ACYG04 13.8KV Secundaria REG670

The document outlines the adjustment orders for the G-04 generator and TR-04 transformer, detailing their nominal values, protection functions, and configuration parameters. It includes specific settings for various protection functions such as 87G and 87SP, as well as signal matrices for analog and binary inputs/outputs. Additionally, it provides guidelines for configuring current transformers and voltage transformers within the system.

Uploaded by

j77965265
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
20 views26 pages

ACYG04 13.8KV Secundaria REG670

The document outlines the adjustment orders for the G-04 generator and TR-04 transformer, detailing their nominal values, protection functions, and configuration parameters. It includes specific settings for various protection functions such as 87G and 87SP, as well as signal matrices for analog and binary inputs/outputs. Additionally, it provides guidelines for configuring current transformers and voltage transformers within the system.

Uploaded by

j77965265
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 26

GT/DEL2 O.A.

nº : GT/DEL2 - 076
ANDE
ORDENES DE AJUSTE REV nº : 000
Interno : GT/DEL2/007/2011
PANEL PROT. SECUNDARIA : G-04 FABRICANTE: EQUIPO :
FUNCION/ES : 87G-87T-87N-50BF-51N ABB G-04
60FL-51-67-64R-21-24-32-59-40-50AE-46-49-59THD-87SP
MODELO : LOCALIZACIÓN: CIRCUITO:
REG 670 Sala de relés - CH-ACY G-04 - (60,7 MVA)
RTC(A) : RTP(V) :
---
FECHA : 11/07/2011 OBSERVACIONES :

Generador G-04

Valores nominales
Potencia 60,7 MVA
Tensión 13.8 kV
cos Ø 0.8
Corriente nominal 2540 [A]
Frecuencia 50 Hz
Xq" 0.22 p.u.
Xq' 0.5 p.u.
Xq 0.6 p.u.
Xd 0.86 p.u.
Xd' 0.23 p.u.
Xd'' 0.16 p.u.
X2 0.19 p.u.
X0 0.07 p.u. Base = 60.7 MVA

Transformador elevador TR-04

Valores nominales
Potencia 75 MVA
Tensión 220 - 13.8 kV
Conexionado YNd11
Impedancia 0.112 p.u. Base = 75 MVA

1/26
Diagrama Unifilar de la posición

1000/5

800/5

VT ratio = 13.8/0.11 kV

3000/5

1500/5 (87SP)
3000/5

Funciones de protección utilizadas


+ 87SP

General settings for the TerminalID (TEID-) function


Parameter Range Step Selected value Unit Description
StationName 0 - 18 1 CH-ACARAY - Station name
StationNumber 0 - 99999 1 0 - Station number
ObjectName 0 - 18 1 G-04 - Nome do objeto
ObjectNumber 0 - 99999 1 0 - Object number
UnitName 0 - 18 1 REG670 - Unit name
UnitNumber 0 - 99999 1 0 - Unit number

2/26
Signal matrix for analog inputs (SMAI)
Este grupo define las entradas analógicas de corriente y tensión utilizadas por el relé
deben ser configurados a traves deL Application Configuration (CAP531) del programa PCM600, conforme proyecto

General settings for the AISERVAL (AISV-) function


Parameter Range Step Default Unit Description
Reference channel for
PhaseAngleRef 1 - 24 1 7 Ch phase angle presentation

Colocar el canal analógico a ser utilizado como referencia de fase


Ej.: ajustar PhaseAngleRef=7 para la tensión fase tierra, normalmente
L1 conectado al canal 7 de la tarjeta analógica de tensión

Basic general settings for the ANALOGIN12I (TA40-) function (Depende del modelo de placa TRM, cantidad de canales)
Parameter Range Step Default Unit Description
FromObject ToObject= towards protected object,
CTStarPoint1 ToObject - ToObject - FromObject=the opposite

Conforme a lo indicado en la siguiente figura colocar los CTStarPoint (de cada TC a ser utilizado, ver application manual REG670):

Parameter Range Step Selected value Unit Description


CTsec1 1 - 10 1 5 A Rated CT secondary current
CTprim1 1 - 99999 1 1000 A Rated CT primary current

Obs.: ejemplo para un TC de 1000/5 A

3/26
Basic general settings for the ANALOGIN6I6U (TD40-) function
Parameter Range Step Selected value Unit Description
VTsec7 0.001 - 999.999 0.001 110 V Rated VT secondary voltage
VTprim7 0.05 - 2000.00 0.05 13.8 kV Rated VT primary voltage

General settings for the RatedFreq (RFR--) function


Parameter Range Step Selected value Unit Description
Frequency 50.0 - 60.0 10.0 50 Hz Rated system frequency

Signal matrix for binary inputs (SMBI)


Signal matrix for binary outputs (SMBO) Deben ser parametrizados de acuerdo con el projeto
HMI

87G - Generator differential protection (PDIF, 87G)


CT input channels used for 13,8 kV
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

CT input channels used for neutr Gen


Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

Basic general settings for the GENPDIF_87G (GDP1-) function


Parameter Range Step Selected value Unit Description
IBase 100.0 - 100000.0 0.1 2540 A Rated current of protected generator
InvertCT2Curr No, Yes - No - Invert CT 2 curr., yes (1)
or no (0). Default is no (0).

Basic parameter group settings for the GENPDIF_87G (GDP1-) function


Parameter Range Step Selected value Unit Description
Operation Off -On - On - Operation Off / On
IdMin 0.05 - 1.00 0.01 0.3 IB Section 1 sensitivity, multiple
of generator rated current
IdUnre 1.00 - 50.00 0.01 12 IB Unrestr. prot. limit, multiple
of generator rated current
OpNegSeqDiff No, Yes - Yes - Negative Sequence Differential
Enable Off/On
IMinNegSeq 0.02 - 0.20 0.01 0.04 IB Neg. sequence curr. limit,
as multiple of gen. Rated curr.

Advanced parameter group settings for the GENPDIF_87G (GDP1-) function


Parameter Range Step Selected value Unit Description
EndSection1 0.20 - 1.50 0.01 1.25 IB End of section 1, multiple
of generator rated current
EndSection2 1.00 - 10.00 0.01 3.00 IB End of section 2, multiple
of generator rated current
SlopeSection2 10.0 - 50.0 0.1 25 % Slope in section 2 of operate-restrain
characteristic, in %n
SlopeSection3 30.0 - 100.0 0.1 60 % Slope in section 3 ofoperate-restrain
characteristic, in %n
OpCrossBlock No, Yes - Yes - Operation On/Off for cross-blockLogic
between phases
NegSeqROA 30.0 - 120.0 0.1 60.0 Deg Operate Angle of int/ext neg. seq.
fault discriminator, deg

4/26
HarmDistLimit 5.0 - 100.0 0.1 10.0 % (Total) relative harmonic distorsion
limit, percent
TempIdMin 1.0 - 5.0 0.1 2.0 IdMin Temp. Id pickup wheninput raise
PickUp=1, multiple of IdMin
AddTripDelay 0.000 - 60.000 0.001 0.100 s Additional trip delay,when input
raisePickUp=1
OperDCBiasing Off, On - Off - Operation DC biasing On/ Off

87SP - Generator differential protection - Split Phase (PDIF, 87SP)

Parameter Range Step Selected value Unit Description


Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 1500 A Rated CT primary current
FromObject Verificar/ToObje ToObject= towards protected object,
CTStarPoint ToObject - ct o FromObjec - FromObject=the opposite

Parameter Range Step Selected value Unit Description


Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 1500 A Rated CT primary current
FromObject Verificar/ToObje ToObject= towards protected object,
CTStarPoint ToObject - ct o FromObjec - FromObject=the opposite

Basic general settings for the GENPDIF_87SP (GDP2-) function


Parameter Range Step Selected value Unit Description
IBase 100.0 - 100000.0 0.1 2540 A Rated current of protected generator
InvertCT2Curr No, Yes - No - Invert CT 2 curr., yes (1)
or no (0). Default is no (0).

Basic parameter group settings for the GENPDIF_87SP (GDP2-) function


Parameter Range Step Selected value Unit Description
Operation Off -On - On - Operation Off / On
IdMin 0.05 - 1.00 0.01 0.3 IB Section 1 sensitivity, multiple
of generator rated current
IdUnre 1.00 - 50.00 0.01 12 IB Unrestr. prot. limit, multiple
of generator rated current
OpNegSeqDiff No, Yes - Yes - Negative Sequence Differential
Enable Off/On
IMinNegSeq 0.02 - 0.20 0.01 0.04 IB Neg. sequence curr. limit,
as multiple of gen. Rated curr.

Advanced parameter group settings for the GENPDIF_87SP (GDP2-) function


Parameter Range Step Selected value Unit Description
EndSection1 0.20 - 1.50 0.01 1.25 IB End of section 1, multiple
of generator rated current
EndSection2 1.00 - 10.00 0.01 3.00 IB End of section 2, multiple
of generator rated current
SlopeSection2 10.0 - 50.0 0.1 25 % Slope in section 2 of operate-restrain
characteristic, in %n
SlopeSection3 30.0 - 100.0 0.1 60 % Slope in section 3 ofoperate-restrain
characteristic, in %n
OpCrossBlock No, Yes - Yes - Operation On/Off for cross-blockLogic
between phases
NegSeqROA 30.0 - 120.0 0.1 60.0 Deg Operate Angle of int/ext neg. seq.
fault discriminator, deg
HarmDistLimit 5.0 - 100.0 0.1 10.0 % (Total) relative harmonic distorsion
limit, percent

TempIdMin 1.0 - 5.0 0.1 2.0 IdMin Temp. Id pickup wheninput raise
PickUp=1, multiple of IdMin
AddTripDelay 0.000 - 60.000 0.001 0.100 s Additional trip delay,when input
raisePickUp=1

5/26
OperDCBiasing Off, On - Off - Operation DC biasing On/ Off

87T
CT input channels used for the LV side CTs
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - ToObject - FromObject=the opposite

CT input channels used for the HV side CTs


Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 1000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - ToObject - FromObject=the opposite

Basic general settings for the T2WPDIF_87T (T2D1-) function


Parameter Range Step Selected value Unit Description
RatedVoltageW1 0.05 - 2000.00 0.05 220 kV transformer winding 1
RatedVoltageW2 0.05 - 2000.00 0.05 13.8 kV Rated voltage of transformer
winding 2 in kV
RatedCurrentW1 1 - 99999 1 197 A Rated current of transformer
winding 1 (HV winding) in A
RatedCurrentW2 1 - 99999 1 3138 A Rated current of transformer
winding 2 in A
ConnectTypeW1 WYE (Y) DELTA (D) - WYE (Y) - Connection type of winding 1:
Y-wye or D-delta
ConnectTypeW2 WYE (Y) DELTA (D) - DELTA (D) - Connection type of winding 2:
Y-wye or D-delta
ClockNumberW2 0 [0 deg] - 11 [30 deg lead] - Phase displacement
1 [30 deg lag] between W2 & W1=HV
2 [60 deg lag] winding, hour notation
3 [90 deg lag]
4 [120 deg lag]
5 [150 deg lag]
6 [180 deg]
7 [150 deg lead]
8 [120 deg lead]
9 [90 deg lead]
10 [60 deg lead]
11 [30 deg lead]
ZSCurrSubtrW1 Off - ON - Enable zer. seq. Curr subtraction
ON for W1 side, On / Off
ZSCurrSubtrW2 Off - Off - Enable zer. seq. Curr subtraction
ON for W2 side, On / Off
TconfigForW1 No - No - Two CT inputs (T-config.) for
Yes winding 1, YES / NO

6/26
Basic parameter group settings for the T2WPDIF_87T (T2D1-) function
Parameter Range Step Selected value Unit Description
Off
Operation ON - ON - Operation Off / On
Off Operation mode for
SOTFMode ON - Off - switch onto fault
Time delay for diff
tAlarmDelay 0.000 - 60.000 0.001 10 s currents alarm level
IDiffAlarm IDiffAlarm 5 - 100 1 20 %IB Diff. current alarm pickup
level set as % of W1 base current
IdMin 0.10 - 0.60 0.01 0.3 IB Sust. dif. cur. alarm; multiple of
Winding 1 rated current
EndSection1 0.20 - 1.50 0.01 1.25 IB End of section 1, multiple
of Winding 1 rated current
EndSection2 1.00 - 10.00 0.01 3.00 IB End of section 2, multiple
of Winding 1 rated current
SlopeSection2 10.0 - 50.0 0.1 40.0 % Slope in section 2 of
operate-restrain characteristic, in%
SlopeSection3 30.0 - 100.0 0.1 80.0 % Slope in section 3 of
operate-restrain characteristic, in%
IdUnre 1.00 - 50.00 0.01 12.00 IB Unrestr. prot. limit, multiple of
Winding 1 rated current
I2/I1Ratio 5.0 - 100.0 1.0 15.0 % Max. ratio of 2nd harm. to
fundamental harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 1.0 25.0 % Max. ratio of 5th harm. to
fundamental harm dif. curr. in %
CrossBlockEn Off - ON - Operation Off/On for cross-block
ON logic between phases
NegSeqDiffEn Off - ON - Operation Off/On for neg.
ON seq. differential protections
IMinNegSeq 0.02 - 0.20 0.01 0.04 IB IB Neg. seq. curr. must be
higher than this level to be used
NegSeqROA 30.0 - 120.0 0.1 60.0 Deg Operate Angle for int. /
ext. neg. seq. fault discriminator
OpenCTEnable Off - ON - Open CT detection feature.
ON Open CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 0.001 3 s Open CT: time in s to
alarm after an open CT is detected
tOCTResetDelay 0.100 - 10.000 0.001 0.250 s Reset delay in s. After
delay, diff. function is activated
tOCTUnrstDelay 0.10 - 6000.00 0.01 10.00 s Unrestrained diff. protection
blocked after this delay, in s

87N
CT input channels used for the Neutral HV side CTs
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 800 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

CT input channels used for the HV side CTs


Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 1000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - ToObject - FromObject=the opposite

7/26
Basic parameter group settings for the REFPDIF_87N (REF1-) function
Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off/On
On
IBase 1 - 99999 1 197 A Base current

IdMin 4.0 - 100.0 0.1 10.0 %IB Maximum sensitivity in %


of Ibase
CTFactorPri1 1.0 - 10.0 0.1 1.0 - CT factor for HV side
CT1 (CT1rated/ Hvrated current)
CTFactorPri2 1.0 - 10.0 0.1 1.0 - CT factor for HV side
CT2 (CT2rated/ Hvrated current)
CTFactorSec1 1.0 - 10.0 0.1 1.0 - CT factor for MV side
CT1 (CT1rated/ Mvrated current)
CTFactorSec2 1.0 - 10.0 0.1 1.0 - CT factor for MV side
CT2 (CT2rated/ Mvrated current)

Advanced parameter group settings for the REFPDIF_87N (REF1-) function


Parameter Range Step Selected value Unit Description
ROA 60 - 90 1 60 Deg Relay operate angle for zero
sequence directional feature

21
CT input channels
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

Parameter Range Step Selected value Unit Description


Vtsec 0.001 - 999.999 0.001 110 V Rated VT secondary voltage
Vtprim 0.05 - 2000.00 0.05 13.8 kV Rated VT primary voltage

Basic parameter group settings for the ZMHPDIS_21 (ZMH1-) function


Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off/On
On
IBase 1 - 99999 1 2540 A Base current

UBase 0.05 - 2000.00 0.05 13,8 kV Base voltage

DirMode Off-Offset-Forward-Reverse
- Offset - Direction mode
-
LoadEnchMode Off - Off - Load enchroachment
On mode Off/On
ReachMode OverReach - OverReach - Reach mode
Underreach Over/Underreach
OpModePE Off _ Off - Operation mode Off / On
On of Phase-Earth loops
ZPE 0.005 - 3000.000 0.001 30000 ohm/p Positive sequence impedance
setting for Phase-Earth loop
ZAngPE 10 - 90 1 80 Deg Angle for positive sequence line
impedance or Phase-Earth loop
KN 0.00 – 3.00 0.01 0.80 - Magnitud of earth return
compensation factor KN
KNAng -180 - 180 1 -15 Deg Angle for earth return
compensation factor KN
ZRevPE 0.005 - 3000.000 0.001 30000 ohm/p Reverse reach of the phase
to earth loop(magnitude)

8/26
tPE 0.000 - 60.000 0.001 0.000 s Delay time for operation
of phase to earth elements

Parameter Range Step Selected value Unit Description


IMinOpPE 10 - 30 1 20 %IB Minimum operation
phase to earth current
OpModePP Off - On - Operation mode Off / On
On of Phase-Phase loops
ZPP 0.005 - 3000.000 0.001 1,2 ohm/p Impedance setting reach
for phase to phase elements
ZAngPP 10 - 90 1 89 Deg Angle for positive sequence line
impedanc for Phase-Phase elem
ZRevPP 0.005 - 3000.000 0.001 1,2 ohm/p Reverse reach of the phase to
phase loop(magnitude)
tPP 0.000 - 60.000 0.001 1 s Delay time for operation
of phase to phase
IMinOpPP 10 - 30 1 20 %IB Minimum operation
phase to phase current

Advanced parameter group settings for the ZMHPDIS_21 (ZMH1-) func


Parameter Range Step Selected value Unit Description
OffsetMhoDir Non-directional - Non-directional - Direction mode for offset
Forward mho
Reverse
OpModetPE Off - On - Operation mode Off / On
On of Zone timer, Ph-E
OpModetPP Off - On - Operation mode Off / On
On of Zone timer, Ph-ph

40
Basic general settings for the LEXPDIS_40 (UEX1-) function
Parameter Range Step Selected value Unit Description
IBase 0.1 - 99999.9 0.1 2540 A Base Current (primary phase
current in Amperes)
UBase 0.1 - 9999.9 0.1 13,8 kV Base Voltage (primary phase
to-phase voltage in kV)
MeasureMode PosSeq - PosSeq - Measuring mode (Pos-Seq,
L1L2 L1L2, L2L3, L3L1)
L2L3
L3L1

Basic parameter group settings for the LEXPDIS_40 (UEX1-) function


Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off / On
On
OperationZ1 Off - On - Operation Off/On zone Z1
On
XoffsetZ1 -1000.00 - 1000.00 0.01 -11.5 % Offset of Z1 circle top point
along X axis in % of Zbase
Z1diameter 0.01 - 3000.00 0.01 83 % Diameter of imedance circle
for Z1 in % of Zbase
tZ1 0.00 - 6000.00 0.01 0.01 s Trip time delay for Z1
OperationZ2 Off - On - Operation Off/On zone Z2
On
XoffsetZ2 -1000.00 - 1000.0 0.01 -11 % Offset of Z2 circle top point
along X axis in % of Zbase
Z2diameter 0.01 - 3000.00 0.01 105.6 % Diameter of imedance circle
for Z2 in % of Zbase
tZ2 0.00 - 6000.00 0.01 2. s Trip time delay for Z2

9/26
Advanced general settings for the LEXPDIS_40 (UEX1-) function
Parameter Range Step Selected value Unit Description
invertCTcurren No - No - Operation Off/On for additional
Yes directional criterion

Advanced parameter group settings for the LEXPDIS_40 (UEX1-) function


Parameter Range Step Selected value Unit Description
DirSuperv Off On - Operation Off/On for
On additional directional criterion
XoffsetDirLine -1000.00 - 3000.00 0.01 0.00 % Offset of directional line
along X axis in % of Zbase
DirAngle -180.0 - 180.0 0.1 -13.0 Deg Angle between directional line
and R-axis in degrees

51 / 67
CT input channels used for the 13,8 kV side CTs
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

Basic general settings for the OC4PTOC_51_67 (TOC1-) function


Parameter Range Step Selected value Unit Description
MeasType DFT - RMS - Selection between DFT
RMS and RMS measurement

Basic parameter group settings for the OC4PTOC_51_67 (TOC1-) function


Parameter Range Step Selected value Unit Description
Operation Off On - Operation Off / On
On
IBase 1 - 99999 1 2540 A Base current

Ubase 0.05 - 2000.00 0.05 13,8 kV Base Voltage

AngleRCA 40 - 65 1 55 Deg Relay characteristic angle (RCA)

AngleROA 40 - 89 1 80 Deg Relay operation angle


(ROA)
StartPhSel Not Used - 1 out of 3 - Number of phases
1 out of 3 required for op (1 of 3, 2
2 out of 3 of 3, 3 of 3)
3 out of 3
DirMode1 Off - Non-directional - Directional mode of step 1
Non-directional (off, nodir, forward,
Forward reverse)
Reverse
Characterist1 ANSI Ext. inv. - IEC Very inv. - Selection of time delay
ANSI Very inv. curve type for step 1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time

10/26
Reserved
Programmable
RI type
RD type
I1> 1 - 2500 1 140 %IB Phase current operate
level for step1 in % of Ibase
t1 0.000 - 60.000 0.001 0.000 s Definitive time delay of step 1

k1 0.05 - 999.00 0.01 0.15 - Time multiplier for the inverse


time delay for step 1
t1Min 0.000 - 60.000 0.001 0.000 s Minimum operate time for
inverse curves for step 1
I1Mult 1.0 - 10.0 0.1 1 - Multiplier for current
operate level for step 1

Advanced parameter group settings for the OC4PTOC_51_67 (TOC1-) function


Parameter Range Step Selected value Unit Description
IMinOpPhSel 1 - 100 1 7 %IB Minimum current for
phase selection in % of Ibase
2ndHarmStab 5 - 100 1 20 %IB Operate level of 2nd harm
restrain op in % of Fundamental
ResetTypeCrv1 Instantaneous - Instantaneous - Selection of reset curve
IEC Reset type for step 1
ANSI reset
HarmRestrain1 Off - Off - Enable block of step 1
On from harmonic restrain

51N
CT input channels used for the HV (Neutral) side CTs -transformer.
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 800 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

Basic parameter group settings for the EF4PTOC_51N67N (TEF1-) function


Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 197 A Base value for current
settings
UBase 0.05 - 2000.00 0.05 220 kV Base value for voltage
settings
AngleRCA -180 - 180 1 65 Deg Relay characteristic
angle (RCA)
polMethod Voltage - Current - Type of polarization
Current
Dual
UPolMin 1 - 100 1 1 %UB Minimum voltage level for
polarization in % of Ubase
IPolMin 2 - 100 1 5 %IB Minimum current level for
polarization in % of IBase
RNPol 0.50 - 1000.00 0.01 25 ohm Real part of source Z to
be used for current polarisation
XNPol 0.50 - 3000.00 0.01 199 ohm Imaginary part of source Z
to be used for current polarisat
IN>Dir 1 - 100 1 10 %IB Residual current level for
Direction release in % of Ibase
2ndHarmStab 5 - 100 1 20 % Second harmonic restrain
operation in % of IN amplitude
BlkParTransf Off - Off - Enable blocking at parallel
On transformers

11/26
Parameter Range Step Selected value Unit Description
UseStartValue IN1> - IN4> - Current level blk at parallel
IN2> transf (step1, 2, 3 or 4)
IN3>
IN4>
SOTF Off - Off - SOTF operation mode
SOTF (Off/SOTF/Undertime/
UnderTime SOTF+undertime)
SOTF+UnderTime
ActivationSOTF Open - Open - Select signal that shall
Closed activate SOTF
CloseCommand
StepForSOTF Step 2 - Step 2 - Selection of step used for
Step 3 SOTF
HarmResSOTF Off - Off - Enable harmonic restrain
On function in SOTF
tSOTF 0.000 - 60.000 0.001 0.200 s Time delay for SOTF

t4U 0.000 - 60.000 0.001 1 s Switch-onto-fault active time

DirMode1 Off - Non-directional - Directional mode of step


Non-directional 1 (off, nodir, forward,
Forward reverse
Reverse
Characterist1 ANSI Ext. inv. - IEC Very inv. - Time delay curve type for
ANSI Very inv. step 1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Reserved
Programmable
RI type
RD type
IN1> 1 - 2500 1 116 %IB Operate residual current
level for step 1 in % of Ibase
t1 0.000 - 60.000 0.001 0.000 s Independent (defenite)
time delay of step 1
k1 0.05 - 999.00 0.01 0.1 - Time multiplier for the
dependent time delay for step 1
IN1Mult 1.0 - 10.0 0.1 1 - Multiplier for scaling the
current setting value for
t1Min 0.000 - 60.000 0.001 0.000 s Minimum operate time for
inverse curves for step 1
HarmRestrain1 Off - Off - Enable block of step 1
On from harmonic restrain

12/26
50BF
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 1000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - ToObject - FromObject=the opposite

Basic parameter group settings for the CCRBRF_50BF (BFP1-) function


Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 197 A Base current

FunctionMode Current - Current - Detection principle for


Contact back-up trip
Current&Contact
BuTripMode 2 out of 4 - 1 out of 3 - Back-up trip mode
1 out of 3
1 out of 4
RetripMode Retrip Off - Retrip Off Operation mode of re-trip
CB Pos Check logic
No CBPos Check
IP> 5 - 200 1 60 %IB Operate phase current
level in % of IBase
IP> 5 - 200 1 60 %IB Operate phase current
level in % of IBase
t1 0.000 - 60.000 0.001 0.1 s Time delay of re-trip

t2 0.000 - 60.000 0.001 0.220 s Time delay of back-up


trip
t2MPh 0.000 - 60.000 0.001 0.220 s Time delay of back-up
trip at multi-phase start
tPulse 0.000 - 60.000 0.001 0.200 s Trip pulse duration

Advanced parameter group settings for the CCRBRF_50BF (BFP1-) function


Parameter Range Step Selected value Unit Description
I>BlkCont 5 - 200 1 65 %IB Current for blocking of
CB contact operation in
% of IBase
t3 0.000 - 60.000 0.001 0.03 s Additional time delay to
t2 for a second back-up trip
tCBAlarm 0.000 - 60.000 0.001 5 s Time delay for CB faulty
signal

13/26
32
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

Basic general settings for the GOPPDOP_32 (GOP1-) function


Parameter Range Step Selected value Unit Description
IBase 1 - 99999 1 2540 A Current-Reference (primary
current A)
UBase 0.05 - 2000.00 0.05 13.8 kV Voltage-Reference (primary
voltage kV)
Mode L1, L2, L3 - Pos Seq - Selection of measured
Arone current and voltage
Pos Seq
L1L2
L2L3
L3L1
L1
L2
L3

Basic parameter group settings for the GOPPDOP_32 (GOP1-) functio


Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off / On
On
OpMode1 Off - OverPower - Operation mode 1
OverPower
Power1 0.0 - 500.0 0.1 1 %SB Power setting for stage 1
in % of Sbase
Angle1 -180.0 - 180.0 0.1 179 Deg Angle for stage 1

TripDelay1 0.010 - 6000.000 0.001 2 s Trip delay for stage 1

DropDelay1 0.010 - 6000.000 0.001 0.060 s Drop delay for stage 1

OpMode2 Off - OverPower - Operation mode 2


OverPower
Power2 0.0 - 500.0 0.1 2 %SB Power setting for stage 2
in % of Sbase
Angle2 -180.0 - 180.0 0.1 179 Deg Angle for stage 2

TripDelay2 0.010 - 6000.000 0.001 1 s Trip delay for stage 2

DropDelay2 0.010 - 6000.000 0.001 0.060 s Drop delay for stage 2

Advanced parameter group settings for the GOPPDOP_32 (GOP1-) function


Parameter Range Step Selected value Unit Description
k 0.00 - 0.99 0.01 0.00 - Low pass filter coefficient
for power measurement,Pand Q
Hysteresis1 0.2 - 5.0 0.1 0.3 pu Absolute hysteresis of
stage 1 in % of Sbase
Hysteresis2 0.2 - 5.0 0.1 0.3 pu Absolute hysteresis of
stage 2 in % of Sbase
IAmpComp5 -10.000 - 10.000 0.001 0.000 % Amplitude factor to calibrate
current at 5% of Ir
IAmpComp30 -10.000 - 10.000 0.001 0.000 % Amplitude factor to calibrate
current at 30% of Ir

14/26
IAmpComp100 -10.000 - 10.000 0.001 0.000 % Amplitude factor to calibrate
current at 100% of Ir

Parameter Range Step Selected value Unit Description


UAmpComp5 -10.000 - 10.000 0.001 0.000 % Amplitude factor to calibrate
voltage at 5% of Ur
UAmpComp30 -10.000 - 10.000 0.001 0.000 % Amplitude factor to calibrate
voltage at 30% of Ur
UAmpComp100 -10.000 - 10.000 0.001 0.000 % Amplitude factor to calibrate
voltage at 100% of Ur
IAngComp5 -10.000 - 10.000 0.001 0.000 Deg Angle calibration for current
at 5% of Ir
IAngComp30 -10.000 - 10.000 0.001 0.000 Deg Angle calibration for current
at 30% of Ir
IAngComp100 -10.000 - 10.000 0.001 0.000 Deg Angle calibration for current
at 100% of Ir

59
Parameter Range Step Selected value Unit Description
ConnType PhG - PhG - TBD
PhPh
PhG RMS
PhPh RMS

Basic parameter group settings for the OV2PTOV_59 (TOV1-) function


Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off / On
On
UBase 0.05 - 2000.00 0.05 13.8 kV Base voltage
OperationStep1 Off - On - Enable execution of step 1
On
Characterist1 Definite time - Definite time - Selection of time delay
Inverse curve A curve type for step 1
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode1 1 out of 3 - 1 out of 3 - Number of phases
2 out of 3 required for op (1 of 3, 2
3 out of 3 of 3, 3 of 3) from step 1

U1> 1 - 200 1 115 %UB Voltage setting/start val


(DT & IDMT) in % of UBase, step 1
t1 0.00 - 6000.00 0.01 5.00 s Definitive time delay of step 1

t1Min 0.000 - 60.000 0.001 5.00 s Minimum operate time for


inverse curves for step 1
k1 0.05 - 1.10 0.01 0.05 - Time multiplier for the
inverse time delay for step 1
HystAbs1 0.0 - 100.0 0.1 0.5 %UB Absolute hysteresis in %
of UBase, step 1
OperationStep2 Off - On - Enable execution of step 2
On
Characterist2 Definite time - Definite time - Selection of time delay
Inverse curve A curve type for step 2
Inverse curve B
Inverse curve C
Prog. inv. curve
OpMode2 1 out of 3 - 3 out of 3 - Number of phases
2 out of 3 required for op (1 of 3, 2
3 out of 3 of 3, 3 of 3) from step 2

15/26
U2> 1 - 200 1 140 %UB Voltage setting/start val
(DT & IDMT) in % of
UBase, step 2
t2 0.000 - 60.000 0.001 0,5 s Definitive time delay of step 2

Parameter Range Step Selected value Unit Description


t2Min 0.000 - 60.000 0.001 5 s Minimum operate time for
inverse curves for step 2
k2 0.05 - 1.10 0.01 0.05 - Time multiplier for the
inverse time delay for step 2
HystAbs2 0.0 - 100.0 0.1 0.5 %UB Absolute hysteresis in %
of UBase, step 2

24
Overexcitation protection
Basic general settings for the OEXPVPH_24 (OEX1-) function
Parameter Range Step Selected value Unit Description
MeasuredU PosSeq - PosSeq - Selection of measured
L1L2 voltage
L2L3
L3L1
MeasuredI L1L2 - PosSeq - Selection of measured
L2L3 current
L3L1
PosSeq
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 2540 A Base current (rated
phase current) in A
UBase 0.05 - 2000.00 0.05 13.8 kV Base voltage (main voltage)
in kV
V/Hz> 100.0 - 180.0 0.1 110.0 %UB/f Operate level of V/Hz at no load %
and rated freq in of (Ubase/frated)
V/Hz>> 100.0 - 200.0 0.1 140.0 %UB/f High level of V/Hz above which
tMin is used,in% of (Ubase/frated)
XLeak 0.000 - 200.000 0.001 0,14 ohm Winding leakage reactance
in primary ohms
TrPulse 0.000 - 60.000 0.001 0.100 s Length of the pulse for
trip signal (in sec)
tMin 0.000 - 60.000 0.001 1 s Minimum trip delay for
V/Hz inverse curve, in sec
tMax 0.00 - 9000.00 0.01 1800.00 s Maximum trip delay for
V/Hz inverse curve, in sec
tCooling 0.10 - 9000.00 0.01 2700 s Transformer magnetic
core cooling time const, in sec
CurveType IEEE - Tailor made - Inverse time curve selection,
Tailor made IEEE/Tailor made
kForIEEE 1 - 60 1 3 - Time multiplier for IEEE
inverse type curve
AlarmLevel 50.0 - 120.0 0.1 98 % Alarm operate level as %
of operate level
tAlarm 0.00 - 9000.00 0.01 5.00 s Alarm time delay, in sec

t1Tailor 0.00 - 9000.00 0.01 6000 s Time delay t1 (longest)


for tailor made curve, in sec
t2Tailor 0.00 - 9000.00 0.01 450 s Time delay t2 (longest)
for tailor made curve, in sec
t3Tailor 0.00 - 9000.00 0.01 45 s Time delay t3 (longest)
for tailor made curve, in sec

16/26
t4Tailor 0.00 - 9000.00 0.01 15 s Time delay t4 (longest)
for tailor made curve, in sec
t5Tailor 0.00 - 9000.00 0.01 6 s Time delay t5 (longest)
for tailor made curve, in sec
t6Tailor 0.00 - 9000.00 0.01 3 s Time delay t6 (longest)
for tailor made curve, in sec

60FL
Fuse failure supervision
Basic parameter group settings for the SDDRFUF (FSD1-) function
Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 2540 A Base current

UBase 0.05 - 2000.00 0.05 13.8 kV Base voltage

OpMode Off - UZsIZs - Operating mode selection


UNsINs
UZsIZs
UZsIZs OR
UNsINs
UZsIZs AND
UNsINs
OptimZsNs
3U0> 1 - 100 1 30 %UB Operate level of residual
overvoltag element in % of Ubase
3I0< 1 - 100 1 10 %IB Operate level of residual
undercurrent element in % of Ibase
3U2> 1 - 100 1 30 %UB Operate level of neg seq
overvoltag element in % of Ubase
3I2< 1 - 100 1 10 %IB Operate level of neg seq
undercurrent element in % of Ibase
OpDUDI Off - On - Operation of change
On based function Off/On
DU> 1 - 100 1 60 %UB Operate level of change
in phase voltage in % of Ubase
DI< 1 - 100 1 15 %IB Operate level of change
in phase current in % of Ibase
UPh> 1 - 100 1 70 %UB Operate level of phase
voltage in % of UBase
IPh> 1 - 100 1 10 %IB Operate level of phase
current in % of IBase
SealIn Off - On - Seal in functionality
On Off/On
USealln< 1 - 100 1 70 %UB Operate level of seal-in
phase voltage in % of Ubase
IDLD< 1 - 100 1 5 %IB Operate level for open phase
current detection in % of Ibase
UDLD< 1 - 100 1 60 %UB Operate level for open phase
voltage detection in % of Ubase

17/26
46
Negative sequence current function
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

Basic parameter group settings for the CVGAPC (GF01-) function


Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off / On
On
CurrentInput phase1 - NegSeq - Select current signal
phase2 which will be measured
phase3 inside function
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
IBase 1 - 99999 1 2540 A Base Current
VoltageInput phase1 - -NegSeq - Select voltage signal
phase2 which will be measured
phase3 inside function
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
UBase 0.05 - 2000.00 0.05 13.8 kV Base voltage
OperHarmRestr Off - Off - Operation of 2nd harmonic
On restrain Off / On
l_2nd/l_fund 10.0 - 50.0 1.0 20.0 % Ratio of second to fundamental
current harmonic in %
BlkLevel2nd 10 - 5000 1 5000 %IB Harm analyse disabled above
this current level in % of Ibase
EnRestrainCurr Off - Off - Enable current restrain
On function On / Off
RestrCurrInput PosSeq - PosSeq - Select current signal
NegSeq which will be used for
3*ZeroSeq curr restrain
Max
RestrCurrCoeff 0.00 - 5.00 0.01 0.00 - Restraining current coefficient
RCADir -180 - 180 1 -75 Deg Relay Characteristic
Angle
ROADir 1 - 90 1 75 Deg Relay Operate Angle

18/26
LowVolt_VM 0.0 - 5.0 0.1 0.5 %UB Below this level in % of Ubase
setting ActLowVolt takes over
Parameter Range Step Selected value Unit Description
Operation_OC1 Off - On - Operation OC1 Off / On
On
StartCurr_OC1 2.0 - 5000.0 1 15 %IB Operate current level for
OC1 in % of Ibase
CurveType_OC1 ANSI Ext. inv. - Programmable - Selection of time delay
ANSI Very inv. curve type for OC1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
tDef_OC1 0.00 - 6000.00 0.01 0.00 s Independent (definitive)
time delay of OC1
k_OC1 0.05 - 999.00 0.01 40 - Time multiplier for the
dependent time delay for OC1
tMin_OC1 0.00 - 6000.00 0.01 0.05 s Minimum operate time for
IEC IDMT curves for OC1
VCntrlMode_OC1 Voltage control - Off - Control mode for voltage
Input control controlled OC1 function
Volt/Input control
Off
VDepMode_OC1 Step - Step - Voltage dependent mode
Slope OC1 (step, slope)
VDepFact_OC1 0.02 - 5.00 0.01 1 - Multiplying factor for I
pickup when OC1 is U dependent
ULowLimit_OC1 1.0 - 200.0 0.1 25 %UB Voltage low limit setting
OC1 in % of Ubase
UHighLimit_OC1 1.0 - 200.0 0.1 100 %UB Voltage high limit setting
OC1 in % of Ubase
HarmRestr_OC1 Off - Off - Enable block of OC1 by
On 2nd harmonic restrain
DirMode_OC1 Non-directional - Non-directional - Directional mode of OC1
Forward (nondir, forward,reverse)
Reverse
DirPrinc_OC1 I&U - IcosPhi&U - Measuring on IandU or
IcosPhi&U IcosPhiandU for OC1
ActLowVolt1_VM Non-directional - Block - Low voltage level action
Block for Dir_OC1 (Nodir, Blk,
Memory Mem)

19/26
Advanced parameter group settings for the CVGAPC (GF01-) function
CurrMult_OC1 1.0 - 10.0 0.1 1 - Multiplier for scaling the
current setting value for OC1
ResCrvType_OC1 Instantaneous - Instantaneous - Curv Reset
IEC Reset
ANSI Reset
tResetDef_OC1 0.00 - 6000.00 0.01 0.0 s Reset Time
P_OC1 0.0001 - 10.0000 0.0001 2 - Parameter P for customer
programmable curve for OC1
A_OC1 0.0000 - 999.0000 0.0001 44.444 - Parameter A for customer
programmable curve for OC1
B_OC1 0.0000 - 99.0000 0.0001 0.0000 - Parameter B for customer
programmable curve for OC1
C_OC1 0.0000 - 1.0000 0.0001 0.0000 - Parameter C for customer
programmable curve for OC1
PR_OC1 0.005 - 3.000 0.001 0.5 - Parameter PR for customer
programmable curve for OC1
TR_OC1 0.005 - 600.000 0.001 13.5 - Parameter TR for customer
programmable
CR_OC1 0.1 - 10.0 0.1 1 - Parameter CR for customer
programmable curve for OC1

64S
95% and 100% Stator earth fault protection based on 3rd harmonic
Basic general settings for the STEFPHIZ_59THD (STE1-) function
Parameter Range Step Selected value Unit Description
GenRatedVolt 1.0 - 100.0 0.1 13.8 kV Generator rated (nominal)
phase-to-phase voltage in kV
TVoltType NoVoltage - AllThreePhases - Used connection type for
ResidualVoltage gen. terminal voltage
AllThreePhases transformer
PhaseL1
PhaseL2
PhaseL3
Operation Off - On - Operation Off / On
On
Beta 0.50 - 10.00 0.01 1.00 - Portion of
voltN3rdHarmonic used as bias
CBexists No - No - Defines if generator CB
Yes exist (between Gen & Transformer)
FactorCBopen 1.00 - 10.00 0.01 1.00 - Beta is multiplied by this
factor when CB is open
UN3rdH< 0.5 - 10.0 0.1 2.0 % Pickup 3rd Harm U< protection
(when activated) % of UB/1,732
UT3BlkLevel 0.1 - 10.0 0.1 1.0 % If UT3 is below limit 3rdH
Diff is blocked, in % of UB/1,732
UNFund> 1.0 - 50.0 0.1 5.0 % Pickup fundamental UN>
protect (95% SEF), % of UB/1,732
t3rdH 0.020 - 60.000 0.001 1 s Operation delay of 3rd harm-
based protection (100% SEF) in s
tUNFund 0.020 - 60.000 0.001 0.5 s Operation delay of fundamental
UN> protection (95% SEF) in s

20/26
64R
Rotor earth fault protection

Parameter Range Step Selected value Unit Description


Operation Off - On - Operation Off / On
On
Ibase 1000 A
Ubase 100 kV
CurrentInput Phase1 Verify this in matrix
VoltageInput Phase1 Verify this in matrix
RCA_Dir 0
ROA_Dir 90
LowVolt_VM 5 %
ROA_Dir Block
OperHarmRestr Off
I_2nd/I_fund 20 %
BlkLev2nd 50000 %
EnRestrainCurr Off
RestCurrInput PosSeq
RestCurrCoeff 0
Operation_OC1 On
StartCurr_OC1 3 % Ibase
DirMode_OC1 Forward
CurrMult_OC1 1

21/26
Parameter Range Step Selected value Unit Description
CurveType_OC1 Def
OC1> 2 A
tDefOC1 5 s
k_OC1 0,3
t1Min_OC1 0,3 s
ResCrvType_OC1 Instantaneous
tResetDef_OC1 0.03 s
HarmRestr_OC1 Off
VoltCntrMode_OC1 Off
VoltDepMode_OC1 Slope
VoltDepFactor_OC1 1
ULowLimit_OC1 50
UHighLimit_OC1 100
ActLowVolt1_VM Block
Operation_UC1 Off
Operation_OV1 Off
Operation_UV1 On
StartVolt_UV1 30 %UB
CurveType_UV1 Definite time
CurveSat_UV1 145 %
BlockLowVolt_UV1 5 %
UV1< 20
tDef_UV1 10 s
t1Min_UV1 0.2 s
tResetDef_UV1 0.1 s
ResCrvType_UV1 Instantaneous
EnBlkLowV_UV1 Off
tResetIDMT_UV1 0 s
Operation_UV2 Off

22/26
51/27
Inadvertent-Energizing protection
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

Basic parameter group settings for the CVGAPC (GF01-) function


Operation Off - On - Operation Off / On
On
CurrentInput phase1 - MaxPh - Select current signal
phase2 which will be measured
phase3 inside function
PosSeq
NegSeq
3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
IBase 1 - 99999 1 2540 A Base Current
VoltageInput phase1 - MaxPhPh - Select voltage signal
phase2 which will be measured
phase3 inside function
PosSeq
-NegSeq
-3*ZeroSeq
MaxPh
MinPh
UnbalancePh
phase1-phase2
phase2-phase3
phase3-phase1
MaxPh-Ph
MinPh-Ph
UnbalancePh-Ph
UBase 0.05 - 2000.00 0.05 13.8 kV Base voltage
OperHarmRestr Off - Off - Operation of 2nd harmonic
On restrain Off / On
l_2nd/l_fund 10.0 - 50.0 1.0 20.0 % Ratio of second to fundamental
current harmonic in %
BlkLevel2nd 10 - 5000 1 5000 %IB Harm analyse disabled above
this current level in % of Ibase
EnRestrainCurr Off - Off - Operation of 2nd harmonic
On restrain Off / On
RestrCurrInput PosSeq - PosSeq - Select current signal
NegSeq which will be used for
3*ZeroSeq curr restrain
Max
RestrCurrCoeff 0.00 - 5.00 0.01 0.00 - Restraining current coefficient
RCADir -180 - 180 1 -70 Deg Relay Characteristic
Angle
ROADir 1 - 90 1 70 Deg Relay Operate Angle

23/26
LowVolt_VM 0.0 - 5.0 0.1 0.5 %UB Below this level in % of Ubase
setting ActLowVolt takes over

Setting of parameters for GF Overcurrent 1 function OC1 for functions GF1


The function is used for Accidential energizing instantanous trip
Parameter Range Step Selected value Unit Description
Operation_OC1 Off - On - Operation OC1 Off / On
On
StartCurr_OC1 2.0 - 5000.0 1 10 %IB Operate current level for
OC1 in % of Ibase
CurveType_OC1 ANSI Ext. inv. - IEC Def. Time - Selection of time delay
ANSI Very inv. curve type for OC1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
tDef_OC1 0.00 - 6000.00 0.01 0.0 s Independent (definitive)
time delay of OC1
k_OC1 0.05 - 999.00 0.01 0.30 - Time multiplier for the
dependent time delay for OC1
tMin_OC1 0.00 - 6000.00 0.01 0.3 s Minimum operate time for
IEC IDMT curves for OC1
VCntrlMode_OC1 Voltage control - Off - Control mode for voltage
Input control controlled OC1 function
Volt/Input control
Off
VoltDepMode_OC1 Step - Slope - Voltage dependent mode
Slope OC1 (step, slope)
VDepFact_OC1 0.02 - 5.00 0.01 1.00 - Multiplying factor for I
pickup when OC1 is U dependent
ULowLimit_OC1 1.0 - 200.0 0.1 50.0 %UB Voltage low limit setting
OC1 in % of Ubase
UHighLimit_OC1 1.0 - 200.0 0.1 100.0 %UB Voltage high limit setting
OC1 in % of Ubase
HarmRestr_OC1 Off - Off - Enable block of OC1 by
On 2nd harmonic restrain
DirMode_OC1 Non-directional - Non-directional - Directional mode of OC1
Forward (nondir, forward,reverse)
Reverse
DirPrinc_OC1 I&U - IcosPhi&U - Measuring on IandU or
IcosPhi&U IcosPhiandU for OC1
ActLowVolt1_VM Non-directional - Block - Low voltage level action
Block for Dir_OC1 (Nodir, Blk, Mem)
Memory
CurrMult_OC1 1.0 - 10.0 0.1 1 - Multiplier for scaling the
current setting value for OC1
ResCrvType_OC1 Instantaneous - Instantaneous - Selection of reset curve
IEC Reset type for OC1
ANSI reset

24/26
tResetDef_OC1 0.00 - 6000.00 0.01 0.00 s Reset time delay used in
IEC Definite Time curve OC1

Setting of parameters for GF Undervoltage 1 function UV1 used to Enable 50AE function
Parameter Range Step Selected value Unit Description
Operation_UV1 Off - On - Operation UV1 Off / On
On
StartVolt_UV1 2.0 - 150.0 0.1 50 %UB Operate undervoltage
level for UV1 in % of Ubase
CurveType_UV1 Definite time - Definite time - Selection of time delay
Inverse curve A curve type for UV1
Inverse curve B
Prog. inv. curve
tDef_UV1 0.00 - 6000.00 0.01 1.00 s Operate time delay in sec
for definite time use of UV1
tMin_UV1 0.00 - 6000.00 0.01 0.1 s Minimum operate time for
IDMT curves for UV1
k_UV1 0.05 - 999.00 0.01 0.30 - Time multiplier for the
dependent time delay for UV1
EnBlkLowV_UV1 Off - Off - Enable internal low voltage
On level blocking for UV1
BlkLowVolt_UV1 1 0.0 - 5.0 0.1 20 %UB Internal low voltage
block level for UV1 in % of Ubase
ResCrvType_UV1 Instantaneous - Instantaneous - Selection of reset curve
Frozen timer type for UV1
Linearly decreased
tResetDef_UV1 0.00 - 6000.00 0.01 0.20 s Reset time delay in sec
for definite time use of UV1
tResetIDMT_UV1 0.00 - 6000.00 0.01 0.00 s Reset time delay in sec
for IDMT curves for UV1

Setting of parameters for GF Overvoltage 1 function OV1 used to Disable 50AE function
Parameter Range Step Selected value Unit Description
Operation_OV1 Off - Off - Operation OV1 Off / On
On
StartVolt_OV1 2.0 - 200.0 0.1 80 %UB Operate voltage level for
OV1 in % of Ubase
CurveType_OV1 Definite time - Definite time - Selection of time delay
Inverse curve A curve type for OV1
Inverse curve B
Prog. inv. curve
tDef_OV1 0.00 - 6000.00 0.01 0.30 s Operate time delay in sec
for definite time use of OV1
tMin_OV1 0.00 - 6000.00 0.01 0.3 s Minimum operate time for
IDMT curves for OV1
k_OV1 0.05 - 999.00 0.01 0.30 - Time multiplier for the
dependent time delay for OV1
ResCrvType_OV1 Instantaneous - Instantaneous - Selection of reset curve
Frozen timer type for OV1
Linearly decreased
tResetDef_OV1 0.00 - 6000.00 0.01 0.020 s Reset time delay in sec
for definite time use of OV1
tResetIDMT_OV1 0.00 - 6000.00 0.01 0.00 s Reset time delay in sec
for IDMT curves for OV1

25/26
49
Thermal overload protection, two time constants (PTTR, 49)
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite

Basic parameter group settings for the TRPTTR_49 (TTR1-) function


Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 2540 A Base Current
Iref 10.0 - 1000.0 1 100.0 %IB Reference current in % of
IBASE
IRefMult 0.01 - 10.00 0.01 1.00 - Multiplication Factor for
reference current
IBase1 30.0 - 250.0 1 100.0 %IB Base current,IBase1 without
Cooling input in % of IBASE
IBase12 30.0 - 250.0 1 100.0 %IB Base current,IBase2 with
Cooling input ON in % of IBASE
Tau1 1.0 - 500.0 1.0 60.0 Min Time constant without
cooling input in min, with IBase1
Tau2 1.0 - 500.0 1.0 60.0 Min Time constant with cooling
input in min, with IBase2
IHighTau1 30.0 - 250.0 1.0 100 %IB1 Current Sett, in % of IBase1
for rescaling TC1 by TC1-IHIGH
Tau1High 5 - 2000 1 100 %tC1 Multiplier in % to TC1
when current is > IHIGH-TC1
ILowTau1 30.0 - 250.0 1 100.0 %IB1 Current Set, in % of IBase1
for rescaling TC1 by TC1-ILOW
Tau1Low 5 - 2000 1 100 %tC1 Multiplier in % to TC1
when current is < ILOW-TC1
IHighTau2 30.0 - 250.0 1 100.0 %IB2 Current Set, in % of
IBase2 for rescaling TC2
Tau2High 5 - 2000 1 100.0 %tC2 Multiplier in % to TC2
when current is >IHIGH-TC2
ILowTau2 30.0 - 250.0 1 100 %IB2 Current Set, in % of IBase2
for rescaling TC2 by TC2-ILOW
Tau2Low 5 - 2000 1 100 %tC2 Multiplier in % to TC2
when current is < ILOW-TC2
ITrip 50.0 - 250.0 1 110.0 %IBx Steady state operate current
level in % of IBasex
Alarm1 50.0 - 99.0 1 80 %Itr First alarm level in % of
heat content trip value
Alarm2 50.0 - 99.0 1 90 %Itr Second alarm level in %
of heat content trip value
ResLo 10.0 - 95.0 1 60 %Itr Lockout reset level in %
of heat content trip value
ThetaInit 0.0 - 95.0 1 50.0 % Initial Heat content, in %
of heat content trip value
Warning 1.0 - 500.0 0.1 30.0 Min Time setting, below
which warning would be set (in min)
tPulse 0.01 - 0.30 0.01 0.10 s Length of the pulse for
trip signal (in msec).

26/26