PRO WTG1 SS ED ELE 001 - R4 - PSLD - 220 33kV - PSS - WTG1 - 18 03 2025 PSLD - A0
PRO WTG1 SS ED ELE 001 - R4 - PSLD - 220 33kV - PSS - WTG1 - 18 03 2025 PSLD - A0
L L
M
P1 14 51 IDMT. OVER CURRENT RELAY 600/1-1-1-1-1A 12 Nos.
202-PCT P2 220kV BUSBAR RP 50kA/1Sec 5 CORE (FOR PROTECTION)
600/1-1-1-1-1A 15 50N 02
INSTANTANEOUS EARTH FAULT RELAY 245kV, 1Ph METERING CURRENT TRANSFORMER
CORE-5 87
BB
50
LBB
TO SCADA
600/1A 203-PCT 16 51N 400-200/1-1A, 50kA/1Sec (TRAFO-1 BAY) 03 Nos.
600/1-1-1-1-1A IDMT. EARTH FAULT RELAY
CLASS: PS 220kV BUSBAR RP 600-400/1-1A, 50kA/1Sec (TRAFO-2 BAY)
PMU TO PPC P2 03 Nos.
CORE-4 CORE-5 17 87T DIFFERENTIAL PROTECTION RELAY (TRANSFORMER) 600/1-1A, 50kA/1Sec (LINE BAY) 03 Nos.
600/1A 220kV LINE CRP 600/1A
87
BB
50
LBB
TO SCADA
J CLASS: 0.2s,10VA
R4
CLASS: PS 18 86 LOCKOUT RELAY CAPACITOR VOLTAGE TRANSFORMER FOR LINE BAY & BUS J
CORE-3 BCU TVM 80 80 86 95 95
19 94 ANTIPUMPING RELAY 03 220kV/110V/110V/110V , 4400pF 09 Nos.
AC DC 1 2 CORE-4 220kV BUS COUPLER CRP 3 3 3 3
600/1A TO SCADA 600/1A
CLASS: 0.2s, 20VA MAIN-2 CLASS: PS 20 96 BUSBAR TRIP LOCKOUT RELAY
80 80
AC DC ELECTROMAGNETIC VOLTAGE TRANSFORMER FOR
21-2 87L 50 50N 51 51N 25 DR
CORE-2 SOTF 21 64R RESTRICTED EARTH FAULT PROTECTION RELAY HV SIDE LINE BAY & TRAFO 1 & 2 BAYS
CORE-3 FROM SELECTED HV 04 09 Nos.
600/1A 81 81 67 67N 85 27 59 FL
STUB
BUS CVT TO 220kV / 110V / 110V
CLASS: PS O U R4 600/1A CLASS: BCU TVM 22 64R RESTRICTED EARTH FAULT PROTECTION RELAY LV SIDE
0.2s, 20VA SCADA LV 3 3 3
MAIN-1
SEF
CORE-1 23 HV HV SIDE STANDBY EARTH FAULT PROTECTION RELAY
21-1 87L 50 50N 51 51N 25 DR SOTF
(TWIN MOOSE AL59) CORE-2 05 M
245kV, 1600A, 50kA FOR 1Sec,1Ph OUTDOOR TYPE 04 Set.
600/1A SEF SF6 CIRCUIT BREAKER ALONG WITH SUPPORT INSULATOR
CLASS: PS
81
O
81
U
67 67N 85 27 59 FL STUB 600/1A 24 LV LV SIDE STANDBY EARTH FAULT PROTECTION RELAY
CLASS: PS
P1 25 24 VOLTS PER HERTZ RELAY 245kV, 1250A, 50kA FOR 1Sec, 3Ph HORIZONTAL DOUBLE
202-89DE2 06 M BREAK ISOLATOR, MECHANICALLY GANGED MOTOR 09 Set.
202-89D CORE-1 26 MOG MAGNETIC OIL GAUGE
1 TO BUS 50 50N 51 51N OPERATED ISOLATOR WITHOUT EARTH SWITCH
BUS-1 CVT-A METERING ISOLATOR HDB 600/1A TO SCADA
VOLTAGE WITH 2 E/S M
CLASS: PS 25 86 95 27 49 THERMAL RELAY
220kV / 110V / 110V / 110V PROTECTION 202-89T 245kV, 1250A, 50kA FOR 1Sec, 3Ph HORIZONTAL DOUBLE
2 SELECTION 245kV, 1250A P1
√3 √3 √3 √3 PROTECTION BYPASS ISO (U.H) 50kA, 1SEC. 28 DR DISTURBANCE RECORDER 07 BREAK ISOLATOR, MECHANICALLY GANGED MOTOR 02 Set.
3 SCHEME M M
CORE-1: CLASS:0.2, 50VA 245kV, 1250A 201-89DE1 202-52 OPERATED ISOLATOR WITH EARTH SWITCH
CORE-2: CLASS:3P, 50VA 50kA, 1SEC. M
SF6 CB 29 63 FIRE PROTECTION TRIP
202-89CE2 245kV, 1600A, 203-89AE2 203-89BE2 245kV, 1600A, 50kA FOR 1Sec, 3Ph HORIZONTAL DOUBLE
I CORE-3: CLASS:3P, 50VA 50kA, 1SEC. 30 95 TRIP CIRCUIT SUPERVISION RELAY I
202-89C 203-89A 203-89B 08 BREAK ISOLATOR, MECHANICALLY GANGED MOTOR 02 Set.
BUS-1 89AE ISOLATOR HDB ISOLATOR (HDB) ISOLATOR (HDB) DC SUPPLY SUPERVISION RELAY OPERATED ISOLATOR WITH 2 EARTH SWITCH
31 80DC
BUS-1 89A R4
WITH 2 E/S M
WITH 2 E/S M WITH 2 E/S M M
(SINGLE MOOSE AL59) 245kV, 1250A 245kV, 1600A, R4
245kV, 1600A, 245kV, 1250A, 50kA FOR 1Sec, 3Ph HORIZONTAL DOUBLE
R4 ISOLATOR M 32 80AC AC SUPPLY SUPERVISION RELAY
245kV, 1250A 50kA, 1SEC. 50kA, 1SEC. 50kA, 1SEC. BREAK ISOLATOR, MECHANICALLY GANGED MOTOR 06 Set.
4" IPS TUBE(SCH-80) 202-89CE1 203-89AE1 203-89BE1 OPERATED ISOLATOR WITH 2 EARTH SWITCH
50kA, 1SEC. 33 25 SYNCHRONIZING OR SYNCHRONISM CHECK DEVICE
220kV MAIN BUS-I, 1600A, 50kA FOR 1SEC. (FOR B-PHASE ONLY) 220kV MAIN BUS-I, 1600A, 50kA FOR 1SEC.
(3" Al. IPS TUBE (SCH-80)) (3" IPS TUBE(SCH-80)) 204-89A (3" Al. IPS TUBE (SCH-80)) 60 FL FUSE FAILURE RELAY WAVE TRAP 1600A,0.5mH 50kA FOR 1Sec.
201-89A 202-89A 34
FOR ONLY R-PHASE ISOLATOR 09 02 Nos.
ISOLATOR ISOLATOR 35
M
245kV, 1250A M M 245kV, 1250A FL FAULT LOCATOR
245kV, 1250A,
50kA, 1SEC. 50kA, 1SEC. 50kA, 1SEC. 220/33kV,POWER TRANSFORMER 110/140MVA ONAN/ONAF,
36 STUB OVER CURRENT RELAY 01 No.
YNyn0, Z=15%
201-89B 202-89B 204-89B 10
37 85 CARRIER (OR) PILOT WIRE RELAY
R4 ISOLATOR M ISOLATOR M ISOLATOR M
245kV, 1250A 3" IPS TUBE(SCH-80) 245kV, 1250A, 245kV, 1250A METERS:-
220/33kV,POWER TRANSFORMER 50/60MVA ONAN/ONAF,
50kA, 1SEC. 50kA, 1SEC. YNyn0, Z=15% 01 No.
H 220kV MAIN BUS-II, 1600A, 50kA FOR 1SEC. 50kA, 1SEC. 220kV MAIN BUS-II, 1600A, 50kA FOR 1SEC.
SI.NO LEGEND DESCRIPTION
(3" Al. IPS TUBE (SCH-80)) 201-89CE1 BUS-2 89A 4" IPS TUBE(SCH-80) (3" Al. IPS TUBE (SCH-80)) BILL OF QUANTITY FOR 33kV SIDE
201-89C ISOLATOR (3" IPS TUBE(SCH-80)) ISOLATOR (FOR R-PHASE ONLY) 1 BCU BAY CONTROL UNIT
M R4 204-89CE1, EARTH SWITCH (3" IPS TUBE(SCH-80)) S.NO. SYMBOLS DESCRIPTION QTY
HDB WITH 2 E/S 245kV, 1250A 204-89C ISOLATOR 2 PQM POWER QUALITY ANALYZER 1 30kV,10kA CLASS - III LIGHTNING ARRESTOR 51 No's
245kV, 1250A, 50kA, 1SEC. HDB WITH 2 E/S
50kA/1SEC, BUS-2 89AE 245kV, 1250A 50kA, 1SEC. 3 PMU PHASOR MEASUREMENT UNIT 33kV VACCUM CIRCUIT BREAKER 800A, 25/kA FOR 3 SEC 9 Sets
M
204-89CE2, EARTH SWITCH M H
201-89CE2, 2 33kV VACCUM CIRCUIT BREAKER 1250A, 25/kA FOR 3 SEC 5 Sets
BUS-2 CVT-B 4 TVM TRIVECTOR METER
201-52 201-89T 33kV VACCUM CIRCUIT BREAKER 3150A, 25/kA FOR 3 SEC 2 Sets
SF6 CB 220kV / 110V / 110V / 110V 5 ABT AVAILABILITY BASED TARIFF METER
BYPASS ISO (U.H) TO BUS 204-52 204-89T
245kV, 1600A, √3 √3 √3 √3 1 SF6 CB BYPASS ISO (U.H) 33kV CURRENT TRANSFORMER 600/1-1-1A, 25kA FOR 3Sec 27 No'S
M
245kV, 1250A METERING
50kA, 1SEC. M
CORE-1: CLASS:0.2, 50VA VOLTAGE 245kV, 1600A,
M
245kV, 1250A LEGENDS:- 33kV CURRENT TRANSFORMER 3000/1-1-1A, 25kA FOR 3Sec
50kA, 1SEC. PROTECTION M 3 No'S
201-89DE1 CORE-2: CLASS:3P, 50VA 2 SELECTION 50kA, 1SEC. 50kA, 1SEC. SYMB COLOR DESCRIPTION 3
201-89D CORE-3: CLASS:3P, 50VA PROTECTION 33kV CURRENT TRANSFORMER 3000/1-1-1-1-1A, 25kA FOR 3Sec 3 No'S
3 SCHEME 204-89DE1 H1 RED R-PHASE
ISOLATOR HDB 204-89D 33kV CURRENT TRANSFORMER 1200/1-1-1-1-1A, 25kA FOR 3Sec 3 No'S
WITH 2 E/S (SINGLE MOOSE AL59) (SINGLE MOOSE AL59) H2 YELLOW Y-PHASE
ISOLATOR HDB 33kV CURRENT TRANSFORMER 1200/1-1-1A, 25kA FOR 3Sec 12 No'S
245kV, 1250A M WITH 2 E/S H3 BLUE B-PHASE
50kA, 1SEC. 245kV, 1250A
M
33kV METERING CURRENT TRANSFORMER 3000/1-1A, 25kA FOR 3Sec 03 No'S
201-89DE2 50kA, 1SEC. H4 GREEN VCB ON INDICATION
204-89DE2 H5 RED VCB OFF INDICATION 4 STATION TRANSFORMER 33/0.415kV,250kVA 2 No'S
201-EMVT
220kV / 110V / 110V 1 204-EMVT H6 AMBER VCB TRIP INDICATION 33kV, 400A, 25kA FOR 3 SEC. ISOLATOR WITHOUT E/S (MANUAL)
220kV / 110V / 110V 1 4 Sets
G √3 √3 √3
√3 √3 √3
H7 BLUE SPRING CHARGING INDICATION
5
CORE 1: 0.2, 20VA 2 H8 WHITE TRIP CIRCUIT HEALTHY 33kV, 3150A, 25kA FOR 3 SEC. ISOLATOR WITHOUT E/S (MANUAL) 2 Sets
CORE 2: 0.2, 20VA CORE 1: 0.2, 20VA 2
CORE 2: 0.2, 20VA H9 RED DC SUPPLY FAIL 33kV / 110V / 110V / 110V
201-MCT P2 36kV BUS PT 3 3 3 3 6 No'S
204-MCT H10 RED BREAKER IN TEST
600-400/1-1A 400-200/1-1A P2 6
CORE-2 ABT BZ BUZZER 33kV / 110V / 110V
CLASS: 0.2s, 10VA CHECK CORE-2 ABT 36kV MPT 3 No'S
CLASS: 0.2s, 10VA CHECK L/R LOCAL/REMOTE SELECTOR SWITCH 3 3 3 G
CORE-1 ABT R4
CLASS: 0.2s, 10VA MAIN ABT TNC TRIP/NEUTRAL/CLOSE
CORE-1
P1 CLASS: 0.2s, 10VA MAIN BCS BREAKER CONTROL SWITCH 33kV, 3150A, 25kA FOR 3 SEC. ISOLATOR WITH ONE EARTH SWITCH (MANUAL) 1 Set
201-PCT P1
EM EM. STOP PUSH BUTTON
600/1-1-1-1-1A P2 220kV BUSBAR RP 204-PCT 7 33kV, 1250A, 25kA FOR 3 SEC. ISOLATOR WITH ONE EARTH SWITCH (MANUAL) 9 Sets
CORE-5 600/1-1-1-1-1A 220kV BUSBAR RP
P2 220kV CT (LINE BAY, TRAFO BAY - 1 & TRAFO BAY-2)
600/1A 87
BB
50
LBB
TO SCADA CORE-5 33kV, 800A, 25kA FOR 3 SEC. ISOLATOR WITH ONE EARTH SWITCH (MANUAL) 18 Sets
CLASS: PS 600/1A 87 50
TO SCADA BURDEN ACCURACY ISF Vk RCT I AT Vk/2
BB LBB
APPLICATION CORE RATIO (VA) CLASS (V) (ohms) EX (mA)
TO PPC CLASS: PS 8 HORN GAP FUSE 36kV, 20A 4 Sets
CORE-4 PQM TO PPC PROTECTION 1 600/1A -- PS -- 600 3 30mA
600/1A CLASS: TO SCADA CORE-4 PQM 33kV BAY CT (BUS SECTION)
0.2s,10VA 600/1A TO SCADA
220kV TRAFO-1 CRP PROTECTION 2 600/1A -- PS -- 3 30mA APPLICATION CORE RATIO BURDEN (VA) ACCURACY ISF Vk (V) RCT (Ohm) IEX AT Vk/2 (Ma)
CLASS: 0.2s,10VA 220kV TRAFO-2 CRP 600
CORE-3 FROM SELECTED BUS CVT
FROM SELECTED BUS CVT PROTECTION 1 3000/1A -- PS -- 1500 5 30mA
600/1A CLASS: BCU TVM CORE-3 METERING 3 600/1A 20 0.2s <5 -- -- --
R4 0.2s, 20VA TO SCADA 600/1A BCU TVM METERING 2 3000/1A 20 0.2s <5 -- -- --
CLASS: 0.2s, 20VA TO SCADA METERING 4 600/1A 10 0.2s <5 -- -- --
R4
CORE-2 PROTECTION 3 3000/1A 20 5P20 <5 -- -- --
50 51 50N 51N 67 67N FROM SELECTED BUS CVT PROTECTION 5 600/1A -- PS -- 600 3 30mA
600/1A CORE-2 50 51 50N 51N 67 67N FROM SELECTED BUS CVT
CLASS: PS 27 59 81O 81U 64RHV TO SCADA 600/1A 33kV BAY CT (TRAFO-1)
80 80 CLASS: PS 27 59 81O 81U 64RHV TO SCADA 220kV CT (BUS COUPLER)
96 95 DC AC
80 80 APPLICATION CORE RATIO BURDEN (VA) ACCURACY ISF Vk (V) RCT (Ohm) IEX AT Vk/2 (Ma)
BURDEN ACCURACY ISF Vk RCT I AT Vk/2
APPLICATION CORE RATIO
95
(ohms) EX (mA)
96 DC AC
CORE-1 86 49 63 MOG
(VA) CLASS (V) PROTECTION 1 3000/1A -- PS -- 1500 5 30mA
F 600/1A SEF TO SCADA CORE-1 86 49 63 MOG
87T 24
HV
600/1A TO SCADA PROTECTION 1 600/1A -- PS -- 600 3 30mA METERING 3000/1A 20 0.2s <5
CLASS: PS SEF
87T HV 24 2 -- -- --
CLASS: PS
(3" IPS TUBE(SCH-80)) P1 PROTECTION 2 600/1A -- PS -- 600 3 30mA PROTECTION 3 3000/1A 20 5P20 <5 -- -- --
201- LA (3" IPS TUBE(SCH-80)) P1 F
216kV, 10kA, CLASS-III 204- LA METERING 3 600/1A 20 0.2s <5 -- -- -- METERING 4 3000/1A 10 0.2s <5 -- -- --
216kV, 10kA, CLASS-III METERING 5 3000/1A 10 0.2s <5
HV BCT P2 PROTECTION -- -- --
600/1-1A HV BCT 4 600/1A -- PS -- 600 3 30mA
CORE-2 64RHV SEFHV 600/1-1A P2 33kV BAY CT (TRAFO-2)
CLASS: PS 64RHV SEFHV PROTECTION 5 600/1A -- PS -- 600 3 30mA
CORE-2 APPLICATION CORE RATIO BURDEN (VA) ACCURACY ISF Vk (V) RCT (Ohm) IEX AT Vk/2 (Ma)
CORE-1 CLASS: PS 220kV MCT (LINE BAY)
CLASS: PS PROTECTION 1 1200/1A -- PS -- 1500 5 30mA
CORE-1 APPLICATION CORE No. RATIO BURDEN (VA) ACCURACY ISF/ALF
P1 CLASS: PS METERING 2 1200/1A 20 0.2s <5 -- -- --
P1CORE-1 P1
CORE-2 P2 P1CORE-1
METERING 1 600/1A 10 0.2s <5
TRAFO-1 CLASS: PS CLASS: PS CORE-2 P2 PROTECTION 3 1200/1A 20 5P20 <5 -- -- --
220/33kV, 110/140MVA, YNyn0, TRAFO-2 CLASS: PS CLASS: PS METERING 2 600/1A 10 0.2s <5
HV NCT METERING 4 1200/1A 10 0.2s <5 -- -- --
Z=15% @140MVA ONAN/ONAF, 600/1-1A 220/33kV, 50/60MVA, YNyn0, HV NCT 220kV MCT (TRAFO-2 BAY) METERING 5 1200/1A 10 0.2s <5
600/1-1A -- -- --
OLTC TAP -10% TO +10% LV NCT Z=15% @60MVA ONAN/ONAF,
3000/1-1A LV NCT APPLICATION CORE No. RATIO BURDEN (VA) ACCURACY ISF/ALF 33kV BAY CT (MVAr & FILTER)
IN STEPS OF 1.25% OLTC TAP -10% TO +10% 1200/1-1A
CLASS: PS CLASS: PS IN STEPS OF 1.25% METERING 1 400-200/1A 10 0.2s <5 APPLICATION CORE RATIO BURDEN (VA) ACCURACY ISF Vk (V) RCT (Ohm) IEX AT Vk/2 (Ma)
LV BCT CORE-1 CORE-2 CLASS: PS CLASS: PS 1 1200/1A -- PS -- 1500 5 30mA
E METERING 2 400-200/1A 10 0.2s <5 PROTECTION
3000/1-1A P1 CORE-1 CORE-2
P1 P2 LV BCT P1 20 0.2s <5
CORE-1 1200/1-1A METERING 2 1200/1A -- -- --
P1 P2 220kV MCT (TRAFO-1 BAY)
CLASS: PS CORE-1 <5
APPLICATION CORE No. RATIO BURDEN (VA) ACCURACY ISF/ALF PROTECTION 3 1200/1A 20 5P20 -- -- --
CLASS: PS
CORE-2
CLASS: PS METERING 1 600-400/1A 10 0.2s <5 33kV BAY CT (FEEDERS)
64RLV SEFLV CORE-2
P2 CLASS: PS 64RLV SEFLV APPLICATION CORE RATIO BURDEN (VA) ACCURACY ISF Vk (V) RCT (Ohm) IEX AT Vk/2 (Ma)
P2 METERING 2 600-400/1A 10 0.2s <5
R4 PROTECTION 1 600/1A -- PS -- 600 3 30mA
220kV BUS & LINE CVT DETAILS
R4 (3" Al. IPS TUBE (SCH-80))
(3" Al. IPS TUBE (SCH-80)) METERING 2 600/1A 20 0.2s <5 -- -- --
APPLICATION CORE No. PRIMARY (kV) SECONDARY (V) OUTPUT (VA) ACCURACY
METERING PROTECTION 3 600/1A 20 5P20 <5 -- -- --
311- LA 1 220/ 3 110/ 3 50 0.2
309 - LA 30kV, 10kA 33kV MCT (BUS SECTION)
30kV, 10kA PROTECTION 2 220/ 3 110/ 3 50 3P
CLASS-IIl APPLICATION CORE RATIO BURDEN (VA) ACCURACY ISF/ALF
CLASS-IIl PROTECTION 3 220/ 3 110/ 3 50 3P
METERING 1 3000/1A 10 0.2s <5
309 - CT 311 - CT
1200/1-1-1-1-1A P2 220kV MVT (TRAFO-1 BAY & TRAFO-2 BAY) DETAILS METERING 2 3000/1A 10 0.2s <5
3000/1-1-1-1-1A P2
309 - CRP
311 - CRP APPLICATION CORE No. PRIMARY (kV) SECONDARY (V) OUTPUT (VA) ACCURACY D
FROM
H1 H4
CORE-5 ABT FROM 33kV BUS PT DETAILS
CORE-5 ABT H2 H5
H7 H8 H9 H10
CHECK BUS PT 1
H1 H4
CHECK BUS PT 2
1 2 3 4
CL: 0.2s, 10VA H2 H5
H7 H8 H9 H10 METERING 1 220/ 3 110/ 3 20 0.2 APPLICATION CORE No. PRIMARY SECONDARY OUTPUT ACCURACY
CL: 0.2s, 10VA H3 H6 5 6 7 8
33kV STATION TRAFO-1
1 2 3 4
AXT2 - 89A 25kA, 3Sec. 25kA, 3Sec. 311- 89A KWH, KVAR, PF, F.
309 - 89A AXT1 - 89A ISOLATOR M
36kV, 400A, ISOLATOR M
(3" Al. IPS TUBE (SCH-80)) 5. CONTROL VOLTAGE FOR 220kV SIDE & 33kV SIDE EQUIPMENT SHALL BE 220V DC. MOTOR SUPPLY FOR 220kV & 33kV ISOLATORS &
M
36kV, 3150A (3" Al. IPS TUBE (SCH-80)) 36kV, 400A, M 36kV, 1250A
25kA, 3Sec. 25kA, 3Sec. 25kA, 3SEC. CB SHALL BE 415/240V AC.
25kA, 3SEC.
309 - 89AE 311-89AE 6. TWO NUMBERS OF 220V DC SUPPLY SHALL BE PROVIDED FOR PROTECTION FUNCTION.
C 33kV BUS SECTION - II, 3000A, 25kA FOR 3SEC F9 33kV BUS SECTION - I, 3000A, 25kA FOR 3SEC F11 C
7. CENTRALIZED BUS DIFFERENTIAL PROTECTION RELAY (WITH MAIN AND CHECK FUNCTION) OF LOW IMPEDANCE NUMERICAL TYPE
(4'' Al. IPS TUBE) (SCH-80) 301 - 89A F1 302 - 89A F2 303 - 89A F3 304 - 89A F4 305 - 89A F5 306 - 89A F6 307 - 89A F7 308 - 89A F8 310 - 89B F10 F12 313 - 89A F13 314 - 89A F14 F15 F16 (4'' Al. IPS TUBE) (SCH-80)
310 - 89A 312 - 89A 315 - 89A 316 - 89A ALONG WITH NECESSARY AUXILIARY RELAYS ETC., SHALL BE PROVIDED
ISOLATOR 36kV, ISOLATOR 36kV, ISOLATOR 36kV, ISOLATOR 36kV, ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR 36kV, ISOLATOR 36kV,
1250A 25kA, 3SEC. 36kV, 800A 36kV, 800A 36kV, 800A 36kV, 800A 36kV, 3150A 36kV, 3150A ISOLATOR 36kV, 800A 25kA, 3SEC. ISOLATOR 36kV, ISOLATOR 36kV, 8. FOR 220kV LINE FEEDER PROTECTION MAIN-1 & MAIN-2 PROTECTION RELAYS SHALL BE PROVIDED WITH DIFFERENT
1250A 25kA, M M
800A 25kA, 3SEC. M 800A 25kA, 3SEC. M M M M M M M M
1250A 25kA, 3SEC. M M M M
302 - 89AE 25kA, 3SEC 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 1250A 25kA, 3SEC. 314-89AE 800A 25kA, 3SEC. 800A 25kA, 3SEC. FIRMWARE/MAKE. LINE BAY RELAY DETAILS TO MATCH WITH REMOTE END PROTECTION RELAYS.
3SEC. 301- 89AE 303 - 89AE 304 - 89AE 305 - 89AE 306 - 89AE 307 - 89AE 308 - 89AE 313-89AE
312 - 89AE 315-89AE 316 - 89AE 9. ALL MAIN PROTECTION RELAYS AND BCU SHALL BE NUMERICAL TYPE & SHALL BE COMPLAINT WITH IEC-61850 PROTOCOL.
301- VCB 302 - VCB 303 - VCB 304 - VCB 305 - VCB 306 - VCB 307 - VCB 308 - VCB 310 - VCB 310- CRP 312 - VCB 313 - VCB 314 - VCB 315 - VCB 316 - VCB 10. TRIPPING RELAY AND ALL AUXILIARY RELAYS SHALL BE ELECTROMECHANICAL/ELECTRICAL RESET TYPE.
36kV, 1250A 301/302 - CRP 36kV, 1250A 301/302 - CRP 36kV, 800A 303/304 - CRP 36kV, 800A 303/304 - CRP 36kV, 800A 305/306 - CRP 36kV, 800A 305/306 - CRP 36kV, 800A 307/308 - CRP 36kV, 800A 307/308 - CRP 36kV, 3150A H1 H4
H7 H8 H9 H10 36kV, 1250A 312/313 - CRP 36kV, 1250A 312/313 - CRP 36kV, 800A 314/315 - CRP 36kV, 800A 314/315 - CRP 36kV,800A 316- CRP
25kA,3 SEC. H1 H4 25kA,3 SEC. H1 H4 25kA,3 SEC. H1 H4 H1 H4 25kA,3 SEC. H1 H4
25kA,3 SEC. H1 H4 25kA,3 SEC. H1 H4 25kA,3 SEC. H1 H4 25kA,3 SEC. H2 H5
1 2 3 4
25kA,3 SEC. 25kA,3 SEC. 25kA,3 SEC. 25kA,3 SEC. 25kA,3 SEC. 11. PQ METER SHALL BE PROVIDED AT GSS END.
H7 H8 H9 H10 H7 H8 H9 H10 H7 H8 H9 H10 25kA,3 SEC. H7 H8 H9 H10 H7 H8 H9 H10 H7 H8 H9 H10 H7 H8 H9 H10 H7 H8 H9 H10 H3 H6 5 6 7 8
H1 H4
H7 H8 H9 H10
H1 H4
H7 H8 H9 H10
H1 H4
H7 H8 H9 H10
H1 H4
H7 H8 H9 H10
H1 H4
H7 H8 H9 H10
H2 H5
1 2 3 4
H2 H5
1 2 3 4
H2 H5
1 2 3 4
H2 H5
1 2 3 4
H2 H5
1 2 3 4
H2 H5
1 2 3 4
H2 H5
1 2 3 4
H2 H5
1 2 3 4 310 - 33kV CTP2 L/R TNC BCS EM 9 10 11 12 H2 H5 H2 H5 H2 H5 H2 H5 H2 H5 12. THE FILTER & CAPACITOR 33kV BAY EQUIPMENTS RATING SHALL BE FINALIZED AFTER SYSTEM STUDY REPORT. HOWEVER WE
P2 H3 H6 5 6 7 8
P2 H3 H6 5 6 7 8
P2 H3 H6 5 6 7 8
P2 H3 H6 5 6 7 8
P2 H3 H6 5 6 7 8
P2 H3 H6 5 6 7 8
P2 H3 H6 5 6 7 8
P2 H3 H6 5 6 7 8
P2 H3 H6
1
5
2
6
3
7
4
8
P2 H3 H6
1
5
2
6
3
7
4
8
P2 H3 H6
1
5
2
6
3
7
4
8
P2 H3 H6
1
5
2
6
3
7
4
8
P2 H3 H6
1
5
2
6
3
7
4
8
AC BUZZER
301 - 33kV CT L/R TNC BCS EM 9 10 11 12 302 - 33kV CT L/R TNC BCS EM 9 10 11 12 303 - 33kV CT L/R TNC BCS EM 9 10 11 12 304 - 33kV CT L/R TNC BCS EM 9 10 11 12 305 - 33kV CT L/R TNC BCS EM 9 10 11 12 306 - 33kV CT L/R BCS EM 9 10 11 12 307 - 33kV CT L/R TNC BCS EM 9 10 11 12 308 - 33kV CT L/R TNC BCS EM 9 10 11 12 3000/1-1-1A DC HOOTER
312 - 33kV CT L/R TNC BCS EM
313 - 33kV CT
9 10 11 12 L/R TNC BCS EM 9 10 11 12
314 - 33kV CT L/R TNC BCS EM 9 10 11 12
315 - 33kV CT L/R TNC BCS EM 9 10 11 12
316 - 33kV CT L/R TNC BCS EM 9 10 11 12 ARE CONSIDER 50MVAr (1600A)
AC BUZZER AC BUZZER AC BUZZER AC BUZZER AC BUZZER AC BUZZER AC BUZZER AC BUZZER
1200/1-1-1A DC HOOTER
1200/1-1-1A DC HOOTER
600/1-1-1A DC HOOTER
600/1-1-1A DC HOOTER
600/1-1-1A DC HOOTER
600/1-1-1A DC HOOTER
600/1-1-1A DC HOOTER
600/1-1-1A DC HOOTER
CORE - 3 1200/1-1-1A 1200/1-1-1A
AC BUZZER AC BUZZER
600/1-1-1A
AC BUZZER
600/1-1-1A
AC BUZZER
600/1-1-1A
AC BUZZER
13. THE AUXILIARY LOAD CONSIDERED FOR CAPACITOR BANK & FILTER BANK.
SPARE DC HOOTER DC HOOTER DC HOOTER DC HOOTER DC HOOTER
CORE - 3 CORE - 3 CORE - 3 CORE - 3 CORE - 3 CORE - 3 CORE - 3 CORE - 3 CL: 5P20, 20VA CORE - 3 CORE - 3 CORE - 3 CORE - 3 CORE - 3
SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE SPARE
CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA CORE - 2 AS A CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA CL: 5P20, 20VA
TVM
CORE - 2 AS A CORE - 2 AS A CORE - 2 AS A CORE - 2 AS A CORE - 2 AS A CORE - 2 AS A CORE - 2 AS A CORE - 2 AS A METERING VS V CORE - 2 AS A
CORE - 2 AS A
CORE - 2 AS A
CORE - 2 AS A
CORE - 2 AS A
TVM TVM TVM TVM TVM TVM TVM TVM TVM TVM TVM TVM TVM
METERING VS V METERING VS V METERING VS V METERING VS V METERING VS V METERING VS V METERING VS V METERING VS V CL: 0.2S, 20VA R4
METERING VS V METERING VS V METERING VS V METERING VS V METERING VS V
50 50 50N
CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA CORE - 1 LBB 51 51N CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA CL: 0.2S, 20VA
50 50N 50 50N 50 50N 50 50N 50 50N 50 50N 50 50N 50 50N 50 50 50 50 50
CORE - 1 LBB
50
51 51N CORE - 1 LBB
50
51 51N CORE - 1 87L
LBB
50
51 51N CORE - 1 87L
LBB
50
51 51N CORE - 1 87L
LBB
50
51 51N CORE - 1 87L
LBB
50
51 51N CORE - 1 87L
LBB
50
51 51N CORE - 1 87L
LBB
50
51 51N PROTECTION 86 94
95
TCS1
95
TCS2 CORE - 1 LBB
50 50N
51 51N CORE - 1 LBB
50
51
50N
51N
CORE - 1
87L
LBB
50
51
50N
51N
CORE - 1
87L
LBB
50
51
50N
51N
CORE - 1
87L
LBB
50
51
50N
51N
R4
PROTECTION 86 94
95 95
TCS1 TCS2
PROTECTION 86 94
95 95
TCS1 TCS2
PROTECTION 86 94
95 95
TCS1 TCS2
PROTECTION 86 94
95 95
TCS1 TCS2
PROTECTION 86 94
95 95
TCS1 TCS2
PROTECTION 86 94
95 95
TCS1 TCS2
PROTECTION 86 94
95 95
TCS1 TCS2
PROTECTION 86 94
95 95
TCS1 TCS2
CL: PS 27 59
PROTECTION 86
95 95
94 TCS1 TCS2 PROTECTION 86 94
95 95
TCS1 TCS2 PROTECTION 86 94
95 95
TCS1 TCS2 PROTECTION 86 94
95 95
TCS1 TCS2 PROTECTION 86 94
95 95
TCS1 TCS2
CL: PS 27 59
CL: PS 27 59
CL: PS 27 59
CL: PS 27 59
CL: PS 27 59
CL: PS 27 59
CL: PS 27 59
CL: PS 27 59 P1 CL: PS 27 59 CL: PS 27 59 CL: PS 27 59 CL: PS 27 59 CL: PS 27 59
FROM P1 P1 P1 P1 P1 P1 P1 P1
310-MCT 3000/1-1A FROM P1 P1 P1 P1 P1
B BUS PT FROM FROM FROM FROM FROM FROM FROM FROM
P2 BUS PT B
CORE-2 ABT ABT FROM FROM FROM FROM FROM
301 - 89L BUS PT 302 - 89L BUS PT 303 - 89L BUS PT 304 - 89L BUS PT 305 - 89L BUS PT 306 - 89L BUS PT 307 - 89L BUS PT 308 - 89L BUS PT CLASS: 0.2s, 10VA CHECK STANDBY 312 - 89L BUS PT 313 - 89L BUS PT 314 - 89L BUS PT 315 - 89L BUS PT 316 - 89L BUS PT
ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR ISOLATOR
36kV, 1250A M 36kV, 1250A M 36kV, 800A M 36kV, 800A M 36kV, 800A M 36kV, 800A M 36kV, 800A M 36kV, 800A M CORE-1 36kV, 1250A M 36kV, 1250A M 36kV, 800A M 36kV, 800A M 36kV, 800A M
25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. CLASS: 0.2s, 10VA 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC. 25kA, 3SEC.
ABT
301 - 89LE 302 - 89LE 303 - 89LE 304 - 89LE 305 - 89LE 306 - 89LE 307 - 89LE 308 - 89LE 310-MPT MAIN 312 - 89LE 313 - 89LE 314 - 89LE 315 - 89LE 316 - 89LE
301 - LA 302 - LA 303 - LA 304 - LA 305 - LA 306 - LA 307 - LA 308 - LA 33kV / 110V / 110V P1 1 312 - LA 313 - LA 314 - LA 315 - LA 316 - LA
30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA 30kV, 10kA
CLASS-IIl CLASS-IIl CLASS-IIl CLASS-IIl CLASS-IIl CLASS-IIl CLASS-IIl CLASS-IIl √3 √3 √3 CLASS-IIl CLASS-IIl CLASS-IIl CLASS-IIl
(TWIN MOOSE (TWIN MOOSE (SINGLE MOOSE (SINGLE MOOSE (SINGLE MOOSE (SINGLE MOOSE (SINGLE MOOSE (SINGLE MOOSE CLASS-IIl (TWIN MOOSE (TWIN MOOSE (SINGLE MOOSE (SINGLE MOOSE (SINGLE MOOSE
CORE 1 - 0.2,100VA 2
AL59) AL59) AL59) AL59) AL59) AL59) AL59) AL59) CORE 2 - 0.2,100VA AL59) AL59) AL59) AL59) AL59)
(4" Al. IPS TUBE
BAY NO: 301 BAY NO: 302 BAY NO: 303 BAY NO: 304 BAY NO: 305 BAY NO: 306 BAY NO: 307 BAY NO: 308 BAY NO: 310 (SCH-80)) BAY NO: 312 BAY NO: 313 BAY NO: 314 BAY NO: 315 BAY NO: 316
SECI-VI FEEDER-7 SECI-VI FEEDER-8 SECI-VI FEEDER-1 SECI-VI FEEDER-2 SECI-VI FEEDER-3 SECI-VI FEEDER-4 SECI-VI FEEDER-5 SECI-VI FEEDER-6 BUS SECTIONALISER CESC FEEDER - 12 CESC FEEDER - 13 CESC FEEDER - 09 CESC FEEDER - 10 CESC FEEDER - 11
33kV MVAr (33kV FILTER) (25.2 MW) (25.2 MW) (25.2 MW) (22.05 MW) (22.05 MW) (SPARE) (33kV MVAr) (33kV FILTER) (25.2 MW) (25.2 MW) (SPARE)
A A
16 15 14 13 12 11 10 9 8 7 6 5 4 3 2 1