CKT LOAD DESCRIPTION QTY. VA per Total VOLTS Load CB/FUSE SIZE OF Conduit
Outlet VA Current RATING WIRE Size
Convenience outlet Sw1 - Swicth 1gang fuse/ circuit Department of Public Works and Highways
breaker OFFICE OF THE BUILDING OFFICIAL
1 Lighting Outlet 1 100 100 230 0.43 A 15 AT 2.0mm² PDX
PB Mlang, Cotabato
Wire Light Oulet Panel board Area Code:12037
2 Convenience Outlet 1 200 200 230 0.86 A 20 AT 3.5 mm² PDX Circiut
Wire Homerun
Total 2 300 300 230 1.29 A 20 AT 2-8.0mm ²25mm Service Permit Issued:
Rsc Pipe Entrance
M KWH Meter Ground
LEGEND AMANDO R. JAROMAY, CE.
BUILDING OFFICIAL
Use 2-8.0 TW Cu. wire COMPUTATION
Single Rack W/ Spool
1. Total load
inside the 25mm RSC Pipe
Entrance Cap 3/4 COTELCO Line (a)General Lighting Load: GENERAL NOTES AND SPECIFICATIONS:
Use SDW #6 16sq. M . x 240 VA/Sq.=420 VA
Straigth
Connector3/4 M KwH Total Computed Current:
1(100) VA/230V= 0.43 A
ALL ELECTRICAL WORKS SHALL BE COMPLIED WITH THE
PROVISION OF THE LATEST APPROVED LIST APPROVED
Rsc Clamp 3/4 EDITION OF THE PHILIPPINE ELECTRICAL CODE WITH
Use 2-8.0 TW Cu. wire (b)Small Appliances Load:
One 20-amperes @ 200VA THE RULES AND REGULATIONS OF THE NATIONAL
RSC Pipe 3/4 inside the 25mm RSC Pipe
Single Enclosure Total Computed Appliances Load: BUILDING CODE AND LOCAL AUTHORITY CONCERNED
wire drip loop 6 inches Panel Board IN THE REINFORCEMENT OF ELECTRICAL LAWS AND
200 VA/230V= 0.86 A
RSC Nipple 3/4 2.Number of Branch Circuit Required: WITH THE RULES AND REGULATION OF THE
TW 8.0mm2
color coding one black ON ON
One 15-amperes 2-wires branch circuit for lighting. One DISTRIBUTION UTILITY CONCERNED.
Circiut Breaker & one white 20-amperes 2- wires branch circuit for convenience outlet.
OFF OFF
THE SERVICE VOLTAGE ENTRY FROM THE DISTRIBUTION
3. Service Entrance Conductor UTILITY SHALL BE 230 VOLTS (NOMINAL)
2.90m
15AT 20AT
Total Full Load
420 VA +1,500 VA=1,920 VA ELECTRICAL WIRING INSTALLATION SHALL BE DONE IN
Application of Demand Factor.
1.80m
zpu=(z/kv2)(kva/1000)=0.023596/0.230)(10/1000)
zpu=0.0111 GROUNDED IN ACCORDANCE WITH THE LATEST
FOR FAULT AT F1:
Isc=(1/0.0008)+0.0111)x10*1000/240)
EDITION OF PHILIPPINE ELECTRICAL CODE.
Isc= 4.314 Kaic
Use 5 Kaic for 30AT main breaker & other protection. THE CONTRACTOR SHALL VERIFY AND ORIENT THE
ACTUAL LOCATION OF SERVICE ENTRANCE FOR
VOLTAGE DROP CALCULATION CONNECTION TO THE. POWER SUPPLY.
RODENCAR HARDWARE 2-THW WIRE,8.0MM2,100m;
ჲ
R=0.00056 /m X100m----from hanbook ALL ELECTRICAL WORKS AND INSTALLATION SHOULD BE
MLANG CROSSING DUGONG BAGONTAPAY R=0.00021ჲ/m X100m----from hanbook DONE UNDER THE DIRECT SUPERVISION OF AN
z=0.0231ჲ ELECTRICAL PRACTITIONER (REGISTERED MASTER
VOLTAGE DROP(VD)=IZ
VD=13.32(0.231) VD=0.3 V ELECTRICIANS UP TO 600 VOLTS ONLY)
PERCENT VOLTAGE DROP
POWER & LIGHTING LAYOUT VICINITY MAP (%VD)= IZ
Scale 1:100 VOLTAGE SUPPLY x100
%VD= 0.3
230 x 100
%VD= 0.1% PDC ALLOWS OF 10% DROP VOLTAGE