Product datasheet
Specifications
Circuit breaker, ComPacT
NS1250H, 70kA at 415VAC, 3P,
fixed, manually operated,
MicroLogic 2.0E control unit, 1250A
C125H32EFM
Main
Range ComPacT
product name ComPacT NS new generation
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Range of product ComPacT NS630b...1600 new generation
Product or component type Circuit breaker
Device application Distribution
Number of poles 3P
Protected poles description 3D
(In) rated current up to 65 °C 1250 A at 50 °C
[Ue] rated operational voltage 690 V AC 50/60 Hz
Network type AC
Network frequency 50/60 Hz
Suitability for isolation Yes conforming to EN/IEC 60947-2
Utilisation category Category B
[Icu] rated ultimate short-circuit 85 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 70 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
65 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
50 kA Icu at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
42 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Performance level H 70 kA 415 V AC
Trip unit name MicroLogic 2.0 E
Trip unit technology Electronic
Trip unit protection functions LI
Control type Manually operated
Mounting mode Fixed
Complementary
[Ui] rated insulation voltage 800 V AC 50/60 Hz conforming to IEC 60947-2
[Uimp] rated impulse withstand 8 kV conforming to IEC 60947-2
voltage
[Ics] rated service short-circuit 52 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
breaking capacity 52 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
48 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
37 kA at 500/525 V AC 50/60 Hz conforming to IEC 60947-2
31 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
[Icw] rated short-time withstand 19.2 kA 1 s conforming to IEC 60947-2
current
Mechanical durability 10000 cycles
14-Mar-2025 1
Electrical durability 2000 cycles at 690 V In
3000 cycles at 690 V In/2
4000 cycles at 440 V In
5000 cycles at 440 V In/2
Power losses 44 W
Mounting support Backplate
Upside connection Front
Downside connection Front
Connection pitch 70 mm
Protection type L : for overload protection (long time)
I : for instantaneous short-circuit protection
Trip unit rating 1250 A at 50 °C
Long-time pick-up adjustment Adjustable 9 settings
type Ir (thermal protection)
[Ir] long-time protection pick-up 0.4...1 x In
adjustment range
Long-time protection delay Adjustable 9 settings
adjustment type tr
[tr] long-time protection delay 12.5…600 s at 1.5 x Ir
adjustment range 0.5…24 s at 6 x Ir
0.7…16.6 s at 7.2 x Ir
Thermal memory 20 mn
Instantaneous protection pick-up Adjustable
adjustment type Ii
[Ii] instantaneous protection pick- 1.5...10 x Ir
up adjustment range
Earth-leakage protection Without
Zone selective interlocking ZSI Without
Auxiliary contact composition 1 NO/NC
Local signalling 4 LEDs (red) for fault indication
1 LED (yellow) for overload
Display type LCD display
Type of measurement Energy meter
Width (W) 210 mm
Height (H) 327 mm
Depth (D) 147 mm
Net weight 14 kg
Environment
Standards EN/IEC 60947-2
Product certifications IECEE CB Scheme
Pollution degree 3 conforming to IEC 60947
IP degree of protection IP40 conforming to IEC 60529
IK degree of protection IK07 conforming to EN 50102
Ambient air temperature for -25…70 °C
operation
Ambient air temperature for -40…85 °C
storage
Relative humidity 0…95 %
Operating altitude 0...2000 m without derating
2000 m...5000 m with derating
2 14-Mar-2025
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 37.0 cm
Package 1 Width 39.5 cm
Package 1 Length 23.0 cm
Package 1 Weight 12.149 kg
14-Mar-2025 3
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Carbon footprint (kg.eq.CO2 per CR, Total Life cycle) 1014
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Recycled metal content at CR level 0
EU RoHS Directive Compliant with Exemptions
REACh Regulation REACh Declaration
PVC free No
Silicon free No
Use Again
Repack and remanufacture
Circularity Profile End of Life Information
Removable battery User replaceable
The product must be disposed on European Union
WEEE markets following specific waste collection and never end
up in rubbish bins
Halogen content performance Product contains halogen above thresholds
Take-back No
4 14-Mar-2025