ACYG04 13.8KV Secundaria REG670
ACYG04 13.8KV Secundaria REG670
nº : GT/DEL2 - 076
ANDE
ORDENES DE AJUSTE REV nº : 000
Interno : GT/DEL2/007/2011
PANEL PROT. SECUNDARIA : G-04 FABRICANTE: EQUIPO :
FUNCION/ES : 87G-87T-87N-50BF-51N ABB G-04
60FL-51-67-64R-21-24-32-59-40-50AE-46-49-59THD-87SP
MODELO : LOCALIZACIÓN: CIRCUITO:
REG 670 Sala de relés - CH-ACY G-04 - (60,7 MVA)
RTC(A) : RTP(V) :
---
FECHA : 11/07/2011 OBSERVACIONES :
Generador G-04
Valores nominales
Potencia 60,7 MVA
Tensión 13.8 kV
cos Ø 0.8
Corriente nominal 2540 [A]
Frecuencia 50 Hz
Xq" 0.22 p.u.
Xq' 0.5 p.u.
Xq 0.6 p.u.
Xd 0.86 p.u.
Xd' 0.23 p.u.
Xd'' 0.16 p.u.
X2 0.19 p.u.
X0 0.07 p.u. Base = 60.7 MVA
Valores nominales
Potencia 75 MVA
Tensión 220 - 13.8 kV
Conexionado YNd11
Impedancia 0.112 p.u. Base = 75 MVA
1/26
Diagrama Unifilar de la posición
1000/5
800/5
VT ratio = 13.8/0.11 kV
3000/5
1500/5 (87SP)
3000/5
2/26
Signal matrix for analog inputs (SMAI)
Este grupo define las entradas analógicas de corriente y tensión utilizadas por el relé
deben ser configurados a traves deL Application Configuration (CAP531) del programa PCM600, conforme proyecto
Basic general settings for the ANALOGIN12I (TA40-) function (Depende del modelo de placa TRM, cantidad de canales)
Parameter Range Step Default Unit Description
FromObject ToObject= towards protected object,
CTStarPoint1 ToObject - ToObject - FromObject=the opposite
Conforme a lo indicado en la siguiente figura colocar los CTStarPoint (de cada TC a ser utilizado, ver application manual REG670):
3/26
Basic general settings for the ANALOGIN6I6U (TD40-) function
Parameter Range Step Selected value Unit Description
VTsec7 0.001 - 999.999 0.001 110 V Rated VT secondary voltage
VTprim7 0.05 - 2000.00 0.05 13.8 kV Rated VT primary voltage
4/26
HarmDistLimit 5.0 - 100.0 0.1 10.0 % (Total) relative harmonic distorsion
limit, percent
TempIdMin 1.0 - 5.0 0.1 2.0 IdMin Temp. Id pickup wheninput raise
PickUp=1, multiple of IdMin
AddTripDelay 0.000 - 60.000 0.001 0.100 s Additional trip delay,when input
raisePickUp=1
OperDCBiasing Off, On - Off - Operation DC biasing On/ Off
TempIdMin 1.0 - 5.0 0.1 2.0 IdMin Temp. Id pickup wheninput raise
PickUp=1, multiple of IdMin
AddTripDelay 0.000 - 60.000 0.001 0.100 s Additional trip delay,when input
raisePickUp=1
5/26
OperDCBiasing Off, On - Off - Operation DC biasing On/ Off
87T
CT input channels used for the LV side CTs
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - ToObject - FromObject=the opposite
6/26
Basic parameter group settings for the T2WPDIF_87T (T2D1-) function
Parameter Range Step Selected value Unit Description
Off
Operation ON - ON - Operation Off / On
Off Operation mode for
SOTFMode ON - Off - switch onto fault
Time delay for diff
tAlarmDelay 0.000 - 60.000 0.001 10 s currents alarm level
IDiffAlarm IDiffAlarm 5 - 100 1 20 %IB Diff. current alarm pickup
level set as % of W1 base current
IdMin 0.10 - 0.60 0.01 0.3 IB Sust. dif. cur. alarm; multiple of
Winding 1 rated current
EndSection1 0.20 - 1.50 0.01 1.25 IB End of section 1, multiple
of Winding 1 rated current
EndSection2 1.00 - 10.00 0.01 3.00 IB End of section 2, multiple
of Winding 1 rated current
SlopeSection2 10.0 - 50.0 0.1 40.0 % Slope in section 2 of
operate-restrain characteristic, in%
SlopeSection3 30.0 - 100.0 0.1 80.0 % Slope in section 3 of
operate-restrain characteristic, in%
IdUnre 1.00 - 50.00 0.01 12.00 IB Unrestr. prot. limit, multiple of
Winding 1 rated current
I2/I1Ratio 5.0 - 100.0 1.0 15.0 % Max. ratio of 2nd harm. to
fundamental harm dif. curr. in %
I5/I1Ratio 5.0 - 100.0 1.0 25.0 % Max. ratio of 5th harm. to
fundamental harm dif. curr. in %
CrossBlockEn Off - ON - Operation Off/On for cross-block
ON logic between phases
NegSeqDiffEn Off - ON - Operation Off/On for neg.
ON seq. differential protections
IMinNegSeq 0.02 - 0.20 0.01 0.04 IB IB Neg. seq. curr. must be
higher than this level to be used
NegSeqROA 30.0 - 120.0 0.1 60.0 Deg Operate Angle for int. /
ext. neg. seq. fault discriminator
OpenCTEnable Off - ON - Open CT detection feature.
ON Open CTEnable Off/On
tOCTAlarmDelay 0.100 - 10.000 0.001 3 s Open CT: time in s to
alarm after an open CT is detected
tOCTResetDelay 0.100 - 10.000 0.001 0.250 s Reset delay in s. After
delay, diff. function is activated
tOCTUnrstDelay 0.10 - 6000.00 0.01 10.00 s Unrestrained diff. protection
blocked after this delay, in s
87N
CT input channels used for the Neutral HV side CTs
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 800 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite
7/26
Basic parameter group settings for the REFPDIF_87N (REF1-) function
Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off/On
On
IBase 1 - 99999 1 197 A Base current
21
CT input channels
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite
DirMode Off-Offset-Forward-Reverse
- Offset - Direction mode
-
LoadEnchMode Off - Off - Load enchroachment
On mode Off/On
ReachMode OverReach - OverReach - Reach mode
Underreach Over/Underreach
OpModePE Off _ Off - Operation mode Off / On
On of Phase-Earth loops
ZPE 0.005 - 3000.000 0.001 30000 ohm/p Positive sequence impedance
setting for Phase-Earth loop
ZAngPE 10 - 90 1 80 Deg Angle for positive sequence line
impedance or Phase-Earth loop
KN 0.00 – 3.00 0.01 0.80 - Magnitud of earth return
compensation factor KN
KNAng -180 - 180 1 -15 Deg Angle for earth return
compensation factor KN
ZRevPE 0.005 - 3000.000 0.001 30000 ohm/p Reverse reach of the phase
to earth loop(magnitude)
8/26
tPE 0.000 - 60.000 0.001 0.000 s Delay time for operation
of phase to earth elements
40
Basic general settings for the LEXPDIS_40 (UEX1-) function
Parameter Range Step Selected value Unit Description
IBase 0.1 - 99999.9 0.1 2540 A Base Current (primary phase
current in Amperes)
UBase 0.1 - 9999.9 0.1 13,8 kV Base Voltage (primary phase
to-phase voltage in kV)
MeasureMode PosSeq - PosSeq - Measuring mode (Pos-Seq,
L1L2 L1L2, L2L3, L3L1)
L2L3
L3L1
9/26
Advanced general settings for the LEXPDIS_40 (UEX1-) function
Parameter Range Step Selected value Unit Description
invertCTcurren No - No - Operation Off/On for additional
Yes directional criterion
51 / 67
CT input channels used for the 13,8 kV side CTs
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite
10/26
Reserved
Programmable
RI type
RD type
I1> 1 - 2500 1 140 %IB Phase current operate
level for step1 in % of Ibase
t1 0.000 - 60.000 0.001 0.000 s Definitive time delay of step 1
51N
CT input channels used for the HV (Neutral) side CTs -transformer.
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 800 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite
11/26
Parameter Range Step Selected value Unit Description
UseStartValue IN1> - IN4> - Current level blk at parallel
IN2> transf (step1, 2, 3 or 4)
IN3>
IN4>
SOTF Off - Off - SOTF operation mode
SOTF (Off/SOTF/Undertime/
UnderTime SOTF+undertime)
SOTF+UnderTime
ActivationSOTF Open - Open - Select signal that shall
Closed activate SOTF
CloseCommand
StepForSOTF Step 2 - Step 2 - Selection of step used for
Step 3 SOTF
HarmResSOTF Off - Off - Enable harmonic restrain
On function in SOTF
tSOTF 0.000 - 60.000 0.001 0.200 s Time delay for SOTF
12/26
50BF
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 1000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - ToObject - FromObject=the opposite
13/26
32
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite
14/26
IAmpComp100 -10.000 - 10.000 0.001 0.000 % Amplitude factor to calibrate
current at 100% of Ir
59
Parameter Range Step Selected value Unit Description
ConnType PhG - PhG - TBD
PhPh
PhG RMS
PhPh RMS
15/26
U2> 1 - 200 1 140 %UB Voltage setting/start val
(DT & IDMT) in % of
UBase, step 2
t2 0.000 - 60.000 0.001 0,5 s Definitive time delay of step 2
24
Overexcitation protection
Basic general settings for the OEXPVPH_24 (OEX1-) function
Parameter Range Step Selected value Unit Description
MeasuredU PosSeq - PosSeq - Selection of measured
L1L2 voltage
L2L3
L3L1
MeasuredI L1L2 - PosSeq - Selection of measured
L2L3 current
L3L1
PosSeq
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 2540 A Base current (rated
phase current) in A
UBase 0.05 - 2000.00 0.05 13.8 kV Base voltage (main voltage)
in kV
V/Hz> 100.0 - 180.0 0.1 110.0 %UB/f Operate level of V/Hz at no load %
and rated freq in of (Ubase/frated)
V/Hz>> 100.0 - 200.0 0.1 140.0 %UB/f High level of V/Hz above which
tMin is used,in% of (Ubase/frated)
XLeak 0.000 - 200.000 0.001 0,14 ohm Winding leakage reactance
in primary ohms
TrPulse 0.000 - 60.000 0.001 0.100 s Length of the pulse for
trip signal (in sec)
tMin 0.000 - 60.000 0.001 1 s Minimum trip delay for
V/Hz inverse curve, in sec
tMax 0.00 - 9000.00 0.01 1800.00 s Maximum trip delay for
V/Hz inverse curve, in sec
tCooling 0.10 - 9000.00 0.01 2700 s Transformer magnetic
core cooling time const, in sec
CurveType IEEE - Tailor made - Inverse time curve selection,
Tailor made IEEE/Tailor made
kForIEEE 1 - 60 1 3 - Time multiplier for IEEE
inverse type curve
AlarmLevel 50.0 - 120.0 0.1 98 % Alarm operate level as %
of operate level
tAlarm 0.00 - 9000.00 0.01 5.00 s Alarm time delay, in sec
16/26
t4Tailor 0.00 - 9000.00 0.01 15 s Time delay t4 (longest)
for tailor made curve, in sec
t5Tailor 0.00 - 9000.00 0.01 6 s Time delay t5 (longest)
for tailor made curve, in sec
t6Tailor 0.00 - 9000.00 0.01 3 s Time delay t6 (longest)
for tailor made curve, in sec
60FL
Fuse failure supervision
Basic parameter group settings for the SDDRFUF (FSD1-) function
Parameter Range Step Selected value Unit Description
Operation Off - On - Operation Off / On
On
IBase 1 - 99999 1 2540 A Base current
17/26
46
Negative sequence current function
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite
18/26
LowVolt_VM 0.0 - 5.0 0.1 0.5 %UB Below this level in % of Ubase
setting ActLowVolt takes over
Parameter Range Step Selected value Unit Description
Operation_OC1 Off - On - Operation OC1 Off / On
On
StartCurr_OC1 2.0 - 5000.0 1 15 %IB Operate current level for
OC1 in % of Ibase
CurveType_OC1 ANSI Ext. inv. - Programmable - Selection of time delay
ANSI Very inv. curve type for OC1
ANSI Norm. inv.
ANSI Mod. inv.
ANSI Def. Time
L.T.E. inv.
L.T.V. inv.
L.T. inv.
IEC Norm. inv.
IEC Very inv.
IEC inv.
IEC Ext. inv.
IEC S.T. inv.
IEC L.T. inv.
IEC Def. Time
Programmable
RI type
RD type
tDef_OC1 0.00 - 6000.00 0.01 0.00 s Independent (definitive)
time delay of OC1
k_OC1 0.05 - 999.00 0.01 40 - Time multiplier for the
dependent time delay for OC1
tMin_OC1 0.00 - 6000.00 0.01 0.05 s Minimum operate time for
IEC IDMT curves for OC1
VCntrlMode_OC1 Voltage control - Off - Control mode for voltage
Input control controlled OC1 function
Volt/Input control
Off
VDepMode_OC1 Step - Step - Voltage dependent mode
Slope OC1 (step, slope)
VDepFact_OC1 0.02 - 5.00 0.01 1 - Multiplying factor for I
pickup when OC1 is U dependent
ULowLimit_OC1 1.0 - 200.0 0.1 25 %UB Voltage low limit setting
OC1 in % of Ubase
UHighLimit_OC1 1.0 - 200.0 0.1 100 %UB Voltage high limit setting
OC1 in % of Ubase
HarmRestr_OC1 Off - Off - Enable block of OC1 by
On 2nd harmonic restrain
DirMode_OC1 Non-directional - Non-directional - Directional mode of OC1
Forward (nondir, forward,reverse)
Reverse
DirPrinc_OC1 I&U - IcosPhi&U - Measuring on IandU or
IcosPhi&U IcosPhiandU for OC1
ActLowVolt1_VM Non-directional - Block - Low voltage level action
Block for Dir_OC1 (Nodir, Blk,
Memory Mem)
19/26
Advanced parameter group settings for the CVGAPC (GF01-) function
CurrMult_OC1 1.0 - 10.0 0.1 1 - Multiplier for scaling the
current setting value for OC1
ResCrvType_OC1 Instantaneous - Instantaneous - Curv Reset
IEC Reset
ANSI Reset
tResetDef_OC1 0.00 - 6000.00 0.01 0.0 s Reset Time
P_OC1 0.0001 - 10.0000 0.0001 2 - Parameter P for customer
programmable curve for OC1
A_OC1 0.0000 - 999.0000 0.0001 44.444 - Parameter A for customer
programmable curve for OC1
B_OC1 0.0000 - 99.0000 0.0001 0.0000 - Parameter B for customer
programmable curve for OC1
C_OC1 0.0000 - 1.0000 0.0001 0.0000 - Parameter C for customer
programmable curve for OC1
PR_OC1 0.005 - 3.000 0.001 0.5 - Parameter PR for customer
programmable curve for OC1
TR_OC1 0.005 - 600.000 0.001 13.5 - Parameter TR for customer
programmable
CR_OC1 0.1 - 10.0 0.1 1 - Parameter CR for customer
programmable curve for OC1
64S
95% and 100% Stator earth fault protection based on 3rd harmonic
Basic general settings for the STEFPHIZ_59THD (STE1-) function
Parameter Range Step Selected value Unit Description
GenRatedVolt 1.0 - 100.0 0.1 13.8 kV Generator rated (nominal)
phase-to-phase voltage in kV
TVoltType NoVoltage - AllThreePhases - Used connection type for
ResidualVoltage gen. terminal voltage
AllThreePhases transformer
PhaseL1
PhaseL2
PhaseL3
Operation Off - On - Operation Off / On
On
Beta 0.50 - 10.00 0.01 1.00 - Portion of
voltN3rdHarmonic used as bias
CBexists No - No - Defines if generator CB
Yes exist (between Gen & Transformer)
FactorCBopen 1.00 - 10.00 0.01 1.00 - Beta is multiplied by this
factor when CB is open
UN3rdH< 0.5 - 10.0 0.1 2.0 % Pickup 3rd Harm U< protection
(when activated) % of UB/1,732
UT3BlkLevel 0.1 - 10.0 0.1 1.0 % If UT3 is below limit 3rdH
Diff is blocked, in % of UB/1,732
UNFund> 1.0 - 50.0 0.1 5.0 % Pickup fundamental UN>
protect (95% SEF), % of UB/1,732
t3rdH 0.020 - 60.000 0.001 1 s Operation delay of 3rd harm-
based protection (100% SEF) in s
tUNFund 0.020 - 60.000 0.001 0.5 s Operation delay of fundamental
UN> protection (95% SEF) in s
20/26
64R
Rotor earth fault protection
21/26
Parameter Range Step Selected value Unit Description
CurveType_OC1 Def
OC1> 2 A
tDefOC1 5 s
k_OC1 0,3
t1Min_OC1 0,3 s
ResCrvType_OC1 Instantaneous
tResetDef_OC1 0.03 s
HarmRestr_OC1 Off
VoltCntrMode_OC1 Off
VoltDepMode_OC1 Slope
VoltDepFactor_OC1 1
ULowLimit_OC1 50
UHighLimit_OC1 100
ActLowVolt1_VM Block
Operation_UC1 Off
Operation_OV1 Off
Operation_UV1 On
StartVolt_UV1 30 %UB
CurveType_UV1 Definite time
CurveSat_UV1 145 %
BlockLowVolt_UV1 5 %
UV1< 20
tDef_UV1 10 s
t1Min_UV1 0.2 s
tResetDef_UV1 0.1 s
ResCrvType_UV1 Instantaneous
EnBlkLowV_UV1 Off
tResetIDMT_UV1 0 s
Operation_UV2 Off
22/26
51/27
Inadvertent-Energizing protection
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite
23/26
LowVolt_VM 0.0 - 5.0 0.1 0.5 %UB Below this level in % of Ubase
setting ActLowVolt takes over
24/26
tResetDef_OC1 0.00 - 6000.00 0.01 0.00 s Reset time delay used in
IEC Definite Time curve OC1
Setting of parameters for GF Undervoltage 1 function UV1 used to Enable 50AE function
Parameter Range Step Selected value Unit Description
Operation_UV1 Off - On - Operation UV1 Off / On
On
StartVolt_UV1 2.0 - 150.0 0.1 50 %UB Operate undervoltage
level for UV1 in % of Ubase
CurveType_UV1 Definite time - Definite time - Selection of time delay
Inverse curve A curve type for UV1
Inverse curve B
Prog. inv. curve
tDef_UV1 0.00 - 6000.00 0.01 1.00 s Operate time delay in sec
for definite time use of UV1
tMin_UV1 0.00 - 6000.00 0.01 0.1 s Minimum operate time for
IDMT curves for UV1
k_UV1 0.05 - 999.00 0.01 0.30 - Time multiplier for the
dependent time delay for UV1
EnBlkLowV_UV1 Off - Off - Enable internal low voltage
On level blocking for UV1
BlkLowVolt_UV1 1 0.0 - 5.0 0.1 20 %UB Internal low voltage
block level for UV1 in % of Ubase
ResCrvType_UV1 Instantaneous - Instantaneous - Selection of reset curve
Frozen timer type for UV1
Linearly decreased
tResetDef_UV1 0.00 - 6000.00 0.01 0.20 s Reset time delay in sec
for definite time use of UV1
tResetIDMT_UV1 0.00 - 6000.00 0.01 0.00 s Reset time delay in sec
for IDMT curves for UV1
Setting of parameters for GF Overvoltage 1 function OV1 used to Disable 50AE function
Parameter Range Step Selected value Unit Description
Operation_OV1 Off - Off - Operation OV1 Off / On
On
StartVolt_OV1 2.0 - 200.0 0.1 80 %UB Operate voltage level for
OV1 in % of Ubase
CurveType_OV1 Definite time - Definite time - Selection of time delay
Inverse curve A curve type for OV1
Inverse curve B
Prog. inv. curve
tDef_OV1 0.00 - 6000.00 0.01 0.30 s Operate time delay in sec
for definite time use of OV1
tMin_OV1 0.00 - 6000.00 0.01 0.3 s Minimum operate time for
IDMT curves for OV1
k_OV1 0.05 - 999.00 0.01 0.30 - Time multiplier for the
dependent time delay for OV1
ResCrvType_OV1 Instantaneous - Instantaneous - Selection of reset curve
Frozen timer type for OV1
Linearly decreased
tResetDef_OV1 0.00 - 6000.00 0.01 0.020 s Reset time delay in sec
for definite time use of OV1
tResetIDMT_OV1 0.00 - 6000.00 0.01 0.00 s Reset time delay in sec
for IDMT curves for OV1
25/26
49
Thermal overload protection, two time constants (PTTR, 49)
Parameter Range Step Selected value Unit Description
Ctsec 1 - 10 1 5 A Rated CT secondary current
Ctprim 1 - 99999 1 3000 A Rated CT primary current
FromObject ToObject= towards protected object,
CTStarPoint ToObject - FromObject - FromObject=the opposite
26/26