Product data sheet
Specifications
Variable Speed Drive, Altivar
Process ATV900, ATV930, 110kW,
400 to 480V, without braking unit,
IP00
ATV930C11N4C
Product availability: Non-Stock - Not normally stocked in
distribution facility
Main
Range of Product Altivar Process ATV900
Device Application Industrial Application
Disclaimer: This documentation is not intended as a substitute for and is not to be used for determining suitability or reliability of these products for specific user applications
Product or Component Type Variable speed drive
Product destination Synchronous motors
Asynchronous motors
Product Specific Application Process for industrial
Variant Standard version
Without braking chopper
Phase 3 phase
Mounting Mode Wall mount
Communication Port Protocol EtherNet/IP
Modbus serial
Modbus TCP
[Us] rated supply voltage 380...480 V - 15...10 %
Continuous output current 211 A 2.5 kHz normal duty
173 A 2.5 kHz heavy duty
EMC filter Integrated
With EMC plate option
IP degree of protection IP21
Degree of protection UL type 1
option module Slot A communication module Profibus DP V1
Slot A communication module PROFINET
Slot A communication module DeviceNet
Slot A communication module EtherCAT
Slot A communication module CANopen daisy chain RJ45
Slot A communication module CANopen SUB-D 9
Slot A communication module CANopen screw terminals
Slot A/slot B/slot C digital and analog I/O extension module
Slot A/slot B/slot C output relay extension module
Slot B 5/12 V digital encoder interface module
Slot B analog encoder interface module
Slot B resolver encoder interface module
communication module Ethernet Powerlink
Discrete input logic 16 preset speeds
Motor power kW 110.0 kW normal duty
90.0 kW heavy duty
Asynchronous motor control Constant torque standard
profile Optimized torque mode
Variable torque standard
Synchronous motor control profile Permanent magnet motor
Synchronous reluctance motor
Price is “List Price” and may be subject to a trade discount – check with your local distributor or retailer for actual price.
May 28, 2025 1
Maximum output frequency 599 Hz
Switching frequency 1...8 kHz adjustable
2.5...8 kHz with derating factor
Nominal switching frequency 2.5 kHz
Line current 201.0 A 380 V normal duty)
170.0 A 380 V heavy duty)
165.0 A 480 V normal duty)
143.0 A 480 V heavy duty)
Apparent power 121.8 kVA 480 V normal duty)
102.6 kVA 480 V heavy duty)
Maximum transient current 253 A 60 s normal duty)
259.5 A 60 s heavy duty)
Network Frequency 50-60 Hz
Prospective line Isc 50 kA
Complementary
Discrete input number 10
Discrete input type DI1...DI8 programmable, 24 V DC <= 30 V)3.5 kOhm
DI7, DI8 programmable as pulse input 0…30 kHz, 24 V DC <= 30 V)
STOA, STOB safe torque off, 24 V DC <= 30 V)> 2.2 kOhm
Discrete output number 2
Discrete output type Logic output DQ+ 0…1 kHz <= 30 V DC 100 mA
Programmable as pulse output DQ+ 0…30 kHz <= 30 V DC 20 mA
Logic output DQ- 0…1 kHz <= 30 V DC 100 mA
Analogue input number 3
Analogue input type AI1, AI2, AI3 software-configurable voltage 0...10 V DC 30 kOhm 12 bits
AI1, AI2, AI3 software-configurable current 0...20 mA/4...20 mA 250 Ohm 12 bits
Analogue output number 2
Analogue output type Software-configurable voltage AQ1, AQ2 0...10 V DC 470 Ohm 10 bits
Software-configurable current AQ1, AQ2 0...20 mA 500 Ohm 10 bits
Relay output number 3
Relay output type Configurable relay logic R1 fault relay NO/NC 100000 cycles
Configurable relay logic R2 sequence relay NO 1000000 cycles
Configurable relay logic R3 sequence relay NO 1000000 cycles
Maximum switching current Relay output R1 resistive, cos phi = 1 3 A 250 V AC
Relay output R1 resistive, cos phi = 1 3 A 30 V DC
Relay output R1 inductive, cos phi = 0.4 7 ms 2 A 250 V AC
Relay output R1 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
Relay output R2, R3 resistive, cos phi = 1 5 A 250 V AC
Relay output R2, R3 resistive, cos phi = 1 5 A 30 V DC
Relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 250 V AC
Relay output R2, R3 inductive, cos phi = 0.4 7 ms 2 A 30 V DC
Minimum switching current Relay output R1, R2, R3 5 mA 24 V DC
Physical interface Ethernet
2-wire RS 485
Connector Type 2 RJ45
1 RJ45
Method of access Slave Modbus TCP
Transmission Rate 10, 100 Mbits
4.8 kbps
9600 bit/s
19200 bit/s
Transmission frame RTU
Number of addresses 1…247
2 May 28, 2025
Data format 8 bits, configurable odd, even or no parity
Type of polarization No impedance
4 quadrant operation possible False
Acceleration and deceleration Linear adjustable separately from 0.01...9999 s
ramps
Motor slip compensation Not available in permanent magnet motor law
Automatic whatever the load
Adjustable
Can be suppressed
Braking to standstill By DC injection
Brake chopper integrated False
Maximum Input Current per Phase 201.0 A
Maximum output voltage 480.0 V
Relative symmetric network 5%
frequency tolerance
Base load current at high 173.0 A
overload
Base load current at low overload 211.0 A
Power dissipation in W Forced convection 2511 W 380 V 2.5 kHz
Natural convection 309 W 380 V 2.5 kHz
With safety function Safely True
Limited Speed (SLS)
With safety function Safe brake True
management (SBC/SBT)
With safety function Safe False
Operating Stop (SOS)
With safety function Safe Position False
(SP)
With safety function Safe False
programmable logic
With safety function Safe Speed False
Monitor (SSM)
With safety function Safe Stop 1 True
(SS1)
With sft fct Safe Stop 2 (SS2) False
With safety function Safe torque True
off (STO)
With safety function Safely False
Limited Position (SLP)
With safety function Safe False
Direction (SDI)
Protection type Thermal protection motor
Safe torque off motor
Motor phase break motor
Thermal protection drive
Safe torque off drive
Overheating drive
Overcurrent between output phases and earth drive
Overload of output voltage drive
Short-circuit protection drive
Motor phase break drive
Overvoltages on the DC bus drive
Line supply overvoltage drive
Line supply undervoltage drive
Line supply phase loss drive
Overspeed drive
Break on the control circuit drive
Quantity per Set 1
Width 12.6 in (320 mm)
Height 33.5 in (852 mm)
Depth 15.5 in (393 mm)
May 28, 2025 3
Net Weight 180.8 lb(US) (82 kg)
Electrical connection Control screw terminal 0.5...1.5 mm² AWG 20...AWG 16
Line side screw terminal 2 x 50...3 x 120 mm² AWG 1/0...300 kcmil
Motor screw terminal 2 x 50...3 x 120 mm² AWG 1/0...300 kcmil
DC bus screw terminal 2 x 50...3 x 120 mm² AWG 1/0...300 kcmil
Transmission Rate 10/100 Mbit/s Ethernet IP/Modbus TCP
4.8, 9.6, 19.2, 38.4 kbit/s Modbus serial
Exchange mode Half duplex, full duplex, autonegotiation Ethernet IP/Modbus TCP
Data format 8 bits, configurable odd, even or no parity Modbus serial
Type of polarization No impedance Modbus serial
Number of addresses 1…247 Modbus serial
Supply External supply for digital inputs 24 V DC 19…30 V), <1.25 mA overload and short-
circuit protection
Internal supply for reference potentiometer (1 to 10 kOhm) 10.5 V DC +/- 5 %, <10
mA overload and short-circuit protection
Internal supply for digital inputs and STO 24 V DC 21…27 V), <200 mA overload and
short-circuit protection
Local signalling Local diagnostic 3 LED mono/dual colour)
Embedded communication status 5 LED dual colour)
Communication module status 2 LED dual colour)
Presence of voltage 1 LED red)
Input compatibility DI1...DI8 discrete input level 1 PLC IEC 61131-2
DI7, DI8 pulse input level 1 PLC IEC 65A-68
STOA, STOB discrete input level 1 PLC IEC 61131-2
Discrete input logic Positive logic (source) DI1...DI8), < 5 V, > 11 V
Negative logic (sink) DI1...DI8), > 16 V, < 10 V
Positive logic (source) DI7, DI8), < 0.6 V, > 2.5 V
Positive logic (source) STOA, STOB), < 5 V, > 11 V
Sampling duration 2 ms +/- 0.5 ms DI1...DI8) - discrete input
5 ms +/- 1 ms DI7, DI8) - pulse input
1 ms +/- 1 ms AI1, AI2, AI3) - analog input
5 ms +/- 1 ms AQ1, AQ2) - analog output
Accuracy +/- 0.6 % AI1, AI2, AI3 for a temperature variation 60 °C analog input
+/- 1 % AQ1, AQ2 for a temperature variation 60 °C analog output
Linearity error AI1, AI2, AI3 +/- 0.15 % of maximum value analog input
AQ1, AQ2 +/- 0.2 % analog output
Refresh time Relay output R1, R2, R3)5 ms +/- 0.5 ms)
Isolation Between power and control terminals
Environment
Operating altitude <= 3280.84 ft (1000 m) without derating
1000...4800 m with current derating 1 % per 100 m
Operating position Vertical +/- 10 degree
Product Certifications UL
CSA
TÜV
Marking CE
Standards UL 508C
IEC 61800-3
IEC 61800-5-1
IEC 61000-3-12
IEC 60721-3
IEC 61508
IEC 13849-1
Maximum THDI <48 % full load IEC 61000-3-12
Assembly style Enclosed
4 May 28, 2025
Electromagnetic compatibility Electrostatic discharge immunity test level 3 conforming to IEC 61000-4-2
Radiated radio-frequency electromagnetic field immunity test level 3 conforming to
IEC 61000-4-3
Electrical fast transient/burst immunity test level 4 conforming to IEC 61000-4-4
1.2/50 µs - 8/20 µs surge immunity test level 3 conforming to IEC 61000-4-5
Conducted radio-frequency immunity test level 3 conforming to IEC 61000-4-6
Environmental class (during Class 3C3 according to IEC 60721-3-3
operation) Class 3S3 according to IEC 60721-3-3
Maximum acceleration under 150 m/s² at 11 ms
shock impact (during operation)
Maximum acceleration under 10 m/s² at 13...200 Hz
vibrational stress (during
operation)
Maximum deflection under 1.5 mm at 2...13 Hz
vibratory load (during operation)
Permitted relative humidity Class 3K5 according to EN 60721-3
(during operation)
Volume of cooling air 158506.07 Gal/hr(US) (600 m3/h)
Overvoltage category III
Regulation loop Adjustable PID regulator
Insulation resistance > 1 MOhm 500 V DC for 1 minute to earth
Noise level 69.9 dB 86/188/EEC
Vibration resistance 1.5 mm peak to peak (f= 2…13 Hz) conforming to IEC 60068-2-6
1 gn (f= 13…200 Hz) conforming to IEC 60068-2-6
Shock resistance 15 gn 11 ms IEC 60068-2-27
Environmental characteristic Chemical pollution resistance class 3C3 IEC 60721-3-3
Dust pollution resistance class 3S3 IEC 60721-3-3
Relative humidity 5…95 % without condensation IEC 60068-2-3
Ambient air temperature for 5…122 °F (-15…50 °C) (without derating)
operation 122…140 °F (50…60 °C) (with derating factor)
Noise level 69.9 dB
pollution degree 2
Ambient air transport -40…158 °F (-40…70 °C)
temperature
Ambient Air Temperature for -40…158 °F (-40…70 °C)
Storage
Ordering and shipping details
Category US1CP4E22277
Discount Schedule CP4E
GTIN 3606480883453
Returnability No
Country of origin IN
Packing Units
Unit Type of Package 1 PCE
Number of Units in Package 1 1
Package 1 Height 25.59 in (65.000 cm)
Package 1 Width 18.70 in (47.500 cm)
Package 1 Length 40.55 in (103.000 cm)
Package 1 Weight 168.433 lb(US) (76.400 kg)
May 28, 2025 5
Compliance
Compliance TAA
BABA
BAA via COTS
6 May 28, 2025
Environmental Data
Schneider Electric aims to achieve Net Zero status by 2050 through supply chain partnerships, lower impact materials, and circularity
via our ongoing “Use Better, Use Longer, Use Again” campaign to extend product lifetimes and recyclability.
Environmental Data explained
How we assess product sustainability
Environmental footprint
Carbon footprint (kg CO2 eq, Total Life cycle) 80649
Environmental Disclosure Product Environmental Profile
Use Better
Materials and Substances
Packaging made with recycled cardboard Yes
Packaging without single use plastic No
Pro-active compliance (Product out of EU RoHS legal
EU RoHS Directive
scope)
SCIP Number 3a1ae1b7-96ff-4a20-9804-40393f13630f
REACh Regulation REACh Declaration
WARNING: This product can expose you to chemicals
including: Lead and lead compounds, which is known to
California proposition 65 the State of California to cause cancer and birth defects
or other reproductive harm. For more information go to
www.P65Warnings.ca.gov
Energy efficiency
Product contributes to saved and avoided emissions Yes
Use Again
Repack and remanufacture
Circularity Profile End of Life Information
Take-back No
The product must be disposed on European Union
WEEE markets following specific waste collection and never end
up in rubbish bins.
May 28, 2025 7
Product data sheet ATV930C11N4C
Dimensions Drawings
Dimensions
Right and Front View
8 May 28, 2025
Product data sheet ATV930C11N4C
May 28, 2025 9
Product data sheet ATV930C11N4C
Drives with Lower Conduit Box Sold Separately
Rear, Front and Left View
10 May 28, 2025
Product data sheet ATV930C11N4C
May 28, 2025 11
Product data sheet ATV930C11N4C
12 May 28, 2025
Product data sheet ATV930C11N4C
Mounting and Clearance
Clearances
X1 X2 X3
≥ 250 mm (10 in.) ≥ 250 mm (10 in.) ≥ 100 mm (3.94 in.)
• Mount the device in a vertical position (±10°). This is required for cooling the device.
• Do not mount the device close to heat sources.
• Leave sufficient free space so that the air required for cooling purposes can circulate from the bottom to the
top of the drive.
May 28, 2025 13
Product data sheet ATV930C11N4C
Mounting Types
Mounting Type A: Individual IP21
a ≥ = 110 mm (4.33 in.)
Mounting Type B: Side by Side IP20 , Only possible at ambient temperature lower than 40
°C (104 °F)
Mounting Type C: Individual IP20
14 May 28, 2025
Product data sheet ATV930C11N4C
a ≥ = 110 mm (4.33 in.)
May 28, 2025 15
Product data sheet ATV930C11N4C
Connections and Schema
Three-Phase Power Supply with Upstream Breaking via Line Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping
category 0 in accordance with standard IEC/EN 60204-1
(1) Line choke if used
(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 : Line Contactor
Q2, Q3 : Circuit breakers
S1, S2 : Pushbuttons
T1 : Transformer for control part
16 May 28, 2025
Product data sheet ATV930C11N4C
Three-Phase Power Supply with Downstream Breaking via Contactor
Connection diagrams conforming to standards EN 954-1 category 1 and IEC/EN 61508 capacity SIL1, stopping
category 0 in accordance with standard IEC/EN 60204-1
(1) Line choke if used
(2) Use relay R1 set to operating state Fault to switch Off the product once an error is detected.
A1 : Drive
KM1 : Contactor
May 28, 2025 17
Product data sheet ATV930C11N4C
Control Block Wiring Diagram
(1) Safe Torque Off
(2) Analog Output
(3) Digital Input
(4) Reference potentiometer
(5) Analog Input
(6) Digital Output
(7) 0-10 Vdc, x-20 mA
(8) 0-10 Vdc, -10 Vdc...+10 Vdc
R1A, R1B, R1C : Fault relay
R2A, R2C : Sequence relay
R3A, R3C : Sequence relay
Sensor Connection
It is possible to connect either 1 or 3 sensors on terminals AI1 or AI3
18 May 28, 2025
Product data sheet ATV930C11N4C
Sink / Source Switch Configuration
The switch is used to adapt the operation of the logic inputs to the technology of the programmable controller outputs.
• Set the switch to Source (factory setting) if using PLC outputs with PNP transistors.
• Set the switch to Ext if using PLC outputs with NPN transistors.
Switch Set to SRC (Source) Position Using the Output Power Supply for the Digital Inputs
Switch Set to SRC (Source) Position and Use of an External Power Supply for the DIs
Switch Set to SK (Sink) Position Using the Output Power Supply for the Digital Inputs
Switch Set to EXT Position Using an External Power Supply for the DIs
May 28, 2025 19
Product data sheet ATV930C11N4C
Performance Curves
Derating Curves
40 °C (104 °F) - Mounting type A, B and C
50 °C (122 °F) - Mounting type A and C
60 °C (140 °F) - Mounting type C
In : Nominal Drive Current
SF : Switching Frequency