HEAT DETECTORS                                                                                                            MIR-600 SERIES
Features
                                                                                         •     Dual Action Rate-of-Rise and Fixed Temperature
                                                                                               Models available
                                                                                         •     One or Two, Normally Open Contacts available
                                                                                         •     Easy Installation
                                                                                         •     Visual indication
                                                                                         •     Operation Testing
                                                                                         •     Complementary, low profile white exterior finish
                                                                                         Installation
                                                                                         Each detector includes a patented reversible mounting
                                                                                         plate. In one position, it easily attaches to 4” junction
                                                                                         box, 3 1/4” octagon box or plaster ring.
                                                                                         In reverse, the plate can be used for open wiring
                                                                                         without a junction box. A 1/4” space between detector
                                                                                         and mounting surface allows for wire connections. All
    Description                                                                          mounting screws are concealed.
    Mircom’s MIR-600 Series Heat Detectors are attractive,                               The detector simply attaches to the mounting plate with
    durable and feature combination rate-of-rise and                                     a push and twist motion. No tools are required. The
    fixed temperature operation. Mircom’s MIR-600 heat                                   mounting plate is molded of white self-extinguishing
    detectors are available in 135°F(57°C) and 200°F (93°C)                              thermoplastic rated at 221°F (105°C). The plate
    temperature ratings. Rate-of-rise detects heat by quickly                            is extremely strong yet adapts to uneven mounting
    responding to a rapid temperature increase. Rate-of-rise                             surfaces.
    units have a wide spacing allowance of 50-foot centers.
    See specification table for details. Fixed temperature                               Mounting Diagram
    reacts to heat by responding to a specific temperature
    setting. Mircom’s MIR-600 Series detectors use the
    same reliable pneumatic rate-of-rise element of former
    models, but offer added aesthetic appeal.
    The pneumatic rate-of-rise element responds to a
    rapid rise in temperature, approximately 15°F (8°C) per
    minute, by expansion of air within the sealed chamber
    faster than it can escape through a calibrated vent. The
    resultant increase in pressure depresses the diaphragm,
    causing the electrical contact to close the circuit. The
    fixed temperature element uses a fusible alloy. When
    activated, the external heat collector drops away to
    provide quick visual confirmation that the element has
    operated. The units protrude only 1-3/8 inch from the
    ceiling surface with a junction box mounting. They have
    pleasing contours and an all-white finish that conforms
    to ceiling aesthetics.
    MIR-600 Testing Methods
    Models 601/621 and 602/622 can be tested by the
    application of quick heat from any convenient source. A
    portable hair dryer is recommended. However, do not
    apply heat that exceeds the fixed temperature rating of
    the detector. Models 603/623 and 604/624 cannot be                                                                                                 MEA
                                                                                                                                                       approved
    tested. However, the fusible alloy element is generally
                                                                                                               S6299         S7498     7270-1477:120   313-97-E
    considered so reliable that testing is not necessary.
                                                                                                                                                                       5110
                                                                                                                       CATALOG NUMBER
                                                             NOT TO BE USED FOR INSTALLATION PURPOSES.
Mircom reserves the right to make changes at any time without notice in prices, colours, materials, components, equipment, specifications and models and also to discontinue models.
Specifications
                                                           Rate-of-Rise
                                           Number                                                        Maximum             ULC
    Model          Identification on                         or Fixed
                                            of N.O.                               Applications            Spacing        Recommended
   Number           Heat Collector                            Type
                                           Contacts                                                      Allowance         Coverage
                                                            Detector
                                                            Rate-of-Rise                                   50 ft.
                                                                                                                         2,500ft² (232m²)
  MIR-601                                       1            and Fixed          Normal temperature        (15.2m)
                                                                                                                           See Note A
                                                            Temperature       fluctuations and ceiling   See Note B
                                                                                 temperatures not          50 ft.
                                                            135°F (57°C)     exceeding 100°F (38°C)                      2,500ft² (232m²)
  MIR-621                                       2                                                         (15.2m)
                                                                                                                           See Note A
                         None                                                                            See Note B
                                                                                                           50 ft.
                                                            Rate-of-Rise        Normal temperature                       2,500ft² (232m²)
  MIR-602                                       1                                                         (15.2m)
                                                                                                                           See Note A
                                                             and Fixed        fluctuations and ceiling   See Note B
                                                            Temperature           temperatures not
                                                                             exceeding 100°F (38°C)        50 ft.
                                                                                                                         2,500ft² (232m²)
  MIR-622                                       2           200°F (94°C)        but not 150°F (66°C)      (15.2m)
                                                                                                                           See Note A
                       Grey Ring                                                                         See Note B
                                                               Fixed             Unusually violent       25 ft. (7.6m)   625ft² (57.8m²)
  MIR-603                                       1                                                        See Note B       See Note A
                                                            Temperature      temperature fluctuations
                                                               Only          and ceiling temperatures
                                                                               not exceeding 100°F       25 ft. (7.6m)   625ft² (57.8m²)
  MIR-623                                       2           135°F (57°C)               (38°C)            See Note B       See Note A
                       Grey Spot
                                                                                 Unusually violent       25 ft. (7.6m)   625ft² (57.8m²)
  MIR-604                                       1              Fixed
                                                                             temperature fluctuations    See Note B       See Note A
                                                            Temperature
                                                                             and ceiling temperatures
                                                               Only
                                                                               not exceeding 100°F
                                                                               (38°C) but not 150°F      25 ft. (7.6m)   625ft² (57.8m²)
  MIR-624                                       2           200°F (94°C)                                 See Note B       See Note A
                   Grey Spot & Ring                                                    (66°C)
NOTE A                                                                     ELECTRICAL RATINGS:
Maximum detector coverage has been determined by ULC to provide                   3.0 Amp. @ 6-125 VAC
detection time equal to sprinkler devices at 10 ft. (3m) intervals on a           1.0 Amp. @ 6-28 VDC
smooth ceiling 15 ft. 9in. (4.8m) high. Higher ceilings can adversely             0.3 Amp. @ 125 VDC
affect detection time. In some instances, earlier detection time may be           1.0 Amp @ 25 VDC
obtained by reducing the spacing between the detectors. Refer to the
latest edition of CAN/ULC-S524, Standard for the Installation of Fire      Screw Terminals
Systems, section heat detectors.
NOTE B
FM rates this detector at 30 ft. (9.14m) spacing. This is the maximum
FM rating available.
NOTE C
Maximum distance shown is from any wall partition or ceiling projection
extending down more than 122 inches (305mm)
The coverage and spacing figures given here are intended as a guide
only. Heat detectors must be spaced and installed as per the specific
requirements outlined in the ULC codes as well as all other applicable
national and local code requirements.
IMPORTANT SPECIAL NOTES
Application:
Heat detectors should be used for property protection. Reliance should
not be solely placed on heat detectors for life safety. When Life Safety
is involved smoke detectors MUST also be used. Detectors must not
ne painted.
Battery Back Up:
Heat detectors should be electronically supervised with battery back-
up at the panel.
                                                    NOT TO BE USED FOR INSTALLATION PURPOSES.
                                                                                  Distributed by:
     Canada                               U.S.A.
     25 Interchange Way                   60 Industrial Parkway, PMB 278
     Vaughan, Ontario L4K 5W3             Cheektowaga, New York 14227
     Telephone: (905) 660-4655            Toll Free: (888) 660-4655
     Fax: (905) 660-4113                  Fax Toll Free: (888) 660-4113
     Web page: http://www.mircom.com        Email: [email protected]                                                                  CAT. 5110
                                                                                                                                        Rev. 4