LV PANEL-28A02 Rev-01 Updated 16.07.2023
LV PANEL-28A02 Rev-01 Updated 16.07.2023
LT PANEL-28A02 FED FROM :TRANS-28A02 INCOMING BREAKER SIZE : 2500 ATP ACB 50KA
REF :
LOC: FAC.-28A /LV ROOM LT PANEL SIZE : 10 WAYS INCOMING CABLE SIZE : 11x1C,630mm2 CU XLPE/AWA/PVC
1RYB 630 FUTURE LOAD FOR FP-2806 411.16 142.40 131.60 137.60 209.37 90 188.43
2RYB 400 4C, 300mm2 CU XLPE/SWA/PVC FP-28A07 226.96 82.04 69.64 75.29 142.40 90 128.16
3RYB 400 4C,300mm2 CU XLPE/SWA/PVC MDB-13A01 298.98 96.21 99.26 103.51 193.12 90 173.81
4RYB 630 FUTURE LOAD 500.00 166.67 166.67 166.67 250.00 90 225.00
5RYB 630 FUTURE LOAD 500.00 166.67 166.67 166.67 250.00 90 225.00
6RYB 630 FUTURE LOAD 500.00 166.67 166.67 166.67 250.00 90 225.00
1RYB 125 FUTURE LOAD FOR SMDB-14A01 41.50 17.47 13.37 14.67 24.68 90 22.21
2RYB 125 FUTURE LOAD FOR SMDB-15A01 41.50 17.47 13.37 14.67 24.68 90 22.21
3RYB 250 4C, 120mm2 CU XLPE/SWA/PVC ATS-16A01 134.34 47.10 41.30 45.95 107.76 90 96.99
4R 40 SPARE
4Y 25 3C, 10mm2 CU XLPE/SWA/PVC CU-27B01 1.60 1.60 1.10 90 0.99
4B 40 SPARE
4C,16mm2 CU XLPE/SWA/PVC+1C,16mm2
3RYB 63 TPN ISOLATOR FOR CCU-G1 (DUTY) 23.70 7.90 7.90 7.90 23.70 90 21.3
CU.PVC
4C,16mm2 CU XLPE/SWA/PVC+1C,16mm2
4RYB 63 TPN ISOLATOR FOR CCU-G1 ( STAND BY)
CU.PVC
4C,10mm2 CU XLPE/SWA/PVC+1C,10mm2
5RYB 40 TPN ISOLATOR FOR CCU-G2 (DUTY) 16.70 5.57 5.57 5.57 16.70 90 15.0
CU.PVC
4C,16mm2 CU XLPE/SWA/PVC+1C,16mm2
6RYB 63 TPN ISOLATOR FOR CCU-G3 (DUTY) 16.70 5.57 5.57 5.57 16.70 90 15.0
CU.PVC
Page 1 of 2
INCOMING BREAKER
SMDB REF : SMDB-16A01 FED FROM : ATS -16A01 / FP-28A07 250 A MCCB 35KA
SIZE :
LOC. : FAC.-16A/ G F / ELEC.RM SMDB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 120mm2 CU XLPE/SWA/PVC
9Y 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CCU-G2 (DUTY) 4.00 4.00 4.00 90 3.60
9B 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CCU-G3 (DUTY) 4.00 4.00 4.00 90 3.60
11B 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G2 (DUTY) 4.00 4.00 4.00 90 3.60
12R 20 3C,6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G2 ( DUTY) 4.00 4.00 4.00 90 3.60
13Y 20 SPARE
14RYB 63 SPARE
Page 2 of 2
DB REF : DB-16A01 FED FROM : SMDB -16A01 INCOMING BREAKER SIZE : 63 A MCCB 35kA
LOC: FAC-16A/ G F / ELEC.RM DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 16mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC
SECTION/RCD
2R 10 2 x 2.5 2.5 LIGHTS IN ELEC ROOM, & KITCHEN + 2 EM LIGHTS 0.05 5 0.25 75 0.19
2Y 10 2 x 2.5 2.5 LIGHTS IN LOBBY & CORRIDOR + 4 EM LIGHTS 0.05 9 0.45 75 0.34
3R 10 2 x 2.5 2.5 LIGHTS IN SHERYAN & MDF ROOM + 3 EM LIGHTS 0.05 9 0.45 75 0.34
40A,(100mA) RCD 4P
3B 10 SPARE
13A FUSED SWITCHED SPUR OUTLET SOCKET WITH
4R 20 2x4 4.0 0.30 1 0.30 90 0.27
INDICATOR LAMP FOR VAV-1
13A FUSED SWITCHED SPUR OUTLET SOCKET WITH
4Y 20 2x4 4.0 0.30 1 0.30 90 0.27
INDICATOR LAMP FOR VAV-3
13A FUSED SWITCHED SPUR OUTLET SOCKET WITH
4B 20 2x4 4.0 0.30 1 0.30 90 0.27
INDICATOR LAMPFOR VAV-2
5R 10 SPARE
3C, 6mm2 CU
5Y 20 SPN ISOLATOR FOR REF1 0.25 1 0.25 90 0.22
XLPE/SWA/PVC
13A FUSED SWITCHED SPUR OUTLET SOCKET WITH
5B 20 2x4 4.0 0.25 1 0.25 90 0.22
INDICATOR LAMPFOR CAV-1
6R 20 SPARE
3C, 6mm2 CU
6Y 20 SPN ISOLATOR FOR REF2 0.50 1 0.50 90 0.45
XLPE/SWA/PVC
6B 20 SPARE
Page 1 of 2
DB REF : DB-16A01 FED FROM : SMDB -16A01 INCOMING BREAKER SIZE : 63 A MCCB 35kA
LOC: FAC-16A/ G F / ELEC.RM DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 16mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC
SECTION/RCD
9R 32 2x4 4.0 13A S.SOCKETS IN STORE, KITCHEN & WATER FILTER 0.20 7 1.40 50 0.70
2 x 4.0 FIRE 4.0 FIRE
40A,(30mA) RCD 4P
9Y 20 13A UNSWITCH SPUR OUTLET SOCKETS FOR FACP 0.30 1 0.30 75 0.23
RATED RATED
20A DOUBLE POLE SWITCH WITH FLEX OUTLET FOR
9B 20 2x4 4.0 1.20 1 1.20 50 0.60
WATER HEATER IN TOILET
10R 20 2x4 4.0 ELECTRICAL ROOM SOCKET 0.20 1 0.20 50 0.10
10Y 20 2x4 4.0 SWITCHED SPUR OUTLET FOR HAND DRIER 0.50 1 0.50 50 0.25
10B 32 SPARE
11R 32 SPARE
11Y 32 SPARE
11B 32 SPARE
12R 32 SPARE
12Y 32 SPARE
12B 32 SPARE
Page 2 of 2
DB REF : DB-16A01/UPS FED FROM :SMDB -16A01 INCOMING BREAKER SIZE : 125 A MCCB 35kA
LOC: FAC-16A/ GF / ELEC.RM DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2 CU.PVC
1R 20 2x4 4.0 13A TWIN SOCKETS IN SHERYAN ROOM 0.40 2 0.80 75 0.60
16A SINGLE PHASE INDUSTRIAL SOCKET IN SHERIYAN
1Y 32 2x6 6.0 1.20 1 1.20 75 0.90
ROOM
16A SINGLE PHASE INDUSTRIAL SOCKET IN SHERIYAN
1B 32 2x6 6.0 1.20 1 1.20 75 0.90
ROOM
16A SINGLE PHASE INDUSTRIAL SOCKET IN SHERIYAN
2R 32 2x6 6.0 1.20 1 1.20 75 0.90
ROOM
2Y 20 2x4 4.0 13A UNSWITCHED SPUR OUTLETS FOR MSFD 0.10 4 0.40 75 0.30
2B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
16A SINGLE PHASE INDUSTRIAL SOCKET IN SHERIYAN
3R 32 2x6 6.0 1.20 1 1.20 75 0.90
ROOM
3Y 20 2x4 4.0 13A TWIN SOCKETS IN MDF ROOM 0.40 2 0.80 75 0.60
3B 20 2x4 4.0 13A TWIN SOCKETS IN MDF ROOM 0.40 2 0.80 75 0.60
4R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN MDF ROOM 1.20 1 1.20 75 0.90
4Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN MDF ROOM 1.20 1 1.20 75 0.90
4B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN MDF ROOM 1.20 1 1.20 75 0.90
5R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90
5Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
5B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
6R 20 2x4 4.0 13A TWIN SOCKETS IN SHERYAN ROOM 0.40 1 0.40 75 0.30
6Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
6B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
7R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90
7Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
(30mA) RCD 4P
7B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
Page 1 of 2
DB REF : DB-16A01/UPS FED FROM :SMDB -16A01 INCOMING BREAKER SIZE : 125 A MCCB 35kA
LOC: FAC-16A/ GF / ELEC.RM DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2 CU.PVC
8R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN MDF ROOM 1.20 1 1.20 75 0.90
8Y 20 2x4 4.0 13A TWIN SOCKETS IN MDF ROOM 0.40 2 0.80 75 0.60
10R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN SMDF ROOM 1.20 1 1.20 75 0.90
10Y 20 2x4 4.0 13A TWIN SOCKETS IN PABX ROOM 0.40 2 0.80 75 0.60
10B 20 2x4 4.0 13A TWIN SOCKETS IN PABX ROOM 0.40 2 0.80 75 0.60
11R 20 2x4 4.0 13A TWIN SOCKETS IN PABX ROOM 0.40 2 0.80 75 0.60
11Y 20 2x4 4.0 13A TWIN SOCKETS IN SMDF ROOM 0.40 2 0.80 75 0.60
11B 20 2x4 4.0 13A TWIN SOCKETS IN SMDF ROOM 0.40 2 0.80 75 0.60
12R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90
12Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90
12B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90
13R 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90
13Y 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90
13B 32 2x6 6.0 16A SINGLE PHASE INDUSTRIAL SOCKET IN PBX ROOM 1.20 1 1.20 75 0.90
14R
14Y 63 SPARE
14B
Page 2 of 2
INCOMING BREAKER
CU REF : CU-27B01 FED FROM : FP-28A07 25 A SPN ISO. + RCD
SIZE :
LOC: FAC.-X1 / OT CU SIZE : 6 WAYS INCOMING CABLE SIZE : 3C, 10mm2 CU XLPE/SWA/PVC
SECTION/RC
CIRCUIT BREAKER
BUSBAR
MCB (KW)
CIRCUIT NO RATING (A) N) (mm2) (E) POINTS FACTOR (%) (KW)
10KA
1C 10 2 x 2.5 2.5 LIGHTS IN OT 0.05 3 0.15 75 0.11
32A,(30mA) RCD 4P
4C 20 SPARE
5C 10 SPARE
6C 32 SPARE
NOTES:-
CU-27A01 WILL BE FED FROM DB-30A01 & INCOMER CABLE WILL BE 3C, 10mm2 CU XLPE/SWA/PVC
CU-27B01 WILL BE FED FROM FP-28A07 & INCOMER CABLE WILL BE 3C, 10mm2 CU XLPE/SWA/PVC
CU-27C01 WILL BE FED FROM DB-02F01 & INCOMER CABLE WILL BE 3C, 16mm2 CU XLPE/SWA/PVC
CU-27D01 WILL BE FED FROM DB-07A01. & INCOMER CABLE WILL BE 3C, 35mm2 CU XLPE/SWA/PVC
CU-27E01 WILL BE FED FROM SMDB-08A201 & INCOMER CABLE WILL BE 3C, 25mm2 CU XLPE/SWA/PVC
Page 1 of 1
MDB REF : MDB-13A01 FED FROM : LT PANEL-28A02 INCOMING BREAKER SIZE : 400 A MCCB MAIN
LOCATION: GROUND FLOOR ELEC.ROOM-02 MDB SIZE : 6 WAYS INCOMING CABLE SIZE : 4C,300mm2 CU XLPE/SWA/PVC
5RYB 80 SPARE
6RYB 63 SPARE
LOCATION: FIRST FLOOR ELEC.ROOM-03 SMDB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 95mm2 CU XLPE/SWA/PVC+ 1C, 50mm2 CU.PVC
1RYB 40 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC DB-13A11 12.35 3.95 4.20 4.20 9.34 90 8.40
2RYB 100 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC DB-13A12 50.50 16.90 16.30 17.30 32.80 90 29.52
3RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC ISOLATOR FOR AHU-G1 ON ROOF 7.50 2.50 2.50 2.50 6.75 90 6.08
4RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC ISOLATOR FOR AHU-G2 ON ROOF 7.50 2.50 2.50 2.50 6.75 90 6.08
5RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC ISOLATOR FOR AHU-F1 ON ROOF 7.50 2.50 2.50 2.50 6.75 90 6.08
6RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC ISOLATOR FOR AHU-F2 ON ROOF 7.50 2.50 2.50 2.50 6.75 90 6.08
7R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-2 AT ROOF 0.656 0.66 0.66 90 0.59
7Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-1 AT ROOF 0.042 0.04 0.04 90 0.04
7B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-1 AT ROOF 0.042 0.04 0.04 90 0.04
8R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-1 AT ROOF 0.042 0.04 0.04 90 0.04
8Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR REF-2 AT ROOF 0.656 0.66 0.66 90 0.59
8B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR BOOSTER PUMP AT ROOF 1.000 1.00 1.00 90 0.90
9RYB 40 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC DB-13A13 16.00 5.50 5.50 5.00 14.40 90 12.96
10R 20 SPARE
10Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 (STAND BY) AT ROOF FOR GF TEL RM 4.00 4.00 4.00 90 3.60
10B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-G1 (STAND BY) AT ROOF FOR GF SEC RM 4.00 4.00 4.00 90 3.60
11RYB 63 SPARE
12RYB 40 SPARE
LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 11 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D
6Y 10
6B 10
7R 10 SPARE
7Y 10 SPARE
7B 10 SPARE
Page 1 of 2
DB REF : DB-13A11 FED FROM :SMDB -13A11 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + 2 RCD
LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 11 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D
8R 10 SPARE
8Y 10 SPARE
8B 10 SPARE
LIGHTS IN KITCHEN 01 & JAN 01 + 2 EM
9R 10 2 x 2.5 2.5 0.05 5 0.25 75 0.19
LIGHT
9Y 10 2 x 2.5 2.5 LIGHTS IN LADIES TOILET-01 + 1 EM LIGHT 0.05 4 0.20 75 0.15
LIGHTS IN KITCHEN 02 & JAN 02 + 2 EM
9B 10 2 x 2.5 2.5 0.05 5 0.25 75 0.19
LIGHT
10R 10 2 x 2.5 2.5 LIGHTS IN OFFICER TOILET-01 + 2 EM LIGHT 0.05 7 0.35 75 0.26
10Y 10 2 x 2.5 2.5 LIGHTS IN LADIES TOILET-02 + 1 EM LIGHT 0.05 4 0.20 75 0.15
10B 10 2 x 2.5 2.5 LIGHTS IN ORS TOILET-01 + 2 EM LIGHT 0.05 7 0.35 75 0.26
11R 10 2 x 2.5 2.5 LIGHTS IN OFFICER TOILET-02 + 2 EM LIGHT 0.05 7 0.35 90 0.32
40A, TPN (30mA RCD
11Y 10 2 x 2.5 2.5 LIGHTS IN DRESS 01& BATH 02 0.05 3 0.15 75 0.11
11B 10 2 x 2.5 2.5 LIGHTS IN ORS TOILET-02 + 2 EM LIGHT 0.05 7 0.35 75 0.26
12R 10 2 x 2.5 2.5 LIGHTS IN DRESS 02& BATH 03 0.05 3 0.15 90 0.14
12Y 10 SPARE
13R 20 SPARE
13Y 20 SPARE
13B 20 SPARE
14R 10 SPARE
14Y 10 SPARE
14B 10 SPARE
Page 2 of 2
DB REF : DB-13A12 FED FROM :SMDB -13A11 INCOMING BREAKER SIZE : 100 A TPN ISOLATOR + RCD
LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC
4B 32 2x4 4.0 13A S.SOCKETS IN OFFICE 05 & 04 & 02 0.20 17 3.40 50 1.70
7R 32 2x4 4.0 13A S.SOCKETS IN KITCHEN 01 & JAN 01 0.20 7 1.40 50 0.70
20A DOUBLE POLE SWITCH FOR W/H IN
7Y 20 2 x4 4.0 1.50 1 1.50 50 0.75
ORS TOILET-01
20A DOUBLE POLE SWITCH FOR W/H IN
7B 20 2x4 4.0 1.50 1 1.50 50 0.75
KITCHEN-02
20A DOUBLE POLE SWITCH FOR W/H IN
8R 20 2x4 4.0 1.50 1 1.50 50 0.75
OFFICER TOILET-02
8Y 32 2x4 4.0 13A S.SOCKETS IN OFFICE 10 0.20 7 1.40 75 1.05
8B 20 SPARE
20A DOUBLE POLE SWITCH FOR W/H IN
9R 20 2x4 4.0 1.50 1 1.50 50 0.75
KITCHEN 01
9Y 20 SPARE
HAND DRIER @ LADIES TOILET & ORS
9B 20 2x4 4.0 0.50 2 1.00 50 0.50
TOILET-2
HAND DRIER @ LADIES TOILET & ORS
10R 20 2x4 4.0 0.50 2 1.00 50 0.50
TOILET-1
9Y 32 2x4 4.0 HAND DRIER @ OFFICERS TOILET-02 0.50 1 0.50 50 0.25
Page 1 of 2
DB REF : DB-13A12 FED FROM :SMDB -13A11 INCOMING BREAKER SIZE : 100 A TPN ISOLATOR + RCD
LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC
10B 20 2x4 4.0 HAND DRIER @ OFFICERS TOILET-01 0.50 1 0.50 50 0.25
11R 32 SPARE
11Y 32 SPARE
11B 32 SPARE
12R 32 SPARE
12Y 32 SPARE
12B 32 SPARE
Page 2 of 2
DB REF : DB-13A13 FED FROM :SMDB-13A11 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + RCD
LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
10R 20 2X4 4.0 13A S.SOCKET FOR CAV-2 0.50 1 0.50 90 0.45
Page 1 of 2
DB REF : DB-13A13 FED FROM :SMDB-13A11 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + RCD
LOCATION: FIRST FLOOR ELEC.ROOM-03 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
10Y 20 2x4 4.0 13A S.SOCKET FOR CAV-3 0.50 1 0.50 90 0.45
10B 20 2x4 4.0 13A S.SOCKET FOR CAV-4 0.50 1 0.50 90 0.45
11R 20 2X4 4.0 13A S.SOCKET FOR CAV-5 0.50 1 0.50 90 0.45
11Y 20 2x4 4.0 13A S.SOCKET FOR CAV-6 0.50 1 0.50 90 0.45
11B 20 SPARE
12R 20 SPARE
12Y 20 SPARE
12B 20 SPARE
Page 2 of 2
SMDB REF : SMDB-13A01 FED FROM : MDB-13A01 INCOMING BREAKER SIZE : 125 A MCCB MAIN
LOCATION: GROUND FLOOR ELEC.ROOM-02 SMDB SIZE : 4 WAYS INCOMING CABLE SIZE : 4C, 50mm2 CU XLPE/SWA/PVC+ 1C, 25mm2 CU.PVC
4RYB 63 SPARE
LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY
D
2Y 10 2 x 2.5 2.5 LIGHTS IN OFFICE 07 & 06 & MEETING-01 + 3 EM LIGHTS 0.05 15 0.75 75 0.56
3Y 10 2 x 2.5 2.5 LIGHTS IN MEETING-02 & OFFICE 15 & 14 + 3 EM LIGHT 0.05 15 0.75 75 0.56
3B 10 2 x 2.5 2.5 LIGHTS IN STORE-01& OFFICE 11 & 10 + 3 EM LIGHTS 0.05 14 0.70 75 0.53
LIGHTS IN ELEC.02 & TELECOM-02 & SECURITY & OFFICE 09 + 4
4R 10 2 x 2.5 2.5 0.05 17 0.85 75 0.64
EM LIGHTS
40A, TPN (100mA RCD)
4Y 10 2 x 2.5 2.5 LIGHTS IN OFFICE 05 & 04 & 02 + 3 EM LIGHTS 0.05 15 0.75 75 0.56
5Y 10 2 x 2.5 2.5 LIGHTS IN MAIN ENTRANCE HALL + 7 EM LIGHTS 0.05 18 0.90 75 0.68
Page 1 of 2
DB REF : DB-13A01 FED FROM :SMDB -13A01 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + 2 RCD
LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY
D
8R 10 SPARE
8Y 10 SPARE
8B 10 SPARE
9R 10 2 x 2.5 2.5 LIGHTS IN KITCHEN 01 & JAN 01 + 2 EM LIGHTS 0.05 5 0.25 75 0.19
9B 10 2 x 2.5 2.5 LIGHTS IN KITCHEN 02 & JAN 02 + 2 EM LIGHTS 0.05 5 0.25 75 0.19
10R 10 SPARE
10Y 10 2 x 2.5 2.5 LIGHTS IN LADIES TOILET-02 + 1 EM LIGHTS 0.05 4 0.20 75 0.15
10B 10 2 x 2.5 2.5 LIGHTS IN ORS TOILET-01 + 2 EM LIGHTS 0.05 7 0.35 75 0.26
11R 10 2 x 2.5 2.5 LIGHTS IN OFFICER TOILET-02 + 2 EM LIGHTS 0.05 7 0.35 75 0.26
40A, TPN (30mA RCD
11Y 10 SPARE
11B 10 2 x 2.5 2.5 LIGHTS IN ORS TOILET-02 + 2 EM LIGHTS 0.05 7 0.35 75 0.26
12R 10 SPARE
12Y 10 SPARE
12B 10 2 x 2.5 2.5 LIGHTS IN OFFICER TOILET-01 + 2 EM LIGHTS 0.05 7 0.35 75 0.26
13R 20 SPARE
13Y 20 SPARE
13B 20 SPARE
14R 10 SPARE
14Y 10 SPARE
14B 10 SPARE
Page 2 of 2
DB REF : DB-13A02 FED FROM :SMDB -13A01 INCOMING BREAKER SIZE : 100 A TPN ISOLATOR + RCD
LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC
TOTAL CIRCUIT
WIRE SIZE (mm2) (P EARTH WIRE SIZE LD/PNT DIVERSIFIED
LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
BUSBAR
4Y 32 2x6 6.0 13A S.SOCKETS IN OFFICE 05 & 04 & 02 0.20 17 3.40 75 2.55
4B 32 2x4 4.0 13A S.SOCKETS IN MAIN ENTRANCE HALL 0.20 8 1.60 50 0.80
5R 32 2x4 4.0 13A S.SOCKETS IN CORRIDOR & ELEC-02 0.20 5 1.00 50 0.50
13A SPUR OUTLET SOCKETS IN MAIN
5Y 20 2 x4 FIRE RATED 4 FIRE RATED 0.30 1 0.30 75 0.23
ENTRANCE HALL FOR FACP
20A DOUBLE POLE SWITCH FOR W/H IN
5B 20 2x4 4.0 1.50 1 1.50 50 0.75
OFFICER TOILET-01
6R 32 2x4 4.0 13A S.SOCKETS IN KITCHEN 01 & JAN 01 0.20 7 1.40 50 0.70
100A, TPN (30mA RCD
7R 32 2x4 4.0 13A S.SOCKETS IN KITCHEN 02 & JAN 02 0.20 7 1.40 50 0.70
7Y 32 SPARE
20A DOUBLE POLE SWITCH FOR W/H IN ORS
7B 20 2x4 4.0 1.50 1 1.50 50 0.75
TOILET-02
Page 1 of 2
DB REF : DB-13A02 FED FROM :SMDB -13A01 INCOMING BREAKER SIZE : 100 A TPN ISOLATOR + RCD
LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 35mm2 CU XLPE/SWA/PVC+1C, 16mm2 CU.PVC
TOTAL CIRCUIT
WIRE SIZE (mm2) (P EARTH WIRE SIZE LD/PNT DIVERSIFIED
LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
BUSBAR
11R 32 SPARE
11Y 32 SPARE
11B 32 SPARE
12R 32 SPARE
12Y 32 SPARE
12B 32 SPARE
Page 2 of 2
DB REF : DB-13A03 FED FROM :SMDB-13A01 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + RCD
LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RCD
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
(KW) LOAD (KW)
MCB N) (mm2)(E) POINTS FACTOR (%)
CIRCUIT NO R Y B
RATING (A)
Page 1 of 2
DB REF : DB-13A03 FED FROM :SMDB-13A01 INCOMING BREAKER SIZE : 40 A TPN ISOLATOR + RCD
LOCATION: GROUND FLOOR ELEC.ROOM-02 DB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RCD
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
(KW) LOAD (KW)
MCB N) (mm2)(E) POINTS FACTOR (%)
CIRCUIT NO R Y B
RATING (A)
10R 20 2X4 4.0 13A S.SOCKET FOR CAV-3 0.50 1 0.50 90 0.45
10Y 20 2x4 4.0 13A S.SOCKET FOR CAV-4 0.50 1 0.50 90 0.45
10B 20 2x4 4.0 13A S.SOCKET FOR CAV-5 0.50 1 0.50 90 0.45
11R 20 2X4 4.0 13A S.SOCKET FOR CAV-6 0.50 1 0.50 90 0.45
11Y 20 2x4 4.0 13A S.SOCKET FOR AIR CURTAIN 0.22 2 0.45 90 0.40
11B 20 SPARE
12R 20 SPARE
12Y 20 SPARE
12B 20 SPARE
Page 2 of 2
SMDB REF : SMDB-13A01/E FED FROM : ATS-13A01 INCOMING BREAKER SIZE : 200 A MCCB MAIN
LOC. GROUND FLOOR ELEC.ROOM-02 SMDB SIZE : 12 WAYS INCOMING CABLE SIZE : 4C, 95mm2 CU XLPE/SWA/PVC+ 1C, 50mm2 CU.PVC
1RYB 125 4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2 CU.PVC DB-13A0B/UPS 37.00 13.00 10.80 13.20 27.75 90 24.98
2RYB 16 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC TPN ISOLATOR FOR LIFT 3.70 1.23 1.23 1.23 3.70 90 3.33
3RYB 63 4C, 16mm2 CU XLPE/SWA/PVC+ 1C, 16mm2 CU.PVC TPN ISOLATOR FOR CCU-B1 (DUTY) AT BASEMENT 10.80 3.60 3.60 3.60 9.72 90 8.75
4R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR SEF-1 AT ROOF 1.10 1.10 1.10 90 0.99
4Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-1 AT ROOF (DUTY) FOR CCU BASEMENT 1.10 1.10 1.10 90 0.99
4B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B1 AT ROOF(STAND BY) FOR BF OPER.RM 4.00 4.00 4.00 90 3.60
5RYB 32 4C, 6mm2 CU XLPE/SWA/PVC+ 1C, 6mm2 CU.PVC TPN ISOLATOR FOR AHU-B1 AT ROOF 4.00 1.33 1.33 1.33 3.60 90 3.24
6R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B1(STAND BY) AT ROOF FOR BF OPER.RM 4.00 4.00 4.00 90 3.60
6Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B1 (STAND BY) AT ROOF FOR BF OPER.RM 4.00 4.00 4.00 90 3.60
6B 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B1 AT ROOF(STAND BY) FOR BF OPER.RM 4.00 4.00 4.00 90 3.60
7RYB 63 4C, 16mm2 CU XLPE/SWA/PVC+ 1C, 16mm2 CU.PVC TPN ISOLATOR FOR CCU-B1 (ASSIST) AT BASEMENT 10.80 3.60 3.60 3.60 9.72 90 8.75
8R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR LIFT LIGHTING 0.50 0.50 0.50 90 0.45
8Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-1 AT ROOF (STAND BY) FOR CCU BASEMENT 1.00 1.00 1.00 90 0.90
8B 20 SPARE
9RYB 40 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC DB-13A0B 10.45 2.35 4.10 4.00 7.86 90 7.07
10R 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B2 AT GF ROOF(DUTY) FOR BF TUNNEL 2.45 2.45 2.45 90 2.21
10Y 20 3C, 6mm2 CU XLPE/SWA/PVC SPN ISOLATOR FOR CU-B2 AT GF ROOF(DUTY) FOR BF TUNNEL 2.45 2.45 2.45 90 2.21
10B 20 SPARE
11R 20 SPARE
11Y 20 SPARE
11B 20 SPARE
12RYB 40 SPARE
LOCATION: BASEMENT FLOOR ELECTRICAL ROOM-01 DB SIZE : 14 WAYS INCOMING CABLE SIZE : 4C, 50mm2 CU XLPE/SWA/PVC+1C, 25mm2 CU.PVC
SECTION/RC
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D
1B 20 2x4 4.0 UNSWITCHED SPUR OUTLETS FOR FM200 0.20 2 0.40 75 0.30
16A INDUSTRIAL SOCKETS IN OPERATION
2R 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
16A INDUSTRIAL SOCKETS IN OPERATION
2Y 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
16A INDUSTRIAL SOCKETS IN OPERATION
2B 20 2x4 4.0 1.20 1 1.20 75 0.90
ROOM
3R 20 SPARE 75 0.00
3Y 32 SPARE
3B 32 SPARE
8B 32 2x4 4.0 13A SOCKETS IN TELECOM ROOM -01 0.20 6 1.20 75 0.90
13Y 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30
13B 32 2x6 6.0 13A SOCKETS IN SECURITY ROOM 0.20 8 1.60 75 1.20
14R 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30
14Y 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30
14B 20 2x4 4.0 13A SOCKETS IN OPERATION ROOM 0.20 2 0.40 75 0.30
Page 1 of 1
DB REF : DB-13A0B FED FROM :SMDB-13A01/E INCOMING BREAKER SIZE : 40 A,TPN ISO. + 2RCD
LOCATION: BASEMENT FLOOR ELECTRICAL ROOM-01 DB SIZE : 10 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D
2R 10 SPARE
3R 10 2x4 4.0 LIGHTS IN OFFICE-01 & ELEC. ROOM + 2 EM LIGHTS 0.05 6 0.30 75 0.23
32A, TPN (100mA RCD)
3Y 10 2x4 4.0 LIGHTS IN TELECOM & SUMP PIT + 1 EM LIGHT 0.05 4 0.20 75 0.15
6RYB 20 3C X 6 CU BOOSTER PUMP CONTROL PANEL 1.20 1 0.40 0.40 0.40 75 0.90
7R 32 SPARE
7Y 20 2x4 4.0 13A SOCKETS IN LOBBY & ELEC.-01 0.20 3 0.60 50 0.30
Page 1 of 2
DB REF : DB-13A0B FED FROM :SMDB-13A01/E INCOMING BREAKER SIZE : 40 A,TPN ISO. + 2RCD
LOCATION: BASEMENT FLOOR ELECTRICAL ROOM-01 DB SIZE : 10 WAYS INCOMING CABLE SIZE : 4C, 10mm2 CU XLPE/SWA/PVC+1C, 10mm2 CU.PVC
SECTION/RC
LD/PNT DIVERSIFIED
(mm2) (P & WIRE SIZE LOAD DESCRIPTION NO.OF DIVERSITY REMARKS
D
8R SPARE
40A, TPN (30mA RCD)
8B SPARE
9R 32 SPARE
9Y 32 SPARE
9B 32 SPARE
10R 32 SPARE
10Y 32 SPARE
10B 32 SPARE
Page 2 of 2