The E-FDC-DD fire damper is designed to prevent fire spread through ventilation ducts, featuring a galvanized steel casing and a calcium silicate damper blade. It is equipped with Belimo electric actuators that automatically close the damper at 72°C and can be operated remotely. The product is tested for fire resistance according to EN standards and is available in various sizes and configurations.

Uploaded by

lofok40031
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
28 views18 pages

Sk17150 en FDC-DD-Product Manual-Master L

The E-FDC-DD fire damper is designed to prevent fire spread through ventilation ducts, featuring a galvanized steel casing and a calcium silicate damper blade. It is equipped with Belimo electric actuators that automatically close the damper at 72°C and can be operated remotely. The product is tested for fire resistance according to EN standards and is available in various sizes and configurations.

Uploaded by

lofok40031
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 18

Product manual

E-FDC-DD
Fire damper

Fire protection
Version 1.0.0
Issue Date: 19.12.2023.
1. Damper frame 2
2. Galvanized steel casing 1
3. Actuator
4. Cold smoke seal 2

PRODUCT OVERVIEW
1
DIMENSIONS

INSTALLATIONS

ACTUATORS

ACCESSORIES
4
MAINTENANCE AND OPERATION

1. Fire resistant damper blade


2. Installation contact layer/side

PRODUCT OVERVIEW

* The images shown are for illustration purposes only and may not be an exact representation of the product.

PRODUCT OVERVIEW
Fire dampers FDDD are used for prevention of fire spread
trough the ventilation ducts and between the fire sections. Fire
damper E-FDC-DD consists of galvanized sheet metal casing, Fire dampers are equipped with Belimo electric actuators
calcium silicate damper blade, high temperature resistant (24 V or 230 V versions). Actuator’s spring closes the
installation frame made from calcium silicate and electric damper blade when it’s thermal fuse senses the ambient
actuator. temperature has reached 72°C. Closing and reopening of
damper blade can also be done remotely via control signal.
Fire damper casing is made out of galvanized steel sheet.
Variants produced from stainless steel and powder coated Declared blade airtightness - class 3 and casing airtightness
steel are also available. Calcium silicate blade is equipped with - class C are tested according to EN 1751.
brass bearings and seals. Brass bearings are pressed into the
casing. Calcium silicate blade is equipped with the seal made
out of EPDM rubber.

Fire dampers E-FDC-DD are produced up to size d315 and


have 25 mm thick damper blade.

2
PRODUCT OVERVIEW

DIMENSIONS

INSTALLATIONS

ACTUATORS

ACCESSORIES

MAINTENANCE AND OPERATION

PRODUCT OVERVIEW

PRODUCT OVERVIEW

FIRE RESISTANCE
CLASSIFICATION E - Integrity
I - Insulation
E-FDC-DD fire resistance is tested according to EN 1366-2
90 - Classification time in minutes
“Fire resistance tests for service installations- Part 2: Fire S - Smoke leakage
dampers”. Classification of the fire dampers is defined ve - Damper installed in vertical compartment
according to EN 13501-3 Fire classification of construction ho - Damper installed in horizontal compartment
products and building elements. i↔o - Fire performance criteria are met on both sides

Installation in both, vertical and horizontal axis of rotation


of the dampers blade is acceptable (with the axis angle 0 -
360°).
Fire resistance of fire damper depends on classification
of walls or ceilings. It is allowed to install products to
walls or ceilings only according to products Declaration of
Performance. Walls or ceilings with greater fire resistance
can also be used. Fire damper should be installed according
to the installation manual which can be found within this
document.

3
1 6

7 16
PRODUCT OVERVIEW
8
DIMENSIONS
9
INSTALLATIONS
2 10
ACTUATORS
3 11
ACCESSORIES
4
E-FDC-DD-d100-M230-S 12 13
MAINTENANCE AND OPERATION
5
14

15

FIRE DAMPER - E-FDC-DD

TECHNICAL DATA Product label Product specifications Pressure drop tables


Pressure drop values are described with the “Zeta” values
Fire damper casing is manufactured from 1 - Casing air leakage classification Nominal sizes E-FDC-DD 100 - 315 [mm]
for each size. The exact pressure drop in [Pa] is calculated
2 - Serial number using the following formula:
galvanized steel sheet, but on demand can be Casing length 170 mm
3 - Production date
produced out of: Δp [Pa]= ζ * v² * 0,6
4 - Type Temperature range -20 °C ... 50 °C
• Galvanized steel and powder coated 5 - Dimension of the fire damper
Release temperature 72 °C (standard) where ζ is Zeta value from the tables below, v is airflow
6 - Mechanism type velocity in [m/s]
7 - Nominal voltage Volume flow rate range up to 21700 m³/h
8 - Signalisation (end contacts)
9 - IP protection Differential pressure range up to 600 Pa
10 - Free space
Casing air leakage Class C, EN 1751
11 - Thermal fuse temperature
12 - Number of the European standard and Closed blade air leakage Class 3, EN 1751
year of its publication
Upstream velocity < 12 m/s
13 - Declaration of performance
14 - Classification according to EN 13501-3 EN 13501-3, EN 1366-2,
15 - Barcode EC conformity EN 15650, EN 1751,
CPR no.305/2011
16 - CE mark
Declaration of
DoP 717/2022
performance

4
PRODUCT OVERVIEW

DIMENSIONS

E-FDC-DD INSTALLATIONS

ACTUATORS
Dimensional range
Diameter Cross section Net area
ACCESSORIES
Model
Ød [mm] [dm²] [dm²]
MAINTENANCE AND OPERATION
E-FDC-DD D100 98 0,74 0,50
E-FDC-DD D125 123 1,17 0,87
E-FDC-DD D160 158 1,93 1,55
E-FDC-DD D200 198 3,05 2,56
E-FDC-DD D250 248 4,79 4,18
E-FDC-DD D315 313 7,64 6,87

DIMENSIONS

50
50

S
S 60
60
X Y
d D+
+ 120
120
Weights Length of damper blade
(with Belimo actuator 1,1kg) outside of casing
Model Weight [kg] Model S X side Y side
E-FDC-DD D100 3,022 68 / /
E-FDC-DD D125 3,389 E-FDC-DD D125 78 / /

Φd
ØD
S
S

E-FDC-DD D160 3,94 92 / /

E-FDC-DD D200 4,619 107 12,1 mm 15,9 mm

E-FDC-DD D250 5,547 E-FDC-DD D250 126 37,1 mm 40,9 mm

E-FDC-DD D315 6,879 E-FDC-DD D315 140 69,6 mm 73,4 mm

90
90
(d +
( D+120)
120) ++6060 170
170

255
255
5
PRODUCT OVERVIEW

DIMENSIONS

MODELS INSTALLATIONS

Casings ACTUATORS
E-FDC-DD ACCESSORIES
Cylindrical fire damper with 25 mm damper blade
and fire classification up to EI 90S. Sizes range MAINTENANCE AND OPERATION
from d100 till d315.

PRODUCT OVERVIEW

Actuators Ordering key


M24-S-ST (1) Damper type (2) Dimension (3) Actuator type
M230-S Belimo 24 V electro motor operating mechanism, comes with integrated end
Belimo 230 V electro motor operating mechanism, comes with integrated switches. In case of fire, the fire damper closes automatically.
end switches. In case of fire, the fire damper closes automatically. E-FDC- - d250 - M230-S
Damper closing can be initiated either by thermoelectric release device or
Damper closing can be initiated either by thermoelectric release device remotely by triggering the electro motor. Upon closure, damper blade is locked
or remotely by triggering the electro motor. Upon closure, damper in closed position and can be opened by sending a signal to electro motor.
blade is locked in closed position and can be opened by sending a (1) E-FDC-DD
Standard thermoelectric release point is 72 °C. Actuator is additionally equipped
signal to electro motor. Standard thermoelectric release point is 72 °C. with connection plug for easy connection with power supply and communication
modules. (2) Damper diameter
M24-S d100 till d315
Belimo 24 V electro motor operating mechanism, comes with integrated
end switches. In case of fire, the fire damper closes automatically.
Damper closing can be initiated either by thermoelectric release device (3) Actuator type:
or remotely by triggering the electro motor. Upon closure, damper M230-S - electric actuator AC/DC 230 V
blade is locked in closed position and can be opened by sending a M24-S - electric actuator AC/DC 24 V
signal to electro motor. Standard thermoelectric release point is 72 °C. M24-S-ST - electric actuator AC/DC 24 V
with connection plug

6
PRODUCT OVERVIEW

DIMENSIONS

INSTALLATION INSTALLATIONS

The E-FDC-DD fire damper is always tested in ACTUATORS


standardized support frames (both in a rigid wall
and in a flexible wall) in accordance with EN 1366-2: ACCESSORIES
2015. The results obtained are valid for all similar
support frames which have a thickness and/ or MAINTENANCE AND OPERATION
density and/or fire resistance similar or greater
than the one on the test.
X
The thermal switch must be
installed so that it does not
interfere with the operation of
the damper blade and must not
be installed on the E-FDC-DD
casing! E-FDC-DD
Ød [mm] 98 123 158 198 248 313
X [mm] 90 90 90 100 130 160
X - Recommended distance for installation of thermal switch

INSTALLATION

The duct connected to the fire damper must be supported


or hung in such a way that the damper does not carry its
weight. The damper must not support any part of the The gap in the installation opening between the fire
surrounding construction or wall which could cause damage damper and the wall/ceiling can be increased by up to 50%,
and consequent damper failure. It is recommended to or decreased to the smallest dimension where there is
connect the damper with a flexible connection on either sufficient space for installation of the seal!
end of the damper.
The damper driving mechanism can be placed on either side Opening size - Ød+2A
Damper size - Ød [mm]
of the wall, however it needs to be placed in such way that it (Max)
ensures an easy access during inspection.
Ød Ød + 15 mm
• Mounting is possible with the blade axis in horizontal or
in vertical position Recommended opening dimensions:
• The installation must comply with the tests that were Installation in both, vertical and horizontal axis of rotation of
performed during certification the dampers blade is acceptable
• Avoid any obstruction of the moving blade by the
360° Φd
(rigid walls with the axis angle 0 - 360°,
connected ducts +
flexibile walls 0 °- 90°-180°- 270°- 360°). 15
• The class of air-tightness is maintained in case the mm
installation of the damper is made in accordance with
the technical manual
• Operating temperature: 50 °C max
• For indoor use only

7
Range

Supporting Wall Supporting construction Tested Construction Sealing


Type of installation Classification Details
construction thickness details underpressure type type

Aerated concrete
( ≥ 550kg/m³)
Rigid wall ≥ 100 mm / EI 60 (ve i↔o)S 300Pa
Reinforced concrete
(≥ 2200kg/m³)

Gypsum blocks Aerated concrete ( ≥ 550 kg/m³) or


≥ 70 mm / EI 60 (ve i↔o)S 300Pa reinforced concrete (≥ 2200 kg/m³)
(≥ 995kg/m³)
wall, more than 100 mm thick

Gypsum blocks (≥ 995 kg/m³) wall,


A: Plasterboard more than 100 mm thick
type F (EN520),
mineral wool up to
60 kg/m³ Plasterboard wall, type F (EN520),
≥ 100 mm / EI 60 (ve i↔o)S 300Pa Plasterboard wall, type A (EN520),
more than 100 mm thick
B: Plasterboard
E-FDC-DD

type A (EN520),
Flexible wall Plasterboard wall, type F (EN520),
mineral wool up to
60 kg/m³ Plasterboard wall, type A (EN520),
more than 100 mm thick
A: Plasterboard
type F (EN520), Floor/ Ceiling installation, Aerated
EI 90 (ve i↔o)S concrete ( ≥ 550kg/m³) Reinforced
mineral wool up to
60 kg/m³ concrete (≥ 2200kg/m³) more than
Installation with 100 mm thick
≥ 100 mm 300Pa
profile inserts
B: Plasterboard
type A (EN520),
EI 60 (ve i↔o)S FIRE DAMPER - E-FDC-DD
mineral wool up to
60 kg/m³

Aerated concrete
( ≥ 550kg/m³) Remote from floor/ceiling E-FDC-DD installation
Floor/ Ceiling ≥ 100 mm EI 60 (ho o↔i)S 300Pa
Reinforced concrete on the insulated duct
(≥ 2200kg/m³)

8
PRODUCT OVERVIEW

DIMENSIONS

Rigid wall INSTALLATIONS

installation ACTUATORS

The wall is composed of concrete blocks ACCESSORIES


(minimum density of 550 kg/m³) or
reinforced concrete (minimum density of 2200 kg/ MAINTENANCE AND OPERATION
m³) and with a minimum thickness of 100 mm.

Possible damper orientations

0 - 90 - 180 - 270 - 360°

INSTALLATION

6 5 4 3 2 1
1. Create a wall opening.

2. Before installing the damper on the wall, it is D D

necessary to apply a thin strip of silicone to the


OPTIONAL
contact layer of calcium silicate. silicone
*Use silicone resistant to elevated temperatures.

3.Insert fire damper into the wall and fasten with ⌀d


screws (8 pcs, 6x100 mm).
+
15 C C
mm
4. OPTIONAL Seal the gap on the oposite side
of the wall with silicone resistant to elevated
temperatures. NOTE! Fire dampers are tested and
classified without the sealing on the opposite side
of the wall. This sealing is for visual purposes only, B B
and does not affect the performance of the fire
damper.

Damper blade must be closed during 1 2 3 silicone 4


installation!

Test the operation of the damper blade! A A


Designed by Checked by Approved by Date Date

Marko Kokolic 07.06.22

Edition Sheet
FDC-DD D315 1/1
6 5 4 3 2 1
9
PRODUCT OVERVIEW

DIMENSIONS

Gypsum blocks INSTALLATIONS

wall installation ACTUATORS

The wall is composed of gypsum blocks ACCESSORIES


(minimum density of 995 kg/m³), and with minimum
thickness of 70 mm. MAINTENANCE AND OPERATION

Possible damper orientations

0 - 90 - 180 - 270 - 360°

INSTALLATION

1. Create a wall opening. 6 5 4 3 2 1

2. Before installing the damper on the wall, it is


necessary to apply a thin strip of silicone to the D D

contact layer of calcium silicate. OPTIONAL


*Use silicone resistant to elevated temperatures. silicone

3. Insert fire damper into the wall and fasten with


screws (8 pcs, 6x100 mm). ⌀d
+
15 C C
mm
4. OPTIONAL Seal the gap on the oposite side
of the wall with silicone resistant to elevated
temperatures. NOTE! Fire dampers are tested and
classified without the sealing on the opposite side
of the wall. This sealing is for visual purposes only,
and does not affect the performance of the fire B B
damper.

Damper blade must be closed during


installation! 1 2 3 silicone 4
Test the operation of the damper blade!
A Designed by Checked by Approved by Date Date
A
Marko Kokolic 07.06.22

Edition Sheet
FDC-DD D315 1/1
6 5 4 3 2 1
10
Flexible wall
installation PRODUCT OVERVIEW
The wall is composed of 2x2 plasterboard
boards, DIMENSIONS
12,5 mm thick, installed on a steel frame
construction. To fulfill the classification it is NOT INSTALLATIONS
mandatory to use the mineral wool inside the wall
(mineral wool with density up to 60 kg/m³ can be ACTUATORS
used).The minimum thickness of the wall is 100
mm. ACCESSORIES
With subframe for flexibile wall
MAINTENANCE AND OPERATION
The wall is made out of type F or type A (EN520)
plasterboard - EI 60 (ve i↔o)S
With profile inserts
The wall is made out of
type F (EN520) -EI 90 (ve i↔o)S
or type A (EN520) - EI 60 (ve i↔o)S
plasterboard.

Possible damper orientations

0 - 90 - 180 - 270 - 360°

INSTALLATION

6 5 4 3 2 1
Create subframe for instalation in flexibile wall!
(page 13.)
D D

1. Create a wall opening. OPTIONAL


silicone
2. Before installing the damper on the wall, it is
necessary to apply a thin strip of silicone to the
contact layer of calcium silicate. ⌀d
+
*Use silicone resistant to elevated temperatures. 15 C C
mm
3. Insert fire damper into the wall and fasten with
screws (8 pcs, 6x100 mm).

4. OPTIONAL Seal the gap on the oposite side


of the wall with silicone resistant to elevated B B
temperatures. NOTE! Fire dampers are tested and
classified without the sealing on the opposite side
of the wall. This sealing is for visual purposes only,
and does not affect the performance of the fire 1 2 3 silicone 4
damper.

Damper blade must be closed during A Designed by

Marko Kokolic
Checked by Approved by Date Date

07.06.22
A

installation! Edition Sheet


FDC-DD D315 1/1
6 5 4 3 2 1
Test the operation of the damper blade! 11
Ferninstallation
vom Boden/Decke
1. Schaffen Sie eine Öffnung in der Decke, die 85 mm
größer ist als der Nenndurchmesser des Lüftungskanals. PRODUKTÜBERSICHT

2. Führen Sie die entsprechende Lüftungsleitung in die ABMESSUNGEN


Öffnung ein und drücken Sie die 80 mm dicke U Protect
Wired Mat 4.0 Wolle zwischen sie und die Öffnung. Die INSTALLATION
Breite des um den Lüftungskanal zu stopfenden Woll-
stücks sollte der Dicke der Decke entsprechen - 100 mm. ANTRIEBE

3. Beide Seiten der gepressten Wolle in der Deckenöff- KOMMUNIKATIONS MODULE


nung müssen mit ISOVER Protect BSF-Beschichtung in
einer Breite von 50 mm um den Lüftungskanal herum ZUBEHÖR
beschichtet werden.
ERSETZUNGEN
4. Der Lüftungskanal wird beidseitig mit Kanalschellen
und Stahl-L-Profilen 30 x 30 x 3 mm an der Unterkon- WARTUNG UND BETRIEB
struktion (Decke) befestigt. Die Enden des L-Profils soll-
ten ca. 350 mm von der Lüftungsleitung entfernt sein.
Die Stahlschellen mit Blechschrauben 4,2 x 19 (DIN 7504)
- 4 Stück alle 90° - an der Lüftungsleitung befestigen.
Befestigen Sie die längeren L-Profile über eine
Stahlschelle mit einer Blechschraube 4,2 x 19 - DIN7504
an der Lüftungsleitung.
Die kürzeren L-Profile über Stahlklammern mit Schrau-
ben M6 x 20 (DIN 933), Unterlegscheiben 6.4 (DIN 9021)
und Muttern M6 (DIN 934) am Lüftungskanal befestigen.
Die angegebenen L-Profile (kürzer und länger) mit den
Schrauben 7 x 50 an der Decke befestigen.
FIRE DAMPER - E-FDC-DD
Hinweis: Hängen Sie den Lüftungskanal auf die gleiche
Weise von unten ein, wobei die L-Profile und die Ka-
nalstahlklammer um 90° gegenüber den Profilen auf der
Oberseite gedreht sein müssen.

5. Die Brandschutzklappe E-FDC-DD wird in den ver-


tikalen Lüftungskanal eingesetzt und zusätzlich mit
selbstschneidenden Schrauben (8 Stück - DIN 7504 3,5 x
9,5 mm), die gleichmäßig über den Umfang verteilt sind,
befestigt. Es ist darauf zu achten, dass das Klappenblatt
beim Öffnen und Schließen nicht an den genannten
Schrauben hängen bleibt.

6. Schneiden Sie zwei Stücke der U Protect U Wired


Mat 4.0 Alu1 Wolle gemäß den nachstehenden Anweis-
ungen zu. Umwickeln Sie den Lüftungskanal mit Wolle
und verbinden Sie die Anschlüsse mit einem Draht. Die
Verbindungen zwischen der Wolle und der Decke sowie
zwischen der Wolle und dem Isolierrahmen der Brand-
schutzklappe E-FDC-DD müssen mit ISOVER BSK-Kleber
bestrichen werden.

7. Schweißen Sie die entsprechenden Stifte für den 1-2 3-4 5 6-7
Lüftungskanal durch die eingebrachte Wolle (6 Stück
pro Umfang) gemäß den nachstehenden Anweisungen.
Die Stifte sollten 90 mm von der Kante des Wollstücks
entfernt sein.

12
PRODUCT OVERVIEW

DIMENSIONS

UW50
UW50 rail INSTALLATIONS

ACTUATORS

ACCESSORIES
 d+15
 (max)
MAINTENANCE AND OPERATION
CW50
CW50
rail

INSTALLATION

FIRE DAMPER - E-FDC-DD


S+40
Installation with D+15 (max)

profiles inserts
 d+15 (max)

UW50 rail

CW50
rail UW50 rail

13
PRODUKTÜBERSICHT

ABMESSUNGEN
Minimale Installa- INSTALLATION
tionsabstände ANTRIEBE

KOMMUNIKATIONS MODULE

75
ZUBEHÖR

ERSETZUNGEN

WARTUNG UND BETRIEB

200
75 200

FIRE DAMPER - E-FDC-DD

*Mindestabstand von der Decke / Wand oder anderen Brandschutzklappen!

14
PRODUCT OVERVIEW

ELECTRIC DIMENSIONS

ACTUATOR INSTALLATIONS

E-M24-S, E-M230-S, ACTUATORS

E-M24-S-ST ACCESSORIES
Damper is delivered in closed position. When MAINTENANCE AND OPERATION
electric actuator is connected to the power supply,
damper blade will open. When the damper reaches
the end position (damper open), the electro
motor will stop. Closing fire damper takes place
automatically when a power failure occurs. Thermal
tripping device that comes with fire damper causes
power circuit break at a temperature of 72 °C. If
checking is needed for proper functioning of fire
damper, pushing the switch on the thermal tripping
device will close damper.

ACTUATORS

Technical specifications Wiring diagram


When switch on tripping device is released, the
damper will open. Damper can be opened without 1 negative (direct-current) or neutral (alternating
connecting to a voltage with enclosed handle by Type of Belimo actuator BFL24-T BFL230-T current)
turning it in the direction of the arrow on electric AC/DC 24 V,
AC 2 positive (direct-current) or faze (alternating cur-
actuator (clockwise). Damper can be locked in the Nominal voltage 230 V, 50/60 rent)
50/60 Hz
desired position by puling brake on Belimo BFL. voltage / Hz
S1 common micro switch closed damper
power opening 2,5 W 3,5 W
con- S2 normally closed micro switch closed damper
To unlock the electro motor, release brake for Be- sumption holding 0,8 W 1,1 W
S3 normally open micro switch closed damper
limo BFL. After release, damper will be closed by for wire sizing 4 VA 6,5 VA
return spring. When damper is opened manually, S4 common micro switch open damper
1 mA...3 A 1 mA...3 A
electric actuator will not move the damper into End switch (0,5 A), DC 5 (0.5 A), DC 5 S5 normally closed micro switch open damper
closed position in case of power failure. V...AC 250V V...AC 250 V S6 normally open micro switch open damper
motor < 60 s < 60 s Tf temperature sensor on the outer side of the duct
Running
time spring (ambient temperature) max. 72 °C
~20 s ~20 s
return
Ambient temperature
min. -30 °C, max. 50 °C
range

15
F

PRODUCT OVERVIEW

D DIMENSIONS

ACCESSORIES INSTALLATIONS

ACTUATORS
C Flexible duct connections - Flexible duct connec-
tors are used in HVAC systems for isolation from ACCESSORIES
structure-borne noise, expansion compensation
and fire damper connections (total length 150mm, MAINTENANCE AND OPERATION
flexible 60mm).

D/E Safety grilles - Fire damper, safety grille and, if


applicable, extension piece are assembled at the
factory to form a unit. The free cross sectional area
of the cover grille is approx. 70%. (1) Type (2) Accessories (3) Dimension

E-FD-A - FLEX - d100


(1) E-FD-A - Accessories for round fire damper (3) d100...d315 nominal diameter of the round fire damper

(2) FLEX - Flexible duct connections (1pc) C


SG1 - Safety grill on operation side E
SG2 - Safety grill on installation side D

ACCESSORIES

• For safety reasons, parts need to be changed by a


trained personnel or the manufacturer. A B
• WARNING! Install the original parts only!

A Communication module bracket FD-A-CMB


B Belimo thermal fuse 72 °C FD-A-BAT72
Drill hole (ø16 mm) for the fuse of Belimo
mechanism and fix it with self-tapping screws.

16
PRODUCT OVERVIEW

DIMENSIONS

INSTALLATIONS

ACTUATORS

ACCESSORIES

MAINTENANCE AND OPERATION

MAINTENANCE

TRANSPORT MAINTENANCE AND It is not permitted to alter the dampers in any way nor
perform any changes to their structure (except for the
FUNCTIONS
After arrival, check the fire damper for transport damage
and shortcomings. In case of any damage or shortcom- OPERATION service procedures described in this manual) without the
manufacturer’s consent. Provide at least one annual check
• Release mechanism:
Damper blade can be closed and opened manually
ings, immediately contact your supplier. of the damper. The functional test must be carried out in • Electric actuator:
Fire dampers are designed with fully enclosed drive compliance with the basic maintenance principles of the
mechanism outside of the duct and as such do not require Signal testing - the damper blade must close/open
European norms EN 13306, EN 15423 and EN15650.
STORAGE cleaning and regular maintenance.
However, activation mechanism should be inspected for
If the damper is not installed immediately:
proper operation on regular basis. COMMISSIONING
• Remove any wrapping. • Provide at least one annual check of the damper • Carefully unpack E-FDC-DD fire damper - be careful
• Protect fire damper from dust and contamina- • After each intervention, provide a systematic cleaning of sharp edges and do not use excessive force for
tion. of dust unpacking
• Do not expose the fire damper to the effects of
weather - store fire damper in dry place.
• Check if the electrical terminals are tightened • Inspect the fire damper - check the fire damper for
• Cleaning instruction: clean with a sponge, with water or damage
• Do not store the unit below -20 °C or above 50 a mild detergent
°C. • Installation of the fire damper - according to the
• Disinfection instruction: spray disinfectant (desinfectant installation instructions (page 7.)
may contain alcohol which is flammable, take precau-
Please properly dispose of packaging material. • Before commissioning: check the fire damper
tion to avoid ignition)
functions.

17