0% found this document useful (0 votes)
52 views36 pages

TL 1. Vds Certification - fcs-8000-Vfd-b - Aviotec Ip Starlight-Đã G P

Robert Bosch LLC has been accredited by A2LA for mechanical and electrical testing in accordance with ISO/IEC 17025:2017, valid until November 30, 2025. The accreditation covers a range of tests including tensile, compression, thermal shock, and electromagnetic compatibility tests. The laboratory demonstrates technical competence and maintains a quality management system for its defined scope of testing capabilities.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
52 views36 pages

TL 1. Vds Certification - fcs-8000-Vfd-b - Aviotec Ip Starlight-Đã G P

Robert Bosch LLC has been accredited by A2LA for mechanical and electrical testing in accordance with ISO/IEC 17025:2017, valid until November 30, 2025. The accreditation covers a range of tests including tensile, compression, thermal shock, and electromagnetic compatibility tests. The laboratory demonstrates technical competence and maintains a quality management system for its defined scope of testing capabilities.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 36

SCOPE OF ACCREDITATION TO ISO/IEC 17025:2017

ROBERT BOSCH LLC


Engineering Technical Center
15000 Haggerty Road
Plymouth, MI 48170
Christopher Milhan Phone: 248-207-2979

MECHANICAL

Valid To: November 30, 2025 Certificate Number: 3305.01

In recognition of the successful completion of the A2LA evaluation process, accreditation is granted to
this laboratory to perform the following tests on electrical/electronic control modules:

Test Type/Capabilities Test Method(s)


Mechanical
Tensile and Compression Testing GMW3172 (2010, 2012, 2014, 2015, 2018,
Up to 30 kN of applied force, 2023);
Speeds of 25 to 150 mm/min GMW3191 (2007, 2012, 2019);
Displacement from -250mm to 250mm USCAR-25 (2008)
Thermal Shock (TS)
Temperature Range: (-70 to 175) ˚C CETP-00.00-E-412 (2011);
Max Product Load: Up to 50 lbs CS-11982 (2012, 2013);
Temp Transition between Environments: <30s GMW3172 (2010, 2012, 2014, 2015, 2018,
Thermal Cycle Transitions: Up to 20˚C/min 2023);
ISO 16750-4 (2010);
EG-812-22611 (2008)
Visual Inspections
Scanning Electron Microscopy CETP-00.00-E-412 (2011);
Optical Microscopy CS-11982 (2013);
GMW3172 (2010, 2012, 2014, 2015, 2018,
2023)
Temperature/Humidity
Temperature Test: CETP-00.00-E-412 (2011);
Temperature Range: (-70 to 170) °C CS-11982 (2013);
Max Product Load: Up to 100 lb. GMW3172; (2010, 2012, 2014, 2015, 2018,
Temperature Transition Rate: 15 °C/min max 2023);
IEC 60068-2-38 (2009, 2021);
Humidity Test: IEC 60068-2-78 (2012);
Humidity Range: (25 to 95) %RH ISO 16750-4 (2010);
EG812-22611 (2008)
Vibration
Frequency Range: (5 to 2,500) Hz ASTM D4728 (2006,2017);
Force Capabilities: Up to 24,000 lb. Force CETP-00.00-E-412 (2011);
Displacement: Up to 3.5 inch Peak-to-Peak CS-11982 (2013);

(A2LA Cert. No. 3305.01) Revised 10/21/2024 Page 1 of 3


Test Type/Capabilities Test Method(s)
Random, Sine, Sine-on-Random GMW3172; (2010, 2012, 2014, 2015, 2018,
Resonance Search and Dwell 2023);
IEC 60068-2-64 (2008);
Combined Environment: ES-JL3E-9F991-AA (2010);
Temperature Range: (-45 to 170)°C ISO16750-3 (2012, 2023);
Temperature Transition Rate: 5°C/minute max EG812-22612 (2008);
Humidity Range: (20 to 95)% RH DC-10611 (2003, 2007);
IEC 60068-2.64 (2008);
MIL-STD-810G METHOD 514.6
Sound Testing using a Semi-Anechoic Chamber GMW14482 (2006, 2012, 2017);
Ambient Noise Level <28dB(A) FIAT PF.90010 (rev A, C) section 5.3.2;
Frequency Range of Microphones (20Hz to 20 kHz) DC-10879 (rev A, B) section 5.2.4;
Sampling Rate (48kHz) FIAT FCA PF90012 (2017), section 6.4.2;
Data Analysis Using HEAD Acoustics Artemis FIAT 9.93160/02 (2001), section 1.9 Noise;
Vibration Measurements (0-5G, 1-20kHz) GMW14478 (2015);
FORD 03.03-E-402 (rev 2007, 2015);
Renault/ Nissan RNDS-C-00366_2.0 (2018),
section 6.2;
ISO 3744 (2010);
ISO 11200 (2014, Amd 2018(E))
Chamber Testing
Water Tests ISO-20653 (2013-02);
IP2 EG812-22611 (2008)
IP7
IP8
IP9K
Ice Water Shock Test ISO 16750-4 (2010-4);
Icing/Freezing Rain MIL-STD-810G Method 521.3

Dust Tests SAE J-575: 4.5 (2015) Dust Exposure Test;


IP5K EG812-22611 (2008)
IP6K
Mechanical Shock
Waveform: Half-Sine, Triangular CETP-00.00-E-412 (2011);
Maximum g Level: Up to 800g CS-11982 (2013);
Duration: (1 to 30) ms Fiat 9.90110 (2014);
GMW3172; (2010, 2012, 2014, 2015, 2018,
2023);
IEC 60068-2-27 (2008);
EG812-22612 (2008);
ISO 16750-3 (2012, 2023)
Corrosion
Salt Fog1 ASTM B117; (2016, 2019);
Salt Mist1 ASTM D 1735; (2014);
Cyclic Corrosion1 ISO 9227; (2012, 2017);
JIS Z 2371 (2015);
GMW3172 (2010, 2012, 2014, 2015, 2018,
2023);
Ambient Temp: Up to 70˚C TP-0000808 (Rev. 04 and 05);

(A2LA Cert. No. 3305.01) Revised 10/21/2024 Page 2 of 3


Test Type/Capabilities Test Method(s)
Ambient: Up to 95% RH & Condensing IEC 60068-2-52 (2017);
CETP 00.-L-467-Ford; (2020);
SAE J2334 (2003,2016);
Ambient: Up to 95% RH & Condensing (continued) ESLX61-8C607-A2-CC (2015);
BI 123-03 (Cooling Fan) (2005);
EG812-22611 (2008);
GMW 14872 (2006, 2010, 2013,2018, 2021);
IEC 60068-2-11 (1981, 2021);
Nissan CCT-1 (2009-N);
Bosch-Norm N42AP 226 (2016);
Bosch 5360Z-TVA -A050-M1 (2017);
5360Z TVA A0 5 0 M1 (2017);
HES D 6501-06 (rev 3);
7664Z-S5A-000 (2000);
CETP.00.00-E-412 (2011)
Free Fall
Drop Range: Up to 1.1 Meters GMW3172; (2010, 2012, 2014, 2015, 2018,
2023); EG 812-22612 (2008)
1
Also using the above methods and customer supplied test methods directly related to the capabilities
listed above.

(A2LA Cert. No. 3305.01) Revised 10/21/2024 Page 3 of 3


Accredited Laboratory
A2LA has accredited

ROBERT BOSCH LLC


Plymouth, MI
for technical competence in the field of

Mechanical Testing
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017
General requirements for the competence of testing and calibration laboratories. This accreditation demonstrates
technical competence for a defined scope and the operation of a laboratory quality management system
(refer to joint ISO-ILAC-IAF Communiqué dated April 2017).

Presented this 14th day of February 2024.

_______________________
Mr. Trace McInturff, Vice President, Accreditation Services
For the Accreditation Council
Certificate Number 3305.01
Valid to November 30, 2025
Revised October 21, 2024

For the tests to which this accreditation applies, please refer to the laboratory’s Mechanical Scope of Accreditation.
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2017

ROBERT BOSCH LLC


Automotive Group Electromagnetic Compatibility
15000 Haggerty Rd.
Plymouth, MI 48170
Christopher Milhan Phone: 248-207-2979

ELECTRICAL (EMC)

Valid To: November 30, 2025 Certificate Number: 3305.02

In recognition of the successful completion of the A2LA evaluation process, accreditation is granted to
this laboratory to perform the following automotive electromagnetic compatibility tests:

Test Technology Test Method(s)

*Automotive Electrical Tests of the following types: GMW3172 (2010, 2012, 2014, 2015, 2018,
-Point Functional/Parametric Check 2023);
-Jump Start ISO 16750-2 (2010, 2012, 2023)
-Reverse Polarity
-Over Voltage
-Discrete Digital Input Threshold Voltage
-Crank Pulse Capability and Durability
-Power Supply Interruptions
-Battery Voltage Dropout
-State Change Waveform Characterization
-Ground Path Inductance Sensitivity
-Parasitic Current
-Sinusoidal Superimposed Voltage
-Pulse Superimposed Voltage
-Battery Line Transients
-Ground Offset
-Open Circuit – Single Line Interruption
-Open Circuit – Multiple Line Interruption
-Power Offset
-Over Load – All Circuits
-Over Load – Fuse Protected Circuits
-Multiple Power and Multiple Ground Short Circuits
Including Pass Through
-Intermittent Short Circuit to Battery and to Ground
-Switched Battery Lines
-Continuous Short Circuit to Battery and to Ground
for Input/Output
- AutoStart Voltage Transient
Electrostatic Discharge (ESD) ISO 10605 (2001, 2008, 2023)
Conducted Emissions CISPR 25 (2002, 2008), Sections 6.2 & 6.3;
CISPR 25 (2016, 2021), Sections 6.3 & 6.4

(A2LA Cert. No. 3305.02) 02/14/2024 Page 1 of 2


Test Technology Test Method(s)

Radiated Emissions CISPR 25 (2002, 2008) Section 6.4;


CISPR 25 (2016, 2021) Section 6.5
Bulk Current Injection (BCI) ISO 11452-4 (2005,2011, 2020)
Absorber Lined Shielded Enclosure (ALSE) ISO 11452-2 (2004, 2019)
(Substitution Method, Metallic Bench)
(Freq. 200 MHz-4.2 GHz, up to 600V/m)
Conducted Immunity (Transients) ISO-7637-2 (2011);
ISO-7637-3 (2007, 2016);
ISO-16750-2 (2010, 2012, 2023)
Voltage Transient Emissions Test ISO-7637-2 (2011), Section 4.3
Portable Transmitters ISO 11452-9 (2012, 2021)
Magnetic Field Immunity ISO 11452-8 (2015)
Steady Rate Ripple SAE J1113-2 (2004)
Horn Noise (Relay Chatter) SAE J1113-12 (2017,2022)
Insulation Resistance MIL-STD-202F-302
Dielectric Strength, AC MIL-STD-202F-301
Reverberation Mode Tuning ISO 11452-11 (2010);
200Mhz - 6 GHz IEC 61000-4-21 (2011)

*Using the above customer supplied test methods and specifications, directly related to the test
technologies and equipment parameters listed above.

(A2LA Cert. No. 3305.02) 02/14/2024 Page 2 of 2


Accredited Laboratory
A2LA has accredited

ROBERT BOSCH LLC


Plymouth, MI
for technical competence in the field of

Electrical Testing
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017
General requirements for the competence of testing and calibration laboratories. This accreditation demonstrates
technical competence for a defined scope and the operation of a laboratory quality management system
(refer to joint ISO-ILAC-IAF Communiqué dated April 2017).

Presented this 14th day of February 2024.

_______________________
Mr. Trace McInturff, Vice President, Accreditation Services
For the Accreditation Council
Certificate Number 3305.02
Valid to November 30, 2025

For the tests to which this accreditation applies, please refer to the laboratory’s Electrical Scope of Accreditation.
SCOPE OF ACCREDITATION TO ISO/IEC 17025:2017

ROBERT BOSCH LLC


Engineering Technical Center
15000 Haggerty Rd
Plymouth, MI 48170
Christopher Milhan Phone: 248-207-2979

MECHANICAL

Valid To: November 30, 2025 Certificate Number: 3305.03

In recognition of the successful completion of the A2LA evaluation process, accreditation is granted to
this laboratory to perform the following dimensional testing:

I. Dimensional Testing

Parameter Range Comments

Length 3D Up to (900 × 1300 × 700) mm CMM

Up to (900 × 1500 × 700) mm


Optical CMM
Up to (300 × 200 × 200) mm

FOV :
75 mm 3D Scanner
125 mm
250 mm
350 mm

Length 2D Up to (22 × 130) mm Profilometer

Up to (20 x 200) mm

Surface Finish Up to (22 × 130) mm Profilometer

Up to (20 x 200) mm

Surface Waviness Up to (22 × 130) mm Profilometer

Up to (20 x 200) mm

(A2LA Cert. No. 3305.01) 02/14/2024 Page 1 of 2


Parameter Range Comments

Length 1D Up to 600 mm Digital Height Gage

Up to 300 mm Digital Caliper

Up to 50 mm Digital Indicator

Up to 25 mm Digital Micrometer

(A2LA Cert. No. 3305.01) 02/14/2024 Page 2 of 2


Accredited Laboratory
A2LA has accredited

ROBERT BOSCH LLC


Plymouth, MI
for technical competence in the field of

Mechanical Testing
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017
General requirements for the competence of testing and calibration laboratories. This accreditation demonstrates
technical competence for a defined scope and the operation of a laboratory quality management system
(refer to joint ISO-ILAC-IAF Communiqué dated April 2017).

Presented this 14th day of February 2024.

_______________________
Mr. Trace McInturff, Vice President, Accreditation Services
For the Accreditation Council
Certificate Number 3305.03
Valid to November 30, 2025

For the tests to which this accreditation applies, please refer to the laboratory’s Mechanical Scope of Accreditation.
Accredited Laboratory
A2LA has accredited

ROBERT BOSCH LLC


Plymouth, MI
for technical competence in the field of

Mechanical Testing
This laboratory is accredited in accordance with the recognized International Standard ISO/IEC 17025:2017
General requirements for the competence of testing and calibration laboratories. This accreditation demonstrates
technical competence for a defined scope and the operation of a laboratory quality management system
(refer to joint ISO-ILAC-IAF Communiqué dated April 2017).

Presented this 14th day of February 2024.

_______________________
Mr. Trace McInturff, Vice President, Accreditation Services
For the Accreditation Council
Certificate Number 3305.03
Valid to November 30, 2025

For the tests to which this accreditation applies, please refer to the laboratory’s Mechanical Scope of Accreditation.
Building Technologies

Applied Illumination and Electronics Co., Ltd. Bosch


Sicherheitssysteme GmbH
2th Floor, Hoa Phat Giai Phong Building
Fritz-Schäffer-Straße 9
257 Giai Phong Road, Phuong Mai Ward 81737 München
Dong Da Dist. / Hanoi Germany
Vietnam www.boschsecurity.com

12 th February 2025

Product Test Report

Dear partners,

Product Name: AVIOTEC 8000i IR


Model Number: FCS-8000-VFD-I

This report presents the test results of the AVIOTEC 8000i IR (Model: FCS-8000-VFD-I), conducted
in accordance with VdS Guideline 3847 as part of the certification process. The tests were performed
to verify compliance with the required fire detection performance and environmental standards. Below
is a summary of the test results:

VdS 3847: Test


2019-07 (01) Specific Test Description passed
Cl. & Test Yes
The software contained in the VCD must comply with the
5.1.1 Software software requirements according to the guidelines VdS ☒
2203.
6.2 Fire sensitivity According to 6.2.2 with most unfavorable settings: ☒
6.3 Dependance of the 30 sec / robust (smoke detection mode) and 20 sec /
response behaviour on the robust (flame detection mode) ☒
inclination angle Camera viewing angle: max. opening angle of 103 degree
6.4 Reproducibility Fire alarm activation time: please refer to 6.2.2.3, Type 3 ☒
6.5 Repeatability Camera locations according to 6.3.2: minimum and ☒
maximum inclination angle of 0 and 40 degree
6.7 Glare (operational) ☒

Sitz: Stuttgart, Registergericht: Amtsgericht Stuttgart HRB 23118


Aufsichtsratsvorsitzender: Frank Meyer; Geschäftsführung: Thomas Quante, Peter Löffler, Henrik Siegle, Peter von Wartenberg
Die Bildmarke und die Wortmarke BOSCH sind registrierte Marken der Robert Bosch GmbH, Deutschland
Building Technologies

12th February 2025


Seite 2 von 4

6.8 Dry heat (operational)


Environmental class II:
- Tests Bb or Bd according ☒

Temperature 55 ± 2°C, duration: 16 hrs
to IEC 60068-2-2:2007
6.9 Cold (operational) -
Environmental class II:
Test Ab according to EN ☒
Temperature -10 ± 3°C, duration: 16 hrs
60068-2-1:2007
6.10 Damp heat, cyclic
Environmental class II:
(operational) - according
Lower Temperature 25 ± 2°C, relative Humidity ≥ 95%
to EN 60068-2-30:2005 ☒
Upper Temperature 40 ± 2°C, relative Humidity ≥ 93 ± 3%
applying the variant 2 test
Number of cycles: 2
cycle
6.11 Damp heat, steady
state (endurance) - Temperature 40 ± 2°C

according to test Cab EN Duration: 21 days
60068-2-78:2001
6.12 Sulphur dioxide (S02) Temperature 25 ± 2°C
corrosion (endurance) - Relative humidity: (93 ± 3) %

Test Kc according to EN SO2 concentration: (25 ± 5) μl/l
60068-2-42:2003 Duration: 21 days
For specimens with a mass ≤ 4,75 kg:
Shock pulse type: Half sine
Pulse duration: 6 ms
6.13 Shock (operational) -
Peak acceleration: 10 × (100 – 20 M) m/s2 (where M is the
Test Ea according to EN ☒
mass of the specimen in kg)
60068-2-27:2009
Number of directions: 6
Pulses per direction: 3
Do not test specimens with a mass > 4,75 kg.

Impact energy: 0,5 ± 0.04 J


Number of impacts per point: 3
The impacts shall be applied to all accessible surfaces of
6.14 Impact (operational) -
the specimen. Three blows shall be applied to each of
Test Ehb according to EN ☒
these surfaces at one or more points for which damage to
60068-2-75
or impairment of operation by the test Object is considered
possible.
Building Technologies

12th February 2025


Seite 3 von 4

Environmental class II
6.15 Vibration, sinusoidal Frequency range: (10 to 150) Hz
(operational) - Test FC Acceleration amplitude:

according to IEC 60068-2- 5 m/s2 (≈0,5 gn)
6:1995 Number of axes:3 / Sweep rate: 1 octave/min
Number of sweep cycles: 1/axis
Environmental class II:
6.16 Vibration, sinusoidal Frequency range: (10 to 150) Hz
(endurance) - Test Acceleration amplitude:

according to EN 60068-2- 10 m/s2 (≈1,0 gn)
6:2008 Number of axes:3 / Sweep rate: 1 octave/min
Number of sweep cycles: 20/axis
The specimen shall be connected to the supply and
6.17 Displacement of the monitoring equipment and focused
FOV (option with on a fixed image area. Then the alignment of the specimen ☒
requirements) is changed manually according to the manufacturer’s
specifications.
The specimen shall be connected to the supply and
monitoring equipment. Then the response behaviour of the
test specimen shall be measured at the upper and lower
6.18 Variation in supply limit

parameters (operational) values of the range of supply parameters (e.g. voltage)
specified by the manufacturer in
accordance with the test method described in section
6.1.3.
Using the devices and test methods the following EMC
immunity tests must be performed:
a) Mains supply voltage variations — if the VCD
6.19 Electromagnetic incorporates a mains supply;
compatibility (EMC), b) Mains supply voltage dips and short interruptions — if
immunity tests the VCD incorporates a mains supply;

(operational) according to c) Electrostatic discharge;
EN 50130-4:2011 + A1 d) Radiated electromagnetic fields;
:2014 e) Conducted disturbances induced by electromagnetic
fields;
f) Fast transient bursts;
g) Slow high-energy surge voltages.
Building Technologies

12th February 2025


Seite 4 von 4

Cl. 6.8, 6.9, 6.10, 6.13, 6.14, 6.15, 6.18, 6.19:


• Test Conditions: Tests were conducted under a 4-second response time setting.
• Notice: Highest sensitivity setting applied as no alarm and trouble condition is allowed for
these tests. Trouble only allowed for 6.13, 6.14 and 6.15 due to effect on the image.

For further specific test descriptions please refer to VdS-Guideline 3847:


https://shop.vds.de/download/vds-3847en

Bosch Sicherheitssysteme GmbH,


pki, BOSCH, DE, Digitally signed by pki,
BOSCH, DE, T, H,
Digitally signed by pki, BOSCH,
DE, M, I, Michael.Hirsch4 T, H, Thomas.Knauel
Date: 2025.04.03 10:00:20 Date: 2025.04.02 18:13:31
Thomas.Knauel +02'00'
________________________
+02'00'
_________________________
Hirsch Michael Knauel Thomas
VP Business Unit Fire Director Product Management
Fire Alarm Systems - FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67

FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67


AVIOTEC 8000i IR

u Starlight X technology for next level low-light


performance with maximum detail

u Powerful long range (850nm) smart IR


illumination up to 80 m

u Extremely robust and stable design with


exceptional corrosion resistance for any
outdoor application including traffic
monitoring, critical infrastructure and
perimeter security

u Covers large monitoring area

u Robust against false alarms

u Very fast and reliable fire and smoke detection

Video-based fire detection is the system of choice The cameras have a powerful, embedded processor
when reliable video motion fire detection is needed. with dedicated hardware to support advanced
It operates as stand-alone unit and does not need a machine learning and deep neural networks.
separate evaluation unit. Subject to the installation AVIOTEC 8000i IR allows easy configuration and
and operating conditions explained in the monitoring through network devices such as Client
documentation, it can, for example, supplement PCs or mobile devices. A video recording
traditional fire detection systems or provide means management system may be integrated optionally.
of fire detection where traditional fire detection Furthermore, there is a relay output to transmit
systems are technically limited. alarm signals, e.g. to the AVENAR panel. In this case
AVIOTEC 8000i IR can be used as primary fire the camera acts as supervisory signal-initiating
detection system when the application is not covered device. Alarms have to be verified by an operator in a
by any code of practice or other kind of standards or monitoring center owing to non-existing standards.
if the necessary approvals/releases have been Automatic alarm-forwarding to fire services is not
obtained for the intended applications in accordance provided.
with the applicable laws and other regulations.
The FCS-8000-VFD-I is an extremely robust bullet Functions
camera for mission-critical applications. The Fast and reliable flame and smoke detection
ruggedized and stable design has exceptional The smoke and flame algorithm analyzes video
corrosion resistance for use in any outdoor frames by means of characteristic spatio-temporal
application. patterns and variables. The core of the detection
Using 1/1.8" sensors with 4MP resolution, the algorithm is a Deep Learning Network which was
FCS-8000-VFD-I provides the perfect balance trained on a large-scale internal database, which is
between high resolution and extreme low light representative of the use cases of a Video-based Fire
sensitivity. Detection System. The fast detection algorithm is
Starlight X technology combined with powerful smart based on a real-time image processing on the camera
IR illumination ensure highly detailed images even in firmware.
the most challenging situations.
Fire Alarm Systems - FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67 2|7

The video-based fire detection works under The camera is capable of delivering high-quality and
remarkable low-light performance (down to 1 or 0 lx high-resolution video with low network load.
with the internal IR illumination) and detects test With a doubling of encoding efficiency, H.265 has
fires TF1 to TF8. In case of flame or smoke detection become the new compression standard of choice for
the video broadcast has the advantage to verify the IP video surveillance systems.
alarm, speed up the rescue chain and give insights to
Resists rain, dust, and tampering with reliable
rescue teams.
operation across a wide temperature range
Monitoring large areas Suitable for indoor and outdoor usage.
Insensitive to dust and humidity thanks to the optical The robust design of the camera is rated to IP66 /
principle, it is possible to monitor large indoor and IP67 and IK10 standards, safeguarding the camera
sheltered outdoor areas that push conventional against rain and dust while also offering protection
systems to their limits. AVIOTEC 8000i IR is the against vandalism and tampering.
innovative solution for: The camera can operate in a wide ambient
• Industry temperature range between -50 °C up to +60 °C.
• Transportation Easy installation
• Energy & Utilities The FCS-8000-VFD-I uses the proven 3-step
• Warehouses installation concept. The mounting plate has multiple
hole patterns for installation. The back box can be
Large application range
attached with a simple rotate and click. All wires can
The video-based fire detection is suitable for a range
be connected in the back box.
of challenging applications in harsh environments
Power can be supplied through Power-over-Ethernet.
with a high fire hazard like paper mills. Highly
With this configuration, only a single cable
versatile in application, AVIOTEC 8000i IR offers the
connection is required to view, power, and control
possibility to complement existing systems or to tap
the camera. Using PoE makes installation easier and
into new application fields.
more cost effective, as cameras do not require a
Individually adjustable and adaptable local power source.
Verification time, sensitivity, detection size and The design of the camera focuses on robustness and
selective masking for smoke and flame are stability. A patented optimized swivel design further
individually configurable to adjust them to the helps with the ease of installation.
customer needs. Flame and smoke detection can be The swivel has a big-ball joint for optimal stability.
activated or deactivated separately. When combined with electronic image stabilization,
this helps to ensure stable images in challenging
Root cause analysis
environments, such as traffic monitoring.
Connecting the camera to a video management
The camera features a short housing and a big
system offers the possibility to find out the cause of
swivel, to ensure maximum stability.
fires. Based on video recordings, incidents can
carefully be established and evaluated. This helps Advanced edge recording
eliminating and preventing hazardous situations in Advanced edge recording provides the storage
the future. solution possible due to the combination of the
following functionalities:
Starlight X - Next level starlight performance
Starlight X technology combines the latest high • Dual microSD cards that can be set up as either:
performance, large pixel sensors, optics, improved – Mirrored, for redundant storage
image processing and noise suppression, resulting in – Failover, for extended service intervals
a 5.5x improved sensitivity compared to the standard
starlight camera. – Extended, for maximum retention time
• Industrial microSD card support allows for
IR illumination extreme lifetime
The camera offers integrated advanced intelligent IR
• Health monitoring of industrial microSD cards
illumination. The IR range covers a distance of up to
provide early service indications
80 m (262 ft).
The combination of multiple IR beam angles, linked Cloud-based services
to the zoom position of the lens, ensure uniform The camera supports time-based or alarm-based
illumination of the full scene, without hot spots or JPEG posting to four different accounts. These
dark corners in any field of view. Intelligent IR accounts can address FTP servers or cloud-based
ensures a balanced image without over exposure on storage. Video clips or JPEG images can also be
objects closer to the camera. exported to these accounts.
Alarms can be set up to trigger an e-mail or SMS
H.265 high-efficiency video encoding
notification so you are always aware of abnormal
The camera is designed on the most efficient and
events.
powerful H.264 and H.265/HEVC encoding platform.
Fire Alarm Systems - FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67 3|7

Regulatory information Type Standard

Type Standard IEC 62368-3


EN IEC 62368-3
Emission EN 55032 (Class B)
IEC 62471
EN 50121-4
EN 62471
EN IEC 61000-6-3
EN IEC 61000-6-4 Impact protection EN 62262 (IK10)
CFR 47 FCC part 15 (Class B)
Ingress protection EN 60529 (IP66/IP67)
ICES-003 Issue 7
NEMA 250 (4X)
Immunity EN 55035
ISO 20653 IP6K9K
EN 50130-4
EN 50121-4 Marks CE, cULus, RCM, WEEE, VCCI, CMIM, UKCA
EN IEC 61000-6-1
Compliance NDAA compliant
EN IEC 61000-6-2
EN 61000-4-2
Region Regulatory compliance/quality marks
EN 61000-4-3
Europe CE FCS-8000-VFD-I
EN 61000-4-4
EN 61000-4-5 Morocco CMIM FCS-8000-VFD-I
EN 61000-4-6
EN 61000-4-8 Installation/configuration notes

Environmental EN 50130-5 (Class IV) IMPORTANT: Video fire indication systems are video
content analysis systems. They give indications for
EN 60068-2-2 possible fires and are designed to supplement fire
EN 60068-2-5 detection systems and human guards in monitoring
EN 60068-2-6 centers in order to recognize possible dangerous
situations.
EN 60068-2-18
Video fire indication systems are confronted with a
EN 60068-2-27 higher amount of challenges considering scenery and
EN 60068-2-30 background compared to conventional fire detection
systems. They cannot ensure that fire will be
EN 60068-2-42
detected reliably in all scenery settings. Thus, the
EN 60068-2-52 video fire detection system shall be seen as a
EN 60068-2-75 support system that enhances the probability of early
fire detection, with the restriction that it shall not be
EN 60068-2-78
seen as a system that ensures fire detection in all
TS 2-2003, Section 2 (Environmental require- possible image scenarios and it might detect false
ments) alarms. Conventional fire alarm systems must in no
EN IEC 63000 (RoHS) way be replaced by video-based fire alarm systems.
California Proposition 65
In addition, and for the U.S. market only, Bosch
Security Systems makes no representation that the
Corrosion resistance ISO 14993
video fire indication system will prevent any personal
injury or property loss by fire or otherwise; or that
Safety IEC 62368-1
such product will in all cases provide adequate
EN 62368-1 warning or protection. Buyer understands that a
UL 62368-1 properly installed and maintained fire indication
system may only reduce the risk of a fire or other
CSA C22.2 No. 62368-1
events occurring without providing an alarm, but it is
IEC 60950-22 not insurance or a guarantee that such will not occur
EN 60950-22 or that there will be no personal injury or property
UL 60950-22 loss as a result.

CSA C22.2 No. 60950-22


Fire Alarm Systems - FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67 4|7

Consequently, Bosch Security Systems shall have Quantity Component


no liability for any personal injury, property
damage or other loss based on a claim the product 1 TR20 key
failed to give warning.
1 Mini screwdriver

1 Grommet (IP66)

1 Grommet (IP67)

1 Quick installation guide

3 Installer UX labels

Technical specifications

Electrical

Algorithm Overview

Dimensions in mm (inch) Min. detection size for Smoke, standard setting 1.6
(% of picture width)

Smoke speed 0.5 - 16


(% of picture height/s)

Smoke speed 0%-30%


(% of picture width/s)

Min. Smoke density (%) needs to be visible


α
dmax
in the picture
W
W
Min. detection size for Flame, standard setting 1.1
(% of picture width)
W
Min. illumination level (lx) 1
α
100º 90º 60º 48.5º Min. illumination level with IR illumination (lx) 0
W dmax

0.3m 11.4m 13.6m 23.6m 30.2m Max. illumination level for flame detection (lx) 20,000
0.5m 19.0m 22.7m 39.3m 50.4m

0.75m 28.6m 34.0m 59.0m 75.6m

1m 38.1m 45.4m 78.7m 100.9m


PoE input PoE IEEE 802.3af / 802.3at Type 1,
1.25m 47.6m 56.8m 98.4m 126.1m
Class 3;
1.5m 57.2m 68.1m 118.0m 151.3m PoE and auxiliary power can be con-
α nected simultaneously for redundant
100º 90º 60º 48.5º operation
W dmax

0.3m 7.8m 9.3m 16.2m 20.8m Input voltage (VAC) 24 VAC ±10%
0.5m 13.1m 15.6m 27.0m 34.6m

0.75m 19.6m 23.4m 40.5m 52.0m Input voltage (VDC) 12 VDC – 26 VDC ±10%
1m 26.2m 31.2m 54.1m 69.3m

1.25m 32.7m 39.0m 67.6m 86.7m Power consumption PoE (W) (typ- 7 W – 12.95 W
1.5m 39.3m 46.8m 81.1m 104.0m ical – maximum)

For further information refer to user manual and Power consumption VAC (W) (typ- 7.10 W – 13 W
planning manual on: https://www.boschsecurity.com ical – maximum)

Parts included Power consumption VDC (W) (typ- 7.50 W – 16 W


ical – maximum)
Quantity Component

1 FCS-8000-VFD-I
Fire Alarm Systems - FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67 5|7

Sensor Sensor modes 60 fps, 2688 x 1520 (4.1 MP)

Sensor type 1/1.8 inch CMOS Streaming 4 configurable streams in H.265;


H.264 and M-JPEG; Configurable
Effective pixels (H x V px) 2688 x 1520;
framerate and bandwidth; Bosch In-
2.9 μm
telligent Streaming (available with fu-
ture firmware update)
Total sensor pixels 4.10 MP approx.
Camera processing latency <67ms (60 fps)
Sensitivity
GOP structure IP; IBP; IBBP
Low light technology starlight X
Frame rate (fps) 1 fps – 60 fps
Sensitivity 30 IRE
Video signal-to-noise ratio (dB) >55 dB
Color (lx) (sensitivity measured ac- 0.0078 lx
cording to IEC 62676 Part 5) Video Resolution 4.1 MP 2688 x 1520;
Monochrome (lx) (sensitivity meas- 0.0011 lx (0 with IR) HD 1080p 1920 x 1080;
ured according to IEC 62676 Part 5) 1.3 MP 1536 x 864;
HD 720p 1280 x 720;
High Dynamic Range (HDR) (dB) 141 dB SD 432p 768 x 432;
0.1 MP 512x288
Optical
Camera installation
Lens focal length (mm) 4.70 mm – 10 mm
Mirror image On; Off
Iris control P-iris
Image rotation 0°, 180°
IR corrected Yes
Camera LED Auto disable; Enable; Disable
Lens aperture (/F) F/1.35 - F/1.97
Video functions
Zoom/focus control Motorized
ALC mode Standard; Fluorescent
Field of View wide (H x V) 103° x 53°
Shutter modes Automatic Electronic Shutter (AES)
Field of View tele (H x V) 48° x 27°
Day/night modes Auto
Night vision
White balance (K) 2,000 K – 10,000 K
IR function On; Off; Auto; Intelligent IR
White balance modes Basic; Standard; Sodium vapor;
LED Exchangeable illumination modules: Manual mode; Hold mode; 3 auto-
850 nm (default); matic modes

Distance 850 nm IR (default) 80 m | 262 ft Number of privacy masks 8

Illumination intensity Manually adjustable; Intelligent in- Display stamping Name; Logo; Alarm message; Time
tensity
Storage
Firmware
Internal storage 5-s-pre-alarm-recording
Common Product Platform CPP14
Memory card slot Dual micro SDHC; Dual micro SDXC;
Video streaming Dual micro SD card up to 2 TB

Video compression H.264 (ISO/IEC 14496-10); M- Industrial SD cards Extreme lifetime and health monitor-
JPEG; H.265/HEVC ing support that provides early ser-
vice indication
Fire Alarm Systems - FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67 6|7

Dual SD-card slot configurations Mirror (redundant storage); Failover no-ip.com); SMTP; iSCSI; UPnP
(extended service interval); Extend (SSDP); DiffServ (QoS); LLDP;
(maximum retention time); Auto- SOAP; CHAP; Digest authentication
matic Network Replenishment
Ethernet type 10/100BASE-T
Inputs and outputs
Conformity ONVIF Profile S; ONVIF Profile G;
Ethernet Shielded RJ45; ONVIF Profile T; ONVIF Profile M
Punch down connector
Data security
Audio line in 10 kOhm typical; max. 1 Vrms
Crypto coprocessor (TPM) RSA 4096 bit; AES/CBC 256 bit
Audio line out 1.5 kOhm typical; 1 Vrms
PKI X.509 certificates
Alarm inputs 2;
Dry contact; End-to-end encryption Full end-to-end with supported VMS
5 - 40 VDC;
2.2 K end-of-line resistor Encryption TLS 1.2; TLS 1.0; TLS 1.1; AES
256; AES 128; TLS 1.3
Alarm outputs 2
max 30 VAC; Local storage encryption XTS-AES
+40 VDC;
0.5 A; Video authentication MD5; SHA-1; SHA-256; Checksum
continuous 10 VA
Firmware protection Signed firmware; Secure boot
Power output 12 VDC, max 50mA
Mechanical
Surge protection 1 kV; 1 kA to ground (8/20 μs)
Material Housing: Aluminum with dehumidify-
USB USB 2.0 Type C, for use with wire- ing membrane and waterproof con-
less USB dongle for setup and com- nection area
missioning (sold separately)
Dimensions (Ø x H) (mm) 148 mm x 115 mm
Fiber optics (sold separately) The Fiber Optic Ethernet Media Con-
verter kit (VG4-SFPSCKT) installed Weight (kg) 2.95 kg
inside a Surveillance Cabinet
(NBA-7070-PA0, NBA-7070-PA1 or Color in RAL RAL 9003 Signal white
NBA-7070-PA2) provides the fiber
optic interface to the mounted cam- Mounting type Surface-mounted
era
Environmental
Audio
Operating temperature (°C) -40 °C – 60 °C PoE;
Compression and sampling rate AAC-LC 48kbps 16 kHz -50 ºC — 60 ºC 12 VDC/24VAC;
Up to 74 ºC according to NEMA TS
Minimum signal-to-noise ratio (dB) >50 dB 2-2003 (R2008), para 2.1.5.1 us-
ing fig. 2.1 test profile
Audio streaming Full duplex; Half duplex
Storage temperature (°C) -40 °C – 70 °C
Network
Cold start temperature (°C) -40 °C
Protocols / standards IPv4; IPv6; UDP; TCP; HTTP; HTTPS;
RTP/RTCP; IGMP V2/V3; ICMP; Operating relative humidity, non- 5% – 93%
ICMPv6; RTSP; FTP; ARP; DHCP; condensing (%)
APIPA (Auto-IP, link local address);
Operating relative humidity, con- 5% – 100%
NTP (SNTP); SNMP (V1, MIBII);
densing (%)
SNMP (V3, MIBII); DNS; DNSv6;
DDNS (DynDNS.org, selfHOST.de, Storage relative humidity (%) 0% – 98%
Fire Alarm Systems - FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67 7|7

Impact protection IK10

IP rating IP66; IP67; IP6K9K

Degree of protection NEMA type 4X

Ordering information

FCS-8000-VFD-I AI-VFD Bullet 4MP 4.4-10mm IP67


Very fast and reliable identification of smoke and
flames by video-based fire detection.
Bullet,4MP,4.4-10mm
Order number FCS-8000-VFD-I | F.01U.406.348

Accessories
NDA-U-PMAL Pole mount adapter large
Universal pole mount adapter, white; large
Order number NDA-U-PMAL | F.01U.324.944
MSD-064G IP SECURITY MICROSD CARD 64GB
64 GB industrial microSD card with health status
monitoring
Order number MSD-064G | F.01U.394.680
MSD-128G IP SECURITY MICROSD CARD 128GB
128 GB industrial microSD card with health status
monitoring
Order number MSD-128G | F.01U.394.681
MSD-256G IP SECURITY MICROSD CARD 256GB
256 GB industrial microSD card with health status
monitoring
Order number MSD-256G | F.01U.394.682
NCA-U-PIG Push-in grommet IP66 patch comp. 25pcs
Push-in grommet IP66 patch comp. 25pcs
Order number NCA-U-PIG | F.01U.411.437
NCA-U-PIGS Push-in grommet IP67 4.5-7.5mm 25pcs
Push-in grommet IP67, 4.5-7.5mm, 25pcs
Order number NCA-U-PIGS | F.01U.411.438
NCA-U-PIGL Push-in grommet IP67 7.5-10mm 25pcs
Push-in grommet IP67, 7.5-10m, 25pcs
Order number NCA-U-PIGL | F.01U.411.568

Represented by:

Europe, Middle East, Africa: Germany: North America: Asia-Pacific:


Bosch Security Systems B.V. Bosch Sicherheitssysteme GmbH Bosch Security Systems, LLC Robert Bosch (SEA) Pte Ltd, Security Systems
P.O. Box 80002 Robert-Bosch-Ring 5 130 Perinton Parkway 11 Bishan Street 21
5600 JB Eindhoven, The Netherlands 85630 Grasbrunn Fairport, New York, 14450, USA Singapore 573943
Phone: + 31 40 2577 284 Tel.: +49 (0)89 6290 0 Phone: +1 800 289 0096 Phone: +65 6571 2808
www.boschsecurity.com/xc/en/contact/ Fax:+49 (0)89 6290 1020 Fax: +1 585 223 9180 Fax: +65 6571 2699
www.boschsecurity.com [email protected] [email protected] www.boschsecurity.com/xc/en/contact/
www.boschsecurity.com www.boschsecurity.com www.boschsecurity.com

Data subject to change without notice | 202310170957 | V3 | October 17, 2023 © Bosch Security Systems 2023
CERTIFICATE OF QUALITY
CONTRACT No. 01.AVIOTEC/2025/AICE-BOSCH/VS
Date 29 April 2025
Invoice Number: 3390045842

This is hereby to certify that the following BOSCH branded products manufactured by Bosch Manufacturer Plant have
passed the Quality Control and tested according to the relevant internationally recognized standards and manufacturer’s
Quality Standards of Manufacturer Plant. As such, their Quality is certified for conformity and satisfaction of the
customer.

Commercial Type
No. SAP Description Unit Quantity Origin
No.
1 F.01U.406.348 FCS-8000-VFD-I Bullet 4MP 4.4-10mm IP67 pcs 58 Portugal

Certified True & Correct

Leonard Hew
Head of Sales & Marketing, Asia Pacific
Business Unit Fire Safety, Building Technologies,
Robert Bosch (SEA) Pte Ltd

Rickmond Tong
Controller
Robert Bosch (SEA) Pte Ltd
Building Technologies

To: SAIGONCOMM Corporation Robert Bosch (South East


Asia) Pte. Ltd.
11 Bishan Street 21
Singapore 573943
Tel +65 6258 5511
Fax +65 6258 4671
www.bosch.com.sg

LEE CHI HOU, BT-FS/SAL2-AP2 14th February 2025


Tel +60 3 7966 3000
[email protected]

CONFIRMATION LETTER – Supply of Bosch brand Camera Equipment

First and foremost, BUILDING TECHNOLOGIES of ROBERT BOSCH (SOUTH


EAST ASIA) PTE. LTD. would like to extend our sincere appreciation for your
continued trust and partnership over the years.

To improve service quality, ensure transparency in our distribution system, and


better support customers during the purchasing process, all transactions
involving the purchase of our products will be conducted through our officially
authorized distribution agents.

Our officially authorized distributor in Vietnam is:


Distributor Name: Applied Illumination and Electronics Co., Ltd
Address: 2Fl - Hoa Phat Giai Phong Building 257 Giai Phong
Road, Phương Mai Ward, Dong Da Dist, Hanoi, Vietnam
Tax Code: 0100943819
Phone: (024) 37344174
Email: [email protected]
Representative: Mr. PHAM THANH BINH – Director

By this letter, Building Technologies of Robert Bosch (South East Asia) Pte
Ltd, headquartered in Singapore, hereby confirms that Applied Illumination
and Electronics Co., Ltd. will be the entity responsible for importing the goods
and delivering them to Saigoncomm Corporation.

The shipment includes 58 units of Infrared Bullet Cameras with IP67 rating,
4MP resolution, and 4.4–10mm focal length (Model: FCS-8000-VFD-I),
along with all relevant supporting documents, including:

Company Registration No. 195800026C


BOSCH and the symbol are registered trademarks of Robert Bosch GmbH, Germany
Building Technologies

• Certificate confirming that Applied Illumination and Electronics Co., Ltd. 14th February 2025
Page 2 of 2
is an authorized distributor of Bosch in Vietnam.
• Goods delivery and receipt report.
• Certificate of Origin (CO) and Certificate of Quantity/Quality (CQ).
• Technical documentation of the product.
• VDS 3487 certificate for Camera FCS-8000-VFD-I.
• Valid ISO 17025 international laboratory accreditation certificate.
• Product test report equivalent to or exceeding VDS 3487 standards.

The responsibility for conducting fire prevention and fighting (PCCC)


inspections in accordance with the applicable laws of the host country lies with
Saigoncomm Corporation. Applied Illumination and Electronics Co., Ltd.
is responsible for providing all necessary documentation, as agreed, to support
Saigoncomm Joint Stock Company in the inspection process.

Note: Building Technologies of Robert Bosch (South East Asia) Pte Ltd,
headquartered in Singapore, shall not be held liable for any purchase
transactions conducted outside of the authorized distributor network.

We kindly ask for your understanding and cooperation to ensure that all
transactions proceed smoothly and effectively.

Thank You.

Yours sincerely,

LEE CHI HOU LEONARD HEW


Sales Manager, SEA Head of Sales & Marketing, AP
BU Fire Safety BU Fire Safety
Robert Bosch Sdn Bhd Robert Bosch (SEA) Pte. Ltd.
Certificate
Bosch Building Technologies hereby acknowledges

APPLIED ILLUMINATION & ELECTRONICS CO., LTD.


as a partner of Bosch Life Safety Systems

2025
Your expertise and dedication to quality and service along with your
commitment to training entitle you to this prestigious distinction.

Leonard Hew Rickmond Tong


Head of Sales & Marketing Controller
BU Fire Safety