Ga & RCC Details of SC, Eqt, MBBR, TWT, SCLF & SHT, r0
Ga & RCC Details of SC, Eqt, MBBR, TWT, SCLF & SHT, r0
PROJECT
SUPPLY AND INSTALLATION OF 300 KLD SEWAGE
TREATMENT PLANT AT THE TRAINEE HOSTEL,GUEST
HOUSE AND VILLA IN VEDANTA LIMITIED
JHARSUGUDA.
CONTRACTOR
CLIENT
VEDANTA LIMITED
SUPPLY AND INSTALLATION OF 300 KLD SEWAGE
TREATMENT PLANT AT THE TRAINEE HOSTEL,GUEST
HOUSE AND VILLA IN VEDANTA LIMITIED JHARSUGUDA
VEDANTA Doc.
EFFWA Doc. No. Description
No.
GA and RCC details of Stilling chamber,
Equalisation Tank, Anoxic Tank, MBBR Tank,
P - 103- DE: CVL- 002, R0 -
Clear water/ chlorination Tank, Secondary Clarifier,
Treated Water Tank & Sludge Holding Chamber
EFFWA VEDANTA
Page 1 of 19
Design depth of tank , a = 0.30 m
2
Allowable stress = fy/1.15 = 435 N/mm
Horizontal Reinforcement
Area of steel required, Ast = Mu/σst.jd
2
1.5 x 0.17 x 1e7 = 93.8 mm <<
300 x .90 x 100
So providing 8 mm dia bars at 200 c/c (251 mm^2) both ways as reinforcement.
B Equalisation Tank
Length of tank, b = 8.00 m
Width of tank, c = 6.00 m
Safe water Depth (SWD), a = 3.20 m
Free board 0.90 m
Design depth of tank , a = 3.20 m
Page 2 of 19
For a rectangular wall for fixed base, free top and subjected to triangular load,
Reinforcement calculation
2
Yield strength of reinforcement steel = 500 N/mm
Partial safety factor of steel = 1.15
2
Allowable stress = fy/1.15 = 435 N/mm
Page 3 of 19
Horizontal Reinforcement
Area of steel required, Ast = Mu/σst.jd + Tu/ (σst. 2)
Providing 10 mm dia bars at 200 mm c/c (393 mm^2) both faces with 10 mm dia bar at
200 c/c extra (785 mm^2) at inner corners as horizontal steel.
Vertical Reinforcement
Area of steel required on inner face = M/σst.jd
Providing 10 mm dia bars at 180 mm c/c (437 mm^2) both faces as vertical steel with 12 mm
dia bars at 180 mm c/c extra ( 1064 mm^2) at bottom.
Page 4 of 19
Actual eccentricity, e = M/V - 1.5
0.37 m
2
= 7.34 T/m <10.0 T/m2 So Safe
2
Min. upward soil pressure, w = 1.06 T/m
2
Upward soil pressure at raft wall junction = 6.40 T/m
250
200
.
250
2.50 m
Reinforcement
Thickness of raft provided = 250 mm
Shear force on wall at the raft level due = 0.245 w.H^2 triangular loading
to water pressure 2.51 T
T ult = 1.5T = 3.76 T
Providing 10 mm dia bars at 180 mm c/c top and bottom (437 mm^2) with 12 mm dia 180 c/c
extra (1064 mm^2) at top bent up from wall.
2
1.05 x 1e7 = 325.00 mm
300 x 0.90 x 120
So providing 10 mm dia bars at 200 mm c/c ( 393 mm^2 ) as main steel with 8 mm dia at
200 c/c as dstribution.
εm = ε1 - ε2
= 0.0006
εm = 0.00123 - 0.0006
= 0.00061
For a rectangular wall for fixed base, free top and subjected to triangular load,
Page 7 of 19
Max. vertical moment (outer face) , Mx = 0.012 w.a^3
T-3, IS 3370 (part-IV), 1967
i.e 0.016 x 1 x 3.3 x 3.3 x 3.3 = 0.57 T-m
M ult = 1.5M = 0.86 T-m
Reinforcement calculation
2
Yield strength of reinforcement steel = 500 N/mm
Partial safety factor of steel = 1.15
2
Allowable stress = fy/1.15 = 435 N/mm
Horizontal Reinforcement
Area of steel required, Ast = Mu/σst.jd + Tu/ (σst. 2)
Providing 10 mm dia bars at 200 mm c/c (393 mm^2) both faces with 10 mm dia bar at
200 c/c extra (785 mm^2) at corners as horizontal steel.
Vertical Reinforcement
Area of steel required on inner face = M/σst.jd
Page 8 of 19
Max. +ve steel required on wall,
2
4.31 x 1e7 = 840.63 mm Inner face
300 x .90 x 190
Providing 10 mm dia bars at 180 mm c/c both faces (437 mm^2) with 10 mm dia 180 c/c
extra (872 mm^2) at bottom inner face.
Shear force on wall at the raft level due = 0.191 w.H^2triangular loading
to water pressure = 2.08 T
T ult = 1.5T = 3.12 T
Providing 10 mm dia bars at 180 mm c/c top and bottom (437 mm^2) with 10 mm dia 180 c/c
extra (872 mm^2) at top bent up from wall.
Page 9 of 19
6.1 Vertical Wall Panel
When tank is full with liquid upto SWD
Bending Moment and tension calculation
Max. width of wall panel, b = 4.25 m
For a rectangular wall for fixed base, free top and subjected to triangular load,
Reinforcement calculation
Page 10 of 19
2
Yield strength of reinforcement steel = 500 N/mm
Partial safety factor of steel = 1.15
2
Allowable stress = fy/1.15 = 435 N/mm
Horizontal Reinforcement
Area of steel required, Ast = Mu/σst.jd + Tu/ (σst. 2)
Providing 10 mm dia bars at 200 mm c/c (393 mm^2) both faces with 10 mm dia bar at
200 c/c extra (785 mm^2) at corners as horizontal steel.
Vertical Reinforcement
Area of steel required on inner face = M/σst.jd
Providing 10 mm dia bars at 180 mm c/c top and bottom (437 mm^2) with 10 mm dia 180 c/c
extra (872 mm^2) at bottom inner face.
2
= 358.40 mm
For a rectangular wall for fixed base, free top and subjected to triangular load,
As the moments and shear are less than that of Anoxic tank, providing same section and
reinforcement for the wall and raft.
For a rectangular wall for fixed base, free top and subjected to triangular load,
As the moments and shear are less than that of Anoxic tank, providing same section and
reinforcement for the wall and raft.
For a cylinderical wall for fixed base, free top and subjected to triangular load
Reinforcement calculation
2
Yield strength of reinforcement bar = 500 N/mm
Partial safety factor of steel = 1.15
2
Allowable stress = fy/1.15 = 435 N/mm
Vertical steel
Vertical steel required at inner face = M/σst.jd
Providing 8 mm dia bars at 200 mm c/c both faces (251 mm^2) both faces as vertical steel.
2
Total area of vertical steel provided, Ast = 251 mm
Horizontal steel
Area of steel required, Ast = Tu/ (σst. 2) Hoop tension
2
6.75 x 1e4 = 112.50 mm Both faces
300 x 2
Providing 8 mm dia bars at 200 mm c/c (251 mm^2) both faces as horizontal steel.
2
Total area of horizontal steel provided, Ast = 251 mm
Shear force on wall at the raft level due = 0.17 w.H^2 T-10, IS 3370 (part-IV), 1967
to water pressure 1.53 T
T ult = 1.5T = 2.30 T
Providing 8 mm dia bars at 200 mm c/c top and bottom (251 mm^2) both ways.
εm = ε1 - ε2
ε1 = σ st./Es ( D - x)/d- x)
0.0007
= 0.0024
εm = 0.00074 - 0.0024
= -0.00170
Page 16 of 19
acr = √( 50^2 + 100^2) - 4 c/c of bar = 200 mm
= 107.80 mm
For a rectangular wall for fixed base, free top and subjected to triangular load,
Horizontal Reinforcement
Area of steel required, Ast = Mu/σst.jd + Tu/ (σst. 2)
Providing 8 mm dia bars at 200 mm c/c (251 mm^2) both faces as horizontal steel.
Vertical Reinforcement
Area of steel required on inner face = M/σst.jd
Providing 8 mm dia bars at 200 mm c/c (251 mm^2) both faces as vertical steel with 8 mm
dia bars at 200 mm c/c extra ( 503 mm^2) at bottom inner face.
11 STAIRCASE
RCC staircase is provided between ground level to floor level
RL of ground level = 205 m
RL of floor level = 208.1 m
Page 18 of 19
Difference in elevation, = 3.10 m
Providing Rise of steps = 150 mm & tread of steps =300 mm
max. horizontal span of staircase, = 4.30 m
Loading
2
Dead load of base slab ( 150 thk) = 0.38 T/m
2
Self wt. of steps, 0.15 x 2.5/2 = 0.19 T/m
2
Floor finish = 0.10 T/m
2
Live load on steps = 0.50 T/m
2
Total UDL on slab = 1.21 T/m
2
= 918.0 mm
Providing 16 mm dia baes at 200 mm c/c ( 1005 mm^2) as main steel with 8 mm dia at 200 c/c
as distribution
EIRL VEDANATA
Submission
Prep. Chk. App.
For Approval For Information Revision
AG AS SK √ R0
17.05.2025 17.05.2025 17.05.2025
Page 19 of 19