The document outlines fire safety regulations and design considerations for residential buildings in London, including means of escape for houses and apartments. It details requirements for various building heights, escape routes, and fire safety measures such as smoke venting and suppression systems. Additionally, it addresses specialized housing types and the importance of maintaining fire safety during and after construction.

Uploaded by

Adrian Jugariu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views55 pages

Residential Fire Safety Presentation

The document outlines fire safety regulations and design considerations for residential buildings in London, including means of escape for houses and apartments. It details requirements for various building heights, escape routes, and fire safety measures such as smoke venting and suppression systems. Additionally, it addresses specialized housing types and the importance of maintaining fire safety during and after construction.

Uploaded by

Adrian Jugariu
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 55

Residential Fire

Safety
Design and flexibility

London Building Control


13 Woodstock Street, Mayfair, London, W1C 2AG

Tel: 0207 099 3636


[email protected]
www.londonbuildingcontrol.co.uk
Residential Means of Escape
Houses
• The options

Apartments
Within apartments
• Open plan and Inner room provisions
• Gallery floors
• MOE - Floor is not more than 4.5m above GL
• MOE – Floor more than 4.5m above GL
The Common parts

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Houses

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
• Single storey
• Two storey (top floor less than 4.5 metres from GL)
• Three storey (top floor more than 4.5 metres above
GL)
• Four storey
Houses
• Basements

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
• Means of escape
Floors not more than 4.5m above GL

• Ground floor:
Direct access to an exit
or
Egress window for inner rooms

• First floor:
Houses 2 storey Egress window for habitable rooms
or
Internal protected stairway

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Means of escape – Internal planning
Floors more than 4.5m above GL
Protected escape route or open plan with
suppression and smoke protected access to first floor
escape window
Means of escape – Internal planning
Floors more than 7.5m above GL
Houses 3 & 4 storey Protected escape route plus alternative exit or
suppression

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Inner rooms ADB
• Acceptable as a kitchen, laundry, utility, dressing room,
bathroom or gallery
• Any room, not more than 4.5m above GL that has an
egress window
• An inner-inner room may be acceptable if it falls under
one of the above uses, and, not more than one door
Houses separates the room from an interlinked smoke alarm and
none of the access rooms are a kitchen

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Escape windows ADB
• Max height of cill 1100mm
• Min height 800mm or 600mm for a window in the roof
• Locks (with or without removable keys) can be fitted
with a release catch which may be child resistant
• They should remain in the open position to allow
persons escaping.

Basement lightwell escape


• Alternative escape via fixed non corrosive robust ladder
Houses (max 70 degree pitch) with stepped rungs and guarding
accepted.

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
ADB options for three storey:
• Suppression to ground floor plus
• Separation of ground floor from first floor to allow top floor
smoke free access to a first floor escape window plus
• Enhanced fire detection grade D2 LD1 plus
• Kitchen remote from escape route
Or
• Smoke curtain to protect escape route from habitable
Houses – Open plan accommodation as far as the final exit plus
ground floor • Enhanced Fire detection grade D2 LD1

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Two storey house becoming three storey
Options for protected stairway ADB vol 1
• Replace existing doors to protect stairway with FD20
doors (including bathrooms if they include a heat
producing appliance)
Or
• if the existing doors are robust solid doors at least
House Loft 32mm thick and fit well in their frames these can be
Conversions retained with enhanced fire detection Grade D LD1
Notes. All glass in doors to be fire resisting in both situations.

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Apartments

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Internal planning where top floor is less than 4.5
metres from external GL

ADB vol 1
• Inner rooms are not an issue provided there are
suitable escape windows from those rooms
Within apartments

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Internal planning where top floor is more than 4.5
metres above GL

ADB Vol 1

• Maximum travel distance and layout guidance provided.


Open plan is okay but no inner rooms permitted
Within apartments • Gallery guidance

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Galleries ADB

Should have an alternative exit or egress window if


not more than 4.5m above GL
•If the gallery has neither of the above, it should
comply with the following

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Gallery Floors
Overlook 50% of the room below
Max 3m from foot of access stair to room door
Max 7.5m across gallery to access stair
Cooking facilities in the access room should be remote or enclosed
in FR construction

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Allowable variations without
calculated Fire Engineering solutions

Within apartments

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
BS 9991: 2015
Open plan flats – Para 9.7

• Open-plan flats that have bedrooms as inner rooms


without alternative MOE, may be permitted provided that
the flat is fitted with a sprinkler system and a Grade D LD1
alarm

Within apartments
• Note Should not be used for sheltered housing or extra care housing

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
BS9991 Open plan flats Conditions to
allow inner rooms
•Size should not exceed 16m x 12m
•Single level only [no gallery]
•Minimum room height of 2.25m
•The kitchen should be enclosed if the area of the flat
exceeds 8m x 4m
Within apartments
Note: Flats smaller than this should have cooking appliances remote from
the flat entrance

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
BS9991 Open plan
flat size flexibility
with suppression

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Where the entrance floor level and the floors above/
below do not exceed 7.5m, provide protected stairway,
plus AFD in all habitable rooms and HD in the kitchen, or
a protected staircase and sprinklers throughout.

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Apartments Common Escape

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
•Single staircase guidance
•More than one staircase guidance
Apartments common
escape

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Small single-stair buildings
• Top floor not more than 11m above GL
• No more than 3 storeys above GL
• Does not connect to covered car park
• Does not serve ancillary accommodation unless
Apartments common protected with ventilated lobby
escape • High level 1.0m2 OV at each floor, or single vent at
head of stair operated at building access level

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Apartments common
escape

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Single-stair but does not meet the
definition for small single stair?

Diagram 3.7
•Note common lobby corridor smoke venting
provisions and travel distances.
Apartments common
escape •BS 9991 provides flexibility on the travel distances in
ventilated areas

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
BS9991
Max TD in
Common Part
15m with
sprinklers

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Smoke Venting Requirements

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Smoke control in lobbies
• Locate as high as possible with top edge at least as high
as the top of the stair door
• In single stair buildings, vents on the fire floor and at
the head of the stair, should be actuated by AFD in the
common parts
• Where there is more than one stair, the vent can be
Apartments common actuated manually, provided the vent at the head of the
escape stair is opened before, or at the same time, as the vent on
the fire floor

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Vent design

• Locate on external wall, free area 1.5m2

Or

• Discharge into vertical smoke shaft


Apartments common
escape

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Min cross-sectional area 1.5m2
Min dimension 0.85m in any direction
Opening at roof at least 0.5m above adjacent structures
within 2.0m horizontally
Extend 2.5m above ceiling of highest storey
Non-combustible material
Vertical shaft with nmt 4m at an inclined max 300
Apartments common Upon detection, the vent on the fire floor and at head
escape of staircase should open together (all other vents
should remain closed)

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Mechanical Smoke
Vents-Make up Air

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Other relevant guidance

• Sub divide corridors that connect 2 or more exits


• No storage in single staircase buildings
• Escape over roof OK if not the only route
• For buildings with nmt -3 storeys stairs can serve other occupancies
provided that they are separated with lobbies at all levels
Apartments common • If more than 3 storeys, should be ancillary, have independent
escape alternative escape and be lobbied

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
B5 Access for fire fighting
Consider the height of the development
• The 45m rule applies from the pumping appliance
to every point within the flats
• The hose laying distance is taken up the pitch of
the flight and not vertically through the staircase
enclosure
• Providing a dry rising main may be a suitable
Apartments alternative
BS9991 allowances with suppression -Two storey 90m and
Three storey 75m

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Height of top floor above external ground floor
level 2020 changes
> 11 metres? –
Mandatory suppression for Residential
Non-combustible walls
> 18 metres? –
Dry Riser
Fire fighting shaft and lift required

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Fire safety during construction

The CDM Regulations 2015


HSG 168 guide
UKTFA 16 steps guide

Identify the risks and mitigate

Maintaining Fire Safety after occupation


The Regulatory Reform (Fire Safety) Order 2005.

Housekeeping, maintenance procedures


and Tolerable Risk

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Specialised housing

• Cluster accommodation -BS9991


• Sheltered, Retirement, Assisted flats-BS9991
• Shared house -LaCors Guide
• Bedsits -LaCors guide

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Cluster
accommodation

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Cluster
accommodation

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
LaCors Guide

35. Shared houses

• 35.1 There is no legal definition of a ‘shared house’ and so


this term can sometimes cause confusion. Whilst shared
houses fall within the legal definition of an HMO (see
Appendix 1, paragraph A.32) and will be licensable where
licensing criteria are met, it is recognised that they can often
HMO shared house present a lower fire risk than traditional bedsit-type HMOs
due to their characteristics.

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
35.2 For the purposes of this guidance, shared houses are
described as HMOs where the whole property has been
rented out by an identifiable group of sharers such as
students, work colleagues or friends as joint tenants. Each
occupant normally has their own bedroom but they share the
kitchen, dining facilities, bathroom, WC, living room and all
other parts of the house.
HMO shared house

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
All the tenants will have exclusive legal possession and
control of all parts of the house, including all the bedrooms.
There is normally a significant degree of social interaction
between the occupants and they will, in the main, have rented
out the house as one group. There is a single joint tenancy
agreement. In summary, the group will possess many of the
characteristics of a single family household, although the
property is still technically an HMO as the occupants are not
HMO shared house
all related.

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
LaCors case
study example

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
LaCors Guide
Bedsit-type HMOs
These are HMOs which have been converted into a number of
separate non-self-contained bedsit lettings or floor-by-floor
lets. Typically there will be individual cooking facilities within
each bedsit, but alternatively there may be shared cooking
facilities or a mixture of two. Toilets and bathing/washing
facilities will mostly be shared. There is unlikely to be a
communal living or dining room. Each bedsit or letting will be
HIMO Bedsits let to separate individuals who will live independently, with little
or no communal living between tenants. Each letting will have
its own individual tenancy agreement and there will usually be
a lock on each individual letting door.
Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
LaCors case
study example

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Heights and distances
9m 11m
Design Change Points

4.5m 45m

7.5m 50m 18m

15m 30m

20m

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Heights and distances
Design Change Points

Limits of small single stair building.


Max travel distance in flats 9m 11m 2020 changes-Sprinkler required above this height.
Non-combustible walls changes 2020?

Max lobby travel distance.


B5 max hose distance
Height where lobbies required 4.5m 45m
Limits of escape window use

Fire fighting shafts


Dry risers
Max travel distance with
smoke venting
7.5m 50m 18m Distance pump appliance to riser.
Wet riser Non combustable cladding. 2019 reqmt
Increased fire resistance 90 minutes.

Single direction travel distance 15m Flats sprinklers required pre 2020 changes
30m
with suppression added and increased fire resistance 120 minutes

B5 dead end distance limit 20m

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Any questions?

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Thank you for
listening

Tel: 0207 099 3636 * [email protected] * www.londonbuildingcontrol.co.uk

ISO9001 Certified
Head Office:

London Building Control,


13 Woodstock Street, Mayfair,
London, W1C 2AG

Tel: 0207 099 3636


www.londonbuildingcontrol.co.uk
[email protected]

Offices also in:

Chichester: 01243 882990


Manchester: 0161 660 0806
Welwyn Garden City: 01707 248611
Exeter: 01392 240770

You might also like