Secador QUALITROL - EE-50519
Secador QUALITROL - EE-50519
OPERATING INSTRUCTIONS.
(QUALITROL).
INSTRUCTION SHEET
IST-111-1
Background
The Qualitrol STB-100/200 Series Breather has an NPT center thread to which the STB-10x/20x
mounting flange assembly is fastened. The flange assembly nipple has pre-coated threads which
will seal when tightened to the Breather.
Instructions
STB-10x Series
Position the Breather horizontally on a flat surface as shown. Hold the flange assembly by the hex nipple
and hand-tighten to the Breather.
MOUNTING
FLANGE
ASSEMBLY
HEX
NIPPLE
Securely maintain the horizontal position of the Breather while using a wrench to rotate the nipple 1.5 to
2.5 full turns. Stop rotation when the positions of the flange mounting holes are as shown.
MOUNTING
FLANGE
ASSEMBLY
DIN
MOUNTING
FLANGE
ASSEMBLY
7/8" HEX
WRENCH FLATS
STB-20x Series
Position the Breather horizontally on a flat surface as shown. Hold the flange assembly by the hex nipple
and hand-tighten to the Breather.
MOUNTING
FLANGE
ASSEMBLY
HEX
NIPPLE
Securely maintain the horizontal position of the Breather while using a wrench to rotate the nipple 1.5 to
2.5 full turns. Stop rotation when the positions of the flange mounting holes are as shown.
MOUNTING
FLANGE
ASSEMBLY
3
1 8" HEX FINAL MOUNTING
WRENCH FLATS HOLE ORIENTATION
(STB-201 Shown Above)
QUALITROL STB-1xx-1xx
QUALITROL STB-1xx-2xx
Information in this document is subject to change without notice. This document is provided to purchasers of Qualitrol
products for use in the installation, operation and servicing of such products. No other use, nor any reproduction, distribution
or the making of any derivatives of this document is authorized, without the express prior written permission of Qualitrol.
Qualitrol endeavors to ensure the accuracy and quality of its published materials; however, no warranty, expressed or
implied, is provided. Qualitrol disclaims any responsibility or liability for any direct or indirect damages resulting from the use
of the information in this manual or products described in it. Mention of any product or brand does not constitute an
endorsement by Qualitrol of that product or brand.
This document was originally composed in English and was subsequently translated into other languages. The fidelity of
subsequent translations cannot be guaranteed. In case of conflict between the English version and another language version,
the English version takes precedence.
©2008 QUALITROL Company LLC, an ISO 9001 system certified company. All rights reserved. Information subject to change without notice.
®
All trademarks are properties of their respective companies, as noted herein. IST-099-1.
2 www.qualitrolcorp.com
About Qualitrol®
QUALITROL® manufactures substation and transformer monitoring and protection devices
used by electric utilities and OEM manufacturing companies. It is the global leader in sales
and installations of transformer asset protection equipment, fault recorders, and fault
locators. Established in 1945, QUALITROL® produces different types of products on
demand, customized to meet unique requirements.
3 www.qualitrolcorp.com
Table of Contents
List of Abbreviations/Acronyms .............................................................................................. 7
Chapters in the manual .......................................................................................................... 8
Introduction ............................................................................................................................ 9
QUALITROL® STB .............................................................................................................. 9
Operation ............................................................................................................................ 9
Specifications ....................................................................................................................... 11
Safety ................................................................................................................................... 12
Installation ............................................................................................................................ 13
Mounting the STB.............................................................................................................. 13
Electrical Connection......................................................................................................... 15
AC Power connections .................................................................................................. 15
MODBUS Connections .................................................................................................. 15
4-20 mA current loop ..................................................................................................... 16
Regeneration status relay .............................................................................................. 16
DIP Switch Setting for Frequency Generation ................................................................... 17
Startup............................................................................................................................... 18
Establishing Communication with STB Control Unit .......................................................... 19
USB Communication ..................................................................................................... 19
MODBUS Communication ............................................................................................. 25
Troubleshooting ................................................................................................................... 29
Alarms ............................................................................................................................... 29
Priority of Alarms ........................................................................................................... 29
Troubleshooting the USB Communication Link ................................................................. 30
USB Communication ..................................................................................................... 31
MODBUS Communication ............................................................................................. 31
Annual Inspection .............................................................................................................. 32
Servicing .............................................................................................................................. 33
Notes…………………………………………………………………………………………………34
4 www.qualitrolcorp.com
List of Figures
Figure 1. Parts of STB ........................................................................................................ 10
Figure 2. Mounting Plate Dimensions ................................................................................. 13
Figure 3. Hose Barb ............................................................................................................ 14
Figure 4. AC Power Connections ........................................................................................ 15
Figure 5. MODBUS Connections ........................................................................................ 15
Figure 6. Current Loop ........................................................................................................ 16
Figure 7. Error and Regenaration Status Relays ................................................................ 16
Figure 8. Control Box Screws ............................................................................................. 17
Figure 9. Printed Circuit Board DIP Switch ......................................................................... 17
Figure 10. Accessing the Filter.............................................................................................. 32
Figure 11. Removing the RH Sensor Cap ............................................................................. 32
Figure 12. Cleaning the RH Sensor ...................................................................................... 33
5 www.qualitrolcorp.com
List of Tables
Table 1. Parts of STB ........................................................................................................ 10
Table 2. Specifications ....................................................................................................... 11
Table 3. DIP Switch Setting ............................................................................................... 18
Table 4. Terminal Communications Parameters ................................................................ 21
Table 5. MODBUS Parameters.......................................................................................... 25
Table 6. Error Description .................................................................................................. 29
Table 7. Control Actions..................................................................................................... 30
Table 8. Multiple Error Display ........................................................................................... 30
6 www.qualitrolcorp.com
List of Abbreviations/Acronyms
List of Abbreviations/Acronyms
Abbreviations/Acronyms Expansion
AC Alternating Current
RH Relative Humidity
7 www.qualitrolcorp.com
Chapters in the manual
Chapters Description
8 www.qualitrolcorp.com
Introduction
Introduction
The STB Polar Execution (PE) Series includes additional heaters for cold climates and are
suitable for operation in ambient temperatures from -60°C to 80°C. The On-Load Tap
Changer (TC) Series is designed specifically for those installations which do not require
monitoring of inhale/exhale status prior to regeneration. The Offshore Extreme (SS) Series
incorporates special materials and construction to withstand corrosion due to salt spray
environments.
Operation
Atmospheric air enters the STB and is routed through the silica gel desiccant to the top
port, where a relative humidity (RH) sensor continuously monitors the humidity level of the
air exiting the breather to the transformer. Based on the RH sensor input the
microcontroller determines whether regeneration of the desiccant is necessary. A heater
placed at the center of the desiccant container regenerates the silica gel based on either
the RH level or the user selectable regeneration frequency, whichever occurs first. The
moisture from the desiccant then condenses on the clear outer tube and drains out of
bottom port of the STB. The regeneration occurs only during the exhale phase of the
conservator except on TC models. The built-in intelligence system monitors the system’s
status and automatically selects an appropriate time window for desiccant regeneration.
System status is communicated via a local USB port, local LED indication, MODBUS
protocol, 4-20 mA output, and both regeneration status and error status relays.
9 www.qualitrolcorp.com
Introduction
10 www.qualitrolcorp.com
Specifications
Specifications
Electrical
Voltage / frequency 100 – 240 VAC, 50 / 60 Hz
Operating Conditions
*
Temperature -60°C to 80°C
Table 2. Specifications
*Note that at temperatures less than 0°C, condensation in the tube may frost over – this does not affect the proper operation of the STB.
11 www.qualitrolcorp.com
Safety
Safety
The following symbols appear throughout the manual and indicate important safety
instructions:
Warning
Indicates information is important for personal safety. Failure to follow may result in
personal injury or death.
Caution
Indicates information is important for the proper operation of the equipment. Failure to
follow may result in damage to the equipment.
Warning
Switch off the power supply before performing installation, maintenance and/or
troubleshooting.
Do not touch the STB when in operation (when the amber light is ON) as the
heater and polycarbonate (or glass) tube can become hot.
12 www.qualitrolcorp.com
Installation
Installation
Caution
Mounting the STB
1. Mount the STB in the vertical position shown. Do not mount on its back or side.
13 www.qualitrolcorp.com
Installation
2. Connect the hose barb fitting or mounting flange to the sensor block and tighten it.
14 www.qualitrolcorp.com
Installation
Electrical Connection
Warning
Make sure to ground the STB according to local regulations.
Communications and relay connections must be made with shielded cabling. The STB is
supplied with two M20 (Ø8- Ø11 mm) and one M20 (Ø11- Ø15 mm) cable glands.
AC Power connections
AC power wiring (J6) is shown in Figure 4. See inside cover label for fuse size/location.
Grounding has to be provided as a part of installation and it must be in accordance
with requirements of National Electric Code (NEC) or any international code that is in
effect locally.
15 www.qualitrolcorp.com
Installation
16 www.qualitrolcorp.com
Installation
CONTROL
BOX CONTROL
BOX COVER
PC BOARD
COVER
SCREW (4)
17 www.qualitrolcorp.com
Installation
3. Set the DIP switch position according to table 3. The default setting is 70 days.
DIP Switch Position Regeneration
Frequency
Position 1 Position 2
ON ON 10 Days
ON OFF 40 Days
OFF ON 70 Days
Startup
To start the STB:
1. Verify that the STB is mounted in an upright position.
2. Verify that all electrical connections are properly made.
Caution
3. Verify that the control box enclosure screws have been properly fastened: use
approximately 24 in-lbs torque to assure cover is fully seated and sealed. Tighten
power and communications cable glands so that they tightly grip cables, providing
sealing and strain relief to cables. Any unused cable gland entries should be plugged.
4. Energize the STB.
5. Verify that the green LED is lit.
Note: Make sure that the amber and red LEDs are OFF. The red LED will light
momentarily. If the green LED does not turn ON, refer to “Troubleshooting”.
18 www.qualitrolcorp.com
Installation
http://www.ftdichip.com/Drivers/VCP.htm
Follow the steps below to establish USB communication between a PC/laptop and the
STB:
1. Switch OFF the STB.
2. Connect the STB and a PC/laptop with a USB cable. Switch ON the STB unit.
3. Open HyperTerminal (or equivalent) on laptop/PC
4. Enter the session name and click OK.
5. Select the COM port assigned to the STB connection and click OK.
19 www.qualitrolcorp.com
Installation
20 www.qualitrolcorp.com
Installation
The Device Selection is a factory setting which can only be accessed with a password.
The Read Menu allows the user to read the following Device status and factory Device
settings from the STB:
Parameter Menu Description
Current Breather Firmware Device Status 4 kg (Jumbo), 1-2 kg Main Tank or 1 kg OLTC
DIP switch setting Device Status Run time status of DIP switch
System up time Device Status Time in days from last device restart
Forced regeneration days Device Status Elapsed zero pressure days before forced regen enabled
DIP switch time Device Status Current DIP switch timer status in days
Humidity safe zone value Device Settings Threshold for post regeneration heater error
Regen frequency setting Device Settings Regeneration frequency for each DIP switch position
21 www.qualitrolcorp.com
Parameters
Parameters
a) To read Device Status:
1. Press 'B' to select the Read Menu
2. Press '1' to select the Device Status
Note: the backspace key used to return to previous menus may vary with the terminal emulator in
use. On PuTTY and Tera Term, for example, Control H may be used.
22 www.qualitrolcorp.com
Parameters
The Write Menu can be used to change the relative humidity threshold trigger from its
default value of 50%, or to change the operation of either of the status relays from their
default non-failsafe mode to failsafe mode.
c) To change the Humidity Threshold:
1. From the Main Menu, Press 'C' to display the Write Menu.
2. Press ‘1’ to set the Humidity Values, and '1' to set the Humidity Threshold.
3. Enter the threshold value from the available list.
23 www.qualitrolcorp.com
Parameters
The Error Status relay and Regeneration Status relays have two operating modes,
Failsafe and Non-failsafe.
The Write Menu can be used to change the operation of either of the status relays from
their default NonFailsafe mode to Failsafe mode.
In NonFailsafe mode the relays are not normally energized and the Normally Open and
Normally Closed connections shown apply.
In Failsafe mode the relays are energized and the Normally Open and Normally Closed
connections are reversed. If power to the STB is interrupted the relays become de-
energized and enter their alarm condition. This is especially useful for the Error Status
relay.
Relay Mode No error/No regeneration Error/ Regeneration
24 www.qualitrolcorp.com
Parameters
MODBUS Communication
MODBUS communication is supported with RS-485 2-wire and 4-wire mode to enable
remote monitoring and control of STB parameters.
In MODBUS communication, the STB acts as a SLAVE and 509ITM device acts as the
MASTER. Note: Check with factory to confirm availability of STB MODBUS on the 509ITM.
Follow the below steps to establish RS-485 communication between MODBUS Master
and STB:
1. Switch OFF the STB.
2. Connect the STB and MODBUS Master with suitable cable (for more details, refer
MODBUS Connections).
3. In MODBUS Master, open the GUI.
4. Select the correct COM port used for MODBUS communication.
5. Configure the rest of the communication parameters as shown below:
Baud rate: 9600
Data bits: 8
Stop bits: 1
Parity: Even
Error Checking: CRC16
Slave address: 1
6. Click on ‘Connect’ tab provided in Master GUI.
7. User can use function code 0x03 to read data from and 0x06 to write data to the STB.
25 www.qualitrolcorp.com
Parameters
26 www.qualitrolcorp.com
Parameters
0x0015 MBR_SHT11_TEMPR_READ R BIT 15: 1 – Temp value updated in this register is negative
0 – Temp value updated in this register positive
BIT 7-0: STH11 SENSOR TEMPERATURE VALUE
0x0016 MBR_REGN_TIMER_READ R REGENERATION TIMER READING
0x0017 MBR_SYS_FLAGS_LTC R Bit 0 = 1: HEATER 1 ENABLED (LC)
Bit 1= 1: HEATER 2 ENABLED (LC)
Bit 2 = 1: FOIL HEATER ENABLED
Bit 3 = 1: Unused, read as zero
Bit 4 = 1: DIP REGENERATION TRIGGERED
Bit 5 = 1: RH REGENERATION TRIGGERED
Bit 6 = 1: DIP REGERATION ENABLED
Bit 7 = 1: RH REGENERATION ENABLED
Bit 8-15: Unused, read as zero
27 www.qualitrolcorp.com
28 www.qualitrolcorp.com
Troubleshooting
Troubleshooting
Alarms
Category of Alarms
Critical: The STB will stop working and the defective part must be replaced.
Soft: The STB will continue to work. The defective part has to be serviced or replaced as
per the requirement.
The following table lists the LED status and the corresponding errors:
29 www.qualitrolcorp.com
Troubleshooting
The following table lists the alarm type, its category and the STB control actions.
Run time DIP switch Soft Alarm is conveyed to remote monitoring unit.
error Breather will continue operation with initial DIP switch settings
Breather control logic will continuously look for recovery
Humidity sensor Soft Alarm is conveyed to local display and remote monitoring unit.
failure Breather will continue working in auto mode.
Regeneration frequency is reduced to default 5 days. Only DIP
switch trigger will be considered for regeneration.
Breather control logic will continuously look for recovery
Regen Heater Critical Alarm is conveyed to local display and remote monitoring unit.
failure Breather will stop working in auto mode and starts operating in
conventional mode.
Manual servicing and device restart is required
Encl Heater/ Soft Alarm is conveyed to local display and remote monitoring unit
Temperature (MODBUS).
sensor failure Breather will continue working
Solenoid/Pressure Critical Alarm is conveyed to local display and remote monitoring unit.
Switch Failure Breather will stop working in auto mode and starts operating in
conventional mode.
Manual servicing and device restart is required
Should the STB have multiple errors, all errors will be displayed in the order shown below.
Each error will displayed 7 times continuously, followed by a 2 second delay and then the
next error.
Error Priority
Regen Heater error 1
Solenoid/Pressure switch error 2
Humidity sensor error 3
Encl Heater/Temperature sensor error 4
Table 8. Multiple Error Display
30 www.qualitrolcorp.com
Troubleshooting
Troubleshooting Communications
USB Communication
If a problem occurs in establishing a USB communication link between the PC/laptop
and the STB:
Check that the STB control unit is energized.
Check that the cable connected to the COM port is assigned to the present USB
communication link.
Check that the port parameter configurations like baud rate, data bits, parity, stop
bits, and flow control are correct.
MODBUS Communication
If a problem occurs in establishing a MODBUS communication link between the 509ITM
and the STB:
Check that the STB unit is energized.
Check that the RS-485 connection is made as per the guidelines in MODBUS
Connections.
Check that communications parameters such as slave address, baud rate, data bits,
parity, stop bits, and CRC are correct.
Check that the function code and address/data range are valid.
31 www.qualitrolcorp.com
Troubleshooting
Maintenance
The STB is equipped with a real time monitoring system that signals whenever there is a
malfunction.
Note: Check the STB regularly for proper operation.
Annual Inspection
For annual inspection of the STB:
1. Remove the two pan head screws at the bottom of the STB.
Note: on Polar Execution models you will first need to remove the cable gland plate screws and
the bottom insulator before gaining access to the two screws holding the heating block, filter,
and top insulator to the STB.
2. Take the filter out and inspect for contamination. If any contaminants are present
clean the filter with a soft brush before re-assembling.
Filter
32 www.qualitrolcorp.com
Servicing
Servicing
RH Sensor
33 www.qualitrolcorp.com
Notes
34 www.qualitrolcorp.com