* 79 : OPTIONAL, CAN BE CONFIGURED AS PER FEEDER TYPE.
( IF OVERHEAD LINE FEEDER TYPE).
PROTECTION ENGINEERING DEPARTMENT
13.8kV OUTGOING FEEDER-19 (H27)
(132/13.8kV SUBSTATION)
ALFANAR ELECTRICAL SYSTEM
OPTIMIZED SCHEME DIAGRAM
OPDS-ALFANAR-251-REF620-OG
PROTECTION CODE PROTECTION RELAY TYPE ORDERING CODE
50/50N,51/51N,50BF ABB NBFNAAAANEA1BNN11G
79*,94,74TCS
alfanar
X9A
X5
B SECTION D-D A
D D
GND
X3 TH HYG B7 B8
X4
X1D
X1A
XCBF
X2 B9 B10 X6 B1 B2 B3 B4 B5 B6
X1B
X9
REXT1 REXT2 XHR XRL
X8 74CO KM
X9A
X1C
SECTION A-A SECTION A-A
C C
B A
X9B X7
LED LAMP
SECTION C-C
Toll Free : 800 124 1333
alfanar www.alfanar.com
Manufacturer's Name Alfanar Electrical Systems Rated Voltage (Ur) 17.5 kV.
Country Of Origin K.S.A System Voltage (Un) 13.8 kV.
OPEN
Rated Frequency (f r) 60 Hz.
CLOSE
Type Designation ALFA-12
Rated Power Frequency Withstand 38 kV.
Reference Of SEC Specification 32-TMSS-01 Rev.03 Voltage (Ud)
Rated Lightning Impulse Withstand 95 kV.
Manufacturer's Serial No. ALFA-12/0091/02.2023/0239 Voltage (Up)
Instruction Book Reference XXXXXX Rated Normal Current (Ir) 1250 A.
alfanar
Rated Short-time WithstandCurrent (Ik) 25 kA.
Alfanar Electrical Systems
Year Of Manufacture 2024 (for main and earthing circuits)
Applicable Standard IEC 62271-200 Rated Duration Of Short Circuit (tk) 3 sec.
(for main and earthing circuits)
Alfanar Sales Order No. 1020406 Rated Peak Withstand Current (Ip) 65 kA.
(for main and earthing circuits)
OPEN
SEC. Contract No. 4400018641 IAC : AFLR. 25 kA/1s.
CLOSE
Auxiliary Voltage (AC/DC) 230V/125V
OPEN
CLOSE
70.00
145.00
45.00
45.00
CABLE TERMINATION LUG
PLAIN OUTGOING FEEDER
VCB OFF
VCB ON
EARTH SWITCH ON
VCB IN SERVICE
VCB IN TEST
LED INDICATING LAMPS
27DC
27DC
TS1
13.8kV VCB CLOSED
13.8kV CB CLOSE BLOCK
13.8kV CB TRIP COIL-1
13.8kV CB TRIP COIL-2
SAS/REMOTE INDICATION
COMMON BCU
INITIATE CBF
TRIP COIL SAVE (TC1 & TC2)
INITIATE 86BB (13.8kV BB BUS RISER PANEL)
BCPU SOFT CLOSE BLOCK
CT RATIO SELECTION AT SECONDARY
1250/1A (2S4-2S1) 800/1A (2S3-2S1) 400/1A (2S2-2S1)
CT REF
SLIDE LINK SELECTION SLIDE LINK SELECTION SLIDE LINK SELECTION
CT1R CLOSE LINK (RIGHT): CLOSE LINK (RIGHT): CLOSE LINK (RIGHT):
X1A-2,5,7,10,12,15,16,17 X1A-3,5,8,10,13,15,16,17 X1A-4,5,9,10,14,15,16,17
CT1Y
CT1B OPEN LINK (LEFT): OPEN LINK (LEFT): OPEN LINK (LEFT):
X1A-1,3,4,6,8,9,11,13,14 X1A-1,2,4,6,7,9,11,12,14 X1A-1,2,3,6,7,8,11,12,13
CT SHORTING CLOSE LINK (RIGHT): X1A-1,5,6,10,11,15,17
CT ISOLATION
NOTE: OPEN LINK (LEFT): X1A-2,7,12,16
SHORT BEFORE ISOLATE
50CBF, BCPU & 74TCS METERING A,V & MW
REF620-NBFNAAAANEA1BNN11G
50/51,50N/51N,94,79***
CT RATIO SELECTION AT SECONDARY
1250/1A (1S4-1S1) 800/1A (1S3-1S1) 400/1A (1S2-1S1)
CT REF
SLIDE LINK SELECTION SLIDE LINK SELECTION SLIDE LINK SELECTION
CT1R CLOSE LINK (RIGHT): CLOSE LINK (RIGHT): CLOSE LINK (RIGHT):
X1B-2,5,7,10,12,15,16 X1B-3,5,8,10,13,15,16 X1B-4,5,9,10,14,15,16
CT1Y OPEN LINK (LEFT): OPEN LINK (LEFT): OPEN LINK (LEFT):
CT1B X1B-1,3,4,6,8,9,11,13,14,17 X1B-1,2,4,6,7,9,11,12,14,17 X1B-1,2,3,6,7,8,11,12,13,17
CT SHORTING CLOSE LINK (RIGHT): X1B-1,5,6,10,11,15,17
CT ISOLATION
NOTE: OPEN LINK (LEFT): X1B-2,7,12,16
SHORT BEFORE ISOLATE
CT RATIO SELECTION AT SECONDARY
3600/1A (S1-S2)
CT REF
TER. NO. SLIDE LINK SELECTION
CT2R CLOSE LINK (RIGHT):
CT2Y S1-S2 X1C-1,2,4,5,7,8,10,11
CT2B OPEN LINK(LEFT)
X1C-3,6,9
CT SHORTING CLOSE LINK (UP): X1C-1,3,4,6,7,9,11
CT ISOLATION
NOTE: OPEN LINK (DOWN): X1C-2,5,8,10
SHORT BEFORE ISOLATE
METERING A,V & MW
REF620-NBFNAAAANEA1BNN11G
ILK 94UV-A1
ILK 94UV-A2
ILK 94UV-A3
ILK 94UF-IA1
ILK 94UF-IA2
·
··
···
Circuit Breaker (CB) Racking Operating Instruction
AUXILIARY POWER SUPPLY SHOULD BE CONNECTED
BEFORE INSERT RACK IN HANDLE.
A. Racking-IN to Service Position:
1. Ensure that ON/OFF indicator of the Circuit Breaker (CB) is at 'OFF' status.
2. Connect the wiring plug with the main body of Circuit Breaker and close the
Circuit Breaker (CB) compartment door.
3. Confirm Earth Switch (ES) is 'OFF' position.
4. Ensure Earthing Switch operation access cover is closed.
5. Ensure VCB Rack-in access selector switch is at " ON " position.
6. Ensure VCB Test indication lamp is ON.
7. Open the Circuit Breaker (CB) Insertion/Withdrawal Screw cover.
8. Insert the operating handle into Insertion/Withdrawal Screw.
9. Rotate the operating handle clockwise direction.
10. Circuit Breaker (CB) is in Service Position when it sounds successive crash
sound cause by a result of run-idling of this screw.
11. Check that the arrow of position indicator points out "SERVICE" /
and service indication " ON ".
12. Remove operating handle and close the Insertion/Withdrawal Screw cover.
B. Racking-OUT to Test Position:
1. Ensure that ON/OFF indicator of the Circuit Breaker (CB) is at 'OFF' status.
2. Ensure VCB Rack-in access selector switch is at " ON " position.
3. Open the Circuit Breaker (CB) Insertion/Withdrawal Screw cover.
4. Insert the operating handle into Insertion/Withdrawal Screw.
5. Turn it counter-clockwise to rack Circuit Breaker (CB) out.
6. Circuit Breaker (CB) is in Test Position when it sounds successive
crash sound cause by a result of run-idling of this screw.
7. Check that the arrow of position indicator points out "TEST" /
and test indication " ON ".
8. Remove operating handle and close the Insertion/Withdrawal Screw cover.
Earth Switch (ES) Operating Instruction (Cable Earthing)
A. Closing the Earth Switch (ES):
1. Ensure rear cover closed and bolted.
2. Confirm Circuit Breaker is in Test Position.
3. Confirm cables are not energize by checking 'CVI'.
4. Earth switch handle access knob rotate to " OPEN " position.
5. Engage the ES operating handle; rotate it to the left until handle rotation
stop to close the Earth Switch (ES).
6. Check Earth switch (ES) indication shows .
7. Remove the handle and close the access shutter.
B. Opening the Earth Switch (ES):
1. Open the shutter.
2. Engage the ES operating handle and turn it to the right until handle rotation
Stop to open the Earth Switch (ES).
3. Check Earth switch (ES) indication shows .
4. Rotate Earth Switch (ES) knob to close the access for ES operating shaft.
EARTHING EARTHING
OPEN SWITCH OPEN SWITCH
CLOSE CLOSE
Control circuit diagram - VL type
VL-06/12/17/20/25/36
Trip coil monitoring contact
Secondary trip coil with TCM Contact
Note3) Note4)
Current Trip Coil(1A,5A) indicating contact
Closing Spring Contact (Charge completion indicating contact)
<Connecting terminal arrangement>
—: External terminal of VCB : : Anti-Pumping Device
52 : Vacuum circuit breaker Anti-Pumping Device is installed inside as standard IEC62271-100 3.6.128
M : Spring charging motor Q type connector
LS4, LS5 : Position S/W (TEST position)
TC : Trip coil(SHT)
LS6, LS7 : Position S/W (SERVICE position)
TC1 : Secondary Trip coil(SHT1) 24 23 22 A6 A5 A4 A3 A2 A1
42 41 40 29 28 27 26 25
C : Closing coil(CC) TEST : 2a TEST : 1a1b 49 48 47 46 45 44 43
TEST:a1b 51 50 39 38 37 36 61 60
UVT : Under Voltage Trip S/W 58 57 56 55 54 53 52
SERVICE:2b SERVICE:2a SERVICE:1a1b 1 75 74 73 72 71 70 59
No. 10 9 8 7 6 5 4 12 3 11 2
52a : Auxiliary switch (NO) 34 16 15 14 13 D2 D1
A3 A4 A5
52b : Auxiliary switch (NC)
LS4 Close at TEST positionClose at TEST position Close at TEST position
LS2 : Motor stop limit switch
CTC : Current Trip coil(3A) LS5 OPEN at TEST position Close at TEST position OPEN at TEST position (10a10b)
CTC1 : Secondary Current Trip coil(3A) LS6 OPEN at SERVICE position Close at SERVICE position Close at SERVICE position
CTC2 : Current Trip coil(1A,5A) LS7 OPEN at SERVICE position Close at SERVICE position OPEN at SERVICE position
CTC3 : Current Trip coil(1A,5A) LM : Locking magnet(only withdrawable type)
LET : Low Energy Trip Device(25m+,100m+)
CS : Closing spring charged indication limit switch