Technical - Manual - Midea - Aqua Thermal - MC - SUxxx - RN8L - B
Technical - Manual - Midea - Aqua Thermal - MC - SUxxx - RN8L - B
Engineering Data
Aqua thermal
MBT Confidential
Aqua thermal
CONTENTS
CONTENTS
1
MBT Confidential
Midea Aqua thermal Engineering Data Book
2
Aqua thermal
MBT Confidential
1 Aqua thermal
Part 1
General Information
1 System introduction ................................................................................... 4
2 Product lineup............................................................................................ 7
3 Nomenclature ............................................................................................ 7
3
MBT Confidential
Aqua thermal
1 System introduction
1.1 System Schematic
Aqua thermal is an integrated air-to-water space heating and space cooling heat pump system. The outdoor heat pump
system extracts heat from the outdoor air and transfers this heat through refrigerant piping to the plate heat exchanger in the
hydronic system. The heated water in the hydronic system circulates to low temperature heat emitters (floor heating loops or
low temperature radiators) to provide space heating. The 4-way valve in the outdoor unit can reverse the refrigerant cycle so
that the hydronic system can provide chilled water for cooling using fan coil units.
The heating capacity of heat pumps decreases with ambient temperature. Aqua thermal is reserved an auxiliary electric
heater control port to provide additional heating capacity for use during extremely cold weather when the heat pump capacity is
insufficient. The auxiliary electric heater also serves as a backup in case of heat pump malfunction and for anti-freeze protection
of the outside water piping in winter.
Legend
Stop valve Pressure gauge Flexible joint Gate valve Automatic discharge valve
4
MBT Confidential
1 Aqua thermal
1.2.2 Space Cooling and Heating through Fan Coil Unit
Stop valve Pressure gauge Flexible joint Gate valve Automatic discharge valve
5
MBT Confidential
Aqua thermal
1.2.3 Space Heating Through Floor Heating Loops and Space Cooling Through Fan Coil Unit
Midea Aqua thermal Engineering Data Book
Legend
Stop valve Pressure gauge Flexible joint Gate valve Automatic discharge valve
Note:
In space cooling mode, the 2-way valve on the floor heating branch circuit is closed to prevent cold water entering the floor heating loops.
6
MBT Confidential
1 Aqua thermal
2 Product lineup
MC-SU75-RN8L-B MC-SU90-RN8L-B MC-SU140-RN8L-B MC-SU180-RN8L-B
Model
MC-SU75M-RN8L-B MC-SU90M-RN8L-B MC-SU140M-RN8L-B MC-SU180M-RN8L-B
Power
380-415V/3Ph/50Hz 380-415V/3Ph/50Hz 380-415V/3Ph/50Hz 380-415V/3Ph/50Hz
supply
Appearance
3 Nomenclature
M C - S U 75 M - R N8 - B
Refrigerant: R32
Series code
C: Chiller
M: Midea
7
MBT Confidential
Aqua thermal
Is corrected Aqua thermal capacity ≥ Required total heat load on outdoor units3
Yes No
Notes:
1. Up to 16 units (8 units for MC-SU180-RN8L-B) can be connected together, giving a system cooling/heating capacity range from 75kW to 2240kW.
2. If the required water temperatures of the heat emitters are not all the same, the Aqua thermal’s outlet water temperature setting should be set at the
highest of the heat emitter required water temperatures. If the water outlet design temperature falls between two temperatures listed in the outdoor
unit's capacity table, calculate the corrected capacity by interpolation.
3. Select Aqua thermal which satisfies both total heating and cooling load requirements.
8
MBT Confidential
1 Aqua thermal
4.2 Modular Chiller Leaving Water Temperature (LWT) Selection
The recommended design LTW ranges for different types of heat emitter are:
For floor heating: 30 to 35⁰C
For fan coil units: 30 to 45⁰C
For low temperature radiators: 40 to 50⁰C
9
MBT Confidential
Midea Aqua thermal Engineering Data Book
10
Aqua thermal
MBT Confidential
Aqua thermal
Part 2
Engineering Data
1 Specifications ........................................................................................... 12
5 Capacity Tables......................................................................................... 18
11
MBT Confidential
Aqua thermal
1 Specifications
Model name MC-SU75-RN8L-B MC-SU90-RN8L-B MC-SU140-RN8L-B MC-SU180-RN8L-B
Power supply V/Ph/Hz 380~415/3/50 380~415/3/50 380~415/3/50 380~415/3/50
Capacity kW 70 82 130 164
Cooling 1 Rated input kW 26.8 27.8 50.5 56
EER 2.61 2.95 2.57 2.93
Capacity kW 75 90 138 180
Heating2 Rated input kW 23.7 28.1 44.5 57
COP 3.16 3.2 3.1 3.16
Type Finned tube Finned tube Finned tube Finned tube
Fan motor type DC motor DC motor DC motor DC motor
Air side heat
Fan motor output W 920 920 1500 920
exchanger
Fan motor quantity 2 2 2 4
Air flow rate m3/h 28500 35000 50000 70000
Midea Aqua thermal Engineering Data Book
Water Cooling °C 0 to 20 0 to 20 0 to 20 0 to 20
outlet
temperature Heating °C 25 to 54 25 to 54 25 to 54 25 to 54
12
MBT Confidential
Aqua thermal
Model name MC-SU75M-RN8L-B MC-SU90M-RN8L-B MC-SU140M-RN8L-B MC-SU180M-RN8L-B
Power supply V/Ph/Hz 380~415/3/50 380~415/3/50 380~415/3/50 380~415/3/50
Capacity kW 69.7 82 129.5 163.0
Cooling 1 Rated input kW 27.3 28.3 51.4 57.7
EER 2.55 2.90 2.52 2.82
Capacity kW 75.4 90 138.6 181.2
Heating2 Rated input kW 24.3 29 45.6 59.1
COP 3.10 3.10 3.04 3.07
Type Finned tube Finned tube Finned tube Finned tube
Fan motor type DC motor DC motor DC motor DC motor
Air side heat
Fan motor output W 920 920 1500 920
exchanger
Fan motor quantity 2 2 2 4
Air flow rate m3/h 28500 35000 50000 70000
Type Plate Plate Plate Plate
Water side
Volume L 5.17 7.05 11.1 6.96×2
heat
Rated water flow m3/h 12.04 15 22.36 28.2
exchanger
Water flow range m3/h 8.0~15.5 10.2 ~ 18 15.6~28.5 20~36.1
Refrigerant type R32 R32 R32 R32
Refrigerant
Refrigerant charge3 kg 9 16 (11.5+4.5) 15.5(11.5+4) 16 (5.5+10.5)*2
temperature Heating °C 25 to 54 25 to 54 25 to 54 25 to 54
13
MBT Confidential
Aqua thermal
Notes:
1. Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C;
2. Outdoor ambient temperature 7°C DB/6°C WB. EWT 40°C, LWT 45°C;
3. The total amount of refrigerant for unit which capacity above 90kW include (factory charged + field charged).
4. Test standard: EN12102-1. Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C
5. Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C
Sound pressure level is the test average measured in a semi-anechoic chamber. The test position is 1m right in front of the unit for four sides and (1+H)/2m
(where H is the height of the unit) above the floor. During in-situ operation, sound pressure levels may be higher as a result of ambient noise.
1000
Test position
H Unit (H+1000)/2
7. Seasonal space heating energy efficiency class tested in average climate conditions.
2 Electrical Characteristics
Outdoor unit Power current Compressor Fan
System Voltage Min. Max. MCA MOP MSC RLA FLA
Hz kW
(V) (V) (V) (A) (A) (A) (A) (A)
Note:
14
MBT Confidential
Aqua thermal
3 Dimensions and Center of Gravity
MC-SU75-RN8L-B, MC-SU75M-RN8L-B
1780
270
390
Water entrancing pipe
190
700 1995
570
960
MC-SU90-RN8L-B, MC-SU90M-RN8L-B
15
MBT Confidential
Aqua thermal
MC-SU140-RN8L-B, MC-SU140M-RN8L-B
2300
86 270
700
520
1135
MC-SU180-RN8L-B, MC-SU180M-RN8L-B
400
870
2221
1320
2753
16
MBT Confidential
Aqua thermal
4 Operating Limits
T4:Ambient temperature(℃)
Two:Leaving water temperature(℃)
4.1 Cooling operating range
②
①
30
outdoor temperature (℃)
30
25
25
20
20
15
15
10
10
5
5
0
0
20 25 30 35 40 45 50 55 60 -5
-5
-10
-10
-15
-15
-20
-20
-25
-25
20 25 30 35 40 45 50 55 60
Outlet water temperature (℃) Outlet water temperature (℃)
Fig. 1-1-2 Heating operating range
17
MBT Confidential
Aqua thermal
5 Capacity Tables
5.1 Heating Capacity Tables
MC-SU75-RN8L-B
DB
LWT -20 -18 -15 -10 -5 0
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 30.9 13.2 2.3 41.3 15.3 2.7 42.2 15.4 2.7 43.2 15.5 2.8 45.7 15.5 2.9 49.5 15.8 3.1
30 31.2 15.2 2.1 40.8 15.9 2.6 42.1 16.0 2.6 43.3 16.1 2.7 45.9 16.3 2.8 48.6 16.5 2.9
35 30.2 16.1 1.9 39.2 17.3 2.3 40.3 17.4 2.3 41.4 17.5 2.4 46.7 18.7 2.5 47.8 17.3 2.8
40 23.7 14.1 1.7 35.7 19.4 1.8 37.2 19.6 1.9 38.7 19.8 2.0 44.6 20.4 2.2 46.1 18.4 2.5
45 18.8 13.2 1.4 32.8 20.2 1.6 34.5 20.4 1.7 36.3 20.6 1.8 40.4 21.0 1.9 44.5 19.5 2.3
48 25.6 19.8 1.3 29.1 20.2 1.4 32.6 20.4 1.6 37.8 21.0 1.8 42.6 20.1 2.1
50 28.8 20.1 1.4 29.7 19.5 1.5 35.2 20.9 1.7 40.8 20.7 2.0
54 23.9 16.3 1.5 28.4 17.5 1.6 32.9 17.4 1.9
Midea Aqua thermal Engineering Data Book
DB
LWT 5 7 10 15 20 25
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 54.1 16.4 3.3 82.2 23.2 3.5 83.6 20.8 4.0 96.9 23.2 4.2 100.3 22.8 4.4 106.2 22.8 4.6
30 53.2 16.9 3.2 80.7 22.9 3.5 82.2 21.5 3.8 91.4 22.5 4.1 96.5 22.6 4.3 104.7 23.1 4.5
35 55.1 18.3 3.0 74.7 21.3 3.5 76.9 21.0 3.7 88.2 22.4 3.9 93.4 22.5 4.1 102.5 22.8 4.5
40 55.7 19.6 2.8 74.9 23.3 3.2 77.8 22.9 3.4 85.7 23.5 3.7 87.4 22.0 4.0 96.1 22.4 4.3
45 56.4 21.0 2.7 75.0 23.7 3.2 76.2 23.5 3.2 79.0 23.1 3.4 85.2 23.0 3.7 93.4 23.5 4.0
48 56.2 21.4 2.6 66.2 23.0 2.9 70.2 23.2 3.0 51.0 15.6 3.3 79.9 22.0 3.6 86.2 22.7 3.8
50 56.1 21.9 2.6 65.0 23.1 2.8 68.0 22.9 3.0 38.4 12.3 3.1 76.2 21.5 3.6 79.4 21.5 3.7
54 45.2 18.3 2.5 63.8 23.0 2.8 68.0 23.2 2.9 18.6 6.2 3.0 22.6 7.3 3.1 23.5 7.5 3.2
DB
LWT 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER
25 113.6 21.6 5.2 114.4 19.4 5.9 115.9 18.6 6.2 114.3 17.7 6.5
30 115.4 23.0 5.0 118.6 20.8 5.7 123.3 21.1 5.9 117.1 19.6 6.0
35 114.2 23.7 4.8 121.5 22.9 5.3 126.2 23.3 5.4 118.6 21.0 5.6
40 105.7 23.9 4.4 112.5 22.5 5.0 117.9 23.0 5.1 110.3 20.8 5.3
45 95.4 22.6 4.2 102.8 21.6 4.8 105.4 21.7 4.9 99.3 19.8 5.0
48 70.8 17.5 4.0 74.7 16.5 4.5 77.8 16.8 4.6 71.7 15.1 4.8
50 56.7 14.4 3.9 59.1 14.0 4.2 63.4 14.6 4.4 57.8 12.7 4.6
54 25.4 7.8 3.3 28.5 8.4 3.4 40.2 11.5 3.5
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.
18
MBT Confidential
Aqua thermal
MC-SU75M-RN8L-B
DB
LWT -20 -18 -15 -10 -5 0
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 30.9 14.7 2.1 41.3 16.8 2.5 42.2 16.9 2.5 43.2 17.0 2.5 45.7 17.0 2.7 49.5 17.3 2.9
30 31.2 16.7 1.9 40.8 17.4 2.3 42.1 17.5 2.4 43.3 17.6 2.5 45.9 17.8 2.6 48.6 18.0 2.7
35 30.2 17.6 1.7 39.2 18.8 2.1 40.3 18.9 2.1 41.4 19.0 2.2 46.7 20.2 2.3 47.8 18.8 2.5
40 23.7 15.6 1.5 35.7 20.9 1.7 37.2 21.1 1.8 38.7 21.3 1.8 44.6 21.9 2.0 46.1 19.9 2.3
45 18.8 14.7 1.3 32.8 21.7 1.5 34.5 21.9 1.6 36.3 22.1 1.6 40.4 22.5 1.8 44.5 21.0 2.1
48 25.6 21.3 1.2 29.1 21.7 1.3 32.6 21.9 1.5 37.8 22.5 1.7 42.6 21.6 2.0
50 28.8 21.6 1.3 29.7 21.0 1.4 35.2 22.4 1.6 40.8 22.2 1.8
54 23.9 17.8 1.3 28.4 19.0 1.5 32.9 18.9 1.7
DB
LWT 5 7 10 15 20 25
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 54.1 17.9 3.0 82.2 24.7 3.3 83.6 22.3 3.7 96.9 24.7 3.9 100.3 24.3 4.1 106.2 24.3 4.4
30 53.2 18.4 2.9 80.7 24.4 3.3 82.2 23.0 3.6 91.4 24.0 3.8 96.5 24.1 4.0 104.7 24.6 4.3
DB
LWT 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER
25 113.6 23.1 4.9 114.4 20.9 5.5 115.9 20.1 5.8 114.3 19.2 6.0
30 115.4 24.5 4.7 118.6 22.3 5.3 123.3 22.6 5.5 117.1 21.1 5.5
35 114.2 25.2 4.5 121.5 24.4 5.0 126.2 24.8 5.1 118.6 22.5 5.3
40 105.7 25.4 4.2 112.5 24.0 4.7 117.9 24.5 4.8 110.3 22.3 4.9
45 95.4 24.1 4.0 102.8 23.1 4.5 105.4 23.2 4.5 99.3 21.3 4.7
48 70.8 19 3.7 74.7 18.0 4.2 77.8 18.3 4.3 71.7 16.6 4.3
50 56.7 15.9 3.6 59.1 15.5 3.8 63.4 16.1 3.9 57.8 14.2 4.1
54 25.4 9.3 2.7 28.5 9.9 2.9 40.2 13.0 3.1
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.
19
MBT Confidential
Aqua thermal
MC-SU90-RN8L-B
DB
LWT -20 -18 -15 -10 -7 4
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 44.7 21.1 2.1 49.6 21.8 2.3 56.8 22.8 2.5 67.4 23.2 2.9 73.7 23.5 3.1 79.1 24.3 3.3
30 43.9 21.7 2.0 48.7 22.4 2.2 55.8 23.4 2.4 66.2 23.9 2.8 72.4 24.2 3.0 77.7 25.0 3.1
35 42.7 24.8 1.7 47.0 25.3 1.9 53.6 25.9 2.1 63.9 26.1 2.5 70.2 26.2 2.7 75.5 26.3 2.9
40 39.7 26.6 1.5 44.2 27.0 1.6 51.0 27.6 1.8 61.6 28.2 2.2 68.0 28.6 2.4 73.7 28.7 2.6
42 42.4 26.7 1.6 48.9 27.3 1.8 59.9 28.6 2.1 66.5 29.4 2.3 72.2 29.5 2.4
45 45.8 26.9 1.7 57.2 29.2 2.0 64.1 30.6 2.1 69.9 30.8 2.3
47 50.6 27.1 1.9 56.6 28.4 2.0 63.6 29.3 2.2
48 48.6 27.7 1.8 54.5 29.0 1.9 61.2 29.9 2.0
50 48.0 28.0 1.7 55.3 29.3 1.9
54 47.5 29.6 1.6
Midea Aqua thermal Engineering Data Book
DB
LWT 2 7 15 20 25 30
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 89.9 25.9 3.5 102.0 23.8 4.3 104.8 23.1 4.5 104.9 21.7 4.8 102.8 20.0 5.2 100.0 17.6 5.7
30 88.3 26.6 3.3 101.4 24.5 4.1 103.9 23.7 4.4 104.0 22.3 4.7 101.9 20.5 5.0 99.2 18.1 5.5
35 86.3 26.4 3.3 100.2 26.4 3.8 102.4 24.9 4.1 102.3 23.5 4.3 100.2 20.7 4.8 96.0 18.3 5.2
40 84.9 28.8 2.9 95.7 27.0 3.5 99.1 25.8 3.8 99.6 24.5 4.1 99.3 21.5 4.6 94.6 18.7 5.1
42 83.5 29.8 2.8 92.8 27.5 3.4 98.5 26.8 3.7 98.9 25.0 4.0 98.3 21.8 4.5 90.7 18.8 4.8
45 81.5 31.3 2.6 90.4 28.8 3.1 97.7 28.2 3.5 98.2 25.5 3.9 96.8 22.3 4.3 84.9 18.8 4.5
47 77.6 31.1 2.5 86.5 31.2 2.8 93.5 27.1 3.5 90.1 22.8 3.9 83.7 19.4 4.3 74.6 17.4 4.3
48 74.6 31.8 2.3 83.2 31.9 2.6 89.9 27.6 3.3 86.6 23.3 3.7 80.5 19.8 4.1 71.8 17.8 4.0
50 70.0 32.1 2.2 78.3 32.2 2.4 84.7 27.2 3.1 79.1 22.2 3.6 75.6 19.2 3.9 63.0 17.1 3.7
54 59.9 33.3 1.8 67.0 34.0 2.0 73.9 27.0 2.7 70.2 21.2 3.3 58.9 15.7 3.8 47.0 14.4 3.3
DB
LWT 35 40 43
HC PI EER HC PI EER HC PI EER
25 93.6 15.0 6.3 89.6 13.6 6.6 88.8 13.5 6.6
30 92.8 15.4 6.0 88.9 14.0 6.3 88.0 13.8 6.4
35 89.0 16.7 5.3 80.0 13.3 6.0 78.6 12.4 6.4
40 85.0 16.0 5.3 71.4 11.4 6.3 70.1 10.7 6.5
42 81.7 16.0 5.1 69.2 11.8 5.9 67.8 11.3 6.0
45 76.8 16.2 4.7 66.0 12.4 5.3 64.3 12.2 5.3
47 67.9 15.0 4.5 57.7 11.6 5.0 56.0 11.4 4.9
48 65.3 15.3 4.3 55.5 11.8 4.7
50
54
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.
20
MBT Confidential
Aqua thermal
MC-SU90M-RN8L-B
DB
LWT -20 -18 -15 -10 -7 4
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 44.7 22.6 2.0 49.6 23.3 2.1 56.8 24.3 2.3 67.4 24.7 2.7 73.7 25.0 2.9 79.1 25.8 3.1
30 43.9 23.2 1.9 48.7 23.9 2.0 55.8 24.9 2.2 66.2 25.4 2.6 72.4 25.7 2.8 77.7 26.5 2.9
35 42.7 26.3 1.6 47.0 26.8 1.8 53.6 27.4 2.0 63.9 27.6 2.3 70.2 27.7 2.5 75.5 27.8 2.7
40 39.7 28.1 1.4 44.2 28.5 1.6 51.0 29.1 1.8 61.6 29.7 2.1 68.0 30.1 2.3 73.7 30.2 2.4
42 42.4 28.2 1.5 48.9 28.8 1.7 59.9 30.1 2.0 66.5 30.9 2.2 72.2 31.0 2.3
45 45.8 28.4 1.6 57.2 30.7 1.9 64.1 32.1 2.0 69.9 32.3 2.2
47 50.6 28.6 1.8 56.6 29.9 1.9 63.6 30.8 2.1
48 48.6 29.2 1.7 54.5 30.5 1.8 61.2 31.4 1.9
50 48.0 29.5 1.6 55.3 30.8 1.8
54 47.5 31.1 1.5
DB
LWT 2 7 15 20 25 30
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
DB
LWT 35 40 43
HC PI EER HC PI EER HC PI EER
25 93.6 16.5 5.7 89.6 15.1 5.9 88.8 15.0 5.9
30 92.8 16.9 5.5 88.9 15.5 5.7 88.0 15.3 5.8
35 89 18.2 4.9 80.0 14.8 5.4 78.6 13.9 5.7
40 85 17.5 4.9 71.4 12.9 5.5 70.1 12.2 5.7
42 81.7 17.5 4.7 69.2 13.3 5.2 67.8 12.8 5.3
45 76.8 17.7 4.3 66.0 13.9 4.7 64.3 13.7 4.7
47 67.9 16.5 4.1 57.7 13.1 4.4 56.0 12.9 4.3
48 65.3 16.8 3.9 55.5 13.3 4.2
50
54
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate..
21
MBT Confidential
Aqua thermal
MC-SU140-RN8L-B
DB
LWT -20 -18 -15 -10 -5 0
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 60.4 27.2 2.2 78.8 31.9 2.5 81.7 32.4 2.5 97.1 35.9 2.7 82.7 30.0 2.8 91.4 31.3 2.9
30 61.9 28.9 2.1 78.5 32.8 2.4 80.0 33.8 2.4 95.2 37.4 2.5 82.6 31.7 2.6 91.8 33.6 2.7
35 57.2 29.3 1.9 74.4 34.0 2.2 80.4 36.6 2.2 95.6 40.5 2.4 83.5 34.8 2.4 92.2 36.3 2.5
40 38.1 23.1 1.7 67.4 34.9 1.9 81.4 39.5 2.1 96.7 43.8 2.2 85.2 37.4 2.3 90.8 38.7 2.3
45 13.0 12.1 1.1 54.9 33.4 1.6 79.5 42.5 1.9 94.5 47.0 2.0 86.9 42.2 2.1 89.4 41.4 2.2
48 50.9 33.0 1.5 75.4 41.7 1.8 89.7 46.1 1.9 84.1 42.5 2.0 87.3 42.6 2.0
50 69.8 40.9 1.7 83.0 45.3 1.8 75.4 39.6 1.9 80.3 41.4 1.9
54 57.7 35.4 1.6 55.6 32.9 1.7 56.4 32.7 1.7
DB
LWT 5 7 10 15 20 25
Midea Aqua thermal Engineering Data Book
DB
LWT 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER
25 220.2 52.1 4.2 226.9 50.8 4.5 216.6 46.7 4.6 211.4 44.7 4.7
30 204.2 48.5 4.2 209.8 47.5 4.4 198.0 44.4 4.5 192.1 42.6 4.5
35 191.0 44.2 4.3 198.1 44.9 4.4 183.7 44.0 4.2 178.5 42.2 4.2
40 168.7 39.4 4.3 177.1 40.5 4.4 163.5 42.8 3.8 156.8 40.4 3.9
45 150.1 40.0 3.8 158.5 41.5 3.8 143.9 41.6 3.5 136.6 39.1 3.5
48 136.1 37.6 3.6 141.5 38.4 3.7 130.2 40.4 3.2 124.5 38.0 3.3
50 124.9 35.3 3.5 129.2 36.1 3.6 117.1 38.9 3.0 111.0 36.1 3.1
54 79.1 23.8 3.3 89.1 26.4 3.4 80.8 29.3 2.8
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.
22
MBT Confidential
Aqua thermal
MC-SU140M-RN8L-B
DB
LWT -20 -18 -15 -10 -5 0
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 60.4 29.4 2.1 78.8 34.1 2.3 81.7 34.6 2.4 97.1 38.1 2.5 82.7 32.2 2.6 91.4 33.5 2.7
30 61.9 31.1 2.0 78.5 35.0 2.2 80.0 36.0 2.2 95.2 39.6 2.4 82.6 33.9 2.4 91.8 35.8 2.6
35 57.2 31.5 1.8 74.4 36.2 2.1 80.4 38.8 2.1 95.6 42.7 2.2 83.5 37.0 2.3 92.2 38.5 2.4
40 38.1 25.3 1.5 67.4 37.1 1.8 81.4 41.7 2.0 96.7 46.0 2.1 85.2 39.6 2.2 90.8 40.9 2.2
45 13 14.3 0.9 54.9 35.6 1.5 79.5 44.7 1.8 94.5 49.2 1.9 86.9 44.4 2.0 89.4 43.6 2.1
48 50.9 35.2 1.4 75.4 43.9 1.7 89.7 48.3 1.9 84.1 44.7 1.9 87.3 44.8 1.9
50 69.8 43.1 1.6 83.0 47.5 1.7 75.4 41.8 1.8 80.3 43.6 1.8
54 57.7 37.6 1.5 55.6 35.1 1.6 56.4 34.9 1.6
DB
LWT 5 7 10 15 20 25
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 120.1 37.7 3.2 158.9 44.6 3.6 169.7 45.3 3.7 180.1 47.3 3.8 196.8 50.3 3.9 213.6 53.7 4.0
30 116.2 39.1 3.0 150.6 45.5 3.3 166.2 46.5 3.6 178.3 49.4 3.6 188.4 51.1 3.7 198.5 53.1 3.7
DB
LWT 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER
25 220.2 54.3 4.1 226.9 53.0 4.3 216.6 48.9 4.4 211.4 46.9 4.5
30 204.2 50.7 4.0 209.8 49.7 4.2 198.0 46.6 4.2 192.1 44.8 4.3
35 191 46.4 4.1 198.1 47.1 4.2 183.7 46.2 4.0 178.5 44.4 4.0
40 168.7 41.6 4.1 177.1 42.7 4.1 163.5 45.0 3.6 156.8 42.6 3.7
45 150.1 42.2 3.6 158.5 43.7 3.6 143.9 43.8 3.3 136.6 41.3 3.3
48 136.1 39.8 3.4 141.5 40.6 3.5 130.2 42.6 3.1 124.5 40.2 3.1
50 124.9 37.5 3.3 129.2 38.3 3.4 117.1 41.1 2.8 111.0 38.3 2.9
54 79.1 26 3.0 89.1 28.6 3.1 80.8 31.5 2.6
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.
23
MBT Confidential
Aqua thermal
MC-SU180-RN8L-B
DB
LWT -20 -18 -15 -10 -7 -4
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 89.5 42.5 43.9 99.1 43.9 2.3 111.8 45.7 2.4 134.8 46.8 2.9 148.1 48.1 3.1 158.2 48.9 3.2
30 87.9 43.7 45.1 97.4 45.1 2.2 109.8 47.0 2.3 132.4 48.1 2.8 145.5 49.4 2.9 155.4 50.3 3.1
35 85.3 50.0 50.8 94.1 50.8 1.9 106.0 51.9 2.0 127.9 52.5 2.4 141.0 52.7 2.7 151.1 52.9 2.9
40 79.4 53.6 54.4 88.4 54.4 1.6 100.8 55.9 1.8 123.3 56.9 2.2 136.9 57.4 2.4 147.3 57.7 2.6
42 84.8 56.9 1.5 97.3 57.3 1.7 120.3 57.6 2.1 134.2 58.7 2.3 144.8 59.3 2.4
45 92.7 59.8 1.5 114.5 58.8 1.9 128.8 60.7 2.1 139.8 62.0 2.3
47 103.8 57.3 1.8 118.1 59.7 2.0 129.0 61.2 2.1
48 97.2 55.8 1.7 111.4 58.5 1.9 122.3 60.3 2.0
50 101.0 57.4 1.8 110.7 59.1 1.9
54 95.0 59.5 1.6
Midea Aqua thermal Engineering Data Book
DB
LWT 0 5 7 10 15 20
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 174.3 51.2 3.4 190.3 47.0 4.1 198.2 46.5 4.3 206.0 45.4 4.5 207.5 44.8 4.6 207.8 43.6 4.8
30 171.2 52.6 3.3 188.0 48.6 3.9 196.5 47.0 4.2 204.2 46.8 4.4 205.7 46.1 4.5 206.0 44.9 4.6
35 167.1 53.1 3.1 183.0 49.9 3.7 190.8 49.6 3.9 199.2 49.8 4.0 200.9 49.2 4.1 200.5 47.4 4.2
40 164.0 57.9 2.8 178.6 56.2 3.2 185.4 54.2 3.4 196.1 51.8 3.8 198.2 51.1 3.9 199.2 49.4 4.0
42 161.7 59.8 2.7 176.8 57.0 3.1 183.9 55.4 3.3 195.0 53.6 3.6 197.3 52.9 3.7 198.1 49.8 4.0
45 157.0 62.7 2.5 173.3 58.3 3.0 180.0 57.0 3.2 193.0 56.5 3.4 195.4 55.7 3.5 196.0 50.3 3.9
47 147.3 63.0 2.3 166.7 63.3 2.6 175.3 61.6 2.8 184.1 56.2 3.3 185.7 55.1 3.4 181.9 48.4 3.8
48 142.1 63.0 2.3 162.6 66.1 2.5 172.3 64.2 2.7 178.6 55.7 3.2 179.8 54.5 3.3 173.3 46.9 3.7
50 132.2 63.2 2.1 155.5 67.3 2.3 166.6 69.2 2.4 168.9 53.6 3.2 169.4 52.1 3.3 158.2 44.7 3.5
54 113.2 65.1 1.7 132.8 67.4 2.0 142.1 68.4 2.1 146.8 52.3 2.8 147.8 50.9 2.9 140.5 42.7 3.3
DB
LWT 25 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 205.7 40.2 5.1 200.1 35.5 5.6 187.3 30.1 6.2 179.2 28.5 6.3 177.6 27.7 6.4
30 203.9 41.3 4.9 198.4 36.5 5.4 185.7 31.0 6.0 177.7 29.3 6.1 176.1 28.5 6.2
35 200.5 41.4 4.8 192.0 36.8 5.2 178.0 32.0 5.6 160.0 27.9 5.7 157.2 26.8 5.9
40 198.6 42.7 4.7 189.2 37.6 5.0 170.0 32.9 5.2 142.8 26.0 5.5 140.1 25.0 5.6
42 196.9 43.8 4.5 182.7 37.7 4.8 164.5 32.7 5.0 139.1 26.0 5.3 136.3 24.9 5.5
45 193.6 45.6 4.3 169.8 37.9 4.5 153.6 32.5 4.7 132.0 25.9 5.1 128.6 24.7 5.2
47 173.4 42.7 4.1 155.6 36.4 4.3 141.7 31.6 4.5 124.1 25.4 4.9 120.2 23.9 5.0
48 161.0 40.6 4.0 143.5 34.5 4.2 130.6 29.8 4.4 114.4 24.0 4.8
50 139.2 37.3 3.7 126.0 32.4 3.9
54 117.9 33.3 3.5 94.0 25.3 3.7
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate..
24
MBT Confidential
Aqua thermal
MC-SU180M-RN8L-B
DB
LWT -20 -18 -15 -10 -7 -4
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 89.5 44.0 2.0 99.1 45.4 2.2 111.8 47.2 2.4 134.8 48.3 2.8 148.1 49.6 3.0 158.2 50.4 3.1
30 87.9 45.2 1.9 97.4 46.6 2.1 109.8 48.5 2.3 132.4 49.6 2.7 145.5 50.9 2.9 155.4 51.8 3.0
35 85.3 51.5 1.7 94.1 52.3 1.8 106.0 53.4 2.0 127.9 54.0 2.4 141.0 54.2 2.6 151.1 54.4 2.8
40 79.4 55.1 1.4 88.4 55.9 1.6 100.8 57.4 1.8 123.3 58.4 2.1 136.9 58.9 2.3 147.3 59.2 2.5
42 84.8 58.4 1.5 97.3 58.8 1.7 120.3 59.1 2.0 134.2 60.2 2.2 144.8 60.8 2.4
45 92.7 61.3 1.5 114.5 60.3 1.9 128.8 62.2 2.1 139.8 63.5 2.2
47 103.8 58.8 1.8 118.1 61.2 1.9 129.0 62.7 2.1
48 97.2 57.3 1.7 111.4 60.0 1.9 122.3 61.8 2.0
50 101.0 58.9 1.7 110.7 60.6 1.8
54 95.0 61.0 1.6
DB
LWT 0 5 7 10 15 20
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
DB
LWT 25 30 35 40 43
HC PI EER HC PI EER HC PI EER HC PI EER HC PI EER
25 205.7 41.7 4.9 200.1 37.0 5.4 187.3 31.6 5.9 179.2 30.0 6.0 177.6 29.2 6.1
30 203.9 42.8 4.8 198.4 38.0 5.2 185.7 32.5 5.7 177.7 30.8 5.8 176.1 30.0 5.9
35 200.5 42.9 4.7 192.0 38.3 5.0 178.0 33.5 5.3 160.0 29.4 5.4 157.2 28.3 5.6
40 198.6 44.2 4.5 189.2 39.1 4.8 170.0 34.4 4.9 142.8 27.5 5.2 140.1 26.5 5.3
42 196.9 45.3 4.3 182.7 39.2 4.7 164.5 34.2 4.8 139.1 27.5 5.1 136.3 26.4 5.2
45 193.6 47.1 4.1 169.8 39.4 4.3 153.6 34.0 4.5 132.0 27.4 4.8 128.6 26.2 4.9
47 173.4 44.2 3.9 155.6 37.9 4.1 141.7 33.1 4.3 124.1 26.9 4.6 120.2 25.4 4.7
48 161.0 42.1 3.8 143.5 36.0 4.0 130.6 31.3 4.2 114.4 25.5 4.5
50 139.2 38.8 3.6 126.0 33.9 3.7
54 117.9 34.8 3.4 94.0 26.8 3.5
Abbreviations:
HC: Total heating capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C)
DB: Dry-bulb temperature for outdoor air temperature (°C)
Performance specifications measured with water pump operating at rated water flow rate.
25
MBT Confidential
Aqua thermal
5.2 Cooling Capacity Tables
MC-SU75-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 52.0 17.7 2.9 61.1 17.7 3.5
5 60.5 18.6 3.3 69.0 18.9 3.7
7 66.7 19.8 3.4 75.5 20.2 3.7
10 61.9 10.3 6.0 61.0 11.0 5.6 58.9 11.7 5.0 57.2 12.5 4.6 68.2 19.8 3.4 82.3 20.8 4.0
15 70.8 10.4 6.8 69.6 11.6 6.0 66.5 11.4 5.8 65.4 11.6 5.7 66.9 17.4 3.8 90.8 18.4 4.9
20 78.4 11.3 6.9 77.5 12.0 6.5 76.5 12.3 6.2 74.4 12.1 6.2 68.3 16.7 4.1 95.9 18.6 5.2
DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
Midea Aqua thermal Engineering Data Book
0 60.5 18.0 3.4 59.9 18.7 3.2 59.4 22.3 2.7 56.9 24.3 2.3 36.5 16.5 2.2 23.2 11.4 2.0
5 68.2 19.3 3.5 67.6 20.0 3.4 67.0 23.8 2.8 64.2 26.0 2.5 41.2 17.6 2.3 26.2 12.1 2.2
7 75.1 20.4 3.7 74.2 21.4 3.5 70.8 24.2 2.9 70.0 26.8 2.6 47.3 18.8 2.5 31.8 13.5 2.4
10 81.2 21.1 3.8 79.3 21.4 3.7 77.4 24.9 3.1 74.8 27.1 2.8 51.6 19.1 2.7 35.5 13.7 2.6
15 88.0 19.5 4.5 86.8 20.9 4.2 82.4 23.0 3.6 78.7 24.5 3.2 53.2 16.8 3.2 37.1 12.5 3.0
20 94.5 19.6 4.8 93.5 21.3 4.4 91.6 23.0 4.0 87.4 23.2 3.8 58.0 15.8 3.7 43.3 12.7 3.4
DB
LWT 45 48
CC PI EER CC PI EER
0 21.3 11.2 1.9 11.3 8.3 1.4
5 24.1 11.9 2.0 12.7 8.9 1.4
7 27.4 12.6 2.2 14.5 8.9 1.6
10 31.2 12.9 2.4 17.1 9.0 1.9
15 33.9 12.1 2.8 21.3 9.0 2.4
20 39.0 12.3 3.2 25.1 9.0 2.8
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.
26
MBT Confidential
Aqua thermal
MC-SU75M-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 52.0 19.2 2.7 61.1 19.2 3.2
5 60.5 20.1 3.0 69.0 20.4 3.4
7 66.7 21.3 3.1 75.5 21.7 3.5
10 61.9 11.8 5.2 61.0 12.5 4.9 58.9 13.2 4.5 57.2 14.0 4.1 68.2 21.3 3.2 82.3 22.3 3.7
15 70.8 11.9 5.9 69.6 13.1 5.3 66.5 12.9 5.2 65.4 13.1 5.0 66.9 18.9 3.5 90.8 19.9 4.6
20 78.4 12.8 6.1 77.5 13.5 5.7 76.5 13.8 5.5 74.4 13.6 5.5 68.3 18.2 3.8 95.9 20.1 4.8
DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 60.5 19.5 3.1 59.9 20.2 3.0 59.4 23.8 2.5 56.9 25.8 2.2 36.5 18.0 2.0 23.2 12.9 1.8
5 68.2 20.8 3.3 67.6 21.5 3.1 67.0 25.3 2.6 64.2 27.5 2.3 41.2 19.1 2.2 26.2 13.6 1.9
7 75.1 21.9 3.4 74.2 22.9 3.2 70.8 25.7 2.8 70.0 28.3 2.5 47.3 20.3 2.3 31.8 15.0 2.1
10 81.2 22.6 3.6 79.3 22.9 3.5 77.4 26.4 2.9 74.8 28.6 2.6 51.6 20.6 2.5 35.5 15.2 2.3
DB
LWT 45 48
CC PI EER CC PI EER
0 21.3 12.7 1.7 11.3 9.8 1.2
5 24.1 13.4 1.8 12.7 10.4 1.2
7 27.4 14.1 1.9 14.5 10.4 1.4
10 31.2 14.4 2.2 17.1 10.5 1.6
15 33.9 13.6 2.5 21.3 10.5 2.0
20 39.0 13.8 2.8 25.1 10.5 2.4
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.
27
MBT Confidential
Aqua thermal
MC-SU90-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 81.9 18.8 4.4 81.5 25.5 3.2
5 94.1 26.8 3.5 93.1 27.3 3.4
7 96.3 29.6 3.3 95.6 26.4 3.6
10 75.8 18.6 4.1 75.9 16.0 4.8 76.6 15.2 5.0 75.8 17.4 4.4 106.0 27.4 3.9 111.7 29.5 3.8
15 84.0 16.4 5.1 84.1 16.2 5.2 84.0 16.9 5.0 84.1 14.8 5.7 123.7 25.6 4.8 127.2 28.1 4.5
20 92.3 14.2 6.5 92.3 16.4 5.6 91.3 18.6 4.9 91.1 14.6 6.2 129.2 26.3 4.9 133.9 28.7 4.7
DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 78.2 26.5 3.0 76.1 20.9 3.6 74.1 24.3 3.1 68.3 29.6 2.3 57.3 27.5 2.1 46.9 24.9 1.9
Midea Aqua thermal Engineering Data Book
5 91.8 28.7 3.2 90.3 27.8 3.2 87.4 29.5 3.0 80.9 32.2 2.5 69.9 30.2 2.3 60.9 28.2 2.2
7 94.7 30.0 3.2 93.1 21.6 4.3 89.1 28.9 3.1 82.1 27.3 3.0 71.5 25.9 2.8 63.7 24.2 2.6
10 107.6 31.5 3.4 102.9 27.5 3.7 99.9 30.3 3.3 93.7 33.0 2.8 81.6 27.7 3.0 72.2 24.2 3.0
15 117.3 29.3 4.0 111.7 25.6 4.4 108.3 25.2 4.3 104.2 28.4 3.7 92.6 28.0 3.3 81.8 24.0 3.4
20 127.1 29.4 4.3 121.3 23.5 5.2 117.3 24.7 4.7 112.4 27.5 4.1 102.3 27.9 3.7 92.1 25.3 3.6
DB
LWT 45 48
CC PI EER CC PI EER
0 32.8 20.1 1.6 18.0 12.1 1.5
5 48.5 24.2 2.0 29.3 16.5 1.8
7 56.0 21.8 2.6 38.1 18.0 2.1
10 62.9 22.4 2.8 45.1 19.2 2.4
15 72.8 23.4 3.1 55.0 17.8 3.1
20 80.7 22.2 3.6 60.9 19.3 3.1
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.
28
MBT Confidential
Aqua thermal
MC-SU90M-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 81.9 20.3 4.0 81.5 27.0 3.0
5 94.1 28.3 3.3 93.1 28.8 3.2
7 96.3 31.1 3.1 95.6 27.9 3.4
10 75.8 20.1 3.8 75.9 17.5 4.3 76.6 16.7 4.6 75.8 18.9 4.0 106.0 28.9 3.7 111.7 31.0 3.6
15 84.0 17.9 4.7 84.1 17.7 4.8 84.0 18.4 4.6 84.1 16.3 5.2 123.7 27.1 4.6 127.2 29.6 4.3
20 92.3 15.7 5.9 92.3 17.9 5.2 91.3 20.1 4.5 91.1 16.1 5.7 129.2 27.8 4.6 133.9 30.2 4.4
DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 78.2 28.0 2.8 76.1 22.4 3.4 74.1 25.8 2.9 68.3 31.1 2.2 57.3 29.0 2.0 46.9 26.4 1.8
5 91.8 30.2 3.0 90.3 29.3 3.1 87.4 31.0 2.8 80.9 33.7 2.4 69.9 31.7 2.2 60.9 29.7 2.1
7 94.7 31.5 3.0 93.1 23.1 4.0 89.1 30.4 2.9 82.1 28.8 2.9 71.5 27.4 2.6 63.7 25.7 2.5
10 107.6 33.0 3.3 102.9 29.0 3.5 99.9 31.8 3.1 93.7 34.5 2.7 81.6 29.2 2.8 72.2 25.7 2.8
DB
LWT 45 48
CC PI EER CC PI EER
0 32.8 21.6 1.5 18.0 13.6 1.3
5 48.5 25.7 1.9 29.3 18.0 1.6
7 56.0 23.3 2.4 38.1 19.5 2.0
10 62.9 23.9 2.6 45.1 20.7 2.2
15 72.8 24.9 2.9 55.0 19.3 2.8
20 80.7 23.7 3.4 60.9 20.8 2.9
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.
29
MBT Confidential
Aqua thermal
MC-SU140-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 105.2 38.4 2.7 117.4 38.0 3.1
5 120.0 40.8 2.9 135.2 40.4 3.3
7 128.2 42.7 3.0 142.2 41.2 3.5
10 114.4 25.6 4.5 112.8 25.7 4.4 111.3 26.1 4.3 109.7 26.4 4.2 133.3 42.8 3.1 146.5 41.6 3.5
15 133.7 26.3 5.1 131.8 26.2 5.0 130.5 26.4 4.9 129.2 26.6 4.9 138.2 40.7 3.4 155.0 38.5 4.0
20 144.7 25.0 5.8 143.1 25.4 5.6 141.6 25.7 5.5 140.1 25.9 5.4 146.6 40.7 3.6 156.3 37.1 4.2
DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 111.5 38.8 2.9 110.1 40.5 2.7 108.4 44.5 2.4 106.5 49.8 2.1 86.5 41.8 2.1 74.1 38.0 1.9
Midea Aqua thermal Engineering Data Book
5 128.4 41.1 3.1 125.6 43.3 2.9 124.5 46.8 2.7 121.7 52.9 2.3 98.3 44.5 2.2 85.1 40.6 2.1
7 136.9 41.6 3.3 133.5 45.3 3.0 132.1 47.9 2.8 130.0 50.5 2.6 104.8 43.0 2.4 91.2 41.3 2.2
10 142.8 42.4 3.4 142.1 46.1 3.1 141.1 49.0 2.9 139.1 52.5 2.7 107.7 41.3 2.6 100.9 40.9 2.5
15 151.0 39.9 3.8 148.3 44.3 3.3 147.4 46.7 3.2 146.2 49.3 3.0 115.5 40.3 2.9 110.3 39.9 2.8
20 152.9 38.1 4.0 150.2 42.4 3.5 149.8 44.7 3.4 148.4 46.9 3.2 119.9 38.7 3.1 114.9 37.7 3.0
DB
LWT 45 48
CC PI EER CC PI EER
0 71.4 39.7 1.8 41.0 28.2 1.5
5 81.1 42.0 1.9 46.8 29.8 1.6
7 86.4 41.9 2.1 57.7 31.7 1.8
10 92.6 39.0 2.4 63.5 32.3 2.0
15 95.0 35.4 2.7 65.3 29.1 2.2
20 97.3 32.6 3.0 70.3 26.3 2.7
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.
30
MBT Confidential
Aqua thermal
MC-SU140M-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 105.2 40.6 2.6 117.4 40.2 2.9
5 120.0 43.0 2.8 135.2 42.6 3.2
7 128.2 44.9 2.9 142.2 43.4 3.3
10 114.4 27.8 4.1 112.8 27.9 4.0 111.3 28.3 3.9 109.7 28.6 3.8 133.3 45.0 3.0 146.5 43.8 3.3
15 133.7 28.5 4.7 131.8 28.4 4.6 130.5 28.6 4.6 129.2 28.8 4.5 138.2 42.9 3.2 155.0 40.7 3.8
20 144.7 27.2 5.3 143.1 27.6 5.2 141.6 27.9 5.1 140.1 28.1 5.0 146.6 42.9 3.4 156.3 39.3 4.0
DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 111.5 41 2.7 110.1 42.7 2.6 108.4 46.7 2.3 106.5 52.0 2.0 86.5 44.0 2.0 74.1 40.2 1.8
5 128.4 43.3 3.0 125.6 45.5 2.8 124.5 49.0 2.5 121.7 55.1 2.2 98.3 46.7 2.1 85.1 42.8 2.0
7 136.9 43.8 3.1 133.5 47.5 2.8 132.1 50.1 2.6 130.0 52.7 2.5 104.8 45.2 2.3 91.2 43.5 2.1
10 142.8 44.6 3.2 142.1 48.3 2.9 141.1 51.2 2.8 139.1 54.7 2.5 107.7 43.5 2.5 100.9 43.1 2.3
DB
LWT 45 48
CC PI EER CC PI EER
0 71.4 41.9 1.7 41.0 30.4 1.3
5 81.1 44.2 1.8 46.8 32.0 1.5
7 86.4 44.1 2.0 57.7 33.9 1.7
10 92.6 41.2 2.2 63.5 34.5 1.8
15 95 37.6 2.5 65.3 31.3 2.1
20 97.3 34.8 2.8 70.3 28.5 2.5
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.
31
MBT Confidential
Aqua thermal
MC-SU180-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 163.8 48.5 3.4 163.1 51.1 3.2
5 188.2 52.0 3.6 186.3 54.7 3.4
7 199.1 52.2 3.8 197.6 55.0 3.6
10 151.7 37.3 4.1 151.8 32.0 4.7 153.3 30.5 5.0 151.6 34.9 4.3 212.0 52.7 4.0 223.5 59.2 3.8
15 168.1 32.8 5.1 168.2 32.5 5.2 168.0 31.6 5.3 168.2 29.7 5.7 247.4 51.4 4.8 254.4 56.4 4.5
20 184.5 28.4 6.5 184.5 32.9 5.6 182.6 30.6 6.0 182.3 29.3 6.2 258.5 48.6 5.3 267.8 56.3 4.8
DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 156.5 50.5 3.1 152.1 50.4 3.0 148.2 48.8 3.0 136.7 59.3 2.3 114.7 55.3 2.1 93.8 50.0 1.9
Midea Aqua thermal Engineering Data Book
5 183.5 56.3 3.3 180.6 57.7 3.1 174.9 59.1 3.0 161.7 64.7 2.5 139.8 60.7 2.3 121.9 56.7 2.2
7 195.6 57.2 3.4 192.4 59.6 3.2 184.2 60.2 3.1 164.0 56.0 2.9 147.7 54.0 2.7 131.7 50.3 2.6
10 215.1 59.4 3.6 205.8 60.0 3.4 199.7 60.7 3.3 187.5 59.5 3.1 163.3 54.8 3.0 144.4 50.0 2.9
15 234.6 58.8 4.0 223.4 51.4 4.3 216.5 50.5 4.3 208.4 56.9 3.7 185.1 56.3 3.3 163.7 50.7 3.2
20 254.3 59.0 4.3 242.7 47.1 5.2 234.6 49.7 4.7 224.7 55.2 4.1 204.7 55.9 3.7 184.2 52.5 3.5
DB
LWT 45 48
CC PI EER CC PI EER
0 65.6 40.3 1.6 36.0 24.4 1.5
5 96.9 48.6 2.0 58.6 33.2 1.8
7 115.7 45.5 2.5 78.6 37.6 2.1
10 125.8 45.0 2.8 90.2 38.5 2.3
15 145.6 46.9 3.1 110.0 38.6 2.9
20 161.3 48.0 3.4 121.7 38.8 3.1
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.
32
MBT Confidential
Aqua thermal
MC-SU180M-RN8L-B
DB
LWT -10 -5 0 5 10 15
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 163.8 50.0 3.3 163.1 52.6 3.1
5 188.2 53.5 3.5 186.3 56.2 3.3
7 199.1 53.7 3.7 197.6 56.5 3.5
10 151.7 38.8 3.9 151.8 33.5 4.5 153.3 32.0 4.8 151.6 36.4 4.2 212.0 54.2 3.9 223.5 60.7 3.7
15 168.1 34.3 4.9 168.2 34.0 4.9 168.0 33.1 5.1 168.2 31.2 5.4 247.4 52.9 4.7 254.4 57.9 4.4
20 184.5 29.9 6.2 184.5 34.4 5.4 182.6 32.1 5.7 182.3 30.8 5.9 258.5 50.1 5.2 267.8 57.8 4.6
DB
LWT 20 25 30 35 40 43
CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER CC PI EER
0 156.5 52 3.0 152.1 51.9 2.9 148.2 50.3 2.9 136.7 60.8 2.2 114.7 56.8 2.0 93.8 51.5 1.8
5 183.5 57.8 3.2 180.6 59.2 3.1 174.9 60.6 2.9 161.7 66.2 2.4 139.8 62.2 2.2 121.9 58.2 2.1
7 195.6 58.7 3.3 192.4 61.1 3.1 184.2 61.7 3.0 164.0 57.5 2.9 147.7 55.5 2.7 131.7 51.8 2.5
10 215.1 60.9 3.5 205.8 61.5 3.3 199.7 62.2 3.2 187.5 61.0 3.1 163.3 56.3 2.9 144.4 51.5 2.8
DB
LWT 45 48
CC PI EER CC PI EER
0 65.6 41.8 1.6 36.0 25.9 1.4
5 96.9 50.1 1.9 58.6 34.7 1.7
7 115.7 47.0 2.5 78.6 39.1 2.0
10 125.8 46.5 2.7 90.2 40.0 2.3
15 145.6 48.4 3.0 110.0 40.1 2.7
20 161.3 49.5 3.3 121.7 40.3 3.0
Abbreviations:
CC: Total cooling capacity (kW)
PI: Power input (kW)
LWT: Leaving water temperature (°C )
DB: Dry-bulb temperature for outdoor air temperature (°C )
Notes: Performance specifications measured with water pump operating at rated water flow rate.
33
MBT Confidential
Aqua thermal
6 Performance Adjustment Factors
6.1 Ethylene and Propylene Glycol factors
The antifreeze must be required according to anyone condition as following:
The ambient temperature is below 0 ⁰C;
Don’t start up the unit for a long time.
The power supply was cut off and needn’t change the water in system.
A glycol solution is required when the unit with condition as mentioned. The use of glycol will reduce the performance of the
unit depending on concentration.
Other terms used in the literature to describe fouling include: deposit formation, encrustation, crudding, deposition, scaling,
scale formation, slagging, and sludge formation. The last six terms have a more narrow meaning than fouling within the scope of
34
MBT Confidential
Aqua thermal
the fouling science and technology, and they also have meanings outside of this scope; therefore, they should be used with
caution.
Fouling phenomena are common and diverse, ranging from fouling of ship hulls, natural surfaces in the marine environment
(marine fouling), fouling of heat-transfer components through ingredients contained in the cooling water or gases, and even the
development of plaque or calculus on teeth, or deposits on solar panels on Mars, among other examples.
Foreign matter in the chilled water system will adversely affect the heat transfer capability of the evaporator, and could increase
the pressure drop and reduce the water flow. To provide optimum unit operation, proper water treatment must be maintained.
Refer to the able as following.
Fouling Factor
Difference of water
ALTITUDE
inlet and outlet temp. 0.018 m2. ⁰C /kW 0.044 m2. ⁰C /kW 0.086 m2. ⁰C /kW 0.172 m2. ⁰C /kW
(m)
(⁰C)
C P C P C P C P
35
MBT Confidential
Aqua thermal
7 Hydronic Performance
MC-SU75-RN8L-B
180
160
140
Water pressure drop (kPa)
120
100
80
Midea Aqua thermal Engineering Data Book
60
40
20
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19
Water flow rate (m3/h)
MC-SU90-RN8L-B
180
160
140
Water pressure drop (kPa)
120
100
80
60
40
20
0
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25
Water flow rate (m3/h)
36
MBT Confidential
Aqua thermal
MC-SU140-RN8L-B
180
160
140
Water pressure drop (kPa)
120
100
80
60
40
20
0
0 3 6 9 12 15 18 21 24 27 30 33 36
Water flow rate (m3/h)
250
200
Water pressure drop (kPa)
150
100
50
0
0 3 6 9 12 15 18 21 24 27 30 33 36 39 42 45
Water flow rate (m3/h)
37
MBT Confidential
Aqua thermal
MC-SU75M-RN8L-B
300
250
External static pressure(kPa)
200
150
100
50
0
Midea Aqua thermal Engineering Data Book
6 8 10 12 14 16
Water flow rate (m3/h)
MC-SU90M-RN8L-B
500
450
400
External static pressure(kPa)
350
300
250
200
150
100
50
0
0 2 4 6 8 10 12 14 16 18 20
Water flow rate (m3/h)
38
MBT Confidential
Aqua thermal
MC-SU140M-RN8L-B
160
140
120
External static pressure(kPa)
100
80
60
40
20
MC-SU180M-RN8L-B
400
350
300
External static pressure(kPa)
250
200
150
100
50
0
18 20 22 24 26 28 30 32 34 36
Water flow rate (m3/h)
39
MBT Confidential
Aqua thermal
8 Octave Band Levels
Side Two
Test condition:Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C
MC-SU75-RN8L-B
90
80
Octave band sound level: dB(A)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)
40
MBT Confidential
Aqua thermal
MC-SU75M-RN8L-B
90
80
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
MC-SU90-RN8L-B
90
80
Octave band sound level: dB(A)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)
41
MBT Confidential
Aqua thermal
MC-SU90M-RN8L-B
90
80
Octave band sound level: dB(A)
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
Midea Aqua thermal Engineering Data Book
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)
MC-SU140-RN8L-B
90
80
70
Octave band sound level: dB(A)
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)
42
MBT Confidential
Aqua thermal
MC-SU140M-RN8L-B
90
80
70
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Side Four
Test condition:Outdoor ambient temperature 35°C DB. EWT 12°C, LWT 7°C
43
MBT Confidential
Aqua thermal
MC-SU180-RN8L-B
90
80
70
NC-70
Octave band sound level (dB)
60
NC-60
50
NC-50
40
NC-40
Midea Aqua thermal Engineering Data Book
30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)
MC-SU180M-RN8L-B
90
80
70
Octave band sound level (dB)
NC-70
60
NC-60
50
NC-50
40
NC-40
30
NC-30
20
NC-20
10
63 125 250 500 1000 2000 4000 8000
Octave band central frequency (Hz)
44
MBT Confidential
Aqua thermal
Part 3
User Interface
Field Settings
1 User Interface Field Settings ................................................................ 45
45
MBT Confidential
Aqua thermal
1 User Interface Field Settings
1.1 Introduction
During installation, the unit’s settings and parameters should be configured by the installer to suit the installation
configuration, climate conditions and end-user preferences. The relevant settings are accessible and programmable
through the SERVICE and PROJECT menu on the wired controller’s user interface.
KJRM-120H2/BMWKO-E
Midea Aqua thermal Engineering Data Book
Icon Function
Enter the menu structure from the home page
Navigate the cursor on the display/navigate in the menu structure/ adjust the settings
46
MBT Confidential
Aqua thermal
1.2 SERVICE MENU
1.2.1 Structure
5. TEMPERATURE COMPENSATION
E9 PROTECT TIME
E9 DETECTION METHOD
6. PUMP CONTROL
FORCED PUMP OPEN
INV PUMP SETTING
PUMP ON/OFF TIME
7. MANUAL DEFROST
9. VACUUM SWITCH
0 0 0
OK
STATE QUERY allows installers to check the operation parameters. Press ◄ ► to select the address of units.
STATE QUERY STATE QUERY STATE QUERY
SELECT ADDRESS 07 # H-P PRESSURE 3.83 MPa TZ TEMP -20℃
ODU MODEL 130 kW L-P PRESSURE 1.00 MPa T3 TEMP -20℃
COMP FREQUENCE 50 Hz TP1 DISCHARGE TEMP 30 ℃ T4 TEMP -20℃
COMP1 CURRENT 20 A TP2 DISCHARGE TEMP 30 ℃ T6A TEMP 40℃
COMP2 CURRENT 20 A TH SUCTION TEMP -20 ℃ T6B TEMP 40℃
BACK OK 2/9 BACK 3/9
48
MBT Confidential
Aqua thermal
STATE QUERY STATE QUERY STATE QUERY
TAF2 TEMP 30 ℃ COMP TIME 65535 H DEFROSTING STATE
T5 TEMP 30 ℃ FIX PUMP TIME 65535 H 00 01 02 03 04 05 06 07
COMP TIME1 120 MIN INV PUMP TIME 65535 H 08 09 10 11 12 13 14 15
COMP TIME2 120 MIN ODU SOFTWARE V45 E2 SOFTWARE V45
COMP TIME3 120 MIN HMI SOFTWARE V45 END
BACK 7/9 BACK 8/9 OK 9/9
Note:
1. Tz plate heat exchanger outlet temperature
T3 lowest temperature of condenser tube
T4 ambient temperature
T6A, T6B EVI plate heat exchanger refrigerant temperature
Tfin1, Tfin2 inverter module temperature
TDSH Discharge superheat temperature
TSSH Suction superheat temperature
TCSH Injection superheat temperature
Twi Unit water inlet temperature
CLEAR HISTORY ERRORS is used to clear the history error codes and component operation time.
CLEAR UNIT HIS ERRS CLEAR ALL HIS ERRS
SELECT ADDRESS 07 DO YOU WANT TO YES
DO YOU WANT TO YES CLEAR?
CLEAR?
OK OK
OK OK
49
MBT Confidential
Aqua thermal
1.2.5 Setting address
MENU > Service Menu > Setting address
SERVICE MENU
CONTROLLER 10 #
STATE QUERY ADDRESS
CLEAR HISTORY ERROR CONTROL ENABEL NO
SETTING ADDRESS MODBUS ENABLE NO
HEAT CONTROL MODBUS ADDRESS 10 #
OK 1/3 OK
SETTING ADDRESS is used to set whether the unit can be controlled by wired controller and through MDOBUS. SETTING
ADDRESS can also enter by combining buttons pressing , ► for 3s.
CONTROLLER 10 #
ADDRESS
CONTROL ENABEL NO
MODBUS ENABLE NO
Midea Aqua thermal Engineering Data Book
MODBUS ADDRESS 10 #
OK
CONTROLLER ADDRESS selects the unit address then we can check the parameters about this unit.
If CONTROL ENABLE sets as YES, it means the controller can set all the parameters; if CONTROL ENABLE sets as NO, it
means the controller can only display the parameters.
If the chiller system access to MODBUS system, MODBUS ENABLE should be set as YES. Please note that in this case,
COMTROL ENABLE should be also set as YES, otherwise the units cannot be controlled.
MODBUS ADDRESS set the controller address if the Modbus system is available.
HEAT1 HEAT2
HEAT1 ENABLE NO ALL HEAT2 DISABLE YES
TEMP- 07 ℃ SELECT ADDRESS 10 #
AUXHEAT1-ON HEAT2-ENABLE NO
TW.HEAT1-ON 25 ℃ T-HEAT2-DELAY 190 MIN
TW.HEAT1-OFF 45 ℃ DT5-HEAT2-OFF 10 ℃
OK 1/2 OK 1/2
50
MBT Confidential
Aqua thermal
HEAT2 FORCED HEAT2 OPEN
T4-HEAT2-ON 10 ℃ SELECTED ADDRESS 10 #
FORCED HEAT2 OPEN NO
00 01 02 03 04 05 06 07 00 01 02 03 04 05 06 07
08 09 10 11 12 13 14 15 08 09 10 11 12 13 14 15
OK 2/2 OK
TEMP-AUXHEAT1-ON sets the ambient temperature below which the pipe heater (field supplied) turns on.
When the leaving water temperature reaches TW. HEAT1-ON, the pipe electric heater (field supplied) turns on
automatically.
When the leaving water temperature reaches TW. HEAT1-OFF, the pipe electric heater (field supplied) turns off
automatically.
If the system is installed with tank booster heater, ALL HEAT2 DISABLE should be set as YES.
HEAT2-ENABLE sets the state of tank booster heater of SELECT ADDRESS.
T-HEAT2-DELAY sets the delay time for tank booster heater to turn on after the compressor starts.
DT5-HEAT2-OFF sets the temperature difference between the actual water temperature and setting temperature above
which the tank booster heater turns off.
With the help of TEMPERATURE COMPENSATION, water temperature will automatically change as outside air
temperature changes. When outdoor air temperature increases/decreases, the heating load will decrease/increase and
water temperature will decrease/increase automatically. When outdoor air temperature decreases/increases, the cooling
load will decrease/increase and water temperature will increase/decrease automatically.
TEMP COMPENSATION TEMP COMPENSATION
COOL MODE ENABLE YES ℃ HEAT MODE ENABLE YES ℃
T4 COOL-1 15 ℃ T4 HEAT-1 15 ℃
T4 COOL-2 08 ℃ T4 HEAT-2 08 ℃
OFFSET-C 10 ℃ OFFSET-H 10 ℃
OK 1/2 OK 2/2
51
MBT Confidential
Aqua thermal
1.2.8 Pump Control
MENU > Service Menu > Pump Control
FORCED PUMP OPEN is used to control the fixed frequency pump (filed supplied) operation.
INV PUMP SETTING is used to control the inverter water pump (field supplied) operation, the setting range of RATIO-PUMP is
30%-100%. It should ensure its flow meet the requirement of whole unit, otherwise the unit may be damaged.
PUMP ON TIME sets the pump operation time after the unit stops.
If PUMP OFF TIME sets as 0, the pump will run all the time. Otherwise, the pump will operate intermittently according to the
PUMP ON TIME and PUMP OFF TIME setting.
Set range Default value Adjustment range
PUMP ON TIME 5~60min 5 5
PUMP OFF TIME 0~60min 0 5
MANUAL DEFROST can force the unit to enter the defrost mode manually.
If the external unit successfully enters the defrost mode after the “MANUAL DEFROST” is turned on, the defrost icon
52
MBT Confidential
Aqua thermal
1.2.10 Low outlet water temperature control
MENU > Service Menu > Low outlet water temperature control
LOW OUTLET WATER CTRL
SERVICE MENU
MIN TEMP FOR COOL 50℃
TMEPERATURE COMPENSATION HISTORICAL SETTING
PUMP CONTROL 04/06/2020 11:30A 5℃
MANUAL DEFROST 04/06/2020 11:30A 5℃
LOW OUTLET WATER CONTROL 04/06/2020 11:30A 5℃
OK 2/3 OK
At this page, the historical minimum water outlet temperature setting (setting range 0-20℃) can be viewed.
LOW OUTLET WATER CTRL
MIN TEMP FOR COOL 50℃
HISTORICAL SETTING
04/06/2020 11:30A 5℃
04/06/2020 11:30A 5℃
04/06/2020 11:30A 5℃
OK
OK
For projects with temporary electricity supply restrictions, the outdoor unit supports 7 levels of energy management which
53
MBT Confidential
Aqua thermal
can be set to output 40-100% capacity. It prevents tripping during electricity supply restriction conditions and remains
system continue to operate. The historical energy saving switch setting can be viewed.
OK
OK
54
MBT Confidential
Aqua thermal
1.3 PROJECT MENU
1.3.1 Structure
4. SET DEFROSTING
T_FROST
T_DEFROST_IN
T_DEFROST_OUT
5. SET E9 TIME
E9 PROTECT TIME
E9 DETECTION METHOD
55
MBT Confidential
t corresponding item and press “ ◄” or “ ►” to select restore or not. Press
” to back.
Aqua thermal
1.3.2
SETTING Project Menu
MENU > Project Menu
ntact us.Project Menu allows installers to input the system configuration and set the system parameters. Enter the password, using
◄►
and press “ to navigate
” to between
entry. The screen
digits and using ▼ ▲ to
prompts toadjust
enter the
thenumerical
password, as and then press OK. The password is 9877.
values,
PROJECT MENU
0 0 0 0
OK
TWO_COOL_DIFF sets the minimum temperature difference between the leaving water temperature (Two) and the leaving
water set temperature (TwoS) above which the unit will start for cooling mode. When Two - TwoS ≥ TWO_COOL_DIFF,
unit starts. When TwoS - Two ≥ 2 lasts for 5s, unit stops.
TWO_HEAT_DIFF sets the minimum temperature difference between the leaving water temperature (Two) and the leaving
water set temperature (TwoS) above which the unit will start for heating mode. When TwoS – Two ≥ TWO_HEAT_DIFF,
unit starts. When Two - TwoS ≥ 2 lasts for 5s, unit stops.
The target leaving water temperature of DHW mode is Twos=T5S+DT1S5. If Two>TempW_heat_Max_n, then DHW mode is
off.
56
MBT Confidential
Aqua thermal
DtTws is reserved.
TW_COOL_DIFF sets the minimum temperature difference between the total leaving water temperature (Tw) and the total
leaving water set temperature (TwS) above which the unit will start for cooling mode. When Tw - TwS ≥ TW_COOL_DIFF
+ 1, unit starts. When TwoS - Tw ≥ 2 lasts for 5s, unit stops.
RATIO_COOL_FIRST sets the number of initial startup units for cooling mode.
RATIO_HEAT_FIRST sets the number of initial startup units for heating mode.
OK
T_DIFF_PRO set the absolute difference between entering water temperature (Twi) and leaving water temperature (Two).
If |Twi - Two |≥ T_DIFF_PRO, unit stops and error code P9 appears. When |Twi - Two |≤ 6, error code
disappears.
TWI_O_ABNORMAL sets the difference between entering water temperature (Twi) and leaving water temperature (Two).
For cooling mode, if Two – Twi ≥ TWI_O_ABNORMAL and lasts for 20min, unit stops and error code PA appears. If Two –
Twi ≤ TWI_O_ABNORMAL – 1, error code disappears. For heating mode, if Twi – Two ≤ TWI_O_ABNORMAL and lasts
for 20min, unit stops and error code PA appears. If Two – Twi > 1 - TWI_O_ABNORMAL, error code disappears.
57
MBT Confidential
Aqua thermal
1.3.6 SET DEFROSTING
MENU > Project Menu > SET DEFROSTING
SET DEFROSTING
T_FROST 35 min
T_DEFROST_IN 0 ℃
T_FROST_OUT 0 ℃
OK
T_FROST sets the time between the end of the last defrost mode and the beginning of the next defrost mode.
T_DEFROST_IN sets the temperature for T3 of entering defrosting mode. When T3 reaches T_DEFROST_IN, unit enters
defrosting mode.
T_FROST_OUT sets the temperature for T3 of exiting defrosting model. When T3 reaches T_DEFROST_IN, unit exits
Midea Aqua thermal Engineering Data Book
defrosting mode.
1.3.7 DHW time setting(Customized)
MENU > Project Menu > SET DHW TIME
COOL MAX TIME sets the maximum operation time for cooling mode when DHW requirement exists.
COOL MIN TIME sets the minimum operation time for cooling mode when DHW requirement exists.
HEAT MAX TIME sets the maximum operation time for heating mode when DHW requirement exists.
HEAT MIN TIME sets the minimum operation time for heating mode when DHW requirement exists.
DHW MIN TIME sets the minimum operation time for DHW mode.
DHW MAX TIME sets the maximum operation time for DHW mode.
OK
E9 PROTECT TIME sets the delay time of water flow detection. When unit starts, water flow will not be detected until at least
(2+ E9 PROTECT TIME/60) minutes have elapsed.
E9 DETECTION METHOD sets the method of water flow detection. If “1” is selected, the water flow switch is detected after
58
MBT Confidential
Aqua thermal
water pump starts. If “2” is selected, the water flow switch is both detected before and after the water pump starts.
OK
MIN RATIO sets the minimum output ratio of inverter pump which is installed in the main water pipe.
MAX RATIO sets the maximum output ratio of inverter pump which is installed in the main water pipe.
59
MBT Confidential
Aqua thermal
Menu Parameters Setting range Default value Adjustment range
TWO_COOL_DIFF 1℃~5℃ 2℃ 1℃
TWO_HEAT_DIFF 1℃~5℃ 2℃ 1℃
TIM_CAP_ADJ 60~360s 80s 20s
TW_COOL_DIFF 1℃~5℃ 2℃ 1℃
TW_HEAT_DIFF 1℃~5℃ 2℃ 1℃
RATIO_COOL_FIRST 0~100% 50% 5%
RATIO_HEAT_FIRST 0~100% 50% 5%
T_DIFF_PRO 8~15℃ 12℃ 1℃
Project menu
TWI_O_ABNORMAL 1~5℃ 2℃ 1℃
T_FROST 20~120 min 35 min 5min
T_DEFROST_IN -5~5℃ 0℃ 1℃
T_FROST_OUT -10~+10℃ 0℃ 1℃
E9 PROTECT TIME 2~20s 5s 1
Midea Aqua thermal Engineering Data Book
60
MBT Confidential
Ver. 2022-09
Add.: Midea Headquarters Building, 6 Midea Avenue, Shunde, Foshan, Guangdong, China
Postal code: 528311
mbt.midea.com www.midea-group.com tsp.midea.com
Note: Product specifications change from time to time as product improvements and developments are released and may vary from those in this
document.
MBT Confidential