0% found this document useful (0 votes)
148 views62 pages

Technical - Manual - Midea - Aqua Thermal - MC - SUxxx - RN8L - B

The document provides engineering data for Midea's Aqua thermal air-to-water heat pump system, detailing its general information, product lineup, and installation settings. It includes specifications for various models, system design procedures, and performance characteristics. The Aqua thermal system is designed for both space heating and cooling, utilizing an auxiliary electric heater for cold weather and backup functionality.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
148 views62 pages

Technical - Manual - Midea - Aqua Thermal - MC - SUxxx - RN8L - B

The document provides engineering data for Midea's Aqua thermal air-to-water heat pump system, detailing its general information, product lineup, and installation settings. It includes specifications for various models, system design procedures, and performance characteristics. The Aqua thermal system is designed for both space heating and cooling, utilizing an auxiliary electric heater for cold weather and backup functionality.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 62

R32

Midea Building Technologies Division

Engineering Data
Aqua thermal

MBT Confidential
Aqua thermal

CONTENTS

Part 1 General Information ............................................................................ 3

Part 2 Engineering Data ............................................................................... 11

Part 3 Installation and Field Settings.......................................................... 45

CONTENTS

1
MBT Confidential
Midea Aqua thermal Engineering Data Book

2
Aqua thermal

MBT Confidential
1 Aqua thermal

Part 1
General Information
1 System introduction ................................................................................... 4

2 Product lineup............................................................................................ 7

3 Nomenclature ............................................................................................ 7

4 System Design And Unit Selection .............................................................. 7

Part 1 - General Information

3
MBT Confidential
Aqua thermal
1 System introduction
1.1 System Schematic
Aqua thermal is an integrated air-to-water space heating and space cooling heat pump system. The outdoor heat pump
system extracts heat from the outdoor air and transfers this heat through refrigerant piping to the plate heat exchanger in the
hydronic system. The heated water in the hydronic system circulates to low temperature heat emitters (floor heating loops or
low temperature radiators) to provide space heating. The 4-way valve in the outdoor unit can reverse the refrigerant cycle so
that the hydronic system can provide chilled water for cooling using fan coil units.

The heating capacity of heat pumps decreases with ambient temperature. Aqua thermal is reserved an auxiliary electric
heater control port to provide additional heating capacity for use during extremely cold weather when the heat pump capacity is
insufficient. The auxiliary electric heater also serves as a backup in case of heat pump malfunction and for anti-freeze protection
of the outside water piping in winter.

1.2 Typical Applications


Midea Aqua thermal Engineering Data Book

1.2.1 Space Heating Through Floor Heating Loops

Legend

Stop valve Pressure gauge Flexible joint Gate valve Automatic discharge valve

Y-shaped filter Thermometer Circulating pump Check valve

4
MBT Confidential
1 Aqua thermal
1.2.2 Space Cooling and Heating through Fan Coil Unit

Part 1 - General Information


Legend

Stop valve Pressure gauge Flexible joint Gate valve Automatic discharge valve

Y-shaped filter Thermometer Circulating pump Check valve

5
MBT Confidential
Aqua thermal
1.2.3 Space Heating Through Floor Heating Loops and Space Cooling Through Fan Coil Unit
Midea Aqua thermal Engineering Data Book

Legend

Stop valve Pressure gauge Flexible joint Gate valve Automatic discharge valve

Y-shaped filter Thermometer Circulating pump Check valve

Note:
In space cooling mode, the 2-way valve on the floor heating branch circuit is closed to prevent cold water entering the floor heating loops.

6
MBT Confidential
1 Aqua thermal
2 Product lineup
MC-SU75-RN8L-B MC-SU90-RN8L-B MC-SU140-RN8L-B MC-SU180-RN8L-B
Model
MC-SU75M-RN8L-B MC-SU90M-RN8L-B MC-SU140M-RN8L-B MC-SU180M-RN8L-B
Power
380-415V/3Ph/50Hz 380-415V/3Ph/50Hz 380-415V/3Ph/50Hz 380-415V/3Ph/50Hz
supply

Appearance

3 Nomenclature
M C - S U 75 M - R N8 - B

Part 1 - General Information


Design code

Refrigerant: R32

Power supply: 380-415V/3Ph/50Hz

Hydro module code

Rated heating capacity (kW)

Special function code


U: DC inverter compressor

Series code

C: Chiller

M: Midea

7
MBT Confidential
Aqua thermal

4 System Design and Unit Selection


4.1 Selection Procedure
Step 1: Total heat load calculation

Calculate conditioned surface area


Select the heat emitters (type, quantity, water temperature and heat load)

Step 2: System configuration

Decide whether to enable or disable auxiliary electric heater

Step 3: Selection of outdoor units


Midea Aqua thermal Engineering Data Book

Determine required total heat load on outdoor units


Set capacity safety factor
Select power supply

Provisionally select Aqua thermal Series unit capacity1 based on nominal


capacity

Correct capacity of the outdoor units for the following items:


Outdoor air temperature / Outdoor humidity / Water outlet temperature2 /
Altitude / Anti-freeze type

Is corrected Aqua thermal capacity ≥ Required total heat load on outdoor units3

Yes No

Aqua thermal system Select a larger model or enable


selection is complete auxiliary electric heater operation

Notes:
1. Up to 16 units (8 units for MC-SU180-RN8L-B) can be connected together, giving a system cooling/heating capacity range from 75kW to 2240kW.
2. If the required water temperatures of the heat emitters are not all the same, the Aqua thermal’s outlet water temperature setting should be set at the
highest of the heat emitter required water temperatures. If the water outlet design temperature falls between two temperatures listed in the outdoor
unit's capacity table, calculate the corrected capacity by interpolation.
3. Select Aqua thermal which satisfies both total heating and cooling load requirements.

8
MBT Confidential
1 Aqua thermal
4.2 Modular Chiller Leaving Water Temperature (LWT) Selection
The recommended design LTW ranges for different types of heat emitter are:
 For floor heating: 30 to 35⁰C
 For fan coil units: 30 to 45⁰C
 For low temperature radiators: 40 to 50⁰C

4.3 Optimizing System Design


To get the most comfort with the lowest energy consumption with Aqua thermal, it is important to take account of the
following considerations:
 Choose heat emitters that allow the heat pump system to operate at as low a hot water temperature as possible
whilst still providing sufficient heating.

Part 1 - General Information

9
MBT Confidential
Midea Aqua thermal Engineering Data Book

10
Aqua thermal

MBT Confidential
Aqua thermal

Part 2
Engineering Data
1 Specifications ........................................................................................... 12

2 Electrical Characteristics ........................................................................... 14

3 Dimensions and Center of Gravity ............................................................ 15

4 Operating Limits ....................................................................................... 17

5 Capacity Tables......................................................................................... 18

6 Performance Adjustment Factors ............................................................. 34

Part 2 - Engineering Data


7 Hydronic Performance.............................................................................. 36

8 Octave Band Levels .................................................................................. 40

11
MBT Confidential
Aqua thermal
1 Specifications
Model name MC-SU75-RN8L-B MC-SU90-RN8L-B MC-SU140-RN8L-B MC-SU180-RN8L-B
Power supply V/Ph/Hz 380~415/3/50 380~415/3/50 380~415/3/50 380~415/3/50
Capacity kW 70 82 130 164
Cooling 1 Rated input kW 26.8 27.8 50.5 56
EER 2.61 2.95 2.57 2.93
Capacity kW 75 90 138 180
Heating2 Rated input kW 23.7 28.1 44.5 57
COP 3.16 3.2 3.1 3.16
Type Finned tube Finned tube Finned tube Finned tube
Fan motor type DC motor DC motor DC motor DC motor
Air side heat
Fan motor output W 920 920 1500 920
exchanger
Fan motor quantity 2 2 2 4
Air flow rate m3/h 28500 35000 50000 70000
Midea Aqua thermal Engineering Data Book

Type Plate Plate Plate Plate


Water side Volume L 5.17 7.05 11.1 6.96×2
heat Rated water flow m3/h 12.04 15 22.36 28.2
exchanger Water flow range m3/h 8.0~15.5 10.2 ~ 18 15.6~28.5 20~36.1
Water pressure drop kPa 65 75 65 96
Refrigerant type R32 R32 R32 R32
Refrigerant
Refrigerant charge3 kg 9 16 (11.5+4.5) 15.5(11.5+4) 16 (5.5+10.5)*2
system
Throttle type EXV EXV EXV EXV
Sound power level4 dB 86 83 92 92
Sound pressure level(1m)5 dB(A) 69 65 73 72
Net dimensions (W×H×D) mm 2000×1770×960 2220×2315×1135 2220×2300×1135 2752×2413×2220
Packed dimensions (W×H×D) mm 2085×1890×1030 2250×2445×1180 2250×2425×1180 2810×2446×2245
Net/Gross weight kg 440/455 635/660 670/690 1400/1420
Water pipe connections mm DN50 DN50 DN65 DN80
Water pressure range MPa 0.05 ~ 1.0 0.05 ~ 1.0 0.05 ~ 1.0 0.05 ~ 1.0
Water flow switch action flow m3/h 8 10 15.6 20
Vent Valve max working pressure Mpa 1 1 1 1
Safety valve action pressure Mpa 0.6 0.6 0.6 0.6
Controller KJRM-120H2/BMWK KJRM-120H2/BMWK KJRM-120H2/BMWK KJRM-120H2/BMWK

Cooling °C -10 to 48 -10 to 48 -10 to 48 -10 to 48


Operating
temperature
Heating °C -20 to 43 -20 to 43 -20 to 43 -20 to 43

Water Cooling °C 0 to 20 0 to 20 0 to 20 0 to 20
outlet
temperature Heating °C 25 to 54 25 to 54 25 to 54 25 to 54

12
MBT Confidential
Aqua thermal
Model name MC-SU75M-RN8L-B MC-SU90M-RN8L-B MC-SU140M-RN8L-B MC-SU180M-RN8L-B
Power supply V/Ph/Hz 380~415/3/50 380~415/3/50 380~415/3/50 380~415/3/50
Capacity kW 69.7 82 129.5 163.0
Cooling 1 Rated input kW 27.3 28.3 51.4 57.7
EER 2.55 2.90 2.52 2.82
Capacity kW 75.4 90 138.6 181.2
Heating2 Rated input kW 24.3 29 45.6 59.1
COP 3.10 3.10 3.04 3.07
Type Finned tube Finned tube Finned tube Finned tube
Fan motor type DC motor DC motor DC motor DC motor
Air side heat
Fan motor output W 920 920 1500 920
exchanger
Fan motor quantity 2 2 2 4
Air flow rate m3/h 28500 35000 50000 70000
Type Plate Plate Plate Plate
Water side
Volume L 5.17 7.05 11.1 6.96×2
heat
Rated water flow m3/h 12.04 15 22.36 28.2
exchanger
Water flow range m3/h 8.0~15.5 10.2 ~ 18 15.6~28.5 20~36.1
Refrigerant type R32 R32 R32 R32
Refrigerant
Refrigerant charge3 kg 9 16 (11.5+4.5) 15.5(11.5+4) 16 (5.5+10.5)*2

Part 2 - Engineering Data


system
Throttle type EXV EXV EXV EXV
Power supply V/Ph/Hz 380~415/3/50 380~415/3/50 380~415/3/50 380~415/3/50
Pump Rated input kW 1.5 1.5 2.2 1.5
Rated current A 3.15 3.15 4.45 3.15
Volume L 0.15 0.15 0.15 0.15
Expansion
Precharge pressure Mpa 1.0 1.0 1.0 1.0
tank
Test pressure Mpa 12 12 24 12
Sound power level4 dB 86 83 93 92
Sound pressure level(1m)5 dB(A) 69 65 74 72
Net dimensions (W×H×D) mm 2000×1770×960 2220×2315×1135 2220×2300×1135 2752×2413×2220
Packed dimensions (W×H×D) mm 2085×1890×1030 2250×2445×1180 2250×2425×1180 2810×2446×2245
Net/Gross weight kg 475/490 686/711 746/767 1500/1504
Water pipe connections mm DN50 DN50 DN65 DN80
Water pressure range MPa 0.05 ~ 1.0 0.05 ~ 1.0 0.05 ~ 1.0 0.05 ~ 1.0
Water flow switch action flow m3/h 8 10 15.6 20
Vent Valve max working pressure Mpa 1 1 1 1
Safety valve action pressure Mpa 0.6 0.6 0.6 0.6
Controller KJRM-120H2/BMWK KJRM-120H2/BMWK KJRM-120H2/BMWK KJRM-120H2/BMWK

Cooling °C -10 to 48 -10 to 48 -10 to 48 -10 to 48


Operating
temperature
Heating °C -20 to 43 -20 to 43 -20 to 43 -20 to 43

Water outlet Cooling °C 0 to 20 0 to 20 0 to 20 0 to 20

temperature Heating °C 25 to 54 25 to 54 25 to 54 25 to 54

13
MBT Confidential
Aqua thermal
Notes:
1. Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C;
2. Outdoor ambient temperature 7°C DB/6°C WB. EWT 40°C, LWT 45°C;
3. The total amount of refrigerant for unit which capacity above 90kW include (factory charged + field charged).
4. Test standard: EN12102-1. Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C
5. Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C
Sound pressure level is the test average measured in a semi-anechoic chamber. The test position is 1m right in front of the unit for four sides and (1+H)/2m
(where H is the height of the unit) above the floor. During in-situ operation, sound pressure levels may be higher as a result of ambient noise.

1000
Test position

H Unit (H+1000)/2

6. Capacity and efficiency data calculated in accordance with EN14511; EN14825


Midea Aqua thermal Engineering Data Book

7. Seasonal space heating energy efficiency class tested in average climate conditions.

2 Electrical Characteristics
Outdoor unit Power current Compressor Fan
System Voltage Min. Max. MCA MOP MSC RLA FLA
Hz kW
(V) (V) (V) (A) (A) (A) (A) (A)

MC-SU75-RN8L-B 380-415 50 342 456 46 54 - 34.09 0.92 4.4

MC-SU75M-RN8L-B 380-415 50 342 456 49 57 34.09 0.92 4.4

MC-SU90-RN8L-B 380-415 50 342 456 60 70 - 60.00 0.92 5.2

MC-SU90M-RN8L-B 380-415 50 342 456 63 73 60.00 0.92 5.2

MC-SU140-RN8L-B 380-415 50 342 456 90 106 - 34.09 1.5 8

MC-SU140M-RN8L-B 380-415 50 342 456 94 110 34.09 1.5 8

MC-SU180-RN8L-B 380-415 50 342 456 120 141 - 30.86 0.92 5.2

MC-SU180M-RN8L-B 380-415 50 342 456 126 147 30.86 0.92 5.2

Note:

MCA: Min. Circuit Amps. (A)


MOP: Maximum overcurrent protector (A)
MSC : Max. Starting Amps. (A)
RLA: In nominal cooling or heating test condition, the input Amps of compressor where MAX. Hz can operate Rated Load Amps. (A)
KW: Rated Motor Output
FLA: Full Load Amps. (A)

14
MBT Confidential
Aqua thermal
3 Dimensions and Center of Gravity
MC-SU75-RN8L-B, MC-SU75M-RN8L-B

1780
270
390
Water entrancing pipe

Water leaving pipe


816

190
700 1995

570
960

Part 2 - Engineering Data


700

MC-SU90-RN8L-B, MC-SU90M-RN8L-B

Water entrancing pipe DN50

Water leaving pipe DN50

15
MBT Confidential
Aqua thermal
MC-SU140-RN8L-B, MC-SU140M-RN8L-B

2300
86 270
700

Water entrancing pipe DN65


Water leaving pipe DN65 1135
910 913
2200
Midea Aqua thermal Engineering Data Book

520

1135

MC-SU180-RN8L-B, MC-SU180M-RN8L-B
400

870

2221
1320
2753

16
MBT Confidential
Aqua thermal
4 Operating Limits
T4:Ambient temperature(℃)
Two:Leaving water temperature(℃)
4.1 Cooling operating range

MC-SU75-RN8L-B, MC-SU90-RN8L-B, MC-SU140-RN8L-B, MC-SU180-RN8L-B


MC-SU75M-RN8L-B, MC-SU90M-RN8L-B, MC-SU140M-RN8L-B, MC-SU180M-RN8L-B


Part 2 - Engineering Data


Notes:
① Normal mode
② Low leaving water temperature mode
Low leaving water temperature mode can be set through wired controller, please refer to the Operation Manual for details. If low leaving water
temperature function is effective, the operation range will extend to the red frame above. When the set temperature is less than 5℃, antifreeze
liquid (concentration above 15%) should be added in the water system, otherwise the unit will be damaged.

4.2 Heating operating range


MC-SU75-RN8L-B, MC-SU75M-RN8L-B MC-SU90-RN8L-B, MC-SU90M-RN8L-B
MC-SU140-RN8L-B, MC-SU140M-RN8L-B MC-SU180-RN8L-B, MC-SU180M-RN8L-B
HEATING
50
50
45
45
40
40
35
35
outdoor temperature (℃)

30
outdoor temperature (℃)

30
25
25
20
20
15
15
10
10
5
5
0
0
20 25 30 35 40 45 50 55 60 -5
-5
-10
-10
-15
-15
-20
-20
-25
-25
20 25 30 35 40 45 50 55 60
Outlet water temperature (℃) Outlet water temperature (℃)
Fig. 1-1-2 Heating operating range
17
MBT Confidential
Aqua thermal
5 Capacity Tables
5.1 Heating Capacity Tables
MC-SU75-RN8L-B
DB
LWT -20 -18 -15 -10 -5 0
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 30.9 13.2 2.3 41.3 15.3 2.7 42.2 15.4 2.7 43.2 15.5 2.8 45.7 15.5 2.9 49.5 15.8 3.1
30 31.2 15.2 2.1 40.8 15.9 2.6 42.1 16.0 2.6 43.3 16.1 2.7 45.9 16.3 2.8 48.6 16.5 2.9
35 30.2 16.1 1.9 39.2 17.3 2.3 40.3 17.4 2.3 41.4 17.5 2.4 46.7 18.7 2.5 47.8 17.3 2.8
40 23.7 14.1 1.7 35.7 19.4 1.8 37.2 19.6 1.9 38.7 19.8 2.0 44.6 20.4 2.2 46.1 18.4 2.5
45 18.8 13.2 1.4 32.8 20.2 1.6 34.5 20.4 1.7 36.3 20.6 1.8 40.4 21.0 1.9 44.5 19.5 2.3
48 25.6 19.8 1.3 29.1 20.2 1.4 32.6 20.4 1.6 37.8 21.0 1.8 42.6 20.1 2.1
50 28.8 20.1 1.4 29.7 19.5 1.5 35.2 20.9 1.7 40.8 20.7 2.0
54 23.9 16.3 1.5 28.4 17.5 1.6 32.9 17.4 1.9
Midea Aqua thermal Engineering Data Book

DB
LWT 5 7 10 15 20 25
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 54.1 16.4 3.3 82.2 23.2 3.5 83.6 20.8 4.0 96.9 23.2 4.2 100.3 22.8 4.4 106.2 22.8 4.6
30 53.2 16.9 3.2 80.7 22.9 3.5 82.2 21.5 3.8 91.4 22.5 4.1 96.5 22.6 4.3 104.7 23.1 4.5
35 55.1 18.3 3.0 74.7 21.3 3.5 76.9 21.0 3.7 88.2 22.4 3.9 93.4 22.5 4.1 102.5 22.8 4.5
40 55.7 19.6 2.8 74.9 23.3 3.2 77.8 22.9 3.4 85.7 23.5 3.7 87.4 22.0 4.0 96.1 22.4 4.3
45 56.4 21.0 2.7 75.0 23.7 3.2 76.2 23.5 3.2 79.0 23.1 3.4 85.2 23.0 3.7 93.4 23.5 4.0
48 56.2 21.4 2.6 66.2 23.0 2.9 70.2 23.2 3.0 51.0 15.6 3.3 79.9 22.0 3.6 86.2 22.7 3.8
50 56.1 21.9 2.6 65.0 23.1 2.8 68.0 22.9 3.0 38.4 12.3 3.1 76.2 21.5 3.6 79.4 21.5 3.7
54 45.2 18.3 2.5 63.8 23.0 2.8 68.0 23.2 2.9 18.6 6.2 3.0 22.6 7.3 3.1 23.5 7.5 3.2

DB
LWT 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER
25 113.6 21.6 5.2 114.4 19.4 5.9 115.9 18.6 6.2 114.3 17.7 6.5
30 115.4 23.0 5.0 118.6 20.8 5.7 123.3 21.1 5.9 117.1 19.6 6.0
35 114.2 23.7 4.8 121.5 22.9 5.3 126.2 23.3 5.4 118.6 21.0 5.6
40 105.7 23.9 4.4 112.5 22.5 5.0 117.9 23.0 5.1 110.3 20.8 5.3
45 95.4 22.6 4.2 102.8 21.6 4.8 105.4 21.7 4.9 99.3 19.8 5.0
48 70.8 17.5 4.0 74.7 16.5 4.5 77.8 16.8 4.6 71.7 15.1 4.8
50 56.7 14.4 3.9 59.1 14.0 4.2 63.4 14.6 4.4 57.8 12.7 4.6
54 25.4 7.8 3.3 28.5 8.4 3.4 40.2 11.5 3.5
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.

18
MBT Confidential
Aqua thermal
MC-SU75M-RN8L-B
DB
LWT -20 -18 -15 -10 -5 0
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 30.9 14.7 2.1 41.3 16.8 2.5 42.2 16.9 2.5 43.2 17.0 2.5 45.7 17.0 2.7 49.5 17.3 2.9
30 31.2 16.7 1.9 40.8 17.4 2.3 42.1 17.5 2.4 43.3 17.6 2.5 45.9 17.8 2.6 48.6 18.0 2.7
35 30.2 17.6 1.7 39.2 18.8 2.1 40.3 18.9 2.1 41.4 19.0 2.2 46.7 20.2 2.3 47.8 18.8 2.5
40 23.7 15.6 1.5 35.7 20.9 1.7 37.2 21.1 1.8 38.7 21.3 1.8 44.6 21.9 2.0 46.1 19.9 2.3
45 18.8 14.7 1.3 32.8 21.7 1.5 34.5 21.9 1.6 36.3 22.1 1.6 40.4 22.5 1.8 44.5 21.0 2.1
48 25.6 21.3 1.2 29.1 21.7 1.3 32.6 21.9 1.5 37.8 22.5 1.7 42.6 21.6 2.0
50 28.8 21.6 1.3 29.7 21.0 1.4 35.2 22.4 1.6 40.8 22.2 1.8
54 23.9 17.8 1.3 28.4 19.0 1.5 32.9 18.9 1.7

DB
LWT 5 7 10 15 20 25
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 54.1 17.9 3.0 82.2 24.7 3.3 83.6 22.3 3.7 96.9 24.7 3.9 100.3 24.3 4.1 106.2 24.3 4.4
30 53.2 18.4 2.9 80.7 24.4 3.3 82.2 23.0 3.6 91.4 24.0 3.8 96.5 24.1 4.0 104.7 24.6 4.3

Part 2 - Engineering Data


35 55.1 19.8 2.8 74.7 22.8 3.3 76.9 22.5 3.4 88.2 23.9 3.7 93.4 24.0 3.9 102.5 24.3 4.2
40 55.7 21.1 2.6 74.9 24.8 3.0 77.8 24.4 3.2 85.7 25.0 3.4 87.4 23.5 3.7 96.1 23.9 4.0
45 56.4 22.5 2.5 75.0 25.2 3.0 76.2 25.0 3.0 79.0 24.6 3.2 85.2 24.5 3.5 93.4 25.0 3.7
48 56.2 22.9 2.5 66.2 24.5 2.7 70.2 24.7 2.8 51.0 17.1 3.0 79.9 23.5 3.4 86.2 24.2 3.6
50 56.1 23.4 2.4 65.0 24.6 2.6 68.0 24.4 2.8 38.4 13.8 2.8 76.2 23.0 3.3 79.4 23.0 3.5
54 45.2 19.8 2.3 63.8 24.5 2.6 68.0 24.7 2.8 18.6 7.7 2.4 22.6 8.8 2.6 23.5 9.0 2.6

DB
LWT 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER
25 113.6 23.1 4.9 114.4 20.9 5.5 115.9 20.1 5.8 114.3 19.2 6.0
30 115.4 24.5 4.7 118.6 22.3 5.3 123.3 22.6 5.5 117.1 21.1 5.5
35 114.2 25.2 4.5 121.5 24.4 5.0 126.2 24.8 5.1 118.6 22.5 5.3
40 105.7 25.4 4.2 112.5 24.0 4.7 117.9 24.5 4.8 110.3 22.3 4.9
45 95.4 24.1 4.0 102.8 23.1 4.5 105.4 23.2 4.5 99.3 21.3 4.7
48 70.8 19 3.7 74.7 18.0 4.2 77.8 18.3 4.3 71.7 16.6 4.3
50 56.7 15.9 3.6 59.1 15.5 3.8 63.4 16.1 3.9 57.8 14.2 4.1
54 25.4 9.3 2.7 28.5 9.9 2.9 40.2 13.0 3.1
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.

19
MBT Confidential
Aqua thermal
MC-SU90-RN8L-B
DB
LWT -20 -18 -15 -10 -7 4
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 44.7 21.1 2.1 49.6 21.8 2.3 56.8 22.8 2.5 67.4 23.2 2.9 73.7 23.5 3.1 79.1 24.3 3.3
30 43.9 21.7 2.0 48.7 22.4 2.2 55.8 23.4 2.4 66.2 23.9 2.8 72.4 24.2 3.0 77.7 25.0 3.1
35 42.7 24.8 1.7 47.0 25.3 1.9 53.6 25.9 2.1 63.9 26.1 2.5 70.2 26.2 2.7 75.5 26.3 2.9
40 39.7 26.6 1.5 44.2 27.0 1.6 51.0 27.6 1.8 61.6 28.2 2.2 68.0 28.6 2.4 73.7 28.7 2.6
42 42.4 26.7 1.6 48.9 27.3 1.8 59.9 28.6 2.1 66.5 29.4 2.3 72.2 29.5 2.4
45 45.8 26.9 1.7 57.2 29.2 2.0 64.1 30.6 2.1 69.9 30.8 2.3
47 50.6 27.1 1.9 56.6 28.4 2.0 63.6 29.3 2.2
48 48.6 27.7 1.8 54.5 29.0 1.9 61.2 29.9 2.0
50 48.0 28.0 1.7 55.3 29.3 1.9
54 47.5 29.6 1.6
Midea Aqua thermal Engineering Data Book

DB
LWT 2 7 15 20 25 30
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 89.9 25.9 3.5 102.0 23.8 4.3 104.8 23.1 4.5 104.9 21.7 4.8 102.8 20.0 5.2 100.0 17.6 5.7
30 88.3 26.6 3.3 101.4 24.5 4.1 103.9 23.7 4.4 104.0 22.3 4.7 101.9 20.5 5.0 99.2 18.1 5.5
35 86.3 26.4 3.3 100.2 26.4 3.8 102.4 24.9 4.1 102.3 23.5 4.3 100.2 20.7 4.8 96.0 18.3 5.2
40 84.9 28.8 2.9 95.7 27.0 3.5 99.1 25.8 3.8 99.6 24.5 4.1 99.3 21.5 4.6 94.6 18.7 5.1
42 83.5 29.8 2.8 92.8 27.5 3.4 98.5 26.8 3.7 98.9 25.0 4.0 98.3 21.8 4.5 90.7 18.8 4.8
45 81.5 31.3 2.6 90.4 28.8 3.1 97.7 28.2 3.5 98.2 25.5 3.9 96.8 22.3 4.3 84.9 18.8 4.5
47 77.6 31.1 2.5 86.5 31.2 2.8 93.5 27.1 3.5 90.1 22.8 3.9 83.7 19.4 4.3 74.6 17.4 4.3
48 74.6 31.8 2.3 83.2 31.9 2.6 89.9 27.6 3.3 86.6 23.3 3.7 80.5 19.8 4.1 71.8 17.8 4.0
50 70.0 32.1 2.2 78.3 32.2 2.4 84.7 27.2 3.1 79.1 22.2 3.6 75.6 19.2 3.9 63.0 17.1 3.7
54 59.9 33.3 1.8 67.0 34.0 2.0 73.9 27.0 2.7 70.2 21.2 3.3 58.9 15.7 3.8 47.0 14.4 3.3

DB
LWT 35 40 43
HC PI EER HC PI EER HC PI EER
25 93.6 15.0 6.3 89.6 13.6 6.6 88.8 13.5 6.6
30 92.8 15.4 6.0 88.9 14.0 6.3 88.0 13.8 6.4
35 89.0 16.7 5.3 80.0 13.3 6.0 78.6 12.4 6.4
40 85.0 16.0 5.3 71.4 11.4 6.3 70.1 10.7 6.5
42 81.7 16.0 5.1 69.2 11.8 5.9 67.8 11.3 6.0
45 76.8 16.2 4.7 66.0 12.4 5.3 64.3 12.2 5.3
47 67.9 15.0 4.5 57.7 11.6 5.0 56.0 11.4 4.9
48 65.3 15.3 4.3 55.5 11.8 4.7
50
54
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.
20
MBT Confidential
Aqua thermal
MC-SU90M-RN8L-B
DB
LWT -20 -18 -15 -10 -7 4
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 44.7 22.6 2.0 49.6 23.3 2.1 56.8 24.3 2.3 67.4 24.7 2.7 73.7 25.0 2.9 79.1 25.8 3.1
30 43.9 23.2 1.9 48.7 23.9 2.0 55.8 24.9 2.2 66.2 25.4 2.6 72.4 25.7 2.8 77.7 26.5 2.9
35 42.7 26.3 1.6 47.0 26.8 1.8 53.6 27.4 2.0 63.9 27.6 2.3 70.2 27.7 2.5 75.5 27.8 2.7
40 39.7 28.1 1.4 44.2 28.5 1.6 51.0 29.1 1.8 61.6 29.7 2.1 68.0 30.1 2.3 73.7 30.2 2.4
42 42.4 28.2 1.5 48.9 28.8 1.7 59.9 30.1 2.0 66.5 30.9 2.2 72.2 31.0 2.3
45 45.8 28.4 1.6 57.2 30.7 1.9 64.1 32.1 2.0 69.9 32.3 2.2
47 50.6 28.6 1.8 56.6 29.9 1.9 63.6 30.8 2.1
48 48.6 29.2 1.7 54.5 30.5 1.8 61.2 31.4 1.9
50 48.0 29.5 1.6 55.3 30.8 1.8
54 47.5 31.1 1.5

DB
LWT 2 7 15 20 25 30
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER

Part 2 - Engineering Data


25 89.9 27.4 3.3 102.0 25.3 4.0 104.8 24.6 4.3 104.9 23.2 4.5 102.8 21.5 4.8 100.0 19.1 5.2
30 88.3 28.1 3.1 101.4 26.0 3.9 103.9 25.2 4.1 104.0 23.8 4.4 101.9 22.0 4.6 99.2 19.6 5.1
35 86.3 27.9 3.1 100.2 27.9 3.6 102.4 26.4 3.9 102.3 25.0 4.1 100.2 22.2 4.5 96.0 19.8 4.8
40 84.9 30.3 2.8 95.7 28.5 3.4 99.1 27.3 3.6 99.6 26.0 3.8 99.3 23.0 4.3 94.6 20.2 4.7
42 83.5 31.3 2.7 92.8 29.0 3.2 98.5 28.3 3.5 98.9 26.5 3.7 98.3 23.3 4.2 90.7 20.3 4.5
45 81.5 32.8 2.5 90.4 30.3 3.0 97.7 29.7 3.3 98.2 27.0 3.6 96.8 23.8 4.1 84.9 20.3 4.2
47 77.6 32.6 2.4 86.5 32.7 2.6 93.5 28.6 3.3 90.1 24.3 3.7 83.7 20.9 4.0 74.6 18.9 3.9
48 74.6 33.3 2.2 83.2 33.4 2.5 89.9 29.1 3.1 86.6 24.8 3.5 80.5 21.3 3.8 71.8 19.3 3.7
50 70 33.6 2.1 78.3 33.7 2.3 84.7 28.7 3.0 79.1 23.7 3.3 75.6 20.7 3.7 63.0 18.6 3.4
54 59.9 34.8 1.7 67.0 35.5 1.9 73.9 28.5 2.6 70.2 22.7 3.1 58.9 17.2 3.4 47.0 15.9 3.0

DB
LWT 35 40 43
HC PI EER HC PI EER HC PI EER
25 93.6 16.5 5.7 89.6 15.1 5.9 88.8 15.0 5.9
30 92.8 16.9 5.5 88.9 15.5 5.7 88.0 15.3 5.8
35 89 18.2 4.9 80.0 14.8 5.4 78.6 13.9 5.7
40 85 17.5 4.9 71.4 12.9 5.5 70.1 12.2 5.7
42 81.7 17.5 4.7 69.2 13.3 5.2 67.8 12.8 5.3
45 76.8 17.7 4.3 66.0 13.9 4.7 64.3 13.7 4.7
47 67.9 16.5 4.1 57.7 13.1 4.4 56.0 12.9 4.3
48 65.3 16.8 3.9 55.5 13.3 4.2
50
54
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate..
21
MBT Confidential
Aqua thermal
MC-SU140-RN8L-B
DB
LWT -20 -18 -15 -10 -5 0
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 60.4 27.2 2.2 78.8 31.9 2.5 81.7 32.4 2.5 97.1 35.9 2.7 82.7 30.0 2.8 91.4 31.3 2.9
30 61.9 28.9 2.1 78.5 32.8 2.4 80.0 33.8 2.4 95.2 37.4 2.5 82.6 31.7 2.6 91.8 33.6 2.7
35 57.2 29.3 1.9 74.4 34.0 2.2 80.4 36.6 2.2 95.6 40.5 2.4 83.5 34.8 2.4 92.2 36.3 2.5
40 38.1 23.1 1.7 67.4 34.9 1.9 81.4 39.5 2.1 96.7 43.8 2.2 85.2 37.4 2.3 90.8 38.7 2.3
45 13.0 12.1 1.1 54.9 33.4 1.6 79.5 42.5 1.9 94.5 47.0 2.0 86.9 42.2 2.1 89.4 41.4 2.2
48 50.9 33.0 1.5 75.4 41.7 1.8 89.7 46.1 1.9 84.1 42.5 2.0 87.3 42.6 2.0
50 69.8 40.9 1.7 83.0 45.3 1.8 75.4 39.6 1.9 80.3 41.4 1.9
54 57.7 35.4 1.6 55.6 32.9 1.7 56.4 32.7 1.7

DB
LWT 5 7 10 15 20 25
Midea Aqua thermal Engineering Data Book

HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER


25 120.1 35.5 3.4 158.9 42.4 3.7 169.7 43.1 3.9 180.1 45.1 4.0 196.8 48.1 4.1 213.6 51.5 4.2
30 116.2 36.9 3.2 150.6 43.3 3.5 166.2 44.3 3.8 178.3 47.2 3.8 188.4 48.9 3.9 198.5 50.9 3.9
35 112.8 37.5 3.0 138.5 42.1 3.3 161.7 45.0 3.6 172.0 47.1 3.6 180.7 48.3 3.7 186.2 48.4 3.9
40 110.5 40.0 2.8 138.8 44.7 3.1 158.9 46.5 3.4 166.0 47.8 3.5 169.2 47.7 3.5 173.0 47.4 3.6
45 107.6 42.4 2.5 138.0 44.5 3.1 156.9 50.1 3.1 148.6 46.5 3.2 155.8 44.8 3.5 158.1 43.9 3.6
48 107.5 45.1 2.4 130.6 46.3 2.8 153.8 51.1 3.0 140.0 44.6 3.1 148.2 43.8 3.4 151.1 42.9 3.5
50 106.5 46.6 2.3 123.7 47.0 2.6 147.8 51.9 2.8 130.1 42.5 3.1 133.5 39.8 3.4 136.1 39.4 3.5
54 66.2 33.0 2.0 71.4 31.2 2.3 80.2 31.0 2.6 86.5 30.4 2.8 85.6 27.5 3.1 89.0 27.6 3.2

DB
LWT 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER
25 220.2 52.1 4.2 226.9 50.8 4.5 216.6 46.7 4.6 211.4 44.7 4.7
30 204.2 48.5 4.2 209.8 47.5 4.4 198.0 44.4 4.5 192.1 42.6 4.5
35 191.0 44.2 4.3 198.1 44.9 4.4 183.7 44.0 4.2 178.5 42.2 4.2
40 168.7 39.4 4.3 177.1 40.5 4.4 163.5 42.8 3.8 156.8 40.4 3.9
45 150.1 40.0 3.8 158.5 41.5 3.8 143.9 41.6 3.5 136.6 39.1 3.5
48 136.1 37.6 3.6 141.5 38.4 3.7 130.2 40.4 3.2 124.5 38.0 3.3
50 124.9 35.3 3.5 129.2 36.1 3.6 117.1 38.9 3.0 111.0 36.1 3.1
54 79.1 23.8 3.3 89.1 26.4 3.4 80.8 29.3 2.8
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.

22
MBT Confidential
Aqua thermal
MC-SU140M-RN8L-B
DB
LWT -20 -18 -15 -10 -5 0
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 60.4 29.4 2.1 78.8 34.1 2.3 81.7 34.6 2.4 97.1 38.1 2.5 82.7 32.2 2.6 91.4 33.5 2.7
30 61.9 31.1 2.0 78.5 35.0 2.2 80.0 36.0 2.2 95.2 39.6 2.4 82.6 33.9 2.4 91.8 35.8 2.6
35 57.2 31.5 1.8 74.4 36.2 2.1 80.4 38.8 2.1 95.6 42.7 2.2 83.5 37.0 2.3 92.2 38.5 2.4
40 38.1 25.3 1.5 67.4 37.1 1.8 81.4 41.7 2.0 96.7 46.0 2.1 85.2 39.6 2.2 90.8 40.9 2.2
45 13 14.3 0.9 54.9 35.6 1.5 79.5 44.7 1.8 94.5 49.2 1.9 86.9 44.4 2.0 89.4 43.6 2.1
48 50.9 35.2 1.4 75.4 43.9 1.7 89.7 48.3 1.9 84.1 44.7 1.9 87.3 44.8 1.9
50 69.8 43.1 1.6 83.0 47.5 1.7 75.4 41.8 1.8 80.3 43.6 1.8
54 57.7 37.6 1.5 55.6 35.1 1.6 56.4 34.9 1.6

DB
LWT 5 7 10 15 20 25
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 120.1 37.7 3.2 158.9 44.6 3.6 169.7 45.3 3.7 180.1 47.3 3.8 196.8 50.3 3.9 213.6 53.7 4.0
30 116.2 39.1 3.0 150.6 45.5 3.3 166.2 46.5 3.6 178.3 49.4 3.6 188.4 51.1 3.7 198.5 53.1 3.7

Part 2 - Engineering Data


35 112.8 39.7 2.8 138.5 44.3 3.1 161.7 47.2 3.4 172.0 49.3 3.5 180.7 50.5 3.6 186.2 50.6 3.7
40 110.5 42.2 2.6 138.8 46.9 3.0 158.9 48.7 3.3 166.0 50.0 3.3 169.2 49.9 3.4 173.0 49.6 3.5
45 107.6 44.6 2.4 138.0 46.7 3.0 156.9 52.3 3.0 148.6 48.7 3.1 155.8 47.0 3.3 158.1 46.1 3.4
48 107.5 47.3 2.3 130.6 48.5 2.7 153.8 53.3 2.9 140.0 46.8 3.0 148.2 46.0 3.2 151.1 45.1 3.4
50 106.5 48.8 2.2 123.7 49.2 2.5 147.8 54.1 2.7 130.1 44.7 2.9 133.5 42.0 3.2 136.1 41.6 3.3
54 66.2 35.2 1.9 71.4 33.4 2.1 80.2 33.2 2.4 86.5 32.6 2.7 85.6 29.7 2.9 89.0 29.8 3.0

DB
LWT 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER
25 220.2 54.3 4.1 226.9 53.0 4.3 216.6 48.9 4.4 211.4 46.9 4.5
30 204.2 50.7 4.0 209.8 49.7 4.2 198.0 46.6 4.2 192.1 44.8 4.3
35 191 46.4 4.1 198.1 47.1 4.2 183.7 46.2 4.0 178.5 44.4 4.0
40 168.7 41.6 4.1 177.1 42.7 4.1 163.5 45.0 3.6 156.8 42.6 3.7
45 150.1 42.2 3.6 158.5 43.7 3.6 143.9 43.8 3.3 136.6 41.3 3.3
48 136.1 39.8 3.4 141.5 40.6 3.5 130.2 42.6 3.1 124.5 40.2 3.1
50 124.9 37.5 3.3 129.2 38.3 3.4 117.1 41.1 2.8 111.0 38.3 2.9
54 79.1 26 3.0 89.1 28.6 3.1 80.8 31.5 2.6
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.

23
MBT Confidential
Aqua thermal
MC-SU180-RN8L-B
DB
LWT -20 -18 -15 -10 -7 -4
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 89.5 42.5 43.9 99.1 43.9 2.3 111.8 45.7 2.4 134.8 46.8 2.9 148.1 48.1 3.1 158.2 48.9 3.2
30 87.9 43.7 45.1 97.4 45.1 2.2 109.8 47.0 2.3 132.4 48.1 2.8 145.5 49.4 2.9 155.4 50.3 3.1
35 85.3 50.0 50.8 94.1 50.8 1.9 106.0 51.9 2.0 127.9 52.5 2.4 141.0 52.7 2.7 151.1 52.9 2.9
40 79.4 53.6 54.4 88.4 54.4 1.6 100.8 55.9 1.8 123.3 56.9 2.2 136.9 57.4 2.4 147.3 57.7 2.6
42 84.8 56.9 1.5 97.3 57.3 1.7 120.3 57.6 2.1 134.2 58.7 2.3 144.8 59.3 2.4
45 92.7 59.8 1.5 114.5 58.8 1.9 128.8 60.7 2.1 139.8 62.0 2.3
47 103.8 57.3 1.8 118.1 59.7 2.0 129.0 61.2 2.1
48 97.2 55.8 1.7 111.4 58.5 1.9 122.3 60.3 2.0
50 101.0 57.4 1.8 110.7 59.1 1.9
54 95.0 59.5 1.6
Midea Aqua thermal Engineering Data Book

DB
LWT 0 5 7 10 15 20
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 174.3 51.2 3.4 190.3 47.0 4.1 198.2 46.5 4.3 206.0 45.4 4.5 207.5 44.8 4.6 207.8 43.6 4.8
30 171.2 52.6 3.3 188.0 48.6 3.9 196.5 47.0 4.2 204.2 46.8 4.4 205.7 46.1 4.5 206.0 44.9 4.6
35 167.1 53.1 3.1 183.0 49.9 3.7 190.8 49.6 3.9 199.2 49.8 4.0 200.9 49.2 4.1 200.5 47.4 4.2
40 164.0 57.9 2.8 178.6 56.2 3.2 185.4 54.2 3.4 196.1 51.8 3.8 198.2 51.1 3.9 199.2 49.4 4.0
42 161.7 59.8 2.7 176.8 57.0 3.1 183.9 55.4 3.3 195.0 53.6 3.6 197.3 52.9 3.7 198.1 49.8 4.0
45 157.0 62.7 2.5 173.3 58.3 3.0 180.0 57.0 3.2 193.0 56.5 3.4 195.4 55.7 3.5 196.0 50.3 3.9
47 147.3 63.0 2.3 166.7 63.3 2.6 175.3 61.6 2.8 184.1 56.2 3.3 185.7 55.1 3.4 181.9 48.4 3.8
48 142.1 63.0 2.3 162.6 66.1 2.5 172.3 64.2 2.7 178.6 55.7 3.2 179.8 54.5 3.3 173.3 46.9 3.7
50 132.2 63.2 2.1 155.5 67.3 2.3 166.6 69.2 2.4 168.9 53.6 3.2 169.4 52.1 3.3 158.2 44.7 3.5
54 113.2 65.1 1.7 132.8 67.4 2.0 142.1 68.4 2.1 146.8 52.3 2.8 147.8 50.9 2.9 140.5 42.7 3.3

DB
LWT 25 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 205.7 40.2 5.1 200.1 35.5 5.6 187.3 30.1 6.2 179.2 28.5 6.3 177.6 27.7 6.4
30 203.9 41.3 4.9 198.4 36.5 5.4 185.7 31.0 6.0 177.7 29.3 6.1 176.1 28.5 6.2
35 200.5 41.4 4.8 192.0 36.8 5.2 178.0 32.0 5.6 160.0 27.9 5.7 157.2 26.8 5.9
40 198.6 42.7 4.7 189.2 37.6 5.0 170.0 32.9 5.2 142.8 26.0 5.5 140.1 25.0 5.6
42 196.9 43.8 4.5 182.7 37.7 4.8 164.5 32.7 5.0 139.1 26.0 5.3 136.3 24.9 5.5
45 193.6 45.6 4.3 169.8 37.9 4.5 153.6 32.5 4.7 132.0 25.9 5.1 128.6 24.7 5.2
47 173.4 42.7 4.1 155.6 36.4 4.3 141.7 31.6 4.5 124.1 25.4 4.9 120.2 23.9 5.0
48 161.0 40.6 4.0 143.5 34.5 4.2 130.6 29.8 4.4 114.4 24.0 4.8
50 139.2 37.3 3.7 126.0 32.4 3.9
54 117.9 33.3 3.5 94.0 25.3 3.7
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate..
24
MBT Confidential
Aqua thermal
MC-SU180M-RN8L-B
DB
LWT -20 -18 -15 -10 -7 -4
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 89.5 44.0 2.0 99.1 45.4 2.2 111.8 47.2 2.4 134.8 48.3 2.8 148.1 49.6 3.0 158.2 50.4 3.1
30 87.9 45.2 1.9 97.4 46.6 2.1 109.8 48.5 2.3 132.4 49.6 2.7 145.5 50.9 2.9 155.4 51.8 3.0
35 85.3 51.5 1.7 94.1 52.3 1.8 106.0 53.4 2.0 127.9 54.0 2.4 141.0 54.2 2.6 151.1 54.4 2.8
40 79.4 55.1 1.4 88.4 55.9 1.6 100.8 57.4 1.8 123.3 58.4 2.1 136.9 58.9 2.3 147.3 59.2 2.5
42 84.8 58.4 1.5 97.3 58.8 1.7 120.3 59.1 2.0 134.2 60.2 2.2 144.8 60.8 2.4
45 92.7 61.3 1.5 114.5 60.3 1.9 128.8 62.2 2.1 139.8 63.5 2.2
47 103.8 58.8 1.8 118.1 61.2 1.9 129.0 62.7 2.1
48 97.2 57.3 1.7 111.4 60.0 1.9 122.3 61.8 2.0
50 101.0 58.9 1.7 110.7 60.6 1.8
54 95.0 61.0 1.6

DB
LWT 0 5 7 10 15 20
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER

Part 2 - Engineering Data


25 174.3 52.7 3.3 190.3 48.5 3.9 198.2 48.0 4.1 206.0 46.9 4.4 207.5 46.3 4.5 207.8 45.1 4.6
30 171.2 54.1 3.2 188.0 50.1 3.8 196.5 48.5 4.1 204.2 48.3 4.2 205.7 47.6 4.3 206.0 46.4 4.4
35 167.1 54.6 3.1 183.0 51.4 3.6 190.8 51.1 3.7 199.2 51.3 3.9 200.9 50.7 4.0 200.5 48.9 4.1
40 164.0 59.4 2.8 178.6 57.7 3.1 185.4 55.7 3.3 196.1 53.3 3.7 198.2 52.6 3.8 199.2 50.9 3.9
42 161.7 61.3 2.6 176.8 58.5 3.0 183.9 56.9 3.2 195.0 55.1 3.5 197.3 54.4 3.6 198.1 51.3 3.9
45 157.0 64.2 2.4 173.3 59.8 2.9 180.0 58.5 3.1 193.0 58.0 3.3 195.4 57.2 3.4 196.0 51.8 3.8
47 147.3 64.5 2.3 166.7 64.8 2.6 175.3 63.1 2.8 184.1 57.7 3.2 185.7 56.6 3.3 181.9 49.9 3.6
48 142.1 64.5 2.2 162.6 67.6 2.4 172.3 65.7 2.6 178.6 57.2 3.1 179.8 56.0 3.2 173.3 48.4 3.6
50 132.2 64.7 2.0 155.5 68.8 2.3 166.6 70.7 2.4 168.9 55.1 3.1 169.4 53.6 3.2 158.2 46.2 3.4
54 113.2 66.6 1.7 132.8 68.9 1.9 142.1 69.9 2.0 146.8 53.8 2.7 147.8 52.4 2.8 140.5 44.2 3.2

DB
LWT 25 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 205.7 41.7 4.9 200.1 37.0 5.4 187.3 31.6 5.9 179.2 30.0 6.0 177.6 29.2 6.1
30 203.9 42.8 4.8 198.4 38.0 5.2 185.7 32.5 5.7 177.7 30.8 5.8 176.1 30.0 5.9
35 200.5 42.9 4.7 192.0 38.3 5.0 178.0 33.5 5.3 160.0 29.4 5.4 157.2 28.3 5.6
40 198.6 44.2 4.5 189.2 39.1 4.8 170.0 34.4 4.9 142.8 27.5 5.2 140.1 26.5 5.3
42 196.9 45.3 4.3 182.7 39.2 4.7 164.5 34.2 4.8 139.1 27.5 5.1 136.3 26.4 5.2
45 193.6 47.1 4.1 169.8 39.4 4.3 153.6 34.0 4.5 132.0 27.4 4.8 128.6 26.2 4.9
47 173.4 44.2 3.9 155.6 37.9 4.1 141.7 33.1 4.3 124.1 26.9 4.6 120.2 25.4 4.7
48 161.0 42.1 3.8 143.5 36.0 4.0 130.6 31.3 4.2 114.4 25.5 4.5
50 139.2 38.8 3.6 126.0 33.9 3.7
54 117.9 34.8 3.4 94.0 26.8 3.5
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.
25
MBT Confidential
Aqua thermal
5.2 Cooling Capacity Tables
MC-SU75-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 52.0 17.7 2.9 61.1 17.7 3.5
5 60.5 18.6 3.3 69.0 18.9 3.7
7 66.7 19.8 3.4 75.5 20.2 3.7
10 61.9 10.3 6.0 61.0 11.0 5.6 58.9 11.7 5.0 57.2 12.5 4.6 68.2 19.8 3.4 82.3 20.8 4.0
15 70.8 10.4 6.8 69.6 11.6 6.0 66.5 11.4 5.8 65.4 11.6 5.7 66.9 17.4 3.8 90.8 18.4 4.9
20 78.4 11.3 6.9 77.5 12.0 6.5 76.5 12.3 6.2 74.4 12.1 6.2 68.3 16.7 4.1 95.9 18.6 5.2

DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
Midea Aqua thermal Engineering Data Book

0 60.5 18.0 3.4 59.9 18.7 3.2 59.4 22.3 2.7 56.9 24.3 2.3 36.5 16.5 2.2 23.2 11.4 2.0
5 68.2 19.3 3.5 67.6 20.0 3.4 67.0 23.8 2.8 64.2 26.0 2.5 41.2 17.6 2.3 26.2 12.1 2.2
7 75.1 20.4 3.7 74.2 21.4 3.5 70.8 24.2 2.9 70.0 26.8 2.6 47.3 18.8 2.5 31.8 13.5 2.4
10 81.2 21.1 3.8 79.3 21.4 3.7 77.4 24.9 3.1 74.8 27.1 2.8 51.6 19.1 2.7 35.5 13.7 2.6
15 88.0 19.5 4.5 86.8 20.9 4.2 82.4 23.0 3.6 78.7 24.5 3.2 53.2 16.8 3.2 37.1 12.5 3.0
20 94.5 19.6 4.8 93.5 21.3 4.4 91.6 23.0 4.0 87.4 23.2 3.8 58.0 15.8 3.7 43.3 12.7 3.4

DB
LWT 45 48
CC PI EER CC PI EER
0 21.3 11.2 1.9 11.3 8.3 1.4
5 24.1 11.9 2.0 12.7 8.9 1.4
7 27.4 12.6 2.2 14.5 8.9 1.6
10 31.2 12.9 2.4 17.1 9.0 1.9
15 33.9 12.1 2.8 21.3 9.0 2.4
20 39.0 12.3 3.2 25.1 9.0 2.8
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.

26
MBT Confidential
Aqua thermal
MC-SU75M-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 52.0 19.2 2.7 61.1 19.2 3.2
5 60.5 20.1 3.0 69.0 20.4 3.4
7 66.7 21.3 3.1 75.5 21.7 3.5
10 61.9 11.8 5.2 61.0 12.5 4.9 58.9 13.2 4.5 57.2 14.0 4.1 68.2 21.3 3.2 82.3 22.3 3.7
15 70.8 11.9 5.9 69.6 13.1 5.3 66.5 12.9 5.2 65.4 13.1 5.0 66.9 18.9 3.5 90.8 19.9 4.6
20 78.4 12.8 6.1 77.5 13.5 5.7 76.5 13.8 5.5 74.4 13.6 5.5 68.3 18.2 3.8 95.9 20.1 4.8

DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 60.5 19.5 3.1 59.9 20.2 3.0 59.4 23.8 2.5 56.9 25.8 2.2 36.5 18.0 2.0 23.2 12.9 1.8
5 68.2 20.8 3.3 67.6 21.5 3.1 67.0 25.3 2.6 64.2 27.5 2.3 41.2 19.1 2.2 26.2 13.6 1.9
7 75.1 21.9 3.4 74.2 22.9 3.2 70.8 25.7 2.8 70.0 28.3 2.5 47.3 20.3 2.3 31.8 15.0 2.1
10 81.2 22.6 3.6 79.3 22.9 3.5 77.4 26.4 2.9 74.8 28.6 2.6 51.6 20.6 2.5 35.5 15.2 2.3

Part 2 - Engineering Data


15 88 21 4.2 86.8 22.4 3.9 82.4 24.5 3.4 78.7 26.0 3.0 53.2 18.3 2.9 37.1 14.0 2.7
20 94.5 21.1 4.5 93.5 22.8 4.1 91.6 24.5 3.7 87.4 24.7 3.5 58.0 17.3 3.4 43.3 14.2 3.0

DB
LWT 45 48
CC PI EER CC PI EER
0 21.3 12.7 1.7 11.3 9.8 1.2
5 24.1 13.4 1.8 12.7 10.4 1.2
7 27.4 14.1 1.9 14.5 10.4 1.4
10 31.2 14.4 2.2 17.1 10.5 1.6
15 33.9 13.6 2.5 21.3 10.5 2.0
20 39.0 13.8 2.8 25.1 10.5 2.4
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.

27
MBT Confidential
Aqua thermal
MC-SU90-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 81.9 18.8 4.4 81.5 25.5 3.2
5 94.1 26.8 3.5 93.1 27.3 3.4
7 96.3 29.6 3.3 95.6 26.4 3.6
10 75.8 18.6 4.1 75.9 16.0 4.8 76.6 15.2 5.0 75.8 17.4 4.4 106.0 27.4 3.9 111.7 29.5 3.8
15 84.0 16.4 5.1 84.1 16.2 5.2 84.0 16.9 5.0 84.1 14.8 5.7 123.7 25.6 4.8 127.2 28.1 4.5
20 92.3 14.2 6.5 92.3 16.4 5.6 91.3 18.6 4.9 91.1 14.6 6.2 129.2 26.3 4.9 133.9 28.7 4.7

DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 78.2 26.5 3.0 76.1 20.9 3.6 74.1 24.3 3.1 68.3 29.6 2.3 57.3 27.5 2.1 46.9 24.9 1.9
Midea Aqua thermal Engineering Data Book

5 91.8 28.7 3.2 90.3 27.8 3.2 87.4 29.5 3.0 80.9 32.2 2.5 69.9 30.2 2.3 60.9 28.2 2.2
7 94.7 30.0 3.2 93.1 21.6 4.3 89.1 28.9 3.1 82.1 27.3 3.0 71.5 25.9 2.8 63.7 24.2 2.6
10 107.6 31.5 3.4 102.9 27.5 3.7 99.9 30.3 3.3 93.7 33.0 2.8 81.6 27.7 3.0 72.2 24.2 3.0
15 117.3 29.3 4.0 111.7 25.6 4.4 108.3 25.2 4.3 104.2 28.4 3.7 92.6 28.0 3.3 81.8 24.0 3.4
20 127.1 29.4 4.3 121.3 23.5 5.2 117.3 24.7 4.7 112.4 27.5 4.1 102.3 27.9 3.7 92.1 25.3 3.6

DB
LWT 45 48
CC PI EER CC PI EER
0 32.8 20.1 1.6 18.0 12.1 1.5
5 48.5 24.2 2.0 29.3 16.5 1.8
7 56.0 21.8 2.6 38.1 18.0 2.1
10 62.9 22.4 2.8 45.1 19.2 2.4
15 72.8 23.4 3.1 55.0 17.8 3.1
20 80.7 22.2 3.6 60.9 19.3 3.1
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.

28
MBT Confidential
Aqua thermal
MC-SU90M-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 81.9 20.3 4.0 81.5 27.0 3.0
5 94.1 28.3 3.3 93.1 28.8 3.2
7 96.3 31.1 3.1 95.6 27.9 3.4
10 75.8 20.1 3.8 75.9 17.5 4.3 76.6 16.7 4.6 75.8 18.9 4.0 106.0 28.9 3.7 111.7 31.0 3.6
15 84.0 17.9 4.7 84.1 17.7 4.8 84.0 18.4 4.6 84.1 16.3 5.2 123.7 27.1 4.6 127.2 29.6 4.3
20 92.3 15.7 5.9 92.3 17.9 5.2 91.3 20.1 4.5 91.1 16.1 5.7 129.2 27.8 4.6 133.9 30.2 4.4

DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 78.2 28.0 2.8 76.1 22.4 3.4 74.1 25.8 2.9 68.3 31.1 2.2 57.3 29.0 2.0 46.9 26.4 1.8
5 91.8 30.2 3.0 90.3 29.3 3.1 87.4 31.0 2.8 80.9 33.7 2.4 69.9 31.7 2.2 60.9 29.7 2.1
7 94.7 31.5 3.0 93.1 23.1 4.0 89.1 30.4 2.9 82.1 28.8 2.9 71.5 27.4 2.6 63.7 25.7 2.5
10 107.6 33.0 3.3 102.9 29.0 3.5 99.9 31.8 3.1 93.7 34.5 2.7 81.6 29.2 2.8 72.2 25.7 2.8

Part 2 - Engineering Data


15 117.3 30.8 3.8 111.7 27.1 4.1 108.3 26.7 4.1 104.2 29.9 3.5 92.6 29.5 3.1 81.8 25.5 3.2
20 127.1 30.9 4.1 121.3 25.0 4.9 117.3 26.2 4.5 112.4 29.0 3.9 102.3 29.4 3.5 92.1 26.8 3.4

DB
LWT 45 48
CC PI EER CC PI EER
0 32.8 21.6 1.5 18.0 13.6 1.3
5 48.5 25.7 1.9 29.3 18.0 1.6
7 56.0 23.3 2.4 38.1 19.5 2.0
10 62.9 23.9 2.6 45.1 20.7 2.2
15 72.8 24.9 2.9 55.0 19.3 2.8
20 80.7 23.7 3.4 60.9 20.8 2.9
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.

29
MBT Confidential
Aqua thermal
MC-SU140-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 105.2 38.4 2.7 117.4 38.0 3.1
5 120.0 40.8 2.9 135.2 40.4 3.3
7 128.2 42.7 3.0 142.2 41.2 3.5
10 114.4 25.6 4.5 112.8 25.7 4.4 111.3 26.1 4.3 109.7 26.4 4.2 133.3 42.8 3.1 146.5 41.6 3.5
15 133.7 26.3 5.1 131.8 26.2 5.0 130.5 26.4 4.9 129.2 26.6 4.9 138.2 40.7 3.4 155.0 38.5 4.0
20 144.7 25.0 5.8 143.1 25.4 5.6 141.6 25.7 5.5 140.1 25.9 5.4 146.6 40.7 3.6 156.3 37.1 4.2

DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 111.5 38.8 2.9 110.1 40.5 2.7 108.4 44.5 2.4 106.5 49.8 2.1 86.5 41.8 2.1 74.1 38.0 1.9
Midea Aqua thermal Engineering Data Book

5 128.4 41.1 3.1 125.6 43.3 2.9 124.5 46.8 2.7 121.7 52.9 2.3 98.3 44.5 2.2 85.1 40.6 2.1
7 136.9 41.6 3.3 133.5 45.3 3.0 132.1 47.9 2.8 130.0 50.5 2.6 104.8 43.0 2.4 91.2 41.3 2.2
10 142.8 42.4 3.4 142.1 46.1 3.1 141.1 49.0 2.9 139.1 52.5 2.7 107.7 41.3 2.6 100.9 40.9 2.5
15 151.0 39.9 3.8 148.3 44.3 3.3 147.4 46.7 3.2 146.2 49.3 3.0 115.5 40.3 2.9 110.3 39.9 2.8
20 152.9 38.1 4.0 150.2 42.4 3.5 149.8 44.7 3.4 148.4 46.9 3.2 119.9 38.7 3.1 114.9 37.7 3.0

DB
LWT 45 48
CC PI EER CC PI EER
0 71.4 39.7 1.8 41.0 28.2 1.5
5 81.1 42.0 1.9 46.8 29.8 1.6
7 86.4 41.9 2.1 57.7 31.7 1.8
10 92.6 39.0 2.4 63.5 32.3 2.0
15 95.0 35.4 2.7 65.3 29.1 2.2
20 97.3 32.6 3.0 70.3 26.3 2.7
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.

30
MBT Confidential
Aqua thermal
MC-SU140M-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 105.2 40.6 2.6 117.4 40.2 2.9
5 120.0 43.0 2.8 135.2 42.6 3.2
7 128.2 44.9 2.9 142.2 43.4 3.3
10 114.4 27.8 4.1 112.8 27.9 4.0 111.3 28.3 3.9 109.7 28.6 3.8 133.3 45.0 3.0 146.5 43.8 3.3
15 133.7 28.5 4.7 131.8 28.4 4.6 130.5 28.6 4.6 129.2 28.8 4.5 138.2 42.9 3.2 155.0 40.7 3.8
20 144.7 27.2 5.3 143.1 27.6 5.2 141.6 27.9 5.1 140.1 28.1 5.0 146.6 42.9 3.4 156.3 39.3 4.0

DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 111.5 41 2.7 110.1 42.7 2.6 108.4 46.7 2.3 106.5 52.0 2.0 86.5 44.0 2.0 74.1 40.2 1.8
5 128.4 43.3 3.0 125.6 45.5 2.8 124.5 49.0 2.5 121.7 55.1 2.2 98.3 46.7 2.1 85.1 42.8 2.0
7 136.9 43.8 3.1 133.5 47.5 2.8 132.1 50.1 2.6 130.0 52.7 2.5 104.8 45.2 2.3 91.2 43.5 2.1
10 142.8 44.6 3.2 142.1 48.3 2.9 141.1 51.2 2.8 139.1 54.7 2.5 107.7 43.5 2.5 100.9 43.1 2.3

Part 2 - Engineering Data


15 151 42.1 3.6 148.3 46.5 3.2 147.4 48.9 3.0 146.2 51.5 2.8 115.5 42.5 2.7 110.3 42.1 2.6
20 152.9 40.3 3.8 150.2 44.6 3.4 149.8 46.9 3.2 148.4 49.1 3.0 119.9 40.9 2.9 114.9 39.9 2.9

DB
LWT 45 48
CC PI EER CC PI EER
0 71.4 41.9 1.7 41.0 30.4 1.3
5 81.1 44.2 1.8 46.8 32.0 1.5
7 86.4 44.1 2.0 57.7 33.9 1.7
10 92.6 41.2 2.2 63.5 34.5 1.8
15 95 37.6 2.5 65.3 31.3 2.1
20 97.3 34.8 2.8 70.3 28.5 2.5
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.

31
MBT Confidential
Aqua thermal
MC-SU180-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 163.8 48.5 3.4 163.1 51.1 3.2
5 188.2 52.0 3.6 186.3 54.7 3.4
7 199.1 52.2 3.8 197.6 55.0 3.6
10 151.7 37.3 4.1 151.8 32.0 4.7 153.3 30.5 5.0 151.6 34.9 4.3 212.0 52.7 4.0 223.5 59.2 3.8
15 168.1 32.8 5.1 168.2 32.5 5.2 168.0 31.6 5.3 168.2 29.7 5.7 247.4 51.4 4.8 254.4 56.4 4.5
20 184.5 28.4 6.5 184.5 32.9 5.6 182.6 30.6 6.0 182.3 29.3 6.2 258.5 48.6 5.3 267.8 56.3 4.8

DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 156.5 50.5 3.1 152.1 50.4 3.0 148.2 48.8 3.0 136.7 59.3 2.3 114.7 55.3 2.1 93.8 50.0 1.9
Midea Aqua thermal Engineering Data Book

5 183.5 56.3 3.3 180.6 57.7 3.1 174.9 59.1 3.0 161.7 64.7 2.5 139.8 60.7 2.3 121.9 56.7 2.2
7 195.6 57.2 3.4 192.4 59.6 3.2 184.2 60.2 3.1 164.0 56.0 2.9 147.7 54.0 2.7 131.7 50.3 2.6
10 215.1 59.4 3.6 205.8 60.0 3.4 199.7 60.7 3.3 187.5 59.5 3.1 163.3 54.8 3.0 144.4 50.0 2.9
15 234.6 58.8 4.0 223.4 51.4 4.3 216.5 50.5 4.3 208.4 56.9 3.7 185.1 56.3 3.3 163.7 50.7 3.2
20 254.3 59.0 4.3 242.7 47.1 5.2 234.6 49.7 4.7 224.7 55.2 4.1 204.7 55.9 3.7 184.2 52.5 3.5

DB
LWT 45 48
CC PI EER CC PI EER
0 65.6 40.3 1.6 36.0 24.4 1.5
5 96.9 48.6 2.0 58.6 33.2 1.8
7 115.7 45.5 2.5 78.6 37.6 2.1
10 125.8 45.0 2.8 90.2 38.5 2.3
15 145.6 46.9 3.1 110.0 38.6 2.9
20 161.3 48.0 3.4 121.7 38.8 3.1
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.

32
MBT Confidential
Aqua thermal
MC-SU180M-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 163.8 50.0 3.3 163.1 52.6 3.1
5 188.2 53.5 3.5 186.3 56.2 3.3
7 199.1 53.7 3.7 197.6 56.5 3.5
10 151.7 38.8 3.9 151.8 33.5 4.5 153.3 32.0 4.8 151.6 36.4 4.2 212.0 54.2 3.9 223.5 60.7 3.7
15 168.1 34.3 4.9 168.2 34.0 4.9 168.0 33.1 5.1 168.2 31.2 5.4 247.4 52.9 4.7 254.4 57.9 4.4
20 184.5 29.9 6.2 184.5 34.4 5.4 182.6 32.1 5.7 182.3 30.8 5.9 258.5 50.1 5.2 267.8 57.8 4.6

DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 156.5 52 3.0 152.1 51.9 2.9 148.2 50.3 2.9 136.7 60.8 2.2 114.7 56.8 2.0 93.8 51.5 1.8
5 183.5 57.8 3.2 180.6 59.2 3.1 174.9 60.6 2.9 161.7 66.2 2.4 139.8 62.2 2.2 121.9 58.2 2.1
7 195.6 58.7 3.3 192.4 61.1 3.1 184.2 61.7 3.0 164.0 57.5 2.9 147.7 55.5 2.7 131.7 51.8 2.5
10 215.1 60.9 3.5 205.8 61.5 3.3 199.7 62.2 3.2 187.5 61.0 3.1 163.3 56.3 2.9 144.4 51.5 2.8

Part 2 - Engineering Data


15 234.6 60.3 3.9 223.4 52.9 4.2 216.5 52.0 4.2 208.4 58.4 3.6 185.1 57.8 3.2 163.7 52.2 3.1
20 254.3 60.5 4.2 242.7 48.6 5.0 234.6 51.2 4.6 224.7 56.7 4.0 204.7 57.4 3.6 184.2 54.0 3.4

DB
LWT 45 48
CC PI EER CC PI EER
0 65.6 41.8 1.6 36.0 25.9 1.4
5 96.9 50.1 1.9 58.6 34.7 1.7
7 115.7 47.0 2.5 78.6 39.1 2.0
10 125.8 46.5 2.7 90.2 40.0 2.3
15 145.6 48.4 3.0 110.0 40.1 2.7
20 161.3 49.5 3.3 121.7 40.3 3.0
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.

33
MBT Confidential
Aqua thermal
6 Performance Adjustment Factors
6.1 Ethylene and Propylene Glycol factors
The antifreeze must be required according to anyone condition as following:
The ambient temperature is below 0 ⁰C;
Don’t start up the unit for a long time.
The power supply was cut off and needn’t change the water in system.

A glycol solution is required when the unit with condition as mentioned. The use of glycol will reduce the performance of the
unit depending on concentration.

Concentration Modification coefficient


of ethylene Freezing point (°C)
Cooling capacity Power input Water resistance Water flow
glycol (%)
0 1.000 1.000 1.000 1.000 0
Midea Aqua thermal Engineering Data Book

10 0.984 0.998 1.118 1.019 -4


20 0.973 0.995 1.268 1.051 -9
30 0.965 0.992 1.482 1.092 -16
40 0.960 0.989 1.791 1.145 -23
50 0.950 0.983 2.100 1.200 -37

Concentration Modification coefficient


of propylene Freezing point (°C)
Cooling capacity Power input Water resistance Water flow
glycol (%)
0 1.000 1.000 1.000 1.000 0
10 0.976 0.996 1.071 1.00 -3
20 0.961 0.992 1.189 1.016 -7
30 0.948 0.988 1.380 1.034 -13
40 0.938 0.984 1.728 1.078 -22
50 0.925 0.975 2.150 1.125 -35

6.2 Evaporator temperature drop factors


Performance tables are based on a 5⁰C temperature drop through the evaporator. Temperature drops outside this range can
affect the control system’s capability to maintain acceptable control and are not recommended.

6.3 Altitude correction factors


Performance tables are based at sea level. Elevations other than sea level affect the performance of the unit. The decreased air
density will reduce condenser capacity and reduce the unit’s performance. Maximum allowable altitude is 1800meters.

6.4 Fouling factor


Fouling refers to the accumulation of unwanted material on solid surfaces, most often in an aquatic environment. The fouling
material can consist of either living organisms (biofouling) or a non-living substance (inorganic or organic). Fouling is usually
distinguished from other surface-growth phenomena in that it occurs on a surface of a component, system or plant performing a
defined and useful function, and that the fouling process impedes or interferes with this function.

Other terms used in the literature to describe fouling include: deposit formation, encrustation, crudding, deposition, scaling,
scale formation, slagging, and sludge formation. The last six terms have a more narrow meaning than fouling within the scope of

34
MBT Confidential
Aqua thermal
the fouling science and technology, and they also have meanings outside of this scope; therefore, they should be used with
caution.

Fouling phenomena are common and diverse, ranging from fouling of ship hulls, natural surfaces in the marine environment
(marine fouling), fouling of heat-transfer components through ingredients contained in the cooling water or gases, and even the
development of plaque or calculus on teeth, or deposits on solar panels on Mars, among other examples.

Foreign matter in the chilled water system will adversely affect the heat transfer capability of the evaporator, and could increase
the pressure drop and reduce the water flow. To provide optimum unit operation, proper water treatment must be maintained.
Refer to the able as following.

Fouling Factor
Difference of water
ALTITUDE
inlet and outlet temp. 0.018 m2. ⁰C /kW 0.044 m2. ⁰C /kW 0.086 m2. ⁰C /kW 0.172 m2. ⁰C /kW
(m)
(⁰C)
C P C P C P C P

3 1.036 1.077 1.019 1.076 0.991 0.975 0.963 0.983


4 1.039 1.101 1.022 1.080 0.994 0.996 0.971 0.984
Sea level
5 1.045 1.105 1.028 1.086 1.000 1.000 0.977 0.989

Part 2 - Engineering Data


6 1.051 1.109 1.034 1.093 1.006 1.004 0.983 0.994
3 1.024 1.087 1.008 1.064 0.980 0.984 0.951 0.991
4 1.027 1.111 1.011 1.068 0.983 1.005 0.959 0.992
600
5 1.034 1.115 1.017 1.074 0.989 1.009 0.965 0.997
6 1.043 1.115 1.026 1.084 0.998 1.009 0.973 0.999
3 1.013 1.117 0.996 1.052 0.969 1.011 0.942 1.002
4 1.015 1.118 0.998 1.055 0.971 1.012 0.948 1.003
1200
5 1.023 1.122 1.006 1.063 0.979 1.015 0.955 1.005
6 1.031 1.125 1.015 1.072 0.987 1.018 0.962 1.007
3 1.002 1.128 0.986 1.042 0.959 1.021 0.935 1.007
4 1.005 1.129 0.989 1.045 0.962 1.022 0.941 1.010
1800
5 1.012 1.132 0.995 1.051 0.968 1.024 0.945 1.012

6 1.018 1.134 1.001 1.058 0.974 1.026 0.949 1.014


Abbreviations:
C: Cooling capacity
P: Power input

35
MBT Confidential
Aqua thermal
7 Hydronic Performance
MC-SU75-RN8L-B

180

160

140
Water pressure drop (kPa)

120

100

80
Midea Aqua thermal Engineering Data Book

60

40

20

0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Water flow rate (m3/h)

MC-SU90-RN8L-B

180

160

140
Water pressure drop (kPa)

120

100

80

60

40

20

0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Water flow rate (m3/h)

36
MBT Confidential
Aqua thermal
MC-SU140-RN8L-B

180

160

140
Water pressure drop (kPa)

120

100

80

60

40

20

0
0 3 6 9 12 15 18 21 24 27 30 33 36
Water flow rate (m3/h)

Part 2 - Engineering Data


MC-SU180-RN8L-B

250

200
Water pressure drop (kPa)

150

100

50

0
0 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45
Water flow rate (m3/h)

37
MBT Confidential
Aqua thermal
MC-SU75M-RN8L-B

300

250
External static pressure(kPa)

200

150

100

50

0
Midea Aqua thermal Engineering Data Book

6 8 10 12 14 16
Water flow rate (m3/h)

MC-SU90M-RN8L-B

500

450

400
External static pressure(kPa)

350

300

250

200

150

100

50

0
0 2 4 6 8 10 12 14 16 18 20
Water flow rate (m3/h)

38
MBT Confidential
Aqua thermal
MC-SU140M-RN8L-B

160

140

120
External static pressure(kPa)

100

80

60

40

20

Part 2 - Engineering Data


14 16 18 20 22 24 26 28
Water flow rate (m3/h)

MC-SU180M-RN8L-B

400

350

300
External static pressure(kPa)

250

200

150

100

50

0
18 20 22 24 26 28 30 32 34 36
Water flow rate (m3/h)

39
MBT Confidential
Aqua thermal
8 Octave Band Levels

Side Two

Side three Side One

Electric control box Side Four


Midea Aqua thermal Engineering Data Book

Test condition:Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C
MC-SU75-RN8L-B

90

80
Octave band sound level: dB(A)

70
NC-70

60
NC-60

50
NC-50
40
NC-40

30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)

40
MBT Confidential
Aqua thermal
MC-SU75M-RN8L-B

90

80

Octave band sound level: dB(A) 70


NC-70

60
NC-60
50
NC-50
40
NC-40

30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000

Part 2 - Engineering Data


Octave band central frequency (Hz)

MC-SU90-RN8L-B

90

80
Octave band sound level: dB(A)

70
NC-70

60
NC-60
50
NC-50

40
NC-40
30
NC-30

20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)

41
MBT Confidential
Aqua thermal
MC-SU90M-RN8L-B

90

80
Octave band sound level: dB(A)
70
NC-70

60
NC-60
50
NC-50
40
NC-40

30
NC-30
Midea Aqua thermal Engineering Data Book

20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)

MC-SU140-RN8L-B

90

80

70
Octave band sound level: dB(A)

NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)

42
MBT Confidential
Aqua thermal
MC-SU140M-RN8L-B

90

80

70
NC-70

60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000

Part 2 - Engineering Data


Side Two

Side Three Side One

Electric control box

Side Four

Test condition:Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C

43
MBT Confidential
Aqua thermal
MC-SU180-RN8L-B

90

80

70
NC-70
Octave band sound level (dB)

60
NC-60

50
NC-50

40
NC-40
Midea Aqua thermal Engineering Data Book

30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)
MC-SU180M-RN8L-B
90

80

70
Octave band sound level (dB)

NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)

44
MBT Confidential
Aqua thermal

Part 3
User Interface
Field Settings
1 User Interface Field Settings ................................................................ 45

Part 3 - Installation and Field Settings

45
MBT Confidential
Aqua thermal
1 User Interface Field Settings
1.1 Introduction
During installation, the unit’s settings and parameters should be configured by the installer to suit the installation
configuration, climate conditions and end-user preferences. The relevant settings are accessible and programmable
through the SERVICE and PROJECT menu on the wired controller’s user interface.

KJRM-120H2/BMWKO-E
Midea Aqua thermal Engineering Data Book

Icon Function
Enter the menu structure from the home page

Navigate the cursor on the display/navigate in the menu structure/ adjust the settings

Turn on or off the space operation mode


Come back to the up level
Long press for unlocking /locking the controller
Go to the next step when programming a schedule in the menu structure / confirm a
selection/enter a submenu in the menu structure

46
MBT Confidential
Aqua thermal
1.2 SERVICE MENU
1.2.1 Structure

For SERVICE Menu


1. STATE QUERY
1. STATE QUERY
2. CLEAR HSITORY ERRORS
3. SETTING ADDRESS 2. CLEAR HISTORY ERRORS
4. HEAT CONTROL CLEAR UNIT HISTORY ERRORS
5. TEMPERATURE COMPENSATION CLEAR ALL HISTORY ERRORS
6. PUMP CONTROL CLEAR LOCK ERRORR
7. MANUAL DEFROST CLEAR RUN TIME
8. LOW OUTLET WATER CONTROL
9. VACUMM SWITCH 3. SETTING ADDRESS
10. ENERGY SAVING SWITCH CONTROLLER ADDRESS
11. DHW ENABLE CONTROL ENABEL
12. FACTORY DATA RESET MODBUS ENABLE
MODBUS ADDRESS

Part 3 - Installation and Field Settings


4. HEAT CONTROL
HEAT1
HEAT2
FORCED HEAT2 OPEN

5. TEMPERATURE COMPENSATION
E9 PROTECT TIME
E9 DETECTION METHOD

6. PUMP CONTROL
FORCED PUMP OPEN
INV PUMP SETTING
PUMP ON/OFF TIME

7. MANUAL DEFROST

8. LOW OUTLETWATER CONTROL

9. VACUUM SWITCH

10. ENERGY SAVING SWITCH

11. DHW ENABLE

12. FACTORY DATA RESET


47
MBT Confidential
Aqua thermal
1.2.2 Service Menu
MENU > Service Menu
Service Menu allows installers to input the system configuration and set the system parameters. Enter the password, using
◄ ► to navigate between digits and using ▼ ▲ to adjust the numerical values, and then press . The password is 234.
SERVICE MENU

PLEASE INPUT THE


PASSWORD

0 0 0
OK

The following pages will be displayed after putting the password.

SERVICE MENU SERVICE MENU SERVICE MENU


STATE QUERY TMEPERATURE COMPENSATION VACUUM SWITCH
CLEAR HISTORY ERRORS PUMP CONTROL ENERGY SAVING SWITCH
Midea Aqua thermal Engineering Data Book

SETTING ADDRESS MANUAL DEFROST DHW ENABLE


HEAT CONTROL LOW OUTLET WATER CONTROL FACTORY DATA RESET
OK 1/3 OK 2/3 OK 3/3

1.2.3 State query


MENU > Service Menu > State query

SERVICE MENU SERVICE MENU SERVICE MENU


STATE QUERY TMEPERATURE COMPENSATION VACUUM SWITCH
CLEAR HISTORY ERRORS PUMP CONTROL ENERGY SAVING SWITCH
SETTING ADDRESS MANUAL DEFROST DHW ENABLE
HEAT CONTROL LOW OUTLET WATER CONTROL FACTORY DATA RESET
OK 1/3 OK 2/3 OK 3/3

STATE QUERY allows installers to check the operation parameters. Press ◄ ► to select the address of units.
STATE QUERY STATE QUERY STATE QUERY
SELECT ADDRESS 07 # H-P PRESSURE 3.83 MPa TZ TEMP -20℃
ODU MODEL 130 kW L-P PRESSURE 1.00 MPa T3 TEMP -20℃
COMP FREQUENCE 50 Hz TP1 DISCHARGE TEMP 30 ℃ T4 TEMP -20℃
COMP1 CURRENT 20 A TP2 DISCHARGE TEMP 30 ℃ T6A TEMP 40℃
COMP2 CURRENT 20 A TH SUCTION TEMP -20 ℃ T6B TEMP 40℃
BACK OK 2/9 BACK 3/9

STATE QUERY STATE QUERY STATE QUERY


TFIN1 TEMP 60 ℃ FAN1 SPEED 850 RPM EXV C 1800P
TFIN2 TEMP 60 ℃ FAN2 SPEED 850 RPM Twi TEMP 30℃
TDSH 30 ℃ FAN3 SPEED 850 RPM Two TEMP 30℃
TSSH 15 ℃ EXV A 1800 P Tw TEMP 30℃
TCSH 15 ℃ EXV B 1800 P TAF1 TEMP 30℃
BACK 4/9 BACK 5/9 BACK 6/9

48
MBT Confidential
Aqua thermal
STATE QUERY STATE QUERY STATE QUERY
TAF2 TEMP 30 ℃ COMP TIME 65535 H DEFROSTING STATE
T5 TEMP 30 ℃ FIX PUMP TIME 65535 H 00 01 02 03 04 05 06 07
COMP TIME1 120 MIN INV PUMP TIME 65535 H 08 09 10 11 12 13 14 15
COMP TIME2 120 MIN ODU SOFTWARE V45 E2 SOFTWARE V45
COMP TIME3 120 MIN HMI SOFTWARE V45 END
BACK 7/9 BACK 8/9 OK 9/9

Note:
1. Tz plate heat exchanger outlet temperature
T3 lowest temperature of condenser tube
T4 ambient temperature
T6A, T6B EVI plate heat exchanger refrigerant temperature
Tfin1, Tfin2 inverter module temperature
TDSH Discharge superheat temperature
TSSH Suction superheat temperature
TCSH Injection superheat temperature
Twi Unit water inlet temperature

Part 3 - Installation and Field Settings


Two Unit water outlet temperature
Tw Total water outlet temperature
Taf1 tank antifreeze temperature
Taf2 Water side antifreeze temperature
T5 Water tank temperature
2. For ODU SOFWARE and HMI SOFTWARE, the version number will vary with product iterations.

1.2.4 Clear history errors


MENU > Service Menu > Clear history errors

SERVICE MENU CLEAR HISTORY ERRORS


STATE QUERY CLEAR UNIT HISTORY ERRORS
CLEAR HISTORY ERROR CLEAR ALL HISTORY ERRORS
SETTING ADDRESS CLEAR LOCK ERROR
HEAT CONTROL CLEAR RUN TIME
OK 1/3 OK

CLEAR HISTORY ERRORS is used to clear the history error codes and component operation time.
CLEAR UNIT HIS ERRS CLEAR ALL HIS ERRS
SELECT ADDRESS 07 DO YOU WANT TO YES
DO YOU WANT TO YES CLEAR?
CLEAR?

OK OK

CLEAR LOCK ERR CLEAR RUN TIME


DO YOU WANT TO YES SELECT ADDRESS 07
CLEAR? CLEAR COMP TIME? NO
CLEAR FIX PUMP TIME? NO
CLEAR INV PUMP TIME? NO

OK OK

49
MBT Confidential
Aqua thermal
1.2.5 Setting address
MENU > Service Menu > Setting address

SERVICE MENU
CONTROLLER 10 #
STATE QUERY ADDRESS
CLEAR HISTORY ERROR CONTROL ENABEL NO
SETTING ADDRESS MODBUS ENABLE NO
HEAT CONTROL MODBUS ADDRESS 10 #
OK 1/3 OK

SETTING ADDRESS is used to set whether the unit can be controlled by wired controller and through MDOBUS. SETTING
ADDRESS can also enter by combining buttons pressing , ► for 3s.

CONTROLLER 10 #
ADDRESS
CONTROL ENABEL NO
MODBUS ENABLE NO
Midea Aqua thermal Engineering Data Book

MODBUS ADDRESS 10 #
OK

CONTROLLER ADDRESS selects the unit address then we can check the parameters about this unit.
If CONTROL ENABLE sets as YES, it means the controller can set all the parameters; if CONTROL ENABLE sets as NO, it
means the controller can only display the parameters.
If the chiller system access to MODBUS system, MODBUS ENABLE should be set as YES. Please note that in this case,
COMTROL ENABLE should be also set as YES, otherwise the units cannot be controlled.
MODBUS ADDRESS set the controller address if the Modbus system is available.

1.2.6 Heat control


MENU > Service Menu > Heat control

SERVICE MENU HEAT CONTROL


STATE QUERY HEAT1
CLEAR HISTORY ERROR HEAT2
SETTING ADDRESS
FORCED HEAT2 OPEN
HEAT CONTROL
OK 1/3 OK

HEAT1 means pipe electric heating in cooling/heating mode.


HEAT2 means tank electric heating in DHW mode.

HEAT1 HEAT2
HEAT1 ENABLE NO ALL HEAT2 DISABLE YES
TEMP- 07 ℃ SELECT ADDRESS 10 #
AUXHEAT1-ON HEAT2-ENABLE NO
TW.HEAT1-ON 25 ℃ T-HEAT2-DELAY 190 MIN
TW.HEAT1-OFF 45 ℃ DT5-HEAT2-OFF 10 ℃
OK 1/2 OK 1/2

50
MBT Confidential
Aqua thermal
HEAT2 FORCED HEAT2 OPEN
T4-HEAT2-ON 10 ℃ SELECTED ADDRESS 10 #
FORCED HEAT2 OPEN NO

00 01 02 03 04 05 06 07 00 01 02 03 04 05 06 07
08 09 10 11 12 13 14 15 08 09 10 11 12 13 14 15
OK 2/2 OK

TEMP-AUXHEAT1-ON sets the ambient temperature below which the pipe heater (field supplied) turns on.
When the leaving water temperature reaches TW. HEAT1-ON, the pipe electric heater (field supplied) turns on
automatically.
When the leaving water temperature reaches TW. HEAT1-OFF, the pipe electric heater (field supplied) turns off
automatically.
If the system is installed with tank booster heater, ALL HEAT2 DISABLE should be set as YES.
HEAT2-ENABLE sets the state of tank booster heater of SELECT ADDRESS.
T-HEAT2-DELAY sets the delay time for tank booster heater to turn on after the compressor starts.
DT5-HEAT2-OFF sets the temperature difference between the actual water temperature and setting temperature above
which the tank booster heater turns off.

Part 3 - Installation and Field Settings


T4_HEAT2_ON sets the ambient temperature that tank booster heater turns on. (00~15 means unit address)
If FORCED HEAT2 OPEN is set as YES, when T5<T5S-1, then tank electric heater turns on; when T5≥T5S, then tank electric
heater off. (00~15 means unit address)

1.2.7 Temperature Compensation


MENU > Service Menu > Temperature Compensation
TEMP COMPENSATION TEMP COMPENSATION
SERVICE MENU
COOL MODE ENABLE YES ℃ HEAT MODE ENABLE YES ℃
TMEPERATURE COMPENSATION T4 COOL-1 T4 HEAT-1
15 ℃ 15 ℃
PUMP CONTROL T4 COOL-2 08 ℃ T4 HEAT-2 08 ℃
MANUAL DEFROST OFFSET-C 10 ℃ OFFSET-H 10 ℃
LOW OUTLET WATER CONTROL
OK 2/3 OK 1/2 OK 2/2

With the help of TEMPERATURE COMPENSATION, water temperature will automatically change as outside air
temperature changes. When outdoor air temperature increases/decreases, the heating load will decrease/increase and
water temperature will decrease/increase automatically. When outdoor air temperature decreases/increases, the cooling
load will decrease/increase and water temperature will increase/decrease automatically.
TEMP COMPENSATION TEMP COMPENSATION
COOL MODE ENABLE YES ℃ HEAT MODE ENABLE YES ℃
T4 COOL-1 15 ℃ T4 HEAT-1 15 ℃
T4 COOL-2 08 ℃ T4 HEAT-2 08 ℃
OFFSET-C 10 ℃ OFFSET-H 10 ℃

OK 1/2 OK 2/2

T4 COOL-1, T4 COOL-2 set the ambient temperature for cooling mode.


T4 HEAT-1, T4 HEAT-2 set the ambient temperature for heating mode.
Offset_c, Offset_h is the temperature difference between current water temperature and T4_cool_1, T4_heat_1
corresponding water temperature.

51
MBT Confidential
Aqua thermal
1.2.8 Pump Control
MENU > Service Menu > Pump Control

SERVICE MENU PUMP CONTROL


TMEPERATURE COMPENSATION FORCED PUMP OPEN
PUMP CONTROL INV PUMP SETTING
MANUAL DEFROST PUMP ON/OFF TIME
LOW OUTLET WATER CONTROL
OK 2/3 OK

FOECED PUMP OPEN FORCED PUMP OPEN


INV PUMP SETTING PUMP ON/OFF TIME
SELECT ADDRESS 0 # SELECT ADDRESS #
07 control
Cannot thePUMP
pumpON TIME 05 MIN
FORCED PUMP OPEN NO SWITCH ON THE before PUMP OFF TIME
NO shutting down. 05 MIN
PUMP
RATIO PUMP 100 #
OK OK OK
Midea Aqua thermal Engineering Data Book

FORCED PUMP OPEN is used to control the fixed frequency pump (filed supplied) operation.

INV PUMP SETTING is used to control the inverter water pump (field supplied) operation, the setting range of RATIO-PUMP is
30%-100%. It should ensure its flow meet the requirement of whole unit, otherwise the unit may be damaged.

PUMP ON TIME sets the pump operation time after the unit stops.

If PUMP OFF TIME sets as 0, the pump will run all the time. Otherwise, the pump will operate intermittently according to the
PUMP ON TIME and PUMP OFF TIME setting.
Set range Default value Adjustment range
PUMP ON TIME 5~60min 5 5
PUMP OFF TIME 0~60min 0 5

1.2.9 Manual Defrost


MENU > Service Menu > Manual Defrost

SERVICE MENU MANUAL DEFROST


TMEPERATURE COMPENSATION SELECT ADDRESS 07 #
PUMP CONTROL MANUAL DEFRIOST NO
MANUAL DEFROST
LOW OUTLET WATER CONTROL
OK 2/3 OK

MANUAL DEFROST can force the unit to enter the defrost mode manually.

If the external unit successfully enters the defrost mode after the “MANUAL DEFROST” is turned on, the defrost icon

will be displayed at homepage of the wired controller.

52
MBT Confidential
Aqua thermal
1.2.10 Low outlet water temperature control
MENU > Service Menu > Low outlet water temperature control
LOW OUTLET WATER CTRL
SERVICE MENU
MIN TEMP FOR COOL 50℃
TMEPERATURE COMPENSATION HISTORICAL SETTING
PUMP CONTROL 04/06/2020 11:30A 5℃
MANUAL DEFROST 04/06/2020 11:30A 5℃
LOW OUTLET WATER CONTROL 04/06/2020 11:30A 5℃
OK 2/3 OK

At this page, the historical minimum water outlet temperature setting (setting range 0-20℃) can be viewed.
LOW OUTLET WATER CTRL
MIN TEMP FOR COOL 50℃
HISTORICAL SETTING
04/06/2020 11:30A 5℃
04/06/2020 11:30A 5℃
04/06/2020 11:30A 5℃
OK

Part 3 - Installation and Field Settings


MIN TEMP FOR COOL sets the lowest water temperature for cooling mode. Please notice that When the setting
temperature is less than 5℃, antifreeze liquid should be added in the water system.
LOW OUTLET WATRER CONTROL

The setting temp is below 5 degrees.


please confirm whether it is an
antifreeze system?

OK

1.2.11 Vacuum switch


MENU > Service Menu > Vacuum switch

SERVICE MENU VACUUM SWITCH


VACUUM SWITCH VACUUM SWITCH NO
ENERGY SAVING SWITCH
DHW ENABLE
FACTORY DATA RESET
OK 3/3 OK

VACUUM SWITCH is used for vacuuming.

1.2.12 Energy saving mode


MENU > Service Menu > Energy saving mode
ENERGY SAVING SWITCH
SERVICE MENU
SAVING SWITCH 80%
VACUUM SWITCH HISTORICAL SETTING
ENERGY SAVING SWITCH 04/06/2020 11:30A 80%
DHW ENABLE 04/06/2020 11:30A 80%
FACTORY DATA RESET 04/06/2020 11:30A 80%
OK 3/3 OK

For projects with temporary electricity supply restrictions, the outdoor unit supports 7 levels of energy management which
53
MBT Confidential
Aqua thermal
can be set to output 40-100% capacity. It prevents tripping during electricity supply restriction conditions and remains
system continue to operate. The historical energy saving switch setting can be viewed.

1.2.13 DHW ENABLE


MENU > Service Menu > DHW ENABLE
Domestic hot water function can be customized.
DHW ENABLE
DHW ENABLE NO

OK

1.2.14 Factory data reset


Midea Aqua thermal Engineering Data Book

MENU > Service Menu > Factory data reset


Factory data reset is used to reset all the data to the factory default setting.
FACTORY DATA RESET
DO YOU WANT TO YES
RESET?

OK

54
MBT Confidential
Aqua thermal
1.3 PROJECT MENU
1.3.1 Structure

For PROJECT Menu


1. SET UNIT-AIRCONDITIONING 1. SET UNIT-AIRCONDITIONING
2. SET PARALLEL UNIT TWO_COOL_DIFF
3. SET UNIT PROTECTION TWO_HEAT_DIFF
4. SET DEFROSTING DT5_ON
5. SET E9 TIME DTIS5
6. INV PUMP RATIO DtTws
7. CHECK PARTS
2. SET PARALLEL UNIT
TIM_CAP_ADJ
TW_COOL_DIFF
TW_HEAT_DIF
RATIO_COOL_FIRST
RATIO_HEAT_FIRST

Part 3 - Installation and Field Settings


3. SET UNIT PROTECTION
T_DIFF_PRO
TWI_O_ABNORMAL

4. SET DEFROSTING
T_FROST
T_DEFROST_IN
T_DEFROST_OUT

5. SET E9 TIME
E9 PROTECT TIME
E9 DETECTION METHOD

6. INV PUMP RATIO


MIN RATIO
MAX RATIO

55
MBT Confidential
t corresponding item and press “ ◄” or “ ►” to select restore or not. Press
” to back.
Aqua thermal
1.3.2
SETTING Project Menu
MENU > Project Menu
ntact us.Project Menu allows installers to input the system configuration and set the system parameters. Enter the password, using
◄►
and press “ to navigate
” to between
entry. The screen
digits and using ▼ ▲ to
prompts toadjust
enter the
thenumerical
password, as and then press OK. The password is 9877.
values,
PROJECT MENU

PLEASE INPUT THE


PASSWORD

0 0 0 0
OK

The query interface


The following pages willasbefollows is after
displayed displayed
puttingif the
thepassword.
input is correct:

PROJECT MENU PROJECT MENU


SET UNIT AIRCONDITIONING SET E9 TIME
SET PARALLEL UNIT INV PUMP RATIO
Midea Aqua thermal Engineering Data Book

SET UNIT PROTECTION CHECK PARTS


SET DEFROSTING
OK 1/2 OK 2/2

1.3.3 SET UNIT-AIRCONDITIONING


MENU > Project Menu > SET UNIT-AIRCONDITIONING
SET UNIT
TWO_COOL_DIFF 2 ℃
TWO_HEAT_DIFF 2 ℃
DT5_ON 8 ℃
DTIS5 10 ℃
DtTws 1 ℃
OK

TWO_COOL_DIFF sets the minimum temperature difference between the leaving water temperature (Two) and the leaving
water set temperature (TwoS) above which the unit will start for cooling mode. When Two - TwoS ≥ TWO_COOL_DIFF,
unit starts. When TwoS - Two ≥ 2 lasts for 5s, unit stops.

TWO_HEAT_DIFF sets the minimum temperature difference between the leaving water temperature (Two) and the leaving
water set temperature (TwoS) above which the unit will start for heating mode. When TwoS – Two ≥ TWO_HEAT_DIFF,
unit starts. When Two - TwoS ≥ 2 lasts for 5s, unit stops.

If unit is customized with the DHW function, when TempW_heat_Min_n≤T5<Min(T5S, TempW_heat_Max_n)-dT5_ON


and Two<Min(T5S, TempW_heat_Max_n)-2, then DHW mode is on.
Note:
The value of TempW_heat_Min_n, T5S, TempW_heat_Max_n are related to the ambient temperature, which are already
fixed in the program.
T5 means the water tank temperature
T5S means the setting temperature of DHW mode

The target leaving water temperature of DHW mode is Twos=T5S+DT1S5. If Two>TempW_heat_Max_n, then DHW mode is
off.

56
MBT Confidential
Aqua thermal
DtTws is reserved.

tting: 1.3.4 SET PARALLEL UNIT


MENU >and
RALLEL UNIT” Project
pressMenu
“ > SET
” toPARALLEL UNIT as follows:
entr y. Display
SET PAPALLEL UNIT
TIM_CAP_ADJ 180 S
TW_COOL_DIFF 2 ℃
TW_HEAT_DIFF 2 ℃
RATIO_COOL_FIRST 0 %
RATIO_HEAT_FIRST 50 %
OK

TIM_CAP_ADJ sets the period of capacity adjustment

TW_COOL_DIFF sets the minimum temperature difference between the total leaving water temperature (Tw) and the total
leaving water set temperature (TwS) above which the unit will start for cooling mode. When Tw - TwS ≥ TW_COOL_DIFF
+ 1, unit starts. When TwoS - Tw ≥ 2 lasts for 5s, unit stops.

Part 3 - Installation and Field Settings


TW_HEAT_DIFF sets the minimum temperature difference between the total leaving water temperature (Tw) and the total
leaving water set temperature (TwS) above which the unit will start for heating mode. When TwS – Tw ≥ TW_HEAT_DIFF
+ 1, unit starts. When Tw - TwS ≥ 1 lasts for 5s, unit stops.

RATIO_COOL_FIRST sets the number of initial startup units for cooling mode.

RATIO_HEAT_FIRST sets the number of initial startup units for heating mode.

1.3.5 SET UNIT PROTECTION


MENU > Project Menu > SET UNIT PROTECTION
SET UNIT PROTECTION
T_DIFF_PRO 12 ℃
TWI_O ABNORMAL 2 ℃

OK

T_DIFF_PRO set the absolute difference between entering water temperature (Twi) and leaving water temperature (Two).
If |Twi - Two |≥ T_DIFF_PRO, unit stops and error code P9 appears. When |Twi - Two |≤ 6, error code
disappears.

TWI_O_ABNORMAL sets the difference between entering water temperature (Twi) and leaving water temperature (Two).
For cooling mode, if Two – Twi ≥ TWI_O_ABNORMAL and lasts for 20min, unit stops and error code PA appears. If Two –
Twi ≤ TWI_O_ABNORMAL – 1, error code disappears. For heating mode, if Twi – Two ≤ TWI_O_ABNORMAL and lasts
for 20min, unit stops and error code PA appears. If Two – Twi > 1 - TWI_O_ABNORMAL, error code disappears.

57
MBT Confidential
Aqua thermal
1.3.6 SET DEFROSTING
MENU > Project Menu > SET DEFROSTING
SET DEFROSTING
T_FROST 35 min
T_DEFROST_IN 0 ℃
T_FROST_OUT 0 ℃

OK

T_FROST sets the time between the end of the last defrost mode and the beginning of the next defrost mode.

T_DEFROST_IN sets the temperature for T3 of entering defrosting mode. When T3 reaches T_DEFROST_IN, unit enters
defrosting mode.

T_FROST_OUT sets the temperature for T3 of exiting defrosting model. When T3 reaches T_DEFROST_IN, unit exits
Midea Aqua thermal Engineering Data Book

defrosting mode.
1.3.7 DHW time setting(Customized)
MENU > Project Menu > SET DHW TIME

COOL MAX TIME sets the maximum operation time for cooling mode when DHW requirement exists.
COOL MIN TIME sets the minimum operation time for cooling mode when DHW requirement exists.
HEAT MAX TIME sets the maximum operation time for heating mode when DHW requirement exists.
HEAT MIN TIME sets the minimum operation time for heating mode when DHW requirement exists.
DHW MIN TIME sets the minimum operation time for DHW mode.
DHW MAX TIME sets the maximum operation time for DHW mode.

g: 1.3.8 SET E9 TIME


” and press
MENU “ > Project
” to Menu
entr y.> Display as follows:
SET E9 TIME
SET E9 TIME
E9 PROTECT TIME 10 S
E9 DETECTION METHOD 1 #

OK

E9 PROTECT TIME sets the delay time of water flow detection. When unit starts, water flow will not be detected until at least
(2+ E9 PROTECT TIME/60) minutes have elapsed.

E9 DETECTION METHOD sets the method of water flow detection. If “1” is selected, the water flow switch is detected after
58
MBT Confidential
Aqua thermal
water pump starts. If “2” is selected, the water flow switch is both detected before and after the water pump starts.

1.3.9 INV PUMP RATIO


MENU > Project Menu > INV PUMP RATIO
INV PUMP RATIO
MIN RATIO 70 %
MAX RATIO 100 %

OK

MIN RATIO sets the minimum output ratio of inverter pump which is installed in the main water pipe.

MAX RATIO sets the maximum output ratio of inverter pump which is installed in the main water pipe.

1.3.10 CHECK PARTS


MENU > Project Menu > CHECK PARTS

Part 3 - Installation and Field Settings


State of different parts can be checked in this menu.
CHECK PARTS CHECK PARTS CHECK PARTS
SELECT ADDRESS 07 # SV2 STATE OFF SV8B STATE OFF
FIX PUMP STATE OFF SV4 STATE OFF HEAT1 STATE OFF
INV PUMP STATE 80% SV5 STATE OFF HEAT2 STATE OFF
FOUR-WAY VALVE OFF SV6 STATE OFF COIL VALVE OFF
SV1 STATE OFF SV8A STATE OFF
BACK 1/3 BACK 2/3 BACK 3/3

1.4 Parameters setting


Menu Parameters Setting range Default value Adjustment range
TEMP_AUXHEAT_ON 0~10℃ 5℃ 1℃
TW_HEAT1_ON 0~50℃ 25℃ 1℃
TW_HEAT1_OFF 0~50℃ 45℃ 1℃
T_HEAT2_DELAY 60~240min 90min 5min
DT5_HEAT2_OFF 2~10℃ 5℃ 1℃
T4_HEAT2_ON -5~20℃ 5℃ 1℃
T4_COOL_1 15~30℃ 25℃ 1℃
T4_COOL_2 35~45℃ 40℃ 1℃
Service menu OFFSET_C 0~15℃ 10℃ 1℃
T4_HEAT_1 -10~10℃ 2℃ 1℃
T4_ HEAT _2 15~30℃ 15℃ 1℃
OFFSET_H 0~30℃ 10℃ 1℃
RATIO_PUMP 30%~100% 100% 5%
PUMP ON TIME 5~60min 5min 5min
PUMP OFF TIME 0~60min 0min 5min
MIN TEMP FOR COOL 0~20℃ 7℃ 1℃
ENERGY SAVING SWITCH 40~100% 100% 10%

59
MBT Confidential
Aqua thermal
Menu Parameters Setting range Default value Adjustment range
TWO_COOL_DIFF 1℃~5℃ 2℃ 1℃
TWO_HEAT_DIFF 1℃~5℃ 2℃ 1℃
TIM_CAP_ADJ 60~360s 80s 20s
TW_COOL_DIFF 1℃~5℃ 2℃ 1℃
TW_HEAT_DIFF 1℃~5℃ 2℃ 1℃
RATIO_COOL_FIRST 0~100% 50% 5%
RATIO_HEAT_FIRST 0~100% 50% 5%
T_DIFF_PRO 8~15℃ 12℃ 1℃
Project menu
TWI_O_ABNORMAL 1~5℃ 2℃ 1℃
T_FROST 20~120 min 35 min 5min
T_DEFROST_IN -5~5℃ 0℃ 1℃
T_FROST_OUT -10~+10℃ 0℃ 1℃
E9 PROTECT TIME 2~20s 5s 1
Midea Aqua thermal Engineering Data Book

E9 DETECTION METHOD 1~2 1 1


MIN RATIO 40~100% 75% 5%
MAX RATIO 70~100% 100% 5%
dT5_ON 2~10℃ 8℃ 1℃
dT1S5 5~20℃ 10℃ 1℃
Project menu COOL MIN TIME 0.5~24h 0.5h 0.5h
(customized with DHW) COOL MAX TIME 0.5~24h 8h 0.5h
HEAT MIN TIME 0.5~24h 0.5h 0.5h
HEAT MAX TIME 0.5~24h 8h 0.5h

60
MBT Confidential
Ver. 2022-09

Midea Building Technologies Division


Midea Group

Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China
Postal code: 528311
mbt.midea.com www.midea-group.com tsp.midea.com
Note: Product specifications change from time to time as product improvements and developments are released and may vary from those in this