Refrigeration & Air Conditioning Lab
Department of Mechanical Engineering
Manual
of
Test rig of a vapor compression
refrigeration system
Experiment: A
Test Rig of a Vapor Compression Refrigeration System
Objectives:
a) To carry out steady state measurements on the test rig of a vapor compression
refrigeration system in order to determine
i) Carnot COP, Cycle COP and Actual COP
ii) Overall heat transfer coefficients for the evaporator and the condenser
iii) Overall volumetric efficiency of the compressor
b) Pulldown time and average refrigeration capacity (RC) estimation
Introduction:
The test-rig consists of a hermetic compressor, an air-cooled condenser, a
capillary tube/TEV (Thermo-static Expansion Valve) and a water-cooled evaporator.
In addition to these four major components, the test-rig also consists of several other
components such as manual shut-off valves, sight glass, filter drier etc. Pressure gauges
are installed to measure the condenser and evaporator pressures (in psig). Similarly,
digital thermometers are provided at the inlet and exit of evaporator, compressor and
condenser to facilitate measurement of the refrigerant temperature at these points. A
rotameter is installed in a by-pass liquid line to measure the flow rate of the liquid
refrigerant by opening the manual shut-off valve. The test-rig uses HFC-134a (Tetra-
Fluoro-Ethane) as refrigerant.
Evaporator:
The evaporator used in the test-rig consists of two copper coils immersed in
water kept in a stainless steel container. The stainless steel container is housed in a
wooden box. The gap between the wooden box and the stainless steel container is
Refrigeration & Air Conditioning Laboratory, IIT Kharagpur
filled with fiberglass insulation. A pump is installed in the container to maintain
uniform temperature of water. An electrical heater controlled by a thermostat provides
the required cooling load to the evaporator. As the low pressure, low temperature
refrigerant flows through the copper coil; heat is transferred from the water to the
refrigerant leading to flow boiling of refrigerant liquid inside the coil. In steady state,
the heat input to the water by the heater is approximately equal to the heat absorbed
by the refrigerant, which is the desired refrigeration effect. The energy meter connected
across the heater measures the heater input. A digital thermometer measures the
water temperature.
Compressor:
A hermetic compressor with a piston displacement of 2.759 m3/h is used in the
test-rig. The compressor is located in such a way that the ambient air used for cooling
the condenser also cools the compressor. The energy input to the compressor can be
measured using either the energy meter or from the voltmeter and ammeter readings.
Since the electrical load on the compressor is inductive, a suitable power factor (~ 0.80)
should be used while calculating energy input from the product of voltmeter and
ammeter readings.
Condenser:
The condenser used in the test rig is an air-cooled, fin-and-tube type
compressor. A blower is used to blow the ambient air over the condenser and to extract
the heat rejected by the condensing refrigerant. The heat rejection rate at condensate
is obtained by measuring the airflow rate over the condenser and temperature of air
at the inlet and outlet of the condenser. A vane type anemometer is used to measure
the average velocity of air at the outlet of condenser. The average velocity is obtained
by taking the average of measured air velocities at 5 locations (four corners and center)
on the condenser. The mass flow rate of air is obtained from the average air velocity, face
area of the condenser and the density of air (obtained from barometric pressure and air
Refrigeration & Air Conditioning Laboratory, IIT Kharagpur
temperature).
Expansion device:
A thermostatic expansion valve is used in the test rig as an expansion device
to control the flow of refrigerant into the evaporator. It uses a temperature-sensing
bulb to monitor the evaporator's outlet temperature and adjust the refrigerant flow
according to the superheat.
Measurements:
Objective A: Steady state measurements
Once steady-state is reached, measure the pressure gauge readings,
temperature readings, heater and compressor energy meter (or voltmeter and
ammeter) readings, temperature of water around the evaporator, velocity of air over
the condenser at 5 locations, inlet and outlet temperature of air at condenser,
barometric pressure. Then open the valve in the rotameter by-pass line and take the
rotameter reading. Then the system is switched-off and measurements of condenser and
evaporator dimensions are to be taken. For the condenser, measure the width and height
of condenser, tube diameter, number of condenser tubes (no. of rows × no. of tubes per
row), number of fins (no. of fins per inch × width of condenser in inches), thickness,
width and height of fins and number of tubes passing through the fins. For the
evaporator, measure the copper tube diameter, coil diameter and number of coils for
both inner and outer coils immersed in water.
Observations:
Condenser Pressure, Pc (bar)
Evaporator Pressure, Pe (bar)
Refrigerant temperature at condenser inlet, td (°C)
Refrigerant temperature at condenser outlet, tco (°C)
Refrigeration & Air Conditioning Laboratory, IIT Kharagpur
Refrigerant temperature at evaporator inlet, tei (°C)
Refrigerant temperature at evaporator outlet, ts (°C)
Compressor energy consumption, (W) (= V × I)comp
Heater energy consumption, (W) (= V × I)heater
Number of fins, Nr 153
Fin thickness, e (m) 0.17×10-3
Fin width, b (m) 0.0527
Fin height, h (m) 0.3048
Condenser width, L (m) 0.32
Number of tubes in condenser, Ntc 36
Diameter of condenser tubes, dc (m) 9.5×10-3
Average air velocity through condenser, V (m/s)
Air temperature at condenser inlet, Tair,in (°C)
Air temperature at condenser outlet, Tair,out (°C)
Temperature of water in evaporator, Twater (°C)
Evaporator coil diameter, Dc1 and Dc2 (m) 0.15 and
0.255
Evaporator tube diameter, De1 and De2 (m) 9.5×10-3
Number of tubes in the coil, Nte1 and Nte2 (m) 13 and 20
Room temperature (°C)
Room pressure (bar)
Displacement of compressor, PD (m3/h) 2.759
Rotameter reading (kg/h)
Water mass (kg) 25
Calculations:
i) Carnot COP, Cycle COP and Actual COP
Tevap
COPcarnot
Tcond Tevap
where, Tevap and Tcond are the saturation temperatures (K) corresponding to evaporator
pressure and condenser pressure (to be obtained from Thermodynamic Tables or p-h
charts of R-134a)
Refrigeration & Air Conditioning Laboratory, IIT Kharagpur
(h1 h3 )
COPcycle
( h2 h1 )
where h1, h2 and h3 are the enthalpy of refrigerant vapor at evaporator outlet, enthalpy
of refrigerant vapor at compressor outlet and enthalpy of refrigerant liquid at condenser
outlet respectively (to be obtained from tables or p-h charts from the temperature and
pressure values).
Actual refrigeration effect Energy meter reading of heater
COPactual
Actual energy input to compressor Energy meter reading of compressor
ii) Overall heat transfer coefficients for the evaporator and the condenser
Uevap = )
.(
where Acoil is the area of the evaporator coils (to be obtained from the evaporator tube diameter,
coil diameter and number of coils immersed in water), Twater and Te are the water and refrigerant
temperatures in the evaporator.
( . ) .( )
Ucond = = , ,
. .
where,
Tair ,out Tair ,in
LMTDcond
(T Tair ,in )
ln cond
(Tcond Tair ,out )
Tair,in and Tair,out are the inlet and outlet temperatures of air, Tcond is the saturation
temperature of refrigerant corresponding to condenser pressure.
The condenser area, Acond is the sum total of the bare tube area (primary area) and
the fin area (secondary area). These areas have to be obtained from the condenser
dimensions and geometry, number of fins, fin dimensions etc.
Refrigeration & Air Conditioning Laboratory, IIT Kharagpur
iii) Overall volumetric efficiency of the compressor
̇
ղ = =
.
where ṁref is the mass flow rate of liquid refrigerant as indicated by the rotameter
(kg/hr), ρsuction is the density of refrigerant vapor at compressor inlet (kg/m3). PD is
the piston displacement of the compressor in m3/hr. Refrigerant density is to be
obtained from thermodynamic property tables.
Objective B: Pulldown time and average refrigeration capacity (RC)
estimation
After noting all the required steady-state measurements, turn off the heater and start
the timer to estimate the pulldown time for the water to reach the set temperature.
For each fixed time interval, note all the pressure and temperature readings, the
rotameter reading and the actual compressor power consumption from the energy
meter. Continue the experiment till the compressor cuts out at the set chilled water
temperature. At each time interval, calculate the instantaneous refrigeration capacity
(RC) from the cycle drawn on the p-h chart. Take the average of instantaneous RCs
for the total pulldown time and compare it with the RC calculated from chilled water
side.
( , , )
𝑄̇ =
where, Mw is the mass of water (kg) in the container, Cp is the specific heat of water
(kJ/kg.K), Tchill,i and Tchill,f are the initial and final temperatures of the chilled water,
and t is the pulldown time (s).
Refrigeration & Air Conditioning Laboratory, IIT Kharagpur
Observations:
Pressure Temperature I Inst. Comp Comp
Time ṁref R.C ressor ressor
(min:ss) (A)
Powe Power
(kg/h) (W)
r
Pe Pc Ts Td Tco Tei Tchil (W)
(from (W) (Actual)
l
(bar) (bar) (°C) (°C) (°C) (°C) cycle) (from
(°C) cycle)
At the end of your study, you must try to answer the following questions:
1. What are the errors in measurement of refrigerant temperature? Suggest a better
method of measuring the temperature.
2. What are the errors in energy meter reading?
3. What are the assumptions made in calculating the Carnot, cycle and actual
COPs?
4. How does one find cooling capacity and condenser heat rejection rate from the
refrigerant side? What differences do you observe when you compare cooling
capacity and heat rejection rate calculated from refrigerant side with those
calculated from water/air side?
5. Why is thermostat used in the water tank?
6. What are the safety devices used in the set-up?
7. The experiment gives COP at a fixed temperature. Suggest a method to find the
COP at different condenser and evaporator temperatures.
Refrigeration & Air Conditioning Laboratory, IIT Kharagpur
8. What are the assumptions made in calculating LMTD for condenser?
9. What is the significance of volumetric efficiency of compressor?
10. Carry out an error analysis of your experimental results.
11. What is the significance of estimating the pulldown time?
12. What is the reason for the difference in the average RC calculated from water
side and from the refrigerant side during pulldown?
13. Why is the instantaneous compressor power reducing during pulldown process?
Refrigeration & Air Conditioning Laboratory, IIT Kharagpur