0% found this document useful (0 votes)
51 views32 pages

06 OvervoltageProtectionDevices LV10 2025 en 202412200205201287

The Siemens LV 10 2025 catalog presents innovative solutions for low-voltage power distribution and electrical installation technology, focusing on overvoltage protection devices. It highlights the importance of protecting buildings and systems from lightning strikes and power surges, offering a range of products including surge arresters and circuit breakers. The catalog also provides resources for technical specifications, ordering, and support services.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
51 views32 pages

06 OvervoltageProtectionDevices LV10 2025 en 202412200205201287

The Siemens LV 10 2025 catalog presents innovative solutions for low-voltage power distribution and electrical installation technology, focusing on overvoltage protection devices. It highlights the importance of protecting buildings and systems from lightning strikes and power surges, offering a range of products including surge arresters and circuit breakers. The catalog also provides resources for technical specifications, ordering, and support services.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 32

© Siemens 2024

SENTRON • SIVACON • ALPHA

Low-Voltage Power
Distribution and Electrical
Installation Technology
Overvoltage Protection Devices
siemens.com/lowvoltage

Catalog
Extract Edition
LV 10 2025
© Siemens 2024

Innovative solutions for industrial


controls and power distribution
Reliable components, systems and software solutions are essential in ensuring smooth power
distribution in buildings and industrial plants.

With SIRIUS, SENTRON, SIVACON and ALPHA, we offer an innovative portfolio for standard-compliant
and demand-oriented applications.

Efficient engineering tools and innovative cloud-based solutions can be flexibly tailored to individual
requirements.

We are there when you need us


Your personal contact can be found at
www.siemens.com/lowvoltage/contact

Catalog LV 10 · 2025 The products and systems described in this catalog are manufactured/
distributed under application of a certified quality management system
You will find the latest edition and all future editions in in accordance with EN ISO 9001 (for the Certified Registration Nos., see
SiePortal at www.siemens.com/lowvoltage/catalogs www.siemens.com/system-certificates/ep).
You can find the current prices in SiePortal at The certificate is recognized by all IQNet countries.
www.siemens.com/lowvoltage/product-catalog Technical specifications
The technical specifications are for general information purposes only.
Always heed the operating instructions and notices on individual products
during assembly, operation and maintenance.
All illustrations are not binding.
© Siemens 2024
© Siemens 2024
SENTRON · SIVACON · ALPHA

Low-Voltage Power Distribution and


Electrical Installation Technology
I
Introduction I/2

1
Protecting Air Circuit Breakers 1/1

2
Molded Case Circuit Breakers 2/1

3
Miniature Circuit Breakers 3/1

4
Residual Current Protective Devices/Arc Fault Detection Devices (AFDDs) 4/1

5
Switching Devices 5/1

6
Overvoltage Protection Devices 6/1

7
Fuse Systems 7/1

8
Protecting, Switching and Isolating Switch Disconnectors 8/1

9
Switching and Isolating Transfer Switching Equipment and Load Transfer Switches 9/1

10
Measuring and Monitoring Measuring Devices, Power Monitoring and Digitalization Solutions 10/1

11
Monitoring Devices 11/1

12
Distribution Transformers, Power Supply Units and Socket Outlets 12/1

13
Busbar Systems 13/1

14
Terminal Blocks 14/1

15
Switchboards, Distribution Boards and Small Distribution Boards 15/1

16
Busbar Trunking Systems 16/1

17
System Cubicles, System Lighting and System Air-Conditioning 17/1

A
Appendix A/1
© Siemens 2024
Overvoltage Protection Devices

Overvoltage protection devices

The more than one million lightning strikes in


Germany every year pose a considerable risk for
buildings and systems that can be damaged due
to the unhindered effect of lightning currents,
overvoltage and power surges. In many cases
however, it is not apparent that such damage has
been caused by lightning currents, overvoltage
and power surges.

Overvoltage results in considerable damage to


electrical and electronic equipment.
Even brief transients in power supply lines or
between electrical lines and other conductive
parts (e.g. grounded metallic parts, ground) are
sufficient to cause such damage. The damage
patterns of destroyed lines, printed circuit boards
or switchgear demonstrate this. Such damage
can be prevented employing suitable overvoltage
protection means.

Reliably protected by Siemens lightning and


surge arresters !
© Siemens 2024
Overvoltage Protection Devices

Overvoltage Protection Devices

All the information you need 6/2


System overview 6/4
Basic units 6/6
5SD74 lightning arresters, type 1 6/6
5SD74 combination surge arresters, type 1 + type 2 6/8
5SD74 combination surge arresters with integrated
back-up fuse 6/10 6
5SD74 surge arresters, type 1 + type 2 + type 3
for 40 mm busbar system 6/12
5SD74 combination surge arresters, type 1/type 2 6/14
5SD74 surge arresters, type 2 6/16
5SD74 surge arresters, type 3 6/20
5SD74 surge arresters, type 1 (UL) new 6/21

Siemens LV 10 · 2025 6/1


© Siemens 2024
Overvoltage Protection Devices | All the information you need

A multitude of additional information ...

Information + ordering

All the important things at a glance Everything you need for your order

For information about overvoltage protection devices, Refer to SiePortal to find an overview of your products
please visit our website (product catalog)
www.siemens.com/overvoltage-protection
• Overvoltage protection devices sie.ag/3ZMwRuw
Direct forwarding to the individual products in SiePortal
by clicking on the article number in the catalog or
Your product in detail
entering this web address incl. article number
www.siemens.com/product_catalog_SIEP?Article No.
The SiePortal platform (knowledge base) provides
6 comprehensive information
www.siemens.com/lowvoltage/product-support
• Technology Primer
− Overvoltage protection devices (109756965)
The relevant tender specifications can be found at
www.siemens.com/tenderspecifications
Use our conversion tool for quick and easy conversion to
Siemens products www.siemens.com/conversion-tool

The fast track to the experts

Contact persons in your region


We offer a comprehensive portfolio of services. Competent expert advice on technical questions with a wide
You can find your local contacts at range of demand-optimized services for all our products and
www.siemens.com/lowvoltage/components/contact systems.
You will find further information on services at Assistance with technical queries is provided at
www.siemens.com/service-offers www.siemens.com/support-request

6/2 Siemens LV 10 · 2025


© Siemens 2024
All the information you need | Overvoltage Protection Devices

... can be found in our online services

Commissioning + operation

Your product in detail Manuals

The SiePortal platform (knowledge base) provides Manuals can be found in SiePortal at
detailed technical information www.siemens.com/lowvoltage/manuals
www.siemens.com/lowvoltage/product-support
• Configuration Manual
• Operating instructions − Overvoltage protection devices (45315289)
• Certificates

Online Support app available for download from the


Face-to-face or online training
App Store and Play Store
You will find further information at
www.siemens.com/support-app Our training courses can be found at
www.siemens.com/sitrain-lowvoltage
Provision of 3D data (step and u3d data formats)
• SiePortal (product catalog) • Basic principles of electrical engineering (WT-LVBGET)
www.siemens.com/lowvoltage/product-catalog • Protection concept (WT-LVBPC)
• Image database
www.siemens.com/lowvoltage/picturedb

Engineering data for CAD or CAE systems are available


in the CAx Download Manager at
www.siemens.com/cax

Technical overview – Overvoltage protection devices

The fast way to get you to our online services


This page provides you with comprehensive information and links on overvoltage protection devices
www.siemens.com/lowvoltage/product-support (109769084)

Siemens LV 10 · 2025 6/3


© Siemens 2024
Overvoltage Protection Devices | System overview

System overview

Basic units

5SD74 lightning arresters, 5SD74 combination surge 5SD74 combination surge 5SD74 surge arresters,
type 1 arresters, type 1 + type 2 arresters with integrated type 1 + type 2 + type 3
back-up fuse for 40 mm busbar system

6 5SD74 combination 5SD74 surge arresters, 5SD74 surge arresters, 5SD74 surge arresters,
surge arresters, type 2 (standard design) type 3 type 1 (UL) new
type 1/type 2

Spare part plugs

N-PE L-N, L-PEN (type 1) L-PEN

Note:
You will find a detailed range of accessories with the basic units.

6/4 Siemens LV 10 · 2025


© Siemens 2024
System overview | Overvoltage Protection Devices

Installation locations for surge protection devices (SPDs)


Installation Installation Installation
location 1 location 2 location 3
type 1 and/or type 2 or type 2 or
type 2 type 3 type 3

Z UV Terminal
HAK
equipment
230/400V

S S S
6
P P P
D D D

I201_20525
HAK: Main terminal box Z/HV: In or close to the central meter system/main distribution board UV: Subdistribution board

Installation location 1 must be as close as possible to the supply point for the electrical system, so that the downstream installations are protected.
The SPDs at installation locations 2 and 3 shall not be used without SPDs at installation location 1, and they must be coordinated with these SPDs
(i.e. SPDs all from the same manufacturer).

Siemens LV 10 · 2025 6/5


© Siemens 2024
Overvoltage Protection Devices | Basic units

5SD74 lightning arresters, type 1

For TN-C systems and IT For TN-C systems For TN-S and TT systems
networks
Protection paths L-PE L-PEN L-N, L-PE and N-PE L-N, L-PE and N-PE
Rated voltage Un 690 V AC 240/415 V AC 240 V AC 240/415 V AC
Maximum continuous voltage Uc 800 V AC 350 V AC 350 V AC 350 V AC

Circuit Mounting width


With remote signaling
1+0 – 1) 5SD7411-2 – – –
1+1 4 MW – – 5SD7412-1 –
3+0 6 MW – 5SD7413-1 – –
6 3+1 8 MW – – – 5SD7414-1
1)
No modular installation device.

Further technical specifications 5SD7411-2 5SD7412-1 5SD7413-1 5SD7414-1


Standards
Standards IEC 61643-11; EN 61643-11
Approvals – KEMA, UL/cUL
Voltage
Protection level Up L-N and L-PEN ≤ 4.50 kV ≤ 1.50 kV
L-PE – ≤ 2.50 kV – ≤ 2.50 kV
N-PE – ≤ 1.50 kV – ≤ 1.50 kV
Current
Lightning impulse current Iimp L-N and L-PEN, 1P/3P 35 kA 25 kA 25/75 kA
(10/350 µs) N-PE – 100 kA – 100 kA
Rated discharge surge current In L-N and L-PEN, 1P/3P 35 kA 25 kA 25/75 kA
(8/20 µs) N-PE – 100 kA – 100 kA
Follow current discharge capacity Ifi L-N and L-PEN for 264/350 V – 50/25 kA
(AC) N-PE – 100 A – 100 A
Function
Response time tA L-N and L-PEN ≤ 100 ns
L-N and N-PE – ≤ 100 ns – ≤ 100 ns
Connections
Conductor cross-section Finely stranded 16 … 50 mm2 2.5 … 25 mm2
Solid 16 … 50 mm2 2.5 … 35 mm2
Protection devices
Max. back-up fuse acc. to IEC 61643-1 For stub wiring (gL/gG) 400 A 315 A
For V wiring (gL/gG) 125 A 125 A
Short-circuit strength With max. back-up fuse 50 kA 50 kA
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C

System overview, page 6/4


6/6 Siemens LV 10 · 2025
© Siemens 2024
Basic units | Overvoltage Protection Devices

Accessories
Spare part plugs
Protection paths Basic units Article No.
N-PE 5SD7412-1 and 5SD7414-1 5SD7418-0

L-N and L-PEN For 5SD7412-1, 5SD7413-1 and 5SD7414-1 5SD7418-1

System overview, page 6/4


Siemens LV 10 · 2025 6/7
© Siemens 2024
Overvoltage Protection Devices | Basic units

5SD74 combination surge arresters,


type 1 + type 2
For TN-C systems For TN-S and TT systems
Protection paths L-PEN L-N, L-PE and N-PE L-N, L-PE and N-PE
Rated voltage Un 240/415 V AC 240 V AC 240 V AC
Maximum continuous voltage Uc 350 V AC 350 V AC 350 V AC

Circuit Mounting width


With remote signaling
1+1 4 MW – 5SD7442-1 –
3+0 6 MW 5SD7443-1 – –
3+1 8 MW – – 5SD7444-1

6
Further technical specifications 5SD7442-1 5SD7443-1 5SD7444-1
Standards
Standards IEC 61643-11; DIN EN 61643-11
Approvals KEMA, UL/cUL
Voltage
Protection level Up L-N and L-PEN ≤ 1.50 kV
L-PE ≤ 2.20 kV – ≤ 2.20 kV
N-PE ≤ 1.50 kV – ≤ 1.50 kV
Current
Lightning impulse current Iimp L-N and L-PEN 25 kA
(10/350 µs) N-PE 100 kA – 100 kA
Rated discharge surge current In L-N and L-PEN 25 kA
(8/20 µs) N-PE 100 kA – 100 kA
Follow current discharge capacity Ifi L-N and L-PEN 25 kA
(AC) N-PE 100 A – 100 A
Function
Response time tA L-N and L-PEN ≤ 25 ns
L-N and N-PE ≤ 100 ns – ≤ 100 ns
Connections
Conductor cross-section Finely stranded 2.5 … 25 mm2
Solid 2.5 … 35 mm2
Protection devices
Max. back-up fuse acc. to IEC 61643-1 For stub wiring (gL/gG) 315 A
For V wiring (gL/gG) 125 A
Short-circuit strength With max. back-up fuse 25 kA
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C
Display
Visual function/fault indication Yes

System overview, page 6/4


6/8 Siemens LV 10 · 2025
© Siemens 2024
Basic units | Overvoltage Protection Devices

Accessories
Spare part plugs
Protection paths Type Basic units Article No.
N-PE – 5SD7442-1 and 5SD7444-1 5SD7418-0

L-N and L-PEN 1 5SD7442-1, 5SD7443-1 and 5SD7444-1 5SD7448-1

2 5SD7442-1, 5SD7443-1 and 5SD7444-1 5SD7428-1

System overview, page 6/4


Siemens LV 10 · 2025 6/9
© Siemens 2024
Overvoltage Protection Devices | Basic units

5SD74 combination surge arresters


with integrated back-up fuse
For TN-S and TT systems
Protection paths L-N
Rated voltage Un 230 V AC
Maximum continuous voltage Uc 255 V AC

Circuit Mounting width


1+0 2 MW 5SD7441-1KF00

6 Further technical specifications 5SD7441-1KF00


Standards
Standards EN 61643-11/... IEC 61643-11
Approvals KEMA
Voltage
Protection level Up L-N and L-N/PE ≤ 1.50 kV
Current
Lightning impulse current Iimp (10/350 µs) L-N and L-N/PE 25 kA
Rated discharge surge current In (8/20 µs) L-N and L-N/PE 25 kA
Follow current discharge capacity Ifi (AC) L-N and L-N/PE 50 kA
Function
Response time tA L-N and L-N/PE ≤ 100 ns
Connections
Conductor cross-section Finely stranded 25 mm²
Solid/stranded 35 mm²
Protection devices
Max. back-up fuse None necessary because integrated coordinated back-up
fuse contained in the device
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C

System overview, page 6/4


6/10 Siemens LV 10 · 2025
© Siemens 2024
Basic units | Overvoltage Protection Devices

Accessories
Connection bars
Version Number of poles Article No.
1-phase 3-pole 5SD7490-6

4-pole 5SD7490-7

System overview, page 6/4


Siemens LV 10 · 2025 6/11
© Siemens 2024
Overvoltage Protection Devices | Basic units

5SD74 surge arresters, type 1 + type 2 + type 3


for 40 mm busbar system
For TN-C systems
Protection paths L-PEN
Lightning impulse current Iimp (10/350 µs) 12.5 kA 7.5 kA
Rated voltage Un 240/415 V AC 240/415 V AC 240/415 V AC 240/415 V AC
Maximum continuous voltage Uc 300 V AC 300 V AC 300 V AC 300 V AC

Circuit Mounting width


With remote signaling
3+0 47 mm 5SD7443-8KK21 – 5SD7443-8KK11 –
3+1 47 mm – – – –
With remote signaling and phase tap
6 3+0 47 mm – 5SD7443-8KK22 – 5SD7443-8KK12
3+1 47 mm – – – –

Further technical specifications 5SD7443-8KK21 5SD7443-8KK22 5SD7443-8KK11 5SD7443-8KK12


Standards
Standards IEC 61643-11
Approvals VDE
Voltage
Protection level Up L-N and L-PEN ≤ 1.50 kV
L-N/N-PE – ≤ 1.5/1.5 kV
Current
Lightning impulse current Iimp (10/350 µs) L-N/N-PEN and N-PE 12.5 kA 7.5 kA
Rated discharge surge current In (8/20 µs) L-N/L-PEN and N-PE 20 kA
Follow current discharge capacity Ifi (AC) N-PE –
Connections
Conductor cross-section Finely stranded 25 mm2
Solid 35 mm2
Type of mounting
40 mm busbar system 5 and 10 mm
Protection devices
Max. back-up fuse acc. to IEC 61643-1 For stub wiring (gL/gG) 315 A
Short-circuit strength With max. back-up fuse 25 kA
Ambient conditions
Degree of protection IP20
Temperature range –40 … +80 °C
Display
Visual function/fault indication Yes

System overview, page 6/4


6/12 Siemens LV 10 · 2025
© Siemens 2024
Basic units | Overvoltage Protection Devices

For TN-S and TT systems


L-N, L-PE and N-PE
12.5 kA 7.5 kA
240/415 V AC 240/415 V AC 240/415 V AC 240/415 V AC
300 V AC 300 V AC 300 V AC 300 V AC

– – – –
5SD7444-8KK21 – 5SD7444-8KK11 –

– – – – 6
– 5SD7444-8KK22 – 5SD7444-8KK12

5SD7444-8KK21 5SD7444-8KK22 5SD7444-8KK11 5SD7444-8KK12

12.5 kA 7.5 kA
20/80 kA
100 A RMS

System overview, page 6/4


Siemens LV 10 · 2025 6/13
© Siemens 2024
Overvoltage Protection Devices | Basic units

5SD74 combination surge arresters,


type 1/type 2
For TN-C systems For TN-C systems For TN-S and TT systems For photovoltaic systems
and IT networks
Protection paths L-PE L-PEN L-N, L-PE and N-PE L-N, L-PE and N-PE (L+) – (L–)
Rated voltage Un 690 V AC 240/415 V AC 240 V AC 240/415 V AC –
Maximum continuous voltage Uc 800 V AC 335 V AC 335 V AC 335 V AC 1000 V DC

Circuit Mounting width Plug-in


With remote signaling
1+0 – 1) 5SD7411-2 – – – –
3+0 3 MW – 5SD7413-3 – –
3+1 4 MW – – – 5SD7414-3 –
6 Without remote signaling
1+1 2 MW – – 5SD7412-2 – –
3+0 3 MW – 5SD7413-2 – – 5SD7483-6
3+1 4 MW – – – 5SD7414-2 –
1)
No modular installation device.

5SD7413-2 5SD7414-2
Further technical specifications 5SD7411-2 5SD7412-2 5SD7413-3 5SD7414-3 5SD7483-6
Standards
Standards IEC 61643-11 EN 61643-31
Approvals – KEMA
Voltage
Protection level Up L-N and L-PEN ≤ 4.50 kV ≤ 1.20 kV ≤ 3.50 kV
L-PE – ≤ 2.0 kV –
N-PE – ≤ 1.70 kV – ≤ 1.70 kV –
Current
Lightning impulse current Iimp L-N and L-PEN 35 kA 12.5 kA ≤ 5 kA
(10/350 µs) N-PE – 50 kA – 50 kA –
Rated discharge surge current In L-N and L-PEN 35 kA 12.5 kA 15 kA
(8/20 µs) N-PE – 50 kA –
Max. discharge surge current Imax. L-N 100 kA 12.5 kA 50 kA 40 kA
(8/20 µs) N-PE – 50 kA – 50 kA –
Function
Response time tA L-N and L-PEN < 100 ns ≤ 25 ns
L-N and N-PE – ≤ 100 ns – ≤ 100 ns ≤ 25 ns
Connections
Conductor cross-section Finely stranded 16 … 50 mm2 1.5 … 25 mm2
Solid 16 … 50 mm 2
1.5 … 35 mm2
Protection devices
Max. back-up fuse acc. to IEC 61643-1 For stub wiring (gL/gG) 400 A 160 A –
For V wiring (gL/gG) 125 A 80 A –
Short-circuit strength With max. back-up fuse 50 kA 25 kA –
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C

System overview, page 6/4


6/14 Siemens LV 10 · 2025
© Siemens 2024
Basic units | Overvoltage Protection Devices

Accessories
Spare part plugs
Protection paths Type Basic units Article No.
N-PE – 5SD7412-2, 5SD7412-3, 5SD7414-2 and 5SD7414-3 5SD7418-2

L-N and L-PEN 1 5SD7412-2, 5SD7412-3, 5SD7413-2, 5SD7413-3, 5SD7414-2 and 5SD7418-3
5SD7414-3

L-PE (PV) 2 5SD7483-6 5SD7498-3

System overview, page 6/4


Siemens LV 10 · 2025 6/15
© Siemens 2024
Overvoltage Protection Devices | Basic units

5SD74 surge arresters, type 2


Standard design
For TN and TT systems For TN-C systems For TN-C systems For IT networks
and IT networks
Protection paths N-PE L-PEN and L-N L-PEN and L-N L-PEN L-PEN and L-PE L-PEN and L-PE
Rated voltage Un 240/415 V AC 240/415 V AC 400/690 V AC 240/415 V AC 400/690 V AC 554/960 V AC
Maximum continuous voltage Uc 260 V AC 350 V AC 800 V AC 350 V AC 580 V AC 760 V AC

Circuit Mounting width


With remote signaling
1+0 1 MW – 5SD7461-1 – – – –
2 MW – – 5SD7481-1 – – –

6 3+0 3 MW – – – 5SD7463-1 5SD7473-1 5SD7483-5


3+1 4 MW – – – – – –
Without remote signaling
1+0 1 MW 5SD7481-0 5SD7461-0 – – – –
3+0 3 MW – – – 5SD7463-0 – –
3+1 4 MW – – – – – –

5SD7461-0 5SD7463-0 5SD7464-0


Further technical specifications 5SD7481-0 5SD7461-1 5SD7481-1 5SD7463-1 5SD7464-1 5SD7473-1 5SD7483-5
Standards
Standards IEC 61643-11; DIN EN 61643-11
Approvals KEMA – KEMA,
UL/cUL
Voltage
Protection level Up L-N and L-PEN – ≤ 1.50 kV ≤ 5 kV ≤ 1.50 kV ≤ 1.60 kV ≤ 2.50 kV ≤ 2.90 kV
L-PE – ≤ 1.90 kV –
N-PE ≤ 1.50 kV – ≤ 1.50 kV –
Current
Rated discharge surge current In L-N and L-PEN – 20 kA 15 kA 20 kA 15 kA
(8/20 µs) N-PE 20 kA – 20 kA –
Max. discharge surge current Imax. L-N – 40 kA 30 kA 40 kA 30 kA
(8/20 µs) N-PE 40 kA – 40 kA –
Function
Response time tA L-N and L-PEN – ≤ 25 ns ≤ 100 ns ≤ 25 ns
L-N and N-PE ≤ 100 ns – ≤ 100 ns –
Connections
Conductor cross-section Finely stranded 1.5 … 25 mm2
Solid 1.5 … 35 mm2
Protection devices
Max. back-up fuse acc. to For stub wiring (gL/gG) – 125 A 100 A 125 A 100 A
IEC 61643-1 For V wiring (gL/gG) – 80 A
Short-circuit strength With max. back-up fuse 25 kA
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C

System overview, page 6/4


6/16 Siemens LV 10 · 2025
© Siemens 2024
Basic units | Overvoltage Protection Devices

For TN-S and Fuse bases for photovoltaic fuses


TT systems
L-N, L-PE and N-PE (L+) – (L–); (L+) – PE; (L–) – PE (L+) – (L–); (L+) – PE; (L–) – PE
240/415 V AC – –
350 V AC (L-N, L-PE) 1000 V DC 600 V DC
260 V AC (N-PE)

– – –
– – –
– – –
6
5SD7464-1 – –

– – –
– 5SD7483-0KK02 5SD7483-0KK01
5SD7464-0 – –

5SD7483-0KK01
5SD7483-0KK02 Accessories
Spare part plugs
EN 61643-31 Protection paths Basic units Article No.
KEMA N-PE 5SD7481-0, 5SD7464-0 und 5SD7464-1 5SD7488-0

≤ 3.70 kV

– L-N and L-PEN 5SD7461-0, 5SD7461-1, 5SD7463-0, 5SD7463-1, 5SD7468-1
5SD7464-0 und 5SD7464-1
15 kA

40 kA
L-PEN 5SD7481-1 und 5SD7483-5 5SD7488-2

≤ 25 ns
≤ 25 ns

5SD7481-1 5SD7488-4
1.5 … 25 mm2
1.5 … 35 mm2


– L-PE (PV) 5SD7483-0KK02 5SD7498-4
– 5SD7483-0KK01 5SD7498-5

IP20, with connected conductors


–40 … +80 °C

System overview, page 6/4


Siemens LV 10 · 2025 6/17
© Siemens 2024
Overvoltage Protection Devices | Basic units

5SD74 surge arresters, type 2


Narrow design
For TN-S and TT systems
Protection paths L-N and N-PE L-N and N-PE
Rated voltage Un 240 V AC 240/415 V AC
Rated arrester voltage UC; L-N, N-PE, L-(PE)N 350 V AC 350 V AC
Rated arrester voltage UC; N-PE 264 V AC 264 V AC

Circuit Mounting width


With remote signaling
1+1 24 mm (1 1/3 MW) 5SD7422-1 –
3+1 48 mm (2 2/3 MW) – 5SD7424-1
Without remote signaling
6 1+1 24 mm (1 1/3 MW) 5SD7422-0 –
3+1 48 mm (2 2/3 MW) – 5SD7424-0

5SD7422-0 5SD7424-0
Further technical specifications 5SD7422-1 5SD7424-1
Standards
Standards IEC 61643-11; DIN EN 61643-11
Approvals KEMA/UL/cUL
Voltage
Protection level Up L-N and L-PEN ≤ 1.50 kV
L-PE ≤ 1.90 kV
N-PE ≤ 1.50 kV
Current
Rated discharge surge current In (8/20 µs) L-N and L-PEN 20 kA
N-PE 20 kA
Max. discharge surge current Imax. (8/20 µs) L-N 40 kA
N-PE 40 kA
Function
Response time tA L-N and L-PEN ≤ 25 ns
L-N and N-PE ≤ 100 ns
Connections
Conductor cross-section Finely stranded 2.5 … 16 mm2
Solid 2.5 … 25 mm2
Protection devices
Max. back-up fuse acc. to IEC 61643-1 For stub wiring (gL/gG) 315 A
For V wiring (gL/gG) 63 A
Short-circuit strength With max. back-up fuse 25 kA
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C

System overview, page 6/4


6/18 Siemens LV 10 · 2025
© Siemens 2024
Basic units | Overvoltage Protection Devices

Accessories
Spare part plugs
Protection paths Basic units Article No.
N-PE 5SD7422-0, 5SD7422-1, 5SD7424-0 and 5SD7424-1 5SD7428-0

L-N and L-PEN 5SD7422-0, 5SD7422-1, 5SD7424-0 and 5SD7424-1 5SD7428-1

System overview, page 6/4


Siemens LV 10 · 2025 6/19
© Siemens 2024
Overvoltage Protection Devices | Basic units

5SD74 surge arresters, type 3

For TN-S and TT systems


Protection paths L-N, L-PE, N-PE, (L+) – (L–) L-N, L-PE, N-PE, (L+) – (L–) L-N, L-PE, N-PE, (L+) – (L–)
and (L+/L–) – PE and (L+/L–) – PE and (L+/L–) – PE
Rated voltage Un 24 V AC 120 V AC 230 V AC
Rated arrester voltage UC 34 V AC 150 V AC 264 V AC

Circuit Mounting width


With remote signaling
1+0 1 MW 5SD7432-5 5SD7432-6 5SD7432-7

6 Further technical specifications 5SD7432-5 5SD7432-6 5SD7432-7


Standards
Standards IEC 61643-11; DIN EN 61643-11
Approvals KEMA/UR KEMA/UL KEMA/UR
Voltage
Protection level Up L-N, L-PE and N-PE ≤ 200/≤ 600 V ≤ 750/≤ 850 V ≤ 1250/≤ 1400 V
Current
Rated load current IL (at 30 °C) 26 A
Rated discharge surge current In (8/20 µs) 1 kA 5 kA
Combined surge Uoc 2 kV 6 kV
Function
Response time tA ≤ 100 ns
Connections
Conductor cross-section Finely stranded 0.2 … 2.5 mm2
Solid 0.2 … 4 mm2
Protection devices
Required back-up fuse, max. (gG/B/C) 25 A
Ambient conditions
Degree of protection IP20, with connected conductors
Temperature range –40 … +80 °C
Display
Visual function/fault indication Yes

System overview, page 6/4


6/20 Siemens LV 10 · 2025
© Siemens 2024
Basic units | Overvoltage Protection Devices

5SD74 surge arresters, type 1 (UL) new


Without CE marking
For wye (star) For delta
Protection paths L-G and L-L L-N, L-G, L-L and N-G L-G and L-L L-N, L-G, L-L and N-G L-G and L-L
Rated voltage Un: L-N – 277 V AC – 347 V AC –
L-G 277 V AC 277 V AC 347 V AC 347 V AC 480 V AC
L-L 480 V AC 480 V AC 600 V AC 600 V AC 480 V AC
N-G – 0 V AC – 0 V AC –
Rated arrester voltage UC: L-N – 385 V AC – 510 V AC –
L-G 385 V AC 565 V AC 510 V AC 690 V AC 550 V AC
L-L 770 V AC 770 V AC 1020 V AC 1020 V AC 1100 V AC
N-G – 180 V AC – 180 V AC –

Circuit Mounting width 6


With remote signaling
3+0 3 TE 5SD7413-1KU02 – 5SD7413-1KU03 – 5SD7413-1KU04
3+1 4 TE – 5SD7414-1KU02 – 5SD7414-1KU03 –

Further technical
specifications 5SD7413-1KU02 5SD7414-1KU02 5SD7413-1KU03 5SD7414-1KU03 5SD7413-1KU04
Standards
Standards ANSI UL 1449; CSA C22.2 No. 269.1
Approvals UL, CSA
Voltage
Protection level Up L-N – ≤ 1.20 kV – ≤ 1.50 kV –
L-G ≤ 1.20 kV ≤ 1.80 kV ≤ 1.50 kV ≤ 2.0 kV ≤ 1.80 kV
L-L ≤ 2.50 kV ≤ 2.50 kV ≤ 3.0 kV ≤ 3.0 kV ≤ 3.0 kV
N-G – ≤ 0.60 kV – ≤ 0.60 kV –
Current
Rated discharge surge L-N, L-G and L-L 20 kA
current In (8/20 µs) N-G 20 kA
Max. discharge surge L-N, L-G and L-L 50 kA
current Imax (8/20 µs) N-G 50 kA
Connections
Conductor cross-section Finely stranded/ 2.5 ... 25 mm2
Solid
Busbar 16 mm2
Remote signa- 0.34 ... 1.5 mm²
ling contact
Protection devices
Short-circuit strength 200 kA
Ambient conditions
Degree of protection IP20
Temperature range –40 … +85 °C
Display
Visual/ Electrical function/fault indication Yes

System overview, page 6/4


Siemens LV 10 · 2025 6/21
© Siemens 2024
Appendix
© Siemens 2024
Appendix

Appendix

Conditions of sale and delivery A/2

Link directory A/4

Siemens LV 10 · 2025 A/1


© Siemens 2024
Appendix | Conditions of sale and delivery

Conditions of sale and delivery

1. General Provisions 1.2 For customers with a seat or registered office outside
By using this catalog you can purchase hard- and software European Union
products as well as services (together hereinafter referred to For customers with a seat or registered office outside European
as "products") described therein from Siemens Aktiengesellschaft Union, the following terms and conditions apply subordinate to
subject to the following Terms and Conditions of Sale and T&C:
Delivery (hereinafter referred to as "T&C"). Note, for products
• for products, which include specific terms and conditions in the
purchased from any Siemens entity having a registered office
description text, these specific terms and conditions shall apply
outside of Germany, the respective terms and conditions of sale
and subordinate thereto,
and delivery of the respective Siemens entity apply exclusively.
• for consulting services the "Standard Terms and Conditions for
The following T&C apply exclusively for orders placed with
Consulting Services for Infrastructure & Industry Business
Siemens Aktiengesellschaft, Germany.
(Swiss Law)"1) and/or
1.1 For customers with a seat or registered office in • for other services the "International Terms & Conditions for
European Union Services"1) supplemented by "Software Licensing Conditions"1)
For customers with a seat or registered office in European Union, and/or
the following terms and conditions apply subordinate to T&C: • for other products the "International Terms & Conditions for
Products"1) supplemented by "Software Licensing Conditions"1)
• for products, which include specific terms and conditions in the
text of the product description, these specific terms and 1.3 For customers with master or framework agreement
conditions shall apply and subordinate thereto, To the extent products offered are covered by an existing master
• for stand-alone software products and software products or framework agreement, the terms and conditions of that
forming a part of a product or project, the "General Conditions agreement shall apply instead of T&C.
for Software Products for Infrastructure & Industry Business
2. Additional Terms and Conditions
(German law)"1) and/or
The dimensions are in mm. In Germany, according to the German
• for consulting services the "Allgemeine Geschäftsbedingungen
law on units in measuring technology, data in inches apply only
für Beratungsleistungen für Infrastructure & Industry Geschäft
to devices for export.
(Deutsches Recht)"1) (available only in German) and/or
• for other services, the "Supplementary Terms and Illustrations are not binding.
Conditions for Services for Infrastructure & Industry Business
Insofar as there are no remarks on the individual pages of this
(German Law) ("BL")"1) and/or
catalog – especially with regard to data, dimensions and weights
• for other products the "General Conditions for the Supply
given – these are subject to change without prior notice.
of Products and Services of the Electrical and Electronics
Industry"1).
In case such products should contain Open Source Software,
the conditions of which shall prevail over the "General
Conditions for the Supply of Products and Services of the
Electrical and Electronics Industry"1), the Product will be given
a note as to which special conditions apply to this open source
software. This shall apply mutatis mutandis for notices
referring to other third-party software components.

1)
The text of the Terms and Conditions of Siemens AG can be downloaded at
https://mall.industry.siemens.com/legal/ww/en/terms_of_trade_en.pdf

A/2 Siemens LV 10 · 2025


© Siemens 2024
Conditions of sale and delivery | Appendix

3. Export Control and Sanctions Compliance • (iv) upload to a products platform any customer content
unless it is non-controlled (e.g. in the EU: AL = N;
3.1 General in the U.S.: ECCN = N or EAR99);
Customer shall comply with all applicable sanctions, embargoes • (v) facilitate any of the afore mentioned activities by any user.
and (re-)export control laws and regulations, and, in any event, Customer shall provide all users with all information necessary
with those of the European Union, the United States of to ensure compliance with the Export Regulations.
America and any locally applicable jurisdiction (collectively
"Export Regulations"). 3.4 Semiconductor Development
Customer will not, without advance written authorization from
3.2 Checks for Products Siemens, use offerings for the development or production of
Prior to any transaction by customer concerning products integrated circuits at any semiconductor fabrication facility
(including hardware, documentation and technology) delivered located in China meeting the criteria specified in the U.S. Export
by Siemens, or products (including maintenance and technical Administration Regulations, 15 C.F.R. 744.23.
support) performed by Siemens with a third party, customer shall
check and certify by appropriate measures that 3.5 Information
Upon request by Siemens, customer shall promptly provide
• (i) the customer’s use, transfer, or distribution of such Siemens with all information pertaining to users, the intended
products, the brokering of contracts or the provision of other use and the location of use or the final destination (in the case of
economic resources in connection with products will not be in hardware, documentation and technology) of the products.
violation of any Export Regulations, also taking into account Customer will notify Siemens prior to customer disclosing any
any prohibitions to circumvent these (e.g., by undue diversion) information to Siemens that is defense-related or requires
• (ii) the products are not intended or provided for prohibited or controlled or special data handling pursuant to applicable
unauthorized non-civilian purposes (e.g. armaments, nuclear government regulations, and will use the disclosure tools and
technology, weapons, or any other usage in the field of methods specified by Siemens.
defense and military);
• (iii) customer has screened all direct and indirect parties 3.6 Reservation
involved in the receipt, use, transfer, or distribution of the Siemens shall not be obligated to fulfill this agreement if such
products against all applicable restricted party lists of the fulfillment is prevented by any impediments arising out of
Export Regulations concerning trading with entities, national or international foreign trade or customs requirements
persons and organizations listed therein and or any embargoes or other sanctions. Customer acknowledges
• (iv) products within the scope of items-related restrictions, as that Siemens may be obliged under the Export Regulations to
specified in the respective annexes to the Export Regulations, limit or suspend access by customer and/or users to products.
will not, unless permitted by the Export Regulations, be
4. Miscellaneous
(a) exported, directly or indirectly (e.g., via Eurasian Economic
Errors excepted and subject to change without prior notice.
Union (EAEU) countries), to Russia or Belarus, or
(b) resold to any third party business partner that does not take
a prior commitment not to export such products to Russia or
Belarus.
3.3 Non-Acceptable Use of Software and Cloud Services
Customer shall not, unless permitted by the Export Regulations
or respective governmental licenses or approvals,
• (i) download, install, access or use the products from or in any
location prohibited by or subject to comprehensive sanctions
or subject or to license requirements according to the Export
Regulations;
• (ii) grant access to, transfer, (re-)export (including any
"deemed (re-)exports"), or otherwise make available the
products to any entity, person, or organization identified on a
restricted party list of the Export Regulations; A
• (iii) use the products for any purpose prohibited by the Export
Regulations (e.g. use in connection with armaments, nuclear
technology or weapons);

Siemens LV 10 · 2025 A/3


© Siemens 2024
Appendix | Link directory

Link directory
Catalog LV 10

General information
Information on low-voltage power distribution and electrical www.siemens.com/lowvoltage
installation technology
Tender specifications www.siemens.com/tenderspecifications
Conversion tool www.siemens.com/conversion-tool
Image database www.siemens.com/lowvoltage/picturedb
CAx download manager www.siemens.com/cax
Newsletter system www.siemens.com/lowvoltage/newsletter
Siemens YouTube channel www.youtube.com/Siemens
Catalog LV 10 www.siemens.com/lv10
Catalog LV 13 www.siemens.com/lv13
Catalog LV 18 www.siemens.com/lv18
Brochures/catalogs www.siemens.com/lowvoltage/catalogs
Operating instructions/manuals www.siemens.com/lowvoltage/manuals
SiePortal www.siemens.com/sieportal
SiePortal (knowledge base) www.siemens.com/lowvoltage/product-support
SiePortal (product catalog) www.siemens.com/lowvoltage/product-catalog
Online Support App www.siemens.com/support-app
My Documentation Manager (MDM) www.siemens.com/lowvoltage/mdm
Configurators www.siemens.com/lowvoltage/configurators
Direct forwarding to SiePortal www.siemens.com/product_catalog_SIEP?Article No.
Training www.siemens.com/sitrain-lowvoltage
Local contacts www.siemens.com/lowvoltage/contact
www.siemens.com/lowvoltage/components/contact
www.siemens.com/lowvoltage/systems/contact
www.siemens.com/lowvoltage/software/contact
Technical Support www.siemens.com/support-request
Information on services www.siemens.com/service-offers
Control panels for the North American market www.siemens.com/northamerican-standards
Integrated Control Panels www.siemens.com/controlpanel
Smart Control Panel Design www.siemens.com/controlpanel/cpd
Energy savings and amortization www.automation.siemens.com/sinasave
SIMATIC Energy Suite www.siemens.com/energysuite
SITOP power supplies www.siemens.com/sitop
Power distribution with Totally Integrated Power www.siemens.com/tip
TIA Selection Tool www.siemens.com/tst
Electrical Product Finder www.siemens.com/electrical-product-finder
Sustainability www.siemens.com/sustainability
Siemens EcoTech www.siemens.com/SiemensEcoTech
www.siemens.com/lowvoltage/SiemensEcoTech
SENTRON product phase-out www.siemens.com/info-sentron

A/4 Siemens LV 10 · 2025


© Siemens 2024

Catalogs and further information

LV 10 ET D1
© Siemens 2023

Low-Voltage Power Distribution and Switches and Socket Outlets


Electrical Installation Technology DELTA
SENTRON • SIVACON • ALPHA
PDF (SIEP-C10409-00-7600)
PDF (E86060-K8280-A101-B9-7600) Catalog
ET D1
Edition
2023

DELTA

Switches and Socket Outlets


siemens.com/delta

LV 13 SiePortal
3WA Air Circuit Breakers Information and Ordering Platform
SENTRON on the Internet:
PDF (E86060-K8280-B101-A4-7600) sieportal.siemens.com

LV 18 SITRAIN
Air Circuit Breakers and Molded Case Digital Industry Academy
Circuit Breakers with UL Certification
www.siemens.com/sitrain
SENTRON
PDF (E86060-K8280-E347-B2-7600)

IC 10 Siemens TIA Selection Tool


Industrial Controls for the selection, configuration and
SIRIUS ordering of TIA products and devices
PDF (E86060-K1010-A101-B7-7600) www.siemens.com/tst

The catalogs listed above and additional catalogs are Further information on low-voltage power distribution
available in PDF format at and electrical installation technology is available on the
www.siemens.com/lowvoltage/catalogs Internet at www.siemens.com/lowvoltage
© Siemens 2024

Cybersecurity information
Siemens provides products and solutions with For additional information on industrial cybersecurity
industrial cybersecurity functions that support the measures that may be implemented, please visit
secure operation of plants, systems, machines and www.siemens.com/cybersecurity-industry.
networks. Siemens’ products and solutions undergo continuous
In order to protect plants, systems, machines and development to make them more secure. Siemens
networks against cyber threats, it is necessary to strongly recommends that product updates are applied
implement – and continuously maintain – a holistic, as soon as they are available and that the latest
state-of-the-art industrial cybersecurity concept. product versions are used. Use of product versions that
Siemens’ products and solutions constitute one are no longer supported, and failure to apply the latest
element of such a concept. updates may increase customer’s exposure to cyber
Customers are responsible for preventing unautho- threats.
rized access to their plants, systems, machines and To stay informed about product updates, subscribe to
networks. Such systems, machines and components the Siemens Industrial Cybersecurity RSS Feed under
should only be connected to an enterprise network or www.siemens.com/cert.
the internet if and to the extent such a connection is
necessary and only when appropriate security
measures (e.g. firewalls and/or network segmenta­
tion) are in place.

Get more information


www.siemens.com/lowvoltage

Published by
Siemens AG

Smart Infrastructure
Electrical Products
Siemensstraße 10
93055 Regensburg, Germany

Subject to changes and errors. The information


For the U.S. published by given in this document only contains general
Siemens Industry Inc. descriptions and/or performance features which
may not always specifically reflect those described,
or which may undergo modification in the course
3617 Parkway Lane of further development of the products. The
Peachtree Corners, GA 30092 requested performance features are binding only
United States when they are expressly agreed upon in the
concluded contract.
PDF (Catalog Extract All product designations may be trademarks or
E86060-K8280-A101-B9-7600) other rights of Siemens AG, its affiliated companies
KG 1224 28 En or other companies whose use by third parties for
Produced in Germany their own purposes could violate the rights of the
© Siemens 2024 respective owner.

© 2024 by Siemens AG, Berlin and Munich