The document outlines the Bill of Quantities (BOQ) for electrical installations at an ATC Tower and Technical Building, detailing specifications for MV switchgear and power panels, including supply, installation, and testing requirements. It includes various assembly panels with specific ratings for incomers, outgoing circuits, busbars, and current transformers, emphasizing compliance with technical specifications and local standards. Vendors are instructed to ensure proper design coordination, SCADA integration, and to account for future enhancements in their quotes.

Uploaded by

Jagadeesh r
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
84 views20 pages

ATC Electrical BOQ

The document outlines the Bill of Quantities (BOQ) for electrical installations at an ATC Tower and Technical Building, detailing specifications for MV switchgear and power panels, including supply, installation, and testing requirements. It includes various assembly panels with specific ratings for incomers, outgoing circuits, busbars, and current transformers, emphasizing compliance with technical specifications and local standards. Vendors are instructed to ensure proper design coordination, SCADA integration, and to account for future enhancements in their quotes.

Uploaded by

Jagadeesh r
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as XLS, PDF, TXT or read online on Scribd
You are on page 1/ 20

ELECTRICAL BOQ _ATC TOWER AND TECHNICAL BUILDING

Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate

1.0 MV SWITCHGEAR & POWER PANELS

1.1 Supply, installation, testing and commissioning of cubicle type panels (Form 3b) as per -
specifications and shown on drawing.
i) Main busbars with bar type feeder connections & all internal wiring and connections.
ii) Earthing all components, frame etc. to a common internal earth bar.
iii) Painting all sheet metal works.
iv) All accessories & supporting structure.
v) Brass glands, Al lugs for Al cables; Cu lugs for Copper Cable & bimetallic lugs for
difference in metal; for sending and receiving ends suitable for cable sizes mentioned in
SLD.
(Crimping lugs forming part of the termination)
vi) All ammeters with C.T's and voltmeter and energy meters with necessary fuses. (All
meters shall be digital)
vii) Panel components as specified.
viii) MS base frame.
ix) All switch gear to have short circuit levels as specified.
x) Space heaters with thermostat.
xi) SPD to be provided in Main LT Panel.
xii)The Panels shall have Indicating lamps for the phases and its ON , OFF , TRIP
Indications as per the schematics provided.
xiii) Phase sequence for transformer shall be matched.
xiii) Protective relay's as per schematics

Note : Panel vendor should co relate the boq with the schematic and give the quote .

If any deviation from the Boq and schematics should mention in the devaition list before
quote .
Vendor should design the CT,PT burden ration and shall be liable for the design .
Breaker up stream and down stream coordination shall be taken care and ensure the
system shall function properly without any interrupts/faults.
Relay cordination , CT calcualtion shall be part of vendor and asses the deisgn and
provide the quote .
Minimum spares and 10 % space cubicle to be considered in the design for the future
enhancebility .
panel fabrication shall comply to the technical specification and local standards .Type
should be Minimum 3b
All incomers bus couplers should have SCADA integration provision in the main LT
panels.
Fault current provided in the panels is designed level, as per the breaker availibility of
incomers fault current should be selected .
And correspondinmg downstream coordination to be done in the breakers .
Outgoing breakers which are provided with letter M ie motorized breakers . These should
have SCADA provisions for the interface .Vendor to provide
All energy meter are dual source meters with RS 485 port for the BMS integration.

Where a panel with Bus coupler and two incomers are provided, irrespective either
specified in the schematcis of BOQ , do consider the interlocking arrangement through
electrical and mechanical.

Vendor to evaluate the incoming and outgoing feeders with their capacities inconjunction
with the schematic.
Please consider Main incoming breakers as LSIG protection and outgoing with LSI
protection for all Main LT panels .

1.1.1 Assem ATC -MAIN LT PANEL


bly

891817480.xls Page 1 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate

A) Incomer-1 & 2
i) 2 sets- 1600A, 4P, ACB, EDO, 50KA
ii) 1 set- 1600A, 4P, ACB, EDO, 50KA as Bus coupler
iii) Electrical interlocking between both incomers and Bus coupler.

B) Outgoing:
i) 2 sets - 63A, TPN,MCCB, 25KA
ii) 2 sets - 100A, TPN,MCCB, 25KA
iii) 6 sets - 250A, TPN, MCCB, 25KA
iv) 4 sets - 320A, TPN, MCCB, 25KA
v) 6 sets - 400A, TPN, MCCB, 25KA

C) Busbar Rating 1
1600A ,4P, 433V, 50HZ, AL BUSBAR, 50KA FOR 1 SEC

D) Current Transformer Rating


i) 2 sets -1600/5A CT,CL-1.0, MFM.(BMS/SCADA Compatible)
ii) 2 sets -1600/5A CT,CL-1.0 APFC Sensing
iii) 1 sets -1600/5A CT,CL-5P10

E) Potential Transformer Rating


i) 1 Set- 415V/sqrt3 / 110V/sqrt3, CL- 3P

F) Trasient Voltage Surge Suppressor


SPD TYPE -1

1.1.2 Assem PRESSURIZATION LOAD PANEL


bly

A) Incomer
i) 1 sets- 63A, TPN,MCCB, 16KA

B) Outgoing:
i) 2sets - 32A, TPN,MCB, 10KA
ii) 2sets - 25A, TPN,MCB, 10KA
C) Busbar Rating
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC
1

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.3 Assem ELECTRICAL PANEL- ATC-TOWER PANEL


bly

A) Incomer
i) 1 sets- 250A, ATS
ii) 1 sets- 250A, TPN, MCCB, 16KA

B) Outgoing:
i) 1 sets - 100A, TPN,MCCB, 10KA
ii) 1 sets - 63A, TPN,MCCB, 10KA
iii) 9 sets - 32A, TPN,MCB, 10KA
iv) 1 sets - 40A, TPN,MCB, 10KA
v) 3 sets - 63A, TPN,MCB, 10KA 1

C) Busbar Rating
250A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 250/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.4 Assem LIGHTING & P0WER PANEL


bly

891817480.xls Page 2 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate

A) Incomer
i) 1 sets- 320A, 4P, ATS
ii) 1 sets- 320A, TPN, MCCB, 16KA

B) Outgoing:
i) 9 sets - 32A, TPN,MCB, 10KA
ii) 13 sets - 40A, TPN,MCB, 10KA

C) Busbar Rating
1
320A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 320/5A CT MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.5 Assem AIR-CONDITIONING POWER PANEL-1


bly

A) Incomer
i) 1 sets- 400A, 4P, ATS
ii) 1 sets- 400A, TPN, MCCB,MP-Based, 16KA with Shunt trip coil

B) Outgoing:
i) 12 sets - 63A, TPN,MCB, 10KA
ii) 14 sets - 40A, TPN,MCB, 10KA

C) Busbar Rating
1
400A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 400/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.6 Assem AIR-CONDITIONING POWER PANEL-2


bly

A) Incomer
i) 1 sets- 250A, 4P, ATS
ii) 1 sets- 250A, TPN, MCCB,TM-Based, 16KA with Shunt trip coil

B) Outgoing:
i) 7 sets - 63A, TPN,MCCB, 16KA

C) Busbar Rating 1
250A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 250/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.7 Assem GROUND FLOOR AC PANEL


bly

A) Incomer
i) 1 sets- 63A, TPN, MCCB,TM-Based, 16KA with Shunt trip coil

B) Outgoing:
i) 1 sets - 25A, TPN,MCB, 10KA
ii) 6 sets - 32A, TPN,MCB, 10KA
iii) 7 sets - 40A, TPN,MCB, 10KA

C) Busbar Rating
1
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.8 Assem FIRST FLOOR AC PANEL


bly

891817480.xls Page 3 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate

A) Incomer
i) 1 sets- 63A, TPN, MCCB,TM-Based, 16KA with Shunt trip coil

B) Outgoing:
ii) 9 sets - 32A, TPN,MCB, 10KA

C) Busbar Rating
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC
1

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.9 Assem SECOND FLOOR AC PANEL


bly

A) Incomer
i) 1 sets- 63A, TPN, MCCB,TM-Based, 16KA with Shunt trip coil

B) Outgoing:
ii) 13 sets - 32A, TPN,MCB, 10KA

C) Busbar Rating
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC
1

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.10 Assem THIRD FLOOR AC PANEL


bly

A) Incomer
i) 1 sets- 63A, TPN, MCCB,TM-Based, 16KA with Shunt trip coil

B) Outgoing:
i) 1 sets - 25A, TPN,MCB, 10KA
ii) 12 sets - 32A, TPN,MCB, 10KA
iii) 3 sets - 40A, TPN,MCB, 10KA

C) Busbar Rating
1
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.11 Assem TERRACE FLOOR AC PANEL


bly

A) Incomer
i) 1 sets- 63A, TPN, MCCB,TM-Based, 16KA with Shunt trip coil

B) Outgoing:
i) 35 sets - 32A, DP,MCB, 10KA
ii) 3 sets - 25A, TPN,MCB, 10KA

C) Busbar Rating 1
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.12 Assem UPS POWER PANEL-TB


bly

891817480.xls Page 4 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate

A) Incomer
i) 1 sets- 400A, ATS
ii) 1 sets- 400A, TPN, MCCB,MP-Based, 16KA

B) Outgoing:
i) 3 sets - 100A, TPN,MCCB, 10KA
ii) 2 sets - 63A, TPN,MCB, 10KA
iii) 10 Sets- 40A TPN MCB
1
C) Busbar Rating
400A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 400/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.13 Assem EMERGENCY LIGHTING PANEL


bly

A) Incomer
i) 1 sets- 63A, TPN,MCCB,TM-Based, 16KA

B) Outgoing:
i) 10 sets - 32A, TPN, MCB, 10KA

C) Busbar Rating
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC
1

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.14 Assem PLUMBING PANEL


bly

A) Incomer
i) 1 sets- 63A, TPN,MCCB,TM-Based, 16KA

B) Outgoing:
i) 4 sets - 32A, TPN,MCB, 10KA

C) Busbar Rating
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC
1

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.15 Assem ELEVATOR POWER PANEL


bly

A) Incomer
i) 1 sets- 100A, TPN,MCCB,TM-Based, 16KA

B) Outgoing:
i) 5 sets - 40A, TPN,MCB, 10KA

C) Busbar Rating
100A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC
1

D) Current Transformer Rating


i) 1 sets - 100/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.16 Assem ATC-TOWER PRESSURIZATION LOAD PANEL


bly

891817480.xls Page 5 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate

A) Incomer
i) 1 sets- 63A, TPN,MCCB,TM-Based, 16KA

B) Outgoing:
i) 4 sets - 40A, TPN,MCB, 10KA

C) Busbar Rating
63A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC
1

D) Current Transformer Rating


i) 1 sets - 63/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.17 Assem ATC-TOWER UPS POWER PANEL


bly
A) Incomer
i) 1 sets- 100A, TPN,MCCB,TM-Based, 16KA

B) Outgoing:
i) 2 sets - 63A, TPN,MCCB, 10KA
ii) 1 set - 63A, TPN,MCB, 10KA
iii) 2 sets - 40A, TPN,MCB, 10KA
iv) 1 set - 32A, TPN,MCB, 10KA
1
C) Busbar Rating
100A ,TPN, 433V, 50HZ, AL BUSBAR, 16KA FOR 1 SEC

D) Current Transformer Rating


i) 1 sets - 100/5A CT, MFM.(BMS/SCADA Compatible)

E) Trasient Voltage Surge Suppressor


SPD TYPE -2

1.1.18 Assem APFC Panel


bly

All capacitors shall be heavy duty 525V with 7% detunned harmonic filter complete with
manual switches and power factor relay with 8 # sequence switches and all other
required accessories as per the drawing/schematic no.-GGIAL-MW-ATCTB-EL-30-AL-001

A) Stages
1st Stage - 25 KVAR
2nd Stage - 25KVAR
3rd Stage - 25KVAR
4th Stage - 25KVAR
5th Stage - 15KVAR
6th Stage - 15KVAR
7th Stage - 10KVAR
8th Stage - 10KVAR

B) Incomer:
i) 1 set - 320A, TPN,MCCB, 25KA

C) Busbar Rating
320A ,433V, 50HZ, AL BUSBAR, 25KA FOR 1 SEC

D) Capacitor duty Contactor


2
i) 4 Nos. - 32A
ii) 2 Nos. - 25A
iii) 2 Nos.- 16A

D) MCB with Capacitor Fuse (D series)


i) 4 Nos. - 40A
ii) 4 Nos. - 32A

E) Indicating lamps
Incomer shall have Phase and trip indications.
Each Cap Bank feeder shall have ON indications.

Total for 1.0

891817480.xls Page 6 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
2.0 DISTRIBUTION BOARDS

2.1 Supply, installation, testing & commissioning of 500V Distribution Boards as


specified & shown on drawing with
i) Copper busbars together with tapped neutral bar for individual phases.
ii) Copper earth strip with tapping
iii) Interconnections and earthing.
iv) Sheet steel enclosure suitable for recessed or surface mounting with hinged
lockable doors interlocked with the incomer switch.
v) Phase to phase isolation (PPI) in case of 3Ph boards.
vi) Necessary support frame & painting, labeling etc. complete.
vi) Brass glands, Al lugs for Al cables; Cu lugs for Copper Cable & bimetallic lugs
for difference in metal; for sending and receiving ends suitable for cable sizes
mentioned in DWG
(Crimping lugs forming part of the termination)
vii) Isc= 10kA/16kA
viii) Outgoing SP MCB should be B curve for lighting circuit.
ix) Outgoing SP MCB should be C curve for power circuit.
x) Outgoing SP MCB should be D curve for motor.

2.1.1 Each Power Distribution Board (GL-PDB-1-12 way TPN DB) for ground floor (Z1)
specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (100mA)
ii) 10*3 # 20A SP MCB

2.1.2 Each Power Distribution Board (GL-PDB-2-12 way TPN DB) for ground floor(Z2)
specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (100mA)
ii) 10*3 # 20A SP MCB

2.1.3 Each Power Distribution Board (L1-PDB-1-12 way TPN DB) for First Floor (Z1)
specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (100mA)
ii) 10*3 # 20A SP MCB

2.1.4 Each Power Distribution Board (L1-PDB-2-12 way TPN DB) for First Floor (Z2)
specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (100mA)
ii) 10*3 # 20A SP MCB

2.1.5 Each Power Distribution Board (L2-PDB-1-12 way TPN DB) for Second Floor (Z1)
specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (100mA)
ii) 10*3 # 20A SP MCB

891817480.xls Page 7 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
2.1.6 Each Power Distribution Board (L2-PDB-2-12 way TPN DB) for Second Floor (Z2)
specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (100mA)
ii) 10*3 # 20A SP MCB

2.1.7 Each Power Distribution Board (L3-PDB-1-12 way TPN DB) for Third Floor (Z1)
specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (100mA)
ii) 10*3 # 20A SP MCB

2.1.8 Each Power Distribution Board (L3-PDB-2-12 way TPN DB) for Third Floor (Z2)
specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (100mA)
ii) 10*3 # 20A SP MCB

2.1.9 Each UPS Power Distribution Board (GL-UDB-1- 8 Way TPN DB) for ground floor
(Z1)specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 40A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.10 Each UPS Power Distribution Board (GL-UDB-2- 6 Way TPN DB) for ground floor
(Z2)specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 40A DP RCCB (100mA)
iv) 4*3 # 20A SP MCB

2.1.11 Each UPS Power Distribution Board (L1-UDB-1- 8 Way TPN DB) for First floor
(Z1)specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 40A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.12 Each UPS Power Distribution Board (L1-UDB-2- 8 Way TPN DB) for First floor
(Z2)specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 40A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

891817480.xls Page 8 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
2.1.13 Each UPS Power Distribution Board (L2-UDB-1- 8 Way TPN DB) for Second floor
(Z1)specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 40A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.14 Each UPS Power Distribution Board (L2-UDB-2- 8 Way TPN DB) for Second floor
(Z2)specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 40A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.15 Each UPS Power Distribution Board (L3-UDB-1- 8 Way TPN DB) for Third floor
(Z1)specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 40A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.16 Each UPS Power Distribution Board (L3-UDB-2- 8 Way TPN DB) for Third floor
(Z2)specified & shown on drgs consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 40A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.17 Each AC Power Distribution Board (GL-ACDB- 8 Way TPN DB) for Ground floor
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
iii) 3 # 25A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.18 Each AC Power Distribution Board (L1-ACDB- 8 Way TPN DB) for First floor specified
& shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
iii) 3 # 25A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.19 Each AC Power Distribution Board (L2-ACDB- 8 Way TPN DB) for Second floor
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
iii) 3 # 25A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

891817480.xls Page 9 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
2.1.20 Each AC Power Distribution Board (L3-ACDB- 6 Way TPN DB) for Third floor specified
& shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
iii) 3 # 25A DP RCCB (100mA)
iv) 4*3 # 20A SP MCB

2.1.21 Each Lighting & Power Distribution Board (LPDB-ATC-S/S- 12 Way SPN DB) for sub
station specified & shown on drgs consisting of :
Incomer:
i) 1# 32A DP MCB
1
Outgoing:
i) 1 # 25A DP RCCB (30mA)
ii) 4 # 20A SP MCB
iii) 4 #10A SP MCB

2.1.22 Each Emergency Lighting & Power Distribution Board (ELPDB-ATC-S/S- 8 Way SPN
DB) for sub station specified & shown on drgs consisting of :
Incomer:
i) 1# 32A DP MCB
1
Outgoing:
i) 1 # 25A DP RCCB (30mA)
ii) 4 # 20A SP MCB
iii) 4 #10A SP MCB

2.1.23 Each Lighting Distribution Board (GL-LDB1- 8 Way TPN DB) for Ground floor ( Z-1)
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

2.1.24 Each Lighting Distribution Board (GL-LDB2- 8 Way TPN DB) for Ground floor ( Z-2)
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

2.1.25 Each Lighting Distribution Board (L1-LDB1- 8 Way TPN DB) for First floor ( Z-1)
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

2.1.26 Each Lighting Distribution Board (L1-LDB2- 8 Way TPN DB) for First floor ( Z-2)
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

891817480.xls Page 10 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
2.1.27 Each Lighting Distribution Board (L2-LDB1- 8 Way TPN DB) for Second floor ( Z-1)
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

2.1.28 Each Lighting Distribution Board (L2-LDB2- 8 Way TPN DB) for Second floor ( Z-2)
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

2.1.29 Each Lighting Distribution Board (L3-LDB1- 8 Way TPN DB) for Third floor ( Z-1)
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

2.1.30 Each Lighting Distribution Board (L3-LDB2- 8 Way TPN DB) for Third floor ( Z-2)
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

2.1.31 Each Emergency Lighting Distribution Board (GL-ELDB1-6 Way TPN DB) for ground
floor( Z-1) specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

2.1.32 Each Emergency Lighting Distribution Board (GL-ELDB2-6 Way TPN DB) for ground
floor( Z-2) specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

2.1.33 Each Emergency Lighting Distribution Board (L1-ELDB1-6 Way TPN DB) for First
floor( Z-1) specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

891817480.xls Page 11 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
2.1.34 Each Emergency Lighting Distribution Board(L1-ELDB2-6 Way TPN DB) for First
floor( Z-2) specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

2.1.35 Each Emergency Lighting Distribution Board (L2-ELDB1-6 Way TPN DB) for Second
floor( Z-1) specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

2.1.36 Each Emergency Lighting Distribution Board(L2-ELDB2-6 Way TPN DB) for Second
floor( Z-2) specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

2.1.37 Each Emergency Lighting Distribution Board (L3-ELDB1-6 Way TPN DB) for Third
floor( Z-1) specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

2.1.38 Each Emergency Lighting Distribution Board (L3-ELDB2-6 Way TPN DB) for Third
floor( Z-2) specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

2.1.39 Each Façade Distribution Board - 8 Way TPN DB specified & shown on drgs consisting
of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 3 # 25A DP RCCB (100mA)
iv) 6*3 # 20A SP MCB

2.1.40 Each Vertical Distribution Board - 4 Way VTPN DB specified & shown on drgs
consisting of :
Incomer:
i) 1# 40A TPN MCB
1
Outgoing:
iii) 2 # 25A TP MCB
iv) 2 # 16A SP MCB ; v) 3 # 10A SP MCB

TECHNICAL TOWER

891817480.xls Page 12 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
2.1.41 Each UPS DB Distribution Board (L7-UDB-6 Way TPN DB) for Tower specified &
shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4 # 20A SP MCB

2.1.42 Each Power Distribution Board (L7-PDB- 12 Way TPN DB) for Tower specified &
shown on drgs consisting of :
Incomer:
i) 1# 63A TPN MCB
1
Outgoing:
i) 3 # 40A DP RCCB (30mA)
ii) 10*3 # 20A SP MCB

2.1.43 Each Lighting Distribution Board (LDB- 8 Way TPN DB) for Tower specified & shown on
drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 6*3 # 10A SP MCB

2.1.44 Each Emergency Lighting Distribution Board (ELDB- 6 Way TPN DB) for Tower
specified & shown on drgs consisting of :
Incomer:
i) 1# 32A TPN MCB
1
Outgoing:
i) 3 # 25A DP RCCB (30mA)
ii) 4*3 # 10A SP MCB

Total for 2.0 - -


-
3 CABLING -
3.1 Power Cabling -
3.1.1 Unloading ,Receiving, storing, laying heavy duty 1100V grade PVC / XLPE -
insulated sheathed & armoured (unless otherwise specified as flexible) Fire
Retarded Low Smoke Halogen(FRLS-H) cables indoor or outdoor with AL / Cu
conductors as specified and shown on drgs. complete with:
a) Cable clamps on walls,trays, columns, beams, built-up trenches, cable markers
etc. for indoor cables.
b) Earthing the glands armouring etc.
c) Copper cables shall be proposed up to size 16 Sqmm with full neutral cable
Size & above Aluminum cables with 50 % neutral cable size

3.1.1.1 m 3.5 C 300 sqmm XLPE-AL


3.1.1.2 m 3.5 C 240 sqmm XLPE-AL 955
3.1.1.3 m 3.5 C 185 sqmm XLPE-AL
3.1.1.4 m 3.5 C 150 sqmm XLPE-AL 430
3.1.1.5 m 3.5 C 120 sqmm XLPE-AL
3.1.1.6 m 3.5 C 95 sqmm XLPE-AL
3.1.1.7 m 3.5 C 70 sqmm XLPE-AL 175
3.1.1.8 m 3.5 C 50 sqmm XLPE-AL 150
3.1.1.9 m 3.5 C 35 sqmm XLPE-AL
3.1.1.10 m 3.5 C 25 sqmm XLPE-AL 285
3.1.1.11 m 4 C 16 sqmm YRY
3.1.1.12 m 4 C 10 sqmm YRY 325
3.1.1.13 m 4 C 6 sqmm YRY 1760
3.1.1.14 m 4 C 4 sqmm YRY 2160
3.1.1.15 m 4 C 2.5 sqmm YRY

891817480.xls Page 13 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
3.1.1.16 m 3 C 16 sqmm YRY
3.1.1.17 m 3 C 10 sqmm YRY
3.1.1.18 m 3 C 6 sqmm YRY
3.1.1.19 m 3 C 4 sqmm YRY 1000
3.1.1.20 m 3 C 2.5 sqmm YRY

3.2 Cable Termination


3.2.1 Making cable end terminations including brass double compression glands &
crimping type lugs for cable sizes mentioned below of (Glands form part of
Panels / DB's)

Al lugs for Al cables; Cu lugs for Copper Cable & bimetallic lugs for difference in
metal

3.2.1.1 Each 3.5 C 300 sqmm XLPE-AL


3.2.1.2 Each 3.5 C 240 sqmm XLPE-AL 20
3.2.1.3 Each 3.5 C 185 sqmm XLPE-AL
3.2.1.4 Each 3.5 C 150 sqmm XLPE-AL 8
3.2.1.5 Each 3.5 C 120 sqmm XLPE-AL
3.2.1.6 Each 3.5 C 95 sqmm XLPE-AL
3.2.1.7 Each 3.5 C 70 sqmm XLPE-AL 4
3.2.1.8 Each 3.5 C 50 sqmm XLPE-AL 6
3.2.1.9 Each 3.5 C 35 sqmm XLPE-AL
3.2.1.10 Each 3.5 C 25 sqmm XLPE-AL 18
3.2.1.11 Each 4 C 16 sqmm YRY
3.2.1.12 Each 4 C 10 sqmm YRY 14
3.2.1.13 Each 4 C 6 sqmm YRY 104
3.2.1.14 Each 4 C 4 sqmm YRY 134
3.2.1.15 Each 4 C 2.5 sqmm YRY
3.2.1.16 Each 3 C 16 sqmm YRY
3.2.1.17 Each 3 C 10 sqmm YRY
3.2.1.18 Each 3 C 6 sqmm YRY
3.2.1.19 Each 3 C 4 sqmm YRY 64
3.2.1.20 Each 3 C 2.5 sqmm YRY

3.3 Control Cables


Supply and laying of 1100 grade armoured XLPE insulated outer sheathed Fire Retarded
Low Smoke Halogen (FRLS-H) control cables with copper conductors generally as
specified and shown on drgs.

3.3.1 m 3 C x 2.5 Sqmm 50


3.3.2 m 12 C x 2.5 Sqmm 50

Note: All cables are with copper conductors unless specified otherwise.

3.4 Making cable end terminations including brass compression 'glands and crimping type
copper lugs for control cables sizes mentioned below.

3.4.1 Each 3 C x 2.5 Sqmm 4


3.4.2 Each 12 C x 2.5 Sqmm 4

3.5 Cable Trays


3.5.1 Supply, fabrication, installation & painting of GI cable racks / trays with necessary
painted M.S. structural supports in horizontal or vertical formation & single /
multitier formation, icluding bends, Tees etc. and all the required accessories to
complete the job as specified and shown on drawings and as per the details
mentioned in specification.

Note: Till 300 mm wide cable tray shall be 2 mm thikness and above 2.5 mm
thikness as per cable load at actual.

3.5.1.1 m 100 x 40 mm wide - 1 Tier (perforated GI tray) 510


3.5.1.2 m 150 x 40 mm wide - 1 Tier (perforated GI tray) 200
3.5.1.3 m 200 x 40 mm wide - 1 Tier (perforated GI tray)
3.5.1.4 m 300 x 40 mm wide- 1 Tier (perforated GI tray) 480
3.5.1.5 m 450 x 75 mm wide- 1 Tier (ladder GI tray) 70
3.5.1.6 m 500 x 75 mm wide - 1 Tier(ladder GI tray)
3.5.1.7 m 600 x 75 mm wide - 1 Tier (ladder GI tray) 40
3.5.1.8 m 750 x 75 mm wide - 1 Tier(ladder GI tray) 30
3.5.1.9 m 1000 x 75 mm wide - 1 Tier (ladder GI tray) 35

891817480.xls Page 14 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
NOTE:
1) For ladder type trays distance between two rungs shall be 300mm.
2) Double tier trays will be paid as two single tier

3.6 RACEWAYS AND TRUNKING


Supply and installation of single or multi compartment GI raceway of cross section given
below laid in floor including proper binding and grouting to the floor complete as
specified.
a) Raceway
b) All bends, joints, supports, end plates couplers earth conductivity.
3.6.1 m 200 x 50 single compartment (Power)
3.6.2 m 150 x 50 single compartment (Power)
3.6.3 m 100 x 50 single compartment (Power)
3.6.4 m 50 x 50 single compartment (Power) 8

3.7 Supply and installation of single or multi compartment GI junction box of cross section
given below with tile cover, laid in floor or above false ceiling complete as specified

3.7.1 Each 75 x 75 x 50 mm Junction box with removable cover 3


3.7.2 Each 125 x 175 x 50 mm Junction box with removable cover
3.7.3 Each 150 x 175 x 50 mm Junction box with removable cover
3.7.4 Each 250 x 175 x 50 mm Junction box with removable cover

Total for 3.0 ###


-
4.0 CONDUIT WIRING -
4.1 Conduit wiring including conduit for lights, fans, switches, socket outlets as shown
on drgs. & consisting of:
a) Wiring in heavy MS conduits in exposed places and above false ceiling as
specified and using FR HMS PVC conduits only when buried in brick or concrete.
b) 1100V grade FRLS copper wires as specified.
c) Insulated Protective Earthing (PE) as specified and earthing of switch boxes
etc.
d) Wall chasing with finishing
As shown on drgs.

4.1.1 Mtr Primary conduit Wiring using 3 x2.5 Sqmm Cu from DB upto to Switch Board on
the circuit as specified 2000

4.1.2 Mtr Primary conduit Wiring using 3x2.5 Sqmm Cu from DB upto to first light point on
850
the circuit as specified

4.1.3 Mtr Secondary conduit Wiring extending from 4.1.1 and 4.1.2to the various
light,using 3x1.5 Sqmm Cu as specified 8000

4.1.4 Mtr Switch board to switch board conduit Wiring using 3x2.5 Sqmm Cu as specified
900

4.1.5 Mtr Primary conduit Wiring using 3 x 4.0 Sqmm Cu from DB to first point on the
7350
circuit ( Power point) as specified

4.1.6 Mtr Secondary conduit Wiring extending from 4.1.5 to the various power points using
9250
3 x 2.5 Sqmm Cu as specified

4.2 Supply & installation of switches, sockets including mild steel electro galvanised
switch box,face plate etc. complete with earthing.
Note: Standard GI back box with 1.2 mm ( 18 SWG) thikness.
4.2.1 Each 1# 6A Switch similar to Legrand Myrius Series 6730 00 or equivalent to the
80
same series.
4.2.2 Each 2# 6A Switch similar to Legrand Myrius Series 6730 00 or equivalent to the
55
same series.
4.2.3 Each 3# 6A Switch similar to Legrand Myrius Series 6730 00 or equivalent to the
18
same series.
4.2.4 Each 4# 6A Switch similar to Legrand Myrius Series 6730 00 or equivalent to the
1
same series.
4.2.5 Each 5# 6A Switch similar to Legrand Myrius Series 6730 00 or equivalent to the
1
same series.

891817480.xls Page 15 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
4.2.6 Each 1# 6A socket with switch similar to Legrand Myrius Series 6730 44 & 6730 00 or
533
equivalent to the same series.
4.2.6 Each 2# 6A socket with 16A switch similar to Legrand Myrius Series 6730 44 & 6730
163
00 or equivalent to the same series.
4.2.7 Each 1# 6A socket without switch similar to Legrand Myrius Series 6730 44 or
211
equivalent to the same series.
4.2.8 Each 1# 6 / 16A socket & 16A switch similar to Legrand Myrius Series 6730 45 &
236
6730 08 or equivalent to the same series.
4.2.9 Each 1#16A metal clad socket with MCB similar to Legrand Cat No.-507817+ 408656
1
or equivalent to the same series.
4.2.10 Each 1# 6 / 16A socket & 16A switch whether proof similar to Legrand Myrius Series
24
6730 45 & 6730 08 or equivalent to the same series.
4.2.11 Each 1# 25A 3PH socket with MCB (IP65) ###
4.2.12 Each 1# 16A 3PH metal clad socket with MCB for exhaust fan
4.2.13 Each 1# 16A 1PH metal clad socket with MCB for exhaust fan
4.2.13 Each Emergency stop Push Button Station nearby transformer. 2

Total for 4.0

5.0 LIGHT FIXTURES


5.1 Receiving, Storing, installation, testing & commissioning of light fixtures complete
with high efficiency drivers :
a) All fixing accessories mounting bracket/hangging rod/connecting flexible
wires/connectors etc
b) Earthing of fittings
c) UGR values as per IS-3646 Standard.

5.1.1 Each 20W LED wall/recess mounted light fixture Make: Crompton Greaves cat no.-
16
IGP131LT8-20 or equivalent
5.1.2 Each 36W LED surface mounted light fixture Make: PHILIPS -Cat no:- SM134V PSD
120
or equivalent
5.1.3 Each 36W LED mirror optic recess mounted light fixture Make: PHILIPS- Cat
426
no.RC125Bor equivalent
5.1.4 Each 22W LED Recessed Down Light fixture Make: PHILIPS-Cat no:- DN130B D217
221
or equivalent
5.1.5 Each 12W LED Recessed Down Light fixture Make: PHILIPS-Cat no:- DN130B D165
141
or equivalent
5.1.4 Each 26W LED Surface mount Down Light fixture Make: PHILIPS-Cat no:- DN570C or
5
equivalent
5.1.6 Each 1x7W MIRROR LTGHT FIXTURE Make: Crompton Greaves cat no.- LCL-07-CDl
14
or equivalent
5.1.7 Each BULKHEAD CFL LIGHT FIXTURE Make: Crompton Greaves cat no.- LBHP-10-
59
CDL or equivalent
5.1.8 Each 36w/2x20W LED Flame proof surface mounted light fixture.Make: Crompton
19
Greaves cat no.-Fiamma II or equivalent
5.1.8 Each
11W EXIT signage light. 27

5.2 Supply ,installation, testing & commissioning of Landscape/ Facade light fixtures
complete with high efficiency drivers :
a) All fixing accessories mounting bracket/hangging rod/connecting flexible
wires/connectors etc
b) Earthing of fittings
c) UGR values as per IS-3646 Standard.

5.2.1 Each Installation of Upliters


5.2.2 Each Installation of Bollards

5.2.3 RM Installation of LED Strip Lights


5.2.4 Each Color kinematic reachlite intellihue with 20 degree wide beam

5.2.5 Each COLORKINETICS COLORGRAZE INTELLIHUE WITH 9x9 DEG BEAM ANGLE

Total for 5.0

6.0 UPS SYSTEM

891817480.xls Page 16 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
Supply, installation ,testing and commissioning of online UPS System (1+1) Three phase
input & Three phase output, 50 Hz, 415 V in parallel mode meeting the intents of
specifications and the data sheets.The UPS shall be microproccesor based online with
IGBT and automatic static by pass.The UPS system shall be provided with VRLA
batteries with 15 minutes back up for each UPS, and MODBUS/BACNET communication
interface.

6.1 Each 30kVA (1+1), 3phase online UPS with necessary associated works and accessories 1

6.2 Each 180kVA (1+1), 3phase online UPS with necessary associated works and accessories 1

Total for 6.0

7 ISOLATOR
Supply, installation, testing and commissioning of Isolator/ MCB complete with
i) Galvanised & painted steel enclosure to IP43
ii) SC rating 10kA/16kA
iii) Suitable for connecting cables as shown in SLD at incoming & outgoing side.

iv) Set of phase indication lamps


as specified & shown on drgs. GGIAL-MW-ATC-EL-10-GL-002

7.2 Each 1# 25A Three phase Isolator similar to Legrand- 406517 or equivalent to the
2
same series
7.3 Each 1# 32A Three phase Isolator similar to Legrand- 406518 or equivalent to the
30
same series
7.4 Each 1# 40A Three phase Isolator similar to Legrand - 406519 or equivalent to the
9
same series
7.5 Each 1# 63A Three phase Isolator similar to Legrand - 406520 or equivalent to the
same series
7.1 Each 1# 16A DP Isolator similar to Legrand- 406517 or equivalent to the same series
32
(outdoor type)
7.2 Each 1# 25A Three phase Isolator similar to Legrand- 406517 or equivalent to the
3
same series (outdoor type)
7.3 Each 1# 32A Three phase Isolator similar to Legrand- 406518 or equivalent to the
1
same series (outdoor type)
7.4 Each 1# 40A Three phase Isolator similar to Legrand - 406519 or equivalent to the
12
same series (outdoor type)
7.5 Each 1# 63A Three phase Isolator similar to Legrand - 406520 or equivalent to the
11
same series (outdoor type)
7.6 Each 1# 100A Three phase Isolator similar to Legrand- 406522 or equivalent to the
same series
7.7 Each 1# 125A Three phase Isolator similar to Legrand- 406523 or equivalent to the
same series
7.8 Each 1# 160A TPN ISOLATOR
7.9 Each 1# 250A TPN ISOLATOR for UPS
7.10 Each 1# 40A 4P MCB+ELM ( 30-300 mA)
Total for 7.0
8.0 FIRE SAFETY AUXILIARIES

8.1 Each Supply and installation External Hooter in weather proof enclosure at 90dB at 5
mtr free field with necessory accessories.
8.2 m2 Supply and installation of 11KV grade rubber matting, havinig thickness of 6.5mm
2
in front of panels (1200mm wide) as per IS 15652:2006
8.3 m2 Supply and installation of 1100 V grade rubber matting, havinig thickness of
6.5mm in front of panels, battery rack, UPS(1200mm wide) as per IS 15652:2006 14

8.4 Each Supply and installation of First aid box & framed first aid chart in LT panel room
1

8.5 Each Supply and instalaltion of shock treatment chart in LT room 1


8.5.1 Each Supply of 11KV grade gloves pairs 1
8.5.2 Each Supply of 1000V grade gloves pairs 5
8.5.3 Each Supply & installation of 11000V Danger boards 1
8.5.4 Each Supply & Installation of 433V Danger boards 5
8.5.5 Each Supply & Installation of Approved Main Scheme (SLD) from consultant in a proper
lamination in Main LT Room. 1

891817480.xls Page 17 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate

Total for 8.0


9.0 MISCELLANEOUS
9.1 m DWC pipe size 50 mm dia for cable laid in Hardscape & Landscape Area
9.2 m DWC pipe size 75 mm dia for cable laid in Hardscape & Landscape Area
9.3 m DWC pipe size 100 mm dia for cable laid in Hardscape & Landscape Area
9.3 m DWC pipe size 160 mm dia for cable laid in Hardscape & Landscape Area 215
9.4 m Supply & Installation of 25mm dia Rigid FR HMS PVC conduit with accessories
50
including chasing in wall or flooring and finishing
9.5 m Supply & Installation of 32mm dia Rigid FR HMS PVC conduits with accessories
including chasing in wall or flooring and finishing
9.6 m Supply & installation of wiring in Rigid UPVC (HMS) fire retardant conduit as
specified using 3 x 2.5 sqmm Cu, 1100V grade FRLS wires
9.7 m Supply & installation of wiring in Rigid UPVC (HMS) fire retardant conduit as
specified using 3 x 4 sqmm Cu, 1100V grade FRLS wires

9.8 m Supply & laying of 1.5 sqmm Cu, 1100V grade FRLS wires
9.9 m Supply & laying of 2.5 sqmm Cu, 1100V grade FRLS wires
9.10 m Supply & laying of 4.0 sqmm Cu, 1100V grade FRLS wires
9.11 m Supply & Laying of 150mm dia Hume Pipe including necessary fixing accessories
etc. Cost shall include excavation and back filling of soil .NP3 pipe s for road
crossing.
9.12 m Supply & Laying of 200mm dia Hume Pipe including necessary fixing accessories
etc. Cost shall include excavation and back filling of soil ..NP3 pipe s for road
crossing.
9.13 m Supply & Laying of 300mm dia Hume Pipe including necessary fixing accessories 135
etc. Cost shall include excavation and back filling of soil ..NP3 pipe s for road
crossing.
9.14 m Supply & Laying of 450mm dia Hume Pipe including necessary fixing accessories
etc. Cost shall include excavation and back filling of soil ..NP3 pipe s for road
crossing.

Total for 9.0

10.0 LIGHTNING PROTECTION


Vendor to assess the soil report and provide the deisgn to achieve the
desired effective earthing resitance less than 10 ohm.Vendor to provide the
desired calcualtion to the client before execution.

10.1 Nos. Supply of 15 mm dia and 2000 mm length solid aluminium blunt
tip Air termination with Base plate (Vertical air terminal with 12
accessories:Providing of Air terminals as per IS-IEC -62305-3)
10.2 Nos Supply of Concrete Block for mounting vertical AT with all required
12
accessories to withstand high wind load
10.3 Mtrs Supply of 8 mm dia solid Aluminium Conductor for roof top mesh grid meets the
requirement of IS IEC 62305 (As specified in Drawing) and tested as per IEC 640
62561-7
10.4 Nos Supply of Al conductor holding clamp suitabe for mesh grid
conductor ,.Conductor holder @ 1 meter distance to meet the requirement of IS 640
IEC 62305
10.5 Nos Supply of concrete block for fixing Aluminium conductor on Roof Top Mesh with
640
special white cement to mount Conductor without Roof puncturing
10.6 Nos Supply of Straight Splicers for Aluminium Conductor meets the requirement of IS
IEC 62305 (As specified in Drawing) and tested as per IEC 62561-7 320
(Type JISP01 or Equivalent)
10.7 Nos Providing of cross universal connector: For T and cross connection, to route
vertical down conductor /mesh formation meets the requirement of IS IEC 62305
(As specified in Drawing) and tested as per IEC 62561-7 40
( Type JISP02 or Equivalent)
10.8 Nos Supply of expansion piece with connector: For equalising temperature related
length changes. Necessary on conductors length over 20 meters. For round
conductor Rd 8/ALU. meets the requirement of IS IEC 62305 32
(As specified in Drawing) (Type JISP05 or Equivalent)
@ DOWN CONDUCTOR
10.9 Mtrs Supply of 8 mm dia solid Aluminium Conductor for Down Conductor meets the
670
requirement of IS IEC 62305 (As specified in Drawing)

891817480.xls Page 18 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate
10.10 Nos. Supply of Al conductor holding clamp suitabLe for mesh grid
670
conductor ,.Conductor holder @ 1 meter distance to meet the requirement of IS
10.11 Nos. IEC
Supply of fixing type arrangement Special arrangement to connect railing to
Aluminium conductor(If railing is metallic)

10.12 Nos Each down-conductor should be provided with a test link in order to disconnect
the earth termination system for enabling measurements.Test Link to connect 26
8mm Al. conductor with GI Strip

@ RING EARTHING
10.13 Suply of 25x6mm GI strip from AL Conductor to the earth pit station and further
the same strip shall be used for interconnecting all the earth pits below ground
leve Zinc coating: 500 g/m square (Approx :70 micron coating) Should be tested
and use exclusively for lightning protection ,earthing system and ring
equipotential bonding (Type DW1 V). Earthing strip should be calculated inline
Lot with the soil resisitivity and shall meet the desired valve of 10 ohms. Strip size 1
to be designed accordingly and furnish the calcualtion for approval. excavation
of soil and back filling shall be part of the vendor scope

10.14 Supply of conductor holding clamp suitabe for 25 X 6 mm GI strip(Type


Nos 26
JICL08 OR EQUIVALENT)
10.15 Lot Supply of Maintenance Free Earthing system comprising of 17.2 /25 mm dia 3/6
mtr long Earth electrode of low carbon steel electrode with min 100 micron
copper bonding & 1 bag of Carbon based Carbon Based environment friendly
backfill and suitable clamp Eco Friendly rust proof heavy duty weather proof
Polyethylene Earth Pit Chamber with following dimensions :254 mm dia (top),
330 mm dia (bottom) & 260 mm (height). ( Type R01ETHCB02 OR EQUIVALENT)
Earthing rod/strip should be calculated inline with the soil resisitivity and shall
meet the desired valve of 10 ohms. Rod & Strip size to be designed accordingly 1
and furnish the calcualtion for approval.Chemical shall be non
bentonite .excavation of soil and back filling shall be part of the vendor scope

10.16 Nos Supply and installation of Surge protection device with potential free contact to be
installed at main switchboard. Rating Iimp-7.5KA (L-N)& 25 KA (N-PE), Imax- 50
KA -3 Phase - Without Enclosure (Class I+ II) (Make: LEPS Model- DMD3-50 1
MAG/Equivalet)

Total for 10.0


11.0 Earthing
Vendor to assess the soil report and provide the deisgn to achieve the
desired effective earthing resitance less than 1 ohm.Vendor to provide the
desired calcualtion to the client before execution.

Supply & laying GI/Cu earthing strips for interconnecting the earthing stations, panels,
DB's etc. on walls/ceiling, buried in ground, generally as specified, directed & shown on
drawings complete with;
a) Fixing accessories.
11.1 Each b) Corrosion protection of buried conductors with bituminous coating and covered with
PVC tapes.
c) Lugs(Any GI to Al/Cu or Al/Cu to GI connection shall be done using Bimetalic lugs.)
d) Running in cable trays
e) Insulators as required

11.1.1 m 1 x 50 x 6 mm GI 200
11.1.2 m 1 x50 x 4 mm GI
11.1.3 m 1 x 25 x 3 mm GI 1200
11.1.4 m 1 x 25 x 6 mm GI 110
11.1.5 m 6 SWG GI 200
11.1.6 m 8 SWG GI 265
11.1.7 m 1 x 25 x 3 mm Cu
11.1.8 m 1 x 25 x 6 mm Cu
11.1.9 m 1C x 50sqmm Copper insulated cable
11.1.10 m 1C x 70sqmm Copper insulated cable
8 SWG Cu

891817480.xls Page 19 of 20
Qty.
RATE Total
Pay
Item No. Description Total
Unit
Material Labour Unit Amount
Rate

SITC of Maintenance Free Earthing system comprising of 17.2/25 mm dia 3/6 mtr
long Earth electrode of low carbon steel electrode with 250 micron copper
11.1.17 Lot bonding & 1 bag of Carbon based Ecosafe environment friendly backfill and 1
suitable clamp. excavation of soil and back filling shall be part of the vendor
scope including the construction of chamber with heavy grade lid cover.
Note: Vendor to assess the soil report and provide the deisgn to achieve the
desired effective earthing resitance less than 1 ohm.Vendor to provide the
desired calcualtion to the client before execution.Chemical shall be non
bentonite . Including the earth pit chamber

Total for 11.0

891817480.xls Page 20 of 20