IOM1266 - Chiller WME-C
IOM1266 - Chiller WME-C
Magnitude®
Magnetic Bearing Centrifugal Chillers
Table of Contents
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
General Description . . . . . . . . . . . . . . . . . . . . . . . . . . 6 Operator Responsibilities . . . . . . . . . . . . . . . . . . . . . 25
The Control System . . . . . . . . . . . . . . . . . . . . . . . . . . 7 Operator Schools . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Sequence of Unit Operation . . . . . . . . . . . . . . . . . . 25
Nameplates . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Unit Enabling/Disabling and Overrides . . . . . . . . . . 26
Receiving and Handling . . . . . . . . . . . . . . . . . . . . . . . 8 Human Machine Interface (HMI) . . . . . . . . . . . . . . . 27
Location . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 Alarms . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
Long Term Storage . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Controller Inputs and Outputs . . . . . . . . . . . . . . . . . 49
Clearance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Building Automation Systems (BAS) . . . . . . . . . . . . 51
Mounting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 Use with On-Site Generators . . . . . . . . . . . . . . . . . . 51
Unit Dimensions and Shipping Weight . . . . . . . . . . . 10 Startup and Maintenance . . . . . . . . . . . . . . . . . . . . . 52
Retrofit Knockdown . . . . . . . . . . . . . . . . . . . . . . . . . . 11 Chiller Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . 55
Water Piping . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 Seasonal Shutdown . . . . . . . . . . . . . . . . . . . . . . . . . 55
Condenser Water Temperature Control . . . . . . . . . . 19 Seasonal Startup . . . . . . . . . . . . . . . . . . . . . . . . . . . 55
Relief Valves . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20 Maintenance Schedule . . . . . . . . . . . . . . . . . . . . . . . 56
Field Insulation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Appendix . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Field Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . 21 Definitions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
Temperature/Pressure Chart . . . . . . . . . . . . . . . . . . 58
Limited Product Warranty . . . . . . . . . . . . . . . . . . . . . 59
©2022 Daikin Applied. Illustrations and data cover the Daikin Applied product at the time of publication and we reserve the right to
make changes in design and construction at any time without notice.
Introduction
This manual provides installation, operation, and maintenance information for Daikin Magnitude® WME centrifugal chillers with the
MicroTech® controller.
NOTE: Installation and maintenance are to be performed only by licensed, if required by local codes and regulations, or qualified
personnel who are familiar with local codes and regulations and are experienced with this type of equipment.
DANGER
LOCKOUT/TAGOUT all power sources prior to service, pressurizing, de-pressuring, or powering down the Chiller. Failure to follow
this warning exactly can result in serious injury or death. Disconnect electrical power before servicing the equipment. More than
one disconnect may be required to denergize the unit. Be sure to read and understand the installation, operation, and service
instructions within this manual.
WARNING
Electric shock hazard. Improper handling of this equipment can cause personal injury or equipment damage. This equipment must
be properly grounded. Connections to and service of the MicroTech® control panel must be performed only by personnel that are
knowledgeable in the operation of the equipment being controlled.
WARNING
This equipment generates, uses, and can radiate radio frequency energy. If not installed and used in accordance with this instruction
manual, it may cause interference with radio communications. Operation of this equipment in a residential area is likely to cause
harmful interference in which case the owner will be required to correct the interference at the owner’s own expense.
Daikin Applied disclaims any liability resulting from any interference or for the correction thereof.
WARNING
Polyolester Oil, commonly known as POE oil is a synthetic oil used in many refrigeration systems, and may be present in this Daikin
product. POE oil, if ever in contact with PVC/CPVC, will coat the inside wall of PVC/CPVC pipe causing environmental stress
fractures. Although there is no PVC/CPVC piping in this product, please keep this in mind when selecting piping materials for your
application, as system failure and property damage could result. Refer to the pipe manufacturer’s recommendations to determine
suitable applications of the pipe.
CAUTION
Static sensitive components. A static discharge while handling electronic circuit boards can cause damage to the components.
Discharge any static electrical charge by touching the bare metal inside the control panel before performing any service work.
Never unplug any cables, circuit board terminal blocks, or power plugs while power is applied to the panel.
CAUTION
When moving refrigerant to/from the chiller from an auxiliary tank, a grounding strap must be used. An electrical charge builds
when halo-carbon refrigerant travels in a rubber hose. A grounding strap must be used between the auxiliary refrigerant tank and
the chiller’s end sheet (earth ground), which will safely take the charge to the ground. Damage to sensitive electronic components
could occur if this procedure is not followed.
DANGER
Danger indicates a hazardous situation, which will result in death or serious injury if not avoided.
WARNING
Warning indicates a potentially hazardous situations, which can result in property damage, personal injury, or death if not avoided.
CAUTION
Caution indicates a potentially hazardous situations, which can result in minor injury or equipment damage if not avoided.
General Description
Daikin Magnitude® Centrifugal Chillers are complete, self- piping, electric power, and control interlocks are required,
contained, automatically controlled, liquid-chilling units thereby simplifying installation and increasing reliability.
featuring oil-free, magnetic bearing compressors. All Necessary equipment protection and operating controls are
Magnitude® chillers are equipped with a single evaporator and included.
a single condenser along with either one or two compressors All Daikin Applied centrifugal chillers must be commissioned by
depending on the model. a factory-trained Daikin Applied service technician. Failure to
Magnitude® chillers are designed for indoor, non-freezing follow this startup procedure can affect the equipment warranty.
installation only. The chillers use refrigerant HFC-134a that The standard limited warranty on this equipment covers parts
operates at a positive pressure over the entire operation range, that prove defective in material or workmanship. Specific
so no purge system is required. details of this warranty can be found in the warranty statement
Only normal field connections such as water piping, relief valve furnished with the equipment.
NOMENCLATURE
W M E 106C S C
Water-Cooled Vintage
Control Panel
Evaporator Vessel
Human Machine
Interface (HMI)
Tube Sheet
Condenser Vessel
Compressor
Compressor
Evaporator Vessel
The Control System The MicroTech unit controller also communicates with the HMI
for graphic display and is located in the unit control panel, as
The MicroTech® control system consists of a Human Machine shown in Figure 4. The on-board compressor controllers are
Interface (HMI), a microprocessor-based unit controller, and located in each compressor control panel, shown in Figure 3.
compressor on-board controllers, providing monitoring and A single HMI is used per unit. The HMI panel, see Figure
control functions required for efficient chiller operation. 1, is mounted on a moveable arm to allow placement in a
The MicroTech® controllers acquire and process data related convenient position for the operator. The HMI, see Figure 2 for
to chiller operation, issue instructions to various components of an example of a screen display, is the device used for viewing
the chiller, and maintain controlled operation of the chiller. As unit information and entering setpoints into the control system.
a part of operating the chiller successfully, the unit controller Select information from the HMI panel can be downloaded
offers necessary condenser water control. See “Condenser via a USB port located on the left side of the panel. For more
Water Temperature Control” on page 20 for more information on the HMI, see “Human Machine Interface (HMI)”
information. on page 28.
Installation
Nameplates CAUTION
There are several identification nameplates on the chiller:
Extreme care must be used when rigging the unit to prevent
• The unit nameplate is located on the exterior of the Unit
damage to the control panels and refrigerant piping. See the
Control Panel. Both the Model No. and Serial No. are certified dimension drawings included in the job submittal for
located on the unit nameplate; the Serial No. is unique to the weights and center of gravity of the unit. If the drawings
the unit. These numbers should be used to identify the are not available, consult the local Daikin Applied sales office
unit for service, parts, or warranty questions. This plate for assistance.
also has the unit refrigerant charge and electrical ratings.
• Vessel nameplates are located on the evaporator and The unit can be lifted by fastening the rigging hooks to the four
condenser. They have a National Board Number (NB) corners of the unit where the rigging eyes are located, see
and a serial number, either of which identify the vessel Figure 5. A spreader bar must be used between the rigging
(but not the entire unit). lines to prevent damage to the control panels, piping, and
Receiving and Handling electrical panels. The spreader bar length should be equal
to, or no more than 1-foot shorter than, the distance between
The unit should be inspected immediately after receipt for the lifting holes located at opposite ends of the chiller. The
possible damage. All Daikin Applied centrifugal water chillers unit will require a single spreader bar of this length capable
are shipped FOB factory and all claims for handling and of supporting 1.5 times the shipping weight of the unit.
shipping damage are the responsibility of the consignee. Separately, all cables and hooks by themselves must also be
capable of supporting 1.5 times the shipping weight of the unit.
On units with factory-installed insulation, the insulation
is removed from the vessel lifting hole (also used for NOTE: The spreader bars in Figure 5 are a representation
transportation tie-downs) locations and is shipped loose. It only and may not reflect the appearance of the actual
should be secured in place after the unit is finally placed. spreader bars needed.
Neoprene vibration isolation pads are shipped loose in the If a knockdown option was ordered on the unit, reference the
power panel. If the unit is equipped with a shipping skid, leave “Retrofit Knockdown” section starting on page 12 for more
the skid in place until the unit is in its final position. This will aid information.
in handling the equipment.
Location
WME chillers are intended only for installation in an indoor or
weather protected area consistent with the NEMA 1 rating on CAUTION
the chiller, controls, and electrical panels. Equipment room If the ambient temperature of the storage location is expected
temperature for operating and standby conditions is 40°F to to exceed 113°F (45°C), then the refrigerant must be removed.
104°F (4.4°C to 40°C).
For additional tasks required, contact Daikin Applied service.
NOTE: Excessive humidity in the mechanical room should
be avoided. A limit of 90% non-condensing humidity
should be met to minimize electrical components Clearance
exposure to water condensing in panels. Humidity The unit must be placed in an area that allows for adequate
levels in the mechanical room, even if lower than
clearance around the unit. See Figure 6 for clearance
90%, can cause water to condense on/near all cool
surfaces and potentially lead to premature component requirements around the sides of the chiller. Doors and
wear. If possible, the mechanical room should be removable wall sections can be utilized to meet these
conditioned which can extend the useful lifetime for clearance requirements. There must be a minimum 3-foot
all mechanical room equipment. clearance above the top of the chiller. The U.S. National
Electrical Code® (NEC) or local codes can require more
Radiant heat from boilers or piping that would
adversely raise component surface temperatures clearance in and around electrical components and must be
beyond ambient limits must also be avoided. checked for compliance.
Drawing Notes pressure is 150 psi (1034 kPa). Consult the factory for
unit dimensions with higher design pressures.
1. Final connections must allow for +/- 1/2 inch (0.5 inch,
12.7 mm) manufacturing tolerances. 6. Unit vibration isolator pads are provided for field
installation and when fully loaded are 0.25 inches
2. 1.00-inch FPT (25.4 mm) evaporator and condenser
(6 mm) thick.
relief valves must be piped per ANSI/ASHRAE 15. See
“Relief Valves” on page 21 for more information. 7. 3.25-inch (83 mm) diameter lifting holes are provided.
See Figure 5 for lifting details.
3. Minimum Clearances (See Figure 6):
• Check local codes for any additional clearance 8. The shipping skid adds 4.00 inches (105 mm) to the
requirements. overall unit height.
• Installation layout should be designed by qualified 9. If main power wiring is brought up through the floor, this
personnel familiar with local codes. wiring must be outside the envelope of the unit.
• Hinged type waterboxes may require more clearance. 10. The unit is shipped with a full operating charge of
Consult a Daikin Applied representative for details. refrigerant except with the “Partial Disassembly”
4. Unit shown has standard right-hand water connections. knockdown option.
Left-hand connections are available for either vessel. 11. Power landing panel is on top of the cabinet. Multiple
ANSI-flanged nozzle connections are available upon point power will have two separate landing panels as
request. When using ANSI-flanged connections, add 0.5 shown in Figure 6.
inch (13 mm) to each flanged end. 12. Units with single point power, 575V, and/or the optional
5. Dimensions shown are for units (evaporator/condenser) harmonic filter will require additional panels than shown
with standard design pressures. The waterside design in Figure 7.
VFD #1 VFD #2
R.75
OUT
IN
H
OUT
IN
L W
NOTE: 1. Unit configuration may be different than illustrated. Refer to certified drawings for specific configuration/dimensions.
2. Unit length represents 2 pass, 150 psi water box configuration with grooved connections.
3. Unit height represents largest configuration possible but does not include height of removable eye bolt.
Retrofit Knockdown
Magnitude® WME chillers are relatively easy to disassemble due to the small compressor size, simplified refrigerant piping, and
the absence of a lubrication system with its attendant components and piping. Various knockdown arrangements are available as
options and are ideal for retrofit applications with tight installation clearances.
Scope:
• Site disassembly and reassembly must be supervised or • Blockoff plates are required to cover any refrigerant
completed by Daikin Applied service personnel. connection left open for extended periods of time. Contact
• Unit is fully tested at the factory prior to shipment. Daikin Applied service to obtain these parts.
• The chiller is shipped completely assembled with the • Check that no power is being applied to the unit. Before
full refrigerant charge, which must be recovered before disconnecting any wire, it is prudent to label its function
breaking any refrigerant connection. and connection point to facilitate reconnection.
• The refrigerant charge must be removed from the unit • Unit ships with vessel and/or head insulation, if ordered.
if the vessels are to be separated. Exert the proper • Unit ships with replacement refrigerant gaskets and
precautions before attempting any disassembly, assume O-rings, stick-on wire ties, and touch-up paint. Some
the condenser isolation valves may have leaked and that insulation repair and touch-up painting may be required.
any component of the chiller may be pressurized with
refrigerant. CAUTION
• Suction and discharge lines have bolt-on flanges. Standard torque specs must be followed when re-installing
bolts. Contact Daikin Applied service for this information.
• Motor cooling line is brazed at mechanical connections.
VESSEL
BREAKPOINTS
COMPRESSOR
(x2 FOR DUAL COMPRESSOR MODELS)
VESSEL
BREAKPOINTS
GLUE
Scope:
• Site reassembly must be supervised or completed prior to attempting to open any connection.
by Daikin Applied service personnel. Cost for unit • All free piping ends are capped. Blockoffs will cover all
reassembly and supervision by Daikin Applied service compressor and vessel openings.
is not included in the purchase price of the equipment.
• Unit ships with vessel and/or head insulation, if ordered.
Contact Daikin Applied service for pricing.
• Unit ships with replacement refrigerant gaskets and
• Unit is fully tested at the factory prior to disassembly and
O-rings, stick-on wire ties, and touch-up paint.
shipment.
• All associated piping and wiring remain attached, if CAUTION
possible. Suction and discharge lines have bolt-on Standard torque specs must be followed when re-installing
flanges and, if possible, remain attached. If the stack size bolts. Contact Daikin Applied service for this information.
or weight dictates further disassembly, the vessels can
be separated by disconnecting any interconnecting wiring WARNING
and tubing and then unbolting them.
Remove compressor, piping or vessel holding charge through
• Refrigerant will not be shipped with the chiller and must
the Schrader valve in the blockoff plates before attempting to
be procured by others. Compressor(s) and vessels
loosen any fittings on them. Failure to do so can cause severe
receive an inert gas holding charge that must be released
bodily injury.
W28 W28
W28 TOP VIEW TOP VIEW
(E30/C2612 ONLY) TOP VIEW
(E30/C2612 ONLY)
(E30/C2612 ONLY)
W23
W23W23
H26 H26
H26
W27 W27
W27
FRONT VIEW FRONT
FRONT VIEW
VIEW RIGHT VIEW RIGHT
RIGHT VIEWVIEW
LEFT VIEW LEFTVIEW
LEFT VIEW UNIT REPRESENTATION UNIT
UNIT REPRESENTATION
REPRESENTATION (E30/C2612 ONLY) (E30/C2612
(E30/C2612 ONLY)
ONLY)
(E30/C2612 ONLY) (E30/C2612
(E30/C2612ONLY)
ONLY) (E30/C2612 ONLY) (E30/C2612 ONLY)
(E30/C2612 ONLY)
W28
EVAPORATOR
CONDENSER
TOP VIEW
W24
H27
H26
H28
H25
Figure 11: Unit Dimensional Diagram for Typical WME Knockdown - Dual Compressor Models
W29
W28
EVAPORATOR
CONDENSER
TOP VIEW
FRONT VIEW
TYPICAL UNIT REPRESENTATION
334981973
W24
H27
H28
H26
H25
W27 W23
LEFT END VIEW RIGHT END VIEW
NOTE: See page 11 for overall unit length, width, and height dimensions for WME models.
Label Description
H28 70.2 (1784) 54.7 (1389) 58.6 (1489) 62.1 (1577) 71.5 (1817) 71.1 (1807) 79.5 (2021) 79.5 (2021) 79.5 (2021) 84.3 (2141)
in the two holes on the top of the compressor (see Figure 15,
flag #9). Use a spreader bar between the two chain hoists,
as shown in Figure 13, to safely lift the compressor. Note
compressor weights and dimensions in Table 6 and unit rigging
instructions in Figure 5 on page 9.
6
335652806
Compressor Removal
1. Loosen and remove bolts/screws on either side of the
cast suction elbow (see Figure 15, flag #1).
NOTE: The spreader bar in Figure 13 is a representation
only and may not reflect the appearance of the actual
spreader bar needed. Figure 15: Compressor Removal/Re-Attachment
9
CAUTION
Units are shipped with refrigerant valves closed to isolate the
refrigerant in the unit condenser. Valves must remain closed
until startup by the factory service technician.
Relief Valves
Field Insulation for wiring information. These wiring diagrams are also provided
with the chiller.
If the optional factory installation of thermal insulation is not NOTE: Wiring, fuse, and wire size must be in accordance
ordered, insulation should be field installed to reduce heat with the National Electrical Code® (NEC). The voltage
loss and prevent condensation from forming. Insulation should to these units must be within ±10% of nameplate
cover: voltage (415V units must have voltage within -13%
and +6% of nameplate voltage) and the voltage
• the evaporator barrel, tube sheet, and waterboxes.
unbalance between phases must not exceed 2%.
• the suction line from the top of the evaporator to the Since a 2% voltage unbalance will cause a current
compressor inlet flange. unbalance of 6 to 10 times the voltage unbalance per
• the compressor support brackets welded to the the current version of the NEMA MG-1 Standard, it is
evaporator. most important that the unbalance between phases
be kept at a minimum.
• the liquid line from the expansion valve to the evaporator
inlet, including the expansion valve. CAUTION
• the part load balance valve to the evaporator. Do not use power factor correction capacitors with WME
Approximate total square footage of insulation surface required chillers. Doing so can cause harmful electrical resonance in
for individual packaged chillers is tabulated by evaporator code the system. Correction capacitors are not necessary since
and can be found in Table 9. VFDs inherently maintain high power factors.
24N-11
24-20
The standard power wiring connection to Magnitude® chillers 22 for wiring. When Lon protocol is used the UE1 module
is multi-point for dual compressor WME models. Power conduit HMI
+
-
entry will be at the top of the unit power panel; see Figure 21 2 remains and a Lon card is connected to the Unit controller inS1
the BMS CARD port.
24-18
E-PORT2
3 Figure 22: BAS Module Wiring Schematic
ETR4
ETR2
vary by unit configuration. Copper wiring must be used for
CMPR BOX #1
+24V
24N
33
VGA
01-5
01-10
FIELD WIRING
VDC OR VAC
AR4
FOR BACNET-MSTP
NO
NC
OR MODBUS
01-2
01-2
SENSOR GND
SENSOR +5V
DANGER 8
8
10 9
10 9
24-15
24-16
24N-7
24-11
120-13
120-12
RED(3)
BLK(3)
Tx+/Rx+
Tx+/Rx+
+Vdc
+5Vref
GND
GND
NO3
C3/4/5
NO4
C3/4/5
NO5
NO1
C1/2
NO2
NO6
NC6
C6
or death.
Tx-/Rx-
GND
J10 J12
J11 J9
J3 DISP J4 FBus
BUE1
UE1
Address = 1
EHUB
TxL/RxL
GND
GND
U10
GND
U4
U5
U6
U7
U8
U9
G0
G
WHT
WHT
RED
RED
RED
RED
BLK
24N-4
24-12
24-13
24-14
32 24 25
CLWT
21
25 FIELD WIRING
ELWT
BACNET-IP
01-4
01-4
CEWT
EEWT
GND
+5V
PE
(SCALE: 0-125% RLA)
0-10V
PE
GND
GND
PWR
SIG
PWR
SIG
PWR
SIG
Standard RapidRestore®
Fast Loading
Compressor Compressor RideThrough®
to 80% Load
Re-Start Re-Start
20 sec
60 sec after power 75 sec** 5 sec***
failure*
* Requires customer supplied Uninterruptible Power Supply (UPS) to the WME
control panel.
** After compressor re-start time
*** Time is based on unit operating at AHRI conditions.
24-40 24N-21
24N-20
24-41
RR
RM
RPS
WME SINGLE RR
BLK
BLK
BLK
BLK
PE PE PE
120N
120V
PE
BLK
BLK
GRN
GRN
UPWR1-#7
UPWR1-#2
UPWR1-#1
DRAWING 3360781020A01
SCHEM, COMPRESSOR CONTROLLER
SEE DWG 336078103
SCH
REV. DATE DRN ECO REV CHANGES
ADDED LOCAL NOTES OF APPLICABILITY TO RAPID RESTORE AND
EEWT EVAPORATOR ENTERING WATER TEMPERATURE PC INDUSTRIAL COMPUTER UE1 UNIT CONTROLLER EXPANSION
ELWT EVAPORATOR LEAVING WATER TEMPERATURE PE PROTECTIVE EARTH USB UNIVERSAL SERIAL BUS
EMI ELECTRO-MAGNETIC INTERFERENCE FILTER PFD POWER FAULT DETECTION UTB UNIT TERMINAL BLOCK
EN ENABLE PFD-CM POWER FAULT DETECTION - COMMON VFD VARIABLE FREQUENCY DRIVE
EP EVAPORATOR PUMP PLBV PART LOAD BALANCING VALVE VFDN VARIABLE FREQUENCY DRIVE BUS (-)
ETR ETHERNET PLBDRV PART LOAD BALANCING DRIVER VFDP VARIABLE FREQUENCY DRIVE BUS (+)
EVPP EVAPORATOR PRESSURE SENSOR PS POWER SUPPLY VFEN VFD ENABLE
EXV ELECTRONIC EXPANSION VALVE PWR POWER VFPLC VFD ENABLE 24 VOLTS
EXVDRV EXPANSION VALVE DRIVE
FIELD CONNECTIONS
MAIN MULTI POINT CONNECTION MAIN SINGLE POINT CONNECTION
CIRCUIT BREAKER CIRCUIT BREAKER CIRCUIT BREAKER
(BY OTHERS) (BY OTHERS) (BY OTHERS)
L1 CUSTOMER L1 CUSTOMER L1
CIRCUIT BREAKER SUPPLIED CIRCUIT BREAKER SUPPLIED CIRCUIT BREAKER
OR L2 L2 OR POWER L2 OR
POWER
DISCONNECT DISCONNECT DISCONNECT
SWITCH L3 L3 SWITCH L3 SWITCH
(+24V) (CM)
TOUCH SCREEN
(MONITOR)
DISPLAY
FIELD OPTIONS
UTB2 25 UTB2 34 UNIT MOTOR UNIT CONTROL BOX
0-10V CURRENT OUTPUT UNIT CONTROLLER EXPANSION CONTROLLER
CB1 CUSTOMER SUPPLIED Customer
CUSTOMER SUPPLIED
(SCALE: 0-125%) L1 Customer L2 UTB1 RELAY COMMON UTB1 9 UTB1 13
Supplied
RELAY COMMON Supplied
11
POWER (24VDC OR ALARM RELAY POWER
24
OUTPUT CP1 CONDENSOR PUMP #1
NO4
UTB1 4 UTB1 12
UTB2 30 UTB2 35 COOLING TOWER
0-10V CP2 CONDENSOR PUMP #2
VFD OUTPUT
NO5
UTB1 5 UTB1 12
REMOTE ENABLE TS1 TOWER STAGE #1
UTB2 31 (BUILDING) UTB2 22 FEEDBACK INPUT
REMOTE NO6
(UNIT SUPPLIED UTB1 6 UTB1 12
SWITCH TS2 TOWER STAGE #2
24VDC)
www.DaikinApplied.com
Installation
Installation
12
11
10
1
Figure 25: WME Unit Wiring Schematic
21
+24V
UE1
24N
21
J10
24N-4
J1
24N-7
36
G0 C1/2 01-2
32
PE
Vbat NO2
EEWT RED
HMI
U1 NO3
ELWT
ENCLOSURE
RED
BUE1
DOOR
GS1
CEWT
J11
RED
U3 NO4
BLK(3)
GND C3/4/5
PWR +5V
01-4
CLWT RED
U4 NO5
EVPP
GND
01-4 WHT
GND
ALARM NO/NC
U5 120-12
NO6 AR3
J2
WHT
SIG
8
U6
13 13 13
NC
8
J12
120-14
PWR
NC6 AR4
PE
BLK
CNDP
GND
10 9
10 9
NO
ON
120-13
GND
Address = 1
C6
33
24/120V
1234 1234
MODBUS
UE1
SIG U7 VDC OR VAC
24N-8
PWR
RED(3) SENSOR +5V 01-5
U8 +5Vref 01-10 24-18
LLP
GND
24-13 BLK(3) SENSOR GND
GND
J9
U9 01-10
WME-C UNIT BOX SCH SECT 2
24 25
USB
24-14
SIG
U10 +Vdc
25
GND
+Vtwrm
PC1
FOR BACNET-MSTP
UNIT MOTOR CURRENT OUTPUT
(J3 DISP)
TxL/RxL
(J5 CAN)
FIELD WIRING
0-10V Tx-/Rx-
ADAPTER
OR MODBUS
34
(BUE1)
TxH/RxH Tx+/Rx+ VGA
336078102
PART NUMBER
GND GND
FIELD WIRING
ETR2
(EHUB)
BACNET-IP
20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36
(BUE1)
(J4 FBus)
+24V
Tx-/Rx-
J6 BMS
SCHEM, COMPRESSOR
SEE DWG 336078103
CONTROLLER
E-PORT2
Tx+/Rx+
CMPR BOX #2
24-15
UTB2 TERMINAL BLOCK JUMPERS
GND
24-16
REVISION
ETR4
24-17
0A
24-1
22
G
RJ45
pLAN
24-20
+
21
J1
S1
24N-1 -
G0 24N-11
34
-
35
J11 pLAN
ETR3
+Vterm
+
J24
SCHEM, COMPRESSOR
CONTROLLER
SEE DWG 336078103
GND
E-PORT1
CMPR BOX #1
GND
ETR1
+5Vref
LEAVING WATER RESET
4-20mA
24N
24-2
ETHERNET
U1
1
28 28
26 27
26 27
HUB
DEMAND LIMIT
24-3 CUSTOMER SUPPLIED POWER
4-20mA U2
2
Customer
24/120VAC
U3
J2
L1
L2
24-4
GND CB1 120N-1
28
120-2
RM/POWER WIRING
SEE PAGE 2 FOR
120-1
+VDC C1
11
L2
6A
L1
EVAP PUMP #1
120-3
NO1 EP1
1
DRAWING 3360781020A01
11 11 11
1
EVAP PUMP #2
U4
J12
120-4
NO2 EP2
PE
CONDENSOR PUMP #1
2
GND NO3
120-5
CP1
LLT
J3
RED
U5 C1
120-6
BLK
GND
C4 CONDENSOR PUMP #2
1 2 3 4 5 6 7 8 9 10 11 12 13
24-5
VG NO4
120-7
CP2
UTB1 TERMINAL BLOCK JUMPERS
20
12 12 12
4
4
TOWER STAGE #1
24N-2
VG0
J13
120-8
NO5 TS1
32
5
5
29 30
29 30
J4
6
6
24-8
01-2 Y3
Y4 C7 TOWER STAGE #3
J14
120-11
NO7 TS3
13
7
ID1 C7
NEUTRAL BLOCK
ID2
ID3 NO8
22
J15
24-23
PC RESET
ID4 C8
24-18
REMOTE
NC8
SWITCH
24-9 01-3
ID5
J5
31
INPUT
22
31
PWR
-
UC1:ID6 WHT
01-12 ID6
J25 BMS2
UC1:ID7 WHT
01-9
ID7
01-12
SW-1 WHT
+
ID8 GND
23
24-8
IDC1
SW-1
-
+ BRN
23
EEFS
+24VAC/DC
+ BLK
J26 FBus2
ON
BLK S+
36
SW1 (UNIT SWITCH)
UC1
24N-9
1 2 34 5 6 7 8
+
UC1:ID6 WHT
3
UP TO 4 ACTUATORS
S-
01-10
24N-3
- 24-11
BLU 01-5 OPEN
33
24N WHT
24N-7
GND 01-5 REF
LONMARK WIRING
BLK(2)
ACT1
ACT2
B
4
EXVDRV
GND A
23
WHT(2)
BLK
+ BRN W
23
+24VAC/DC
CEFS
GRN(2)
+ BLK
BMS CARD
G
RED(2)
SW-2
35
UC1:ID7 WHT R
01-10 GRN 24-19
- BLU 24V+
33
20
24N 24N-10
B
24V-
RED
36
21
Operation
Sequence of Unit Operation accomplished by opening the Part Load Balance Valve
(PLBV).
A general chiller sequence of operation is outlined below 8. Chiller shutdown
for Magnitude® Model WME chillers. A separate sequence
The compressor will adjust capacity to manage the
is provided for single and dual compressor units. Certain
chiller load and will shut off when the load reduces below
conditions and chiller alarms may alter the sequence, but the
the compressor's minimum capacity and the leaving
chiller’s objective is to achieve the target temperature of the
water temperature goes below setpoint and reaches the
leaving water.
stop delta temperature. Anytime the chiller is disabled,
Placing two chillers in series evaporator operation or series- it will perform an orderly unload and shutdown of the
counterflow configuration is possible and requires connecting compressor.
an Ethernet cable between the unit control panels and
reassigning a temperature sensor. Communication directly Dual Compressor Units
between the chillers allows better control of leaving water
temperature while balancing the load. Contact a Daikin Applied The following sequence of operation applies to Magnitude®
representative for specific details. Model WME chillers with dual compressors.
1. Chiller enabled
Single Compressor Units With the chiller enabled via its onboard interlocks
The following sequence of operation applies to Magnitude® and selected external control source, it will start the
Model WME chillers with a single compressor. evaporator pump and check for flow and chiller load.
1. Chiller enabled 2. Water flow and load proven
With the chiller enabled via its onboard interlocks Once evaporator flow has been confirmed and the
and selected external control source, it will start the chiller load proven, the sequence for starting the Lead
evaporator pump and check for flow and chiller load. compressor will begin. Auto lead-lag logic will determine
which compressor to start first based on number of
2. Water flow and load proven
starts. For 099 models, the smaller compressor will start
Once evaporator flow has been confirmed and the chiller first.
load proven, the sequence for starting the compressor
3. Compressor shaft levitation
will begin.
The magnetic bearings are activated and correct shaft
3. Compressor shaft levitation
position is verified.
The magnetic bearings are activated and correct shaft
4. Condenser pump start
position is verified.
The condenser pump is commanded to start and water
4. Condenser pump start
flow is confirmed. EXV must be open.
The condenser pump is commanded to start and water
Human Machine Interface The Home View Screen, see Figure 27, is the main information
page for the chiller. This screen contains the AUTO and STOP
(HMI) buttons in the upper right-hand corner, which are used to start
and stop the unit when in “User” control mode. Other groups
The HMI is turned on/off with a switch located at the lower of screens can be accessed from the Home View Screen by
right-hand edge of the display panel. Screen control buttons pressing one of the icons on the bottom of the screen.
are located to either side of it and elicit on-screen prompts
An initial startup step may be to select the Operator icon on the
when pressed. The HMI is equipped with a screen saver (a
bottom right of the HMI to access the Operator screen (Figure
blank, black screen). If the screen is black, touch it first to be
26) to set display language and unit of measure preferences as
sure it is on before using the ON/OFF button.
well as input the appropriate level of password for making unit
adjustments going forward. Should the touch screen cursor
Chiller Operation Without the HMI not respond to where the screen is being pressed, use the
The Human Machine Interface (HMI) communicates with the Calibrate button to recalibrate the screen. The Calibrate button
embedded Chiller PC (Figure 4 on page 7), displaying is oversized to make it easier for the non-calibrated cursor to
data and transmitting touch screen inputs to the controllers. select.
The HMI does no actual controlling and the chiller can operate
without it. Should the Touch Screen become inoperable, no
commands are necessary for continuing unit operation. All
normal inputs and outputs will remain functional. A PC monitor
and USB mouse can be connected to the Chiller PC via its
display port and can be used to view operational data, to clear
alarms, and to change setpoints, if necessary.
If the HMI and the chiller both appear to be inoperable, the
embedded Chiller PC should be checked since it is required for
the chiller to run.
Navigation Summary
(III) Additional Home View Trend Data Graphs Additional HMI View Screens
• Entering and leaving evaporator water temperatures Pressing the Detail Tab on the top of the Home View Screen
• Entering and leaving condenser water temperatures provides specific unit operating parameters shown in Figure
• Percent compressor speed 32. Similarly, the Power Tab will show current, voltage, and
power information for each compressor as well as the unit, see
• Compressor kW
Figure 33.
(IV) Alarm
The HMI screens for the four main components will highlight
• The ALARM icon will turn red and begin flashing should the relevant portion of the chiller (see Figure 34 to Figure 37)
an alarm occur. This red ALARM button will appear on and provide additional information not found on the Home
all screens in the case of an alarm. See Figure 31 for an screens. Similarly, the cooling tower information is shown on
example of an active alarm alert. For more information on Figure 38.
alarms, see page 44 through page 46.
To make setpoint adjustments or change operating parameters,
Figure 31: Active Alarm Icon tap on the Settings icon at the bottom of the screen, see Figure
39 on page 34.
The Compressor State Information on the right side of the the shut down process, the sequence transitions back to "Off"
screen is a compilation of events the chiller sequences through and the highlight color will switch to black.
at startup. A green light indicates that a particular sequence The left-side information displays the status of the compressor
requirement has been satisfied. It is recommended that this in greater detail than on the Home Detail screen (Figure 32).
information be viewed during the startup sequence. One Compressor related setpoint adjustments can be made within
can see the requirements light up as they are met and also the Settings screen on the Modes and Motor tabs.
determine why a non-start may have occurred. Similarly during
NOTE: Selection and setup of cooling tower control methods is in the Settings icon, Tower tab, see Figure 44 on page 37.
SET Screens
The Setpoint Screens on the HMI are used to input the 8. COMMISSION - sets parameters and component
various setpoints associated with equipment of this type. (Note configurations.
that if the HMI is unavailable, setpoints can be changed by 9. INTERFACE - sets the network protocol and associated
connecting a laptop.) Appropriate setpoints are factory set and options.
checked by a Daikin Applied service representative during
commissioning; however, adjustments and changes are often 10. UPDATER - allows upload of software file updates.
required to meet job conditions. Certain settings involving
pumps and tower operation are field set.
A typical Setpoint Screen is displayed in Figure 39. A list of
Pressing the Settings icon found at the bottom of every screen setpoints along with their default value, available setting range,
accesses the last Setpoint tab used. There are nine setpoint and password authority can be found in the tables after each
tabs accessible across the top of the Settings screen: Setpoint Screen, starting on page 35. The WATER button,
1. WATER - sets leaving water temperature setpoint, start for example, contains various setpoints relating to water
and stop Delta T, resets, etc. temperature setpoints.
2. MODES - selects various unit parameters such as liquid In Table 14 and in the rest of the Setpoint tables on the
injection, timers, pump staging, control source, unit following pages, the letters in the Password column refer to the
mode, etc. following:
3. MOTOR - selects power related setpoints such as amp • M = Manager Level (The password number will be
limits. supplied by Daikin Applied service at startup.)
4. TOWER - selects the method of controlling the cooling • O = Operator Level (The password number for
tower and sets the parameters for fan staging/VFD. operator level is 100.)
• T = Technician Level (The password number for
5. VALVE - sets the parameters for operation of the
technician level is only provided to Daikin Applied
expansion valve.
technicians.)
6. OFFSETS - adjustment values based on calibration.
7. ALARMS - sets the limit and shutdown alarms.
Procedure for Changing a Setpoint 5. Additional setpoints can be changed by selecting another
setpoint on the screen using the Setpoint Selection
1. Press the applicable Setpoint Group.
buttons or by selecting an entirely new group of setpoints
2. Select the desired setpoint by pressing the numbered using the Setpoint Group buttons.
Setpoint Field.
3. A password must be entered before changing any
CAUTION
setpoint value. A keypad prompt will appear to enter a
password and then the keypad or drop down menu will Many setpoints are interactive. Changes may have an adverse
appear to make the desired change. effect on chiller operation. Only trained operators should be
allowed to change chiller setpoints.
Input the appropriate password number. There is a small NOTE: Setpoints that have a technician level password
delay between pressing the keypad and recording the (T) should only be changed by a Daikin Applied
entry. Be sure that an asterisk appears in the window technician. Contact a Daikin Applied service
before pressing the next number. representative for more information.
4. Setpoints with numeric values can be changed in two
ways:
• Select the desired value by pressing the numbered
buttons on the Numeric Keypad.
• Press the UP or DOWN button to increase or
decrease the value displayed.
Some setpoints are selectable text menus rather than
numeric values. Select the desired option using the
dropdown menu that appears on that particular setpoint.
Toggle between choices using the UP or DOWN button.
If dashed lines appear in the setpoint window, it means
that toggling in that direction can go no further, so
reverse direction.
For all of the methods listed above, press ENTER on the
Setpoint Screen to enter the value or CANCEL to cancel
the transaction. The CANCEL or ENTER buttons must be
pressed before another setpoint can be selected.
CAUTION
Chiller Nameplate RLA MUST match chiller dataplate per compressor.
Tower Control Strategies • VFD speed -100%/N stages when adding 2nd and
or 3rd stage
There are four possible tower control strategies that can be
selected with the Cooling Tower Control (Temp, Lift) and Tower • VFD speed +80%/N stages when dropping 2nd and
Control Mode (Manual, Auto, Auto Efficiency) settings: or 3rd stage
• For one tower fan stage
1. Manual: Tower control outputs are set to operator
configured values. • turn on at 90 TCLO if tower bypass valve position is
2. Temp, Auto: Tower control is reactive to the delta > 90% of Valve Control Range - Max
between set point and process value (CEWT), and the • turn off at 20 TCLO
process value rate of change. This allows the set point • For multiple tower fan stages:
to be reached by adjusting tower output over time, if
• (E)nable threshold = 90 / N stages
possible, given the cooling tower capability as well as
outdoor air temperature and humidity. • (D)isable threshold = 20
3. Lift, Auto: Tower control is reactive to the delta between • For 2 stages:
set point and process value (Lift), and the process • 1 on E*1 TCLO and tower valve > 90%, 2 on E*2
value rate of change. This allows the set point to be TCLO and tower valve = 100%
reached by adjusting tower output over time, if possible,
• 2 off D*2 TCLO, 1 off D*1 TCLO
given the cooling tower capability as well as outdoor air
temperature and humidity. • For 3 3 stages:
4. Temp, Auto Efficiency: Operates the same as Auto, • 1 on E*1 TCLO and tower valve > 90%, 2 on E*2
except that when tower fan output is at 100%, after 15 TCLO and tower valve = 100%, 3 on E*3 TCLO
minutes has elapsed, tower fan output is slowly reduced and tower valve = 100%
until CEWT increases to find where increasing tower fan
• 3 off D*2 TCLO, 2 off D*1 TCLO, 1 off D*.5
output would no longer be effective in reducing CEWT.
TCLO
Fan output control will return to normal if the process
value increases by more than 0.2°F or drops below the Figure 45: Chiller Unit Tower Control
set point. Cooling Tower
5. Lift, Auto Efficiency can be selected but will operate the Fan Staging
same as Lift, Auto. Cooling Tower Control by temperature (Up to 2 fans) Tower
is recommended. Control
0-10 VDC Panel
For all strategies, the chiller unit controller can control up to w/ Fan
Signal
three tower fan stages, as well as a tower fan VFD and either a VFD
tower bypass valve or condenser pump VFD. See Figure 45.
Bypass Line Bypass
Within each variation of the Auto and Auto Efficiency, a PD loop MicroTech® Valve
determines a tower capacity loop output (TCLO) value that Controller 0-10 VDC Signal
goes from -100 to 100, where -100 is reducing tower capacity
as quickly as possible, 0 is leaving tower capacity unchanged, Condenser
and 100 is increasing tower capacity as quickly as possible.
• Tower bypass valve BAS Tower Control
• steps open above 10 TCLO In the above control strategies, the chiller unit controller is
• steps closed below -40 TCLO directly controlling the cooling tower fan stages, variable
• Tower fan on/off events limited in frequency by timers for frequency drives, and bypass valve. As an alternative, a BAS
staging up and staging down can control these components based on the 0-10 VDC signals
for the tower fan VFD and tower bypass valve or condenser
• For a given number N of tower fan stages, all VFD
pump VFD. See Figure 46.
controlled:
• all stages run at the same speed Figure 46: BAS Tower Control
• VFD speed steps up from minimum speed setting
to maximum speed setting when above 15 TCLO
Tower
and tower bypass valve position is > 90% of Valve Control BAS
Control Range - Max Panel
w/ Fan
• VFD speed steps down below -5 TCLO VFD
• For a given number N of tower fan stages, where one
Bypass Line
stage is VFD controlled:
MicroTech®
• VFD speed steps up from minimum speed setting to Controller 0-10 VDC Signal
CAUTION
Changing setpoint below 28 psi minimum requires glycol to be added to the system otherwise there is a risk of freezing the evaporator.
NOTE: If both compressors have the same sequence number, they will automatically balance starts and run-hours. User cannot manually
stage compressors as this is an internal process.
NOTE: It is likely that the chiller will contain the factory settings for date and time; therefore, it is important to verify or change these settings
when the chiller is first used on the jobsite. Failure to do so will result in incorrectly labeled History files.
The version numbers shown towards the bottom left of the screen are the controllers’ software identification. These numbers may be
required by Daikin Applied to answer questions about unit operation or to assist in possible future upgrades of software.
NOTE: “Sensor Range” in Table 26 indicates the range of the input, NOT the operating range of the chiller.
NOTE: “Sensor Range” in Table 28 indicates the range of the output, NOT the operating range of the chiller.
Pre-Startup
Inspect the chiller to ensure no components became loose or It is required that the flow switch be mounted such that the
damaged during shipping or installation including leak test and electrical connection and indentation ‘mark’ are pointed in the
wiring check. Complete the pre-start checklist at the front of direction of flow as shown in Figure 58.
this manual and return to Daikin Applied prior to startup date. If the flow sensor is to be mounted away from the unit, the
CAUTION sensor should be mounted on the wall of the outlet pipe of
evaporator and condenser, or in a run of straight pipe that
Dyes used for refrigerant leak detection are not tested allows 5 to 10 pipe diameters prior to the sensor and 3 to 5
or recommended for use in Daikin chillers. Use of these pipe diameters of straight pipe after the sensor. Flow switch
products may damage and/or degrade the performance of the is placed in outlet pipe to reflect flow leaving the barrel. If
equipment and will void the manufacturer warranty installation on the inlet pipe is necessary, contact Chiller
NOTICE: Technical Response at [email protected] to
Daikin Applied service personnel or factory authorized review the jobsite details.
service agency must perform initial startup in order to activate
warranty. They must return the “WME Centrifugal Equipment Figure 58: Mount in Direction of Flow
Warranty Form” within 10 working days to Daikin Applied as
instructed on the form to obtain full warranty benefits.
Mounting
Figure 57 highlights the position of the electrical connector and
indentation ‘mark’ on flow switch.
Figure 57: Flow Switch Details
If needed, the adapter is threaded into the pipe using pipe Figure 60: Automatic Teach of Setpoint
sealant appropriate for the application. The flow sensor is
mounted onto the adapter using silicone grease. Carefully
apply lubricant to the inside threads and O-ring so temperature
probe does not become coated with lubricant. Torque the
adapter/sensor connection to 18.5 ft/lbs.
Wiring
Refer to wiring diagram in the unit control panel.
Either AC or DC is used to power the flow switch. The unit
controller’s digital input is a DC signal which is supplied
through the switch output of the flow switch for flow indication.
It is required that the AC and DC commons of power be
separated. Contact Chiller Technical Response for alternate Step 3: After the ‘Teach’ function is completed and the outer
wiring scenarios. LEDs have flashed, the flow switch will indicate a new setpoint
based upon the current flow which should still be at the steady
Flow Switch Setup state minimum desired operating flow. Figure 61 shows a
typical display for this condition. All LEDs to the left of the
The flow switch comes from the factory set at a default velocity SP LED are lit green. The SP LED is lit RED (or may toggle
of 20 cm/s. This value is typically well below the minimum amber) which indicates that the flow switch is OPEN. Typically,
water flow specified for the unit evaporator and condenser so an increase in fluid flow between 15% to 30% above the
field adjustment is required for adequate low flow protection. ‘Teach’ function flow is required for the SP LED to turn AMBER
Table 33 shows the calculated gallons per minute (gpm) for and the flow switch to CLOSE indicating acceptable flow.
Schedule 40 steel pipe for various fluid velocities from
20 cm/s to 300 cm/s. The flow switch has an overall range of
adjustment from 3 cm/s to 300 cm/s. Figure 61: Teach Adjustment Complete
Table 34: In Step 3, the ‘Teach’ function re-adjusted the flow switch SP while flow was at the minimum desired operating flow. The
chiller will not operate at this flow because the flow switch is OPEN after performing the ‘Teach’ function. The benefit of the ‘Teach’
function is to quickly set the setpoint within the desired operating range. Additional ‘manual’ adjustment of setpoint is required in
order to allow for chiller operation at this minimum flow. The ‘+’ and ‘-’ buttons on the face of the flow switch allow for the manual
adjustment of the SP. Pressing the ‘+’ button reduces the flow setpoint while pressing the ‘-’ button increases the flow setpoint.
Each button press, ‘+’ or ‘-‘, changes the flow setpoint by 2.5 cm/s.
Step 4: Press the ‘+’ button until LED ‘9’ begins to flash, as Flow below display range: The SP LED will be lit red and
shown in Figure 62. Opening of flow switch should now occur the leftmost LED will be flashing green. For example, if the SP
at approximately 80% to 90% of minimum flow. was set to 200 cm/s, the flashing labeled ‘0’ would indicate that
the flow was below 180 cm/s. This would be shown if no flow
Figure 62: Upper Range of Minimum Flow through chiller or lowered than desired flow.
Maintenance Schedule
Table 35 provides an overview of recommended maintenance procedures along with how frequently these procedures should be
performed.
Table 35: Recommended Maintenance Schedule
Performance
As Required
Shutdown
Seasonal
Seasonal
Quarterly
Annually
Annually
Monthly
Startup
During
During
Semi-
By
I. Compressor
A. Analyze Compressor Fault Log X
B. Check IGV operation X
C. Check and tighten compressor electrical connections X
D. An inspection should be performed on the compressor *X
rotor grounding rod every 5 year
II. MicroTech® Controls
A. Check for proper settings X
B. Verify transducers and sensors for accuracy X
C. Retrieve and archive HMI Trend Logs O
D. Perform MicroTech® check, log, and last fault analysis X
III. Condenser
A. Confirm correct water flow and pressure drop O X
B. Confirm appropriate water treatment O
C. Clean and Leak Test condenser tubes X X X
D. Eddy Current Test - tube wall thickness X
E. Seasonal Protection X
F. Clean Flow Sensor X X
IV. Evaporator
A. Confirm correct water flow and pressure drop O X
B. Confirm appropriate water treatment O
C. Clean and Leak Test evaporator tubes X
D. Eddy Current Test - tube wall thickness X
E. Seasonal Protection X
F. Clean Flow Sensor X
V. Chiller Unit
A. Run Test/Performance Evaluation X
B. Leak Test entire unit X X X
C. General Appearance:
1. Paint/Corrosion X
2. Insulation X
VI. Electrical
A. Check and record line voltage X
B. Inspect power components for signs of overheating X
C. Check and tighten unit electrical components X X
D. Check all panels for cleanliness - remove dust and debris X
from electrical boards and connections
Definitions Appendix
Temperature/Pressure Chart
Table 36: R-134a Temperature/Pressure Chart
Daikin Applied Americas Inc. dba Daikin Applied (“Company”) warrants to contractor, purchaser and any owner of the product
(collectively “Owner”) that Company, at it’s option, will repair or replace defective parts in the event any product manufactured by
Company, including products sold under the brand name Daikin and used in the United States or Canada, proves defective in material
or workmanship within twelve (12) months from initial startup or eighteen (18) months from the date shipped by Company, whichever
occurs first. Authorized replaced parts are warranted for the duration of the original warranty. All shipments of such parts will be
made FOB factory, freight prepaid and allowed. Company reserves the right to select carrier and method of shipment.
In addition, labor to repair or replace warranty parts is provided during Company normal working hours on products with rotary
screw compressors and centrifugal compressors. Warranty labor is not provided for any other products.
Company’s liability to Owner under this warranty shall not exceed the lesser of the cost of correcting defects in the products sold or the
original purchase price of the products.
PRODUCT STARTUP ON CENTRIFUGAL AND SCREW COMPRESSOR PRODUCTS IS MANDATORY and must be
performed by a Daikin Applied or a Company authorized service representative.
It is Owner’s responsibility to complete and return the Registration and Startup Forms accompanying the product to Company within
ten (10) days of original startup. If this is not done, the ship date and the startup date will be deemed the same for warranty period
determination, and this warranty shall expire twelve (12) months from that date.
EXCEPTIONS
1. If free warranty labor is available as set forth above, such free labor does not include diagnostic visits, inspections, travel time and
related expenses, or unusual access time or costs required by product location.
2. Refrigerants, fluids, oils and expendable items such as filters are not covered by this warranty.
3. This warranty shall not apply to products or parts which (a) have been opened, disassembled, repaired, or altered by anyone other
than Company or its authorized service representative; or (b) have been subjected to misuse, negligence, accidents, damage, or
abnormal use or service; or (c) have been operated, installed, or startup has been provided in a manner contrary to Company’s
printed instructions, or (d) were manufactured or furnished by others and which are not an integral part of a product manufactured
by Company; (e) have been exposed to contaminates, or corrosive agents, chemicals, or minerals, from the water supply source, or
(f) have not been fully paid for by Owner.
ASSISTANCE
To obtain assistance or information regarding this warranty, please contact your local sales representative or a Daikin Applied office.
SOLE REMEDY
THIS WARRANTY CONSTITUTES THE OWNER’S SOLE REMEDY. IT IS GIVEN IN LIEU OF ALL OTHER
WARRANTIES. THERE IS NO IMPLIED WARRANTY OF MERCHANTABILITY OR FITNESS FOR A PARTICULAR
PURPOSE. IN NO EVENT AND UNDER NO CIRCUMSTANCE SHALL COMPANY BE LIABLE FOR INCIDENTAL,
INDIRECT, SPECIAL, CONTINGENT OR CONSEQUENTIAL DAMAGES, WHETHER THE THEORY BE BREACH OF
THIS OR ANY OTHER WARRANTY, NEGLIGENCE OR STRICT LIABILITY IN TORT.
No person (including any agent, sales representative, dealer or distributor) has the authority to expand the Company’s obligation
beyond the terms of this express warranty or to state that the performance of the product is other than that published by Company.
For additional consideration, Company will provide an extended warranty(ies) on certain products or components thereof. The terms
of the extended warranty(ies) are shown on a separate extended warranty statement.
Warranty
All Daikin Applied equipment is sold pursuant to its standard terms and conditions of sale, including
Limited Product Warranty. Consult your local Daikin Applied representative for warranty details. To find
your local Daikin Applied representative, go to www.DaikinApplied.com.
Aftermarket Services
To find your local parts office, visit www.DaikinApplied.com or call 800-37PARTS (800-377-2787).
To find your local service office, visit www.DaikinApplied.com or call 800-432-1342.
This document contains the most current product information as of this printing. For the most up-to-date
product information, please go to www.DaikinApplied.com.