, to IEC 60068-2-78
Damp heat, cyclic, to IEC 60068-2-30
Ambient temperature
06/25/2019 Eaton 095813 ED2019 V57.0 EN 1/5
Open °C -25 - +50
Enclosed °C -25 - +40
Overvoltage category/pollution degree III/3
Rated impulse withstand voltage Uimp V AC 6000
Mechanical shock resistance g 15
Mounting position As required
Contacts
Electrical characteristics
Rated operational voltage Ue V AC 690
Rated uninterrupted current Iu A 20
Note on rated uninterrupted current !u Rated uninterrupted current Iu is specified for max. cross-section.
Load rating with intermittent operation, class 12
AB 25 % DF x Ie 2
AB 40 % DF x Ie 1.6
AB 60 % DF x Ie 1.3
Short-circuit rating
Fuse A gG/gL 20
Rated short-time withstand current (1 s current) Icw Arms 320
Note on rated short-time withstand current lcw Current for a time of 1 second
Rated conditional short-circuit current Iq kA 6
Switching capacity
cos ϕ rated making capacity as per IEC 60947-3 A 130
Rated breaking capacity cos ϕ to IEC 60947-3 A
230 V A 100
400/415 V A 110
500 V A 80
690 V A 60
Safe isolation to EN 61140
between the contacts V AC 440
Current heat loss per contact at Ie W 0.6
Current heat loss per auxiliary circuit at Ie (AC-15/230 V) CO 0.6
Lifespan, mechanical Operations x 10
6 > 0.4
Maximum operating frequency Operations/h 1200
AC
AC-3
Rating, motor load switch P kW
220 V 230 V P kW 3
230 V Star-delta P kW 5.5
400 V 415 V P kW 5.5
400 V Star-delta P kW 7.5
500 V P kW 5.5
500 V Star-delta P kW 7.5
690 V P kW 4
690 V Star-delta P kW 5.5
Rated operational current motor load switch
230 V Ie A 11.5
230 V star-delta Ie A 20
400V 415 V Ie A 11.5
400 V star-delta Ie A 20
500 V Ie A 9
500 V star-delta Ie A 15.6
690 V Ie A 4.9
690 V star-delta Ie A 8.5
AC-21A
06/25/2019 Eaton 095813 ED2019 V57.0 EN 2/5
Rated operational current switch
440 V Ie A 20
AC-23A
Motor rating AC-23A, 50 - 60 Hz P kW
230 V P kW 3
400 V 415 V P kW 5.5
500 V P kW 7.5
690 V P kW 5.5
Rated operational current motor load switch
230 V Ie A 13.3
400 V 415 V Ie A 13.3
500 V Ie A 13.3
690 V Ie A 7.6
DC
DC-1, Load-break switches L/R = 1 ms
Rated operational current Ie A 10
Voltage per contact pair in series V 60
DC-21A Ie A
Rated operational current Ie A 1
Contacts Quantity 1
DC-23A, motor load switch L/R = 15 ms
24 V
Rated operational current Ie A 10
Contacts Quantity 1
48 V
Rated operational current Ie A 10
Contacts Quantity 2
60 V
Rated operational current Ie A 10
Contacts Quantity 3
120 V
Rated operational current Ie A 5
Contacts Quantity 3
240 V
Rated operational current Ie A 5
Contacts Quantity 5
DC-13, Control switches L/R = 50 ms
Rated operational current Ie A 10
Voltage per contact pair in series V 32
Control circuit reliability at 24 V DC, 10 mA Fault HF -5
< 10 , < 1 fault in 100000 operations
probability
Terminal capacities
Solid or stranded mm
2 1 x (1 - 2,5)
2 x (1 - 2,5)
Flexible with ferrules to DIN 46228 mm
2 1 x (0.75 - 2.5)
2 x (0.75 - 2.5)
Terminal screw M3.5
Tightening torque for terminal screw Nm 1
Technical safety parameters:
Notes B10d values as per EN ISO 13849-1, table C1
Rating data for approved types
Contacts
Rated operational voltage Ue V AC 600
Rated uninterrupted current max.
Main conducting paths
General use A 16
06/25/2019 Eaton 095813 ED2019 V57.0 EN 3/5
Auxiliary contacts
General Use IU A 10
Pilot Duty A 600
P 600
Switching capacity
Maximum motor rating
Single-phase
120 V AC HP 0.5
200 V AC HP 1
240 V AC HP 1.5
Three-phase
200 V AC HP 3
240 V AC HP 3
480 V AC HP 7.5
600 V AC HP 7.5
Short Circuit Current Rating SCCR
Basic Rating kA 5
max. Fuse A 50
High fault rating kA 10
max. Fuse A 20, Class J
Terminal capacity
Solid or flexible conductor with ferrule AWG 18 - 14
Terminal screw M3.5
Tightening torque lb-in 8.8
Design verification as per IEC/EN 61439
Technical data for design verification
Rated operational current for specified heat dissipation In A 20
Heat dissipation per pole, current-dependent Pvid W 0.6
Equipment heat dissipation, current-dependent Pvid W 0
Static heat dissipation, non-current-dependent Pvs W 0
Heat dissipation capacity Pdiss W 0
Operating ambient temperature min. °C -25
Operating ambient temperature max. °C 50
IEC/EN 61439 design verification
10.2 Strength of materials and parts
10.2.2 Corrosion resistance Meets the product standard's requirements.
10.2.3.1 Verification of thermal stability of enclosures Meets the product standard's requirements.
10.2.3.2 Verification of resistance of insulating materials to normal heat Meets the product standard's requirements.
10.2.3.3 Verification of resistance of insulating materials to abnormal heat Meets the product standard's requirements.
and fire due to internal electric effects
10.2.4 Resistance to ultra-violet (UV) radiation UV resistance only in connection with protective shield.
10.2.5 Lifting Does not apply, since the entire switchgear needs to be evaluated.
10.2.6 Mechanical impact Does not apply, since the entire switchgear needs to be evaluated.
10.2.7 Inscriptions Meets the product standard's requirements.
10.3 Degree of protection of ASSEMBLIES Does not apply, since the entire switchgear needs to be evaluated.
10.4 Clearances and creepage distances Meets the product standard's requirements.
10.5 Protection against electric shock Does not apply, since the entire switchgear needs to be evaluated.
10.6 Incorporation of switching devices and components Does not apply, since the entire switchgear needs to be evaluated.
10.7 Internal electrical circuits and connections Is the panel builder's responsibility.
10.8 Connections for external conductors Is the panel builder's responsibility.
10.9 Insulation properties
10.9.2 Power-frequency electric strength Is the panel builder's responsibility.
10.9.3 Impulse withstand voltage Is the panel builder's responsibility.
10.9.4 Testing of enclosures made of insulating material Is the panel builder's responsibility.
06/25/2019 Eaton 095813 ED2019 V57.0 EN 4/5
10.10 Temperature rise The panel builder is responsible for the temperature rise calculation. Eaton will
provide heat dissipation data for the devices.
10.11 Short-circuit rating Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.12 Electromagnetic compatibility Is the panel builder's responsibility. The specifications for the switchgear must be
observed.
10.13 Mechanical function The device meets the requirements, provided the information in the instruction
leaflet (IL) is observed.
Technical data ETIM 7.0
Low-voltage industrial components (EG000017) / Voltmeter selector switch (EC000911)
Electric engineering, automation, process control engineering / Low-voltage switch technology / Off-load switch, circuit breaker, control switch / Volt meter switch ([email protected]
[AKF068013])
Measurement between phases possible Yes
Measuring between phase and N-neutral possible Yes
With 0 (off) position Yes
Device construction Front installation
Modular version No
With control unit Yes
Degree of protection (IP) IP65
Degree of protection (NEMA) 12
Approvals
Product Standards UL 60947-4-1;CSA - C22.2 No. 60947-4-1-14; CSA-C22.2 No. 94; IEC/EN 60947-3; CE
marking
UL File No. E36332
UL Category Control No. NLRV
CSA File No. 12528
CSA Class No. 3211-05
North America Certification UL listed, CSA certified
Suitable for Branch circuits, suitable as motor disconnect
Degree of Protection IEC: IP65; UL/CSA Type 1, 12
Dimensions
② ZFS-... Label mount not included as standard
Assets (links)
Declaration of CE Conformity
00003075
Instruction Leaflets
IL03801020Z2018_05
06/25/2019 Eaton Industries GmbH 5/5
http://www.eaton.eu
© 06/2019 by Eaton Industries GmbH
Eaton 095813 ED2019 V57.0 EN