Eaton Fire Addressable Control Panel Fx6100 Fx61002 Manual 25 16329 en
Eaton Fire Addressable Control Panel Fx6100 Fx61002 Manual 25 16329 en
Power Power
ON Fault
FIRE
System
Fault
General
Fault
TEST
General
Sounder
Disable
Disable
Fault
16
VdS
0786
G211013 DoP0228
EN54-2:1997 + A1:2006
EN54-4:1997 + A1:2002 + A2:2006
Contents
Contents
SECTION 1: SYSTEM INSTALLATION AND DESIGN. . . . . . . . . . . . . . . . . . 8
Introduction. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
Project planning . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
System design guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
Compatible equipment:. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .10
Equipment compatibility. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
System overview . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Technical specification. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .15
Optional functions as per EN54 P2&4 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19
External connections. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .21
Networking. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 22
Input/outputs. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 23
Maintainance. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
SECTION 2: COMMISSIONING. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Commissioning mode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Configuration. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26
Panel fault finding. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28
PC comissioning software . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Device input programming. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
Device outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
Panel outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
Change passcode. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 77
Add zone. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 78
Delete zone. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
Add device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 80
Delete device . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 81
Configure heat detectors . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
Network filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 83
Network filter . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 84
Language . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
Day/night. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Password protection. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
SECTION 4: APPENDIX. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
System wiring. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Detector base wiring (CAB300) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 89
Call point wiring (CBG370S/CBG370WP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Base sounder wiring (CAS380, CASBB384). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 90
Loop powered beacon wiring (CAB382). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
Wall sounder wiring (CAS381, CASB383). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 91
IP66 wall sounder wiring (CAS381WP, CASB383-WP). . . . . . . . . . . . . . . . . . . . . . 92
Base Sounder VAD (CASBB394). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 93
Wall Sounder VAD (CASB393) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 94
IP66 Wall Sounder VAD (CASB393WP). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 95
3 way input output unit (CIO351, CIO351S, CIO351SST) . . . . . . . . . . . . . . . . . . . 96
1 Channel mains rated I/O unit wiring (CMIO353). . . . . . . . . . . . . . . . . . . . . . . . . 97
Zone monitor unit wiring (CZMU352). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 98
Intrinsically safe zone monitor unit wiring (CZMU352-IS). . . . . . . . . . . . . . . . . . . . 99
Shop monitor unit wiring (MSU840). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 100
Spur isolator wiring (CSI350) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 101
4 Way sounder controller wiring (CSC354CPR) . . . . . . . . . . . . . . . . . . . . . . . . . . 102
4-20mA interface wiring (CGI420, CIT420, CGI420R, CIT420R). . . . . . . . . . . . . . 103
Micro zone monitor module wiring (MIU872). . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
Micro input module wiring (MCIM) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 105
Micro output module wiring
(MCOM, MCOM-R, MCOM-S). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 106
Technical I/O Unit Wiring (CFC301). . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 107
PROPRIETARY NOTICE
All data and information contained within this manual is of a proprietary nature. Do
not reproduce, transcribe, store in a retrieval system or translate into any language,
any part of this manual without the prior permission of ‘EATON‘. EATON reserves the
right to make changes to product specification without notice or liability. Every care
has been taken to ensure the accuracy of the information contained in this manual,
but no liability can be accepted for any errors or omission.
SUPPORT SERVICES
The goal of Eaton is to ensure your greatest possible satisfaction with the operation
of our products. We are dedicated to providing fast, friendly, and accurate assistance.
That is why we offer you so many ways to get the support you need. Whether it is
by phone, fax, or email, you can access Eaton’s support information 24 hours a day,
seven days a week. Our wide range of services is listed below. You should contact
your local distributor for product pricing, availability, ordering, expediting and repairs.
Website
Use the Eaton website to find product information. You can also find information on
local distributors or Eaton’s sales offices.
www.eaton.com
WARNING
Indicates a potentially hazardous situation which, if
not avoided, can result in serious injury or death.
CAUTION
Indicates a potentially hazardous situation which, if
not avoided, can result in minor to moderate injury, or
serious damage to the product.
NOTICE
The operating system of the control panel may be
revised as a result of enhancements to the system
software or hardware. Revisions to this manual will be
issued and supplied on request and should be logged
in the table supplied on the contents page.
CAUTION
RISK OF EXPLOSION IF BATTERY IS REPLACED BY
AN INCORRECT TYPE. DISPOSE OF THE USED
BATTERIES ACCORDING TO THE INSTRUCTIONS.
Project planning
The following is a typical program and timetable for a Panel installation project, once
the initial order has been received:
1. Project meeting
Installer and user to be present; system specifications, schematic diagram and
proposed circuit drawing to be available. Panel Installation & Commissioning Guide to
be provided.
2. Equipment fix
Typically 2 week’s notice is required for equipment to be delivered. Cable to be
installed and bases/back boxes to be fitted. Then fire detectors, call points, alarm
sounders, isolator units and interface units to be installed.
3. Address schedule
Schedule of sensor locations to be completed by installer and returned to enable
System programming.
4. Auto learn
Fire panel/repeater panels to be installed and terminated. System to be powered up
by installer and auto learn mode activated (see Auto Learn section). System to be
tested and verified by installer, prior to final commissioning.
5. Final commissioning
Minimum 2 weeks notice is required from receipt of Address Schedule and
Commission request form. Eaton Lighting Service Engineer to attend site implement/
oversee the final commissioning procedures (see Commissioning section), in
conjunction with the installer.
Loop lengths
The maximum permitted loop length is 2 km measured from the near to the far
terminals on Panel Motherboard PCB. There is no minimum limit to loop length. Any
wiring spurs off the loop must be included within the 2 km limit. On long loop runs,
the lengths of wiring rises and falls (between floors, down to manual call points)
must be included. Remember to include these especially when taking loop lengths
from plan drawings.
Loop loading - total number of addresses
The total number of addresses per loop is 200. This includes sensors, call points
and all other addressable items (e.g. interfaces, loop repeaters etc.) When designing
systems its recommended that allowances are made for future expansion, Short
circuit isolators are incorporated into every loop device, including Smoke sensors,
heat sensors, sounders, callpoints and interfaces. Therefore, no further fault
protection is required , in the event of a single fault, none of the devices connected
to the loop will fail to operate as the fault will be isolated by the
two adjacent devices.
Spur connected devices downstream of a cable fault will cease to function.
Compatible equipment:
Order code Description Dimensions (mm)
CIOP4 Addressable 4 Way Mimic Relay Board (4 In, 4 Out) 180H x 254W x 90D
CIOP8 Addressable 8 Way Mimic Relay Board (4 In, 8 Out) 180H x 254W x 90D
CIOP-7273 Addressable Door Release Module 130H x 180W x 60D
CIO351 Addressable 3 Channel I/O Unit (Reset on Reset) 130H x 180W x 60D
CIO351S Addressable 3 Channel I/O Unit (Reset on Silence) 130H x 180W x 60D
CIO351SST Addressable 3 Channel I/O Unit (Triple Address) 130H x 180W x 60D
400008FIRE-0022X Addressable Micro Input Module (MCIM) 65H x 35W x 18.5D
Equipment compatibility
Sensors
Loop wired sensors must be of the Eaton soft addressed analogue type. Eaton
conventional detectors can be connected via a Zone Monitor Unit or Shop Unit
interface. The connection of other detector types via a Zone Monitor Unit or Shop
Unit interface is not recommended,
Call points
Loop wired call points must be the Eaton series soft addressed analogue type,
Eaton series conventional callpoints can be connected via a Zone Monitor Unit or
Shop Unit interface.
The connection of other callpoint types via a Zone Monitor Unit or Shop Unit
interface is not recommended,
Sounders
Loop powered addressable sounders must be of the Eaton series soft addressed
analogue type.
Conventional sounders can also be connected either to the conventional sounder
circuits at the panel or to the loop via an addressable sounder controller interface
providing they meet the following:
Note: It is possible to use devices outside these requirements if they are supplied
with power from a separate source and switched via a suitable relay.
Relay circuits
There are Relay circuits built-in the standard Panel. Additional relays can be added
to the system by using Eaton soft addressing, Single Channel or 3 Channel Input/
Output Units.
1. The Panel provides monitored outputs to drive fire and fault relays mounted in
external equipment. External relays should be suppressed. If a non-suppressed
relay is used then a diode can be connected as shown in the wiring diagram in
the appendix, to suppress any reverse EMF on the release of the relay which
might cause the panel to malfunction.
2. A 24V DC output is provided at the panel to make it easy to connect ancillary
equipment. Although the panel can supply a continuous quiescent load of up to
30mA, BS5839 precludes this practice and any ancillary equipment you connect
should only consume power in the alarm or fault mode to meet the requirements
of BS5839.
1. External cables must be connected using the cable entries or knockouts provided.
2. When routing external cables inside the product they must be
a. Kept as short as possible
b. Routed close to the housing
c. Kept as far as possible from the electronics
Any modifications other than those stated in this manual, or any other use of this
product may cause interference and it is the responsibility of the user to comply with
the EMC and Low Voltage Directives.
System overview
Simple user interface
The main element of the user interface with is a large (120mm x 90mm visible area)
touch screen display, which provides comprehensive user information and also acts
as a multifunctional keypad.
Comprehensive context sensitive help information is provided throughout the menus
to assist unfamiliar users with system operation.
The Panel touch screen display automatically reconfigures to suit the selected
function, for example, if the change device text menu option is selected, the touch
screen is automatically formatted as a full QWERTY keyboard to enable fast and
simple text entry.
The use of the touch screen display enables a wide range of user and engineering
facilities to be incorporated into the panel whilst still offering simple operation.
control panel will automatically scan the detection loop and allocate each device
with an address number corresponding with its position on the loop, this avoids
the traditional need for manual addressing of the system devices which is time
consuming and provides a potential for error.
A major innovation with the Panel is the ability to incorporate spurs of analogue
devices which are fed from the loop by utilising a spur isolator.
Whenever the panel detects a spur, it breaks from allocating address numbers to the
loop wired devices, allocates address numbers to each of the devices on the spur in
sequence and then continues to address the devices on the main loop.
Every analogue device incorporates an integral short circuit isolator ensuring
maximum system integrity. A single short circuit will not disable any loop-mounted
devices, the isolators in the devices each side of the short circuit will operate and the
control panel will drive communication from both ends of the loop.
The spur isolator also incorporates a short circuit isolator such that in the event of
a short circuit on the spur, the integrity of the main loop will not be compromised.
Please refer to local standards e.g. BS5839 Pt1:2002 for details of the maximum
allowable are to be covered by a single spur.
Multiple languages
The Panel supports a large number of languages as standard.
Technical specification
Power specification
Mains Fuse : 1.6A Slow Blow
Nominal Voltage : 230 Vac + 10%, -15%
Nominal Current : 75mA
The Panel is protected by an internal thermal device, this requires no maintenance.
Batteries
Number of Batteries :2
Manufacturer: : YSP12-7
Capacity : 7 Ah
Battery Fuse : 4A Quick Blow (F4)
Maximum battery current; : 3.5 Amps
Inputs
Addressable Loops
Max Number : 1 or 2 (Panel depending)
Max Loop Load per loop : 350 mA
Max Number of Addressable : 200
Devices per loop
Class Change : Operated by external volt free contact
Outputs
Conventional sounder circuits
Number of sounder circuits :2
Total sounder Load : 1.5 A
Sounder Circuit Fuses (F1/2) : 1.6 Amp (Quick Blow)
End of line device : 210Ω + Diode
AUX 1
Max Load : 1 Amp
Fused (PTC2) : 1.1A polyswitch
AUX 2
Max Load : 60 mA
Fused (PTC3) : 1.1A polyswitch
This output is not to be used for Fire protecting equipment or Fire alarm routing
Equipment.
Any power taken from the alarm system will effect the standby duration.
Mechanical specification
Weight including batteries : 9 Kg
Weight excluding batteries : 4 Kg
Dimensions (Standard batteries) : 395mm(L) x 270mm(H) x 115mm(D)
Type of Material (backbox) : Mild Steel (Power Coated)
Type of Material (Facia) : PC/ABS
Flammability Rating : UL 94 V0
Total Number of knockouts : 11
Diameter of Knock out : 20mm
Panel outputs
Panel Sounders: (OPTION 7.8 EN54 PT 2).
Two Sounder outputs are provided. ONLY polarised equipment should be used.
Ensure the polarity of the connections are observed at all times and end of line
device are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5 Amp.
All outputs are fused with 1.6 Amp Glass fuse Alarm devices should be spread
equally across the 2 sounder circuits.
WARNING
Do not exceed the rated output current.
Output to fault warning routing equipment (Option 9.4.1C EN54 pt 2)
This output, which is fused and monitored using 2k0 end of line resistor, is used
for the transmission of fault signals to fault warning routing equipment This output
is monitored using 2k0 end of line resistor and it current limited to 30 mA. Under
normal condition it operates by providing 12vdc which can be connected directly to a
12v auxiliary device( relay).It is current limited to 30 mA.
Under fault conditions or even if the Panel is powered down, this output will be
switch to O volts. Ensure the polarity of the connections is observed at all times and
end of line resistors ( 2K0 5% ) are fitted for correct operation.
Alarm verification
The Panel has the facility for global alarm verification where the detector alarm
decision is integrated over 30 seconds.
When choosing your preferred cable type, you must take note of the following cable
and wiring requirements.
Cable resistance
Installation
The panel should be installed in a clean, dry, reasonably well ventilated place, and
not in direct sunlight. Temperatures in excess of +45°C and below -10°C may cause
problems, if in doubt consult Technical Support. The panel should be located away
from any potential hazard, in a position where it is readily accessible to authorised
staff, and the fire services, ideally on the perimeter of a building near a permanent
entrance. Mount the panel to the wall using the drill template provided. Do not drill
through the panel to the wall as dust will contaminate the circuitry.
Installation guide
Care must be taken to avoid connecting the screen to the earthed body of any metal
devices, enclosures or cable containment. The screen or drain wire of the loop cables
should not be considered as safety earth and therefore should not be connected
to terminals marked with the earth symbol, except at the panel, and should not be
insulated with green and yellow sleeving.
Fixing details
Read all the installation instructions before commencing with the installation.
The installation of this panel must be carried out by a suitably qualified/trained
person. The installation must comply with IEE wiring regulations and with BS5839
part 1 2002.
The electronic components within the fire panel are Static Sensitive.
L N E
- + - + NO C NC NO C NC - + A B X Y E A B X Y E - + E S+ S- E S+ S-
SOUNDER SOUNDER FAULT LOOP 1 LOOP 2
MAINS AUX RELAY 1 AUX RELAY 2 NETWORK NETWORK +24V OUT
CIRCUIT 1 CIRCUIT 2 RELAY E F+ F- E F+ F-
Installing cabling
Once the backbox is mounted the next stage is to install the power and loop cables
and fit the glands.
270.00
All Dimensions in MM
141.80 128.20
229.80
345.00
50.00
325.00
External connections
Mains supply
The mains supply should be installed in accordance with the current edition of the
IEE wiring regulations. Connection to the mains supply must be via an isolating
device (e.g. an isolating fuse) reserved solely for the fire alarm system. The cover
should be coloured red and labelled “FIRE ALARM - DO NOT SWITCH OFF”. The
isolating protective device should be secure from unauthorised operation and ideally
installed in a securely closed box with a breakable cover.
An additional warning label should be provided, depending on whether:-
a. The isolating protective device is fed from the live side of the main isolating
device in which case the label on the isolating protective device, should read
in addition
WARNING
“This supply remains alive when the main switch is turned off”.
A further label should be placed on the main isolating device reading
WARNING
“The fire alarm supply remains live when this switch is turned off”.
Or
b. If the isolating protective device is fed from the dead side of the main
isolating device, a label should be fixed to the main isolating device reading.
WARNING
“This switch also controls the supply to the fire alarm system”.
Distributed power supplies
The above also applies to any distributed power supply (i.e. mains connections for
Repeater Panels, Sounders Controller Units, etc.).
Cable segregation
All cables for the fire alarm system should be segregated from any other cables/
wiring/services.
Wiring configurations
Spurs can be taken off the loop in the following ways:
Networking
Up to One Hundred & Twenty Six Panels or repeaters can be networked together to
operate as a single networked system. To achieve this each panel must be fitted with
a network card (Optional Extra).
When operating as a networked system all fire and fault event information is
displayed at every panel, silencing and resetting of alarms can also be carried out
from any panel on a networked system if panels are suitably configured.
Networked Can be connected as loops or radial.
Networked panels can be used as active repeaters, alternatively a low cost passive
repeater is available.
This can either be connected a loop of an individual panel or it can be connected to
the network.
The recommended network cable for the network connection between panels is
an enhanced Firetuf cable Manufactured by Draka cables (part number 910234.)
Screen continuity must be maintained throughout the entire network circuit including
at each junction point. The screen should only be earthed at the connection point
provided at the first panel and not at any other point. The screen or drain wire of the
network cable should not be considered as a safety earth and therefore should not
be connected to terminals marked with the earth symbol, except at the panel, and
should not be insulated with green and yellow sleeving.
Where the network cable passes between buildings, screen continuity should
not be maintained from building to building. A booster device must however be
used irrespective of cable length and should be fitted at a suitable point in the link
between buildings. The cable screen should be connected to the earth of one panel
in each building. 102 S terminator should be fitted at the beginning and the end of
the network. If the distance in the network exceeds 1KM the booster should be
used. The booster requires 24V local supply, which can be connected to nearest
Addressable Panel.
Input/outputs
Panel outputs
Panel Sounders: (OPTION 7.8 EN54 PT 2)
Two pairs of outputs are provided. ONLY polarised equipment should be used.
Ensure the polarity of the connections are observed at all times and end of line
resistors & Diodes) are fitted for correct operation.
The total alarm load across all sounder outputs = 1.5A
All outputs are fused with 1.6 Amp Glass fuse Alarm devices should be spread
equally across the 2 sounder circuits.
WARNING
End of line device.
Do not exceed the rated output current.
All sounders must be polarised
OUTPUT TO FAULT WARNING ROUTING Both sounder circuits must
EQUIPMENT (OPTION 9.4.1C EN54 PT 2) be terminated with an end
of line device.
WARNING
Do not exceed the rated output current.
24 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com
Section 1: System installation and design
Maintainance
Functions: See User Manual for full details.
Daily inspection
Check that only the green “POWER ON” indicator shows. Inspect for any fault
indication. Notify any faults to a system supervisior.
Weekly test
Check indicators.
Press Supervisor mode on the top left of the touch screen. Enter passcode. Select
“others” tab. Press the button labeled weekly test, confirm you wish to perform the
test and the amber “System Test” LED will light. The panel will stay in the weekly
test mode for 5mins before resetting. During the weekly test, trigger a smoke
detector or call point and check the fire panel registers the device and illuminates
the correct zonal indicator. Trigger a different device every time a weekly test is
performed ensuring devices are tested in rotation until all have been checked. It is
advisable to develop a detailed a building plan highlighting devices and locations to
aid testing. The panel will reset automatically once the 5mins have elapsed. If no
devices are triggered during the weekly test the panel will abort the test and reset
after 5mins. Record weekly test in the table provided in this log book.
Quarterly
Check all previous log book entries and verify that remedial action has been taken.
Carry out the weekly test. Visually examine the batteries and their connections, by
loosening the screws behind printer door and opening the hinged front from the right
hand side.
Disconnect the mains supply and check that the battery is capable of supplying the
alarm sounders, by operating a call point.
Annual test
As Weekly Test and Quarterly Test above. Additionally test all sensors and call points
and check operation.
Every 5 years
Replace sealed lead acid battery.
Cleaning: When cleaning the panel, use a moist cloth. Do not use solvents or
harsh abrasives.
Section 2: Commissioning
Commissioning mode
Walk test mode allows a single engineer to test the various detectors and call points
on a system without always having to return to the panel either to reset the system
or silence the alarms. When in COMMISSIONING MODE, the system operates as
normal except that when a detector or call point goes into alarm, the alarms only
operate for a few seconds and then will silence. The panel then tries to reset the
device automatically and, if successful, the alarms are operated again for a few
seconds and the installation engineer can move on to the next detector. After a full
test has been carried out the engineer can check the order in which the detectors/
call points were operated using the DISPLAY LOG mode. This information can also
be printed on the optional printer.
a. When in the LOG mode, “One man walk test” will appear on the display
followed by the address text and device type.
b. On the printout a “One man walk test” message will appear will appear
followed by the address text and device type.
c. During a real fire “FIRE !” Will appear on the display followed by the address
text and device type.
Configuration
Db level check
Panel includes the facility to test and set the system sounders with the minimum
amount of disturbance. In sounder test mode, the sounders will sound for
30 seconds on then 30 seconds off. This facility can be accessed via the
engineering menu.
Detector LED flashing
The Panel Sensor flashing function is used to allow a visual inspection and
confirmation that the fire panel is in communication with the installed system
devices. This facility can be accessed via the engineering menu and can be switched
on or off at any time as required.
Power Power
ON Fault
System
Null Modem Cable
FIRE
Fault A.serial Output
General TEST
Fault
Sounder
General Disable
Disable
Fault
B. USB Output
Via
USB Convertor
L
MAINS
N
E
SOUNDER SOUNDER
CIRCUIT 1 CIRCUIT 2
for
Monitoring
-
NO
E
LOOP 1
S+ S-
F+ F-
E
LOOP 2
PC comissioning software
Isolate zone/address
User can define between zones or addresses to be isolated on activation of the
device. The isolate list button enables the user to enter upto 8 unique zones or
addresses. If non-latching has been enabled, Isolated devices can be un-isolated
as the triggered device returns to normal operation. (a call point keyswitch is an
example for this application).
Device outputs
Delay configuration
The output of a device when triggered can be delayed - based on a user defined
value in minutes.
This programming option is enabled when a value other than zero is entered inside
the ‘Delay’ window.
D Override
This option is a manual intervention override, when enabled (check in box) the delay
can be overridden from any call point on the loop when triggered.
Daynight
See coincidence detection below.
Panel outputs
Coincidence detection
Each panel output can be assigned a unique list of zones derived from the zones
available on the loop, to activate this output, two unique zones from this list have
to be be in fire or alternatively any zone outside this list will trigger the output also.
When the ‘coincidence’ box is checked - the ‘Allocate device’ button allows the user
to populate this list.
Power Power
ON Fault
FIRE
System
Fault
General
Fault
TEST
General
Sounder
Disable
Disable
Fault
1 5
2 6
Power Power
ON Fault
3 7
System
FIRE
Fault
4 8
General
TEST
Fault
Sounder
General
Disable
Disable
Fault
1. System LED’s
2. Touch Screen Display
Pre Alarm
0
Disabled
/Test
Panel operation
The Panel is operated via a backlit touch screen. The default fire screen is shown
below. From this screen all the panels functions can be operated. The first time you
touch the screen the backlight will illuminate the panel.
Pressing a field will highlight it and forward to the next screen as shown below.
Supervisor
FRE Off 11:01:35 Fires
0
Pre Alarm
0
Disabled
/Test
Supervisor Fires Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE Off 1 Alarms 0 0 / Test FRE Off 1 Alarms 0 0 / Test
System Healthy
10 Zones Active Total Fires= 1 Print All Help
Tuesday
dd-mm-yyyy
Tuesday
16:25.25 Dd-mmm-yyy
BST On 16:25.25
BST On
Service Mute
Exit Reset
FRE off Buzzer
Commission
Configure
Test
Service Mute
Exit Reset Select “Auto Run” from
FRE Off Buzzer
the configure menu
screen.
Load CDR from Laptop Analogue Level
Commission devices to
Load logo from PC
hybrids (26V mode)
Service IMPORTANT:
Exit Auto Learn Activating autolearn will
FRE Off
erase all existing
programming, text and
Do you want to continue?
configuration data.
Service Mute
Exit Reset
Buzzer
Commission
Configure
Test
Commission devices to
Load logo from PC
hybrids (26V mode)
IMPORTANT:
Load CDR from Laptop
Do not click commission before
pressing “Yes” on the
This will erase the current CDR
“Load CDR” screen.
Do you want to continue?
Yes No
Service Mute
Exit Reset
Buzzer
Commission
Configure
Test
Service Mute
Exit Reset Select “Download
FRE Off Buzzer CDR to Laptop”
from the
Load CDR from Laptop Analogue Level commission
menu screen.
Download CDR to Laptop Printer Settings
Commission devices to
Load logo from PC
hybrids (26V mode)
Start PC program
OK Cancel
System Healthy
10 Zones Active
Tuesday
dd-mm-yyyy
16:25.25
BST On
Supervisor Fires Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE off 1 Alarms 0 0 / Test FRE off 0 Alarms 6 0 / Test
Supervisor Fires Pre Faults Disabled Supervisor Fires Pre Faults Disabled
FRE off 0 Alarms 6 0 / Test FRE off 0 Alarms 6 5 / Test
View Others
View Faults
Disabled
View Fires View Pre
AC = 0 Alarms
Yes No
Silence alarms
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and
enter the passcode.
Enter the Supervisor Mode Passcode and select “Silence Alarms” button as the top
of the screen.
Supervisor Silence Mute
Evacuate Reset
FRE off Alarms Buzzer
View Others
View Fires
AC = 0 View Pre Faults
Alarms View
Disabled
I/O Zone: 0
Addresses: 0
Touch button to
View list
Supervisor
FRE off
Yes No
Mute buzzer
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and
enter the passcode.
Enter the Supervisor Mode and Select “Mute Buzzer” from the Top Menu.
View Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Reset
Enter the Supervisor Mode and Select “Reset” from the top Menu. Select “Yes” to
reset the panel.
001 14:22:49
Mains Failure
Yes No
Pre-Alarms
Enter the Supervisor Mode and Select “Pre-Alarms” tab.
Supervisor Silence Mute
Evacuate Reset
FRE Off Alarms Buzzer
Others
View
View Faults
Disabled
View Fires View Pre
AC = 0 Alarms
Disabled devices
Enter the Supervisor mode and Select the “Disabled” tab.
View Others
View Fires
AC = 0 View Pre Faults
Alarms View
Disabled
I/O Zone: 0
Addresses: 0
Touch button to
View list
The individual buttons show which devices and the number of devices which
have been disabled. Press one of the buttons to display detailed information for a
particular category.
Faults
Enter Supervisor Mode Passcode and select “Faults” tab.
Fires Others
AC = 0 Pre
Alarms Disabled
Faults
View Fires
AC=100 View Pre
Alarms View
Disabled View
Faults Others
Enable/disable
Enable/Disable Address
Enable/Disable Zone
Enable/Disable I/O
Enable All
Exit
Yes No
Zone 003 Zone 3 Disabled
View Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Check
Lamp test
Auto Config.
Select the Information You wish to Print from the Buttons Listed.
Lamp test
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and
enter the passcode.
Supervisor Silence Mute
Evacuate Reset
FRE off Alarms Buzzer
View Fires
AC = 19 View Pre
Alarms View
Disabled View
Faults Others
Enter the Supervisor Mode and Select the “Others” Tab. Press “Lamp Test”.
Supervisor
FRE off
Lamp Test
Ok Cancel
Weekly test
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
passcode. Select the others tab as shown below. Press Weekly test.
View Fires
AC = 19 Pre
Alarms Disabled
Faults
Others
Supervisor
FRE off
Weekly test
Do you want to continue? Will reset after 4 minutes
Yes No Cancel
The panel will automatically return to the system healthy screen once the weekly
test has been completed.
Viewing events
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and
enter the passcode.
Enter the Supervisor Mode Passcode. Select the “Others” tab and press View Log.
View Fires
Pre
AC = 19
Alarms Disabled
Faults
Others
Use the scroll bar to view the list of upto 1000 events.
The Panel event log stores up to 1000 events including, fires, faults, resets and
address changes. Once the maximum 1000 events has been reached Panel will
automatically overwrite the oldest event every time a new event is stored.
The event log can only be reset by an approved service engineer.
Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others
Supervisor
FRE Off
Replace Device
Exit
Check
Auto Config
Yes No
Replace device
Replace device enables an existing device to be replaced with a new device without
losing the existing text and sounder programming.
Replace a single device then use the replace device menu to allocate an existing
address to the new device.
Fires
AC = 0 View Pre
Alarms View
Disabled View
Faults Others
Check
Change Device
Auto Config.
Supervisor
FRE Off
Replace Device
Exit
Supervisor Supervisor
FRE Off FRE Off
Enter Loop 1 Address
Select a Loop
Loop 1 0 1 2 3
Loop 2
Del 4 5 6
Exit Ok 7 8 9
Exit
Commission
Configure
Test
Enable/Disable Address
Service Mute
Exit Reset Select the “Test device”
FRE Off Buzzer
button.
Test Device
Test Zone
Test zone
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode, Select “Test” and on the Screen Shown Below
Press “Test Zone”
Service Mute
Exit Reset
FRE Off Buzzer
Test Device
Test Zone
Service Reset
Exit
FRE Off
Test Device
Commission
Test Zone
Configure
Sound Level Test Mode
Test
One Man Walk Test
Yes No
Stop
Configure
Test
Test Device
Test Zone
Flashing Off
Service Mute
Exit Buzzer
FRE Off
Commission
Configure
Test
Test Zone
Stop
Yes No
Erase log
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission.
Service Mute
FRE off Exit Reset
Buzzer
Commission
Configure
Test
Number of Panels
Erase Log
in Network
Commission devices to
Load logo from PC
hybrids (26V mode)
Yes No
System details
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission, then Press “System Details”.
Number of Panels
Erase Log
in Network
Test
System Details Screen Cover
Commission devices to
Load logo from PC
hybrids (26V mode)
Service Service
FRE off Print Exit Reset
FRE off
Print Exit Reset
Service
FRE off
Print Exit Reset
SCU 0 0 0 0
Voice Annunciator 13 14 0 0
Repeater 0 0 0 0
ZMU/{SUM 0 0 0 0
Beam Detector 0 0 0 0
Technical Timer 2 1 0 0
Access Control 0 0 0 0
Emerg.Light.Module 0 0 0 0
Carbon Monoxide 0 0 0 0
Commission
Configure
Test
Service Mute
Exit Reset
FRE Off Buzzer
Download CDR to Laptop Printer Settings Select “Load logo from PC” from
the Configure Menu Screen.
Auto Learn Change Panel Number
Exit
Analogue level
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission then press “Analogue Levels”.
Number of Panels
Erase Log
in Network
Test
System Details Screen Cover
Commission devices to
Load logo from PC
hybrids (26V mode)
1 2 3
Service Reset
Exit Goto Enter Address
FRE off
..................
Show Show Show Show Show
4 5 6
All Detectors Optical Ionisation Thermal
Loop 1 0 - 13
001 Device 1, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
Loop 2 0-0
7 8 9
002 Device 2, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
Loop 3 0-0
003 Device 3, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
Loop 4 0-0
ok 0
004 Device 4, Zone 1
Loop: 1, Zone: 1, Type: Opto/thermal
Number of Panels
To activate the touch screen, touch the top left corner
Erase of
Log the screen until the screen
in Network
illuminates. To enter the
Test supervisor mode touch the supervisor button and enter the
System Details Screen Cover
service passcode.
Commission devices to
Load logo from PC
hybrids (26V mode)
Enter the Service Mode and Select Commission then press “Change Panel
Service Mute
Number”.
Exit Reset
FRE Off Buzzer
1 2 3
Service Mute
Exit Reset Change Panel Number
FRE Off Buzzer
Commission
Load CDR from Laptop Analogue Level 0
..............................
Auto Learn
Printer Settings
ok 0
System Details Screen Cover
1 2 3
FRE Off Buzzer Load CDR from Laptop Analogue Level
Change Panel Number
To activate the touch screen, touch the top left corner of the screen Number
Configure until the screen
of Panels
illuminates. To enter the supervisor mode touch theErase Log
supervisor button inand enter the
Network
service passcode.
7
Test
Enter the Service Mode and Select Commission then 8 9
System Details
press “Number
Screen Cover
of devices to
Commission
ok 0
Load logo from PC
hybrids (26V mode)
Panels in Network”.
Cancel
1 2 3
Service Mute
Exit Reset Number of Panels
FRE Off Buzzer
in Network
Load CDR from Laptop Analogue Level 1
..............................
Auto Learn
Printer Settings
1 2 3
Number of Panels
in Network
1
..............................
4 5 6
60 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com
Section 3: Panel controls & indicators
Screen cover
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Commission then press “Screen Cover”.
Commission
Configure
Test
Service Mute
Exit Reset
FRE Off Buzzer
Number of Panels
Erase Log
in Network
Commission devices to
Load logo from PC
hybrids (26V mode)
Service
FRE off Exit Reset
Installed
Not Required
Italian mode
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Configure then press “Italian Mode”.
Service Mute
FRE off Exit Reset
Buzzer
Commission
Configure
Test
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Service Mute
Exit Reset
FRE off Buzzer
Italian Mode
Enabled Disabled
Service Mute
FRE off Exit Reset
Buzzer
Commission
Configure
Test
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Service
Exit Reset
FRE off
Sounder tone
Service Mute
FRE off Exit Reset
Buzzer
Commission
Configure
Test
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Service
Exit Reset
FRE off
Sounder tone
Service Mute
FRE off Exit Reset
Buzzer
Commission
Configure
Programming I/O
Add/Delete
and Sounders
Service
Exit Reset
FRE off
Sounder tone
Service Mute
Exit Reset
FRE Off Buzzer
Commission
Configure
Select “Programming
Test
I/O and Sounders”
from the Configure
Menu Screen. Then
Enable/Disable Address press Alarm Verification
Programming I/O
Add/Delete
and Sounders
Panel Outputs T1/T2
Service
Exit Reset
FRE off
AVF Zones
Sound settings
Touch “Sound settings”.
Service
Exit Reset
FRE off
Sound Settings
Selections from the screens below will become the global settings for all loop
sounders.
Service Service
Exit Reset Exit Reset
FRE off FRE off
Volume
This will effect all sounders
Volume Low
Medium
Sound High
Service Service
Exit Reset Exit Reset
FRE off FRE off
Sound
This will effect all sounders
Volume Slow Woop
Two Tone
Sound Continuous
Change date/time
Enter the Service Mode and Select Configure. Select Change Date/Time.
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
BST On
+1 +1 +1
Current Date: Day Month Year
-1 -1 -1
Wednesday
Day Month Year
dd-mmm-yyyy
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Service Mute
Exit Reset
FRE Off Buzzer
Press
Change zone text “Change
Zone Text”
Change Panel Text
Select the zone you wish to Change and Edit Using the Keyboard.
Service
Reset
FRE Off Enter the name for Zone 2
Exit
Zone 2
.......................................................................................
Change text
Enter the Service Mode and Select Configure. Select “Change Text”.
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Service Mute
Exit Buzzer Reset
FRE Off
Select the Address you wish to change and edit using the keyboard.
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
DF6000
.......................................................................................
1 2 3 4 5 6 7 8 9 0
Q W E R T Y U I O P
A S D F G H J K L
CAPS Z X C V B N M , .
Configure zones
Enter the Service Mode and Select Configure. Select “Configure Zones”.
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Service Reset
Exit
FRE Off
Change passcode
Enter the Service Mode and Select Configure. Select “Change User Code”.
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
1 2 3
Service Mute
Exit Reset
FRE off Buzzer Please enter Passcode:
..............................
..............................
4 5 6
Change User code
Verify New Code:
..............................
7 8 9
Cancel
ok 0
Ok Ok Ok
Add zone
Enter the Service Mode and Select Configure. Select “Add Zone”.
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Service
Exit Reset
FRE Off
Add Zone
Delete Zone
Add Device
Delete Device
Add Zone ?
Yes No
Delete zone
Enter the Service Mode and Select Configure, select “Add/Delete”
then “Delete Zone”.
Service
Exit Reset
FRE Off
Add Zone
Delete Zone
Add Device
Delete Device
Service
Reset
FRE Off
Delete Zone 2?
Yes No
Add device
Enter the Service Mode and Select Configure, select “Add/Delete”
then “Add Device”.
Service
Exit Reset
FRE Off
Add Zone
Delete Zone
Add Device
Delete Device
Service
FRE Off Reset
Loop 1
Loop 2
Loop 3
Loop 4
Exit
Loop 2 Loop 2
Saving...
Scanning Loop Loop 1, Address 30, Type [device type]
Exit Exit
Delete device
Enter the Service Mode and Select Configure, select “Add/Delete”
then “Delete Device”
Service
Exit Reset
FRE Off
Add Zone
Delete Zone
Add Device
Delete Device
Delete Device 3?
Device 3
Loop 1, Address 3, Device Type Opto/thermal
Yes
No
Programming I/O
Add/Delete
and Sounders
Thermal A1R
Thermal BS
Thermal CS
Exit
Network filter
Enter the Service Mode and Select Configure. Select “Network”, This menu defines
whether messages are broadcast across the network or remain local.
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Service
Exit Receive message over network
FRE Off
Reset Network
Evacuate Network
Silence Network
Fire Network
Fault Network
Pre-Alarm Network
Language
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Configure.
Select “Programming I/O and Sounders” from the Configure Menu Screen.
Then press Language.
Service Mute
Exit Reset
FRE off Buzzer
Programming I/O
Add/Delete
and Sounders
Day/night
To activate the touch screen, touch the top left corner of the screen until the screen
illuminates. To enter the supervisor mode touch the supervisor button and enter the
service passcode.
Enter the Service Mode and Select Configure.
Service Mute
FRE off Exit Reset
Buzzer
Service Mute
FRE off Exit Commission Reset
Buzzer
Commission
Configure
Configure
Test
Test
Mute
Select “Day/Night” fromService
the
FRE off Configure Menu Screen.
Exit Buzzer
Reset
Programming I/O
Service Mute
Exit Add/Delete Reset
FRE offand Sounders Buzzer
Change Date/Time Configure Heat Detectors
Programming I/O
Add/Delete
and Sounders
Change Text Network
Change Date/Time Configure Heat Detectors
Configure Zones Language
Change Text Network
Change Passcode Day/Night
Configure Zones Language
Italian Mode Network Protocol
Change Passcode Day/Night
Delay (minutes)
Service
Exit Reset
FRE off
Off
Delay (minutes)
1 2 3 4 5
Off
6 7 8 9 10
1 2 3 4 5
Exit
6 7 8 9 10
Password protection
1 2 3
Service
FRE Off
4 5 6
7 8 9
Cancel
ok 0
The system has password protection which restricts access to the DISABLE Menu
and to TEST/COMMISSIONING MODE. The password is a four digit code and the
default number is 2214. The password entry screen is accessed via the supervisor
mode button. Press supervisor mode and the password entry screen will be
displayed, type in the passcode and press Ok. If the wrong password is entered
three times further access to the system is denied.
83
INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com
A n y 3 0 0 S e r ie s A n a lo g u e S e n s o r c a n b e C o n n e c te d to th e L o o p
Section 4: Appendix
NO C NC - + - + 0V - + 26V - + S+ S- F- F+ S+ S- F- F+ S+ S- F- F+ S+ S- F- F+ - + + 1 - + 2 - + 1 - + 2 - Tx Rx C TS RTS OV T x+ T x-
System wiring
AU X F AU LT + 24V F IR E R /E F IR E P /E LOOP 1 LOOP 2 LOOP 3 LOOP 4 S O U ND E R S O U ND E R MO D E M/P C MIMIC
R E L AY R E L AY O /P C L AS S C IR C U IT 1 C IR C U IT 2 R s232 R E P E AT E R
C H A NG E
L O O P C IR C U IT S
Section 4: Appendix
Wiring hints
• Each terminal is suitable for clamping up to 2 wires
• Clamping of 2 wires of very different diameters under one screw
is not recommended
• Suitable for mounting to mounting boxes with 50-80mm fixing centres
General
If difficulty is experienced when mounting the sensor, this may be due
to the following:
• Wiring causing an obstruction - move or shorten wires
• Although the base is tolerant to uneven mounting surfaces, a very uneven surface
may cause the base to deform when the mounting screws are tightened down -
loosen screws to reduce this or slide base to a flat position
WARNING
DO NOT USE HIGH VOLTAGE TESTERS WHEN
SENSORS OR CONTROL PANEL ARE CONNECTED TO
THE SYSTEM.
+ R emote
Indicator
LE D
+ V IN ( optional)
L oop Start
S+
A n a lo g u e A d d re s s a b le
_
S
F ire A la rm P a n e l
_
_
_
Compatible
_
L oop F inish
F
F+
_
_
_
_
- V E C O M IN - VE C O M O UT
E a r th s c r e e n o f c a b le to b e c o n tin u o u s b e twe e n s e n s o r s
IN O UT
E - + E - +
L O O P IN LO O P O UT
A n a lo g u e A d d r e s s a b le L o o p
- +- + - +- +
Loop Finish Loop Start
S+
Analogue Addressable
_
S
F ire Alarm P anel
_
_
Compatible
_
_
_
F
F+
_
_
_
_
Due to restricted
access space, do
not use excessive
cable in this area.
WARNING
Do NOT use high voltage testers if any equipment is
connected to the system.
IN O UT
E - + E - +
L O O P IN LO O P O UT
A n a lo g u e A d d r e s s a b le L o o p
WARNING
Do NOT use high voltage testers if ANY equipment
is connected to the system. Earth screen must be
continuous along entire length of loop.
IN OUT
E - + E - +
Note: Care should be taken to ensure the cable does not put stress
on the circuit board
86 INSTALLATION AND OPERATION MANUAL 25-16329-B December 2019 www.eaton.com
Section 4: Appendix
WARNING
Do NOT use high voltage testers if ANY equipment
is connected to the system. Earth screen must be
continuous along entire length of loop.
IN O UT
E - + E - +
A n a lo g u e A d d r e s s a b le L o o p
System functionality
1. Volume and tone are set by control panel, no need to access
sounder to alter setting.
2. Soft addressed.
Standard connections
3 3
Intelligent Addressable
Loop start
- -
+ - + + - +
S+ 2 E 2
Control Panel
E
Compatible
S-
4 4
Loop finish
F-
LED 1 LED 1
F+
Note: Base terminal 1, 2, 3 and 4 not used. All wiring terminates as shown above.
WARNING
Do NOT use high voltage testers if ANY equipment
is connected to the system. Earth screen must be
continuous along entire length of loop.
System functionality
1. Volume and tone are set by control panel, no need to access sounder to
alter setting.
2. Soft addressed.
Standard connections
WARNING
Do NOT use high voltage testers if ANY equipment
is connected to the system. Earth screen must be
continuous along entire length of loop.
System functionality
1. Volume and tone are set by control panel, no need to access sounder to
alter setting.
2. Soft addressed.
Standard connections
WARNING
Do NOT use high voltage testers if ANY equipment
is connected to the system. Earth screen must be
continuous along entire length of loop.
Standard connections
Note: CIO351SST
has different
22k 22k 22k resistor values.
ANAL O G U E
AD D R E S S AB L E L O O P
O UTP UTS
E - + E - + - + - + - + N /O C N /C N /O C N /C N /O C N /C
IN O UT IN P U T S
LO O P
Standard connections
5k6
22k
A n a lo g u e A d d r e s s a b le L o o p
V o lt- F r e e O u tp u t
2 3 0 V R a te d
E - + E - + - + E C N /C N /O
IN O UT SP UR
IN P U T
Note:
1. Only connect cable screen to its adjacent earth terminal
2. The end of line resistor must always be fitted, even if the spur is unused
Standard Connections
EOLM-1
12K
- OUT +
- IN +
E - + E - + E - + E - +
O UT IN C AL L D E T E C T O R Z O NE
LOOP P O IN T
Z O NE
Note:
1. This unit can only be used with CDB300/I detector base and compatible detectors
2. Only connect cable screen to its adjacent earth terminal
3. The end of line resistor must always be fitted, even if the spur is unused
4. Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage
5. Maximum number of call points allowed is unlimited
6. Detector zone end of line device is EOLM-1 (supplied)
7. Callpoint zone has end of line resistor
Note:
1. This detection zone can only be used with intrinsically safe detectors SLR-E-IS
(optical) / DCD-1E-IS (Heat) with the non-diode base YBN-R/4IS
2. The call point zone can only be used with BG3 I/S call points
3. Only connect cable screen to its adjacent earth terminal
4. The end of line resistor must always be fitted, even if the spur is unused
5. Maximum spur length – See BS5839 Pt1:2001 for Zone Coverage
- O UT +
- IN + -
12K +
Analogue Addressable Loop
- O UT +
- IN +
E - + E - + E - + E - + N/O C N/C + - + - E - +
O UT IN C AL L DE TE C TO R ZO NE F IR E + - E + -
E XTE R NAL 24V
LOOP P O INT R E L AY E XTE R NAL
ZO NE 1 2 P SU
MO N ITO R P SU
SO UNDE R INP UT
Callpoints can be connected with detectors
on detector zone if preferred
Note:
1. This unit can only be used with CDB300/I detector base and compatible detectors
2. Only connect cable screen to its adjacent earth terminal
3. The end of line resistor must always be fitted, even if the spur is unused
4. Maximum spur length - See BS5839 Pt1:2002 for Zone Coverage
5. Maximum number of call points allowed is unlimited
6. Detector zone end of line device is EOLM-1
7. Callpoint zone has end of line resistor
OUT
-
+
ANALO G UE
ADDR E SSABLE N O E N D O F L IN E
R E S IS T O R R E Q U IR E D
E
LO O P
E
IN
-
SPUR
-
+
Note:
1. Only connect cable screen to its adjacent earth terminal
2. For maximum spur length / load see BS5839 Pt1:2002
3. This unit can only be used with Eaton CAB300 and CDB300/I Sensor bases and
compatible sensors
ANAL O G UE
ADDR E SSABL E
LOOP
230V AC MAINS
F IR E R E L AY
N/O C N/C
L N E E + - E + - E + - E + - E - + E - +
O UT IN
+
+
BAC K UP
BATT BATTE R Y
-
-
Note:
1. Only connect cable screen to its adjacent earth terminal
2. The end of line resistors must always be fitted, even if the sounder
circuits are unused
Addressable
loop
4-20mA
+
Gas detector
In
-
Loop comms
E
24V 24V
Input Output
+
Out
-
E
JP1
DIL
Switches 4-20mA PSU PSU
Input Input Output
- + 0V 24V 0V 24V
JP2
DIL
Switches
JP3
DIL
Switches
Note:
Recommended Loop Cable Type: FIRETUF, FP200, MICC No addressing of the
interface is required. See control panel operation for details. There are no serviceable
parts so no maintenance procedures apply
IN +
Earth
INPUT
IN - Loop In+
LOOP
Loop In-
EARTH Earth
Loop Out+
Loop Out-
JIU872
Standard connections
Note:
1. This unit can only be used with Eaton FXN520 detector base
and compatible detectors
2. Only connect cable screen to its adjacent earth terminal
3. The end of line resistor must always be fitted, even if the spur is unused
4. Maximum spur length – See BS5839 Pt1:2001 for Zone Coverage
5. Maximum number of call points allowed is unlimited
Detector zone end of line device is EOLM-1 (supplied)
IN +
Earth
INPUT
IN - Loop In+
LOOP
Loop In-
EARTH Earth
Loop Out+
Loop Out-
MJIM
Note:
1. Only connect cable screen to its adjacent earth terminal
2. The end of line resistor provided must always be fitted, even if the input is unused
3. Monitored inputs can detect open or short circuit faults
IN +
INPUT
IN - Loop In+
LOOP
Loop In-
EARTH Earth
Loop Out+
Loop Out-
MJOM Earth
Note:
1. Only connect cable screen to its adjacent earth terminal
2. Output relay are volt-free contacts and are not monitored
Eaton
EMEA Headquarters
Route de la Longeraie 7
1110 Morges, Switzerland
Eaton.eu