Generator relay report
Generator relay report
II. MEASUREMENTS:
21 PHASE DISTANCE-2:
Circle diameter - 1.7 ohm Offset – (0.0)
Impedance angle – 89 Time delay – 40 cycles.
24 VOLT/HERTZ -2:
Pickup – 105% Time delay - 30 cycles
40 LOSS OF FIELD-2:
Circle diameter – 33.9 ohm offset – (-1.8)
Time delay – 25 cycles
Step -1 : 50/27
Phases Injected Voltage(V) Injected Current(A) Time(sec)
R 63.51∟0⸰ 4.51
Y 63.51∟-120⸰ 4.51 0.034
B 63.51∟120⸰ 4.51
NOTE: Output -2 Operated.
Step – 2 : 50/27
Phases Injected Voltage(V) Injected Current(A) Time(sec)
R 28.51∟0⸰ 4.51
Y 28.51∟-120⸰ 4.51 2.025
B 28.51∟120⸰ 4.51
NOTE: Output -2 Operated.
59 OVER VOLTAGE - 2:
Pickup – 125 Time delay- 1500 cycles
59 OVER VOLTAGE - 3:
Pickup – 132 Time delay- 50 cycles
81 OVER FREQUENCY - 2:
Pickup – 52.0 HZ Time delay- 5 cycles
81 UNDER FREQUENCY - 1:
Pickup – 47.0 HZ Time delay- 3000 cycles
81 UNDER FREQUENCY - 2:
Pickup – 46.8 HZ Time delay- 5 cycles
STABILITY TEST:
Phases 5 CTT-1 3 CTT-1 Id Ib
R 4.07 ∟0˚ 4.07 ∟180˚
0.02 4.071
Y 4.07 ∟-120˚ 4.07 ∟60˚
B 4.07 ∟120˚ 4.07 ∟300˚ STATUS: NO TRIP
UNSTABILITY TEST:
Phases 5 CTT-1 3 CTT-1 Id Ib
R 4.07 ∟0˚ 4.07 ∟0˚
8.14 4.07
Y 4.07 ∟-120˚ 4.07 ∟-120˚
B 4.07 ∟120˚ 4.07 ∟120˚ STATUS: TRIP (6.4 ms)
SLOPE TEST – 1:
FLC X 1.5
FLC ON 3 CTT-1 4.07 X 1.5 = 6.104
FLC ON 5 CTT-1 4.07 X 1.5 = 6.104
FLC X 1
FLC ON 3 CTT-1 4.07 X 1.0 = 4.07
FLC ON 5 CTT-1 4.07 X 1.0 = 4.07
XX. RESULT:
Relay Found Healthy.