Trane - NV Series - NTXM - Service Manual - OBHT702 Rev H - 11-2018

Revision H of the service manual includes modifications to the Indoor/Outdoor Unit Compatibility Table, Specification, and Data sections. The document lists various models compatible with specific refrigerants and provides safety precautions for servicing the units. Previous revisions have been voided, and users are warned against using incorrect refrigerants to prevent accidents.

Uploaded by

Michael Martin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
83 views146 pages

Trane - NV Series - NTXM - Service Manual - OBHT702 Rev H - 11-2018

Revision H of the service manual includes modifications to the Indoor/Outdoor Unit Compatibility Table, Specification, and Data sections. The document lists various models compatible with specific refrigerants and provides safety precautions for servicing the units. Previous revisions have been voided, and users are warned against using incorrect refrigerants to prevent accidents.

Uploaded by

Michael Martin
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 146

Revision H:

• INDOOR / OUTDOOR UNITCOMPATIBILITY


TABLE, 4. SPECIFICATION and 9. DATA
have been modified.
OBHT702 REVISED EDITON-G is void.

OUTDOOR UNIT
HFC No. OBHT702
utilized REVISED EDITION-H
SERVICE MANUAL R410A

Models
NTXMMX20A122AA NTXMMX20A122BA NTXMMX20A122CA
NTXMMX20A122AC
NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA

Indoor unit service manual


NT(A)XWPH·A Series (OBHT(A)683) NT(A)XCKS·A Series (OCHT(A)669) T(A)PCA0A·KA Series [TCHT006(7)]
NT(A)X(Y)WST·A Series (OBHT(A)732) T(A)PLA·A·EA Series (OCH(A)T640) N(A)TXAMT·A Series [MD-1404-K042(43)]
NT(A)XWPH·B·AA Series (OBHT(A)872) NT(A)XDKS·A Series [HWE18300(440)]
NT(A)XFKS·A Series (OBHT(A)752) T(A)PEADA·AA Series [HWE19030(40)]

CONTENTS
• INDOOR / OUTDOOR UNIT
COMPATIBILITY TABLE·······················3
1. TECHNICAL CHANGES·······························5
2. SAFETY PRECAUTION································6
3. PART NAMES AND FUNCTIONS················· 10
4. SPECIFICATION······································· 11
5. NOISE CRITERIA CURVES························· 30
6. OUTLINES AND DIMENSIONS···················· 33
7. WIRING DIAGRAM···································· 39
8. REFRIGERANT SYSTEM DIAGRAM············ 57
9. DATA······················································· 70
10. ACTUATOR CONTROL···························· 101
11. SERVICE FUNCTIONS····························· 102
12. TROUBLESHOOTING······························ 105
NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA 13. DISASSEMBLY INSTRUCTIONS················ 134
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA PARTS CATALOG (OBBT702)
Use the specified refrigerant only
Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when the unit is being used, serviced, or disposed of.
Correct refrigerant is specified in the manuals and on the spec labels provided with our products.
We will not be held responsible for mechanical failure, system malfunction, unit breakdown or accidents caused by failure to
follow the instructions.

<Preparation before the repair service>


Prepare the proper tools.
Prepare the proper protectors.
Provide adequate ventilation.
After stopping the operation of the air conditioner, turn off the power-supply breaker and pull the power plug.
Discharge the capacitor before the work involving the electric parts.

<Precautions during the repair service>


Do not perform the work involving the electric parts with wet hands.
Do not pour water into the electric parts.
Do not touch the refrigerant.
Do not touch the hot or cold areas in the refrigeration cycle.
When the repair or the inspection of the circuit needs to be done without turning off the power, exercise great caution not to
touch the live parts.

WARNING
• When the refrigeration circuit has a leak, do not execute pump down with the compressor.
• When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
The compressor may burst if air etc. get into it.
• When opening or closing the valve below freezing temperatures, refrigerant may spurt out from the gap
between the valve stem and the valve body, resulting in injuries.

Revision A:
• NTXWPH·B·AA series have been added to INDOOR / OUTDOOR UNIT COMPATIBILITY TABLE.
• 2. SAFETY PRECAUTION has been added.
• 9-2. CAPACITY AND THE INPUT CURVES has been modified.
• 12. TROUBLESHOOTING has been modified. OBHT702 is void.

Revision B:
• NTXMMX20A122AC has been added.

Revision C:
• NTXMMX20A122BA, NTXMMX24A132BA, NTXMMX30A132BA, NTXMMX36A142BA, NTXMMX42A152BA,
NTXMPH20A122BA, NTXMPH24A132BA and NTXMPH30A132BA has been added.

Revision D:
• Models of refrigeration oil for NTXMMX24/30A132BA, NTXMMX36A142BA, NTXMMX42A152BA, NTXMPH20A122BA and
NTXMPH24/30A132BA at 4. SPECIFICATION have been added.

Revision E:
• NTXMMX20A122CA, NTXMMX24A132CA, NTXMMX30A132CA, NTXMMX36A142CA, NTXMMX42A152CA,
NTXMPH20A122CA, NTXMPH24A132CA and NTXMPH30A132CA have been added.

Revision F:
• 1. TECHNICAL CHANGES has been corrected.
Descriptions of technical changes for NTXMMX20A122CA, NTXMMX24A132CA, NTXMMX30A132CA, NTXMMX36A142CA,
NTXMMX42A152CA, NTXMPH20A122CA, NTXMPH24A132CA and NTXMPH30A132CA have been corrected.
• 4. SPECIFICATION has been corrected.
Specifications of NTXMMX20A122CA, NTXMMX24A132CA, NTXMMX30A132CA have been corrected.

Revision G:
• INDOOR / OUTDOOR UNIT COMPATIBILITY TABLE, 4. SPECIFICATION and 9. DATA have been modified.

Revision H:
• INDOOR / OUTDOOR UNITCOMPATIBILITY TABLE, 4. SPECIFICATION and 9. DATA have been modified.

OBHT702H 2
INDOOR / OUTDOOR UNIT COMPATIBILITY TABLE
<NTXMMX20A122AA NTXMMX20A122AC> <NTXMMX42A152AA>
Connectable indoor unit lineups (Heat pump inverter type) Connectable indoor unit lineups (Heat pump inverter type)
Capacity class [kBTU/h] Capacity class [kBTU/h]
Model type Model name Model type Model name
06 09 12 15 18 24 30 36 06 09 12 15 18 24 30 36
NTXWPH**A112AA ● ● ● ● NTXWPH**A112AA ● ● ● ● ●
Wall mounted NTXWPH**B112AA ● ● ● ● Wall mounted NTXWPH**B112AA ● ● ● ● ●
NTXWST**A112AA ● ● ● ● NTXWST**A112AA ● ● ● ● ● ●
Floor standing NTXFKS**A112AA ● ● ● Floor standing NTXFKS**A112AA ● ● ● ●
NTXCKS**A112AA ● ● NTXCKS**A112AA ● ● ●
4-way cassette 4-way cassette
PLA-A**EA7 PLA-A**EA7 ●
NTXDKS**A112AA ● ● ● NTXDKS**A112AA ● ● ● ●
Ceiling concealed Ceiling concealed
TPEADA0**AA80* ● ● TPEADA0**AA80* ● ● ● ● ●
Ceiling suspended PCA-A**KA6.TH Ceiling suspended PCA-A**KA6.TH ●
Multi-position NTXAMT**A112AA ● Multi-position NTXAMT**A112AA ● ● ●

<NTXMMX24A132AA> <NTXMPH20A122AA>
Connectable indoor unit lineups (Heat pump inverter type) Connectable indoor unit lineups (Heat pump inverter type)
Capacity class [kBTU/h] Capacity class [kBTU/h]
Model type Model name Model type Model name
06 09 12 15 18 24 30 36 06 09 12 15 18 24 30 36
NTXWPH**A112AA ● ● ● ● ● NTXWPH**A112AA ● ● ● ●
Wall mounted NTXWPH**B112AA ● ● ● ● ● Wall mounted NTXWPH**B112AA ● ● ● ●
NTXWST**A112AA ● ● ● ● ● NTXWST**A112AA ● ● ● ●
Floor standing NTXFKS**A112AA ● ● ● ● Floor standing NTXFKS**A112AA ● ● ●
NTXCKS**A112AA ● ● ● NTXCKS**A112AA ● ●
4-way cassette 4-way cassette
PLA-A**EA7 ● PLA-A**EA7
NTXDKS**A112AA ● ● ● ● NTXDKS**A112AA ● ● ●
Ceiling concealed Ceiling concealed
TPEADA0**AA80* ● ● ● ● TPEADA0**AA80* ● ●
Ceiling suspended PCA-A**KA6.TH Ceiling suspended PCA-A**KA6.TH
Multi-position NTXAMT**A112AA ● ● Multi-position NTXAMT**A112AA ●

<NTXMMX30A132AA> <NTXMPH24A132AA>
Connectable indoor unit lineups (Heat pump inverter type) Connectable indoor unit lineups (Heat pump inverter type)
Capacity class [kBTU/h] Capacity class [kBTU/h]
Model type Model name Model type Model name
06 09 12 15 18 24 30 36 06 09 12 15 18 24 30 36
NTXWPH**A112AA ● ● ● ● ● NTXWPH**A112AA ● ● ● ● ●
Wall mounted NTXWPH**B112AA ● ● ● ● ● Wall mounted NTXWPH**B112AA ● ● ● ● ●
NTXWST**A112AA ● ● ● ● ● ● NTXWST**A112AA ● ● ● ● ●
Floor standing NTXFKS**A112AA ● ● ● ● Floor standing NTXFKS**A112AA ● ● ● ●
NTXCKS**A112AA ● ● ● NTXCKS**A112AA ● ● ●
4-way cassette 4-way cassette
PLA-A**EA7 ● PLA-A**EA7 ●
NTXDKS**A112AA ● ● ● ● NTXDKS**A112AA ● ● ● ●
Ceiling concealed Ceiling concealed
TPEADA0**AA80* ● ● ● ● ● TPEADA0**AA80* ● ● ● ●
Ceiling suspended PCA-A**KA6.TH ● Ceiling suspended PCA-A**KA6.TH
Multi-position NTXAMT**A112AA ● ● ● Multi-position NTXAMT**A112AA ● ●

<NTXMMX36A142AA> <NTXMPH30A132AA>
Connectable indoor unit lineups (Heat pump inverter type) Connectable indoor unit lineups (Heat pump inverter type)
Capacity class [kBTU/h] Capacity class [kBTU/h]
Model type Model name Model type Model name
06 09 12 15 18 24 30 36 06 09 12 15 18 24 30 36
NTXWPH**A112AA ● ● ● ● ● NTXWPH**A112AA ● ● ● ● ●
Wall mounted NTXWPH**B112AA ● ● ● ● ● Wall mounted NTXWPH**B112AA ● ● ● ● ●
NTXWST**A112AA ● ● ● ● ● ● NTXWST**A112AA ● ● ● ● ● ●
Floor standing NTXFKS**A112AA ● ● ● ● Floor standing NTXFKS**A112AA ● ● ● ●
NTXCKS**A112AA ● ● ● NTXCKS**A112AA ● ● ●
4-way cassette 4-way cassette
PLA-A**EA7 ● PLA-A**EA7 ●
NTXDKS**A112AA ● ● ● ● NTXDKS**A112AA ● ● ● ●
Ceiling concealed Ceiling concealed
TPEADA0**AA80* ● ● ● ● ● TPEADA0**AA80* ● ● ● ● ●
Ceiling suspended PCA-A**KA6.TH ● Ceiling suspended PCA-A**KA6.TH ●
Multi-position NTXAMT**A112AA ● ● ● Multi-position NTXAMT**A112AA ● ● ●

OBHT702H 3
<NTXMMX20A122BA NTXMMX20A122CA <NTXMMX42A152BA NTXMMX42A152CA>
Connectable indoor unit lineups (Heat pump inverter type) Connectable indoor unit lineups (Heat pump inverter type)
Model type Model name Model name Capacity class [kBTU/h] Model type Model name Model name Capacity class [kBTU/h]
(Trane) (American Standard) 06 09 12 15 18 24 30 36 (Trane) (American Standard) 06 09 12 15 18 24 30 36
Wall mounted NTXWPH**A112A* NAXWPH**A112A* ● ● ● ● Wall mounted NTXWPH**A112A* NAXWPH**A112A* ● ● ● ● ●
NTXWPH**B112A* NAXWPH**B112A* ● ● ● ● NTXWPH**B112A* NAXWPH**B112A* ● ● ● ● ●
NTXWST**A112A* NAXWST**A112A* ● ● ● ● NTXWST**A112A* NAXWST**A112A* ● ● ● ● ● ●
NTXWST**B112A* NAXWST**B112A* ● ● ● ● NTXWST**B112A* NAXWST**B112A* ● ● ● ● ● ●
Floor standing NTXFKS**A112A* NAXFKS**A112A* ● ● ● Floor standing NTXFKS**A112A* NAXFKS**A112A* ● ● ● ●
4-way cassette NTXCKS**A112A* NAXCKS**A112A* ● ● 4-way cassette NTXCKS**A112A* NAXCKS**A112A* ● ● ●
TPLA0A0**1EA70* APLA0A0**1EA70* TPLA0A0**1EA70* APLA0A0**1EA70* ●
1-way cassette NTXUKS**A112A* NAXUKS**A112A* ● ● 1-way cassette NTXUKS**A112A* NAXUKS**A112A* ● ● ●
NTXUKS**A112B* - ● ● NTXUKS**A112B* - ● ● ●
NTXUKS**A112A* - ● NTXUKS**A112A* - ●
Ceiling NTXDKS**A112A* NAXDKS**A112A* ● ● ● Ceiling NTXDKS**A112A* NAXDKS**A112A* ● ● ● ●
concealed TPEADA0**1AA80* APEADA0**1AA80* ● ● concealed TPEADA0**1AA80* APEADA0**1AA80* ● ● ● ● ●
Ceiling Ceiling
TPCA0A***1KA70* APCA0A***1KA70* TPCA0A***1KA70* APCA0A***1KA70* ●
suspended suspended
Multi-position NTXAMT**A112A* NAXAMT**A112A* ● Multi-position NTXAMT**A112A* NAXAMT**A112A* ● ● ●

<NTXMMX24A132BA NTXMMX24A132CA> <NTXMPH20A122BA NTXMPH20A122CA>


Connectable indoor unit lineups (Heat pump inverter type) Connectable indoor unit lineups (Heat pump inverter type)
Model type Model name Model name Capacity class [kBTU/h] Model type Model name Model name Capacity class [kBTU/h]
(Trane) (American Standard) 06 09 12 15 18 24 30 36 (Trane) (American Standard) 06 09 12 15 18 24 30 36
Wall mounted NTXWPH**A112A* NAXWPH**A112A* ● ● ● ● ● Wall mounted NTXWPH**A112A* NAXWPH**A112A* ● ● ● ●
NTXWPH**B112A* NAXWPH**B112A* ● ● ● ● ● NTXWPH**B112A* NAXWPH**B112A* ● ● ● ●
NTXWST**A112A* NAXWST**A112A* ● ● ● ● ● NTXWST**A112A* NAXWST**A112A* ● ● ● ●
NTXWST**B112A* NAXWST**B112A* ● ● ● ● ● NTXWST**B112A* NAXWST**B112A* ● ● ● ●
Floor standing NTXFKS**A112A* NAXFKS**A112A* ● ● ● ● Floor standing NTXFKS**A112A* NAXFKS**A112A* ● ● ●
4-way cassette NTXCKS**A112A* NAXCKS**A112A* ● ● ● 4-way cassette NTXCKS**A112A* NAXCKS**A112A* ● ●
TPLA0A0**1EA70* APLA0A0**1EA70* ● TPLA0A0**1EA70* APLA0A0**1EA70*
1-way cassette NTXUKS**A112A* NAXUKS**A112A* ● ● ● 1-way cassette NTXUKS**A112A* NAXUKS**A112A* ● ●
NTXUKS**A112B* - ● ● ● NTXUKS**A112B* - ● ●
NTXUKS**A112A* - ● NTXUKS**A112A* - ●
Ceiling NTXDKS**A112A* NAXDKS**A112A* ● ● ● ● Ceiling NTXDKS**A112A* NAXDKS**A112A* ● ● ●
concealed TPEADA0**1AA80* APEADA0**1AA80* ● ● ● ● concealed TPEADA0**1AA80* APEADA0**1AA80* ● ●
Ceiling Ceiling
TPCA0A***1KA70* APCA0A***1KA70* TPCA0A***1KA70* APCA0A***1KA70*
suspended suspended
Multi-position NTXAMT**A112A* NAXAMT**A112A* ● ● Multi-position NTXAMT**A112A* NAXAMT**A112A* ●

<NTXMMX30A132BA NTXMMX30A132CA> <NTXMPH30A132BA NTXMPH30A132CA>


Connectable indoor unit lineups (Heat pump inverter type) Connectable indoor unit lineups (Heat pump inverter type)
Model type Model name Model name Capacity class [kBTU/h] Model type Model name Model name Capacity class [kBTU/h]
(Trane) (American Standard) 06 09 12 15 18 24 30 36 (Trane) (American Standard) 06 09 12 15 18 24 30 36
Wall mounted NTXWPH**A112A* NAXWPH**A112A* ● ● ● ● ● Wall mounted NTXWPH**A112A* NAXWPH**A112A* ● ● ● ● ●
NTXWPH**B112A* NAXWPH**B112A* ● ● ● ● ● NTXWPH**B112A* NAXWPH**B112A* ● ● ● ● ●
NTXWST**A112A* NAXWST**A112A* ● ● ● ● ● ● NTXWST**A112A* NAXWST**A112A* ● ● ● ● ● ●
NTXWST**B112A* NAXWST**B112A* ● ● ● ● ● ● NTXWST**B112A* NAXWST**B112A* ● ● ● ● ● ●
Floor standing NTXFKS**A112A* NAXFKS**A112A* ● ● ● ● Floor standing NTXFKS**A112A* NAXFKS**A112A* ● ● ● ●
4-way cassette NTXCKS**A112A* NAXCKS**A112A* ● ● ● 4-way cassette NTXCKS**A112A* NAXCKS**A112A* ● ● ●
TPLA0A0**1EA70* APLA0A0**1EA70* ● TPLA0A0**1EA70* APLA0A0**1EA70* ●
1-way cassette NTXUKS**A112A* NAXUKS**A112A* ● ● ● 1-way cassette NTXUKS**A112A* NAXUKS**A112A* ● ● ●
NTXUKS**A112B* - ● ● ● NTXUKS**A112B* - ● ● ●
NTXUKS**A112A* - ● NTXUKS**A112A* - ●
Ceiling NTXDKS**A112A* NAXDKS**A112A* ● ● ● ● Ceiling NTXDKS**A112A* NAXDKS**A112A* ● ● ● ●
concealed TPEADA0**1AA80* APEADA0**1AA80* ● ● ● ● ● concealed TPEADA0**1AA80* APEADA0**1AA80* ● ● ● ● ●
Ceiling Ceiling
TPCA0A***1KA70* APCA0A***1KA70* ● TPCA0A***1KA70* APCA0A***1KA70* ●
suspended suspended
Multi-position NTXAMT**A112A* NAXAMT**A112A* ● ● ● Multi-position NTXAMT**A112A* NAXAMT**A112A* ● ● ●

<NTXMMX36A142BA NTXMMX36A142CA> <NTXMPH24A132BA NTXMPH24A132CA>


Connectable indoor unit lineups (Heat pump inverter type) Connectable indoor unit lineups (Heat pump inverter type)
Model type Model name Model name Capacity class [kBTU/h] Model type Model name Model name Capacity class [kBTU/h]
(Trane) (American Standard) 06 09 12 15 18 24 30 36 (Trane) (American Standard) 06 09 12 15 18 24 30 36
Wall mounted NTXWPH**A112A* NAXWPH**A112A* ● ● ● ● ● Wall mounted NTXWPH**A112A* NAXWPH**A112A* ● ● ● ● ●
NTXWPH**B112A* NAXWPH**B112A* ● ● ● ● ● NTXWPH**B112A* NAXWPH**B112A* ● ● ● ● ●
NTXWST**A112A* NAXWST**A112A* ● ● ● ● ● ● NTXWST**A112A* NAXWST**A112A* ● ● ● ● ●
NTXWST**B112A* NAXWST**B112A* ● ● ● ● ● ● NTXWST**B112A* NAXWST**B112A* ● ● ● ● ●
Floor standing NTXFKS**A112A* NAXFKS**A112A* ● ● ● ● Floor standing NTXFKS**A112A* NAXFKS**A112A* ● ● ● ●
4-way cassette NTXCKS**A112A* NAXCKS**A112A* ● ● ● 4-way cassette NTXCKS**A112A* NAXCKS**A112A* ● ● ●
TPLA0A0**1EA70* APLA0A0**1EA70* ● TPLA0A0**1EA70* APLA0A0**1EA70* ●
1-way cassette NTXUKS**A112A* NAXUKS**A112A* ● ● ● 1-way cassette NTXUKS**A112A* NAXUKS**A112A* ● ● ●
NTXUKS**A112B* - ● ● ● NTXUKS**A112B* - ● ● ●
NTXUKS**A112A* - ● NTXUKS**A112A* - ●
Ceiling NTXDKS**A112A* NAXDKS**A112A* ● ● ● ● Ceiling NTXDKS**A112A* NAXDKS**A112A* ● ● ● ●
concealed TPEADA0**1AA80* APEADA0**1AA80* ● ● ● ● ● concealed TPEADA0**1AA80* APEADA0**1AA80* ● ● ● ●
Ceiling Ceiling
TPCA0A***1KA70* APCA0A***1KA70* ● TPCA0A***1KA70* APCA0A***1KA70*
suspended suspended
Multi-position NTXAMT**A112A* NAXAMT**A112A* ● ● ● Multi-position NTXAMT**A112A* NAXAMT**A112A* ● ●

OBHT702H 4
See the table below for connection restrictions.
No. BA CA
(1) ― ○
(2) ○ ○
(3) ○ ○
(4) ○ ―

(1) : Up to two NT/AXAMT units can be connected. (The total maximum number of connections is two when connected two NT/
AXAMT units.)
When you connect one NT/AXAMT unit, there is no limit on the total number of connections.
(2) : NT/AXAMT unit and T/APEADA unit cannot be connected in the same system.
(3) : Maximum of two T/APEADA units can be connected.
(4) : Only one NT/AXAMT unit can be connected.

1 TECHNICAL CHANGES

NTXMMX20A122AA
NTXMMX24A132AA
NTXMMX30A132AA
NTXMMX36A142AA
NTXMMX42A152AA
NTXMPH20A122AA
NTXMPH24A132AA
NTXMPH30A132AA
1. New model

NTXMMX20A122AA NTXMMX20A122AC
1. Outdoor fan motor has been changed.
2. Outdoor control P.C. board has been changed.

NTXMMX20A122AC NTXMMX20A122BA
NTXMMX24A132AA NTXMMX24A132BA
NTXMMX30A132AA NTXMMX30A132BA
NTXMMX36A142AA NTXMMX36A142BA
NTXMMX42A152AA NTXMMX42A152BA
NTXMPH20A122AA NTXMPH20A122BA
NTXMPH24A132AA NTXMPH24A132BA
NTXMPH30A132AA NTXMPH30A132BA
1. Outdoor fan motor has been changed.
2. Outdoor control P.C. board has been changed.

NTXMMX20A122BA NTXMMX20A122CA
NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142BA NTXMMX36A142CA
NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132BA NTXMPH30A132CA
1. Outdoor control P.C. board has been changed.

OBHT702H 5
2 SAFETY PRECAUTION

2-1. ALWAYS OBSERVE FOR SAFETY


Before obtaining access to terminal, all supply circuit must be disconnected.

Preparation before the repair service Precautions during the repair service
• Prepare the proper tools. • Do not perform the work involving the electric parts with
• Prepare the proper protectors. wet hands.
• Provide adequate ventilation. • Do not pour water into electric parts.
• After stopping the operation of the air conditioner, turn off • Do not touch the refrigerant.
the power-supply breaker. • Do not touch the hot or cold areas in the refrigerating
• Discharge the condenser before the work involving the cycle.
electric parts. • When the repair or the inspection of the circuit needs
to be done without turning off the power, exercise great
caution not to touch the live parts.
• When opening or closing the valve below freezing
temperatures, refrigerant may spurt out from the gap
between the valve stem and the valve body, resulting in
injuries.

2-2. CAUTIONS RELATED TO R410A REFRIGERANT


Cautions for units utilizing refrigerant R410A
Make sure that the inside and outside of refriger- Use the following tools specifically designed for
ant piping is clean and it has no contaminants use with R410A refrigerant.
such as sulfur, oxides, dirt, shaving particles, etc., The following tools are necessary to use R410A refrigerant.
which are hazard to refrigerant cycle.
Tools for R410A
In addition, use pipes with specified thickness.
Gauge manifold Flare tool
Contamination inside refrigerant piping can cause deterio- Charge hose Size adjustment gauge
ration of refrigerant oil, etc.
Gas leak detector Vacuum pump adaptor
Torque wrench Electronic refrigerant
Store the piping indoors, and keep both ends of
charging scale
the piping sealed until just before brazing.
(Leave elbow joints, etc. in their packaging.)
If dirt, dust or moisture enters into refrigerant cycle, that can cause Handle tools with care.
deterioration of refrigerant oil or malfunction of compressor.
If dirt, dust or moisture enters into refrigerant cycle, that can
cause deterioration of refrigerant oil or malfunction of
The refrigerant oil applied to flare and flange
compressor.
connections must be ester oil, ether oil or
alkylbenzene oil in a small amount.
Use the specified refrigerant only.
If large amount of mineral oil enters, that can cause deterio-
ration of refrigerant oil, etc. Never use any refrigerant other than that specified.
Doing so may cause a burst, an explosion, or fire when
Charge refrigerant from liquid phase of gas the unit is being used, serviced, or disposed of.
cylinder. Correct refrigerant is specified in the manuals and on the
If the refrigerant is charged from gas phase, composition spec labels provided with our products.
change may occur in refrigerant and the efficiency will be We will not be held responsible for mechanical failure,
lowered. system malfunction, unit breakdown or accidents caused
by failure to follow the instructions.

Do not use refrigerant other than R410A.


Do not use a charging cylinder.
If other refrigerant (R22, etc.) is used, chlorine in refrigerant
can cause deterioration of refrigerant oil, etc. If a charging cylinder is used, the composition of refriger-
ant will change and the efficiency will be lowered.
Use a vacuum pump with a reverse flow check
valve. Ventilate the room if refrigerant leaks during
operation. If refrigerant comes into contact with
Vacuum pump oil may flow back into refrigerant cycle and
a flame, poisonous gases will be released.
that can cause deterioration of refrigerant oil, etc.

OBHT702H 6
[1] Cautions for service
(1) Perform service after recovering the refrigerant left in unit completely.
(2) Do not release refrigerant in the air.
(3) After completing service, charge the cycle with specified amount of refrigerant.
(4) If moisture or foreign matter might have entered the refrigerant piping during service, ensure to remove them.

[2] Additional refrigerant charge


When charging directly from cylinder
(1) Check that cylinder for R410A on the market is a siphon type.
(2) Charging should be performed with the cylinder of siphon stood vertically. (Refrigerant is charged from liquid phase.)

Unit

Electronic weighing scale

[3] Service tools


(1) Use the below service tools as exclusive tools for R410A refrigerant.

No. Tool name Specifications


1 Gauge manifold ·Only for R410A
·Use the existing fitting specifications. (UNF1/2)
·Use high-tension side pressure of 768.7 PSIG [5.3 MPaG] or over.
2 Charge hose ·Only for R410A
·Use pressure performance of 738.2 PSIG [5.09MPaG] or over.
3 Electronic weighing scale —
4 Gas leak detector ·Use the detector for R134a, R407C or R410A.
5 Adaptor for reverse flow check ·Attach on vacuum pump.
6 Refrigerant charge base —
7 Refrigerant cylinder ·Only for R410A
·Top of cylinder (Pink)
·Cylinder with siphon
8 Refrigerant recovery equipment —

OBHT702H 7
2-3. Cautions for refrigerant piping work
Refrigerant R410A is adopted for replacement inverter series. Although the refrigerant piping work for R410A is the same as for
R22, exclusive tools are necessary so as not to mix with different kind of refrigerant. Furthermore as the working pressure of
R410A is 1.6 times higher than that of R22, their sizes of flared sections and flare nuts are different.
Thickness of pipes
Since the working pressure of R410A is higher compared to R22, be sure to use refrigerant piping with thickness shown below.
(Never use pipes of 7/256 in [0.7 mm] or below.)
Diagram below: Piping diameter and thickness
Nominal Outside Thickness: in [mm]
dimensions (inch) diameter (mm) R410A R22
1/4 6.35 1/32 [0.8] 1/32 [0.8]
3/8 9.52 1/32 [0.8] 1/32 [0.8]
1/2 12.70 1/32 [0.8] 1/32 [0.8]
5/8 15.88 5/128 [1.0] 5/128 [1.0]
3/4 19.05 — 5/128 [1.0]

Dimensions of flare cutting and flare nut


The component molecules in HFC refrigerant are smaller compared to conventional refrigerants. In addition to that, R410A is
a refrigerant, which has higher risk of leakage because its working pressure is higher than that of other refrigerants. Therefore,
to enhance airtightness and strength, flare cutting dimension of copper pipe for R410A has been specified separately from the
dimensions for other refrigerants as shown below. The dimension B of flare nut for R410A also has partly been changed to
increase strength as shown below. Set copper pipe correctly referring to copper pipe flaring dimensions for R410A below. For
1/2 and 5/8 inch pipes, the dimension B changes.
Use torque wrench corresponding to each dimension.

Dimension A

Dimension B

Flare cutting dimensions Unit: in [mm] Flare nut dimensions Unit: in [mm]
Nominal Outside Dimension A (+0
-0.4 ) Nominal Outside Dimension B
dimensions (in) diameter (mm) R410A R22 dimensions (in) diameter (mm) R410A R22
1/4 6.35 11/32-23/64 [9.1] 9.0 1/4 6.35 43/64 [17.0] 17.0
3/8 9.52 1/2-33/64 [13.2] 13.0 3/8 9.52 7/8 [22.0] 22.0
1/2 12.70 41/64-21/32 [16.6] 16.2 1/2 12.70 1-3/64 [26.0] 24.0
5/8 15.88 49/64-25/32 [19.7] 19.4 5/8 15.88 1-9/64 [29.0] 27.0
3/4 19.05 — 23.3 3/4 19.05 — 36.0

OBHT702H 8
Tools for R410A (The following table shows whether conventional tools can be used or not.)
Tools and materials Use R410A tools Can R22 tools be used? Can R407C tools be used?
Gauge manifold Air purge, refrigerant charge Tool exclusive for R410A
Charge hose and operation check Tool exclusive for R410A
Gas leak detector Gas leak check Tool for HFC refrigerant
Refrigerant recovery equipment Refrigerant recovery Tool exclusive for R410A
Refrigerant cylinder Refrigerant charge Tool exclusive for R410A
Ester oil, ether oil and Ester oil, ether oil:
Applied oil Apply to flared section alkylbenzene oil Alkylbenzene oil:
(minimum amount) minimum amount
Prevent compressor malfunction
Safety charger when charging refrigerant by Tool exclusive for R410A
spraying liquid refrigerant
Prevent gas from blowing out
Charge valve Tool exclusive for R410A
when detaching charge hose
Tools for other refrigerants can be
Vacuum drying and air (Usable if equipped with (Usable if equipped with
Vacuum pump used if equipped with adopter for
purge adopter for reverse flow) adopter for reverse flow)
reverse flow check
Tools for other refrigerants can be (Usable by adjusting (Usable by adjusting
Flare tool Flaring work of piping
used by adjusting flaring dimension flaring dimension) flaring dimension)
Bender Bend the pipes Tools for other refrigerants can be used
Pipe cutter Cut the pipes Tools for other refrigerants can be used
Welder and nitrogen gas cylinder Weld the pipes Tools for other refrigerants can be used
Refrigerant charging scale Refrigerant charge Tools for other refrigerants can be used
Check the degree of vacuum.
Vacuum gauge or
(Vacuum valve prevents back Tools for other refrigerants
thermistor vacuum
flow of oil and refrigerant to can be used
gauge and vacuum valve
thermistor vacuum gauge)
Charging cylinder Refrigerant charge Tool exclusive for R410A ─
: Prepare a new tool. (Use the new tool as the tool exclusive for R410A.)
: Tools for other refrigerants can be used under certain conditions.
: Tools for other refrigerants can be used.

OBHT702H 9
3 PART NAMES AND FUNCTIONS

NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA


Air inlet
(Back and side)

Air outlet

Drain outlet

NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA


NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
Air inlet
(Back and side)

Air outlet

Drain outlet

NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA


NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
Air inlet
(Back and side)

Air outlet

Drain outlet

OBHT702H 10
4 SPECIFICATION

Outdoor model NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA


Item
Indoor type Non-Duct (09+09) Duct (09+12)
Cooling *1 Btu/h 18,000 20,000
Capacity Heating 47 *1 Btu/h 22,000 22,000
Heating 17 *2 Btu/h 15,500 14,500
Cooling *1 W 1,417 2,000
Power
Heating 47 *1 W 1,641 1,771
consumption
Heating 17 *2 W 1,750 1,810
EER Cooling 12.7 10.0
SEER Cooling 20.0 16.0
HSPF IV(V) Heating 10.0 9.3
COP Heating 3.93 3.64
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 20
Min. circuit ampacity A 17.2
Fan motor F.L.A 1.77
Model SNB140FQUH2T
Winding resistance
Ω U-V1.99 V-W 1.99 W-U 1.99
Compressor (at 68 °F)
R.L.A 10.7
L.R.A 15.5
Refrigerant control LEV
Sound level dB(A) 50/54
Defrost method Reverse cycle
W in. 33-1/16
Dimensions D in. 13
H in. 27-15/16
Weight lb. 126
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12 - 24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 5 lb. 15 oz.
Refrigeration oil (Model) fl oz. (L) 20.3 (0.6) (NEO22)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 11
Outdoor model NTXMMX20A122CA
Item
Indoor type Non-Duct (09+09) Duct (09+12)
Cooling *1 Btu/h 18,000 20,000
Capacity Heating 47 *1 Btu/h 22,000 22,000
Heating 17 *2 Btu/h 15,500 14,500
Cooling *1 W 1,417 2,000
Power
Heating 47 *1 W 1,641 1,771
consumption
Heating 17 *2 W 1,750 1,810
EER Cooling 12.7 10.0
EER2 Cooling 12.7 10.0
SEER Cooling 20.0 16.0
SEER2 Cooling 20.0 16.0
HSPF IV(V) Heating 10.0 9.3
HSPF2 IV(V) Heating 9.7(7.5) 9.1 (7.5)
COP Heating 3.93 3.64
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 20
Min. circuit ampacity A 17.2
Fan motor F.L.A 1.77
Model SNB140FQUH2T
Winding resistance
Ω U-V1.99 V-W 1.99 W-U 1.99
Compressor (at 68 °F)
R.L.A 10.7
L.R.A 15.5
Refrigerant control LEV
Sound level dB(A) 50/54
Defrost method Reverse cycle
W in. 33-1/16
Dimensions D in. 13
H in. 27-15/16
Weight lb. 126
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12 - 24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 5 lb. 15 oz.
Refrigeration oil (Model) fl oz. (L) 20.3 (0.6) (NEO22)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 12
Outdoor model NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132BA
Item
Indoor type Non-Duct (06+09+09) Duct (09+09+09) Duct (12+12)
Cooling *1 Btu/h 22,000 23,600 23,600
Capacity Heating 47 *1 Btu/h 25,000 24,600 24,000
Heating 17 *2 Btu/h 19,600 19,600 19,600
Cooling *1 W 1,620 2,100 2,195
Power
Heating 47 *1 W 1,750 1,900 1,890
consumption
Heating 17 *2 W 2,580 2,440 2,773
EER Cooling 13.6 11.2 ―
EER2 Cooling BA: 13.6 ― 10.75
SEER Cooling 20.0 16.0 ―
SEER2 Cooling BA: 20.0 ― 15.0
HSPF IV(V) Heating 10.0 (7.6) 9.2 (7.6) ―
HSPF2 IV(V) Heating BA: 9.5 (7.4) ― 7.9 (6.6)
COP Heating 4.20 3.80 3.72
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 25
Min. circuit ampacity A 22.1
Fan motor F.L.A 2.43
Model SNB220FQGMC
Winding resistance
Ω U-V 0.95 V-W 0.95 W-U 0.95
Compressor (at 68 °F)
R.L.A 12
L.R.A 13.7
Refrigerant control LEV
Sound level dB(A) 51/55
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 31-11/32
Weight lb. 137
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A:1/2 B,C:3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 6lb. 13oz.
Refrigeration oil (Model) fl oz. (L) 23.7 (0.7) AA: (FV50S) / BA: (FV50S/FW68S)
NOTE: Test conditions are based on AHRI 210/240.

OBHT702H 13
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 14
Outdoor model NTXMMX24A132CA
Item
Indoor type Non-Duct (06+09+09) Duct(09+09+09) Duct (12+12)
Cooling *1 Btu/h 22,000 23,600 23,600
Capacity Heating 47 *1 Btu/h 25,000 24,600 24,000
Heating 17 *2 Btu/h 21,000 19,600 21,000
Cooling *1 W 1,610 2,100 2,107
Power
Heating 47 *1 W 1,740 1,890 1,851
consumption
Heating 17 *2 W 2,860 2,440 2,960
EER Cooling 13.60 11.20 ―
EER2 Cooling 13.60 ― 11.20
SEER Cooling 20.00 15.80 ―
SEER2 Cooling 20.00 ― 16.00
HSPF IV(V) Heating 10.00 (7.60) 9.20 ―
HSPF2 IV(V) Heating 10.00 (7.60) ― 8.60 (7.50)
COP Heating 4.20 3.80 3.80
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 25
Min. circuit ampacity A 22.1
Fan motor F.L.A 2.43
Model SNB220FCGMC
Winding resistance
Ω U-V 0.95 V-W 0.95 W-U 0.95
Compressor (at 68 °F)
R.L.A 12
L.R.A 13.7
Refrigerant control LEV
Sound level dB(A) 51/55
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 31-11/32
Weight lb. 142
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A:1/2 B,C:3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 6lb. 13oz.
Refrigeration oil (Model) fl oz. (L) 23.7 (0.7) (FV50S/FW68S)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 15
Outdoor model NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132BA
Item
Indoor type Non-Duct (09+09+12) Duct (09+09+12) Duct (15+15)
Cooling *1 Btu/h 28,400 27,400 27,400
Capacity Heating 47 *1 Btu/h 28,600 27,600 27,600
Heating 17 *2 Btu/h 21,000 21,000 21,000
Cooling *1 W 2,680 2,840 2,840
Power
Heating 47 *1 W 2,150 2,220 2,200
consumption
Heating 17 *2 W 2,740 2,820 3,540
EER Cooling 10.6 9.65 ―
EER2 Cooling BA: 10.6 ― 9.65
SEER Cooling 19.0 16.2 ―
SEER2 Cooling BA: 19.0 ― 15.4
HSPF IV(V) Heating 10.6 (8.0) 9.6 (8.0) ―
HSPF2 IV(V) Heating BA: 9.3 (7.4) ― 8.8 (7.0)
COP Heating 3.90 3.64 3.64
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 25
Min. circuit ampacity A 22.1
Fan motor F.L.A 2.43
Model SNB220FQGMC
Winding resistance
Ω U-V 0.95 V-W 0.95 W-U 0.95
Compressor (at 68 °F)
R.L.A 12
L.R.A 13.7
Refrigerant control LEV
Sound level dB(A) 52/56
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 31-11/32
Weight lb. 137
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A:1/2 B,C:3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 6lb. 13oz.
Refrigeration oil (Model) fl oz. (L) 23.7 (0.7) AA: (FV50S) / BA:(FV50S/FW68S)
NOTE: Test conditions are based on AHRI 210/240.

OBHT702H 16
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 17
Outdoor model NTXMMX30A132CA
Item
Indoor type Non-Duct (09+09+12) Duct(09+09+12) Duct (18+18)
Cooling *1 Btu/h 28,400 27,400 27,400
Capacity Heating 47 *1 Btu/h 28,600 27,600 27,600
Heating 17 *2 Btu/h 21,000 21,000 21,000
Cooling *1 W 2,670 2,840 2,854
Power
Heating 47 *1 W 2,149 2,220 2,247
consumption
Heating 17 *2 W 2,860 2,960 2,960
EER Cooling 10.60 9.60 ―
EER2 Cooling 10.60 ― 9.60
SEER Cooling 19.00 16.20 ―
SEER2 Cooling 19.00 ― 16.20
HSPF IV(V) Heating 10.60 9.60 ―
HSPF2 IV(V) Heating 10.00 (7.90) ― 8.80 (7.00)
COP Heating 3.90 3.60 3.60
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 25
Min. circuit ampacity A 22.1
Fan motor F.L.A 2.43
Model SNB220FCGMC
Winding resistance
Ω U-V 0.95 V-W 0.95 W-U 0.95
Compressor (at 68 °F)
R.L.A 12
L.R.A 13.7
Refrigerant control LEV
Sound level dB(A) 52/56
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 31-11/32
Weight lb. 142
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A:1/2 B,C:3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 6lb. 13oz.
Refrigeration oil (Model) fl oz. (L) 23.7 (0.7) (FV50S/FW68S)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 18
Outdoor model NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142BA
Item
Indoor type Non-Duct (09+09+09+09) Duct (09+09+09+09) Duct(18+18)
Cooling *1 Btu/h 35,400 34,400 33,400
Capacity Heating 47 *1 Btu/h 36,000 34,400 34,400
Heating 17 *2 Btu/h 26,600 26,600 24,400
Cooling *1 W 3,760 3,940 3,839
Power
Heating 47 *1 W 3,020 3,100 3,100
consumption
Heating 17 *2 W 3,440 3,540 3,540
EER Cooling 9.4 8.7 ―
EER2 Cooling BA: 9.4 ― 8.7
SEER Cooling 19.2 16.0 ―
SEER2 Cooling BA: 19.2 ― 14.9
HSPF IV(V) Heating 11.0 (8.4) 9.8 (8.4) ―
HSPF2 IV(V) Heating BA: 9.8 (7.8) ― 8.5(7.0)
COP Heating 3.50 3.25 3.25
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 25
Min. circuit ampacity A 23.1
Fan motor F.L.A 2.43
Model SNB220FQGMC
Winding resistance
Ω U-V 0.95 V-W 0.95 W-U 0.95
Compressor (at 68 °F)
R.L.A 12
L.R.A 13.7
Refrigerant control LEV
Sound level dB(A) 54/56
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 31-11/32
Weight lb. 139
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A:1/2 B,C,D:3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 6lb. 13oz.
Refrigeration oil (Model) fl oz. (L) 23.7 (0.7) AA: (FV50S) / BA:(FV50S/FW68S)
NOTE: Test conditions are based on AHRI 210/240.

OBHT702H 19
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 20
Outdoor model NTXMMX36A142CA
Item
Indoor type Non-Duct (09+09+09+09) Duct(09+09+09+09) Duct (18+18)
Cooling *1 Btu/h 35,400 34,400 33,400
Capacity Heating 47 *1 Btu/h 36,000 34,400 34,400
Heating 17 *2 Btu/h 26,600 26,600 26,000
Cooling *1 W 3,760 3,940 3,840
Power
Heating 47 *1 W 3,010 3,090 3,090
consumption
Heating 17 *2 W 3,440 3,540 3,540
EER Cooling 9.40 8.70 ―
EER2 Cooling 9.40 ― 8.70
SEER Cooling 19.20 16.00 ―
SEER2 Cooling 19.20 ― 16.00
HSPF IV(V) Heating 11.00 9.80 ―
HSPF2 IV(V) Heating 9.80 (7.70) ― 8.5 (7.00)
COP Heating 3.50 3.26 3.26
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 25
Min. circuit ampacity A 23.1
Fan motor F.L.A 2.43
Model SNB220FCGMC
Winding resistance
Ω U-V 0.95 V-W 0.95 W-U 0.95
Compressor (at 68 °F)
R.L.A 12
L.R.A 13.7
Refrigerant control LEV
Sound level dB(A) 54/56
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 31-11/32
Weight lb. 143
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A:1/2 B,C,D:3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 6lb. 13oz.
Refrigeration oil (Model) fl oz. (L) 23.7 (0.7) (FV50S/FW68S)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 21
Outdoor model NTXMMX42A152AA NTXMMX42A152BA
Item
Indoor type Non-Duct (06+09+09+09+09) Duct (09+09+09+09+09)
Cooling *1 Btu/h 40,500 AA: 37,500 / BA: 37,400
Capacity Heating 47 *1 Btu/h 45,000 41,000
Heating 17 *2 Btu/h 30,500 29,100
Cooling *1 W 4,403 4,112
Power
Heating 47 *1 W 3,575 3,463
consumption
Heating 17 *2 W 4,750 5,231
EER Cooling 9.2 9.0
SEER Cooling 19.7 15.2
HSPF IV(V) Heating 10.3 (7.7) 9.1 (7.7)
COP Heating 3.69 3.47
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 40
Min. circuit ampacity A 32.5
Fan motor F.L.A 2.43
Model MNB33FBTMC-L
Winding resistance
Ω U-V 0.30 V-W 0.30 W-U 0.30
Compressor (at 68 °F)
R.L.A 20
L.R.A 28.8
Refrigerant control LEV
Sound level dB(A) 56/58
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 41-11/32
Weight lb. 189
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A:1/2 B,C,D,E: 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 8 lb. 13 oz.
Refrigeration oil (Model) fl oz. (L) 37.2 (1.1) AA: (FV50S) / BA: (FV50S/FVC68D)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 22
Outdoor model NTXMMX42A152CA
Item
Indoor type Non-Duct (06+09+09+09+09) Duct(09+09+09+09+09) Duct (24+24)
Cooling *1 Btu/h 40,500 37,400 36,400
Capacity Heating 47 *1 Btu/h 45,000 41,000 41,000
Heating 17 *2 Btu/h 30,500 29,100 29,100
Cooling *1 W 4,403 4,112 4,045
Power
Heating 47 *1 W 3,575 3,463 4,520
consumption
Heating 17 *2 W 4,750 5,231 5,231
EER Cooling 9.2 9.0 ―
EER2 Cooling 9.2 ― 9.0
SEER Cooling 19.7 15.2 ―
SEER2 Cooling 19.7 ― 15.2
HSPF IV(V) Heating 10.3 9.1 ―
HSPF2 IV(V) Heating 9.2 (7.4) ― 8.3 (7.0)
COP Heating 3.68 3.46 2.66
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 40
Min. circuit ampacity A 32.5
Fan motor F.L.A 2.43
Model MNB33FBTMC-L
Winding resistance
Ω U-V 0.30 V-W 0.30 W-U 0.30
Compressor (at 68 °F)
R.L.A 20
L.R.A 28.8
Refrigerant control LEV
Sound level dB(A) 56/58
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 41-11/32
Weight lb. 189
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A:1/2 B,C,D,E: 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 8 lb. 13 oz.
Refrigeration oil (Model) fl oz. (L) 37.2 (1.1) (FV50S)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 23
Outdoor model NTXMPH20A122AA NTXMPH20A122BA
Item
Indoor type Non-Duct (09+09) Duct (09+12)
Cooling *1 Btu/h 18,000 20,000
Capacity Heating 47 *1 Btu/h 22,000 22,000
Heating 17 *2 Btu/h 22,000 22,000
Cooling *1 W 1,334 1,819
Power
Heating 47 *1 W 1,612 1,750
consumption
Heating 17 *2 W 3,071 3,224
EER Cooling 13.5 11.0
SEER Cooling 17.0 15.0
HSPF IV(V) Heating 10.0 (7.8) 9.5 (7.8)
COP Heating 4.00 3.69
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 40
Min. circuit ampacity A 29.5
Fan motor F.L.A 2.43
Model MNB33FBTMC-L
Winding resistance
Ω U-V 0.30 V-W 0.30 W-U 0.30
Compressor (at 68 °F)
R.L.A 20
L.R.A 28.8
Refrigerant control LEV
Sound level dB(A) 54/58
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 41-11/32
Weight lb. 187
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A,B: 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 8 lb. 13 oz.
Refrigeration oil (Model) fl oz. (L) 37.2 (1.1) AA: (FV50S) / BA: (FV50S/FVC68D)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 24
Outdoor model NTXMPH20A122CA
Item
Indoor type Non-Duct (09+09) Duct(09+12) Duct (12+12)
Cooling *1 Btu/h 18,000 20,000 20,000
Capacity Heating 47 *1 Btu/h 22,000 22,000 22,000
Heating 17 *2 Btu/h 22,000 22,000 22,000
Cooling *1 W 1,334 1,819 1,819
Power
Heating 47 *1 W 1,612 1,750 1,750
consumption
Heating 17 *2 W 3,071 3,224 3,545
EER Cooling 13.5 11.0 ―
EER2 Cooling 13.5 ― 11.0
SEER Cooling 17.0 15.0 ―
SEER2 Cooling 17.0 ― 14.3
HSPF IV(V) Heating 10.0 9.5 ―
HSPF2 IV(V) Heating 10.0 (8.6) ― 7.9 (6.6)
COP Heating 4.00 3.68 3.68
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 40
Min. circuit ampacity A 26.9
Fan motor F.L.A 2.43
Model MNB33FBTMC-L
Winding resistance
Ω U-V 0.30 V-W 0.30 W-U 0.30
Compressor (at 68 °F)
R.L.A 17.1
L.R.A 28.8
Refrigerant control LEV
Sound level dB(A) 54/58
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 41-11/32
Weight lb. 187
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A,B: 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 8 lb. 13 oz.
Refrigeration oil (Model) fl oz. (L) 37.2 (1.1) (FV50S)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 25
Outdoor model NTXMPH24A132AA NTXMPH24A132BA
Item
Indoor type Non-Duct (06+06+09) Duct (09+09+09)
Cooling *1 Btu/h 22,000 23,600
Capacity Heating 47 *1 Btu/h 25,000 24,600
Heating 17 *2 Btu/h 25,000 24,600
Cooling *1 W 1,630 2,360
Power
Heating 47 *1 W 1,725 1,871
consumption
Heating 17 *2 W 3,557 3,795
EER Cooling 13.5 10.0
SEER Cooling 19.0 15.5
HSPF IV(V) Heating 10.0 (7.4) 9.0 (7.4)
COP Heating 4.25 3.80
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 40
Min. circuit ampacity A 30.5
Fan motor F.L.A 2.43
Model MNB33FBTMC-L
Winding resistance
Ω U-V 0.30 V-W 0.30 W-U 0.30
Compressor (at 68 °F)
R.L.A 20
L.R.A 28.8
Refrigerant control LEV
Sound level dB(A) 54/58
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 41-11/32
Weight lb. 189
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A: 1/2 B,C: 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 8 lb. 13 oz.
Refrigeration oil (Model) fl oz. (L) 37.2 (1.1) AA: (FV50S) / BA: (FV50S/FVC68D)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 26
Outdoor model NTXMPH24A132CA
Item
Indoor type Non-Duct (06+06+09) Duct(09+09+09) Duct (12+12)
Cooling *1 Btu/h 22,000 23,600 23,600
Capacity Heating 47 *1 Btu/h 25,000 24,600 24,600
Heating 17 *2 Btu/h 25,000 24,600 24,600
Cooling *1 W 1,630 2,360 2,360
Power
Heating 47 *1 W 1,725 1,871 1,950
consumption
Heating 17 *2 W 3,557 3,795 3,795
EER Cooling 13.5 10.0 ―
EER2 Cooling 13.5 ― 10.0
SEER Cooling 19.0 15.5 ―
SEER2 Cooling 19.0 ― 14.4
HSPF IV(V) Heating 10.0 9.0 ―
HSPF2 IV(V) Heating 10.0 (8.2) ― 7.9 (6.6)
COP Heating 4.24 3.80 3.70
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 40
Min. circuit ampacity A 31.5
Fan motor F.L.A 2.43
Model MNB33FBTMC-L
Winding resistance
Ω U-V 0.30 V-W 0.30 W-U 0.30
Compressor (at 68 °F)
R.L.A 19.2
L.R.A 28.8
Refrigerant control LEV
Sound level dB(A) 54/58
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 41-11/32
Weight lb. 189
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A: 1/2 B,C: 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 8 lb. 13 oz.
Refrigeration oil (Model) fl oz. (L) 37.2 (1.1) (FV50S)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 27
Outdoor model NTXMPH30A132AA NTXMPH30A132BA
Item
Indoor type Non-Duct (09+09+12) Duct (09+09+12)
Cooling *1 Btu/h 28,400 27,400
Capacity Heating 47 *1 Btu/h 28,600 27,600
Heating 17 *2 Btu/h 28,600 27,600
Cooling *1 W 2,272 2,661
Power
Heating 47 *1 W 2,096 2,187
consumption
Heating 17 *2 W 4,192 4,258
EER Cooling 12.5 10.3
SEER Cooling 18.0 16.0
HSPF IV(V) Heating 11.0 (8.5) 9.8 (7.7)
COP Heating 4.00 3.70
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 40
Min. circuit ampacity A 30.5
Fan motor F.L.A 2.43
Model MNB33FBTMC-L
Winding resistance
Ω U-V 0.30 V-W 0.30 W-U 0.30
Compressor (at 68 °F)
R.L.A 20
L.R.A 28.8
Refrigerant control LEV
Sound level dB(A) 54/58
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 41-11/32
Weight lb. 189
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A: 1/2 B,C: 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 8 lb. 13 oz.
Refrigeration oil (Model) fl oz. (L) 37.2 (1.1) AA: (FV50S) / BA: (FV50S/FVC68D)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 28
Outdoor model NTXMPH30A132CA
Item
Indoor type Non-Duct (09+09+12) Duct(09+09+12) Duct (18+18)
Cooling *1 Btu/h 28,400 27,400 27,400
Capacity Heating 47 *1 Btu/h 28,600 27,600 27,600
Heating 17 *2 Btu/h 28,600 27,600 27,600
Cooling *1 W 2,272 2,661 2,660
Power
Heating 47 *1 W 2,096 2,187 2,280
consumption
Heating 17 *2 W 4,192 4,258 4,258
EER Cooling 12.5 10.3 ―
EER2 Cooling 12.5 ― 10.3
SEER Cooling 18.0 16.0 ―
SEER2 Cooling 18.0 ― 16.0
HSPF IV(V) Heating 11.0 9.8 ―
HSPF2 IV(V) Heating 10.0 (7.9) ― 8.5 (7.0)
COP Heating 4.00 3.70 3.55
External finish Munsell 3.0Y 7.8/1.1
Power supply V, phase, Hz 208/230, 1, 60
Max. fuse size (time delay) A 40
Min. circuit ampacity A 31.5
Fan motor F.L.A 2.43
Model MNB33FBTMC-L
Winding resistance
Ω U-V 0.30 V-W 0.30 W-U 0.30
Compressor (at 68 °F)
R.L.A 19.2
L.R.A 28.8
Refrigerant control LEV
Sound level dB(A) 54/58
Defrost method Reverse cycle
W in. 37-13/32
Dimensions D in. 13
H in. 41-11/32
Weight lb. 189
Remote controller Wireless type Wired type
Control voltage (by built-in transformer) 12-24 V DC
Refrigerant piping Not supplied (optional parts)
Liquid in. 1/4
Valve size
Gas in. A: 1/2 B,C: 3/8
Indoor Flared
Connection method
Outdoor Flared
Refrigerant charge (R410A) lb. 8 lb. 13 oz.
Refrigeration oil (Model) fl oz. (L) 37.2 (1.1) (FV50S)
NOTE: Test conditions are based on AHRI 210/240.
Unit: °F
Indoor air condition Outdoor air condition
Mode Test
Dry bulb Wet bulb Dry bulb Wet bulb
Cooling *1: "A" Cooling steady state at rated compressor speed 80 67 95 (75)
"B-2" Cooling steady state at rated compressor speed 80 67 82 (65)
"B-1" Cooling steady state at minimum compressor speed 80 67 82 (65)
Low ambient cooling steady state at minimum compressor speed 80 67 67 (53.5)
Intermediate cooling steady state at intermediate compressor speed 80 67 87 (69)
Heating *1: Standard rating-heating at rated compressor speed 70 60 47 43
*2: Low temperature heating at maximum compressor speed 70 60 17 15
Maximum temperature heating at minimum compressor speed 70 60 62 56.5
High temperature heating at minimum compressor speed 70 60 47 43
Frost accumulation at rated compressor speed 70 60 35 33
Frost accumulation at intermediate compressor speed 70 60 35 33

OBHT702H 29
5 NOISE CRITERIA CURVES
NTXMMX20A122AA FAN SPEED FUNCTION SPL(dB(A)) LINE NTXMMX24A132AA FAN SPEED FUNCTION SPL(dB(A)) LINE

NTXMMX20A122AC High Cooling 50 NTXMMX24A132BA High Cooling 51

NTXMMX20A122BA High Heating 54 High Heating 55

NTXMMX20A122CA
90 90
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR


80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

NTXMMX24A132CA FAN SPEED FUNCTION SPL(dB(A)) LINE NTXMMX30A132AA FAN SPEED FUNCTION SPL(dB(A)) LINE

High Cooling 51 NTXMMX30A132BA High Cooling 52


High Heating 55 High Heating 56

90 90
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR

80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

OUTDOOR UNIT

39.4 in.
MICROPHONE Test conditions
Cooling: Dry-bulb temperature 95°F Wet-bulb temperature 75°F
Heating: Dry-bulb temperature 45°F Wet-bulb temperature 43°F

OBHT702H 30
NTXMMX30A132CA FAN SPEED FUNCTION SPL(dB(A)) LINE NTXMMX36A142AA FAN SPEED FUNCTION SPL(dB(A)) LINE

High Cooling 52 NTXMMX36A142BA High Cooling 54


High Heating 56 High Heating 56

90 90

OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR


OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR

80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

NTXMMX36A142CA FAN SPEED FUNCTION SPL(dB(A)) LINE NTXMMX42A152AA FAN SPEED FUNCTION SPL(dB(A)) LINE

High Cooling 54 NTXMMX42A152BA High Cooling 56


High Heating 56
NTXMMX42A152CA High Heating 58

90 90
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR

80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

OBHT702H 31
NTXMPH20A122AA FAN SPEED FUNCTION SPL(dB(A)) LINE NTXMPH24A132AA FAN SPEED FUNCTION SPL(dB(A)) LINE

NTXMPH20A122BA High Cooling 54 NTXMPH24A132BA High Cooling 54

NTXMPH20A122CA High Heating 58


NTXMPH24A132CA High Heating 58

90 90
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR

OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR


80 80

70 70
NC-70 NC-70

60 60
NC-60 NC-60

50 50
NC-50 NC-50

40 40
NC-40 NC-40

30 30
NC-30 NC-30

20 APPROXIMATE 20 APPROXIMATE
THRESHOLD OF THRESHOLD OF
HEARING FOR NC-20 HEARING FOR NC-20
CONTINUOUS CONTINUOUS
NOISE NOISE
10 10
63 125 250 500 1000 2000 4000 8000 63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz BAND CENTER FREQUENCIES, Hz

NTXMPH30A132AA FAN SPEED FUNCTION SPL(dB(A)) LINE

NTXMPH30A132BA High Cooling 54

NTXMPH30A132CA High Heating 58

90
OCTAVE BAND SOUND PRESSURE LEVEL, 0dB = 0.0002 MICRO BAR

80

70
NC-70

60
NC-60

50
NC-50

40
NC-40

30
NC-30

20 APPROXIMATE
THRESHOLD OF
HEARING FOR NC-20
CONTINUOUS
NOISE
10
63 125 250 500 1000 2000 4000 8000

BAND CENTER FREQUENCIES, Hz

OBHT702H 32
6 OUTLINES AND DIMENSIONS

NTXMMX20A122AA NTXMMX20A122BA NTXMMX20A122CA Unit: inch (mm)


NTXMMX20A122AC

6-21/32” 19-11/16” 6-23/32”


2-9/16” 8-5/32” 12-3/8”

11/16”
1-11/32”
Air
Inlet

23/32”
21/32”

15-19/32”
(Bolt Pitch)
14-3/16”
15/32”
Air Inlet

11/16”
3-ø(1-5/16”) Drain hole
Air
Outlet

4-(13/32”×13/16”) Oval Hole


(Foundation Bolt M8)

Handle
13/32” 33-1/16” 1-3/16”
7-7/8” 1-1/32” 13” 1/2”

Connecting
wire hole

9-7/16”
2-19/32”

27-15/16”
Connecting
wire hole
1-25/32”

14-3/16”
18-1/8

LIQ
5-5/16”

Unit B
GAS LIQ 1/4”(ø6.35)FLARE
LIQ GAS 3/8”(ø9.52)FLARE
Unit A
GAS
3-5/16”

29/32” 11-25/32”

Grounding terminal
Conduit
cover

Lock nut Connector

OBHT702H 33
NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA Unit: inch (mm)
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA

(AA, BA)
Conduit plates
Conduit connector

Lock nut

(CA)
Conduit plate

Conduit connector

Lock nut Conduit plate

OBHT702H 34
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA Unit: inch (mm)

(AA, BA)
Conduit plates
Conduit connector

Lock nut

(CA)
Conduit plate

Conduit connector

Lock nut Conduit plate

OBHT702H 35
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA Unit: inch (mm)

Conduit plate Top

Lock nut Conduit connector


Conduit plate Under

OBHT702H 36
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA Unit: inch (mm)

Lock nut Conduit plate

Conduit connector

OBHT702H 37
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA Unit: inch (mm)
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA

Lock nut Conduit plate Top

Conduit connector

Conduit plate Under

OBHT702H 38
7 WIRING DIAGRAM

NTXMMX20A122AA
NTXMMX20A122AC

[Connection between reactor and outdoor power P.C. board]


* There are 2 types of reactors, which may have a number display.
Even if there is a number display, please wire as shown in the figure below.
Connect to TAB3 Connect to TAB6

Connect to TAB5 Connect to TAB4

OBHT702H 39
NTXMMX20A122BA

[If the reactor does not have a number display, refer to the figure below.]
No.4 No.3

No.1 No.2

OBHT702H 40
NTXMMX20A122CA

[If the reactor does not have a number display, refer to the figure below.]
No.4 No.3

No.1 No.2

OBHT702H 41
NTXMMX24A132AA
NTXMMX30A132AA

[Connection between reactor and outdoor power P.C. board]


* There are 2 types of reactors, which may have a number display.
Even if there is a number display, please wire as shown in the figure below.
Connect to TAB3 Connect to TAB6

Connect to TAB5 Connect to TAB4

OBHT702H 42
NTXMMX24A132BA
NTXMMX30A132BA

[If the reactor does not have a number display, refer to the figure below.]
No.4 No.3

No.1 No.2

OBHT702H 43
NTXMMX24A132CA
NTXMMX30A132CA

[If the reactor does not have a number display, refer to the figure below.]
No.4 No.3

No.1 No.2

OBHT702H 44
NTXMMX36A142AA

[Connection between reactor and outdoor power P.C. board]


* There are 2 types of reactors, which may have a number display.
Even if there is a number display, please wire as shown in the figure below.
Connect to TAB3 Connect to TAB6

Connect to TAB5 Connect to TAB4

OBHT702H 45
NTXMMX36A142BA

[If the reactor does not have a number display, refer to the figure below.]
No.4 No.3

No.1 No.2

OBHT702H 46
NTXMMX36A142CA

[If the reactor does not have a number display, refer to the figure below.]
No.4 No.3

No.1 No.2

OBHT702H 47
NTXMMX42A152AA

OBHT702H 48
NTXMMX42A152BA
L1 L2
CIRCUIT
WH RD WH RD BREAKER
TAB5 TAB3 TAB6 TAB4 X52CA TAB1 TB1
BK

POWER SUPPLY
BU
L1

208/230V
L2

AC 60Hz
IC501 IC411 IC401 X52CB
GNYE
X65A PTC1
TAB2
GR
BK U
PTC2
WH V PTC3
RD W TB6
GY
S3 12-24V

TO INDOOR
1 BK

UNIT No. E
BU
F1
3 BU BK
S2 208/230V~
OUTDOOR
D1
F2 CNAC1
S1
POWER P.C.
CB1 CB2 CB3 CB4
BOARD TB5
YE
S3 12-24V

TO INDOOR
UNIT No. D
BU
CNDC CN151 CN152
TBE1 TBE2 TBE3 TBE4 CNAC2 CN171 BK S2 208/230V~
1 3 1 7 1 2 1 3 1 2 S1
CNMC

BK

BK
MF MS

BK

BK

BK

BK
BK WH RD 3~ t°
5 RT64
BN
BK

BK

BK
BK
BK
BK
BK

BK
BK

V
U MS W 1 7 1 3 1 7 1 2 1 3 5
TB4
3~ CNF1 CNDC CN702 CN701 CNAC OG
S3 12-24V

TO INDOOR
MC CN621

UNIT No. C
GY BU
T801 OUTDOOR CONTROL P.C. BOARD F711
YE BK S2 208/230V~
LED3
1
S1
IC801
3 OG
CN611 WH
LED2 1 5
TB3
(BK) (BU) (WH) WH
S3 12-24V

TO INDOOR
1

UNIT No. B
CN741 CN795 CN793 CN791 BU
X712 X713 X714
1 5 1 5 1 5 5 RD BK S2 208/230V~
LED1 BU S1
(YE) (RD) CN601
CNTH1 CNTH2 CN794 CN792 CN712 CN713 CN714 CN63H BK
1 8 1 2 1 5 1 5 1 2 1 2 1 2 1 3 1
TB2
RD
S3 12-24V

TO INDOOR
5 5 5 5 5

UNIT No. A
BU
t° t° t° t° M M M M M 21S4 21S2 HPS BK S2 208/230V~
RT61 RT62 RT68 RT65 S1
LEV E LEV D LEV C LEV B LEV A

SYMBOL NAME SYMBOL NAME NOTES:


CB1~4 SMOOTHING CAPACITOR RT62 DISCHARGE TEMP. THERMISTOR 1. About the indoor side electric wiring refer to the indoor unit
D1 DIODE RT64 FIN TEMP. THERMISTOR electric wiring diagram for the service.
F1, F2 FUSE (T6.3AL 250V) RT65 AMBIENT TEMP. THERMISTOR 2. Use copper conductors only (For field wiring).
F711 FUSE (T3.15AL 250V) OUTDOOR HEAT EXCHANGER 3. Symbols below indicate.
RT68 : Terminal block
HPS HIGH PRESSURE SWITCH TEMP. THERMISTOR
IC401 DIODE BRIDGE T801 TRANSFORMER : Connector
IC411 POWER MODULE TB1~6 TERMINAL BLOCK
IC501 POWER MODULE X52CA, B RELAY NOTES:
IC801 POWER DEVICE X65A RELAY 1.À propos du câblage électrique de côté intérieur se référer à l'unité intérieure câblage
L1, L2 REACTOR X712 RELAY schéma électrique pour l'entretien.
LED 1~3 LED X713 RELAY 2.Utiliser des conducteurs en cuivre (pour le câblage).
LEV A~E EXPANSION VALVE COIL X714 RELAY 3.Symbole ci-dessous indique.
MC COMPRESSOR 21S2 2WAY VALVE SOLENOID COIL :Bornier
MF FAN MOTOR 21S4 REVERSING VALVE SOLENOID COIL :Connecteur
PTC1~3 CIRCUIT PROTECTOR
RT61 DEFROST THERMISTOR

OBHT702H 49
NTXMMX42A152CA
L1 L2
CIRCUIT
WH RD WH RD BREAKER
TAB5 TAB3 TAB6 TAB4 X52CA TAB1 TB1
BK

POWER SUPPLY
BU
L1

208/230V
L2

AC 60Hz
IC501 IC411 IC401 X52CB
GNYE
TAB2
X65A PTC1
BK U
PTC2
WH V PTC3
RD W TB6
GY
S3 12-24V

TO INDOOR
1 BK

UNIT No. E
BU
F1
3 BU BK
S2 208/230V~
OUTDOOR
D1
F2 CNAC1
S1
POWER P.C.
CB1 CB2 CB3 CB4
BOARD TB5
YE
S3 12-24V

TO INDOOR
UNIT No. D
BU
CNDC CN151 CN152
TBE1 TBE2 TBE3 TBE4 CNAC2 CN171 BK S2 208/230V~
1 3 1 7 1 2 1 3 1 2 S1
CNMC

BK

BK
MF MS

BK

BK

BK

BK
BK WH RD 3~ t°
5 RT64
BN
BK

BK

BK
BK
BK
BK
BK

BK
BK

V
U MS W 1 7 1 3 1 7 1 2 1 3 5
TB4
3~ CNF1 CNDC CN702 CN701 CNAC OG
S3 12-24V

TO INDOOR
MC CN621

UNIT No. C
GY BU
T801 OUTDOOR CONTROL P.C. BOARD F711
YE BK S2 208/230V~
LED3
1
S1
IC801
3 OG
CN611 WH
LED2 1 5
TB3
(BK) (BU) (WH) WH
S3 12-24V

TO INDOOR
1

UNIT No. B
CN741 CN795 CN793 CN791 BU
X712 X713 X714
1 5 1 5 1 5 5 RD BK S2 208/230V~
LED1 BU S1
(YE) (RD) CN601
CNTH1 CNTH2 CN794 CN792 CN712 CN713 CN714 CN63H BK
1 8 1 2 1 5 1 5 1 2 1 2 1 2 1 3 1
TB2
RD
S3 12-24V

TO INDOOR
5 5 5 5 5

UNIT No. A
BU
t° t° t° t° M M M M M 21S4 21S2 HPS BK S2 208/230V~
RT61 RT62 RT68 RT65 S1
LEV E LEV D LEV C LEV B LEV A

SYMBOL NAME SYMBOL NAME NOTES:


CB1~4 SMOOTHING CAPACITOR RT62 DISCHARGE TEMP. THERMISTOR 1. About the indoor side electric wiring refer to the indoor unit
D1 DIODE RT64 FIN TEMP. THERMISTOR electric wiring diagram for the service.
F1, F2 FUSE (T6.3AL 250V) RT65 AMBIENT TEMP. THERMISTOR 2. Use copper conductors only (For field wiring).
F711 FUSE (T3.15AL 250V) OUTDOOR HEAT EXCHANGER 3. Symbols below indicate.
RT68 : Terminal block
HPS HIGH PRESSURE SWITCH TEMP. THERMISTOR
IC401 DIODE BRIDGE T801 TRANSFORMER : Connector
IC411 POWER MODULE TB1~6 TERMINAL BLOCK
IC501 POWER MODULE X52CA, B RELAY NOTES:
IC801 POWER DEVICE X65A RELAY 1.À propos du câblage électrique de côté intérieur se référer à l'unité intérieure câblage
L1, L2 REACTOR X712 RELAY schéma électrique pour l'entretien.
LED 1~3 LED X713 RELAY 2.Utiliser des conducteurs en cuivre (pour le câblage).
LEV A~E EXPANSION VALVE COIL X714 RELAY 3.Symbole ci-dessous indique.
MC COMPRESSOR 21S2 2-WAY VALVE SOLENOID COIL :Bornier
MF FAN MOTOR 21S4 4-WAY VALVE SOLENOID COIL :Connecteur
PTC1~3 CIRCUIT PROTECTOR
RT61 DEFROST THERMISTOR

OBHT702H 50
NTXMPH20A122AA

OBHT702H 51
NTXMPH20A122BA

L1 L2
CIRCUIT
WH RD WH RD BREAKER
TAB5 TAB3 TAB6 TAB4 X52CA TB1

POWER SUPPLY
TAB1 BK
L1

208/230V
BU

AC 60Hz
IC501 IC411 IC401 X52CB
GNYE
L2
X65A PTC1
TAB2
GR
BK U
PTC2
WH V PTC3
RD W
1 BK
F1
3 BU
D1
OUTDOOR F2 CNAC1
POWER P.C.
CB1 CB2 CB3 CB4
BOARD

CNDC CN151 CN152 CNAC2 CN171


TBE1 TBE2 TBE3 TBE4
1 3 1 7 1 2 1 3 1 2

CNMC

BK

BK
MF MS BK

BK

BK

BK
BK WH 3~ t°
RD
5 RT64
BN
BK

BK

BK
BK
BK
BK
BK

BK
BK

V
U MS W 1 7 1 3 1 7 1 2 1 3
3~ CNF1 CNDC CN702 CN701 CNAC
MC TB3
T801 OUTDOOR CONTROL P.C. BOARD F711 WH
S3 12-24V

TO INDOOR
BU

UNIT No. B
LED3
IC801 BK S2 208/230V~
3 S1
CN611 WH
LED2 1 5 (WH)
CN791 1
CN741
1 5
X712 X713 X714
5 TB2
RD RD
LED1 S3 12-24V

TO INDOOR
BU

UNIT No. A
BU
CNTH1 CNTH2
(RD)
CN792 CN712 CN713 CN714
CN601
BK BK S2 208/230V~
1 8 1 2 1 5 1 2 1 2 1 2 1
CN63H
3 1
S1

5 5 RD 2 2 BK BK
t° t° t° t° M M 21S4 21S2 HPS 1 1 BK BK 26H
RT61 RT62 YE
RT68 RT65 2 2 BK
LEV B LEV A
BK 1 1 BK H

SYMBOL NAME SYMBOL NAME NOTES:


CB1~4 SMOOTHING CAPACITOR RT61 DEFROST THERMISTOR 1. About the indoor side electric wiring refer to the indoor unit
D1 DIODE RT62 DISCHARGE TEMP. THERMISTOR electric wiring diagram for the service.
F1, F2 FUSE (T6.3AL 250V) RT64 FIN TEMP. THERMISTOR 2. Use copper conductors only (For field wiring).
F711 FUSE (T3.15AL 250V) RT65 AMBIENT TEMP. THERMISTOR 3. Symbols below indicate.
HPS HIGH PRESSURE SWITCH OUTDOOR HEAT EXCHANGER : Terminal block
RT68 : Connector
H DEFROST HEATER TEMP. THERMISTOR
IC401 DIODE BRIDGE T801 TRANSFORMER
IC411 POWER MODULE TB1~3 TERMINAL BLOCK NOTES:
IC501 POWER MODULE X52CA, B RELAY 1.À propos du câblage électrique de côté intérieur se référer à l'unité intérieure câblage
IC801 POWER DEVICE X65A RELAY schéma électrique pour l'entretien.
L1, L2 REACTOR X712 RELAY 2.Utiliser des conducteurs en cuivre (pour le câblage).
LED 1~3 LED X713 RELAY 3.Symbole ci-dessous indique.
LEV A, B EXPANSION VALVE COIL X714 RELAY :Bornier
MC COMPRESSOR 21S2 2WAY VALVE SOLENOID COIL :Connecteur
MF FAN MOTOR 21S4 REVERSING VALVE SOLENOID COIL
PTC1~3 CIRCUIT PROTECTOR 26H HEATER PROTECTOR

OBHT702H 52
NTXMPH20A122CA

OBHT702H 53
NTXMPH24A132AA
NTXMPH30A132AA

OBHT702H 54
NTXMPH24A132BA
NTXMPH30A132BA

L1 L2 CIRCUIT
WH RD WH RD BREAKER
TB1

POWER SUPPLY
TAB5 TAB3 TAB6 TAB4 X52CA TAB1 BK
L1

208/230V
AC 60Hz
BU
IC501 IC411 IC401 X52CB
GNYE
L2
X65A PTC1
TAB2
GR
BK U
PTC2
WH V PTC3
RD W
1 BK
F1
3 BU
D1
OUTDOOR F2 CNAC1
POWER P.C.
CB1 CB2 CB3 CB4
BOARD

CNDC CN151 CN152 CNAC2 CN171


TBE1 TBE2 TBE3 TBE4
1 3 1 7 1 2 1 3 1 2

CNMC

BK

BK
MF MS

BK

BK

BK

BK
t° TB4
3~ OG
BK WH RD
S3 12-24V

TO INDOOR
5 RT64 BU

UNIT No. C
BN
BK

BK

BK
BK
BK
BK
BK

BK
BK

BK S2 208/230V~
V
U MS W 1 7 1 3 1 7 1 2 1 3
S1
3~ CNF1 CNDC CN702 CN701 CNAC
MC TB3
T801 OUTDOOR CONTROL P.C. BOARD F711 WH
S3 12-24V
BU

TO INDOOR
S2 208/230V~

UNIT No. B
LED3 BK
IC801
3 OG S1
CN611 WH
LED2 1 5 (BU) (WH)
CN793 CN791 1
CN741
1 5 1 5
X712 X713 X714
5 TB2
RD RD
LED1 BU S3 12-24V

TO INDOOR
BU
S2 208/230V~

UNIT No. A
(RD) CN601
CN712 CN713 CN714 BK BK
CNTH1 CNTH2 CN792
1 8 1 2 1 5 1 2 1 2 1 2 1
CN63H
3 1
S1

5 5 5 RD 2 2 BK BK
t° t° t° t° M M M 21S4 21S2 HPS 1 1 BK BK 26H
RT61 RT62 YE
RT68 RT65 2 2 BK
LEV C LEV B LEV A
BK 1 1 BK H

SYMBOL NAME SYMBOL NAME NOTES:


CB1~4 SMOOTHING CAPACITOR RT61 DEFROST THERMISTOR 1. About the indoor side electric wiring refer to the indoor unit
D1 DIODE RT62 DISCHARGE TEMP. THERMISTOR electric wiring diagram for the service.
F1, F2 FUSE (T6.3AL 250V) RT64 FIN TEMP. THERMISTOR 2. Use copper conductors only (For field wiring).
F711 FUSE (T3.15AL 250V) RT65 AMBIENT TEMP. THERMISTOR 3. Symbols below indicate.
HPS HIGH PRESSURE SWITCH OUTDOOR HEAT EXCHANGER : Terminal block
RT68 : Connector
H DEFROST HEATER TEMP. THERMISTOR
IC401 DIODE BRIDGE T801 TRANSFORMER
IC411 POWER MODULE TB1~4 TERMINAL BLOCK NOTES:
IC501 POWER MODULE X52CA, B RELAY 1.À propos du câblage électrique de côté intérieur se référer à l'unité intérieure câblage
IC801 POWER DEVICE X65A RELAY schéma électrique pour l'entretien.
L1, L2 REACTOR X712 RELAY 2.Utiliser des conducteurs en cuivre (pour le câblage).
LED 1~3 LED X713 RELAY 3.Symbole ci-dessous indique.
LEV A~C EXPANSION VALVE COIL X714 RELAY :Bornier
MC COMPRESSOR 21S2 2WAY VALVE SOLENOID COIL :Connecteur
MF FAN MOTOR 21S4 REVERSING VALVE SOLENOID COIL
PTC1~3 CIRCUIT PROTECTOR 26H HEATER PROTECTOR

OBHT702H 55
NTXMPH24A132CA
NTXMPH30A132CA
L1 L2 CIRCUIT
WH RD WH RD BREAKER
TB1

POWER SUPPLY
TAB5 TAB3 TAB6 TAB4 X52CA TAB1 BK
L1

208/230V
AC 60Hz
BU
IC501 IC411 IC401 X52CB
GNYE
L2
TAB2
X65A PTC1
BK U
PTC2
WH V PTC3
RD W
1 BK
F1
3 BU
D1
OUTDOOR F2 CNAC1
POWER P.C.
CB1 CB2 CB3 CB4
BOARD

CNDC CN151 CN152 CNAC2 CN171


TBE1 TBE2 TBE3 TBE4
1 3 1 7 1 2 1 3 1 2

CNMC

BK

BK
MF MS

BK

BK

BK

BK
t° TB4
3~ OG
BK WH RD
S3 12-24V

TO INDOOR
5 RT64 BU

UNIT No. C
BN
BK

BK

BK
BK
BK
BK
BK

BK
BK

BK S2 208/230V~
V
U MS W 1 7 1 3 1 7 1 2 1 3
S1
3~ CNF1 CNDC CN702 CN701 CNAC
MC TB3
T801 OUTDOOR CONTROL P.C. BOARD F711 WH
S3 12-24V
BU

TO INDOOR
S2 208/230V~

UNIT No. B
LED3 BK
IC801
3 OG S1
CN611 WH
LED2 1 5 (BU) (WH)
CN793 CN791 1
CN741
1 5 1 5
X712 X713 X714
5 TB2
RD RD
LED1 BU S3 12-24V

TO INDOOR
BU
S2 208/230V~

UNIT No. A
(RD) CN601
CN712 CN713 CN714 BK BK
CNTH1 CNTH2 CN792
1 8 1 2 1 5 1 2 1 2 1 2 1
CN63H
3 1
S1

5 5 5 RD 2 2 BK BK
t° t° t° t° M M M 21S4 21S2 HPS 1 1 BK BK 26H
RT61 RT62 YE
RT68 RT65 2 2 BK
LEV C LEV B LEV A
BK 1 1 BK H

SYMBOL NAME SYMBOL NAME NOTES:


CB1~4 SMOOTHING CAPACITOR RT61 DEFROST THERMISTOR 1. About the indoor side electric wiring refer to the indoor unit
D1 DIODE RT62 DISCHARGE TEMP. THERMISTOR electric wiring diagram for the service.
F1, F2 FUSE (T6.3AL 250V) RT64 FIN TEMP. THERMISTOR 2. Use copper conductors only (For field wiring).
F711 FUSE (T3.15AL 250V) RT65 AMBIENT TEMP. THERMISTOR 3. Symbols below indicate.
HPS HIGH PRESSURE SWITCH OUTDOOR HEAT EXCHANGER : Terminal block
RT68 : Connector
H DEFROST HEATER TEMP. THERMISTOR
IC401 DIODE BRIDGE T801 TRANSFORMER
IC411 POWER MODULE TB1~4 TERMINAL BLOCK NOTES:
IC501 POWER MODULE X52CA, B RELAY 1.À propos du câblage électrique de côté intérieur se référer à l'unité intérieure câblage
IC801 POWER DEVICE X65A RELAY schéma électrique pour l'entretien.
L1, L2 REACTOR X712 RELAY 2.Utiliser des conducteurs en cuivre (pour le câblage).
LED 1~3 LED X713 RELAY 3.Symbole ci-dessous indique.
LEV A~C EXPANSION VALVE COIL X714 RELAY :Bornier
MC COMPRESSOR 21S2 2-WAY VALVE SOLENOID COIL :Connecteur
MF FAN MOTOR 21S4 4-WAY VALVE SOLENOID COIL
PTC1~3 CIRCUIT PROTECTOR 26H HEATER PROTECTOR

OBHT702H 56
8 REFRIGERANT SYSTEM DIAGRAM

NTXMMX20A122AA NTXMMX20A122BA NTXMMX20A122CA Unit: inch (mm)


NTXMMX20A122AC

Service
port
Compressor
R.V. coil Service Discharge
OFF Refrigerant flow in cooling temperature
port
thermistor RT62
ON Refrigerant flow in heating Muffler

High pressure switch


Union
Indoor unit ø 3/8 (ø9.52) Stop valve with 4-way
B service port valve

Sub
Indoor unit ø 3/8 (ø9.52) Muffler
A
Outdoor heat
exchanger
temperature FAN-OUT
thermistor
RT68

HEX-OUT
Ambient
temperature
thermistor
RT65
Capillary tube
O.D.0.16 x I.D.0.11 x 3.94
(ø4.0 x ø2.8 x 100) Defrost
Union thermistor
ø 1/4 (ø6.35) RT61
Indoor unit
A Capillary tube
Strainer LEV A O.D.0.14 × I.D.0.09 ×19.68
#100 (ø3.6 × ø2.4 × 500)
Strainer Stop valve Strainer
#100 LEV R #100 Distributor
Power
receiver

ø 1/4 (ø6.35)
Indoor unit
B LEV B
Strainer
#100

OBHT702H 57
NTXMMX20A122AA NTXMMX20A122BA NTXMMX20A122CA
NTXMMX20A122AC
Operating Range
Indoor intake air temperature Outdoor intake air temperature
Maximum 95°FDB, 71°FWB 115°FDB
Cooling
Minimum 67°FDB, 57°FWB 14°FDB
Maximum 80°FDB, 67°FWB 75°FDB, 65°FWB
Heating
Minimum 70°FDB, 60°FWB 6°FDB, 5°FWB

MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION


Piping length each indoor unit (a, b) 82 ft. MAX.
Total piping length (a+b) 164 ft. MAX.
Bending point for each unit 25 MAX.
Total bending point 50 MAX.
*It is irrelevant which unit is higher.

Indoor a
units
Max. height difference

Outdoor
unit
49 ft.

49 ft.

33 ft.
b

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When the diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Unit: inch
Outdoor unit union diameter
For
Liquid 1/4
Indoor unit A
Gas 3/8
Liquid 1/4
Indoor unit B
Gas 3/8

OBHT702H 58
NTXMMX24A132AA NTXMMX24A132BA Unit: inch (mm)
NTXMMX30A132AA NTXMMX30A132BA

R.V.coil
OFF Refrigerant flow in heating
ON Refrigerant flow in cooling
Accumulator
Compressor
Service port
High pressure switch
Compressor shell
Muffler temperature
thermistor
Service port
RT62
Union Header(Gas)
ø 1/2 (ø12.7) Stop valve
Indoor unit A 4-way valve
(with service port)

ø 3/8 (ø9.52)
Indoor unit B Sub Header (Evaporator)
muffler

ø 3/8 (ø9.52) Outdoor


Indoor unit C heat exchanger
Outdoor
heat exchanger temperature
thermistor Ambient
Capillary tube RT68 temperature
O.D.0.16 x I.D.0.11 x 3.94 thermistor
(ø4.0 x ø2.8 x 100) Capillary tube
Union Strainer RT65
ø 1/4 (ø6.35) #100 LEVA Defrost
temperature
Indoor unit A
Strainer thermistor
ø 1/4 (ø6.35) Strainer #100 RT61
LEVB
#100 Strainer
Distributor #50
Indoor unit B Stop valve
Strainer
ø 1/4 (ø6.35) #100 LEVC
Indoor unit C

NTXMMX24A132CA
NTXMMX30A132CA

R.V.coil
OFF Refrigerant flow in heating
ON Refrigerant flow in cooling
Accumulator
Compressor
Service port
High pressure switch
Compressor shell
Muffler temperature
thermistor
Service port
RT62
Union Header(Gas)
ø 1/2 (ø12.7) Stop valve
Indoor unit A 4-way valve
(with service port)

ø 3/8 (ø9.52)
Indoor unit B Sub Header (Evaporator)
muffler

ø 3/8 (ø9.52) Outdoor


Indoor unit C heat exchanger
Outdoor
heat exchanger temperature
thermistor Ambient
Capillary tube RT68 temperature
O.D.0.16 x I.D.0.11 x 3.94 thermistor
(ø4.0 x ø2.8 x 100) Capillary tube
Union Strainer RT65
ø 1/4 (ø6.35) #100 LEVA Defrost
temperature
Indoor unit A
Strainer thermistor
ø 1/4 (ø6.35) Strainer #100 RT61
LEVB
#100 Strainer
Distributor #50
Indoor unit B Stop valve
Strainer
ø 1/4 (ø6.35) #100 LEVC
Indoor unit C

OBHT702H 59
NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
Operating Range
Indoor intake air temperature Outdoor intake air temperature
Maximum 95°FDB, 71°FWB 115°FDB
Cooling
Minimum 67°FDB, 57°FWB 14°FDB
Maximum 80°FDB, 67°FWB 75°FDB, 65°FWB
Heating
Minimum 70°FDB, 60°FWB 6°FDB, 5°FWB

MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION


Piping length each indoor unit (a, b, c) 82 ft. MAX.
Total piping length (a+b+c) 230 ft. MAX.
Bending point for each unit 25 MAX.
Total bending point 70 MAX.
*It is irrelevant which unit is higher.

Indoor a
units
Max. height difference

Outdoor
unit
c 49 ft.

49 ft.

49 ft.
b

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When the diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Unit: inch
Outdoor unit union diameter
For
Liquid 1/4
Indoor unit A
Gas 1/2
Liquid 1/4
Indoor unit B
Gas 3/8
Liquid 1/4
Indoor unit C
Gas 3/8

OBHT702H 60
NTXMMX36A142AA NTXMMX36A142BA Unit: inch (mm)

R.V.coil
OFF Refrigerant flow in heating
ON Refrigerant flow in cooling
Accumulator
Compressor
Service port
High pressure switch
Compressor shell
Muffler
temperature
thermistor
Service port RT62
Union Header(Gas)
ø 1/2 (ø12.7) Stop valve
4-way valve
Indoor unit A (with service port)
ø 3/8 (ø9.52)
Indoor unit B
ø 3/8 (ø9.52) Sub Header (Evaporator)
muffler
Indoor unit C
Outdoor
ø 3/8 (ø9.52)
Indoor unit D heat exchanger
Outdoor
heat exchanger
temperature Ambient
Capillary tube thermistor temperature
O.D.0.16 x I.D.0.11 x 3.94 RT68 thermistor
(ø4.0 x ø2.8 x 100)
Capillary tube RT65
Union Strainer
ø 1/4 (ø6.35) #100 LEV A Defrost
temperature
Indoor unit A
Strainer Strainer thermistor
ø 1/4 (ø6.35) #100 LEV B RT61
#100
Indoor unit B Strainer
Strainer Distributor
LEV C #50
ø 1/4 (ø6.35) #100 Stop valve
Indoor unit C
Strainer
ø 1/4 (ø6.35) #100 LEV D
Indoor unit D

NTXMMX36A142CA

R.V.coil
OFF Refrigerant flow in heating
ON Refrigerant flow in cooling
Accumulator
Compressor
Service port
High pressure switch
Compressor shell
Muffler
temperature
thermistor
Service port RT62
Union Header(Gas)
ø 1/2 (ø12.7) Stop valve
4-way valve
Indoor unit A (with service port)
ø 3/8 (ø9.52)
Indoor unit B
ø 3/8 (ø9.52) Sub Header (Evaporator)
muffler
Indoor unit C
Outdoor
ø 3/8 (ø9.52)
Indoor unit D heat exchanger
Outdoor
heat exchanger
temperature Ambient
Capillary tube thermistor temperature
O.D.0.16 x I.D.0.11 x 3.94 RT68 thermistor
(ø4.0 x ø2.8 x 100)
Capillary tube RT65
Union Strainer
ø 1/4 (ø6.35) #100 LEV A Defrost
temperature
Indoor unit A
Strainer Strainer thermistor
ø 1/4 (ø6.35) #100 LEV B RT61
#100
Indoor unit B Strainer
Strainer Distributor
LEV C #50
ø 1/4 (ø6.35) #100 Stop valve
Indoor unit C
Strainer
ø 1/4 (ø6.35) #100 LEV D
Indoor unit D

OBHT702H 61
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA

Operating Range
Indoor intake air temperature Outdoor intake air temperature
Maximum 95°FDB, 71°FWB 115°FDB
Cooling
Minimum 67°FDB, 57°FWB 14°FDB
Maximum 80°FDB, 67°FWB 75°FDB, 65°FWB
Heating
Minimum 70°FDB, 60°FWB 6°FDB, 5°FWB

MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION


Piping length each indoor unit (a, b, c, d) 82 ft. MAX.
Total piping length (a+b+c+d) 230 ft. MAX.
Bending point for each unit 25 MAX.
Total bending point 70 MAX.
*It is irrelevant which unit is higher.

Indoor a
units
Max. height difference

b Outdoor
unit 49 ft.

49 ft.
c

49 ft.
d

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When the diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Unit: inch
Outdoor unit union diameter
For
Liquid 1/4
Indoor unit A
Gas 1/2
Liquid 1/4
Indoor unit B
Gas 3/8
Liquid 1/4
Indoor unit C
Gas 3/8
Liquid 1/4
Indoor unit D
Gas 3/8

OBHT702H 62
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA Unit: inch (mm)
R.V.coil
OFF Refrigerant flow in heating
ON Refrigerant flow in cooling
Accumulator
Compressor
Compressor shell Service port
temperature
Oil separator thermistor RT62

High pressure switch


Union Header(Gas) Service port 4-way
ø 1/2 (ø12.7) valve
Indoor unit A Sub
muffler
ø 3/8 (ø9.52)
Indoor unit B
ø 3/8 (ø9.52) Stop valve Header(Evaporator)
Indoor unit C (with service port)
ø 3/8 (ø9.52) Capillary tube Outdoor
2-way
Indoor unit D O.D.0.10 x I.D.0.02 x 39.37 heat exchanger
solenoid valve
ø 3/8 (ø9.52) (ø2.5 x ø0.6 x 1000) Outdoor
Indoor unit E Ambient
heat exchanger
temperature temperature
thermistor thermistor
Capillary tube
RT68 RT65
O.D.0.16 x I.D.0.11 x 3.94
(ø4.0 x ø2.8 x 100)
Union Defrost
ø 1/4 (ø6.35) Strainer #100 LEV A temperature
Capillary tube
Indoor unit A thermistor
Strainer
RT61
ø 1/4 (ø6.35) Strainer #100 LEV B #100
Strainer
Indoor unit B Distributor #50
LEV C Strainer
ø 1/4 (ø6.35) Strainer #100 Stop valve #50
Indoor unit C
ø 1/4 (ø6.35) Strainer #100 LEV D
Indoor unit D
ø 1/4 (ø6.35)Strainer #100 LEV E
Indoor unit E

OBHT702H 63
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA

Operating Range
Indoor intake air temperature Outdoor intake air temperature
Maximum 95°FDB, 71°FWB 115°FDB
Cooling
Minimum 67°FDB, 57°FWB 14°FDB
Maximum 80°FDB, 67°FWB 75°FDB, 65°FWB
Heating
Minimum 70°FDB, 60°FWB 6°FDB, 5°FWB

MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION


Piping length each indoor unit (a, b, c, d, e) 82 ft. MAX.
Total piping length (a+b+c+d+e) 262 ft. MAX.
Bending point for each unit 25 MAX.
Total bending point 80 MAX.
*It is irrelevant which unit is higher.

Indoor a
units
Max. height difference

e
49 ft.
Outdoor
unit
b

49 ft.
c

49 ft.
d

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When the diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Unit: inch
Outdoor unit union diameter
For
Liquid 1/4
Indoor unit A
Gas 1/2
Liquid 1/4
Indoor unit B
Gas 3/8
Liquid 1/4
Indoor unit C
Gas 3/8
Liquid 1/4
Indoor unit D
Gas 3/8
Liquid 1/4
Indoor unit E
Gas 3/8

OBHT702H 64
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA Unit: inch (mm)
R.V.coil
OFF Refrigerant flow in heating
ON Refrigerant flow in cooling Accumulator
Compressor
Compressor shell Service port
temperature
Oil separator thermistor RT62

High pressure switch


Union Header(Gas) Service port 4-way
ø 3/8 (ø9.52) valve
Indoor unit A Sub
muffler

Stop valve Header(Evaporator)


(with service port)
Outdoor
Capillary tube
2-way heat exchanger
O.D.0.10 x I.D.0.02 x 39.37
solenoid valve
(ø2.5 x ø0.6 x 1000) Outdoor
ø 3/8 (ø9.52) Ambient
heat exchanger
Indoor unit B temperature
temperature
thermistor thermistor
Capillary tube RT68 RT65
O.D.0.16 x I.D.0.11 x 3.94
Union Strainer (ø4.0 x ø2.8 x 100)
Defrost
ø 1/4 (ø6.35) #100 LEV A
temperature
Indoor unit A Strainer Capillary tube thermistor
#100 RT61
Distributor
Strainer Strainer
Stop valve #50 #50

Strainer
ø 1/4 (ø6.35) #100 LEV B

Indoor unit B

OBHT702H 65
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA

Operating Range
Indoor intake air temperature Outdoor intake air temperature
Maximum 95°FDB, 71°FWB 115°FDB
Cooling
Minimum 67°FDB, 57°FWB 14°FDB
Maximum 80°FDB, 67°FWB 75°FDB, 65°FWB
Heating
Minimum 70°FDB, 60°FWB -12°FDB, -13°FWB

MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION


Piping length each indoor unit (a, b) 82 ft. MAX.
Total piping length (a+b) 164 ft. MAX.
Bending point for each unit 25 MAX.
Total bending point 50 MAX.
*It is irrelevant which unit is higher.

Indoor a
units
Max. height difference

Outdoor
unit 49 ft.

49 ft.

49 ft.
b

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When the diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Unit: inch
Outdoor unit union diameter
For
Liquid 1/4
Indoor unit A
Gas 3/8
Liquid 1/4
Indoor unit B
Gas 3/8

OBHT702H 66
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA Unit: inch (mm)
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
R. V. coil
OFF Refrigerant flow in heating
ON Refrigerant flow in cooling
Accumulator
Compressor
Compressor shell Service port
temperature
Oil separator thermistor RT62

High pressure switch


Union Header(Gas) Service port 4-way
ø 1/2 (ø12.7) valve
Indoor unit A Sub
muffler

Stop valve Header(Evaporator)


ø 3/8 (ø9.52)
Indoor unit B (with service port)
2-way Capillary tube Outdoor
solenoid valve heat exchanger
O.D.0.10 x I.D.0.02 x 39.37
ø 3/8 (ø9.52) (ø2.5 x ø0.6 x 1000) Outdoor
Indoor unit C Ambient
heat exchanger
temperature temperature
Capillary tube thermistor
thermistor
O.D.0.16 x I.D.0.11 x 3.94 RT65
(ø4.0 x ø2.8 x 100) RT68
Union Strainer
ø 1/4 (ø6.35) #100 LEV A
Defrost
Indoor unit A
Strainer temperature
Capillary tube
#100 thermistor
Strainer RT61
LEV B Strainer
ø 1/4 (ø6.35) #100 Stop valve Distributor #50
Indoor unit B Strainer
#50

Strainer
ø 1/4 (ø6.35) #100 LEV C
Indoor unit C

OBHT702H 67
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
Operating Range
Indoor intake air temperature Outdoor intake air temperature
Maximum 95°FDB, 71°FWB 115°FDB
Cooling
Minimum 67°FDB, 57°FWB 14°FDB
Maximum 80°FDB, 67°FWB 75°FDB, 65°FWB
Heating
Minimum 70°FDB, 60°FWB -12°FDB, -13°FWB

MAX. REFRIGERANT PIPING LENGTH & PIPE SIZE SELECTION


Piping length each indoor unit (a, b, c) 82 ft. MAX.
Total piping length (a+b+c) 230 ft. MAX.
Bending point for each unit 25 MAX.
Total bending point 70 MAX.
*It is irrelevant which unit is higher.
Indoor a
units
Max. height difference

Outdoor
unit
c 49 ft.

49 ft.

49 ft.
b

Refrigerant pipe diameter is different according to indoor unit to be connected. When using extension pipes, refer to the
tables below.
When the diameter of refrigerant pipe is different from that of outdoor unit union, use optional Different-diameter pipe.
For further information on Different-diameter pipe, refer to "PARTS CATALOG".
Unit: inch
Outdoor unit union diameter
For
Liquid 1/4
Indoor unit A
Gas 1/2
Liquid 1/4
Indoor unit B
Gas 3/8
Liquid 1/4
Indoor unit C
Gas 3/8

OBHT702H 68
PUMPING DOWN
When relocating or disposing of the air conditioner, pump down the system following the procedure below so that no refrigerant is
released into the atmosphere.
1) Turn off the breaker.
2) Connect the gauge manifold valve to the service port of the stop valve on the gas pipe side of the outdoor unit.
3) Fully close the stop valve on the liquid pipe side of the outdoor unit.
4) Turn on the breaker.
5) Start the emergency COOL operation on all the indoor units.
6) When the pressure gauge shows 0.1 to 0 psi [Gauge] (0.05 to 0 MPa), fully close the stop valve on the gas pipe side of the
outdoor unit and stop the operation. (Refer to the indoor unit installation manual about the method for stopping the operation.)
* If too much refrigerant has been added to the air conditioner system, the pressure may not drop to 0.1 to 0 psi [Gauge] (0.05 to
0 MPa), or the protection function may operate due to the pressure increase in the high pressure refrigerant circuit. If this occurs,
use a refrigerant collecting device to collect all of the refrigerant in the system, and then recharge the system with the correct
amount of refrigerant after the indoor and outdoor units have been relocated.
7) Turn off the breaker. Remove the pressure gauge and the refrigerant piping.

WARNING
When pumping down the refrigerant, stop the compressor before disconnecting the refrigerant pipes.
The compressor may burst and cause injury if any foreign substance, such as air, enters the pipes.

OBHT702H 69
9 DATA

NTXMMX20A122AA NTXMMX20A122AC
Model NTXMMX20A122CA
NTXMMX20A122BA NTXMMX20A122CA
Indoor type Non-Duct (09+09) Duct (09+12)*1 Duct(09+12) *2
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 18,000 22,000 20,000 22,000 20,000 22,000
SHF – – – – – – –
Input kW 1.417 1.641 2.000 1.771 2.000 1.771
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit
Input kW 1.373 1.597 1.880 1.691 1.857 1.668

Comp. current (208/230V) A 6.60 / 5.97 7.68 / 6.94 9.61 / 8.69 8.55 / 7.73 8.93 / 8.07 8.02 / 7.25

Fan motor current A 0.2 0.2 0.2 0.2 0.2 0.2


Refrigerant Condensing pressure PSIG 396 328 419 351 433 335
circuit Suction pressure PSIG 146 94 130 100 133 101
Discharge temperature °F 174 165 170 168 171 163
Condensing temperature °F 116 100 160 101 122 104
Suction temperature °F 74 47 55 49 56 46
Comp. shell bottom temp. °F 173 163 160 157 134 116
Ref. pipe length
ft 82 [164]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 5 lb. 15 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 650 700 650 700 650 700
Airflow CFM 1,342 1,458 1,342 1,458 1,342 1,458
*1: NT/AXDKS09A112AA + NT/AXDKS12A112AA
*2: T/APEADA0091AA + T/APEADA0121AA
NTXMMX24A132AA
Model NTXMMX24A132BA
NTXMMX24A132BA
Indoor type Non-Duct (06+06+09) Duct (09+09+09) Duct(12+12)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total
Capacity Btu/h 22,000 25,000 23,600 24,600 23,600 24,000

SHF – – – – – – –
Input kW 1.62 1.75 2.10 1.90 2.195 1.890
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 1.554 1.684 1.920 1.780 2.031 1.766

Comp. current (208/230V) A 7.47 / 6.76 8.1 / 7.32 9.23 / 8.35 8.56 / 7.74 9.76 / 8.83 8.49 / 7.68

Fan motor current A 0.3 0.3 0.3 0.3 0.3 0.3


Refrigerant Condensing pressure PSIG 395 310 419 345 416 336
circuit Suction pressure PSIG 162 101 138 102 145 102
Discharge temperature °F 143 137 155 141 153 138
Condensing temperature °F 116 98 120 106 119 104
Suction temperature °F 59 36 50 34 52 34
Comp. shell bottom temp. °F 137 128 146 131 150 134
Ref. pipe length
ft 82 [230]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 6lb. 13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 720 750 720 750 720 750
Airflow CFM 2,287 2,382 2,287 2,382 2,287 2,382

OBHT702H 70
Model NTXMMX24A132CA
Indoor type Non-Duct (06+06+09) Duct (09+09+09) Duct(12+12)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total
Capacity Btu/h 22,000 25,000 23,600 24,600 23,600 24,000

SHF – – – – – – –
Input kW 1.61 1.74 2.10 1.89 2.11 1.85
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 1.554 1.684 1.920 1.780 1.907 1.651
Comp. current (208/230V) A 7.47 / 6.76 8.1 / 7.32 9.23 / 8.35 8.56 / 7.74 9.17 / 8.29 7.94 / 7.18
Fan motor current A 0.3 0.3 0.3 0.3 0.3 0.3
Refrigerant Condensing pressure PSIG 407 317 419 345 393 295
circuit Suction pressure PSIG 161 98 138 102 146 107
Discharge temperature °F 147 140 155 141 138 123
Condensing temperature °F 116 110 120 106 115 95
Suction temperature °F 59 34 50 34 54 36
Comp. shell bottom temp. °F 141 131 146 131 144 128
Ref. pipe length
ft 82 [230]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 6lb. 13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 650 680 650 680 650 680
Airflow CFM 2,133 2,243 2,133 2,243 2,133 2,243

Model NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132BA


Indoor type Non-Duct (09+09+12) Duct (09+09+12) Duct(15+15)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 28,400 28,600 27,400 27,600 23,600 24,000
SHF – – – – – – –
Input kW 2.68 2.15 2.84 2.22 2.840 2.220
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 2.614 2.084 2.650 2.090 2.620 2.040
Comp. current (208/230V) A 12.57 / 11.37 10.02 / 9.06 12.74 / 11.52 10.05 / 9.09 12.60/11.39 9.81/8.87
Fan motor current A 0.3 0.3 0.3 0.3 0.3 0.3
Refrigerant Condensing pressure PSIG 432 323 439 323 441 303
circuit Suction pressure PSIG 137 97 132 99 144 96
Discharge temperature °F 159 136 165 136 162 134
Condensing temperature °F 122 101 124 101 124 97
Suction temperature °F 49 32 47 32 52 31
Comp. shell bottom temp. °F 145 121 156 128 159 130
Ref. pipe length
ft 82 [230]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 6 lb.13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 720 750 720 750 720 750
Airflow CFM 2,287 2,382 2,287 2,382 2,287 2,382

OBHT702H 71
Model NTXMMX30A132CA
Indoor type Non-Duct (09+09+12) Duct (09+09+12) Duct (18+18)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 28,400 28,600 27,400 27,600 27,400 27,600
SHF – – – – – – –
Input kW 2.67 2.149 2.84 2.22 2.85 2.25
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 2.614 2.084 2.650 2.090 2.534 1.927
Comp. current (208/230V) A 12.57 / 11.37 10.02 / 9.06 12.74 / 11.52 10.05 / 9.09 12.18 / 11.02 9.26 / 8.38
Fan motor current A 0.3 0.3 0.3 0.3 0.3 0.3
Refrigerant Condensing pressure PSIG 440 323 440 323 412 289
circuit Suction pressure PSIG 142 94 130 99 151 101
Discharge temperature °F 161 139 160 136 143 121
Condensing temperature °F 121 101 119 101 119 93
Suction temperature °F 52 30 52 32 57 34
Comp. shell bottom temp. °F 147 124 151 128 150 127
Ref. pipe length
ft 82 [230]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 6 lb.13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 650 680 650 680 650 680
Airflow CFM 2,133 2,243 2,133 2,243 2,133 2,243

Model NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142BA


Indoor type Non-Duct (09+09+09+09) Duct (09+09+09+09) Duct(18+18)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 35,400 36,000 34,400 34,400 33,400 34,400
SHF – – – – – – –
Input kW 3.76 3.02 3.94 3.10 3.839 3.10
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 3.672 2.932 3.700 2.940 3.619 2.920
Comp. current (208/230V) A 17.65 / 15.97 14.1 / 12.75 17.79 / 16.09 14.13 / 12.78 17.40/15.73 14.04/12.70
Fan motor current A 0.3 0.3 0.3 0.3 0.3 0.3
Refrigerant Condensing pressure PSIG 461 297 470 334 479 325
circuit Suction pressure PSIG 141 89 129 91 134 90
Discharge temperature °F 172 138 176 147 176 143
Condensing temperature °F 127 95 129 103 130 101
Suction temperature °F 51 28 46 29 48 28
Comp. shell bottom temp. °F 162 130 165 139 173 140
Ref. pipe length
ft 82 [230]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 6 lb.13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 720 750 720 750 720 750
Airflow CFM 2,287 2,382 2,287 2,382 2,287 2,382

OBHT702H 72
Model NTXMMX36A142CA
Non-Duct
Indoor type Duct (09+09+09+09) Duct (18+18)
(09+09+09+09)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 35,400 36,000 34,400 34,400 33,400 34,400
SHF – – – – – – –
Input kW 3.76 3.01 3.94 3.09 3.84 3.09
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 3.672 2.932 3.700 2.940 3.520 2.770
Comp. current (208/230V) A 17.65 / 15.97 14.1 / 12.75 17.79 / 16.09 14.13 / 12.78 16.92 / 15.30 13.32 / 12.04
Fan motor current A 0.3 0.3 0.3 0.3 0.3 0.3
Refrigerant Condensing pressure PSIG 479 297 470 334 455 313
circuit Suction pressure PSIG 143 86 129 91 137 95
Discharge temperature °F 175 140 176 147 158 132
Condensing temperature °F 128 95 129 103 126 99
Suction temperature °F 51 26 46 29 53 31
Comp. shell bottom temp. °F 165 132 165 139 165 139
Ref. pipe length
ft 82 [230]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 6 lb.13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 650 680 650 680 650 680
Airflow CFM 2,133 2,243 2,133 2,243 2,133 2,243

NTXMMX42A152AA NTXMMX42A152BA
Model NTXMMX42A152CA
NTXMMX42A152CA
Indoor type Non-Duct (06+09+09+09+09) Duct (09+09+09+09+09) Duct(24+24)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 40,500 45,000 37,400 41,000 36,400 41,000
SHF – – – – – – –
Input kW 4.41 3.58 4.112 3.403 4.045 4.52
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 4.300 3.465 3.870 3.270 3.685 4.160
Comp. current (208/230V) A 20.67 / 18.7 16.66 / 15.07 18.61 / 16.83 15.72 / 14.22 17.72/16.02 20.00/18.09
Fan motor current A 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39
Refrigerant Condensing pressure PSIG 466 305 446 326 449 325
circuit Suction pressure PSIG 153 93 137 98 133 96
Discharge temperature °F 172 155 165 143 165 152
Condensing temperature °F 127 97 124 102 125 101
Suction temperature °F 53 27 47 29 49 32
Comp. shell bottom temp. °F 156 138 145 121 165 152
Ref. pipe length
ft 82 [262]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 8 lb. 13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 630 730 630 730 630 730
Airflow CFM 2,118 2,542 2,118 2,542 2,118 2,542

OBHT702H 73
NTXMPH20A122AA NTXMPH20A122BA
Model NTXMPH20A122CA
NTXMPH20A122CA
Indoor type Non-Duct (09+09) Duct (09+12) Duct(12+12)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 18,000 22,000 20,000 22,000 20,000 22,000
SHF – – – – – – –
Input kW 1.34 1.62 1.82 1.75 1.82 1.75
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 1.296 1.574 1.670 1.660 1.619 1.550
Comp. current (208/230V) A 6.23 / 5.63 7.57 / 6.84 8.03 / 7.26 7.98 / 7.22 7.78 / 7.04 7.45 / 6.74
Fan motor current A 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39
Refrigerant Condensing pressure PSIG 406 341 406 334 366 235
circuit Suction pressure PSIG 154 110 133 113 159 112
Discharge temperature °F 158 131 148 141 125 128
Condensing temperature °F 108 105 112 103 110 80
Suction temperature °F 60 37 46 37 58 38
Comp. shell bottom temp. °F 137 107 127 117 126 128
Ref. pipe length
ft 82 [164]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 8 lb. 13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 630 730 630 730 630 730
Airflow CFM 2,118 2,542 2,118 2,542 2,118 2,542

NTXMPH24A132AA NTXMPH24A132BA
Model NTXMPH24A132CA
NTXMPH24A132CA
Indoor type Non-Duct (06+06+09) Duct (09+09+09) Duct(12+12)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 22,000 25,000 23,600 24,600 23,600 24,600
SHF – – – – – – –
Input kW 1.63 1.73 2.36 1.88 2.36 1.955
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 1.564 1.661 2.180 1.760 2.160 1.750
Comp. current (208/230V) A 7.52 / 6.8 7.99 / 7.22 10.48 / 9.48 8.46 / 7.65 10.38 / 9.39 8.41 / 7.61
Fan motor current A 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39
Refrigerant Condensing pressure PSIG 397 302 377 329 398 248
circuit Suction pressure PSIG 164 106 136 109 144 109
Discharge temperature °F 144 122 152 127 141 132
Condensing temperature °F 114 97 115 103 116 83
Suction temperature °F 59 42 48 36 53 37
Comp. shell bottom temp. °F 128 105 136 109 142 132
Ref. pipe length
ft 82 [230]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 8 lb. 13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 630 730 630 730 630 730
Airflow CFM 2,118 2,542 2,118 2,542 2,118 2,542

OBHT702H 74
NTXMPH30A132AA NTXMPH30A132BA
Model NTXMPH30A132CA
NTXMPH30A132CA
Indoor type Non-Duct (09+09+12) Duct (09+09+12) Duct(18+18)
Item Unit Cooling Heating Cooling Heating Cooling Heating
Total Capacity Btu/h 28,400 28,600 27,400 27,600 27,400 27,600
SHF – – – – – – –
Input kW 2.28 2.10 2.67 2.19 2.66 2.28
Electrical Power supply (V, phase, Hz) 208/230, 1, 60
circuit Input kW 2.214 2.031 2.480 2.060 2.340 1.960
Comp. current (208/230V) A 10.64 / 9.63 9.76 / 8.83 11.92 / 10.78 9.9 / 8.96 11.25 / 10.17 9.42 / 8.52
Fan motor current A 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39 0.43 / 0.39
Refrigerant Condensing pressure PSIG 404 321 416 329 412 272
circuit Suction pressure PSIG 146 103 131 107 153 102
Discharge temperature °F 146 131 153 128 147 125
Condensing temperature °F 117 101 118 103 119 89
Suction temperature °F 52 35 45 35 55 35
Comp. shell bottom temp. °F 129 111 135 108 148 125
Ref. pipe length
ft 82 [230]
[Total pipe length for multi-system]
Refrigerant charge (R410A) – 8 lb. 13 oz.
Outdoor Intake air temperature DB °F 95 47 95 47 95 47
unit WB °F – 43 – 43 – 43
Fan speed rpm 650 730 630 730 630 730
Airflow CFM 2,224 2,542 2,118 2,542 2,118 2,542

OBHT702H 75
9-1. OPERATING RANGE
(1) POWER SUPPLY
Model Rating Guaranteed Voltage
NTXMMX20A122AA NTXMPH20A122AA
NTXMMX20A122AC NTXMPH20A122BA
NTXMMX20A122BA NTXMPH20A122CA
NTXMMX20A122CA NTXMPH24A132AA
NTXMMX24A132AA NTXMPH24A132BA
NTXMMX24A132BA NTXMPH24A132CA
NTXMMX24A132CA NTXMPH30A132AA
NTXMMX30A132AA NTXMPH30A132BA Min. 198 V 208 V 230 V Max. 253 V
Outdoor unit 208/230 V 60 Hz 1ø
NTXMMX30A132BA NTXMPH30A132CA
NTXMMX30A132CA
NTXMMX36A142AA
NTXMMX36A142BA
NTXMMX36A142CA
NTXMMX42A152AA
NTXMMX42A152BA
NTXMMX42A152CA

(2) OPERATION
Intake air Indoor Outdoor
Function temperature
Condition DB (°F) WB (°F) DB (°F) WB (°F)
"A" Cooling steady state
80 67 95 (75)
at rated compressor speed
"B-2" Cooling steady state
80 67 82 (65)
at rated compressor speed
"B-1" Cooling steady state
Cooling 80 67 82 (65)
at minimum compressor speed
Low ambient cooling steady state
80 67 67 (53.5)
at minimum compressor speed
Intermediate cooling steady state
80 67 87 (69)
at intermediate compressor speed
Standard rating-heating
70 60 47 43
at rated compressor speed
Low temperature heating
70 60 17 15
at rated compressor speed
Max. temperature heating
70 60 62 56.5
at minimum compressor speed
Heating
High temperature heating
70 60 47 43
at minimum compressor speed
Frost accumulation
70 60 35 33
at rated compressor speed
Frost accumulation
70 60 35 33
at intermediate compressor speed

OBHT702H 76
NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA
NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
The standard specifications apply only to the operation of the air conditioner under normal conditions.
Since operating conditions vary according to the areas where these units are installed, the following information has been pro-
vided to clarify the operating characteristics of the air conditioner under the conditions indicated by the performance curve.
(1) GUARANTEED VOLTAGE
198 ~ 253 V 60 Hz
(2) AIR FLOW
Air flow should be set at MAX.
(3) MAIN READINGS

}
(1) Indoor intake air wet-bulb temperature : °FWB
(2) Indoor outlet air wet-bulb temperature : °FWB
Cooling
(3) Outdoor intake air dry-bulb temperature : °FDB
(4) Total input: W
(5) Indoor intake air dry-bulb temperature :
(6) Outdoor intake air wet-bulb temperature :
(7) Total input :
°FDB
°FWB
W
} Heating

Indoor air wet and dry bulb temperature difference on the left side of the following chart shows the difference between the
indoor intake air wet and dry bulb temperature and the indoor outlet air wet and dry bulb temperature for your reference at
service.
How to measure the indoor air wet and dry bulb temperature difference
1. Attach at least 2 sets of wet and dry bulb thermometers to the indoor air intake as shown in the figure, and at least 2 sets of
wet and dry bulb thermometers to the indoor air outlet. The thermometers must be attached to the position where air speed
is high.
2. Attach at least 2 sets of wet and dry bulb thermometers to the outdoor air intake.
Cover the thermometers to prevent direct rays of the sun.
3. Check that the air filter is cleaned.
4. Open windows and doors of room.
5. Press the EMERGENCY OPERATION switch once (twice) to start the EMERGENCY COOL (HEAT) MODE.
6. Compressor starts running at 33 Hz (COOL) or 45 Hz (HEAT). The frequency at each operation mode is fixed.
7. When system stabilizes after more than 15 minutes, measure temperature and take an average temperature.
8. 10 minutes later, measure temperature again and check that the temperature does not change.

INDOOR UNIT OUTDOOR UNIT

Wet and dry bulb


Wet and dry bulb thermometers
thermometers

OBHT702H 77
9-2. CAPACITY AND THE INPUT CURVES
NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA

Cooling capacity
6.8 9.6 11.7 11.4 1.3

Capacity correction factors


Indoor air Wet-bulb temperature

6.2 8.8 10.7 10.5 1.2

5.7 8.0 9.7 9.5 1.1


difference (°F)

5.1 7.2 8.7 8.5 1.0


79
4.6 6.5 7.8 7.6 0.9 75
72
68
4.1 5.8 6.9 6.7 0.8
67
64
3.6 5.1 6.0 5.8 0.7
60
Indoor intake air Wet-bulb temperature (°F)
14 24 34 44 54 64 74 84 94 104 114
06 class

09 class

12 class

15 class

Outdoor intake air Dry-bulb temperature (°F)

Total input (Cooling)


1.3
Input correction factors

1.2
64
1.1 67
Indoor intake air Wet-bulb temperature (°F) 68
1.0
72
0.9 60
75
0.8 79
0.7

0.6

0.5

0.4

14 24 34 44 54 64 74 84 94 104 114
Outdoor intake air Dry-bulb temperature (°F)

Heating capacity
26.1 36.7 48.2 52.8 1.4
59
24.3 34.0 44.8 49.1 1.3 68
Capacity correction factors

79
22.5 31.3 41.4 45.4 1.2
Indoor air Wet-bulb temperature

20.5 28.8 38.0 41.6 1.1

18.5 25.7 34.0 37.4 1.0


°F)
difference (°F)

e(
16.6 23.2 30.6 33.7 0.9 ra tur
pe
14.8 20.7 27.2 29.9 0.8 tem
lb
ry -bu
13.0 18.0 24.1 26.5 0.7
air D
ake
11.0 15.3 20.2 22.1 0.6
r int
oo
9.2 13.0 17.1 18.7 0.5 Ind
7.4 10.3 13.5 14.8 0.4

3 7 11 15 19 23 27 31 35 39 43 47 51 55 59 63
06 class

09 class

12 class

15 class

Outdoor intake air Wet-bulb temperature (°F)

Total input (Heating)


1.3

1.2 79
68
Input correction factors

1.1
59
1.0
°F)
0.9 re (
er atu
emp
0.8 lb t
-bu
0.7 ir Dry
kea
inta
0.6 oor
Ind
0.5

0.4

3 7 11 15 19 23 27 31 35 39 43 47 51 55 59 63
Outdoor intake air Wet-bulb temperature (°F)

OBHT702H 78
NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA

Cooling capacity
6.8 9.6 11.7 11.4 14.5 13.2 1.3

Capacity correction factors


Indoor air Wet-bulb temperature

6.2 8.8 10.7 10.5 13.2 12.1 1.2

5.7 8.0 9.7 9.5 12.0 10.9 1.1


difference (°F)

5.1 7.2 8.7 8.5 10.7 9.8 1.0


79
4.6 6.5 7.8 7.6 9.5 8.7 0.9 75
72
68
4.1 5.8 6.9 6.7 8.3 7.6 0.8 67
64
3.6 5.1 6.0 5.8 7.1 6.5 0.7 60
Indoor intake air Wet-bulb temperature (°F)

14 24 34 44 54 64 74 84 94 104 114
06 class

09 class

12 class

15 class

18 class

24 class

Outdoor intake air Dry-bulb temperature (°F)

Total input (Cooling)


1.3
1.2
64
Input correction factors

1.1 Indoor intake air Wet-bulb temperature (°F) 67


1.0 68
60
0.9 72
0.8 75
79
0.7
0.6
0.5
0.4

14 24 34 44 54 64 74 84 94 104 114
Outdoor intake air Dry-bulb temperature (°F)

Heating capacity
26.1 36.7 48.2 52.8 56.5 42.9 1.4 59
Capacity correction factors

24.3 34.0 44.8 49.1 52.8 39.8 1.3 68


79
22.5 31.3 41.4 45.4 49.1 36.7 1.2
Indoor air Wet-bulb temperature

20.5 28.8 38.0 41.6 45.2 33.7 1.1


18.5 25.7 34.0 37.4 40.5 30.2 1.0 )
difference (°F)

(°F
0.9 ure
rat
16.6 23.2 30.6 33.7 36.5 27.2
pe
14.8 20.7 27.2 29.9 32.4 24.1 0.8 tem
lb
bu
13.0 18.0 24.1 26.5 29.0 21.4 0.7 ry-
a ir D
11.0 15.3 20.2 22.1 24.1 18.0 0.6 t ake
r in
oo
9.2 13.0 17.1 18.7 20.5 15.1 0.5 Ind
7.4 10.3 13.5 14.8 16.0 11.9 0.4

3 7 11 15 19 23 27 31 35 39 43 47 51 55 59 63
06 class

09 class

12 class

15 class

18 class

24 class

Outdoor intake air Wet-bulb temperature (°F)

Total input (Heating)


1.3

1.2 79
Input correction factors

68
1.1 59
1.0
°F)
0.9 re (
atu
per
em
0.8 lb t
-bu
Dry
0.7 air
ta ke
0.6 oo r in
Ind
0.5
0.4

3 7 11 15 19 23 27 31 35 39 43 47 51 55 59 63
Outdoor intake air Wet-bulb temperature (°F)

OBHT702H 79
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA

Cooling capacity
6.8 9.6 11.7 11.4 14.5 13.2 1.3

Capacity correction factors


Indoor air Wet-bulb temperature

6.2 8.8 10.7 10.5 13.2 12.1 1.2

5.7 8.0 9.7 9.5 12.0 10.9 1.1


difference (°F)

5.1 7.2 8.7 8.5 10.7 9.8 1.0


79
4.6 6.5 7.8 7.6 9.5 8.7 0.9 75
72
0.8 68
4.1 5.8 6.9 6.7 8.3 7.6 67
64
3.6 5.1 6.0 5.8 7.1 6.5 0.7 60
Indoor intake air Wet-bulb temperature (°F)
14 24 34 44 54 64 74 84 94 104 114
06 class

09 class

12 class

15 class

18 class

24 class

Outdoor intake air Dry-bulb temperature (°F)

Total input (Cooling)


1.3
1.2
Input correction factors

1.1
1.0 Indoor intake air Wet-bulb temperature (°F) 60
64
0.9 67
68
0.8 72
0.7 75
79
0.6
0.5
0.4

14 24 34 44 54 64 74 84 94 104 114
Outdoor intake air Dry-bulb temperature (°F)

Heating capacity
26.1 36.7 48.2 52.8 56.5 42.9 1.4 59
Capacity correction factors

24.3 34.0 44.8 49.1 52.8 39.8 1.3 68


79
22.5 31.3 41.4 45.4 49.1 36.7 1.2
Indoor air Wet-bulb temperature

20.5 28.8 38.0 41.6 45.2 33.7 1.1


18.5 25.7 34.0 37.4 40.5 30.2 1.0
°F)
difference (°F)

e(
16.6 23.2 30.6 33.7 36.5 27.2 0.9 tur
pera
14.8 20.7 27.2 29.9 32.4 24.1 0.8 tem
lb
bu
0.7 ry-
ir D
13.0 18.0 24.1 26.5 29.0 21.4
a
11.0 15.3 20.2 22.1 24.1 18.0 0.6 t ake
r in
oo
9.2 13.0 17.1 18.7 20.5 15.1 0.5 Ind
7.4 10.3 13.5 14.8 16.0 11.9 0.4

3 7 11 15 19 23 27 31 35 39 43 47 51 55 59 63
06 class

09 class

12 class

15 class

18 class

24 class

Outdoor intake air Wet-bulb temperature (°F)

Total input (Heating)


1.3

1.2 79
68
Input correction factors

1.1 59

1.0
°F)
0.9 re (
atu
per
em
0.8 lb t
-bu
Dry
0.7 air
ta ke
0.6 oo r in
Ind
0.5
0.4

3 7 11 15 19 23 27 31 35 39 43 47 51 55 59 63
Outdoor intake air Wet-bulb temperature (°F)

OBHT702H 80
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA

Cooling capacity
6.8 9.6 11.7 11.4 14.5 13.2 1.3

Capacity correction factors


Indoor air Wet-bulb temperature

6.2 8.8 10.7 10.5 13.2 12.1 1.2

5.7 8.0 9.7 9.5 12.0 10.9 1.1


difference (°F)

5.1 7.2 8.7 8.5 10.7 9.8 1.0


79
4.6 6.5 7.8 7.6 9.5 8.7 0.9 75
72
68
4.1 5.8 6.9 6.7 8.3 7.6 0.8 67
64
3.6 5.1 6.0 5.8 7.1 6.5 0.7 60
Indoor intake air Wet-bulb temperature (°F)

14 24 34 44 54 64 74 84 94 104 114
06 class

09 class

12 class

15 class

18 class

24 class

Outdoor intake air Dry-bulb temperature (°F)

Total input (Cooling)


1.3
1.2
Input correction factors

1.1
1.0 Indoor intake air Wet-bulb temperature (°F) 64
67
0.9 60
0.8 68
72
0.7 75
0.6 79

0.5
0.4

14 24 34 44 54 64 74 84 94 104 114
Outdoor intake air Dry-bulb temperature (°F)

Heating capacity
26.1 36.7 48.2 52.8 56.5 42.9 1.4 59
Capacity correction factors

24.3 34.0 44.8 49.1 52.8 39.8 1.3 68


79
Indoor air Wet-bulb temperature

22.5 31.3 41.4 45.4 49.1 36.7 1.2


20.5 28.8 38.0 41.6 45.2 33.7 1.1
difference (°F)

18.5 25.7 34.0 37.4 40.5 30.2 1.0

16.6 23.2 30.6 33.7 36.5 27.2 0.9


Indoor intake air Dry-bulb temperature (°F)
14.8 20.7 27.2 29.9 32.4 24.1 0.8

13.0 18.0 24.1 26.5 29.0 21.4 0.7

11.0 15.3 20.2 22.1 24.1 18.0 0.6

9.2 13.0 17.1 18.7 20.5 15.1 0.5

-14 -10 -6 -2 2 6 10 14 18 22 26 30 34 38 42 46 50 54 58 62
06 class

09 class

12 class

15 class

18 class

24 class

Outdoor intake air Wet-bulb temperature (°F)

Total input (Heating)


1.7
1.6
Input correction factors

1.5
In
1.4 do
or
in
1.3 ta
ke
air
1.2 Dr 79
y-
bu 68
1.1 lb
te 59
m
pe
1.0 ra
tu
re
0.9 (°F
)
0.8

-14 -10 -6 -2 2 6 10 14 18 22 26 30 34 38 42 46 50 54 58 62
Outdoor intake air Wet-bulb temperature (°F)

OBHT702H 81
9-3. CAPACITY AND INPUT CORRECTION BY MEANS OF INVERTER OUTPUT FREQUENCY
(OUTDOOR UNIT: NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA)

1. 06-class unit in single operation


<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.5 2.5

2.0 2.0
1.5 1.5

1.5 1.5
1.0 1.0
1.0 1.0

0.5 0.5
0.5 0.5

0 50 100 150Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
2. 09-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 3.0

2.5
1.5 1.5 1.5
2.0

1.0 1.0 1.0 1.5

1.0
0.5 0.5 0.5
0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
3. 12-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
4. 15-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency

OBHT702H 82
(OUTDOOR UNIT: NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA)
1. 06-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.5

2.0
1.5 1.5 1.5

1.5
1.0 1.0 1.0
1.0

0.5 0.5 0.5


0.5

0 50 100 150Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
2. 09-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
3. 12-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
4. 15-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
5. 18-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
6. 24-class unit in single operation (NTXMMX30A132AA/36A142AA only)
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency

OBHT702H 83
(OUTDOOR UNIT: NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA)
1. 06-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
2. 09-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
3. 12-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
4. 15-class unit in single operation
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
5. 18-class unit in single operation (NTXMMX42A152AA, NTXMPH24A/30A132AA only)
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency
6. 24-class unit in single operation (NTXMMX42A152AA, NTXMPH24A/30A132AA only)
<COOL>Capacity <COOL>Total input <HEAT>Capacity <HEAT>Total input
2.0 2.0 2.0 2.0

1.5 1.5 1.5 1.5

1.0 1.0 1.0 1.0

0.5 0.5 0.5 0.5

0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz 0 50 100 150 Hz


Frequency Frequency Frequency Frequency

OBHT702H 84
9-4. OUTDOOR LOW PRESSURE AND OUTDOOR UNIT CURRENT
1. 06-class unit in single operation
(OUTDOOR UNIT: NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 40 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 40 Hz (COOL) or 48 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.

(PSIG)
170 6.0

re (°F)
ulb temperatu 86 5.0
160 Indoor Dry-b
(°F)

Outdoor unit current (A)


era ture 86
Outdoor low pressure

4.0 bt emp 80
ry -bul 75
150 80 or D 70
Indo
3.0 40 Hz
140 75
2.0

130 70 1.0
40 Hz
120 0.0
65 70 75 80 85 90 95 100 105 110 115 (°F) 65 70 75 80 85 90 95 100 105 110 115 (°F)

Ambient temperature (°F) Ambient temperature (°F)

(2) HEAT operation 7.0


Data is based on the condition of indoor humidity
75%
Set air flow to High speed.
Outdoor unit current (A)

6.0
Inverter output frequency is 48 Hz.

5.0 F)
ratu re (°
tempe
ry- bulb 75
4.0 Indoor D 70
65

3.0

48 Hz
2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (°F)
Ambient temperature (°F)

OBHT702H 85
2. 09-class unit in single operation
(OUTDOOR UNIT: NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 40 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 40 Hz (COOL) or 48 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.

(PSIG)
170 6.0

re (°F)
ulb temperatu 86 5.0
160 Indoor Dry-b Outdoor unit current (A) (°F)
era ture 86
Outdoor low pressure

4.0 bt emp 80
ry -bul 75
150 80 or D 70
Indo
3.0 40 Hz
140 75
2.0

130 70 1.0
40 Hz
120 0.0
65 70 75 80 85 90 95 100 105 110 115 (°F) 65 70 75 80 85 90 95 100 105 110 115 (°F)

Ambient temperature (°F) Ambient temperature (°F)

(2) HEAT operation 7.0


Data is based on the condition of indoor humidity
75%
Set air flow to High speed.
Outdoor unit current (A)

6.0
Inverter output frequency is 48 Hz.

5.0 F)
ratu re (°
tempe
ry- bulb 75
4.0 Indoor D 70
65

3.0

48 Hz
2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (°F)
Ambient temperature (°F)

OBHT702H 86
3. 12-class unit in single operation
(OUTDOOR UNIT: NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 40 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 40 Hz (COOL) or 48 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.

(PSIG)
170 6.0
r e (˚F)
eratu 86
bulb temp 5.0
160 r Dry- (˚F)
Indoo
Outdoor low pressure

ure
Outdoor unit current (A)
rat
te mpe 86
80 4.0
y-bulb 80
150 o r Dr 75
Indo 70
3.0
75 40 Hz
140
2.0

130 70
1.0
40 Hz

120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of indoor humidity 7.0
75%
Set air flow to High speed.
Outdoor unit current (A)

Inverter output frequency is 48 Hz. 6.0

5.0
(˚F)
era ture
temp 75
4.0 ry- bulb 70
or D
Indo 65

3.0
48 Hz

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 87
4. 15-class unit in single operation
(OUTDOOR UNIT: NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 40 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 40 Hz (COOL) or 48 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.

(PSIG)
170 6.0
F)
at ure (˚ 86
lb temper
160 rD ry-bu 5.0
Indoo
Outdoor low pressure

F)
Outdoor unit current (A)
ratu re (˚ 86
80 4.0 te mpe 80
ry-bulb 75
150 or D 70
Indo
3.0
75 40 Hz
140
2.0
70
130
1.0
40 Hz
120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of indoor humidity 7.0
75%
Set air flow to High speed.
Outdoor unit current (A)

Inverter output frequency is 48 Hz. 6.0

5.0
(˚F)
rature
e mpe
ulb t
4.0 rD ry-b 75
In doo 70
65

3.0
48 Hz

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 88
5. 06-class unit in single operation
(OUTDOOR UNIT: NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 24 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 24 Hz (COOL) or 32 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.

(PSIG)
160 86 6.0
re (˚F)
eratu
temp
ry-bulb 5.0
150 oor D (˚F) 86
Ind ture

Outdoor unit current (A)


era 80
temp
Outdoor low pressure

80 bulb 75
4.0 or Dry- 70
140 Indo
75 3.0 24 Hz

130
2.0
70

120 24 Hz 1.0

110 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation 7.0


Data is based on the condition of outdoor humidity
75%.
Set air flow to High speed. ˚F)
Outdoor unit current (A)

Inverter output frequency is 32 Hz.


6.0
ure( 75
erat 70
temp 65
lb
bu
5.0 ry-
rD
oo
Ind
32 Hz
4.0

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 89
6. 09-class unit in single operation
(OUTDOOR UNIT: NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 24 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 24 Hz (COOL) or 32 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.

(PSIG)
160 86 6.0
(˚F)
ture
tempera
Dry-bulb 5.0 )
150 door e (˚F 86
ratur
Outdoor unit current (A)
In pe 80
b tem
Outdoor low pressure

80 l
4.0 ry-bu 75
or D 70
140 Indo
75 3.0 24 Hz

130
2.0
70

120 24 Hz 1.0

110 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation 7.0


Data is based on the condition of outdoor humidity
75%.
)
Set air flow to High speed. (˚F
Outdoor unit current (A)

6.0 e 75
Inverter output frequency is 32 Hz. ra tur
e 70
temp 65
lb
5.0 y-bu
r Dr
oo
Ind
32 Hz
4.0

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 90
7. 12-class unit in single operation
(OUTDOOR UNIT: NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 24 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 24 Hz (COOL) or 32 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(PSIG)
160 86 6.0
(˚F)
rature
re (˚F
) mpe
eratu 5.0 b te
150 emp -bul 86
bulb t or D
ry
Outdoor low pressure

80
Outdoor unit current (A)
ry- 80
Indoo
rD Indo 75
4.0 70
140 75
3.0
24 Hz
130
70 2.0

120 24 Hz
1.0

110 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


7.0
Data is based on the condition of outdoor humidity
75%.
Set air flow to High speed.
)
Outdoor unit current (A)

6.0
Inverter output frequency is 32 Hz. (˚F
re 75
er atu 70
temp
65
5.0 -b ulb
Dry
oor
Ind
4.0
32 Hz

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 91
8. 15-class unit in single operation
(OUTDOOR UNIT: NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 24 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 24 Hz (COOL) or 32 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(PSIG)
170 6.0
)
re (˚F
mperatu 86
5.0
160 ulb te (˚F) 86
r Dry-b era ture
Outdoor low pressure

Outdoor unit current (A)


80
Indoo temp
bulb 75
4.0 or Dry- 70
150 80 Indo

3.0 24 Hz

140 75
2.0

130 70 1.0
24 Hz
120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation 7.0


Data is based on the condition of outdoor humidity
75%
Set air flow to High speed.
Outdoor unit current (A)

6.0 ˚F)
Inverter output frequency is 32 Hz.
ur e(
pe rat 75
em 70
5.0 lb t 65
-bu
r Dry
Indoo
4.0
32 Hz

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 92
9. 18-class unit in single operation
(OUTDOOR UNIT: NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 24 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 24 Hz (COOL) or 32 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(PSIG)
170 6.0

F)
erature (˚ 86
160 ulb temp 5.0 (˚F) 86
Dry-b era ture
Outdoor low pressure

Indoo
r Outdoor unit current (A) temp
80
bulb 75
4.0 or Dry- 70
150 80 Indo

3.0 24 Hz

140 75
2.0

130 70 1.0
24 Hz
120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of outdoor humidity 7.0
75%.
Set air flow to High speed.
Outdoor unit current (A)

Inverter output frequency is 32 Hz. 6.0 ˚F)


ur e(
pe rat 75
em 70
5.0 bu lb t 65
D ry-
oor
Ind
4.0
32 Hz

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 93
10. 24-class unit in single operation
(OUTDOOR UNIT: NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 24 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 24 Hz (COOL) or 32 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.

(PSIG)
180 7.0
(˚F) 86
erature
lb temp
Dry-bu 6.0
170 Indoor
Outdoor unit current (A)
Outdoor low pressure

˚F)
80 5.0
tu re ( 86
160 m pera 80
lb te 75
y-bu
4.0 or Dr 70
Indo
150 75
3.0 24 Hz

140 70
2.0
24 Hz
130 1.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of outdoor humidity
75% 7.0
Set air flow to High speed.
Inverter output frequency is 32 Hz.
6.0
Outdoor unit current (A)

F)
5.0 ture (˚
m pera 75
lb te
Dry-bu 70
Indoor 65
4.0

32 Hz
3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 94
11. 06-class unit in single operation
(OUTDOOR UNIT: NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 18 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 18 Hz (COOL) or 20 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(PSIG)
86
170 6.0 80
re (˚F) 86
˚F) 75
mperatu ure( 70
lb te rat
ry-bu 5.0 pe
160 or D btem
Indo
Outdoor unit current (A)
bul
ry-
Outdoor low pressure

80 4.0 oorD
Ind
150
3.0 18 Hz
75
140
2.0
70
130
1.0
18 Hz

120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of outdoor humidity 7.0
75%.
Set air flow to High speed. ˚F) 75
re (
Outdoor unit current (A)

Inverter output frequency is 20 Hz. 6.0 atu 70


per 65
tem
-bulb
Dry
oor
5.0 Ind

20 Hz
4.0

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 95
12. 09-class unit in single operation
(OUTDOOR UNIT: NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 18 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 18 Hz (COOL) or 20 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(PSIG)
86
170 6.0 80
re (˚F) 86
˚F) 75
mperatu ure( 70
lb te rat
ry-bu 5.0 pe
160 or D btem
Indo
Outdoor unit current (A)
bul
ry-
Outdoor low pressure

80 4.0 oorD
Ind
150
3.0 18 Hz
75
140
2.0
70
130
1.0
18 Hz

120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of outdoor humidity 7.0
75%.
Set air flow to High speed. ˚F) 75
re (
Outdoor unit current (A)

Inverter output frequency is 20 Hz. 6.0 atu 70


per 65
tem
-bulb
Dry
oor
5.0 Ind

20 Hz
4.0

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 96
13. 12-class unit in single operation
(OUTDOOR UNIT: NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 18 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 18 Hz (COOL) or 20 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(PSIG)
86
170 6.0 80
˚F) 86
t ure ( (˚F
) 75
tempera ture 70
ry -bulb 5.0 p era
160 or D tem
Indo
Outdoor unit current (A)
lb
-bu
Outdoor low pressure

Dry
80 4.0 or
Indo
150
3.0 18 Hz
75
140
2.0
70
130
1.0
18 Hz

120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of outdoor humidity 7.0
75%.
Set air flow to High speed. ˚F) 75
re (
Outdoor unit current (A)

6.0 tu 70
Inverter output frequency is 20 Hz. pera 65
em
u lb t
Dry-b
oor
5.0 Ind

20 Hz
4.0

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 97
14. 15-class unit in single operation
(OUTDOOR UNIT: NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 18 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 18 Hz (COOL) or 20 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(PSIG)
180 6.0
re (˚F) 86 ) 86
peratu e (˚F 80
l b tem atur 75
170
rDry-bu 5.0 per
ndoo em 70
lb t
Outdoor unit current (A)
I
bu
ry-
Outdoor low pressure

80 D
160 4.0 oor
Ind

150 75 3.0 18 Hz

140 70 2.0

130 1.0
18 Hz

120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of outdoor humidity 7.0
75%.
Set air flow to High speed. ˚F)
re (
Outdoor unit current (A)

6.0 tu
Inverter output frequency is 20 Hz. pera
em
ulb t
ry-b 75
oorD 70
5.0 Ind
65
20 Hz
4.0

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 98
15. 18-class unit in single operation
(OUTDOOR UNIT: NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 18 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 18 Hz (COOL) or 20 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.
(PSIG)
180 6.0
e (˚F) 86 ) 86
eratur e (˚F 80
temp tur
170 -bulb 5.0 era 75
or Dry temp 70
Indo

Outdoor unit current (A)


-b ulb
Outdoor low pressure

80 Dry
160 4.0 or
Indo

150 75 3.0 18 Hz

140 70 2.0

130 1.0
18 Hz

120 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of outdoor humidity 7.0
75%.
Set air flow to High speed.
re (˚F)
Outdoor unit current (A)

Inverter output frequency is 20 Hz. 6.0


pe ratu
bt em
- bul 75
or Dry
5.0 Indo 70
65
20 Hz
4.0

3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 99
16. 24-class unit in single operation
(OUTDOOR UNIT: NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA)
(1) COOL operation
Data is based on the condition of indoor humidity <How to work fixed-frequency operation>
50% 1. Set emergency switch to COOL or HEAT. The switch is located
Air flow speed: High on indoor unit.
Inverter output frequency: 18 Hz 2. Press emergency run ON/OFF button.
3. Compressor starts running at 18 Hz (COOL) or 20 Hz (HEAT).
4. Indoor fan runs at High speed and continues for 30 minutes.
5. To cancel this operation, press emergency run ON/OFF button
or any button on remote controller.

(PSIG)
200 6.0
e (˚F) 86
ratur ˚F)
e 86 e( 80
emp rat
ur
190 -b ulb t 5.0 e 75
or Dry temp 70
Indo Outdoor unit current (A) ulb
-b
Outdoor low pressure

180 Dry
4.0 or
80
Indo
170
3.0 18 Hz
75
160

70 2.0
150

140 1.0
18 Hz

130 0.0
65 70 75 80 85 90 95 100 105 110 115 (˚F) 65 70 75 80 85 90 95 100 105 110 115 (˚F)

Ambient temperature (˚F) Ambient temperature (˚F)

(2) HEAT operation


Data is based on the condition of outdoor humidity 7.0
75%.
Set air flow to High speed.
re (˚F)
Outdoor unit current (A)

Inverter output frequency is 20 Hz. 6.0


pe ratu
bt em
- bul
or Dry
5.0 Indo

75
70
4.0 65

20 Hz
3.0

2.0
15 20 25 30 35 40 45 50 55 60 65 70 75 (˚F)
Ambient temperature (˚F)

OBHT702H 100
10 ACTUATOR CONTROL

NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA


NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
Relation between main sensor and actuator
Actuator
2-way solenoid
Defrost heater
valve
NTXMMX42A152AA NTXMPH20A122AA
NTXMMX42A152BA NTXMPH20A122BA
NTXMMX42A152CA NTXMPH20A122CA
NTXMPH20A122AA NTXMPH24A132AA
Sensor Purpose Outdoor
Compressor LEV 4-way valve NTXMPH20A122BA NTXMPH24A132BA
fan motor NTXMPH20A122CA NTXMPH24A132CA
NTXMPH24A132AA NTXMPH30A132AA
NTXMPH24A132BA NTXMPH30A132BA
NTXMPH24A132CA NTXMPH30A132CA
NTXMPH30A132AA
NTXMPH30A132BA
NTXMPH30A132CA
Discharge temperature
thermistor
Protection
○ ○ ○
Indoor coil temperature
Cooling: Coil frost
prevention ○ ○
○ ○
thermistor Heating: High pressure
protection
Defrost thermistor Heating: Defrosting
○ ○ ○ ○
Fin temperature
thermistor
Protection
○ ○
Ambient temperature
Control/Protection
○ ○ ○ ○
thermistor Heating: Defrosting
(Heater) ○
Outdoor heat
exchanger temperature
thermistor
Cooling: Control/
Protection ○ ○ ○ ○
Capacity code Control
○ ○

OBHT702H 101
11 SERVICE FUNCTIONS

NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA


NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
11-1. PRE-HEAT CONTROL
If moisture gets into the refrigerant cycle, or when refrigerant is liquefied and collected in the compressor, it may interfere
the startup of the compressor.
To improve start-up condition, the compressor is energized even while it is not operating.
This is to generate heat at the winding.
The compressor uses about 50 W when pre-heat control is turned ON.
Pre-heat control is ON at initial setting.
[How to deactivate pre-heat control]
Turn OFF the power supply for the air conditioner before making the setting.
Set the "4" of SW2 on the outdoor control P.C. board to ON to deactivate pre-heat control function.

Outdoor control P.C. board

LED

SW871
Turn ON the power supply for the air conditioner.

NOTE: Pre-heat control will be turned OFF when the breaker is turned OFF.

OBHT702H 102
11-2. AUTO LINE CORRECTING
Outdoor unit has an auto line correcting function which automatically detects and corrects improper wiring or piping.
Improper wiring or piping can be automatically detected by pressing the piping/wiring correction switch (SW871).
When improper wiring or piping is detected, wiring lines are corrected.
This will be completed in about 10 to 20 minutes.

[How to activate this function]

1. Check that outside temperature is above 32˚F.


(This function does not work when outside temperature is not above 32˚F.)
2. Check that the stop valves of the liquid pipe and gas pipe are open.
3. Check that the wiring between indoor and outdoor unit is correct.
(If the wiring is not correct, this function does not work.)
4. Turn ON the power supply and wait at least 1 minute.
5. Press the piping/wiring correction switch (SW871) on the outdoor control P.C. board.
Do not touch energized parts.
LED indication during detection:
LED1 (Red) LED2 (Yellow) LED3 (Green)
Lit Lit Once

LED indication after detection:


LED1 (Red) LED2 (Yellow) LED3 (Green) Indication
Lit Not lit Lit Completed (Problem corrected/ nomal)
Once Once Once Not completed (Detection failed)
Other indications Refer to "SAFETY PRECAUTIONS WHEN LED BLINKS"
located behind the service panel.
* Make sure that the valves are open and the pipes are not collapsed or clogged.
6. Press the switch to cancel.
LED indication after cancel :
LED1 (Red) LED2 (Yellow) LED3 (Green)
Lit Lit Not lit

NOTE : Indoor unit cannot be operated while this function is activated.


When this function is activated while indoor unit is operating, the operation will be stopped.
Operate indoor unit after the auto line correcting is finished.
Pressing the switch during detection cancels this function.
The record of auto line correcting can be confirmed in the following way:
Press the switch for more than 5 seconds.
LED will show the record of auto correcting for about 30 seconds as shown in the table below:
Number of blinks
Wiring line
LED1 (Red) LED2 (Yellow) LED3 (Green)
Once Once Lit Not corrected
3 times 3 times Lit Corrected

NOTE : Activate this function to confirm the correct wiring after replacing the outdoor control P.C. board.
(Previous records are deleted when the outdoor control P.C. board is replaced.)
The record cannot be shown if auto line correcting is not canceled (Refer to "How to activate this function").

OBHT702H 103
11-3. CHANGING THE SET REFRIGERANT EVAPORATING TEMPERATURE
NOTE: If you lower the refrigerant evaporating temperature with the windows open, it may cause dew drop.

[How to change the refrigerant evaporating temperature]


(1) Make sure there is no possibility of causing dew drop before making the setting.
(2) Make the setting referring to the table below.
SW2 on the outdoor control P.C. board
SW2

42.8 °F
(6 °C)

Normal control

OBHT702H 104
12 TROUBLESHOOTING

NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA


NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
12-1. CAUTIONS ON TROUBLESHOOTING
1. Before troubleshooting, check the following:
1) Check the power supply voltage.
2) Check the indoor/outdoor connecting wire for miswiring.
2. Take care of the following during servicing.
1) Before servicing the air conditioner, be sure to turn OFF the unit first with the remote controller, and then after confirm-
ing the horizontal vane is closed, turn OFF the breaker and/or disconnect the power plug.
2) Be sure to turn OFF the power supply before removing the front panel, the cabinet, the top panel, and the outdoor con-
trol P.C. board.
3) When removing the electrical parts, be careful of the residual voltage of smoothing capacitor.
4) When removing the electronic control P.C. board, hold the edge of the board with care NOT to apply stress on the
components.
5) When connecting or disconnecting the connectors, hold the connector housing. DO NOT pull the lead wires.
<Incorrect> <Correct>

Lead wiring Connector housing

3. Troubleshooting procedure
1) Check if the OPERATION INDICATOR lamp on the indoor unit is blinking on and off to indicate an abnormality. To make
sure, check how many times the OPERATIONAL INDICATOR lamp is blinking on and off before starting service work.
2) When the outdoor control P.C. board seems to be defective, check for disconnection of the copper foil pattern and burnt
or discolored components.
3) When troubleshooting, refer to 12-2, 12-3 and 12-4.
12-2. FAILURE MODE RECALL FUNCTION
This air conditioner can memorize the abnormal condition which has occurred once.
Even though LED indication listed on the troubleshooting check table (12-4) disappears, the memorized failure details can
be recalled.
1. Flow chart of failure mode recall function for the indoor/outdoor unit
Refer to the service manual of indoor unit.

OBHT702H 105
2. Flow chart of the detailed outdoor unit failure mode recall function

Operational procedure
The outdoor unit might be abnormal.
Check if outdoor unit is abnormal according to the following procedures.

Make sure that the remote controller is set to the failure mode recall function.
*3

With the remote controller headed towards the indoor unit, press the
TEMPERATURE buttons to adjust the set temperature to 77°F (25°C). *1

Does the OPERATION INDICATOR lamp on the


indoor unit blink at the interval of 0.5 seconds?
Blinks: The outdoor unit is abnormal. Beep is emitted
at the same timing as the blinking of the No
OPERATION INDICATOR lamp. *2 (OFF)

Yes
(Blinks)

The outdoor unit is abnormal. The outdoor unit is normal.


Check the blinking pattern, and identify the abnormal point by referring to the
table of outdoor unit failure mode recall function (12-2.3.).
Make sure to check at least 2 consecutive blinking cycles. *2

Release the failure mode recall function. *3

Release the failure mode recall function. *3

Repair the failure parts.

Delete the memorized abnormal condition. *3

Release the failure mode recall function. *3

NOTE: 1. Make sure to release the failure mode recall function after it is set up, otherwise the unit cannot operate properly.
2. If the abnormal condition is not deleted from the memory, the last abnormal condition is kept memorized.

*1. Regardless of normal or abnormal condition, 2 short beeps are emitted as the signal is received.
*2. Blinking pattern when outdoor unit is abnormal:

Blinking at 0.5- Blinking at 0.5-


2.5-second OFF 3-second ON second interval 2.5-second OFF 3-second ON second interval
ON
OFF
No beep Beeps No beep Beeps
Repeated cycle Repeated cycle Repeated cycle
*3. Refer to the service manual of indoor unit.

OBHT702H 106
NOTE: Blinking patterns of this mode differ from the ones of
3. Table of outdoor unit failure mode recall function TROUBLESHOOTING CHECK TABLE (12-4.).
The left lamp of LED indication Indoor/outdoor
OPERATION Abnormal point (Outdoor P.C. unit failure
board) Condition Remedy
INDICATOR lamp (Failure mode/protection) mode recall
(Indoor unit) LED 1 LED 2 function
OFF None (Normal) Lit Lit — — —
2-time blink Outdoor power system Lit Lit Overcurrent protection cut-out operates 3 con- • Check the connection of the com-
secutive times within 1 minute after the com- pressor connecting wire.
pressor gets started, or converter protection
cut-out or bus-bar voltage protection cut-out
• Refer to 12-6. "How to check
inverter/compressor". ○
operates 3 consecutive times within 3 minutes • Check the stop valve.
after startup.
3-time blink Discharge temperature thermistor Lit Once A thermistor shorts or opens during compressor • Refer to 12-6. "Check of
Defrost thermistor Lit Once running. outdoor thermistors".
Ambient temperature thermistor Lit Twice
Fin temperature thermistor
P.C. board temperature
Lit
Lit
3 times
4 times • Replace the outdoor control P.C.

thermistor board.
Outdoor heat exchanger Lit 9 times • Refer to 12-6. "Check of
temperature thermistor outdoor thermistors".
4-time blink Overcurrent Once Not lit 18 A (NTXMMX20A122AA/20A122AC/20A122BA/ • Reconnect compressor connector.
20A122CA)/21 A (NTXMMX24A/30A132AA, • Refer to 12-6. "How to check
NTXMMX24A/30A132BA, NTXMMX24A/30A132CA, NTX inverter/compressor".
MMX36A142AA/36A142BA/36A142CA)/28 A (NTXMMX • Check the stop valve.

42A152AA/42A152BA/42A152CA, NTXMPH20A122AA/
20A122BA/20A122CA, NTXMPH24A/30A132AA,
NTXMPH24A/30A132BA, NTXMPH24A/30A132CA)
current flows into power module.
5-time blink Discharge temperature Lit Lit The discharge temperature exceeds 239°F (NTXMMX20A • Check refrigerant circuit and
122AA/20A122AC/20A122BA/20A122CA)/222.8°F refrigerant amount.
(NTXMMX24A/30A132AA, NTXMMX24A/30A132BA, • Refer to 12-6. "Check of LEV".
NTXMMX24A/30A132CA, NTXMMX36A142AA/
36A142BA/36A142CA)/240.8°F (NTXMMX42A152AA/
42A152BA/42A152CA, NTXMPH20A122AA/20A122BA/
20A122CA, NTXMPH24A/30A132AA, NTXMPH24A/
30A132BA, NTXMPH24A/30A132CA) during operation.
Compressor can restart if discharge temperature thermis- —
tor reads 176°F (NTXMMX20A122AA/20A122AC/
20A122BA/20A122CA)/203°F (NTXMMX24A/30A132AA,
NTXMMX24A/30A132BA, NTXMMX24A/30A132CA, NTX
MMX36A142AA/36A142BA/36A142CA)/212°F (NTXMMX
42A152AA/42A152BA/42A152CA, NTXMPH20A122AA/
20A122BA/20A122CA, NTXMPH24A/30A132AA,
NTXMPH24A/30A132BA, NTXMPH24A/30A132CA) or
less 3 minutes later.
6-time blink High pressure Lit Lit The outdoor heat exchanger temperature • Check refrigerant circuit and
exceeds 158°F during cooling or the indoor gas refrigerant amount. —
pipe temperature exceeds 158°F during heating. • Check the stop valve.
7-time blink Fin temperature 3 times Not lit The fin temperature exceeds 190°F (NTXMMX20A122AA/
20A122AC/20A122BA/20A122CA, NTXMMX24A/
30A132AA, NTXMMX24A/30A132BA, NTXMMX24A/
30A132CA, NTXMMX36A142AA/36A142BA/36A142CA)/
192°F(NTXMMX42A152AA/42A152BA/42A152CA, NTX
MPH20A122AA/20A122BA/20A122CA, NTXMPH24A/
30A132AA, NTXMPH24A/30A132BA, NTXMPH24A/
30A132CA) during operation. • Check around outdoor unit.
• Check outdoor unit air passage.
P.C. board temperature 4 times Not lit The P.C. board temperature exceeds 152°F (NTXMM —
• Refer to 12-6. "Check of out-
X20A122AA/20A122AC/20A122BA/20A122CA, door fan motor".
NTXMMX24A/30A132AA, NTXMMX24A/30A132BA,
NTXMMX24A/30A132CA, NTXMMX36A142AA/36A
142BA/36A142CA)/189°F (NTXMMX42A152AA/42A
152BA/42A152CA, NTXMPH20A122AA/20A122BA/
20A122CA, NTXMPH24A/30A132AA,
NTXMPH24A/30A132BA, NTXMPH24A/30A132CA)
during operation.
8-time blink Outdoor fan motor Lit Lit A failure occurs 3 consecutive times within 30 • Refer to 12-6. "Check of out-

seconds after the fan gets started. door fan motor".
4-way valve switching
operation abnormality.
Lit 12 times Connector of R.V. coil is disconnected, poorly con-
nected or 4-way valve is faulty.
• Refer to 12-6. "Check of R.V. coil".
• Check the 4-way valve. ○
9-time blink Outdoor control system Lit 5 times Nonvolatile memory data cannot be read properly. • Replace the outdoor control P.C.
board. ○
10-time blink Low discharge temperature Lit Lit The frequency of the compressor is kept 80 Hz or • Check refrigerant circuit and
protection more and the discharge temperature is kept under refrigerant amount. —
102.2°F for more than 20 minutes. • Refer to 12-6. "Check of LEV".

OBHT702H 107
NOTE: Blinking patterns of this mode differ from the ones of
TROUBLESHOOTING CHECK TABLE (12-4.).
The left lamp of LED indication Indoor/outdoor
OPERATION Abnormal point (Outdoor P.C. unit failure
board) Condition Remedy
INDICATOR lamp (Failure mode/protection) mode recall
(Indoor unit) LED 1 LED 2 function
11-time blink Communication error between Lit 6 times Communication error occurs between the out-
P.C. boards door control P.C. board and outdoor power P.C. • Check the connecting wire —
board for more than 10 seconds. between outdoor control P.C.
board and outdoor power P.C.
The communication between boards protection
cut-out operates 2 consecutive times.
board. ○
Current sensor Lit 7 times A short or open circuit is detected in the current

sensor during compressor operating.

Current sensor protection cut-out operates 2
consecutive times. ○
Zero cross detecting circuit 5 times Not lit Zero cross signal cannot be detected while the • Check the connecting wire among

compressor is operating. outdoor control P.C. board and
The protection cut-out of the zero cross detect-
ing circuit operates 10 consecutive times.
outdoor power P.C. board.

Converter 5 times Not lit A failure is detected in the operation of the con- • Check the voltage of power supply.
verter during operation. • Replace the outdoor power P.C. board.
Bus-bar voltage 5 times Not lit The bus-bar voltage exceeds 400 V or falls to • Check the voltage of power supply. —
low level during compressor operating. • Replace the outdoor power P.C.
board or the outdoor control P.C.
board.
14-time blink 4-way valve switching
operation abnormality.
Lit 12 times Connector of R.V. coil is disconnected, poorly
connected or 4-way valve is faulty.
• Refer to 12-6. "Check of R.V. coil".
• Check the 4-way valve. ○
15-time blink LEV and drain pump Lit Lit The indoor unit detects an abnormality in the • Refer to 12-6. "Check of LEV".

LEV and drain pump. • Check the drain pump of the indoor unit.

OBHT702H 108
12-3. INSTRUCTION OF TROUBLESHOOTING
• Check the indoor unit with referring to the indoor unit service manual, and confirm that there is any problem in the indoor unit.
Then, check the outdoor unit with referring to this page.

Operation start

Check the outdoor unit


LED indicator. LED1 or LED2
Both LED1 and
has blinked.
Both LED1 and LED2 are lighting.
LED2 are OFF.

Refer to 12-6. Refer to 12-4.


"Check of power supply". "Troubleshooting check table".

• Indoor unit • COOL or • When cooling, heat • When cooling • When heating, • When cooling,
serial signal HEAT exchanger of dew drops in the room does not get room is not
error operation only non-operating indoor non-operating warm. cool.
Refer to 12-6. Refer to 12-6. unit frosts. indoor unit. Refer to 12-6. Refer to 12-6.
"How to "Check of •When heating, non- Check of "How to check "How to check
check R.V. coil". operating indoor unit miss-piping. inverter/compressor". inverter/
miswiring and gets warm. Check mis-piping, compressor".
serial signal Refer to 12-6. shortage of capacity.
error". "Check of LEV".

OBHT702H 109
12-4. TROUBLESHOOTING CHECK TABLE
Indication Abnormal point /
No. Symptom Condition Remedy
LED1(Red) LED2(Yellow) Condition
1 Outdoor The indoor unit detects an abnormality in the LEV and • Refer to 12-6. "Check of LEV".
Lit Once LEV and drain pump
unit does drain pump. • Check the drain pump of the indoor unit.
2 not operate. Overcurrent protection cut-out operates 3 consecutive • Check the connection of the compressor
times within 1 minute after the compressor gets started, or connecting wire.
Outdoor power
Lit Twice converter protection cut-out or bus-bar voltage protection • Refer to 12-6. "How to check inverter/
system
cut-out operates 3 consecutive times within 3 minutes after compressor".
startup. • Check the stop valve.
3 A short circuit is detected in the thermistor during opera-
Discharge temperature • Refer to 12-6. "Check of outdoor
Lit 3 times tion, or an open circuit is detected in the thermistor after 10
thermistor thermistors".
minutes of compressor startup.
4 Fin temperature • Refer to 12-6. "Check of outdoor
thermistor A short or open circuit is detected in the thermistor during thermistors".
Lit 4 times
P. C. board operation.
• Replace the outdoor control P.C. board.
temperature thermistor
5 Ambient temperature A short or open circuit is detected in the thermistor during
thermistor operation.
A short circuit is detected in the thermistor during opera-
Outdoor heat
tion, or an open circuit is detected in the thermistor after 5
exchanger temperature • Refer to 12-6. "Check of outdoor
Lit 5 times minutes (in cooling) and 10 minutes (in heating) of com-
thermistor thermistors".
pressor startup.
A short circuit is detected in the thermistor during opera-
Defrost thermistor tion, or an open circuit is detected in the thermistor after 5
minutes of compressor startup.
6 Zero cross detecting
Lit 6 times circuit (Outdoor control Zero cross signal cannot be detected. • Replace the outdoor control P.C. board.
P.C. board)
7 Lit 7 times Outdoor control system The nonvolatile memory data cannot be read properly. • Replace the outdoor control P.C. board.
8 Lit 8 times Current sensor Current sensor protection cut-out operates 2 consecutive times. • Replace the outdoor power P.C. board.
9 • Check the connecting wire between out-
Communication error The communication protection cut-out between boards
door control P.C. board and outdoor
between P.C. boards operates 2 consecutive times.
power P.C. board.
Lit 11 times
• Check the connecting wire between
M-NET communication M-NET adapter P.C. board detects an abnormality in the
M-NET adapter P.C. board and outdoor
error communication error.
control P.C. board, or terminal bed.
10 Zero cross detecting
The protection cut-out of the zero cross detecting circuit
Lit 12 times circuit (Outdoor power • Replace the outdoor power P.C. board.
operates 10 consecutive times.
P.C. board)
11 A short or open circuit is detected in the input current
Lit 13 times Current sensor • Replace the outdoor power P.C. board.
detection circuit during operation.
12 A short or open circuit is detected in the input voltage
Lit 14 times Voltage sensor • Replace the outdoor power P.C. board.
detection circuit during operation.
13 Lit 15 times Relay operation No relay operation is detected during operation. • Replace the outdoor power P.C. board.
14 Connector of R.V. coil is disconnected, poorly connected • Refer to 12-6. "Check of R.V. coil".
Lit 21 times 4-way valve
or 4-way valve is faulty. • Check the 4-way valve.
15 'Outdoor unit Overcurrent is detected after 30 seconds of compressor • Reconnect compressor connector.
IPM protection
stops and startup. • Refer to 12-6. "How to check inverter/
restarts Twice Not lit compressor".
3 minutes Overcurrent is detected within 30 seconds of compressor • Check the stop valve.
Lock protection
later' is startup. • Check the power module (PAM module).
16 repeated. The discharge temperature exceeds 239°F (NTXMMX20A
122AA/20A122AC/20A122BA/20A122CA)/222.8°F
(NTXMMX24A/30A132AA, NTXMMX24A/30A132BA,
NTXMMX24A/30A132CA, NTXMMX36A142AA/36A142BA/
36A142CA)/240.8°F (NTXMMX42A152AA/42A152BA/42A
152CA, NTXMPH20A122AA/20A122BA/20A122CA,
NTXMPH24A/30A132AA, NTXMPH24A/30A132BA,
NTXMPH24A/30A132CA) during operation. • Check the amount of gas and refrigerant
Discharge temperature
3 times Not lit Compressor can restart​if discharge temperature thermistor circuit.
protection
reads 176°F (NTXMMX20A122AA/20A122AC/20A122BA/ • Refer to 12-6. "Check of LEV".
20A122CA)/203°F (NTXMMX24A/30A132AA,
NTXMMX24A/30A132BA, NTXMMX24A/30A132CA, NTX
MMX36A142AA/36A142BA/36A142CA)/212°F (NTXMMX
42A152AA/42A152BA/42A152CA, NTXMPH20A122AA/
20A122BA/20A122CA, NTXMPH24A/30A132AA,
NTXMPH24A/30A132BA, NTXMPH24A/30A132CA) or less
3 minutes later.
17 Fin temperature •Check refrigerant circuit and refrigerant
The fin temperature exceeds during operation.
protection amount.
4 times Not lit
P.C. board temperature •Refer to 12-6. "Check of outdoor fan
The P.C. board temperature exceeds during operation. motor".
protection
18 High pressure is detected with the high pressure switch
(HPS) during operation. • Check around of gas and the refrigerant
High pressure
5 times Not lit The outdoor heat exchanger temperature exceeds 158°F circuit.
protection
during cooling or the indoor gas pipe temperature exceeds • Check the stop valve.
158°F during heating.

OBHT702H 110
Indication Abnormal point /
No. Symptom Condition Remedy
LED1(Red) LED2(Yellow) Condition
19 'Outdoor unit • Reconnect compressor connector.
stops and • Refer to 12-6. "How to check inverter/
6 times Not lit Pre-heating protection Overcurrent is detected during pre-heating.
restarts compressor".
3 minutes • Check the power module.
20 later' is A failure is detected in the operation of the converter
repeated. 8 times Not lit Converter protection • Replace the outdoor power P.C. board.
during operation.
21 • Check the voltage of power supply.
Bus-bar voltage The bus-bar voltage exceeds 400 V or falls to low level • Replace the outdoor power P.C. board or
9 times Not lit
protection during compressor operating. the outdoor control P.C. board.
• Refer to 12-6. "Check of bus-bar voltage".
22 Low out side
temperature The ambient became 10.4°F or less.
protection(cooling)
The ambient became 1.4°F or less.
(NTXMMX24/30A132AA, NTXMMX24/30A132BA,
11 times Not lit NTXMMX24/30A132CA, NTXMMX36A142AA/36A142BA/ —
Low out side 36A142CA, NTXMMX42A152AA/42A152BA/42A152CA)
temperature protection
(Heating) The ambient became -18°F or less.
(NTXMPH20A122AA/20A122BA/20A122CA,
NTXMPH24A/30A132AA, NTXMPH24A/30A132BA,
NTXMPH24A/30A132CA)
23 A failure occurs 3 consecutive times within 30 seconds • Refer to 12-6. "Check of outdoor fan
13 times Not lit Outdoor fan motor
after the fan gets started. motor".
24 4-way valve switching Connector of R.V. coil is disconnected, poorly connected or • Refer to 12-6. "Check of R.V. coil".
14 times Not lit
operation 4-way valve is faulty. • Check the 4-way valve.
25 Current sensor A short or open circuit is detected in the current sensor
Lit 8 times • Replace the outdoor power P.C. board.
protection during compressor operating.
26 Communication Communication error occurs between the outdoor control • Check the connecting wire between out-
Lit 11 times between P.C. boards P.C. board and outdoor power P.C. board for more than 10 door control P.C. board and outdoor
protection seconds. power P.C. board.
27 Zero cross detecting
circuit protection Zero cross signal cannot be detected while the compressor
Lit 12 times • Replace the outdoor power P.C. board.
(Outdoor power P.C. is operating.
board)
28 Outdoor unit The input current exceeds 15.0 A (NTXMMX20A122AA/
operates. 20A122AC/20A122BA/20A122CA)/18.4 A (NTXMMX24A/
30A132AA, NTXMMX24A/30A132BA, NTXMMX24A/
Primary current 30A132CA, NTXMMX36A142AA/36A142BA/36A142CA)/ These symptoms do not mean any abnor-
Once Lit mality of the product, but check the follow-
protection 26.8 A (NTXMMX42A152AA/42A152BA/42A152CA,
NTXMPH20A122AA/20A122BA/20A122CA, ing points.
NTXMPH24A/30A132AA, NTXMPH24A/30A132BA, • Check if indoor filters are clogged.
NTXMPH24A/30A132CA). • Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation
29 High pressure The indoor gas pipe temperature exceeds 113°F during
is short cycled.
protection heating.
Twice Lit
The indoor gas pipe temperature falls 37.4°F or below
Defrosting in cooling
during cooling.
30 • Check refrigerant circuit and refrigerant
The frequency of the compressor is kept 80 Hz or more amount.
Discharge temperature
3 times Lit and the discharge temperature is kept under 122°F(COOL • Refer to 12-6. "Check of LEV".
protection
mode)/104°F(HEAT mode) for more than 40 minutes. • Refer to 12-6. "Check of outdoor
thermistors".
31 The frequency of the compressor is kept 80 Hz or more • Refer to 12-6. "Check of LEV".
Low discharge
4 times Lit and the discharge temperature is kept under 102.2°F for • Check refrigerant circuit and refrigerant
temperature protection
more than 20 minutes. amount.
32 This symptom does not mean any abnor-
mality of the product, but check the follow-
ing points.
Cooling high pressure The outdoor heat exchanger temperature exceeds 136.4°F
5 times Lit • Check if indoor filters are clogged.
protection during operation.
• Check if refrigerant is short.
• Check if indoor/outdoor unit air circulation
is short cycled.
33 During cooling operation, the temperature of indoor heat This symptom does not mean any abnor-
exchanger becomes 37.4°F or less within 1 hour after the mality of the product, but check the follow-
High → Low
compressor starts running, or it becomes less than ing points.
Pressure bypass
53.6°F - 60.8°F* later than that. • Check the indoor filters are not clogged.
valve
7 times Lit * It depends on the difference between the set temperature • Check there is sufficient refrigerant.
Cooling evaporating
and the room temperature. • Check the indoor/outdoor unit air circula-
temperature drop
(NTXMMX42A152AA/42A152BA/42A152CA, NTXMPH20A tion is not short cycled.
prevention control
122AA/20A122BA/20A122CA, NTXMPH24A/30A132AA,
NTXMPH24A/30A132BA, NTXMPH24A/30A132CA)
34 • Check the connecting wire between
M-NET communication M-NET adapter P.C. board detects an abnormality in the
11 times Lit M-NET adapter P.C. board and outdoor
error communication error.
control P.C. board, or terminal block.

OBHT702H 111
Indication Abnormal point /
No. Symptom Condition Remedy
LED1(Red) LED2(Yellow) Condition
35 Outdoor High → Low The room temperature is 75.2°F or more when 1 or 2 This symptom does not mean any abnor-
unit pressure bypass valve unit(s) start(s) the heating operation. mality of the product.
operates High pressure (NTXMMX42A152AA/42A152BA/42A152CA, NTXMPH20
normally. protection control at A122AA/20A122BA/20A122CA, NTXMPH24A/
startup of heating 30A132AA, NTXMPH24A/30A132BA, NTXMPH24A/
operation 30A132CA)
Both the following are true:
7 times Lit • The outside temperature is 28.4°F or less when the heat-
High → Low
ing operation is started.
pressure bypass valve
• [(Discharge temperature) - (Indoor heat exchanger tem-
Compressor oil
perature)] < 9°F
tempering control at
(NTXMMX42A152AA/42A152BA/42A152CA,
startup of heating
NTXMPH20A122AA/20A122BA/20A122CA,
operation
NTXMPH24A/30A132AA, NTXMPH24A/30A132BA,
NTXMPH24A/30A132CA)
36 During cooling operation, the temperature of indoor heat
exchanger becomes 44.6°F - 51.8°F* or less within 1 hour
Cooling evaporating
after the compressor starts running, or it becomes 48.2°F -
8 times Lit temperature
62.6°F* or less later than that.
protection
* It depends on the indoor unit type/model or the difference
between the set temperature and the room temperature.
37 9 times Lit Inverter check mode The unit is operated with emergency operation switch. —
38 Lit Lit Normal — —

NOTE: 1. The location of LED is illustrated at the right figure. Refer to 12-7.1.
2. LED is lit during normal operation.
The blinking frequency shows the number of times the LED blinks after every 2.5-second OFF.
(Example) When the blinking frequency is “2”.
0.5-second ON 0.5-second ON Outdoor control P.C. board
(Parts side)
ON LED1 LED2
2.5-second OFF 2.5-second OFF Lit
OFF 

OBHT702H 112
12-5. TROUBLESHOOTING CRITERION OF MAIN PARTS
NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA
NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
Part name Check method and criterion
Defrost thermistor (RT61) Measure the resistance with a multimeter.
Fin temperature thermistor (RT64)
Ambient temperature thermistor Refer to 12-7. “Test point diagram and voltage”, 1. “Outdoor control P.C.board”,
(RT65) 2. “Outdoor power P.C. board”, for the chart of thermistor.
Outdoor heat exchanger
temperature thermistor (RT68)
Discharge temperature Measure the resistance with a multimeter.
thermistor (RT62) Before measurement, hold the thermistor with your hands to warm it up.
Refer to 12-7. “Test point diagram and voltage”, 1. “Outdoor control P.C. board” for the chart of thermistor.
Compressor Measure the resistance between terminals using a multimeter.
W (Winding temperature: 14°F - 104°F)
RED
Normal (Each phase)
NTXMMX20A122AA NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
V U NTXMMX20A122AC NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
WHT BLK
NTXMMX20A122BA NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
NTXMMX20A122CA
0.63 kΩ - 0.78 kΩ 0.83 Ω - 1.03 Ω
Measure the resistance between terminals using a multimeter.
(Winding temperature: 14°F - 104°F)
Normal (Each phase)
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
0.63 kΩ - 0.78 kΩ
Outdoor fan motor • Refer to 12-6.
R.V. coil Measure the resistance using a multimeter. (Part temperature: 14°F - 104°F)
Normal (Each phase)
NTXMMX20A122AA NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX20A122AC NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX20A122BA NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
NTXMMX20A122CA
1.26 kΩ - 1.62 kΩ 1.20 kΩ - 1.77 kΩ
Measure the resistance using a multimeter. (Part temperature: 14°F - 104°F)
Normal (Each phase)
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
1.24 kΩ - 1.86 kΩ
2-way valve solenoid coil Measure the resistance using a multimeter. (Part temperature: 14°F - 104°F)
Normal (Each phase)
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
0.97 kΩ - 1.37 kΩ

OBHT702H 113
Part name Check method and criterion
Linear expansion valve Measure the resistance using a multimeter. (Part temperature: 14°F - 104°F)
WHT Color of lead wire Normal
RED LEV WHT - RED
ORN RED - ORN
37.4 Ω - 53.9 Ω
YLW - RED
YLW BLU RED - BLU
High pressure switch(HPS) Pressure Normal
537 ± 22 PSIG Close
HPS
696 +-157 PSIG Open
Defrost heater Measure the resistance using a multimeter. (Part temperature: 14°F - 104°F)
Normal
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
0.35 kΩ - 0.50 kΩ

OBHT702H 114
12-6. TROUBLESHOOTING FLOW
• Outdoor unit does not operate.

Check of power supply

Check the main power supply circuit for proper connections.

Turn ON the power supply.

Is there voltage of 208/230 V AC in the


Check the power supply cable.
power supply terminal block? No
Yes
Is the output voltage from the outdoor
Replace the outdoor control P.C. board.
power P.C. board 294/325 V DC? Yes
No
Turn OFF the power supply and recconnect the reactor.

Is the resistance of reactor normal? *1 Replace the reactor.


No
Yes
Replace the outdoor power P.C. board.

*1 NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA


NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
Measuring points Resistance
pin 1 – pin 2 1 Ω or less
pin 3 – pin 4 1 Ω or less
NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
Measuring points Resistance
– 1 Ω or less

OBHT702H 115
• When unit cannot operate neither by the remote controller nor by EMERGENCY OPERATION switch.
Indoor unit does not operate.
• When OPERATION INDICATOR lamp blinks ON and OFF in every 0.5-second.
Outdoor unit does not operate.

How to check miswiring and serial signal error (when outdoor unit does not work)

LED indication Turn OFF the power supply.


for communication status
Communication status is indicated
by the LED. Is there rated voltage in Check the power
the power supply? No supply.
Unit status
Blinking: normal communication
Lit: abnormal communication or Yes
not connected Turn ON the power supply.
Pattern 1 and 2 is repeatedly displayed
alternately. Each pattern is displayed for
15 seconds. Is there rated voltage between
NOTE: "Lit" in the table below does not outdoor terminal block S1 and Check the wiring.
S2? No
indicate abnormal communication.
Yes
Outdoor control P.C. board Press EMERGENCY OPERATION switch once.
LED1 LED2 LED3

Does the left lamp of OPERATION


Blinking INDICATOR lamp light up?
<Confirmation of the power to the indoor unit> No
Pattern LED 1 LED 2 LED 3 Yes
Unit A Unit B Is there any miswiring,
1 Lit
status status poor contact, or wire
Unit C Unit D Not lit Is serial signal error indicated 6 minutes later? disconnection of the Correct them.
2 status status No Yes
indoor/outdoor
Unit E connecting wire?
3 status Blinking Yes

No

Turn OFF the power supply.


Check once more if the indoor/outdoor
B connecting wire is not miswiring.
Bridge the outdoor terminal block S2 and *1 Miswiring may damage indoor electronic control
S3. P.C. board during the operation.
*1 Be sure to confirm the wiring is correct before the
operation starts.

Turn ON the power supply.

Does the LED on the outdoor control P.C.


board repeat "3.6-second-OFF Replace the outdoor control P.C. board.
and 0.8-second-ON quick blinking"? No *2
(Lit
Yes or not lit) *2 Be careful of the residual
voltage of smoothing capacitor.
Turn OFF the power supply.
Remove the bridge between
outdoor terminal block S2 and S3.
Turn ON the power supply.
Is there amplitude of 10 to 20 V DC No
between outdoor terminal block S2
A and S3? <Confirmation of serial
signal>
· Turn OFF inverter-controlled lighting
equipment. Yes
· Turn OFF the power supply and
then turn ON again.
· Press EMERGENCY OPERATION Is there any error of the
switch. Is there rated voltage between indoor/outdoor connecting wire, Replace the
· Reinstall indoor terminal block S1 and S2? such as the damage of the wire, indoor/outdoor
<Confirmation of power voltage> No intermediate connection, poor Yes
either the connecting wire.
unit or the contact to the terminal block?
Yes
light away
Is serial signal from each No
error indicated other.
6 minutes later? No · Attach a filter
on remote
control Replace the indoor electronic control P.C. board.
Yes receiving
section of Be sure to release the failure-mode
the indoor recall function after checking.
B unit.
Refer to indoor unit service manual.

OBHT702H 116
The cooling operation or heating operation does not operate.

Check of R.V. coil

• When cooling operation does not work, CNAC Outdoor control


CN712 P.C. board
1. Disconnect the lead wire leading to the compressor.
Outdoor power
2. 3 minutes after turning ON the power supply, start EMERGENCY CNAC2
P.C. board
OPERATION in COOL mode.

Is there voltage 208/230 V AC


Is there voltage of 208/230 V AC between pin1 Replace the outdoor
between the pin1 and pin3 at
and pin2 at connector CN712? No No power P.C. board.
connector CNAC?
Yes
Yes
Turn OFF the power supply.
Replace the outdoor
Disconnect the connector CNAC2.
control P.C. board.

Is there normal resistance


Replace the R.V. coil.
to R.V. coil? (Refer to 12-5.) No
Yes
Replace the 4-way valve.

• When heating operation does not work,


1. Disconnect the lead wire leading to the compressor.
2. 3 minutes after turning ON the power supply, start EMERGENCY
OPERATION in HEAT mode.

Is there voltage of 208/230 V AC between pin1


Replace the 4-way valve.
and pin2 at connector CN712? No
Yes

Replace the outdoor control P.C. board.

OBHT702H 117
• When cooling, heat exchanger of non-operating indoor unit frosts.
• When heating, non-operating indoor unit gets warm.

Check of LEV

Turn ON the power supply to the outdoor unit after checking LEV coil is CN791
mounted to the LEV body securely. CN792 Outdoor
CN793 control
CN794 P.C. board
Is "click - click" sound heard? CN795
Normal CN797
Or, do you feel vibration of LEV coil with your hand? Yes
No
Disconnect the connectors.
NTXMMX20A122AA/20A122AC/20A122BA/20A122CA
NTXMPH20A122AA/20A122BA/20A122CA
CN791: LEV A, CN792: LEV B,
CN797: LEV R
OTHER MODELS
CN791: LEV A, CN792: LEV B, CN793: LEV C Replace the outdoor control P.C. board.
Yes
CN794: LEV D (NTXMMX36A142AA/36A142BA/36A142CA,
NTXMMX42A152AA/42A152BA/42A152CA)
CN795: LEV E (NTXMMX42A152AA/42A152BA/42A152CA)
Is there normal resistance to LEV coil?
(Refer to 12-5.)
No
Replace LEV coil.

OBHT702H 118
• When heating, room does not get warm.
• When cooling, room does not get cool.

How to check inverter/compressor

Disconnect the terminal of the compressor or the connector (CNMC) between the compressor
and the outdoor power P.C. board. 3 minutes after the power supply is turned ON,
start EMERGENCY OPERATION.

*1 • After the outdoor fan starts running, wait for 1 minute


or more before measuring the voltage.
Measure the voltage between each
• The output voltage values have the tolerance of ± 20%.
lead wire leading to the compressor.
*2 • The output differs depending on the capacity or the
U (BLK) - V (WHT)
number of indoor units to be operated.
V (WHT) - W (RED)
W (RED) - U (BLK) No
Output voltage: 50V-250V
Is proper output voltage detected?
*1, *2
Yes
Is output balanced?
No
Yes

Is the input voltage to the outdoor control


Replace the outdoor power P.C. board.
P.C. board 370 V DC or more? No

Yes
Turn OFF the power supply of indoor and
outdoor unit, and measure the compressor
winding resistance between the compressor Replace the compressor.
terminals. No
Is the resistance between each terminal normal?
(Refer to 12-5.)
Yes

Reconnect the lead wire of compressor, and turn ON


the power supply to indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.

Clarify the causes by counting time until the inverter stops.


0 to 10 seconds: compressor layer short
10 to 60 seconds: compressor lock
60 seconds to 5minutes: refrigerant circuit defective
5 minutes or more: normal

OBHT702H 119
• When thermistor is abnormal,

Check of outdoor thermistors


(NTXMMX24A132AA/24A132BA/24A132CA,
NTXMMX30A132AA/30A132BA/30A132CA,
Disconnect the connector in the following table and Abnormal NTXMMX36A142AA/36A142BA/36A142CA)
measure the resistance of the thermistor to check Replace the thermistor.
whether the thermistor is normal or not. (Refer to 12-7.) (NTXMMX20A122AA/20A122AC/20A122BA/20A122CA,
Normal NTXMMX42A152AA/42A152BA/42A152CA,
NTXMPH20A122AA/20A122BA/20A122CA,
NTXMPH24A132AA/24A132BA/24A132CA,
NTXMPH30A132AA/30A132BA/30A132CA)
Reconnect the connector in the following table and
disconnect the lead wire leading to the compressor. Replace the thermistor except RT64.
3 minutes after turning ON the power supply, If RT64 is abnormal, replace the outdoor power
start EMERGENCY OPERATION. P.C. board since RT64 is combined with this board.

Does the unit operate 10 minutes or more without Replace the outdoor control P.C. board or the
showing thermistor abnormality? No outdoor power P.C. board.
Yes
Normal

Thermistor Symbol Connector, Pin No. Board


Defrost RT61 Between CNTH1 pin1 and pin2
Discharge temperature RT62 Between CNTH1 pin3 and pin4
Outdoor control P.C. board
Outdoor heat exchanger temperature RT68 Between CNTH1 pin7 and pin8
Ambient temperature RT65 Between CNTH2 pin1 and pin2
Fin temperature RT64 Between CN171 pin1 and pin2 Outdoor power P.C. board

OBHT702H 120
• Fan motor does not operate or stops operating shortly after starting the operation.

Check of outdoor fan motor

Disconnect CNF1 and measure the CNF1 Outdoor control


resistance of the outdoor fan motor. P.C. board

Is the resistance of outdoor fan motor Model name of fan motor*:


Replace the outdoor fan motor. SIC-71XX-XXXX-X, SIC-81XX-XXXX-X
normal? (Refer to right table) No
Measuring points Resistance
Yes
pin1 - pin4
Does the outdoor fan motor rotate smoothly? Replace the outdoor fan motor.
No pin5 - pin4 60 kΩ
Yes
CNF1 Voltage pin6 - pin4 160 kΩ
Turn on the power supply to start operation pin7 - pin4
and measure the voltage of connector CNF1. pin1 - pin4 294/325 V DC
pin5 - pin4 15 V DC Model name of fan motor*:
SIC-82XX-XXXX-X, SIC-88XX-XXXX-X
pin6 - pin4 1 - 5 V DC
Measuring points Resistance
* To measure the voltage, connect the negative (-) pin1 - pin4 1.1 MΩ
end of the multimeter to pin4.
* Voltage between pin4 and 6 should be measured pin5 - pin4 40 kΩ
within 1 minute after the operation starts. pin6 - pin4 220 kΩ
Is the voltage of connector CNF1 pin7 - pin4
Replace the outdoor control P.C. board.
normal? (Refer to right table.) No
* To measure the resistance, connect
Yes the negative (-) end of the multimeter
to pin4.
Turn OFF the power supply and connect
* See the spec name plate indicated in
the connector CNF1. the diagram for the model name of fan
Turn ON the power supply and measure motor.
the voltage of connector CNF1 while * Where "X" in model name of fan motor
rotating the motor by the hand. represents numbers and letters

Spec name plate


Does the voltage between pin7 and pin4 of fan motor
Replace the outdoor fan motor.
of connector CNF1 repeat 0V and 5V? No
Yes
Start operation.

Does the fan motor operate for about


Replace the outdoor fan motor.
5 seconds? No
Yes

Replace the outdoor control P.C. board.

OBHT702H 121
• When the operation frequency does not go up from the lowest frequency.

Check of HPS Outdoor control


CN63H
P.C. board

1. Disconnect the connector CN63H in the outdoor control P.C. board.


2. Check the resistance of HPS after 1 minute has passed since the outdoor unit power supply was turned OFF.

Check the resistance between each terminal. Replace HPS.


Infinity
0Ω
Reconnect CN63H.
Turn ON the power supply to the indoor and outdoor unit.
3 minutes later, start EMERGENCY OPERATION.

Is HPS protection displayed immediately Replace the outdoor control P.C. board.
after compressor starts? Yes
No
Normal

The other cases


Indoor unit does not operate. (different operating models in multi system)
• When you try to run 2 indoor units simultaneously, one for cooling and the other for heating, the unit which transmits signal to
the outdoor units first decides the operation mode.
• When the above situation occurs, set all the indoor units to the same mode, turn OFF the indoor units, and then turn them back
ON.
• Though the top of the indoor unit sometimes gets warm, this does not mean malfunction. The reason is that the refrigerant gas
continuously flows into the indoor unit even while it is not operating.

Check of bus-bar voltage

•Check the voltage of power supply.


•Confirm outdoor unit failure mode
recall function. (Refer to 12-2.2.)

Confirm LED1 indication lamp on the


outdoor control P.C. board.

Blink 5 times Lighting

Replace the outdoor power Replace the outdoor control


P.C. board. * P.C. board. *

Turn ON power supply. Start Turn ON power supply. Start


operation. operation.

Confirm LED1 indication lamp Confirm LED1 indication lamp


on the outdoor control P.C. Normal on the outdoor control P.C.
board. Lighting Lighting board.
Blink 9 times Blink 9 times

Replace the outdoor control Replace the outdoor power


P.C. board. * P.C. board. *
* Turn OFF power supply before removing P.C. board.

OBHT702H 122
12-7. TEST POINT DIAGRAM AND VOLTAGE 700
Discharge temperature thermistor (RT62) Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
1. Outdoor control P.C. board 600 Outdoor heat exchanger temperature
NTXMMX20A122AA thermistor (RT68)

Resistance (kΩ)
500 100

NTXMMX20A122AC 400 90

NTXMMX20A122BA 300 80

Resistance (kΩ)
200 70

100 60

0 50
0 10 20 30 40 50 60 70 80 90 100 110 120 (ºC)
32 50 68 86 104 122 140 158 176 194 212 230 248 (ºF)
40
Temperature
Thermistor R100 = 13.36 kΩ ± 2% , B constant = 4014 ± 2% 30
1 1
Rt = 13.36exp{4014( 273+t 373 )} , t: ºC = (ºF - 32)/1.8
20
Serial signal 12 ~ 24 V
10
CN741
208/230 V AC Room A Room B
Signal translation 0
-20 -10 0 10 20 30 40 (ºC)
(To Communication Input -4 14 32 50 68 86 104 (ºF)
adaptor board) CN601 Temperature
Thermistor R25 = 10 kΩ ± 2%
CN611 CN621 B constant = 3950 ± 2%
Rt = 10exp{3950( 1 1 )}
273+t 298
VFG (Rotate signal) t : ºC = (ºF - 32)/1.8
(Voltage between
right pins of PC931,
pin 3 and pin 4)
(Same as
(CNF1 (+)- (−))

VSP (Rotate instruction)


(Voltage between pins
of C930): 0 V DC
(when stopped),
1.8 - 6.5 V DC
(when operated)
(Correspond to
(CNF1 (+)- (−)) F711 FUSE
T3.15AL250V
CNF1
To fan motor CNAC
Bus-bar voltage to outdoor power P.C.
290 ~ 370 V DC board 208/230 V AC
Input
15 V DC
CN714 Base heater
208/230 V AC
Output

CNDC CN713 Valve coil


Bus-bar 208/230 V AC
voltage Output
290 ~ 370
V DC CN712 R.V. coil
208/230 V AC
Output
CNTH2
Ambient temperature
thermistor
(RT65)
CNTH1
Outdoor heat exchanger
temperature thermistor
(RT68)
Discharge temperature
thermistor (RT62)
Defrost thermistor
CN63H (RT61)
High
pressure SW1
switch
SW871

SW2

LED3
(+)
(-)
(+)
15 V
(-)
5 V DC pulse wave15(-)
V
15 V

LED2
CN792 LEV Room B
CN791 LEV Room A

LED1
5 V DC pulse wave
(To power board)
(To power board)

CN797 LEV R
CN701 Signal
CN702 Signal

transmission
transmission

LEV: 12 V DC
pulse wave

OBHT702H 123
1. Outdoor control P.C. board 700
Discharge temperature thermistor (RT62) Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
NTXMMX20A122CA 600 Outdoor heat exchanger temperature
thermistor (RT68)

Resistance (kΩ)
500 100
400 90

300 80

Resistance (kΩ)
200 70

100 60

0 50
0 10 20 30 40 50 60 70 80 90 100 110 120 (ºC)
32 50 68 86 104 122 140 158 176 194 212 230 248 (ºF)
40
Temperature
Thermistor R100 = 13.36 kΩ ± 2% , B constant = 4014 ± 2% 30
1 1
Rt = 13.36exp{4014( 273+t 373 )} , t: ºC = (ºF - 32)/1.8
20
Serial signal 12 ~ 24 V
10

CN741 208/230 V AC Room B


Room A 0
-20 -10 0 10 20 30 40 (ºC)
Signal translation -4 14 32 50 68 86 104 (ºF)
Input
(To Communication Temperature
adaptor board) CN601 Thermistor R25 = 10 kΩ ± 2%
CN621 B constant = 3950 ± 2%
CN611 Rt = 10exp{3950( 1 1 )}
273+t 298
t : ºC = (ºF - 32)/1.8
VFG (Rotate signal)
(Voltage between
right pins of PC931,
pin 3 and pin 4)
(Correspond to
(CNF1 (+)- (−))

VSP (Rotate instruction)


(Voltage between pins
of C930): 0 V DC
(when stopped),
1.8 - 6.5 V DC
(when operated)
(Same as
(CNF1 (+)- (−)) F711 FUSE
CNF1 T3.15AL250V
To fan motor CNAC
Bus-bar voltage to outdoor power P.C. board
290 - 370 V DC 208/230 V AC
15 V DC Input
Rotate instruction CN714 Defrost heater
(Constant voltage) 208/230 V AC
Rotate signal Output
(Pulse wave)
CNDC
Bus-bar
voltage
290 - 370
CN712 R.V. coil
V DC
208/230 V AC
Output
CNTH2
Ambient temperature
thermistor
(RT65)
CNTH1
Outdoor heat exchanger
temperature thermistor
(RT68)
Discharge temperature
thermistor (RT62)
CN63H Defrost thermistor (RT61)
High
pressure SW1
switch
SW871

SW2

CN702 (+) CN791 LED3


Signal transmission LEV Room A LED2
(To power board) 15 V CN792 LED1
5 V DC pulse wave (-) LEV Room B
(-) CN797
15 V LEV R
15 V
(

CN701 LEV: 12 V DC
Signal transmission (-) pulse wave
(To power board) (+)
5 V DC pulse wave

OBHT702H 124
1. Outdoor control P.C. board 700
Discharge temperature thermistor (RT62) Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
NTXMMX24A132AA 600 Outdoor heat exchanger temperature
thermistor (RT68)
NTXMMX24A132BA

Resistance (kΩ)
500 100

NTXMMX30A132AA
400 90

300
NTXMMX30A132BA
80

Resistance (kΩ)
200 70

NTXMMX36A142AA 100 60

NTXMMX36A142BA 0
0
32
10
50
20
68
30
86
40 50 60 70 80 90 100 110 120 (ºC)
104 122 140 158 176 194 212 230 248 (ºF)
50

40
Temperature
Thermistor R100 = 13.36 kΩ ± 2% , B constant = 4014 ± 2% 30
1 1
Rt = 13.36exp{4014( 273+t 373 )} , t: ºC = (ºF - 32)/1.8
20
Serial signal 12 ~ 24 V
10
CN741
208/230 V AC Room A Room B Room C Room D
Signal translation Input 0
-20 -10 0 10 20 30 40 (ºC)
(To Communication -4 14 32 50 68 86 104 (ºF)
adaptor board) CN601 Temperature
Thermistor R25 = 10 kΩ ± 2%
CN611 CN621 B constant = 3950 ± 2%
Rt = 10exp{3950( 1 1 )}
273+t 298
VFG (Rotate signal) t : ºC = (ºF - 32)/1.8
(Voltage between
right pins of PC931,
pin 3 and pin 4)
(Same as
(CNF1 (+)- (−))

VSP (Rotate instruction)


(Voltage between pins
of C930): 0 V DC
(when stopped),
1.8 - 6.5 V DC
(when operated)
(Correspond to
(CNF1 (+)- (−)) F711 FUSE
T3.15AL250V
CNF1
To fan motor CNAC
Bus-bar voltage to outdoor power P.C.
290 ~ 370 V DC board 208/230 V AC
Input
15 V DC
CN714 Base heater
208/230 V AC
Output

CNDC
Bus-bar
voltage
290 ~ 370
V DC CN712 R.V. coil
208/230 V AC
Output
CNTH2
Ambient temperature
thermistor
(RT65)
CNTH1
Outdoor heat exchanger
temperature thermistor
(RT68)
Discharge temperature
thermistor (RT62)
Defrost thermistor
CN63H (RT61)
High
pressure SW1
switch
SW871

SW2

LED3
(+)
(-)
(+)
15 V
(-)
5 V DC pulse wave15(-)
V
15 V

LED2
CN794 LEV Room D
CN793 LEV Room C
CN792 LEV Room B
CN791 LEV Room A

LED1
5 V DC pulse wave
(To power board)
(To power board)

CN701 Signal
CN702 Signal

transmission
transmission

LEV: 12 V DC
pulse wave

OBHT702H 125
1. Outdoor control P.C. board 700
Discharge temperature thermistor (RT62) Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
NTXMMX24A132CA 600 Outdoor heat exchanger temperature
thermistor (RT68)
NTXMMX30A132CA

Resistance (kΩ)
500 100

NTXMMX36A142CA
400 90

300 80

Resistance (kΩ)
200 70

100 60

0 50
0 10 20 30 40 50 60 70 80 90 100 110 120 (ºC)
32 50 68 86 104 122 140 158 176 194 212 230 248 (ºF)
40
Temperature
Thermistor R100 = 13.36 kΩ ± 2% , B constant = 4014 ± 2% 30
1 1
Rt = 13.36exp{4014( 273+t 373 )} , t: ºC = (ºF - 32)/1.8
20
Serial signal 12 ~ 24 V
CN741 10
208/230 V AC Room A Room B Room C Room D
Signal translation Input 0
-20 -10 0 10 20 30 40 (ºC)
(To Communication
-4 14 32 50 68 86 104 (ºF)
adaptor board) CN601 Temperature
Thermistor R25 = 10 kΩ ± 2%
CN611 CN621 B constant = 3950 ± 2%
Rt = 10exp{3950( 1 1 )}
273+t 298
VFG (Rotate signal) t : ºC = (ºF - 32)/1.8
(Voltage between
right pins of PC931,
pin 3 and pin 4)
(Same as
(CNF1 (+)- (−))

VSP (Rotate instruction)


(Voltage between pins
of C930): 0 V DC
(when stopped),
1.8 - 6.5 V DC
(when operated)
(Correspond to
(CNF1 (+)- (−)) F711 FUSE
T3.15AL250V
CNF1
To fan motor CNAC
Bus-bar voltage to outdoor power P.C.
290 ~ 370 V DC board 208/230 V AC
Input
15 V DC
CN714 Base heater
208/230 V AC
Output

CNDC
Bus-bar
voltage
290 ~ 370
V DC CN712 R.V. coil
208/230 V AC
Output
CNTH2
Ambient temperature
thermistor
(RT65)
CNTH1
Outdoor heat exchanger
temperature thermistor
(RT68)
Discharge temperature
thermistor (RT62)
Defrost thermistor
CN63H (RT61)
High
pressure SW1
switch
SW871

SW2

LED3
(+)
(-)
(+)
15 V
(-)
5 V DC pulse wave15(-)
V
15 V

LED2
CN794 LEV Room D
CN793 LEV Room C
CN792 LEV Room B
CN791 LEV Room A

LED1
5 V DC pulse wave
(To power board)
(To power board)

CN701 Signal
CN702 Signal

transmission
transmission

LEV: 12 V DC
pulse wave

OBHT702H 126
1. Outdoor control P.C. board 700
Discharge temperature thermistor (RT62) Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
NTXMMX42A152AA 600 Outdoor heat exchanger temperature
thermistor (RT68)
NTXMMX42A152BA

Resistance (kΩ)
500 100

NTXMPH20A122AA
400 90

300
NTXMPH20A122BA
80

Resistance (kΩ)
200 70

NTXMPH24A132AA 100 60

NTXMPH24A132BA 0
0
32
10
50
20
68
30
86
40 50 60 70 80 90 100 110 120 (ºC)
104 122 140 158 176 194 212 230 248 (ºF)
50

NTXMPH30A132AA Temperature
Thermistor R100 = 13.36 kΩ ± 2% , B constant = 4014 ± 2%
40

NTXMPH30A132BA
30
1 1
Rt = 13.36exp{4014( 273+t 373 )} , t: ºC = (ºF - 32)/1.8
20
Serial signal 12 ~ 24 V
10
CN741
208/230 V AC Room A Room B Room C Room D Room E
Signal translation Input 0
-20 -10 0 10 20 30 40 (ºC)
(To Communication -4 14 32 50 68 86 104 (ºF)
adaptor board) CN601 Temperature
Thermistor R25 = 10 kΩ ± 2%
CN611 CN621 B constant = 3950 ± 2%
Rt = 10exp{3950( 1 1 )}
273+t 298
VFG (Rotate signal) t : ºC = (ºF - 32)/1.8
(Voltage between
right pins of PC931,
pin 3 and pin 4)
(Same as
(CNF1 (+)- (−))

VSP (Rotate instruction)


(Voltage between pins
of C930): 0 V DC
(when stopped),
1.8 - 6.5 V DC
(when operated)
(Correspond to
(CNF1 (+)- (−)) F711 FUSE
T3.15AL250V
CNF1
To fan motor CNAC
Bus-bar voltage to outdoor power P.C.
290 ~ 370 V DC board 208/230 V AC
Input
15 V DC
CN714 Base heater
208/230 V AC
Output

CNDC CN713 Valve coil


Bus-bar 208/230 V AC
voltage Output
290 ~ 370
V DC CN712 R.V. coil
208/230 V AC
Output
CNTH2
Ambient temperature
thermistor
(RT65)
CNTH1
Outdoor heat exchanger
temperature thermistor
(RT68)
Discharge temperature
thermistor (RT62)
Defrost thermistor
CN63H (RT61)
High
pressure SW1
switch
SW871

SW2

LED3
(+)
(-)
(+)
18 V
(-)
5 V DC pulse wave15(-)
V
15 V

LED2
CN794 LEV Room D
CN793 LEV Room C
CN795 LEV Room E

CN792 LEV Room B


CN791 LEV Room A

LED1
5 V DC pulse wave
(To power board)
(To power board)

CN701 Signal
CN702 Signal

transmission
transmission

LEV: 12 V DC
pulse wave

OBHT702H 127
1. Outdoor control P.C. board 700
Discharge temperature thermistor (RT62) Defrost thermistor (RT61)
Ambient temperature thermistor (RT65)
NTXMMX42A152CA 600 Outdoor heat exchanger temperature
thermistor (RT68)
NTXMPH20A122CA

Resistance (kΩ)
500 100

NTXMPH24A132CA
400 90

300
NTXMPH30A132CA
80

Resistance (kΩ)
200 70

100 60

0 50
0 10 20 30 40 50 60 70 80 90 100 110 120 (ºC)
32 50 68 86 104 122 140 158 176 194 212 230 248 (ºF)
40
Temperature
Thermistor R100 = 13.36 kΩ ± 2% , B constant = 4014 ± 2% 30
1 1
Rt = 13.36exp{4014( 273+t 373 )} , t: ºC = (ºF - 32)/1.8
20
Serial signal 12 ~ 24 V 10

)
208/230 V DC Room B Room D 0
Room A Room C Room E -20 -10 0 10 20 30 40 (ºC)
CN741 Input -4 14 32 50 68 86 104 (ºF)
Temperature
Signal translation
Thermistor R25 = 10 kΩ ± 2%
(To Communication B constant = 3950 ± 2%
adaptor board) CN601
Rt = 10exp{3950( 1 1 )}
273+t 298
CN611 CN621 t : ºC = (ºF - 32)/1.8

VFG (Rotate signal)


(Voltage between
right pins of PC931,
pin 3 and pin 4)
(Correspond to
(CNF1 (+)- (−))

VSP (Rotate instruction)


(Voltage between pins
of C930): 0 V DC
(when stopped),
1.8 - 6.5 V DC
(when operated)

F711 FUSE
CNF1 T3.15AL250V
To fan motor CNAC
Bus-bar voltage to outdoor power P.C.
290 - 370 V DC board 208/230 V AC
Input
15 V DC
CN714 Defrost heater
208/230 V AC
Output

CNDC CN713 Valve coil


Bus-bar 208/230 V AC
voltage Output
290 - 370
V DC CN712 R.V. coil
208/230 V AC
Output
CNTH2
Ambient temperature
thermistor
(RT65)
CNTH1
Outdoor heat exchanger
temperature thermistor
(RT68)
Discharge temperature
thermistor (RT62)
Defrost thermistor
CN63H (RT61)
High
pressure SW1
switch
SW871

SW872
SW2

LED3
(+)
(-)
(+)
18 V
(-)
5 V DC pulse wave15(-)
V
15 V

LED2
CN794 LEV Room D
CN793 LEV Room C
CN795 LEV Room E

CN792 LEV Room B


CN791 LEV Room A

LED1
5 V DC pulse wave
(To power board)
(To power board)

CN701 Signal
CN702 Signal

transmission
transmission

LEV: 12 V DC
pulse wave

OBHT702H 128
2. Outdoor power P.C. board
NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA

CN151 Signal transmission


(To Outdoor control

5 V DC pulse wave
P.C. board)
Output to drive compressor

15 V

15 V
CN171
(+)

(-)
(-)
Fin temperature thermistor (-) CN152
(RT64) (+) Signal Transmission
(From Outdoor
Control P.C. board)
5 V DC pulse wave
Connect to earth

CNAC2
208/230 V AC
Output

F1 FUSE
T6.3AL250V

208/230 V AC
Input

F2 FUSE
T6.3AL250V
CNAC1
208/230 V AC
Output

Connect to reactor Connect to reactor CNDC Connect to earth


(Red line) (White line) Bus-bar voltage
290 - 370 V DC
Fin temperature thermistor (RT64)
200
180
160
Resistance (kΩ)

140
120
100
80
60
40
20
0
0 10 20 30 40 50 60 70 80 (°C)
32 50 68 86 104 122 140 158 176 (°F)
Temperature
Thermistor R50 = 17 kΩ ± 2%
B constant = 4150 ± 3%
Rt = 17exp{4150( 1 1 )}
273+t 323
t : ºC = (ºF - 32)/1.8

OBHT702H 129
2. Outdoor power P.C. board
NTXMMX24A132AA NTXMMX24A132BA
NTXMMX30A132AA NTXMMX30A132BA
NTXMMX36A142AA NTXMMX36A142BA

CN151 Signal transmission


(To Outdoor control

5 V DC pulse wave
Output to drive compressor P.C. board)
15 V

15 V
CN171
(+)

(-)
(-)
Fin temperature thermistor (-) CN152
(RT64) (+) Signal Transmission
(From Outdoor
Control P.C. board)
5 V DC pulse wave
Connect to earth

CNAC2
208/230 V AC
Output

F1 FUSE
T6.3AL250V

208/230 V AC
Input

F2 FUSE
T6.3AL250V
CNAC1
208/230 V AC Output

Connect to reactor Connect to reactor CNDC Connect to earth


(Red line) (White line) Bus-bar voltage
290 - 370 V DC
Fin temperature thermistor (RT64)
200
180
160
Resistance (kΩ)

140
120
100
80
60
40
20
0
0 10 20 30 40 50 60 70 80 (°C)
32 50 68 86 104 122 140 158 176 (°F)
Temperature
Thermistor R50 = 17 kΩ ± 2%
B constant = 4150 ± 3%
Rt = 17exp{4150( 1 1 )}
273+t 323
t : ºC = (ºF - 32)/1.8

OBHT702H 130
2. Outdoor power P.C. board
NTXMMX24A132CA NTXMMX30A132CA NTXMMX36A142CA

CN151 Signal transmission

Fin temperature thermistor

(-) Signal Transmission


Control P.C. board)
(To Outdoor control

5 V DC pulse wave

5 V DC pulse wave
(From Outdoor
P.C. board)
CN171

(+) CN152
(RT64)
15 V

15 V
CNDC CNAC1

(+)
Output to drive compressor

(-)
(-)
Bus-bar voltage 208/230 V AC
290 - 370 V DC Output

Connect to earth
F2 FUSE
10A 250V
F1 FUSE
10A 250V

Connect to earth

208/230 V AC
Input

Connect to reactor Connect to reactor CNAC2 Connect to earth


(Black line) (Red line) 208/230 V AC
Fin temperature thermistor (RT64) Output
200
180
160
Resistance (kΩ)

140
120
100
80
60
40
20
0
0 10 20 30 40 50 60 70 80 (°C)
32 50 68 86 104 122 140 158 176 (°F)
Temperature
Thermistor R50 = 17 kΩ ± 2%
B constant = 4150 ± 3%
Rt = 17exp{4150( 1 1 )}
273+t 323
t : ºC = (ºF - 32)/1.8

OBHT702H 131
2. Outdoor power P.C. board
NTXMMX42A152AA NTXMMX42A152BA
NTXMPH20A122AA NTXMPH20A122BA
NTXMPH24A132AA NTXMPH24A132BA
NTXMPH30A132AA NTXMPH30A132BA
CN151 Signal transmission
(To Outdoor control

5 V DC pulse wave
P.C. board)

CNDC
Bus-bar voltage
CN171 Output to drive compressor 290 - 370 V DC CNAC1 Connect to earth
Fin temperature thermistor 208/230 V Output
18 V

15 V
15 V

(RT64)
(+)

(-)
(-)

F1 FUSE
T6.3AL250V
CN152 F2 FUSE
Signal T6.3AL250V
Transmission
(From Outdoor
Control P.C. board)
5 V DC pulse wave
(+)
(-)
Connect
to earth

Connect to reactor Connect to reactor CNAC2 208/230 V AC Input


(White line) (Red line) Connect 208/230 V AC
to earth Output

Fin temperature thermistor (RT64)


200
180
160
Resistance (kΩ)

140
120
100
80
60
40
20
0
0 10 20 30 40 50 60 70 80 (°C)
32 50 68 86 104 122 140 158 176 (°F)
Temperature
Thermistor R50 = 17 kΩ ± 2%
B constant = 4150 ± 3%
Rt = 17exp{4150( 1 1 )}
273+t 323
t : ºC = (ºF - 32)/1.8

OBHT702H 132
2. Outdoor power P.C. board
NTXMMX42A152CA
NTXMPH20A122CA
NTXMPH24A132CA
NTXMPH30A132CA
CN151 Signal transmission
(To Outdoor control
5 V DC pulse wave
P.C. board)

CNDC
Bus-bar voltage
CN171 Output to drive compressor 290 - 370 V DC CNAC1 Connect to earth
Fin temperature thermistor 208/230 V Output
18 V

15 V
15 V

(RT64)
(+)

(-)
(-)

F1 FUSE
10A 250V
CN152 F2 FUSE
Signal 10A 250V
Transmission
(From Outdoor
Control P.C. board)
5 V DC pulse wave
(+)
(-)
Connect
to earth

Connect to reactor Connect to reactor CNAC2 208/230 V AC Input


(White line) (Red line) Connect 208/230 V AC
to earth Output

Fin temperature thermistor (RT64)


200
180
160
Resistance (kΩ)

140
120
100
80
60
40
20
0
0 10 20 30 40 50 60 70 80 (°C)
32 50 68 86 104 122 140 158 176 (°F)
Temperature
Thermistor R50 = 17 kΩ ± 2%
B constant = 4150 ± 3%
Rt = 17exp{4150( 1 1 )}
273+t 323
t : ºC = (ºF - 32)/1.8

OBHT702H 133
13 DISASSEMBLY INSTRUCTIONS

<Detaching method of the terminal with locking mechanism>


The terminal which has the locking mechanism can be detached as shown below.
There are 2 types of the terminal with locking mechanism.
The terminal without locking mechanism can be detached by pulling it out.
Check the shape of the terminal before detaching.
(1) Slide the sleeve and check if there is a locking lever or not. (2) The terminal with this connector shown below
has the locking mechanism.
Sleeve

Slide the sleeve. Hold the sleeve, and


Pull the terminal while pull out the terminal slowly.
Locking lever pushing the locking lever.

Connector

13-1. NTXMMX20A122AA NTXMMX20A122AC NTXMMX20A122BA NTXMMX20A122CA


: Indicates the visible parts in the photos/figures.
NOTE: Turn OFF the power supply before disassembly. : Indicates the invisible parts in the photos/figures.

OPERATING PROCEDURE PHOTOS/FIGURES


1. Removing the cabinet and the panels Photo 1 Screws of the
(1) Remove all the screws of the service panel, and remove top panel
the service panel.
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires. Screws of
(3) Remove all the screws of the top panel, and remove the the cabinet
top panel. Screws of
(4) Remove all the screws of the cabinet, and remove the service
cabinet. panel
(5) Remove all the screws of the back panel, and remove the
back panel (Photo 3).

Photo 3 Screws of the cabinet


Screw of the rear guard
Screws of Screws of the
Photo 2 the cabinet sub panel
Screws of the
top panel

Screws of the
back panel

Screws of
Screws of the cabinet
the back panel
Screws of the
back panel

OBHT702H 134
OPERATING PROCEDURE PHOTOS/FIGURES
2. Removing the outdoor control P.C. board, the out- Photo 4
door power P.C. board and the reactor
Electrical
(1) Remove the service panel (Photo 1). box assembly
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(3) Remove the top panel, the cabinet, and the back panel Catches of the
(Photo 1, 2, 3). outdoor control
(4) Disconnect all the connectors and the lead wires on the P.C. board
outdoor control P.C. board.
(5) Disengage all the catches of the outdoor control P.C.
board, and remove the outdoor control P.C. board.
(6) Remove all the screws of the electrical box assembly,
disengage all the catches of the electrical box assembly,
and remove the electrical box assembly.
(7) Remove all the screws of outdoor control P.C. board Screws of the electrical box assembly
holder, and remove the outdoor control P.C. board holder.
(8) Remove all the screws of the reactor, and remove the
reactor.
(9) Remove all the screws of the reactor bed, and remove
Photo 5
the reactor bed.
(10) Remove all the screws of the heat sink support, and
remove the heat sink support.
(11) Remove all the screws fixing the outdoor power P.C.
board.
(12) Disconnect the connectors and the lead wires on the out-
door power P.C. board.

Photo 6
Screw of the heat
sink support
Screw of
the reactor bed Screws of the outdoor
control P.C. board holder

Photo 7

Screws of the reactor


Heat sink support Screws of
the reactor bed
Screws of the outdoor
power P.C. board

OBHT702H 135
OPERATING PROCEDURE PHOTOS/FIGURES
3. Removing the fan motor Photo 8 Screws of the outdoor fan motor
(1) Remove the service panel (Photo 1).
(2) Disconnect the power supply cord and indoor/outdoor con-
necting wires.
Sound
(3) Remove the top panel, the cabinet, and the back panel proof
(Photo 1, 2, 3). felt
(4) Disconnect the connectors of CN712, CNF1, CNTH1,
CNTH2, CN63H, CN791, CN792, CN797 on the outdoor
control P.C. board and disconnect the relay connector of
the compressor lead wire.
(5) Remove all the screws of the electrical box assembly, and
remove the electrical box assembly (Photo 4).
(6) Remove the propeller fan.
(7) Remove the fan motor.
NOTE: The propeller fan nut is a reverse thread.
Sound
Propeller fan Propeller Separator Sound proof
fan nut proof felt felt

4. Removing the compressor and the 4-way valve


(1) Remove the service panel (Photo 1). Photo 9 R.V. coil 4-way valve
(2) Disconnect the power supply cord and indoor/outdoor con-
necting wires. LEV coil R
(3) Remove the top panel, the cabinet, and the back panel
(Photo 1, 2, 3).
(4) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 kg/cm2 (0 MPa). Expansion valve R
(5) Disconnect the outdoor control P.C. board connectors:
CNF1, CNTH1, CNTH2, CN63H, CN791,CN792, CN797, Discharge pipe
CN712. brazed part
(6) Disconnect the compressor lead wire from the terminal of
the compressor (U, V, W).
(7) Remove all the screws of the electrical box assembly, and
remove the electrical box assembly (Photo 4).
Suction pipe
(8) Remove the propeller fan. brazed part
Sound
(9) Remove the sound proof felt , and .
proof
(10) Remove all the screws of the separator, and remove the felt *2 Compressor nuts
separator.
(11) Detach all the brazed parts of the compressor suction and Photo 10
discharge pipes.
(12) Remove all the compressor nuts and remove the
4-way
compressor.
valve
(13) Detach all the brazed parts of the 4-way valve and pipe.

R.V. coil

Brazed parts

OBHT702H 136
OPERATING PROCEDURE PHOTOS/FIGURES
5. Removing the expansion valve Photo 11
NOTE: Gas recovery is not required if the unit is pumped down.
(1) Remove the top panel and the service panel (Refer to
section 1).
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(3) Remove all the LEV coils.
(4) Detach all the brazed parts of the expansion valves and
pipes.

LEV coils Expansion


valves

6. Before using the service port (High pressure side) Photo 12


(1) Remove the service panel (Photo 1).
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(3) Remove the top panel, the cabinet, and the back panel
(Photo 1, 2, 3).
(4) Disconnect all the connectors and the lead wires on the
outdoor control P.C. board.
(5) Remove all the screws of outdoor control P.C. board holder,
and remove the outdoor control P.C. board holder (Photo 5).
(6) Make sure that the service port is visible.

Service port
(High pressure side)

OBHT702H 137
13-2. NTXMMX24A132AA NTXMMX24A132BA NTXMMX24A132CA
NTXMMX30A132AA NTXMMX30A132BA NTXMMX30A132CA
NTXMMX36A142AA NTXMMX36A142BA NTXMMX36A142CA
Photos: NTXMMX36A142AA
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE PHOTOS/FIGURES
1. Removing the panels Photo 1 Screws of the top panel
(1) Remove all the screws fixing the top panel, and remove
the top panel.
(2) Remove all the screws fixing the service panel.
(3) Pull down on the service panel, and remove the service
panel.
(4) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(5) Remove all the screws fixing the front panel, and remove
the front panel.
(6) Remove all the screws fixing the back panel, and remove
the back panel.

Service panel
Photo 3

Catch of the front panel Catch of the front panel


Screws of the front panel Screws of the service panel
Photo 2
Screws of the top panel

Screws of the front panel Screws of the back panel

OBHT702H 138
OPERATING PROCEDURE PHOTOS/FIGURES
2. Removing the outdoor control P.C. board, the reac- Photo 6
tor, the outdoor power P.C. board, and the heatsink
(1) Remove the top panel and the service panel (Refer to
section 1).
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires. Catches of the
(3) Disconnect the wire-to-wire connector of the compressor outdoor contol
lead wire (Photo 4). P.C. board holder
(4) Disconnect all the connectors on the outdoor control P.C.
board.
(5) Remove the releasable cable tie securing the lead wires
of core, TBE1, CNTH2, and CNAC2 (Photo 4).
(6) Remove all the screws fixing the outdoor control P.C.
board holder (Photo 4).
(7) Remove the lead wires of TBE1, CNTH2, and CNAC2
from the right hook on the top of the outdoor control P.C.
board holder (Photo 4, ).
(8) Remove the lead wires of CN151 and CN152 from the left
Photo 7
hooks on the top and the bottom of the outdoor control
P.C. board holder (Photo 4, and 5). Lead wire of
(9) Remove the outdoor control P.C. board holder. TAB6 (White) (AA, BA)
(10) Disengage all the catches of the outdoor control P.C. TB3B(Black) (CA)
board holder, and remove the outdoor control P.C. board Lead wire of
(Photo 6). TAB3 (Red) (AA, BA)
(11) Disconnect all the lead wires from the reactor (Photo 7). TB1A(Red) (CA)
(12) Remove all the screws fixing the reactor, and remove the
reactor (Photo 7).
Lead wire of
(13) Remove all the lead wires from the clamps on the separa-
TAB4 (White) (AA, BA)
tor (Photo 8).
TB3A(Black) (CA)
Lead wire of
Lead wire Releasable TAB5 (Red) (AA, BA)
Photo 4 of CNDC cable tie TB1B(Red) (CA)
Screws of the reactor
Screws of
NOTE: These the outdoor
lead wires control P.C.
are hooked board holder
from front to
back
Photo 8 Lead wires of
Lead wires of TAB4, TAB5 (AA, BA)
CN791, CN792, Separator TB3A, TB1B (CA)
CN793, CN794,
Lead wire CNTH1, CN63H,
of CNF1 CN712

Connector of Lead wires of


the compressor CN151, CN152
lead wire

Photo 5
Clamps

Left hook on the bottom


of control P.C. board Lead wire of
(CN151, CN152) the compressor

OBHT702H 139
OPERATING PROCEDURE PHOTOS/FIGURES
(14) Disengage all the catches of the PB cover, and remove
Photo 9
the PB cover (Photo 9).
(15) Remove the screw fixing the outdoor power P.C. board
and all the screws fixing the outdoor power P.C. board
and the heatsink (Photo 10).
(16) Disengage all the catches of the outdoor power P.C.
board, and lift the outdoor power P.C. board (Photo 10).
(17) While lifting the outdoor power P.C. board, disconnect the
lead wires, the connectors, and the earth wires; then
remove the outdoor power P.C. board (Photo 11).
NOTE: When reassembling, pass the lead wire of the Catches of PB cover
CN171 thorough the notch and behind the lead
wire of the compressor (Photo 12). Photo 10
(18) Remove all the screws of the heatsink fixing parts and Screw of the power
remove the heatsink fixing parts (Photo 13). P.C. board
NOTE: Some units have only 1 heatsink fixing part.
(19) Remove the heatsink.

Screws of the power


P.C. board and the Catches of the
heatsink power P.C. board

Photo 11
(AA, BA) (CA)
Connetor of CN171 Lead wires of Connetor of CN171 Connetor
TAB1, TAB2 of CNAC1

Connetor Earth wires of Lead wires of


Earth wires of TBE2, TBE4 of CNAC1 TBE3, TBE4, TBE5 TAB1, TAB2

OBHT702H 140
OPERATING PROCEDURE PHOTOS/FIGURES
Photo 12 Photo 13
(AA, BA)

Notch

Lead wire of compressor Lead wire of CN171


(CA) Screws of fixing parts of the heat sink

Notch Lead wires of Lead wire of


compressor CN171

3. Removing the fan motor Photo 14


(1) Remove the top panel, the service panel, and the front
Propeller fan
panel (Refer to section 1).
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(3) Disconnect the connector of CNF1 on the outdoor control
P.C. board.
(4) Remove the propeller fan.
(5) Remove the fan motor.
NOTE: The propeller fan nut is a reverse thread.

Screws of the outdoor fan motor

OBHT702H 141
OPERATING PROCEDURE PHOTOS/FIGURES
4. Removing the compressor and 4-way valve Photo 15
(1) Remove the top panel, the service panel, and the front
panel (Refer to section 1).
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires, and remove the back panel.
(3) Recover gas from the refrigerant circuit.
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 PSIG.
(4) Disconnect the compressor lead wire from the terminal of
the compressor (U, V, W).
(5) Disconnect the outdoor control P.C. board connectors:
CNF1, CNTH1, CNTH2, CN63H, CN712, CN791, CN792,
CN793, CN794 (NTXMMX36A142AA, NTXMMX36A142BA,
NTXMMX36A142CA)
(6) Remove all the screws fixing the electrical parts, and
remove the electrical parts.
Screws of the electrical parts
(7) Remove the propeller fan. Photo 16
(8) Remove all the screws fixing the separator, and remove 4-way valve
the separator.
(9) Remove the sound proof felt.
(10) Detach all the brazed parts of the compressor suction and
discharge pipes (Photo 17). R.V. coil
(11) Remove all the compressor nuts and remove the compres-
sor (Photo 17).
(12) Detach all the brazed parts of 4-way valve and pipes.

Brazed parts
5. Removing the expansion valve Photo 17
NOTE: Gas recovery is not required if the unit is pumped down.
(1) Remove the top panel and the service panel (Refer to
Discharge pipe
section 1).
brazed part
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(3) Remove all the LEV coils.
NOTE: When reassembling, to secure the LEV coils on the Expansion
pipe, make sure to use the metal clips for proper valves
positioning.
(4) Detach all the brazed parts of the expansion valves and
pipes.
Suction pipe
brazed part

Expansion
Compressor nuts valves
LEV coils

OBHT702H 142
13-3. NTXMMX42A152AA NTXMMX42A152BA NTXMMX42A152CA
NTXMPH20A122AA NTXMPH20A122BA NTXMPH20A122CA
NTXMPH24A132AA NTXMPH24A132BA NTXMPH24A132CA
NTXMPH30A132AA NTXMPH30A132BA NTXMPH30A132CA
Photos: NTXMPH30A132AA
NOTE: Turn OFF the power supply before disassembly.
OPERATING PROCEDURE PHOTOS/FIGURES
1. Removing the panels Photo 1 Screws of the top panel
(1) Remove all the screws fixing the top panel, and remove
the top panel.
(2) Remove all the screws fixing the service panel.
(3) Pull down on the service panel, and remove the service
panel.
(4) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(5) Remove all the screws fixing the front panel, and remove
the front panel.
(6) Remove all the screws fixing the back panel, and remove
the back panel.

Photo 3

Screws of the front panel Screws of the service panel

Photo 2 Screws of the top panel

Screw of the back panel


Screws of the front panel

Screws of the back panel

OBHT702H 143
OPERATING PROCEDURE PHOTOS/FIGURES
2. Removing the outdoor control P.C. board, the reac- Screw
tor and the outdoor power P.C. board Photo 4 of the
(1) Remove the top panel, the service panel and the front electrical
panel (Refer to section 1). parts
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires. Screws
(3) Disconnect all the connectors on the outdoor control P.C. board. of the
(4) Remove all the screws fixing the outdoor control P.C. electrical
board, and remove the outdoor control P.C. board. parts
(5) Remove all the screws fixing the electrical parts, and
remove the electrical parts.
(6) Remove all the screws fixing the TB support, and remove
the TB support.
(7) Remove all the screws fixing the control box separator,
and remove the control box separator.
(8) Disconnect the lead wire of the outdoor power P.C. board.
(9) Remove all the screws fixing the outdoor power P.C.
board, and remove the outdoor power P.C. board with the
outdoor P.C. board holder.
(10) Remove all the screws fixing the control box F, and Photo 5
remove the control box F.
(11) Remove all the screws fixing the reactors, and remove Screws
the reactors. of the
Photo 7 outdoor
control
P.C.
board

Photo 6
Screws of the TB support

Screws of the control box F


Photo 8

Screws of
the reactor

Screws of the
Screws of the control box separator outdoor power
P.C. board

OBHT702H 144
OPERATING PROCEDURE PHOTOS/FIGURES
3. Removing the fan motor
(1) Remove the top panel, the service panel, and the front Photo 9
panel (Refer to section 1). Screw of the
(2) Disconnect the power supply cord and indoor/outdoor Screws of the outdoor fan motor VB fixture
connecting wires.
(3) Disconnect the connector of CNF1 on the outdoor control
P.C. board.
(4) Remove the propeller fan.
(5) Remove the fan motor.
NOTE: The propeller fan nut is a reverse thread.

Propeller
fan

4. Removing the compressor and 4-way valve


(1) Remove the top panel, the service panel and the front
panel. Sound
(2) Disconnect the power supply cord and indoor/outdoor proof felt
Screws of the outdoor fan motor
connecting wires, and remove the back panel. VB fixture
(3) Recover gas from the refrigerant circuit. Separator
NOTE: Recover gas from the pipes until the pressure
gauge shows 0 PSIG. Photo 10
(5) Disconnect the compressor lead wire from the terminal of
the compressor (U, V, W).
(6) Disconnect the outdoor control P.C. board connectors:
CNF1, CNTH1, CNTH2, CN63H, CN712, CN713, CN714
(NTXMPH20A122AA, NTXMPH20A122BA,
NTXMPH20A122CA, NTXMPH24A/30A132AA,
NTXMPH24A/30A132BA, NTXMPH24A/30A132CA),
CN791, CN792, CN793
(NTXMMX42A152AA, NTXMMX42A152BA,
NTXMMX42A152CA, NTXMPH24A/30A132AA,
NTXMPH24A/30A132BA, NTXMPH24A/30A132CA)
CN794 (NTXMMX42A152AA, NTXMMX42A152BA,
NTXMMX42A152CA)
CN795 (NTXMMX42A152AA, NTXMMX42A152BA,
NTXMMX42A152CA)
(7) Remove all the screws fixing the electrical parts, and
remove the electrical parts (Photo 4).
(8) Remove the propeller fan. R.V. coil
(9) Remove all the screws fixing the VB fixture, and remove
the VB fixture.
(10) Remove all the screws fixing the separator, and remove
the separator.
NOTE: When installing the separator, insert the tabs of the
heat exchanger into the separator.
(11) Remove all the sound proof felts.
(12) Detach all the brazed parts of the suction and discharge
4-way valve
pipes (Photo 11).
Brazed parts
(13) Remove all the compressor nuts, and remove the com-
pressor (Photo 11).
(14) Detach all the brazed parts of 4-way valve and pipes.

OBHT702H 145
OPERATING PROCEDURE PHOTOS/FIGURES
5. Removing the expansion valve
NOTE: Gas recovery is not required if the unit is pumped down. Photo 11
(1) Remove the top panel and the service panel (Refer to Discharge pipe Suction pipe
section 1). brazed part brazed part
(2) Disconnect the power supply cord and indoor/outdoor
connecting wires.
(3) Remove all the LEV coils.
(4) Detach all the brazed parts of the expansion valves and
pipes.

Expansion
Compressor nuts LEV coils valves

MITSUBISHI ELECTRIC TRANE HVAC US LLC


HEAD OFFICE: 1340 SATELLITE BOULEVARD, SUWANEE, GA 30024, USA

© Copyright 2018 MITSUBISHI ELECTRIC CORPORATION


Issued: Jul. 2023. No. OBHT702 REVISED EDITION-H
Issued: Feb. 2023. No. OBHT702 REVISED EDITION-G
Issued: Nov. 2022. No. OBHT702 REVISED EDITION-F
Issued: Aug. 2022. No. OBHT702 REVISED EDITION-E
Issued: Jun. 2022. No. OBHT702 REVISED EDITION-D
Issued: Dec. 2021. No. OBHT702 REVISED EDITION-C
Issued: Jul. 2021. No. OBHT702 REVISED EDITION-B
Issued: Nov. 2020. No. OBHT702 REVISED EDITION-A
Published: Nov. 2018. No. OBHT702
Made in Japan Specifications are subject to change without notice.
146

You might also like