Super Yc Series 4.25
Super Yc Series 4.25
SUPER YC SERIES
Carrier VRF 2024
Cat-V.01
The specifications, designs, and information in this brochure are subject to change without notice
All Digitalized Service
BIM building
information import Installation service
R410A
Degradation of energy
efficiency 25%
MCFD
Energy consumption and Ensures timely supply
airflow simulation optimization of global after-
sales spare parts.
01 02
Outdoor Unit Functions
Functions
Super Y-C
: equipped as standard; O: customization option; X: without this function
OUTDOOR UNITS
Original communication bus chip greatly simplifies installation
SmartLink and saves installation cost
IP55 Fully sealed electric control box realizes resisting all factors
Sealed Box that cause intrusion and damage to the electric control box
Innovative Technologies
SuperSense pipeline can be known in the whole process
Super YC (Combinable series) Ceta 2.0 Triple variable control to maximize the comfort and energy
efficiency
The Super YC Series VRF uses a variety of algorithms and self-learning technology to monitor the
CHAE 2.0 Provides comfort and healthy air supply
operation of the equipment through operating parameters and timely maintenance, so that the equipment
always runs in optimal condition throughout its life cycle.
Outdoor Unit Lineup All electrical components of outdoor and indoor units are DC
Full DC inverter technology power supply, improving electrical efficiency and achieving energy
saving
Super YC (Combinable series)
HP 8-20 22-30 Enhanced Vapor Injection Increases refrigerant circulation and improves both cooling
capacity
(EVI) compressor
High Efficiency
Micro-channel refrigerant which can further improve the refrigerant heat transfer efficiency
Single
subcooling while reducing the sound
Unit
HP 32-60 62-90
60-step energy manage- The system can be set 40% to 100% capacity output in 1%
ment increments
03 04
Functions Functions
Super YC Super YC
: equipped as standard; O: customization option; X: without this function : equipped as standard; O: customization option; X: without this function
If one unit fails, the other units provide backup so that the system Automatic refrigerant
Backup operation (unit)
can continue operating (available for combined unit) Makes installation and service easier and more efficient ○
charging
Backup operation (fan If one fan motor fails, the other fan motor provide backup so that
It can be used for fault information storage, operation parameter
motor) the system can continue operating (available for unit with two fan
enquiry, system parameter setting, quick after-sales PCB replace-
motors) Bluetooth module ment, indoor and outdoor units programme upgrade, etc., ○
simplifying installation and maintenance.
If one sensor fails, the virtual sensor provide backup so that the
Backup operation (sensor) system can continue operating
4 digit 7-segment display can be intuitive for parameter setting,
Digit display parameter check and error check
High Reliability
High external static Up to 120Pa ESP allows easy handling in a variety of installation 0-20Pa
Can be customized with heavy anti-corrosion treatment for surface
Heavy anti-corrosion pressure environments 20-120Pa ○
protection against corrosive air, acid rain and saline air (for ○
protection installations in coastal regions) to extend overall useful life
It has been certified by UL that our VRF outdoor unit can withstand Arbitrary topology of Supports any communication topology, greatly simplifies
installation and reduces installation cost
UL anti-corrosion certificate 27 years of simulated severe corrosion under a salt contaminated ○ communication wire
traffic environment
2-core non-polarity
Micro-channel refrigerant communication wiring
10 times higher than ordinary refrigerant pipe cooling efficiency Simplifies installation and reduces wiring failures
cooling PCB between the indoor and
outdoor units
Blows away accumulated dust on the outdoor unit, guaranteeing
Auto dust-clean function the unit operating stable in dusty environment
Long communication Communication wiring up to 2000m makes installation more
15-step silent mode selections provide more freedom and Supports manual and
Silent mode automatic defrosting Improves maintenance efficiency
convenience to match the customer needs
Wide Application Range & Enhanced Comfort
Wide operation range Operates stably under extreme conditions -15~55°C (C) Flexible controller Central controller and BMS gateway can connect to ODU at the
connection same time, central controller can connect to ODU or IDU
Easy system commissioning System commissioning and checking can easily be done on-site
Auto addressing Distributes addresses to slave outdoor units automatically, or remotely via the web
and checking*
(ODU~ODU) further simplifying the installation (available for combined unit)
Intelligent maintenance Intelligent bluetooth after-sales kit can simplify maintenance and
○
tool improve maintenance efficiency
Note:
*: The web function needs to be realized through the data cloud gateway, and the data cloud gateway needs to be purchased separately.
05 06
INNOVATIVE
TECHNOLOGIES
Anti-corrosion Rain & snow proof Dustproof Insect proof
Benefits
Flexible installation
High reliability
IP (INGRESS PROTECTION)
Dustproof grade code
SmartLink communication technology supports any wiring pattern rather than just daisy chain connection, reducing Fully enclosed electronic components are isolated from the external environment to protect against corrosion, sand,
the installation cost and the possibility of incorrect connection. It has stronger anti-interference ability, achieving humidity, snowstorm and other harsh conditions, and prevent small animals and insects from entering the chamber.
communication distance up to 2000m. To provide comprehensive protection for internal electronic devices, improve the overall environmental tolerance.
*In ring connection, the communication wire must be connected polarized (M1 port to M1 port and M2 port to M2 port).
60
5 high precision temperature sensors are used to accurately monitor
40
the operation state of electronic control under various conditions to 20
ensure that the internal temperature of the chamber is always kept 0
within a stable range. -20
Conventional filtering Distorted waveform -40
waveform reduction Anti-interference Anti-interference Anti-interference -60 Time
of radio of high voltage of equipment
LN LN LN
11 12
Cooling Mode Cooling Mode
Benefits
High reliability
Stable operation
Enhanced comfort
NORMAL
7 fan speeds
AMOUNT
STEP 3: Adaptive indoor airflow and
refrigerant flow
Each indoor unit automatically adjusts the
! Variable corresponding indoor airflow and refrigerant
Indoor flow according to the evaporating/condensing
temperature, enabling precise temperature Automatic matching of the corresponding indoor airflow to the
INSUFFICIENT REFRIGERANT
Airflow control. load and refrigerant temperature.
*This function is available at the end of July 2022.
Compressor Compressor
output output
Indoor Indoor
temperature temperature
Failure of a Real-time
physical generation of Setting Setting
sensor virtual sensor temperature temperature
Time (min) Time (min)
13 14
Sleep mode Soft wind mode
Benefits
Quiet
Enhanced comfort
Healthy
Benefits Easy maintenance Fast maintenance Low maintenance cost
30°C
Real-time Monitoring of Operating Parameters Cloud-based Big Data Analytics
The Super YC Series VRF synchronizes and stores all the unit Super YC Series VRF transmits the system operation data to the
Automatically setting Automatically setting
temp. 27°C 10°C temp. 24°C parameters to the cloud through the data cloud gateway, including cloud in real time through the data cloud gateway, and timely
the running status, locking status, dirty blocking rate, all spot reminds the system of abnormal conditions through big data
*Temperature on left is for reference.
inspection parameters and so on. Users can query real-time and analysis, helping users to proactively avoid the risk of failure that
Long Distance Air Delivery* Innovative Puro-air Kit historical parameters on computers, tablets and mobile phones at has not yet occurred and minimize hidden problems.
The Four-way Cassette has an additional 50Pa static pressure for Protectors of health and safety any time.
long airflow delivery and is capable of being used in spaces up to
4.5m in floor height. From Germany -
OSRAM
OSRAM quality UV light source
Ozone –Free
Cooling UV leakage-Free
4.5m *The indoor unit needs to be customized in order to use the Puro-air Kit.
*This function is available as a customization option. *The data cloud gateway is still under development and needs to be purchased separately.
15 16
High Efficiency
Full DC Inverter for Outdoor Components The enhanced vapor injection DC inverter compressor increases refrigerant circulation and improves both cooling
capacity.
The Super YC Series VRF uses full DC inverter compressor and fan motor to achieve high precision stepless speed
adjustment according to system operation, and ensures that the system is always in optimum condition, operating
more efficiently, more consistently and with less noise.
Efficiency (%)
100 45%
DC
80
60 AC Wider frequency
40 adjustment range
20
800
600
400
200 Higher energy
EEV
System pressure efficiency
All power devices such as indoor fan motor, drain pump and electric control board are fully DC, which increases
electrical efficiency by 20% and results in more accurate temperature control, a more constant indoor temperature 2nd stage
Subcooling 3~5oC
3.5W
40% 100%
Uneven temperature Uniform temperature 40
distribution distribution
1000 2000 3000 4000 5000 6000 Traditional Super Y-C
17 Speed (RPM) VRF 18
High Reliability
In two fans, two compressors and multiple units, one can run in backup for another. Additionally, the Super YC 1 Unit Duty Cycling 2 Compressor Duty Cycling
series VRF generates a corresponding virtual sensor for each physical sensor by means of a digital algorithm, which
serves as a backup for each other, ensuring no shutdown in the event of a fault, and further guaranteeing comfort. In a multi-unit system, duty cycling equalizes the In units with two compressors, duty cycling equalizes
running time of each outdoor unit, significantly the running time of each compressor, significantly
1 Unit Backup 2 Fan Backup extending unit lifespan. extending compressor lifespan.
In a multi-unit system, the different units act as a In unit with two fans, the two fans act as a backup to
backup to each other, ensuring that the system can
continue to operate if one unit fails.
each other, ensuring that the system can continue to
operate if one fan fails.
1 2 3 1st cycle
1st cycle
1 2
3 1
Operation compressor
Failed compressor
2 2nd cycle
Note: The duty cycling sequence shown in the figure is only a Compressor start-up sequence
Operation fan schematic reference. The actual duty cycling sequence is not a fixed
Failed fan sequence. Please refer to the technical manual for specific rotation
rules.
Sealed Box
IP55 fully enclosed electric control box provides all-round protection for internal electronic components, greatly
Continue operating in case of failure of one unit Automatic backup operation of another fan in improving system reliability.
case of failure of one fan
19 20
Comprehensive Sensor UL Anti-Corrosion Certificate*
Super YC Series VRF uses up to 19 sensors for each outdoor unit and 4 sensors for each indoor unit. The operating It has been certified by UL that our VRF outdoor unit can withstand 27 years of simulated severe corrosion under a
status of the system refrigerant is clearly visible, which can realize intelligent analysis of operation parameters, salt contaminated traffic environment.
intelligent error diagnosis and forecasting, and visualized energy saving. *UL anti-corrosion certificate is available for heavy anti-corrosion treatment units.
The innovatively designed dust-clean function enables the outdoor unit to prevent the dust by itself.
Four stages of oil control technology ensure all outdoor compressor oil is always kept at a safe level, eliminating
any compressor oil shortage problems.
21 22
Wide Application Range
The Super YC Series VRF are available in individual series and combinable series. The individual series has capacities Thanks to the EVI compressor and refrigerant cooling technology, the Super YC Series VRF can operate
from 8HP to 30HP and the combinable series from 8HP to 90HP, perfectly suited for small to large buildings. at temperatures as high as 55°C for cooling.
Super YC- Combinable Series
-15°C 55°C
Cooling
8-20HP 22-30HP
C
Long Piping Capability
32-60HP 62-90HP The total piping length of the Super YC system can be up to 1100m, the level difference between indoor and
outdoor units can be up to 110m and the level difference between indoor units can be up to 40m, making the Super
60-90H
YC Series VRF perfectly suitable for all buildings.
Wide Range of Indoor Units
The Super YC Series VRF offers 12 types of over 100 models of indoor units to meet different scenarios of
applications such as offices, shopping malls, hotels, airports, schools, hospitals, etc.
Total piping length: 1100m
1 Longest piping length - actual (equivalent): 220(260)m
25 26
Easy Installation and Service
SmartLink communication technology supports any wiring pattern rather than just daisy chain connection, reducing Compared to manual refrigerant charging, automatic refrigerant charging greatly simplifies the process, making
the installation cost and the possibility of incorrect connection. It has stronger anti-interference ability, achieving installation and maintenance easier and more efficient.
communication distance up to 2000m.
0 1 2
27 28
Maintenance Mode Easy Software Program Upgrade
The maintenance mode allows the shutdown of some indoor units without shutting down the whole VRF system, In addition to upgrading the program of outdoor and indoor units through USB and burner, the new product can also
and it can be activated on site during maintenance period as the remaining indoor units continue to operate. remotely upgrade all the programs of indoor and outdoor units through data cloud gateway, making system
upgrades very convenient and ensuring that the system program is always up to date.
*The data cloud gateway is still under development and needs to be purchased separately.
Continue work
Compared to traditional VRF with combination ratio of 50-130%, the Super YC Series VRF can be extended With the newly developed smart tool (Bluetooth module and special Bluetooth after-sales kit), system settings,
to 50-200%, and the wider combination ratio allows for more flexible system configuration. The larger operating parameter queries, trial runs and programme upgrades are all possible without opening the cabinet.
combination ratio can be applied to long-term part-load operation scenarios, allowing for further reduction in
installation costs.
Service maintenance
29 30
Super YC (Combinable series)
HP 8 10 12 HP 20 22 24
Model name 38VF008C119018 38VF010C119018 38VF012C119018 Model name 38VF020C119018 38VF022C119018 38VF024C119018
Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60) Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60)
kW 22.4 28 33.5 kW 56 61.5 67
Capacity Capacity
kBtu/h 76.4 95.5 114.2 kBtu/h 191.0 209.7 228.5
Cooling1 Cooling1
Power input kW 4.8 6.8 8.8 Power input kW 17.4 17.3 19.0
EER 4.65 4.14 3.81 EER 3.21 3.55 3.52
50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit
Connected Total capacity capacity capacity capacity Connected Total capacity capacity capacity capacity
indoor unit indoor unit
Maximum quantity 13 16 19 Maximum quantity 33 36 39
Type Scroll DC inverter Scroll DC inverter Scroll DC inverter Type Scroll DC inverter Scroll DC inverter Scroll DC inverter
Compressor Compressor
Quantity 1 1 1 Quantity 1 1 1
Type DC DC DC Type DC DC DC
Quantity 1 1 1 Quantity 1 2 2
Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120 Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120
Static pressure Pa (customized) (customized) (customized) Static pressure Pa (customized) (customized) (customized)
Airflow rate m3/h 12600 12600 13500 Airflow rate m3/h 16500 21500 21500
Type R410A R410A R410A Type R410A R410A R410A
Refrigerant Refrigerant
Factory charge kg 7.4 7.4 7.4 Factory charge kg 10 12.8 12.8
Pipe Liquid pipe mm Φ12.7 Φ12.7 Φ12.7 Pipe Liquid pipe mm Φ15.9 Φ19.1 Φ19.1
connections2 Gas pipe mm Φ25.4 Φ25.4 Φ25.4 connections2 Gas pipe mm Φ28.6 Φ31.8 Φ31.8
Sound pressure level3 dB(A) 57 58 60 Sound pressure level3 dB(A) 63 63 64
Net dimensions (W×H×D) mm 940×1760×825 940×1760×825 940×1760×825 Net dimensions (W×H×D) mm 940×1760×825 1340×1760×825 1340×1760×825
Packed dimensions (W×H×D) mm 1010×1945×890 1010×1945×890 1010×1945×890 Packed dimensions (W×H×D) mm 1010×1945×890 1410×1945×890 1410×1945×890
Net weight kg 185 185 185 Net weight kg 225 260 260
Gross weight kg 200 200 200 Gross weight kg 245 285 285
Ambient temp. operation o Ambient temp. operation o
C -15 to 55 -15 to 55 -15 to 55 C -15 to 55 -15 to 55 -15 to 55
range (Cooling) range (Cooling)
HP 14 16 18 HP 26 28 30
Model name 38VF014C119018 38VF016C119018 38VF018C119018 Model name 38VF026C119018 38VF028C119018 38VF030C119018
Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60) Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60)
kW 40 45 50 kW 73 78.5 85
Capacity Capacity
kBtu/h 136.4 153.5 170.5 kBtu/h 248.9 267.7 289.9
Cooling1 Cooling1
Power input kW 9.7 12.3 13.4 Power input kW 19.4 22.3 26.4
EER 4.12 3.67 3.74 EER 3.76 3.52 3.22
50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit
Connected Total capacity capacity capacity capacity Connected Total capacity capacity capacity capacity
indoor unit indoor unit
Maximum quantity 23 26 29 Maximum quantity 43 46 50
Type Scroll DC inverter Scroll DC inverter Scroll DC inverter Type Scroll DC inverter Scroll DC inverter Scroll DC inverter
Compressor Compressor
Quantity 1 1 1 Quantity 2 2 2
Type DC DC DC Type DC DC DC
Quantity 1 1 1 Quantity 2 2 2
Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120 Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120
Static pressure Pa (customized) (customized) (customized) Static pressure Pa (customized) (customized) (customized)
Airflow rate m3/h 15600 15600 16500 Airflow rate m3/h 22000 22000 22000
Type R410A R410A R410A Type R410A R410A R410A
Refrigerant Refrigerant
Factory charge kg 8.4 8.4 10 Factory charge kg 15.4 15.4 15.4
Pipe Liquid pipe mm Φ15.9 Φ15.9 Φ15.9 Pipe Liquid pipe mm Φ22.2 Φ22.2 Φ22.2
connections2 Gas pipe mm Φ28.6 Φ28.6 Φ28.6 connections2 Gas pipe mm Φ31.8 Φ31.8 Φ31.8
Sound pressure level3 dB(A) 60 61 62 Sound pressure level3 dB(A) 64 64 64
Net dimensions (W×H×D) mm 940×1760×825 940×1760×825 940×1760×825 Net dimensions (W×H×D) mm 1340×1760×825 1340×1760×825 1340×1760×825
Packed dimensions (W×H×D) mm 1010×1945×890 1010×1945×890 1010×1945×890 Packed dimensions (W×H×D) mm 1410×1945×890 1410×1945×890 1410×1945×890
Net weight kg 200 200 212 Net weight kg 325 325 325
Gross weight kg 215 215 232 Gross weight kg 350 350 350
Ambient temp. operation o Ambient temp. operation o
C -15 to 55 -15 to 55 -15 to 55 range (Cooling) C -15 to 55 -15 to 55 -15 to 55
range (Cooling)
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Diameters given are those of the unit's stop valves. 2. Diameters given are those of the unit's stop valves.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
29 30
Super YC (Combinable series)
HP 32 34 36 HP 44 46 48
Model name (Combination unit) 38VF032C119018 38VF034C119018 38VF036C119018 Model name (Combination unit) 38VF044C119018 38VF046C119018 38VF048C119018
Combination type 16HP+16HP 14HP+20HP 16HP+20HP Combination type 20HP+24HP 16HP+30HP 18HP+30HP
Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60) Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60)
kW 90.0 96.0 101.0 kW 123.0 130.0 135.0
Capacity Capacity
1 kBtu/h 307.0 327.4 344.5 1 kBtu/h 419.5 443.4 460.4
Cooling Cooling
Power input kW 24.6 27.1 29.7 Power input kW 36.4 38.7 39.8
EER 3.66 3.54 3.40 EER 3.38 3.36 3.39
50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit
Connected Total capacity capacity capacity capacity Connected Total capacity capacity capacity capacity
indoor unit indoor unit
Maximum quantity 53 56 59 Maximum quantity 64 64 64
Type Scroll DC inverter Scroll DC inverter Scroll DC inverter Type Scroll DC inverter Scroll DC inverter Scroll DC inverter
Compressor Compressor
Quantity 2 2 2 Quantity 2 3 3
Type DC DC DC Type DC DC DC
Quantity 2 2 2 Quantity 3 3 3
Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120 Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120
Static pressure Pa (customized) (customized) (customized) Static pressure Pa (customized) (customized) (customized)
3
Airflow rate m /h 31200 32100 32100 Airflow rate m3/h 38000 37600 38500
Type R410A R410A R410A Type R410A R410A R410A
Refrigerant Refrigerant
Factory charge kg 8.4×2 8.4+10 8.4+10 Factory charge kg 10+12.8 8.4+15.4 10+15.4
Pipe Liquid pipe mm Φ19.1 Φ19.1 Φ19.1 Pipe Liquid pipe mm Φ19.1 Φ19.1 Φ19.1
connections2 Gas pipe mm Φ31.8 Φ31.8 Φ38.1 connections2 Gas pipe mm Φ38.1 Φ38.1 Φ38.1
Sound pressure level3 dB(A) 64 65 65 Sound pressure level3 dB(A) 67 66 66
(940×1760×825)+(1340× (940×1760×825)+(1340× (940×1760×825)+(1340×
Net dimensions (W×H×D) mm (940×1760×825)×2 (940×1760×825)×2 (940×1760×825)×2 Net dimensions (W×H×D) mm 1760×825) 1760×825) 1760×825)
(1010×1945×890)+(1410× (1010×1945×890)+(1410× (1010×1945×890)+(1410×
Packed dimensions (W×H×D) mm (1010×1945×890)×2 (1010×1945×890)×2 (1010×1945×890)×2 Packed dimensions (W×H×D) mm 1945×890) 1945×890) 1945×890)
Net weight kg 200×2 200+225 200+225 Net weight kg 225+260 200+325 212+325
Gross weight kg 215×2 215+245 215+245 Gross weight kg 245+285 215+350 232+350
Ambient temp. operation o Ambient temp. operation o
C -15 to 55 -15 to 55 -15 to 55 C -15 to 55 -15 to 55 -15 to 55
range (Cooling) range (Cooling)
HP 38 40 42 HP 50 52 54
Model name (Combination unit) 38VF038C119018 38VF040C119018 38VF042C119018 Model name (Combination unit) 38VF050C119018 38VF052C119018 38VF054C119018
Combination type 18HP+20HP 16HP+24HP 18HP+24HP Combination type 20HP+30HP 22HP+30HP 24HP+30HP
Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60) Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60)
kW 106.0 112.0 117.0 kW 141.0 146.5 152.0
Capacity Capacity
kBtu/h 361.5 382.0 399.0 kBtu/h 480.9 499.6 518.4
Cooling1 Cooling1
Power input kW 30.8 31.3 32.4 Power input kW 43.8 43.7 45.4
EER 3.44 3.58 3.61 EER 3.22 3.35 3.35
50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit
Connected Total capacity capacity capacity capacity Connected Total capacity capacity capacity capacity
indoor unit indoor unit
Maximum quantity 62 64 64 Maximum quantity 64 64 64
Type Scroll DC inverter Scroll DC inverter Scroll DC inverter Type Scroll DC inverter Scroll DC inverter Scroll DC inverter
Compressor Compressor
Quantity 2 2 2 Quantity 3 3 3
Type DC DC DC Type DC DC DC
Quantity 2 3 3 Quantity 3 4 4
Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120 Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120
Static pressure Pa (customized) (customized) (customized) Static pressure Pa (customized) (customized) (customized)
3
Airflow rate m /h 33000 37100 38000 Airflow rate m3/h 38500 43500 43500
Type R410A R410A R410A Type R410A R410A R410A
Refrigerant Refrigerant
Factory charge kg 10×2 8.4+12.8 10+12.8 Factory charge kg 10+15.4 12.8+15.4 12.8+15.4
Pipe Liquid pipe mm Φ19.1 Φ19.1 Φ19.1 Pipe Liquid pipe mm Φ19.1 Φ19.1 Φ19.1
connections2 Gas pipe mm Φ38.1 Φ38.1 Φ38.1 connections2 Gas pipe mm Φ38.1 Φ38.1 Φ38.1
Sound pressure level3 dB(A) 66 66 66 Sound pressure level3 dB(A) 67 67 67
(940×1760×825)+(1340× (940×1760×825)+(1340× (940×1760×825)+(1340×
Net dimensions (W×H×D) mm (940×1760×825)×2 1760×825) 1760×825) Net dimensions (W×H×D) mm 1760×825) (1340×1760×825)×2 (1340×1760×825)×2
(1010×1945×890)+(1410× (1010×1945×890)+(1410× (1010×1945×890)+(1410×
Packed dimensions (W×H×D) mm (1010×1945×890)×2 1945×890) 1945×890) Packed dimensions (W×H×D) mm 1945×890) (1410×1945×890)×2 (1410×1945×890)×2
Net weight kg 212+225 200+260 212+260 Net weight kg 225+325 260+325 260+325
Gross weight kg 232+245 215+285 232+285 Gross weight kg 245+350 285+350 285+350
Ambient temp. operation o Ambient temp. operation o
range (Cooling) C -15 to 55 -15 to 55 -15 to 55 C -15 to 55 -15 to 55 -15 to 55
range (Cooling)
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent 2. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent
liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the Engineering Data liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the Engineering Data
Book for connection piping diameters. Book for connection piping diameters.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
29 30
Super YC (Combinable series)
HP 56 58 60 HP 68 70 72
Model name (Combination unit) 38VF056C119018 38VF058C119018 38VF060C119018 Model name (Combination unit) 38VF068C119018 38VF070C119018 38VF072C119018
Combination type 26HP+30HP 28HP+30HP 30HP+30HP Combination type 18HP+20HP+30HP 16HP+24HP+30HP 18HP+24HP+30HP
Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60) Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60)
kW 158.0 163.5 170.0 kW 191.0 197.0 202.0
Capacity Capacity
1 kBtu/h 538.8 557.6 579.8 1 kBtu/h 651.4 671.9 688.9
Cooling Cooling
Power input kW 45.8 48.7 52.8 Power input kW 57.2 57.7 58.8
EER 3.45 3.36 3.22 EER 3.34 3.41 3.44
50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit
Connected Total capacity capacity capacity capacity Connected Total capacity capacity capacity capacity
indoor unit indoor unit
Maximum quantity 64 64 64 Maximum quantity 64 64 64
Type Scroll DC inverter Scroll DC inverter Scroll DC inverter Type Scroll DC inverter Scroll DC inverter Scroll DC inverter
Compressor Compressor
Quantity 4 4 4 Quantity 4 4 4
Type DC DC DC Type DC DC DC
Quantity 4 4 4 Quantity 4 5 5
Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120 Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120
Static pressure Pa (customized) (customized) (customized) Static pressure Pa (customized) (customized) (customized)
Airflow rate m3/h 44000 44000 44000 Airflow rate m3/h 55000 59100 60000
Type R410A R410A R410A Type R410A R410A R410A
Refrigerant Refrigerant
Factory charge kg 15.4×2 15.4×2 15.4×2 Factory charge kg 10×2+15.4 8.4+12.8+15.4 10+12.8+15.4
Pipe Liquid pipe mm Φ19.1 Φ19.1 Φ19.1 Pipe Liquid pipe mm Φ22.2 Φ22.2 Φ22.2
connections2 Gas pipe mm Φ41.3 Φ41.3 Φ41.3 connections2 Gas pipe mm Φ44.5 Φ44.5 Φ44.5
Sound pressure level3 dB(A) 67 67 67 Sound pressure level3 dB(A) 68 68 68
Net dimensions (W×H×D) (940×1760×825)×2+(1340 (940×1760×825)+(1340× (940×1760×825)+(1340×
mm (1340×1760×825)×2 (1340×1760×825)×2 (1340×1760×825)×2 Net dimensions (W×H×D) mm ×1760×825) 1760×825)×2 1760×825)×2
Packed dimensions (W×H×D) (1010×1945×890)×2+(1410 (1010×1945×890)+(1410× (1010×1945×890)+(1410×
mm (1410×1945×890)×2 (1410×1945×890)×2 (1410×1945×890)×2 Packed dimensions (W×H×D) mm ×1945×890) 1945×890)×2 1945×890)×2
Net weight kg 325×2 325×2 325×2 Net weight kg 212+225+325 200+260+325 212+260+325
Gross weight kg 350×2 350×2 350×2 Gross weight kg 232+245+350 215+285+350 232+285+350
Ambient temp. operation o Ambient temp. operation
C -15 to 55 -15 to 55 -15 to 55 o
C -15 to 55 -15 to 55 -15 to 55
range (Cooling) range (Cooling)
HP 62 64 66 HP 74 76 78
Model name (Combination unit) 38VF062C119018 38VF064C119018 38VF066C119018 Model name (Combination unit) 38VF074C119018 38VF076C119018 38VF078C119018
Combination type 16HP+16HP+30HP 14HP+20HP+30HP 16HP+20HP+30HP Combination type 20HP+24HP+30HP 16HP+30HP+30HP 18HP+30HP+30HP
Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60) Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60)
kW 175.0 181.0 186.0 kW 208.0 215.0 220.0
Capacity Capacity
1 kBtu/h 596.9 617.3 634.4 1 kBtu/h 709.4 733.3 750.3
Cooling Cooling
Power input kW 51.0 53.5 56.1 Power input kW 62.8 65.1 66.2
EER 3.43 3.38 3.32 EER 3.31 3.30 3.32
50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit 50-130% of outdoor unit
Connected Total capacity capacity capacity capacity Connected Total capacity capacity capacity capacity
indoor unit indoor unit
Maximum quantity 64 64 64 Maximum quantity 64 64 64
Type Scroll DC inverter Scroll DC inverter Scroll DC inverter Type Scroll DC inverter Scroll DC inverter Scroll DC inverter
Compressor Compressor
Quantity 4 4 4 Quantity 4 5 5
Type DC DC DC Type DC DC DC
Quantity 4 4 4 Quantity 5 5 5
Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120 Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120
Static pressure Pa (customized) (customized) (customized) Static pressure Pa (customized) (customized) (customized)
Airflow rate m3/h 53200 54100 54100 Airflow rate m3/h 60000 59600 60500
Type R410A R410A R410A Type R410A R410A R410A
Refrigerant Refrigerant
Factory charge kg 8.4×2+15.4 8.4+10+15.4 8.4+10+15.4 Factory charge kg 10+12.8+15.4 8.4+15.4×2 10+15.4×2
Pipe Liquid pipe mm Φ19.1 Φ19.1 Φ19.1 Pipe Liquid pipe mm Φ22.2 Φ22.2 Φ22.2
connections2 Gas pipe mm Φ41.3 Φ41.3 Φ41.3 connections2 Gas pipe mm Φ44.5 Φ44.5 Φ44.5
Sound pressure level3 dB(A) 67 67 68 Sound pressure level3 dB(A) 69 68 68
(940×1760×825)×2+(1340 (940×1760×825)×2+(1340 (940×1760×825)×2+(1340 (940×1760×825)+(1340× (940×1760×825)+(1340× (940×1760×825)+(1340×
Net dimensions (W×H×D) mm ×1760×825) ×1760×825) ×1760×825) Net dimensions (W×H×D) mm 1760×825)×2 1760×825)×2 1760×825)×2
(1010×1945×890)×2+(1410 (1010×1945×890)×2+(1410 (1010×1945×890)×2+(1410 (1010×1945×890)+(1410× (1010×1945×890)+(1410× (1010×1945×890)+(1410×
Packed dimensions (W×H×D) mm ×1945×890) ×1945×890) ×1945×890) Packed dimensions (W×H×D) mm 1945×890)×2 1945×890)×2 1945×890)×2
Net weight kg 200×2+325 200+225+325 200+225+325 Net weight kg 225+260+325 200+325×2 212+325×2
Gross weight kg 215×2+350 215+245+350 215+245+350 Gross weight kg 245+285+350 215+350×2 232+350×2
Ambient temp. operation o Ambient temp. operation o
C -15 to 55 -15 to 55 -15 to 55 C -15 to 55 -15 to 55 -15 to 55
range (Cooling) range (Cooling)
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent 2. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent
liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the Engineering Data liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer
Book for connection piping diameters. Book for connection piping diameters.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
29 30
HP 80 82 84 HP 86 88 90
Model name (Combination unit) 38VF080C119018 38VF082C119018 38VF084C119018 Model name (Combination unit) 38VF086C119018 38VF088C119018 38VF090C119018
Combination type 20HP+30HP+30HP 22HP+30HP+30HP 24HP+30HP+30HP
Combination type 26HP+30HP+30HP 28HP+30HP+30HP 30HP+30HP+30HP
Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60)
Power supply V/N/Hz 380-415/3/50(60) 380-415/3/50(60) 380-415/3/50(60)
Type Scroll DC inverter Scroll DC inverter Scroll DC inverter Type Scroll DC inverter Scroll DC inverter Scroll DC inverter
Compressor Compressor
Quantity 5 5 5 Quantity 6 6 6
Type DC DC DC Type DC DC DC
Quantity 5 6 6 Quantity 6 6 6
Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120 Fan 0-20 (default); 20-120 0-20 (default); 20-120 0-20 (default); 20-120
Static pressure Pa (customized) (customized) (customized) Static pressure Pa (customized) (customized) (customized)
Airflow rate m3/h 60500 65500 65500 Airflow rate m3/h 66000 66000 66000
Pipe Liquid pipe mm Φ22.2 Φ22.2 Φ25.4 Liquid pipe mm Φ25.4 Φ25.4 Φ25.4
Pipe
connections2
connections2
Gas pipe mm Φ44.5 Φ44.5 Φ50.8 Gas pipe mm Φ50.8 Φ50.8 Φ50.8
(940×1760×825)+(1340×
Net dimensions (W×H×D) mm (1340×1760×825)×3 (1340×1760×825)×3 Net dimensions (W×H×D) mm (1340×1760×825)×3 (1340×1760×825)×3 (1340×1760×825)×3
1760×825)×2
Net weight kg 225+325×2 260+325×2 260+325×2 Net weight kg 325×3 325×3 325×3
Gross weight kg 245+350×2 285+350×2 285+350×2 Gross weight kg 350×3 350×3 350×3
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent 2. Diameters given are those for the pipe connecting the outdoor unit combination to the first indoor branch joint for systems with total equivalent
liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the Engineering Data liquid piping lengths of less than 90m. For systems with total equivalent liquid piping lengths of 90m or longer, please refer to the Engineering Data
Book for connection piping diameters. Book for connection piping diameters.
3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber. 3. Sound pressure level is measured at a position 1m in front of the unit and 1.3m above the floor in a semi-anechoic chamber.
29 30
Indoor Unit
Compact Four-way Cassette
Four-way Cassette
Slim Duct
Medium Static Pressure Duct
Wall Mounted
High Static Pressure Duct
Floor Standing
Two-way Cassette
One-way Cassette
57 58
Indoor Unit Lineup
Four-way Cassette
360° airflow, uniform air flow and tempera-
ture distribution One-way Cassette
Individual louver control
Built-in 1200mm high-lift drain pump
Automatic anti-condensation
Optional medium efficiency filter
Multiple Steps Vertical Swing
Optional plasma sterilization module
Built-in 1200mm high-lift drain pump(Digital
feedback DC water pump)
Slim Duct
199mm ultra-thin height (all models)
450mm ultra-narrow depth (all models)
Static pressure adaption, constant air volume
supply
Built-in 1200mm high-lift drain pump
Optional medium efficiency filter High Static Pressure Duct
Optional plasma sterilization module
5.6kW-16kW ESP up to 250Pa
20kW-56kW ESP up to 400Pa
299mm ultra-thin height (5.6kW-16kW)
Static pressure adaption, constant air volume supply
Medium Static Pressure Duct Built-in 1200mm high-lift drain pump
Optional HEPA filter with H13 rating
ESP up to 160Pa (all models) Optional medium to high efficiency filter
245mm ultra-thin height (all models)
Static pressure adaption, constant air
volume supply
Built-in 1200mm high-lift drain pump
Optional HEPA filter with H12 rating
Optional medium to high efficiency filter
Optional plasma sterilization module
59 60
Indoor Unit Lineup
kW 1.5 1.8 2.2 2.8 3.6 4.5 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 18.0 kW 1.5 1.8 2.2 2.8 3.6 4.5 5.6 6.3 7.1 8.0 9.0 10.0 11.2 12.5 14.0 16.0 18.0 20.0 22.4 25.2 28.0 33.5 40.0 45.0 56.0
5.1 6.1 7.5 9.6 12.3 15.4 19.1 21.5 24.2 27.3 30.7 34.1 38.2 42.7 47.8 54.6 61.4 5.1 6.1 7.5 9.6 12.3 15.4 19.1 21.5 24.2 27.3 30.7 34.1 38.2 42.7 47.8 54.6 61.4 68.3 76.5 86.0 95.6 114.3 136.5 153.6 191.1
Btu/h k k k k k k k k k k k k k k k k k
Btu/h k k k k k k k k k k k k k k k k k K K K K K K K K
Slim Duct
Compact Four-way
Cassette
High Static
Pressure Duct
Duct
Four-way Cassette
Medium Static
Pressure Duct
Cassette
Four-way Cassette
Wall Mounted
Wall Mounted
One-way Cassette
Floor Standing
- Concealed
Floor Standing
Two-way Cassette
Floor Standing
- Exposed
61 62
Indoor Unit Functions
Functions Compact
Four-way Medium Static High Static
Four-way Slim Duct Wall Mounted Two-way Cassette One-way Cassette Floor Standing
: equipped as standard; ○: customization option; × : without this function Cassette Pressure Duct Pressure Duct
Cassette
Auto cooling-heating Automatically selects cooling or heating mode to achieve the set temperature
changeover
When starting to warm up, the fan speed is automatically adjusted according to coil
Cold air prevention
temperature to prevent cold air discharge After warming up, fan speed is set as desired
Digital display on/off Indoor unit displays can be shut off at night, creating a better environment for rest
Buzzer sound on/off The buzzer sound of the indoor unit can be turned off to create a quieter environment
EEV automatic When in heating standby mode, the indoor unit automatically adjusts the EEV opening
adjustment according to the load to eliminate noise of refrigerant flowing.
The indoor temperature of multiple indoorl units is obtained from a designated indoor unit,
Indoor temperature
and multiple indoor units in a large space are controlled uniformly through this designated
detection control
indoor unit.
0.5°C/1°C setting Set temperature can be adjusted in 0.5°C or 1°C steps, enabling precise comfort control
temperature adjustment
Home leave mode During absence, the indoor temperature can be maintained at a certain level
COMFORT & HEALTH
Independent power supply This feature allows the shutdown of some indoor units without shutting down the whole VR Fsystem
Sleep mode The smart sleep mode can realize sleep is not easy to catch a cold and wake up refreshing
pre-filter
Removes airborne dust particles to ensure a steady supply of clean air exchanger and G1 G1 G1 pre-filter pre-filter pre-filter
Air filter G1 × F7 ○
prevent the heat exchanger from mildew F6 ○ F6 ○ G3 ○ F7○ H12 ○
H13 ○
A reserved outside air intake port allows outdoor air to be introduced directly 4.5-7.1kW × ×
Fresh air intake
Visualization of dirty
Dirty blockage rate can be accurately identified and displayed on the controller into the unit × × × × × ×
blockage rate
Silver Ions drain pan Slow-released nano-silver ions can keep the drain pan free of mold for a long time. ○ ○ ○ ○ × × × × ×
Heat exchanger self- Wash the dirt on the heat exchanger through freezing frost, and then high temperature
cleaning* sterilization.
Humidity control Additional humidity sensor can achieve humidity control in 35~75% ○ ○ ○ ○ ○ × × × ×
Puro-air kit Powered by OSRAM's UVC lamps, can effectively kill bacteria, viruses and odors of indoor air × × × ○ × × × × ○
Sterilization device Sterilization module can effectively kill bacteria, viruses and odors of indoor air ○ ○ ○ ○ ○ × × × ×
Possibility to select automatic vertical moving of the air discharge louvre, for uniform air
Vertical swing 5 steps + auto 5 steps + auto × × 5 steps + auto 5 steps + auto 5 steps + auto × ×
flow and temperature distribution
Possibility to select automatic horizontal moving of the air discharge louvre, for uniform air
Horizontal swing × × × × ○ × × × ×
flow and temperature distribution
AIR FLOW
Fan speed steps Multiple fan speeds can be selected to optimize comfort levels 7 steps 7 steps 7 steps 7 steps 7 steps 7 steps 7 steps 7 steps 7 steps
Individual louver control via the wired remote controller makes it simple to fix the position
Individual louver control × × × × × × ×
of each flap individually
Soft wind mode Supplies air against the ceiling to create windless environment ×
* Heat exchanger self-cleaning function can be available only when Super Y Mini is connected. There is no AHU-Kit, Fresh Air Processing Unit and V6 indoor unites in the system.
63 64
Compact
Functions Four-way Medium Static High Static
Four-way Slim Duct Wall Mounted Two-way Cassette One-way Cassette Floor Standing
: equipped as standard; ○: customization option ; × : without this function Cassette Pressure Duct Pressure Duct
Cassette
ECO mode The setting temperature rises automatically by 1°C per hour, up to 3°C
Full DC electronic
The fan motor and water pump are DC power supply
components
Using millimeter-wave radar sensor controller automatically turns indoor units
Human Detect Sensor on or off upon detecting that the room is occupied or unoccupied, ○ ○ × × ○ × × × ×
ensuringclimate control whilst minimizing energy consumption.
Carrier Super Y can upgrade all indoor units at the same time on the outdoor unit,
Program upgrade*
more easy program upgrade.
Long distance air delivery Provides adequate airflow and capacity under high ceiling conditions 3.5m 3m × × × × × × ×
High-lift drain pump Facilitates condensation draining from the indoor unit ○ ×
EASY Installation & Service
When the drain pipe is blocked or the drain pipe is poor, the water level switch ×
Water level switch ○
is turned off, and there is no need to worry about overflowing the ceiling.
The air discharge is specially designed to prevent air blowing against the ceiling × ×
Ceiling anti-dirt setting × × ×
to prevent ceiling dirty
Air baffle fittings for Some air discharge ports can be blocked with air baffle to optimize air × × × ×
× × ×
irregular rooms distribution in irregular shaped rooms
Long communication
Communication wiring up to 1200m makes installation more flexible
wiring
3 digit 7-segment display 3 digit 7-segment display can display more parameters and error information
Timer Timer can be set to start and stop operation anytime on a daily or weekly basis
Infrared remote control Infrared remote control with LCD to remotely control your indoor unit
Wired remote control Wired remote control to remotely control your indoor unit
EASY CONTROL
Centralized control Centralized control to control several indoor units from one single point
Auto-restart The unit restarts automatically at the original settings after power failure
°C/°F setting Temperature unit °C or °F can be set according to your usage habits
Long-distance
on/off function Long-distance startup or shutoff the system by weak electricity external devices
Humidifier connection Additional expansion board can achieve third-party humidifier connection ○ ○ ○ ○ ○ × × ○ ○
Dehumidifier connection Additional expansion board can achieve third-party dehumidifier connection ○ ○ ○ ○ ○ × × ○ ○
○ ○ ○ ○ ○ × × ○ ○
EXTENDED FUNCTIONS
Electric heater connection Additional expansion board can achieve third-party electric heater connection
CO2 sensor connection Additional expansion board can achieve CO2 sensor connection ○ ○ ○ ○ ○ × × ○ ○
PM2.5 sensor connection Additional expansion board can achieve PM2.5 sensor connection ○ ○ ○ ○ ○ × × ○ ○
Third-party controller
Third party controller can realize mode, fan speed and temperature control ○ ○ ○ ○ ○ × × ○ ○
connection
Long-distance on/off ○ ○
Long-distance startup or shutoff the system by strong electricity external devices ○ ○ ○ ○ ○ × ×
function
Long-distance alarm
Long-distance alarm when an error occurs ○ ○ ○ ○ ○ × × ○ ○
function
Multiple protections Multiple protections make the unit run more reliably
*The program upgrade function needs to be implemented through Bluetooth Module or Data Cloud Gateway. The Bluetooth Module and Data Cloud Gateway needs to be purchased separately.
65 66
Independent Power Supply
Some indoor units shut down without
shutting down the whole VRF system.
Communication distance up to
star connection, ring connection and so on.
2000M
Super Anti-interference Capability
Special waveform restoration technology enhances
anti-interference performance for more stable
communication.
67 68
Frosting Defrosting Drying
Frost makes the surface of heat exchanger dirt stripping Water flow flushes dirt from heat exchanger 55˚C high temperature drying water, effective sterilization
HEAT EXCHANGER
SELF-CLEANING*
* Heat exchanger self-cleaning function can be available only when Super Y Mini is connected.
69 70
Full DC Electronic
Components
The fan motor and
water pump are DC
power supply,
making the
temperature control
more precise and the
indoor temperature
more uniform.
Efficiency %
90
80
70
Energy-saving
60
50 20%
40
RPM
1000 2000 3000 4000 5000 6000
71 72
Optional Multi-Functional
Expansion Board
Humidity
control
Electric heater
connection
Multiple
protections
Switch Module
(Customized)
Long-distance
on/off function
Long-distance
alarm function
Humidifier/
Dehumidifier connection
Expansion Board
(Customized)
Third-party controller
connection
CO2 sensor
connection
PM2.5
PM2.5
sensor connection
Refrigerant leak
73 sensor connection 74
COMFORT
EEV automatic adjustment
Two thermistors control
When in heating standby mode, the indoor unit The indoor temperature can be checked
automatically adjusts the EEV opening according to the using the thermistor in the remote controller as
load to eliminate noise of refrigerant flowing. well as from the indoor unit
EEV
Unit
Opening Indoor istor
Therm
Noise is The opening of
generated EEV is adjusted
when the EEV according to
is excessively the refrigerant
open. flow rate
Remote Controller
Thermistor
Time
EEV Opening of Old Generation AC
EEV Opening of New Generation AC Refrigerant flow rate
The indoor unit automatically runs The indoor unit automatically stops
when detecting human body when detecting absence
*This function is available as a customization option for Compact Four Way Cassette.
AIR FLOW
360° Airflow
New design, round airflow path ensures uniform airflow and temperature distribution.
The continuous air supply port air supply area increases by 20%
75 76
7 Fan Speeds Individual Louver Control
EASY INSTALLATION
7 indoor fan speed options to meet the needs of The Individual louver control can control the motors Compact and stylish design
different indoor conditions. separately, making it possible to control all four louvers
independently. New Compact Four-way Cassette panel size is fit into the ceiling tile(620mm×620mm), making installation easier.
7 fan speeds
575mm
Long Distance Air Delivery Soft Wind Mode
The Compact Four-way Cassette has an additional Supplies air against the ceiling to create windless
30Pa static pressure for long airflow delivery and is environment.
Cut ceiling tile to install Pull out an gusset plate to install Reduced by 55mm
capable of being used in spaces up to 3.5m in floor
height.
Cooling
3.5m
Heating
A drain pump with a 1200mm raise height is fitted as When the drain pipe is blocked or the drain pipe is
standard, simplifying installation of the drain piping. poor, the water level switch is turned off, and there is
no need to worry about overflowing the ceiling.
HEALTH
Optional F6-class Air Filter
1200mm
The Compact Four-way Cassette supports 30Pa external static pressure for the F6-class filter installation.
Filtering effect of the F6-class filter reaches up to 80% against particles (particle size > 1µm), creating a cleaner
living environment.
77 78
COMFORT
EEV automatic adjustment Two thermistors control
When in heating standby mode, the indoor unit The indoor temperature can be checked using the
automatically adjusts the EEV opening according to the thermistor in the remote controller as well as from
load to eliminate noise of refrigerant flowing. the indoor unit
EEV
Opening
Unit
Indoor istor
Therm
Noise is The opening of
generated EEV is adjusted
when the EEV according to
is excessively the refrigerant
open. flow rate
Remote Controller
Thermistor
Time
EEV Opening of Old Generation AC
EEV Opening of New Generation AC Refrigerant flow rate
Cooling
Heating
The indoor unit automatically runs The indoor unit automatically stops
when detecting human body when detecting absence
*This function is available as a customization option for Super Y Four Way Cassette.
AIR FLOW
360° Airflow Multiple Steps Vertical Swing
New design, round airflow path ensures uniform The Four-way Cassette unit has a wide range of airflow
airflow and temperature distribution. angles from 30° to 65° and is equipped
with a 5-step louver control and auto swing mode
to better meet the needs of different customers
1
2
3
4
5
30°-65° 65°-30°
The continuous air supply port air supply area increases by 20%
7 Fan Speeds
7 indoor fan speed options to meet the needs of
360° Individual Healthy different indoor conditions.
airflow louver control air supply 7 fan speeds
Four-way Cassette
79 80
Individual Louver Control Soft Wind Mode
The Individual louver control can control the motors Supplies air against the ceiling to create windless
separately, making it possible to control all four louvers environment.
independently.
HEALTH
Mildew proof of heat exchanger Silver Ions drain pan (optional)
When the indoor unit is turned off in cooling mode, the Slow-released nano-silver ions can keep the drain pan
fan is still on, and dry the heat exchanger to avoid mold free of mold for a long time.
on the heat exchanger.
EASY INSTALLATION
Air baffle fittings for irregular rooms High-lift drain pump
Some air discharge ports can be blocked with air A drain pump with a 1200mm raise height is fitted as
baffle to optimize air distribution in irregular shaped standard, simplifying installation of the drain piping.
rooms. Air outlets can be blocked with accessories,
which can be found in the packing material.
1200mm
81 82
COMFORT HEALTH
Quiet Operation Two thermistors control Healthy Air Supply
By optimizing the design of fan motor, air duct and heat The indoor temperature can be checked using the The Slim Duct unit adopts an integrated C-shaped heat exchanger that allows for fast drainage and no dust or ash
exchanger, the new duct operates with noise as low as thermistor in the remote controller as well as from the accumulation. The optional long-life filter, medium-life filter and plasma sterilization module further enhance the air
22dB(A), creating a quieter and more comfortable indoor unit quality of the air supply and create a healthy environment.
environment.
Conventional V-shaped Integrated C-shaped heat
Long-life filter (optional)
Medium efficiency filter (optional) heat exchanger exchanger
tor Long-life, washable
hermis
Ind T Class F6 filter, filters 1~5µm
suspended particles, effectively
blocking PM2.5
22dB(A)
Remote Controller
Thermistor
Fan motor noise reduction
Folded seam hide Fast drainage
Air duct noise reduction
dirt and grime without adhesion
Heat exchanger noise reduction
Integrated C-shaped heat exchanger
(standard)
Quick discharge of dirt, no accumula-
tion of dust or ash.
Auto Cooling-heating Changeover
Automatically selects cooling or heating mode to achieve the set temperature.
Silver Ions drain pan (optional)
Slow-released nano-silver ions can keep the drain pan
free of mold for a long time.
Cooling
Heating
199mm
Constant Airflow
Airflow
Cleaning
reminder Super Y duct unit
100%
Efficient operation
High-lift drain pump Fault Feedback
65% Conventional duct unit A drain pump with a 1200mm raise height is fitted as Early warning of drain pump fault.
No
reminder Inefficient operation standard, simplifying installation of the drain piping.
0 3 6 9 12 Time (weeks)
Conventional duct units Super Y duct units
*Data measured in the UX lab of Carrier after one year of use after one year of use 1200mm
83 84
COMFORT
Quiet Operation
By optimizing the design of fan motor, air duct and heat exchanger, the new duct operates with noise as low as
22dB(A), creating a quieter and more comfortable environment.
22dB(A)
Cooling
25 C
o
25.5oC
17oC 17oC
26oC 26oC 26oC 26oC
26.5 oC Heating
27 oC
30oC 30oC
AIR FLOW
Adaptive Duct Length and Filter Resistance
By digital fan motor and a specially designed independent drive chip enables precise control and output on demand.
It can automatically adapt to duct lengths from 10 to 160 Pa equivalent static pressure without intervention from the
installer.
HEALTH
Compact Healthy Constant Flexible Optional High Efficiency HEPA Filter*
design air supply air volume installation
A static pressure of up to 160 Pa enables the application of medical-grade HEPA filters, and even small capacity models
can be equipped with high-efficiency filters, efficiently filtering fine particles of 0.5 microns with an efficiency of over
Medium Static Pressure Duct 99%.
HEPA filter
Filtration efficiency > 99%
Primary filter
Dirty air
Plasma Module
Catalytic Oxidation Module
Ozone Purification Module
Fresh Air
*This function is available as a customization option for Medium Static Pressure Duct
EASY INSTALLATION
Thin Body with High ESP
All models have a static pressure of 160 Pa and a thickness of only 245 mm. The high static pressure allows air to be
delivered over longer distances without loss of cooling and heating effect. Especially suitable for long and narrow
spaces.
750m
m
160Pa
Wall Mounted
3 Way flexible installation
It is possible to install and connect the outdoor unit in 3 different ways for Duct, providing flexibility to accommodate a
wide range of room designs.
1200mm
87 88
Bi-directional Coanda Airflow
COMFORT With bi-directional Coanda airflow delivery technology, the cold air does not blow directly on people and the
Quiet Operation Enclosed design hot air warms up evenly from the feet for better comfort.
The minimum noise level of Wall Mounted is as low as For Wall Mounted throttling parts and drain pumps adopt
27dB(A), idea for hotels and other noise-sensitive locations. closed design, reducing noise.
Throttle
Common cooling airflow patterns Coanda cooling airflow patterns Common heating airflow patterns Coanda heating airflow patterns
27dB(A) Drain Pump
The indoor unit automatically runs The indoor unit automatically stops
when detecting human body when detecting absence
120°
*This function is available as a customization option for Super Y Wall Mounted. There is some distance from ceiling The distance from the ceiling is 3cm
Auto Cooling-heating Changeover Sleep Mode Free Drainage without Space Restrictions
Automatically selects cooling or heating mode to The smart sleep mode provides a comfortable sleep The Wall Mounted can realize horizontal drainage, downward drainage, upward drainage, making installation more
achieve the set temperature. period and a refreshing wake up time. flexible.
3D Air Flow*
Possibility to select automatic vertical and horizontal moving of the air discharge louvre, for uniform air flow and High-lift drain pump* Fault Feedback
temperature distribution.
A drain pump with a 1200mm raise height is fitted as Early warning of drain pump fault.
standard, simplifying installation of the drain piping.
2
1
2
5
3 3 4
5
1200mm
89 90
COMFORT
Digital Display On/Off Quiet Operation
Indoor unit displays can be shut off at night, creating a The fan motor is DC power supply, which is more
better environment for rest. energy-saving and silent than AC power supply,
creating a more quiet and comfortable environment
Digital display
Fan Motor
Healthy Multi-functional Flexible
air supply Expansion installation
Indoor unit buzzer sound can be set off to not disturb 7 indoor fan speeds provide control flexibility to
the user, creating a quieter environment. meet the needs of different indoor conditions.
91 92
HEALTH
Dirty Filters Indicator Signal
The filter indicator will be on when the running time reaches a certain time to remind user to clean the filter.
Filter reminder
2626 oC C
25 oC
25. o
5
C
27 o C
.5 o
26 o
26oC 26oC
17oC 30oC 17oC 30oC
WIDER APPLICATION
Multi-functional Expansion Board
A wide range of accessories can be connected via Switch module and Expansion Board for even more functionality.
Switch module
(Customized)
Third-party humidifier and dehumidifier
Electric heater connection
Refrigerant leak sensor connection
Third-party controller connection
Long-distance on/off function
The Floor Standing Unit has three appearance options to meet different installation requirement, the F3B
(concealed) unit is designed to be concealed in walls while the F4 (front air intake) and F5 (underside air intake)
offer a choice of air intake options.
93 94
COMFORT WIDER APPLICATION
Digital Display On/Off Buzzer Sound On/Off Auto Cooling-heating Changeover Digital feedback DC water pump
Indoor unit displays can be shut off at night, creating a Indoor unit buzzer sound can be set off to not Automatically selects cooling or heating mode to Digital feedback DC water pump: actively sense the
better environment for rest. disturb the user, creating a quieter environment. achieve the set temperature. pump speed and water flow to determine whether
there is jamming attenuation or damage, and give
early warning to avoid water leakage.
Cooling
Digital display Buzzer
Heating
Quiet Operation
By optimizing the design of fan motor, air duct and heat exchanger, the new duct operates with noise as low as 22dB(A),
creating a quieter and more comfortable environment
HEALTH
Automatic anti-condensation
The One-way Cassette can automatically enter and exit the anti-condensation mode by detecting its own operation
data; In the anti-condensation mode, the machine can change the outlet angle of the guide vane intermittently to
prevent the local temperature difference of the guide panel from being too large and avoid the occurrence of
condensation. 1
1200mm
2
3 Step
4
5 Swing
25. o
5
C
27 o C
.5 o
26 o
26oC 26oC
17oC 30oC 17oC 30oC
95 96
COMFORT
Digital Display On/Off Buzzer Sound On/Off
Indoor unit displays can be shut off at night, creating a Indoor unit buzzer sound can be set off to not
better environment for rest. disturb the user, creating a quieter environment.
Digital display
Buzzer
Quiet Operation
The fan motor and water pump are DC power supply, which is more energy-saving and silent than AC power
supply, creating a more quiet and comfortable environment
The Two-way Cassette can automatically enter and exit the anti-condensation mode by detecting its own
operation data; In the anti-condensation mode, the machine can change the outlet angle of the guide vane
intermittently to prevent the local temperature difference of the guide panel from being too large and avoid the
occurrence of condensation.
97 98
0.5°C/1°C Setting Temperature Adjustment
Set temperature can be adjusted in 0.5°C or 1°C steps, enabling precise comfort control.
2626 oC C
25 oC
25. o
5
C
27 o C
.5 o
26 o
C
26oC 26oC
17oC 30oC 17oC 30oC
WIDER APPLICATION
Auto Cooling-heating Changeover Multiple Steps Vertical Swing
Automatically selects cooling or heating mode to There are 5-steps louver control makes the air flow
achieve the set temperature. direction more precisely. In addition, the auto swing
mode can better meet different customer needs. Air
supply angle 35-65 °. Compact Healthy Constant Flexible
design air supply air volume installation
2 Step
Heating
3
Swing
4
5
Digital feedback DC water pump: actively sense the A drain pump with a 1200mm raise height is fitted as
pump speed and water flow to determine whether standard, simplifying installation of the drain piping.
there is jamming attenuation or damage, and give
early warning to avoid water leakage.
1200mm
99 100
AIR FLOW WIDER APPLICATION
Constant Airflow Technology Ultra-high static pressure Multi-functional Expansion Board
Through the independent constant air volume digital The static pressure can reach 250Pa(5.6-16kW) or A wide range of accessories can be connected via Switch module and expansion board for even more functionality.
fan technology, the air volume is independently 400Pa(20-56kW), so the air supply distance is longer.
detected and adjusted to realize constant air volume Especially in long and narrow spaces such as corri-
and no attenuation in the whole life. dors, it can reduce the number of units used and save Third-party humidifier and dehumidifier
investment costs.. Electric heater connection
Fresh Air Processing unit Refrigerant leak sensor connection
Air volume
Third-party controller connection
Traditional air duct machine Switch module
(Customized)
Long-distance on/off function
Traditional
duct machine
Long-distance alarm function
Air duct + filter resistance
Long-distance Linkage with third-party
equipment such as air valve
1#/2# Expansion Board
Digital feedback DC water pump, Take the initiative to sense the pump speed and water flow, judge whether there is
Visualization of dirty blockage rate jamming attenuation or damage, and give early warning to avoid water leakage
Built-in self-learning model can detect the real-time resistance of the filter screen and restore the true state of the Integrated drainage pipe design reduces the sealing points of traditional design from 6 to 2, reduces breakpoints and
filter screen. 10 levels blockage rates can be accurately identified and displayed on the controller, reminding the user reduces leakage risks
to clean the filter in time.
Diagnose Influence
1200mm
299mm
101 102
Specifications
Compact Four-way Cassette
Four-way Cassette
Slim Duct
Wall Mounted
Floor Standing
Two-way Cassette
One-way Cassette
103 104
Specifications Specifications
Compact Four-way Cassette Four-way Cassette
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
kW 1.5 2.2 2.8 3.6
Capacity kW 2.8 3.6
Capacity
Cooling1 kBtu/h 5.1 7.5 9.6 12.3
Cooling 1
kBtu/h 9.6 12.3
Power input W 14 14 16 18
Power input W 17.0 17.0
kW 1.8 2.4 3.2 4.0
Capacity kW 3.2 4.0
Heating2 kBtu/h 6.1 8.2 10.9 13.7 Capacity
Heating2 kBtu/h 10.9 13.7
Power input W 14 14 16 18
Power input W 17.0 17.0
Air flow rate3 3
m /h 450/425/400/370/345/320/295 510/480/455/425/395/370/340 530/500/470/440/405/375/345
3
Air flow rate 3
m /h 790/740/691/641/591/542/492 790/740/691/641/591/542/492
Sound pressure level4 dB(A) 29/28/27/27/26/26/25 30/29/28/27/26/26/25 31/30/29/28/27/26/25.5
Sound pressure level 4
dB(A) 30/29/28/27.5/27/26/25 30/29/28/27.5/27/26/25
Sound power level dB(A) 40/39/39/39/38/38/38 42/41/40/39/39/38/38 42/40/39/38/38/38/38 5
Net dimensions
mm 840×204×840 840×204×840
Net dimensions5 (W×H×D)
mm 575×235×638
(W×H×D) Packed dimensions
Main body mm 940×250×940 940×250×940
Main body Packed dimensions (W×H×D)
mm 690×285×690
(W×H×D)
Net/Gross weight kg 18/20.5 18/20.5
Net/Gross weight kg 13.0/15.0 14.0/16.0
Net dimensions
Net dimensions (W×H×D) mm 950×50×950 950×50×950
mm 620×65×620
(W×H×D)
Panel Packed dimensions
Panel Packed dimensions (W×H×D) mm 1020×90×1020 1020×90×1020
mm 680×80×665
(W×H×D)
Net/Gross weight kg 5.8/7.6 5.8/7.6
Net/Gross weight kg 2.4/3.2
Refrigerant type R410A/R32
Refrigerant type R410A/R32
Liquid/Gas pipe mm Ø6.35/Ø12.7 Ø9.52/Ø15.9 Pipe Liquid/Gas pipe mm Ø6.35/Ø12.7 Ø6.35/Ø12.7 Ø9.52/Ø15.9
Pipe
connections
connections Drain pipe mm OD Ø25
Drain pipe mm OD Ø25
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Air flow rate are from the highest speed to the lowest speed, total 7 rates for each model. 3. Air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in an anechoic chamber. 4. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in an anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
105 106
Specifications Specifications
Four-way Cassette Slim Duct
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Air flow rate are from the highest speed to the lowest speed, total 7 rates for each model. 3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in an anechoic chamber. 4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher noise levels and lower airflow rate.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. For the optimal external static pressure range refer to the unit’s installation manual.)
5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in an anechoic chamber.
6. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
107 108
Specifications Specifications
Slim Duct Medium Static Pressure Duct
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
Power input W 33 36 40
Power input W 58 65 108
3
Air flow rate 3
m /h 470/438/407/375/343/312/280 500/467/433/400/367/333/300 540/503/467/430/393/357/320
Air flow rate3 m3/h 900/800/761/682/603/ 549/470 1145/1033/957/860/763/671/580 1400/1327/1249/1175/1095/1026/960
External static pressure4 Pa 30 (10~160)
External static pressure 4
Pa 10 (10-50) 10 (10-50) 20Pa(10-80)
Sound pressure level4 dB(A) 36/34.5/33.5/32.5/ 31/29/27 37/35/34/32.5/31/30/29 36.5/35.5/34.5/33/ 32/31.5/30.5 Sound pressure level4 dB(A) 26.5/26/25/24/23/22.5/22 26.5/26/25/24/23/22.5/22 26.5/26/25/24/23/22.5/22
Sound power level dB(A) 56/54/52/50/48/46/44 57/55.5/54/52/50.5/49/47 57/56/54.5/53.5/52/51/49.5 Sound power level dB(A) 46/44.5/43/41.5/40/38.5/37 47/45.5/44/42.5/41/39.5/38 47/45.5/44/42.5/41/39.5/38
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
kW 10 12.5 kW 4 5 6.3
Capacity Capacity
Heating 2
kBtu/h 34.1 42.7 Heating2 kBtu/h 13.7 17.1 21.5
Sound power level dB(A) 57/56/54.5/53.5/52/51/49.5 60.5/59/57.5/55.5/54/52.5/50.5 Sound power level dB(A) 50/48.5/47/45/43/41/39 53/51/49/47/45/43/41 55/53/51/49/47/45/43
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model. 3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher noise levels and lower airflow rate. 4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher noise levels and lower airflow rate.
For the optimal external static pressure range refer to the unit’s installation manual.) For the optimal external static pressure range refer to the unit’s installation manual.)
5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in an anechoic chamber. 5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in a semi-anechoic chamber.
6. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. 6. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
109 110
Specifications Specifications
Medium Static Pressure Duct Wall Mounted
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
Liquid/Gas pipe mm Ø9.52/Ø15.9 Pipe Liquid/Gas pipe mm Ø6.35/Ø12.7 Ø6.35/Ø12.7 Ф9.52/Ф15.9 Ф9.52/Ф15.9
Pipe
connections connections
Drain pipe mm OD Ø25 Drain pipe mm OD Ø16 OD Ø16 OD Ø16 OD Ø16
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model. 3. Air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher noise levels and lower airflow rate. For 4. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 0.8m below the unit in an anechoic chamber.
the optimal external static pressure range refer to the unit’s installation manual.) 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in a semi-anechoic chamber.
6. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
111 112
Specifications Specifications
Floor Standing F3(concealed) Floor Standing (front air intake)
Model name 42VS007H115003018 42VS009H115003018 42VS012H115003018 42VS016H115003018 42VS007H 42VS009H 42VS012H 42VS016H 42VS020H 42VS024H 42VS028H
Model name
115002018 115002018 115002018 115002018 115002018 115002018 115002018
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
kW 2.2 2.8 3.6 4.5 kW 2.2 2.8 3.6 4.5 5.6 7.1 8
Capacity Capacity
Cooling1 kBut/h 7.5 9.6 12.3 15.4 kBut/h 7.5 9.6 12.3 15.4 19.1 24.2 27.3
Cooling1
Input W 35 35 40 44
Input W 35 35 40 44 45 53 62
kW 2.4 3.2 4.0 5.0
Capacity kW 2.4 3.2 4 5 6.3 8 9
kBut/h 8.2 10.9 13.7 17.1 Capacity
Heating2
Heating2 kBut/h 8.2 10.9 13.7 17.1 21.5 27.3 30.7
Input W 35 35 41 46
Input W 35 35 41 46 47 57 64
External static pressure4 Pa 0-60
External static pressure4 Pa(F4) 0-10
Airflow rate3 473/464/454/449/ 473/464/454/449/ 524/503/488/471/ 636/611/584/557/ 507/490/482/466/ 532/512/501/483/ 689/663/639/608/ 934/904/888/860/ 1054/1011/992/955/
m3/h Airflow rate3 m3/h(F4)
439/431/426 439/431/426 450/427/408 533/507/483 449/450/435 466/435/414 575/560/526 821/786/764 924/889/841
Net dimensions5 (W×H×D) mm 915×470×200 915×470×200 915×470×200 1133×470×200 Unit Packed dimensions (W×H×D) mm(F4) 1125×595×285 1125×595×285 1345×595×285 1465×695×285
Unit Packed dimensions (W×H×D) mm 985×555×255 985×555×255 985×555×255 1205×555×255 Net/Gross weight kg(F4) 21.1/26.8 21.9/27.6 26.3/32.4 32.1/39.4 33.3/41.1 33.3/41.1
Model name 42VS020H115003018 42VS024H115003018 42VS028H115003018 42VS007H 42VS009H 42VS012H 42VS016H 42VS020H 42VS024H 42VS028H
Model name
115001018 115001018 115001018 115001018 115001018 115001018 115001018
Power supply 1-phase, 220-240V, 50/60Hz Power supply 1-phase, 220-240V, 50/60Hz
kW 5.6 7.1 8 kW 2.2 2.8 3.6 4.5 5.6 7.1 8
Capacity Capacity
Cooling1 kBut/h 19.1 24.2 27.3 Cooling1 kBut/h 7.5 9.6 12.3 15.4 19.1 24.2 27.3
Input W 45 53 62 Input W 35 35 40 44 45 53 62
Input W 47 57 64 Input W 35 35 41 46 47 57 64
Notes: Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Fan motor speed and air flow rate are from the highest to the lowest, total 7 rates for each model. 3. Fan motor speed and air flow rate are from the highest to the lowest, total 7 rates for each model.
4. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in a anechoic chamber. 4. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.5m below the unit in a anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. 5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
113 114
Specifications Specifications
One-way Cassette High Static Pressure Duct
Model name 40VZ006H11500018 40VZ007H11500018 40VZ009H11500018 40VZ012H11500018 40VZ016H11500018 40VZ020H11500018 40VZ024H11500018 Model name 42VD020H115011018 42VD024H115011018 42VD028H115011018 42VD030H115011018
kW 2.2 2.6 3.2 4.0 5.0 6.3 8.0 Input W 159 159 159 196
Capacity
Heating2 kBut/h 7.5 8.9 10.9 13.6 17.1 21.5 27.3 kW 6.3 8 9 10
Capacity
Input W 25 25 30 30 40 48 60 kBut/h 21.5 27.3 30.7 34.1
Heating2
380/355/330/300/ 460/440/410/380/ 693/662/638/600/ 792/763/728/688/ 933/873/815/749/ Input W 159 159 159 196
Airflow rate3 m3/h
286/263/240 355/330/300 556/510/476 643/589/549 689/637/592
1360/1281/1201/1122/ 1360/1281/1201/1122/ 1360/1281/1201/1122/ 1500/1413/1325/1238/
30/28/27/26/ 37/36/35/34/ 38/37/35/34/ 39/37/36/35/ 41/39/38/37/ 43/41/40/39/ Airflow rate3 m3/h
Sound pressure level4 dB(A) 1043/963/884 1043/963/884 1043/963/884 1150/1063/975
25/24/22 32/31/30 32/31/30 34/32/31 36/35/33 37/36/35
External static pressure4 Pa 80(0~250)
Net dimensions5 (W×H×D) mm 1054×153×428 1275×189×452
Net dimensions( no water tray) 39/37.5/36/34.5/ 39/37.5/36/34.5/ 39/37.5/36/34.5/ 40/38.5/37/35.5/
mm 1054×141×428 1275×176×452 Sound pressure level5 dB(A)
indoor unit (W×H×D) 33/31.5/30 33/31.5/30 33/31.5/30 34/32.5/31
Packed dimensions (W×H×D) mm 1155×245×490 1370×295×505
Net dimensions6 (W×H×D) mm 1135×299×770
Net/Gross weight kg 11.5/14.5 11.8/14.8 15.8/20.2 16.9/21.4
Unit Packed dimensions (W×H×D) mm 1215×359×890
Net dimensions (W×H×D) mm 1180×25×465 1350×25×505
Panel Packed dimensions (W×H×D) mm 1232×107×517 1410×95×560 Net/Gross weight kg 35/38.5 35/38.5 35/38.5 35/38.5
Net/Gross weight kg 3.5/4.7 4/5.6 Refrigerant type R410A/R32 R410A/R32 R410A/R32 R410A/R32
Refrigerant type R410A/R32 R410A/R32 R410A/R32 R410A/R32 R410A/R32 R410A/R32 R410A/R32 Pipe Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.52/Ф15.9
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 5m with zero level difference.
3. Each model's 7 airflow rate options are listed in order, from highest to lowest.
4. Each model's 7 sound pressure levels are listed in order from highest to lowest and correspond to the model's 7 airflow rate options (see Note 3).
Sound pressure level is measured 1.4m below the unit in a anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments. Model name 42VD040H115011018 42VD042H115011018 42VD048H115011018 42VD054H115011018
6. These products are under development and the specifications are always subject to change.
Model name 40VT007H11500018 40VT009H11500018 40VT012H11500018 40VT016H11500018 40VT020H11500018 40VT024H11500018 kW 11.2 12.5 14 16
Capacity
Power supply 1-phase, 220-240V, 50/60Hz Cooling1 kBut/h 38.2 42.7 47.8 54.6
kW 2.2 2.8 3.6 4.5 5.6 7.1 Input W 248 252 284 339
Capacity
Cooling1 kBut/h 7.5 9.6 12.3 15.4 19.1 24.2 kW 12.5 14 16 18
Capacity
Input W 35 40 40 50 69 98
Heating2 kBut/h 42.7 47.8 54.6 61.4
kW 2.6 3.2 4 5 6.3 8
Capacity Input W 248 252 284 339
Heating2 kBut/h 8.9 10.9 13.6 17.1 21.5 27.3
2140/2015/1890/1766/ 2150/2025/1899/1774/ 2400/2260/2120/1980/ 2600/2448/2297/2145/
Airflow rate3 m3/h
Input W 35 40 40 50 69 98 1641/1516/1391 1649/1523/1398 1840/1700/1560 1993/1842/1690
654/612/571/530/ 654/612/571/530/ 725/679/641/591/ 850/792/731/670/ 980/925/855/800/ 1200/1115/1068/1000/ External static pressure4 Pa 80(0~250) 100(0~250)
Airflow rate3 m3/h 488/449/410
488/449/410 554/509/458 631/592/550 755/702/670 921/808/770
41/39.5/38/36.5/ 41/39.7/38.3/37/ 43/41.5/40/38.5/ 44/42.5/41/39.5/
Sound pressure level5 dB(A)
35/33.5/32 35.7/34.3/33 37/35.5/34 38/36.5/35
33/31/30/29/ 33/31/30/29/ 35/33/32/30/ 37/36/35/34/ 39/37/36/35/ 44/42/41/40/
Sound pressure level4 dB(A)
27/25/24 27/25/24 29/27/25 32/31/30 33/31/30 38/36/34
Net dimensions6 (W×H×D) mm 1485×299×770
Net dimensions5 (W×H×D) mm 1259×299×591 Unit Packed dimensions (W×H×D) mm 1565×359×890
indoor unit Packed dimensions (W×H×D) mm 1355×400×675
Net/Gross weight kg 44.5/48.5 46.5/50.5 46.5/50.5 46.5/50.5
Net/Gross weight kg 29.7/36.3 31.6/38.2
Refrigerant type R410A/R32 R410A/R32 R410A/R32 R410A/R32
Net dimensions (W×H×D) mm 1430×53×680
Pipe Liquid/Gas pipe mm Ф9.52/Ф15.9
Panel Packed dimensions (W×H×D) mm 1525×130×765
connections Drain pipe mm OD Ф25
Net/Gross weight kg 11/15 11/15
Refrigerant type R410A/R32 R410A/R32 R410A/R32 R410A/R32 R410A/R32 R410A/R32 1.Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2.Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
Pipe Liquid/Gas pipe mm Ф6.35/Ф12.7 Ф9.52/Ф15.9 3.Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4.Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher noise levels and lower airflow rate.
connections Drain pipe mm OD Ф32 For the
optimal external static pressure range refer to the unit’s installation manual.)
Notes: 5.Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a anechoic chamber.
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference. 6.Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference. 7.All specifications are measured at standard external static pressure.
3. Air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a anechoic chamber.
5. Unit body dimensions given are the largest external dimensions of the unit, including hanger attachments.
115 116
Model name 42VD070H115011018 42VD076H115011018 42VD086H115011018 42VD096H115011018
VRF AHU Control Box
Power supply 1-phase, 220-240V, 50/60Hz
kW 20 22.4 25.2 28
High Efficiency
Capacity
Cooling1 kBut/h 68.3 76.5 86.0 95.6
Input W 780 780 780 780 AHU kit facilitates raising the EER/COP of the complete AHU system.
kW 22.5 25 26 31.5
Capacity
Heating2 kBut/h 76.8 85.3 88.7 107.5
kW 33.5 40 45 56
Capacity
Cooling1 kBut/h 114.3 136.5 153.6 191.1 Compatible with All VRF Systems
Input W 810 1850 1850 2030
kW 38 45 56 63 AHU kits are compatible with all Carrier VRF outdoor units and can be used together with all types of Carrier VRF
Capacity
Heating2 kBut/h 129.7 153.6 191.1 215.0 indoor units.
Input W 810 1850 1850 2030
Net dimensions6
(W×H×D) mm 1300×580×900 1850×580×900
Unit
Packed dimensions
(W×H×D) mm 1530×725×1060 2080×730×1060
Notes:
1. Indoor temperature 27°C DB, 19°C WB; outdoor temperature 35°C DB; equivalent refrigerant piping length 7.5m with zero level difference.
2. Indoor temperature 20°C DB; outdoor temperature 7°C DB, 6°C WB; equivalent refrigerant piping length 7.5m with zero level difference.
3. Fan motor speed and air flow rate are from the highest speed to the lowest speed, total 7 rates for each model.
4. Stable operation external static pressure range. (Note: setting external static pressure outside the unit’s optimal static pressure range may lead to higher noise levels and lower airflow rate.
For the optimal external static pressure range refer to the unit’s installation manual.)
5. Sound pressure level is from highest level to lowest level, total 7 levels for each model. Sound pressure level is measured 1.4m below the unit in a anechoic chamber.
6. The dimension is only the body size, excluding the size of the installation lug, connecting copper pipe, etc. For detailed dimensions, please refer to the installation manual.
7. All specifications are measured at standard external static pressure
117 118
Single AHU Control Box Connection
Remote Controllers
Blower, T1,T2,T2B
P,Q,E Max- 20 HP
Water pump & sensor
Wired Controllers
Centralized Controllers
Max- 120 HP
Accessories
X,Y,E
X,Y,E
X,Y,E
Specifications
Model name AHUKZ-00D AHUKZ-01D AHUKZ-02D AHUKZ-03D AHUKZ-04D AHUKZ-05D
Liquid pipe (in/out) (mm) Φ9.53/Φ9.53 Φ9.53/Φ9.53 Φ12.7/Φ12.7 Φ15.9/Φ15.9 Φ15.9/Φ15.9 Φ15.9/Φ15.9
119 120
CONTROLLER LINEUP Remote Controllers
Wireless Remote Controllers Wired Remote Controllers Centralized Controllers
WL-12F1-CM WR-86S-CM
CRF-270D-CM
WL-12F-CM WR-86T-CM
WR-120T-CM
NW3-CLOUD-CM NW3-BAC-CM
CA3-EK
NW3-MOD-CM
NW3-CLOUD-CM NW3-LON-CM
VRF-DIAG(A)
121 122
Features
Model
On / Off
RM12F1
RM12F
Wired Controllers
Mode selection
Temperature setting (0.5°C or 1°C steps) (0.5°C or 1°C steps)
7-speed fan control
Auto swing
5-step swing louver
Address setting
Follow me ×
Eco mode
Silent mode
Display shut-off
Daily timer
Self Cleaning Mode setting ×
Sterilization function setting ×
Keyboard lock
Background light
Indoor Unit parameter setting
Dimensions (H×W×D) (mm) 170×48×20 170×48×20
Batteries 1.5V (LR03/AAA) × 2
Indoor unit series V8 IDU, 3rd and 2nd generation IDU
Speed 2
Rest time
Speed 1 soft airflow Speed 1
unit louver, the air flow direction can be Frost makes the Water flow 55°C high temperature
surface of heat flushes dirt drying water, effective
controlled more precisely. exchanger from heat sterilization
dirt stripping exchanger
Step 3
4 ON/0ff
Swing Plasma Module
5 Catalytic Oxidation Model
Module
Ozone Purification Module
Fresh Air
123 124
Features Group Control Off Timer Function
One controller can be used to unify the settings across We can use the wired controller to set an automatic off
up to 16 indoor units. timer or after hours function for the indoor unit.
D1D2 D1D2 D1D2
Model
X1X2
Indoor units Up to 16
WR-86S-CM WR-86T-CM WR-120T-CM Note: when the 2nd generation AC indoor units connect to group controller
WDC-120G/WK, the indoor units need to customize D1 D2 terminals.
On / Off Group control is not available for 2nd generation AC Wall Mounted Series.
Mode selection
Main or Secondary Controller Setting
Temperature setting (0.5°C or 1°C steps) (0.5°C or 1°C steps) (0.5°C or 1°C steps)
Two controllers can be used together with single
Dual temperature set points × indoor unit. Operating mode and settings would be set
7-speed fan control according to the most recent instruction received. The
Auto swing controller display screens are synchronized so that
5-step swing louver both displays update when a setting is adjusted.
Address setting Weekly Schedule Timer
X1X2 X1X2 The weekly schedule timer allows users to set multiple
Follow me
schedules each with its own operating mode,
Meta mode
Main Secondary
Indoor units
temperature settings and fan speeds.
Room temperature display
One indoor unit
°F/°C display D1D2 D1D2
Keyboard lock ×
Background light
X1X2 X1X2
Daily timer Up to 16
Weekly Schedule
Weekly schedule timer ×
Auto restart SUN MON TUE WED THU FRI SAT
Two or more indoor units
2 permission levels
Bi-directional communication 2 Permission Levels OFF HEAT COOL FAN
Language English The buzzer sound of the indoor unit can be turned off
One to more control ×
to create a quieter environment.
Buzzer
125 126
Features
Central
Controllers Model
CRF-270D-CM
On/Off
Mode selection
Schedule management
Clock display
2 permission levels
Indoor unit type/model recognition *
Indoor unit with capacity larger
*
than 16kW recognition
Energy management
Group management
USB output
Error report and
Report display operation record
Operation log
LAN access
English,Chinese,Arabic,Spanish,Turkish,
Language supported Portuguese,Korean,Russian,Italian,Polish,French,German,Georgian
127 128
Touch Screen Group Management LAN Access
Colorful touch screen and vivid display make operation Units can be viewed according to group, system or A desktop or laptop PC can be used for browser-based access via a LAN connection.
more convenient and simple. location, making unit management clearer and more
convenient.
Up to 8 refrigerant systems
10.1-inch
X,Y,E P,Q/M1M2 P,Q/M1M2 Up to P,Q/M1M2
64
Up to 6 XYE
Ports
Up to 8 refrigerant systems
LAN X,Y,E Up to
Schedule Management P,Q/M1M2 P,Q/M1M2
64
P,Q/M1M2
Unit Model Recognition Daily, weekly or annual schedules can be used to set
The controller recognizes the model of indoor and unit settings such as on/off, operating mode, set
outdoor units and different models are represented by temperature, fan speed and swing.
different icons.
129 130
4GNS-30-IF
Software model
4GNS-30-IF
On/Off
Mode selection
Temperature setting
Auto swing
Schedule management
°C/display
Clock display
4 permission levels
Energy management
Group management
3D view
English,Chinese,Arabic,Spanish,Turkish,
Portuguese,Korean,Russian,Italian,Polish,
Language supported
French,German,Georgian
Hardware model
4GNS-30-CM
131 132
Device Management and Control User and Permission Management Easy Installation and Debugging
Users can flexibly group and centralize control the The administrator can add or reduce user accounts
VRF devices based on diffferent system or location according to the VRF management teams of the
and scenario. And limit the device functions, such as buliding, and set corresponding roles for each
temperature setting range fan speed, operation account. The administrator can flexibly assign
mode, swing lock, remote controller lock and wired permissions of each function of the software to each Network Cable/Wi-Fi
controller lock. role
ODU
Schedule Function 2D/3D view and setting XYE 4 way cassette ductedtype AC HWALL
PM(Optional)
8 ports
4GNS-30-IF can be used to make a detailed Users can upload project floor drawings and arrange
schedule for the indoor units. The schedule can be equipment locations according to the engineering
Gateway
set for the whole year. information. The software will be able to display the
distribution of system equipment in a 2D or 3D
Network ODU
manner 4 way cassette ductedtype AC HWALL
Cable
PM(Optional)
Max. 512 IDUs can be connected
ODU
4 way cassette ductedtype AC HWALL
XYE
PM(Optional)
8 ports
Gateway
ODU
Power Distribution 4 way cassette ducted type AC HWALL
PM(Optional)
Cooperated with the Carrier digital power meter, IMMPRO II can collect ODU power consumption information and
use the patented Carrier Calculation Method to estimate the electricity consumption of the indoor units and then
using the rules set by the user divide the whole power comsumption among building occupants.
133 134
Network Features
Device control
iEasyComfort
iEasyComfort App
Device monitor
Group control
Schedule management
Group management
Error check function
Operation log
Clock and Weather display
Max. number of gateways per software system Unlimited Unlimited
Hardware model
NW3-CLOUD-CM
Project management
Device management
Event management
Permission management
Max. number of gateways per software system Unlimited
X,Y,E Up to
P,Q,E or M1 M2 64 NW3-CLOUD-CM
Model
24V 0V
NW3-BAC-CM
On / Off
Mode selection
Fan speed
Swing
Energy management
EXV status
Full Integration
Outdoor unit control Emergency Stop
The BACnet Gateway enables seamless connection of Carrier VRF systems with building management systems built on the BACnet
communication protocol. Operating mode
Network Flexibility Fan speed
The gateway can be connected to master outdoor units' XYE ports directly. Compressor operating frequency
Outdoor unit
monitoring Exhaust Temperature
Up to 8 refrigerant systems
Web acess System pressure
X,Y,E Up to
P,Q,E or M1 M2 Error status
64
Error alarms
LAN access
NW3-BAC-CM
TCP/IP Up to 3 XYE
Ports Dimensions (HxWxD)( mm) 154×124×51.5
BACnet BMS
137 138
LonWorks Gateway Features
Port Connections
Model
NW3-LON-CM
XYE Port
Mode selection
LON+/LON-Connection Ports
Temperature setting
On / Off
Full Integration
Operating mode
The Lonworks Gateway enables seamless connection of Carrier VRF systems with home and building management systems built on
the Lonworks communication protocol.
Set temperature
Fan speed
Network Flexibility
The gateway can be connected to master outdoor units' XYE port directly. Indoor unit monitoring Online status
Operating status
X,Y,E P,Q,E or M1 M2
Room temperature
Error status
NW3-LON-CM
X,Y,E
Up to 8 refrigerant
systems Up to 32 Outdoor unit monitoring Error status
indoor units
Model
12V 0V
NW3-MOD-CM
On / Off
Mode selection
Fan speed
X Y E A1 B1 E A2 B2 E LAN
Energy management
The gateway can be connected to master outdoor units' XYE ports directly.
Number of operating IDUs
Outdoor unit
Error status
Up to 8 refrigerant systems
NW3-MOD-CM LAN access
TCP/IP
X,Y,E Up to
P,Q,E or M1 M2 64
HUB Dimensions (HxWxD)( mm) 154×124×51.5
LAN
Modbus TCP 12V DC
or Modbus RTU Power supply
Note:
: equipped as standard; ×: without this function
Modbus BMS
141 142
KNX Gateway Features
Port Connections
Model
NW3-KNX-CM
1 Power Supply DC 29 V
On / Off
2 KNX Programming Button
Swing
Full Integration
On / Off
The KNX Gateway enables seamless connection of Carrier VRF systems with home and building management systems built on the
KNX communication protocol.
Mode selection
Temperature setting
Network Flexibility
The gateway can be connected to indoor units' D1D2 port directly. Monitoring Fan speed
Swing
Room temperature
Outdoor unit
Error alarm
Indoor Unit
Indoor Unit
143 144
Monitor and Diagnose
Diagnosis Software Carrier’s VRF Diagnosis Software tool is used to monitor VRF systems and diagnose system errors.
System settings and operating parameters can be accessed easily and data logs can be reviewed for fault prevention
purposes.
Features
Model
VRF-DIAGNOSIS(A)
Mode selection
Fan speed
Operating mode
Capacity
EXV position
Operating mode
Capacity
Fan speed
Indoor unit
monitoring
Address
EXV position
Error codes
Toubleshooting
Data logs
145 146
Expert Diagnosis Parameter Querying and Parametric Curve Wiring Schematic
Carrier ’s VRF Diagnosis Software is specially designed Access all the system parameters easily.
to allow service engineers, to understand the
operating status of the system at a glance. H1H2E
H1H2E
DIAGNOSIS(A)
X,Y,E
P,Q,E P,Q,E Up to P,Q,E
64
Features
Data logs
Model
CA3-EK
Diagrams
A system schematic, refregetrant flow diagram and parameter chart can be generated to provide a graphical interpreta-
NW3-BAC-CM
tion of the system status.
Up to 8 Refrigerant
Systems
CRF-270D-CM
147 148
Selection Software"CSSP" Compatible Table Of Control System
High Efficiency 1st
Generation
2nd
Generation
(Remote (Remote
Controllers/ 1st Controllers/ 2nd
Carrier's advanced design automation tool can be used by designers, consultants and distributors to greatly reduce Outdoor Indoor Unit Wired Generation
1st
Wired Generation
2nd
Data
Network
Diagnosis
generation Generation Control Accessories
Unit Series Series Controller/ Centralized Controller/ Centralized Converter Software
the time and effort that must be devoted to the selection process. The software provides quick and convenient KNX Controllers
BMS
KNX Controllers
BMS System
selectable options for users, supports multiple languages, and greatly improves the selection process. Gateway1) Gateway1)
The Selection Software provides distributors' sales team with a comprehensive selection of system design reports
and calculations. Load calculations may be on either an initial estimate basis or detailed room-by-room basis. Based
Super X/ WL-12F1-CM
3r d DC / / / / / / / / /
on the indoor units, outdoor units and controllers selected, the software produces detailed system layout diagrams Super Xi WR-86S-CM
CRF-270C-CM
+
WL-12F-CM 5GNS-BAC-CM 4GNS-20-IF
CA-HKCW
Super X/ / / / WL-12B-CM CRF-180B-CM NW-MOD-CM- or
2nd DC CIF-15B-CM VRF-DIAG-B CA-HKCS
Super Xi WR-86KD-CM CRF-270C-CM NW-LON-CM-A 5GNS-20-CM
CA-IS
WR-120G-CM NW-KNXA-CM +
4GNS-20-IF
CRF-270C-CM
+
WR-29B-CM
CRF-180B 4GNS-20-IF CA-NIM05/E
WL-12-CM CRF-40-CM 5GNS-BAC-CM
Super X/ NW-KNX -CM or CA-
1st DC/AC WL-14-CM WCRF-10 / NW-MOD-CM-A CIF-15B-CM VRF-DIAG-B
Super Xi -CM CRF-270C 5GNS-20-CM NIM05B/E
WR-120C -CM NW-LON-CM-A
-CM + CA-NIM09
-CM
4GNS-20-IF
Piping diagram
CRF-270C-CM
+
WL-12F-CM 5GNS-BAC-CM
4GNS-20-IF CA-HKCW
Super X/ WL-12B-CM CRF-180B-CM NW-MOD-CM-A
2nd DC / / / CIF-15B-CM or VRF-DIAG-B CA-HKCS
Super Xi WR-86KD-CM CRF-270C-CM NW-LON-CM-A
5GNS-20-CM CA-IS
WR-120G-CM NW-KNXA-CM
+
4GNS-20-IF
CAD View
WR-29B-CM
M-interface CA-NIM05/E
Non Super X/ WL-12-CM CRF-40-CM CRF-18-CM CRF-180B-CM 5GNS-BAC-CM
1st DC/AC / CIF-15B-CM + VRF-DIAG-B CA-NIM05B/E
Super Xi WL-14-CM WCRF-10-CM NW-KNX-CM CRF-270C-CM NW-LON-CM-A
IMM CA-NIM09
WR-120C-CM
WL-12F-CM
5GNS-BAC-CM M-interface CA-HKCW
Non Super X/ CRF-40-CM WL-12B-CM CRF-180B-CM
2nd DC / CRF-18-CM NW-LON-CM-A CIF-15B-CM + VRF-DIAG-B CA-HKCS
Super Xi WCRF-10-CM WR-86KD-CM CRF-270C-CM
NW-KNXA-CM IMM CA-IS
WR-120G-CM
149 150