SUN2000 - (196KTL-H3, 200KTL-H3, 215KTL-H3) User Manual

The document is a user manual for the SUN2000 series inverters, detailing installation, electrical connections, commissioning, maintenance, and troubleshooting procedures. It is intended for photovoltaic plant operators and qualified electricians, emphasizing safety precautions and compliance with standards. The manual includes updates, safety information, and technical specifications relevant to the models SUN2000-196KTL-H3, SUN2000-200KTL-H3, and SUN2000-215KTL-H3.

Uploaded by

matheus.brisolla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
67 views125 pages

SUN2000 - (196KTL-H3, 200KTL-H3, 215KTL-H3) User Manual

The document is a user manual for the SUN2000 series inverters, detailing installation, electrical connections, commissioning, maintenance, and troubleshooting procedures. It is intended for photovoltaic plant operators and qualified electricians, emphasizing safety precautions and compliance with standards. The manual includes updates, safety information, and technical specifications relevant to the models SUN2000-196KTL-H3, SUN2000-200KTL-H3, and SUN2000-215KTL-H3.

Uploaded by

matheus.brisolla
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 125

SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)

User Manual

Issue 16
Date 2025-03-30

HUAWEI TECHNOLOGIES CO., LTD.


Copyright © Huawei Technologies Co., Ltd. 2025. All rights reserved.
No part of this document may be reproduced or transmitted in any form or by any means without prior
written consent of Huawei Technologies Co., Ltd.

Trademarks and Permissions

and other Huawei trademarks are trademarks of Huawei Technologies Co., Ltd.
All other trademarks and trade names mentioned in this document are the property of their respective
holders.

Notice
The purchased products, services and features are stipulated by the contract made between Huawei and
the customer. All or part of the products, services and features described in this document may not be
within the purchase scope or the usage scope. Unless otherwise specified in the contract, all statements,
information, and recommendations in this document are provided "AS IS" without warranties, guarantees
or representations of any kind, either express or implied.

The information in this document is subject to change without notice. Every effort has been made in the
preparation of this document to ensure accuracy of the contents, but all statements, information, and
recommendations in this document do not constitute a warranty of any kind, express or implied.

Huawei Technologies Co., Ltd.


Address: Huawei Industrial Base
Bantian, Longgang
Shenzhen 518129
People's Republic of China

Website: https://e.huawei.com

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. i


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual About This Document

About This Document

Purpose
This document describes the installation, electrical connections, commissioning,
maintenance, and troubleshooting of the SUN2000-196KTL-H3, SUN2000-200KTL-
H3, and SUN2000-215KTL-H3 (also referred to as SUN2000). Before installing and
operating the inverter, ensure that you are familiar with the features, functions,
and safety precautions provided in this document.

Intended Audience
This document is intended for photovoltaic (PV) plant operators and qualified
electricians.

Symbol Conventions
The symbols that may be found in this document are defined as follows.

Symbol Description

Indicates a hazard with a high level of risk which, if not


avoided, will result in death or serious injury.

Indicates a hazard with a medium level of risk which, if not


avoided, could result in death or serious injury.

Indicates a hazard with a low level of risk which, if not


avoided, could result in minor or moderate injury.

Indicates a potentially hazardous situation which, if not


avoided, could result in equipment damage, data loss,
performance deterioration, or unanticipated results.
NOTICE is used to address practices not related to personal
injury.

Supplements the important information in the main text.


NOTE is used to address information not related to personal
injury, equipment damage, and environment deterioration.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. ii


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual About This Document

Change History
Changes between document issues are cumulative. The latest document issue
contains all the changes made in earlier issues.

Issue 16 (2025-03-30)
Updated 2.2 Appearance.
Added 4.6 (Optional) Installing a Protective Tray.
Updated 7.1 App Operations.
Updated 10 Technical Specifications.
Updated C Grid Codes.

Issue 15 (2025-01-30)
Updated 5.7 Connecting DC Input Power Cables.
Updated 7.1.3.2 Setting Protection Parameters.
Updated 8.2 Power-Off for Maintenance.
Updated 10 Technical Specifications.

Issue 14 (2024-08-22)
Updated 10 Technical Specifications.

Issue 13 (2024-03-20)
Added 8.7 Locating Insulation Resistance Faults.
Updated C Grid Codes.

Issue 12 (2024-01-30)
Updated 2.1 Product Overview.
Updated 2.3.1 Enclosure Labels.
Updated 3 Storage Requirements.
Updated 4.3.1 Environment Requirements.
Updated 4.3.2 Clearance Requirements.
Updated 6.1 Checking Before Power-On.
Updated 7.2 Upgrading the Inverter.

Issue 11 (2023-12-20)
Updated 4.3.1 Environment Requirements.
Updated 5.1 Precautions.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. iii


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual About This Document

Updated 5.6 Connecting the AC Output Power Cable.


Updated 5.7 Connecting DC Input Power Cables.
Updated 8.5 Alarm Reference.
Updated E Contact Information.
Added F Digital Power Customer Service.

Issue 10 (2023-08-31)
Added 2.5 Smart I-V Curve Diagnosis.
Updated 5.7 Connecting DC Input Power Cables. Changed "During DC input
power cabling, leave at least 50 mm of slack." to "During DC input power cabling,
leave at least 150 mm of slack."

Issue 09 (2023-05-25)
Updated 2.1 Product Overview.

Issue 08 (2023-03-30)
Updated 2.1 Product Overview.

Issue 07 (2023-02-23)
Updated C Grid Codes.

Issue 06 (2022-11-30)
Updated 1 Safety Information.
Updated 2.1 Product Overview.
Updated 4.2 Preparing Tools.
Updated 4.5 Installing the Inverter.
Updated 5.6 Connecting the AC Output Power Cable.
Updated 7.1.1 Downloading and Installing the App.
Updated 8.5 Alarm Reference.
Added D Resetting Password.
Added E Contact Information.

Issue 05 (2022-05-10)
Updated 10 Technical Specifications.

Issue 04 (2022-02-20)
Updated 2.2 Appearance.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. iv


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual About This Document

Updated 2.3.1 Enclosure Labels.


Updated 4.3.1 Environment Requirements.
Updated 6.2 System Power-On.
Updated 8.3 Routine Maintenance.
Updated 8.6 Resetting and Turning On the DC SWITCH.

Issue 03 (2021-09-30)
Updated 2.2 Appearance.
Updated 5.3 Opening the Maintenance Compartment Door.
Updated 5.4 (Optional) Replacing the Crimping Module.
Updated 5.5 (Optional) Installing the Power Cable of the Tracking System.
Updated 5.6 Connecting the AC Output Power Cable.
Updated 5.9 Closing the Maintenance Compartment Door.

Issue 02 (2021-08-10)
Updated 6.2 System Power-On.
Updated 7.1.2 Logging In to the App.

Issue 01 (2021-05-30)
This issue is used for first office application (FOA).

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. v


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual Contents

Contents

About This Document................................................................................................................ ii


1 Safety Information.................................................................................................................. 1
1.1 Personal Safety.........................................................................................................................................................................2
1.2 Electrical Safety........................................................................................................................................................................ 4
1.3 Environment Requirements................................................................................................................................................. 7
1.4 Mechanical Safety................................................................................................................................................................... 9

2 Overview................................................................................................................................. 13
2.1 Product Overview..................................................................................................................................................................13
2.2 Appearance............................................................................................................................................................................. 15
2.3 Label Description.................................................................................................................................................................. 18
2.3.1 Enclosure Labels.................................................................................................................................................................18
2.3.2 Product Nameplate........................................................................................................................................................... 20
2.4 Working Principles................................................................................................................................................................ 20
2.4.1 Circuit Diagram.................................................................................................................................................................. 21
2.4.2 Working Modes.................................................................................................................................................................. 21
2.5 Smart I-V Curve Diagnosis................................................................................................................................................. 23

3 Storage Requirements..........................................................................................................24
4 Installation..............................................................................................................................26
4.1 Checking Before Installation............................................................................................................................................. 26
4.2 Preparing Tools...................................................................................................................................................................... 26
4.3 Determining the Installation Position............................................................................................................................ 28
4.3.1 Environment Requirements............................................................................................................................................28
4.3.2 Clearance Requirements................................................................................................................................................. 30
4.4 Installing the Mounting Bracket...................................................................................................................................... 33
4.4.1 Support-mounted Installation.......................................................................................................................................33
4.4.2 Wall-mounted Installation............................................................................................................................................. 34
4.5 Installing the Inverter.......................................................................................................................................................... 35
4.6 (Optional) Installing a Protective Tray.......................................................................................................................... 38

5 Electrical Connections.......................................................................................................... 40
5.1 Precautions.............................................................................................................................................................................. 40
5.2 Crimping an OT or DT Terminal...................................................................................................................................... 41

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. vi


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual Contents

5.3 Opening the Maintenance Compartment Door......................................................................................................... 44


5.4 (Optional) Replacing the Crimping Module................................................................................................................ 45
5.5 (Optional) Installing the Power Cable of the Tracking System............................................................................ 46
5.6 Connecting the AC Output Power Cable...................................................................................................................... 47
5.7 Connecting DC Input Power Cables................................................................................................................................53
5.8 Installing the Communications Cable............................................................................................................................ 57
5.9 Closing the Maintenance Compartment Door........................................................................................................... 60

6 System Commissioning........................................................................................................ 62
6.1 Checking Before Power-On................................................................................................................................................62
6.2 System Power-On................................................................................................................................................................. 63

7 Man-Machine Interactions.................................................................................................. 65
7.1 App Operations...................................................................................................................................................................... 65
7.1.1 Downloading and Installing the App..........................................................................................................................65
7.1.2 Logging In to the App...................................................................................................................................................... 66
7.1.3 Operations Related to the Advanced User............................................................................................................... 66
7.1.3.1 Setting Grid Parameters...............................................................................................................................................66
7.1.3.2 Setting Protection Parameters................................................................................................................................... 66
7.1.3.3 Setting Feature Parameters........................................................................................................................................ 67
7.1.4 Operations Related to the Special User.....................................................................................................................71
7.1.4.1 Setting Grid Parameters...............................................................................................................................................71
7.1.4.2 Setting Protection Parameters................................................................................................................................... 73
7.1.4.3 Setting Feature Parameters........................................................................................................................................ 75
7.1.4.4 Setting Power Adjustment Parameters...................................................................................................................80
7.2 Upgrading the Inverter....................................................................................................................................................... 83

8 Maintenance........................................................................................................................... 85
8.1 System Power-Off................................................................................................................................................................. 85
8.2 Power-Off for Maintenance.............................................................................................................................................. 86
8.3 Routine Maintenance.......................................................................................................................................................... 87
8.4 Replacing a Fan..................................................................................................................................................................... 89
8.5 Alarm Reference.................................................................................................................................................................... 93
8.6 Resetting and Turning On the DC SWITCH................................................................................................................. 93
8.7 Locating Insulation Resistance Faults............................................................................................................................ 94

9 Handling the Inverter...........................................................................................................97


9.1 Removing the SUN2000..................................................................................................................................................... 97
9.2 Packing the SUN2000.......................................................................................................................................................... 97
9.3 Disposing of the SUN2000................................................................................................................................................ 97

10 Technical Specifications.....................................................................................................98
A String Access Detection.....................................................................................................102
B Domain Name List of Management Systems...............................................................105

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. vii


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual Contents

C Grid Codes.............................................................................................................................106
D Resetting Password............................................................................................................ 112
E Contact Information........................................................................................................... 113
F Digital Power Customer Service...................................................................................... 115
G Acronyms and Abbreviations........................................................................................... 116

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. viii


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

1 Safety Information

Statement
Before transporting, storing, installing, operating, using, and/or maintaining
the equipment, read this document, strictly follow the instructions provided
herein, and follow all the safety instructions on the equipment and in this
document. In this document, "equipment" refers to the products, software,
components, spare parts, and/or services related to this document; "the Company"
refers to the manufacturer (producer), seller, and/or service provider of the
equipment; "you" refers to the entity that transports, stores, installs, operates,
uses, and/or maintains the equipment.

The Danger, Warning, Caution, and Notice statements described in this


document do not cover all the safety precautions. You also need to comply with
relevant international, national, or regional standards and industry practices. The
Company shall not be liable for any consequences that may arise due to
violations of safety requirements or safety standards concerning the design,
production, and usage of the equipment.

The equipment shall be used in an environment that meets the design


specifications. Otherwise, the equipment may be faulty, malfunctioning, or
damaged, which is not covered under the warranty. The Company shall not be
liable for any property loss, personal injury, or even death caused thereby.

Comply with applicable laws, regulations, standards, and specifications during


transportation, storage, installation, operation, use, and maintenance.

Do not perform reverse engineering, decompilation, disassembly, adaptation,


implantation, or other derivative operations on the equipment software. Do not
study the internal implementation logic of the equipment, obtain the source code
of the equipment software, violate intellectual property rights, or disclose any of
the performance test results of the equipment software.

The Company shall not be liable for any of the following circumstances or
their consequences:

● The equipment is damaged due to force majeure such as earthquakes, floods,


volcanic eruptions, debris flows, lightning strikes, fires, wars, armed conflicts,
typhoons, hurricanes, tornadoes, and other extreme weather conditions.
● The equipment is operated beyond the conditions specified in this document.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 1


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

● The equipment is installed or used in environments that do not comply with


international, national, or regional standards.
● The equipment is installed or used by unqualified personnel.
● You fail to follow the operation instructions and safety precautions on the
product and in the document.
● You remove or modify the product or modify the software code without
authorization.
● You or a third party authorized by you cause the equipment damage during
transportation.
● The equipment is damaged due to storage conditions that do not meet the
requirements specified in the product document.
● You fail to prepare materials and tools that comply with local laws,
regulations, and related standards.
● The equipment is damaged due to your or a third party's negligence,
intentional breach, gross negligence, or improper operations, or other reasons
not related to the Company.

1.1 Personal Safety

DANGER

Ensure that power is off during installation. Do not install or remove a cable with
power on. Transient contact between the core of the cable and the conductor will
generate electric arcs or sparks, which may cause a fire or personal injury.

DANGER

Non-standard and improper operations on the energized equipment may cause


fire, electric shocks, or explosion, resulting in property damage, personal injury, or
even death.

DANGER

Before operations, remove conductive objects such as watches, bracelets, bangles,


rings, and necklaces to prevent electric shocks.

DANGER

During operations, use dedicated insulated tools to prevent electric shocks or short
circuits. The dielectric withstanding voltage level must comply with local laws,
regulations, standards, and specifications.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 2


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

WARNING

During operations, wear personal protective equipment such as protective


clothing, insulated shoes, goggles, safety helmets, and insulated gloves.

Figure 1-1 Personal protective equipment

General Requirements
● Do not stop protective devices. Pay attention to the warnings, cautions, and
related precautionary measures in this document and on the equipment.
● If there is a likelihood of personal injury or equipment damage during
operations, immediately stop, report the case to the supervisor, and take
feasible protective measures.
● Do not power on the equipment before it is installed or confirmed by
professionals.
● Do not touch the power supply equipment directly or with conductors such as
damp objects. Before touching any conductor surface or terminal, measure
the voltage at the contact point to ensure that there is no risk of electric
shock.
● Do not touch operating equipment because the enclosure is hot.
● Do not touch a running fan with your hands, components, screws, tools, or
boards. Otherwise, personal injury or equipment damage may occur.
● In the case of a fire, immediately leave the building or the equipment area
and activate the fire alarm or call emergency services. Do not enter the
affected building or equipment area under any circumstances.

Personnel Requirements
● Only professionals and trained personnel are allowed to operate the
equipment.
– Professionals: personnel who are familiar with the working principles and
structure of the equipment, trained or experienced in equipment
operations and are clear of the sources and degree of various potential
hazards in equipment installation, operation, maintenance

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 3


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

– Trained personnel: personnel who are trained in technology and safety,


have required experience, are aware of possible hazards on themselves in
certain operations, and are able to take protective measures to minimize
the hazards on themselves and other people
● Personnel who plan to install or maintain the equipment must receive
adequate training, be able to correctly perform all operations, and understand
all necessary safety precautions and local relevant standards.
● Only qualified professionals or trained personnel are allowed to install,
operate, and maintain the equipment.
● Only qualified professionals are allowed to remove safety facilities and inspect
the equipment.
● Personnel who will perform special tasks such as electrical operations,
working at heights, and operations of special equipment must possess the
required local qualifications.
● Only authorized professionals are allowed to replace the equipment or
components (including software).
● Only personnel who need to work on the equipment are allowed to access
the equipment.

1.2 Electrical Safety

DANGER

Before connecting cables, ensure that the equipment is intact. Otherwise, electric
shocks or fire may occur.

DANGER

Non-standard and improper operations may result in fire or electric shocks.

DANGER

Prevent foreign matter from entering the equipment during operations. Otherwise,
equipment short-circuits or damage, load power derating, power failure, or
personal injury may occur.

WARNING

For the equipment that needs to be grounded, install the ground cable first when
installing the equipment and remove the ground cable last when removing the
equipment.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 4


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

WARNING

During the installation of PV strings and the inverter, the positive or negative
terminals of PV strings may be short-circuited to ground if the power cables are
not properly installed or routed. In this case, an AC or DC short circuit may occur
and damage the inverter. The resulting device damage is not covered under any
warranty.

CAUTION

Do not route cables near the air intake or exhaust vents of the equipment.

General Requirements
● Follow the procedures described in the document for installation, operation,
and maintenance. Do not reconstruct or alter the equipment, add
components, or change the installation sequence without permission.
● Obtain approval from the national or local electric utility company before
connecting the equipment to the grid.
● Observe the power plant safety regulations, such as the operation and work
ticket mechanisms.
● Install temporary fences or warning ropes and hang "No Entry" signs around
the operation area to keep unauthorized personnel away from the area.
● Before installing or removing power cables, turn off the switches of the
equipment and its upstream and downstream switches.
● Before performing operations on the equipment, check that all tools meet the
requirements and record the tools. After the operations are complete, collect
all of the tools to prevent them from being left inside the equipment.
● Before installing power cables, check that cable labels are correct and cable
terminals are insulated.
● When installing the equipment, use a torque tool of a proper measurement
range to tighten the screws. When using a wrench to tighten the screws,
ensure that the wrench does not tilt and the torque error does not exceed
10% of the specified value.
● Ensure that bolts are tightened with a torque tool and marked in red and blue
after double-check. Installation personnel mark tightened bolts in blue.
Quality inspection personnel confirm that the bolts are tightened and then
mark them in red. (The marks must cross the edges of the bolts.)

● If the equipment has multiple inputs, disconnect all the inputs and wait until
the equipment is completely powered off before performing operations on the
equipment.
● Before maintaining a downstream electrical or power distribution device, turn
off the output switch on the power supply equipment.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 5


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

● During equipment maintenance, attach "Do not switch on" labels near the
upstream and downstream switches or circuit breakers as well as warning
signs to prevent accidental connection. The equipment can be powered on
only after troubleshooting is complete.
● Do not open equipment panels.
● Check equipment connections periodically, ensuring that all screws are
securely tightened.
● Only qualified professionals can replace a damaged cable.
● Do not scrawl, damage, or block any labels or nameplates on the equipment.
Promptly replace labels that have worn out.
● Do not use solvents such as water, alcohol, or oil to clean electrical
components inside or outside of the equipment.

Grounding
● Ensure that the grounding impedance of the equipment complies with local
electrical standards.
● Ensure that the equipment is connected permanently to the protective
ground. Before operating the equipment, check its electrical connection to
ensure that it is reliably grounded.
● Do not work on the equipment in the absence of a properly installed ground
conductor.
● Do not damage the ground conductor.

Cabling Requirements
● When selecting, installing, and routing cables, follow local safety regulations
and rules.
● When routing power cables, ensure that there is no coiling or twisting. Do not
join or weld power cables. If necessary, use a longer cable.
● Ensure that all cables are properly connected and insulated, and meet
specifications.
● Ensure that the slots and holes for routing cables are free from sharp edges,
and that the positions where cables are routed through pipes or cable holes
are equipped with cushion materials to prevent the cables from being
damaged by sharp edges or burrs.
● Ensure that cables of the same type are bound together neatly and straight
and that the cable sheath is intact. When routing cables of different types,
ensure that they are away from each other without entanglement and
overlapping.
● Secure buried cables using cable supports and cable clips. Ensure that the
cables in the backfill area are in close contact with the ground to prevent
cable deformation or damage during backfilling.
● If the external conditions (such as the cable layout or ambient temperature)
change, verify the cable usage in accordance with the IEC-60364-5-52 or local
laws and regulations. For example, check that the current-carrying capacity
meets requirements.
● When routing cables, reserve at least 30 mm clearance between the cables
and heat-generating components or areas. This prevents deterioration or
damage to the cable insulation layer.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 6


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

1.3 Environment Requirements

DANGER

Do not expose the equipment to flammable or explosive gas or smoke. Do not


perform any operation on the equipment in such environments.

DANGER

Do not store any flammable or explosive materials in the equipment area.

DANGER

Do not place the equipment near heat sources or fire sources, such as smoke,
candles, heaters, or other heating devices. Overheat may damage the equipment
or cause a fire.

WARNING

Install the equipment in an area far away from liquids. Do not install it under
areas prone to condensation, such as under water pipes and air exhaust vents, or
areas prone to water leakage, such as air conditioner vents, ventilation vents, or
feeder windows of the equipment room. Ensure that no liquid enters the
equipment to prevent faults or short circuits.

WARNING

To prevent damage or fire due to high temperature, ensure that the ventilation
vents or heat dissipation systems are not obstructed or covered by other objects
while the equipment is running.

General Requirements
● Store the equipment according to the storage requirements. Equipment
damage caused by unqualified storage conditions is not covered under the
warranty.
● Keep the installation and operating environments of the equipment within the
allowed ranges. Otherwise, its performance and safety will be compromised.
● The operating temperature range provided in the equipment's technical
specifications refers to the ambient temperatures in equipment's installation
environment.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 7


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

● Do not install, use, or operate outdoor equipment and cables (including but
not limited to moving equipment, operating equipment and cables, inserting
connectors to or removing connectors from signal ports connected to outdoor
facilities, working at heights, performing outdoor installation, and opening
doors) in harsh weather conditions such as lightning, rain, snow, and level 6
or stronger wind.
● Do not install the equipment in an environment with dust, smoke, volatile or
corrosive gases, infrared and other radiations, organic solvents, or salty air.
● Do not install the equipment in an environment with conductive metal or
magnetic dust.
● Do not install the equipment in an area conducive to the growth of
microorganisms such as fungus or mildew.
● Do not install the equipment in an area with strong vibration, noise, or
electromagnetic interference. The equipment shall be installed in an
environment with a magnetic field strength less than 4 Gauss. If the magnetic
field strength is greater than or equal to 4 Gauss, the equipment may fail to
work properly. If the magnetic field strength is high, for example, in a
smeltery, you are advised to use a gauss meter to measure the magnetic field
strength of the equipment installation position when the smelting equipment
is running normally.
● Ensure that the site complies with local laws, regulations, and related
standards.
● Ensure that the ground in the installation environment is solid, free from
spongy or soft soil, and not prone to subsidence. The site must not be located
in a low-lying land prone to water or snow accumulation, and the horizontal
level of the site must be above the highest water level of that area in history.
● Do not install the equipment in a position that may be submerged in water.
● If the equipment is installed in a place with abundant vegetation, in addition
to routine weeding, harden the ground underneath the equipment using
cement or gravel (the area shall be greater than or equal to 3 m x 2.5 m).
● Do not install the equipment outdoors in salt-affected areas because it may
be corroded. A salt-affected area refers to the region within 500 m of the
coast or prone to sea breeze. Regions prone to sea breeze vary with weather
conditions (such as typhoons and monsoons) or terrains (such as dams and
hills).
● Before opening doors during the installation, operation, and maintenance of
the equipment, clean up any water, ice, snow, or other foreign objects on the
top of the equipment to prevent foreign objects from falling into the
equipment.
● When installing the equipment, ensure that the installation surface is solid
enough to bear the weight of the equipment.
● After installing the equipment, remove the packing materials such as cartons,
foam, plastics, and cable ties from the equipment area.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 8


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

1.4 Mechanical Safety

WARNING

Ensure that all necessary tools are ready and inspected by a professional
organization. Do not use tools that have signs of scratches or fail to pass the
inspection or whose inspection validity period has expired. Ensure that the tools
are secure and not overloaded.

WARNING

Do not drill holes into the equipment. Doing so may affect the sealing
performance and electromagnetic containment of the equipment and damage
components or cables inside. Metal shavings from drilling may short-circuit boards
inside the equipment.

General Requirements
● Repaint any paint scratches caused during equipment transportation or
installation in a timely manner. Equipment with scratches must not be
exposed for an extended period of time.
● Do not perform operations such as arc welding and cutting on the equipment
without evaluation by the Company.
● Do not install other devices on the top of the equipment without evaluation
by the Company.
● When performing operations over the top of the equipment, take measures to
protect the equipment against damage.
● Use correct tools and operate them in the correct way.

Moving Heavy Objects


● Be cautious to prevent injury when moving heavy objects.

● If multiple persons need to move a heavy object together, determine the


manpower and work division with consideration of height and other
conditions to ensure that the weight is equally distributed.
● If two persons or more move a heavy object together, ensure that the object
is lifted and landed simultaneously and moved at a uniform pace under the
supervision of one person.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 9


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

● Wear personal protective gears such as protective gloves and shoes when
manually moving the equipment.
● To move an object by hand, approach to the object, squat down, and then lift
the object gently and stably by the force of the legs instead of your back. Do
not lift it suddenly or turn your body around.
● Do not quickly lift a heavy object above your waist. Place the object on a
workbench that is half-waist high or any other appropriate place, adjust the
positions of your palms, and then lift it.
● Move a heavy object stably with balanced force at an even and low speed. Put
down the object stably and slowly to prevent any collision or drop from
scratching the surface of the equipment or damaging the components and
cables.
● When moving a heavy object, be aware of the workbench, slope, staircase,
and slippery places. When moving a heavy object through a door, ensure that
the door is wide enough to move the object and avoid bumping or injury.
● When transferring a heavy object, move your feet instead of turning your
waist around. When lifting and transferring a heavy object, ensure that your
feet point to the target direction of movement.
● When transporting the equipment using a pallet truck or forklift, ensure that
the tynes are properly positioned so that the equipment does not topple.
Before moving the equipment, secure it to the pallet truck or forklift using
ropes. When moving the equipment, assign dedicated personnel to take care
of it.
● Choose sea, roads in good conditions, or airplanes for transportation. Do not
transport the equipment by railway. Avoid tilt or jolt during transportation.

Using Ladders
● Use wooden or insulated ladders when you need to perform live-line working
at heights.
● Platform ladders with protective rails are preferred. Single ladders are not
recommended.
● Before using a ladder, check that it is intact and confirm its load bearing
capacity. Do not overload it.
● Ensure that the ladder is securely positioned and held firm.

● When climbing up the ladder, keep your body stable and your center of
gravity between the side rails, and do not overreach to the sides.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 10


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

● When a step ladder is used, ensure that the pull ropes are secured.
● If a single ladder is used, the recommended angle for the ladder against the
floor is 75 degrees, as shown in the following figure. A square can be used to
measure the angle.

● If a single ladder is used, ensure that the wider end of the ladder is at the
bottom, and take protective measures to prevent the ladder from sliding.
● If a single ladder is used, do not climb higher than the fourth rung of the
ladder from the top.
● If you use a single ladder to climb up to a platform, ensure that the ladder is
at least 1 m higher than the platform.

Hoisting
● Only trained and qualified personnel are allowed to perform hoisting
operations.
● Install temporary warning signs or fences to isolate the hoisting area.
● Ensure that the foundation where hoisting is performed on meets the load-
bearing requirements.
● Before hoisting objects, ensure that hoisting tools are firmly secured onto a
fixed object or wall that meets the load-bearing requirements.
● During hoisting, do not stand or walk under the crane or the hoisted objects.
● Do not drag steel ropes and hoisting tools or bump the hoisted objects
against hard objects during hoisting.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 11


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 1 Safety Information

● Ensure that the angle between two hoisting ropes is no more than 90
degrees, as shown in the following figure.

Drilling Holes
● Obtain consent from the customer and contractor before drilling holes.
● Wear protective equipment such as safety goggles and protective gloves when
drilling holes.
● To avoid short circuits or other risks, do not drill holes into buried pipes or
cables.
● When drilling holes, protect the equipment from shavings. After drilling, clean
up any shavings.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 12


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

2 Overview

2.1 Product Overview

Function
The SUN2000 is a three-phase grid-tied PV string inverter that converts the DC
power generated by PV strings into AC power and feeds the power into the power
grid.

Model
This document involves the following product models:
● SUN2000-196KTL-H3
● SUN2000-200KTL-H3
● SUN2000-215KTL-H3

Figure 2-1 Model (SUN2000-196KTL-H3 is used as an example)

Table 2-1 Model description

No. Meaning Description

1 Product family identifier SUN2000: three-phase grid-tied PV


string inverter

2 Power level identifier 196K: The power level is 196 kW.


200K: The power level is 185 kW.
215K: The power level is 200 kW.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 13


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

No. Meaning Description

3 Topology identifier TL: transformerless

4 Product series identifier H3: product series with an input


voltage level of 1500 V DC

NOTE

● The SUN2000-196KTL-H3 is applicable only to the Chinese mainland. For other


countries or regions, Huawei does not provide quality assurance.
● The SUN2000-196KTL-H3, SUN2000-200KTL-H3, and SUN2000-215KTL-H3 inverters
described in this document must not be connected to a winding (of the transformer
station) that has other models of inverters connected to it.

Networking Application
The SUN2000 applies to grid-tied PV systems for commercial rooftop projects and
utility-scale plants. Typically, a grid-tied PV system consists of the PV string,
SUN2000, AC power distribution unit, and step-up transformer.

Figure 2-2 Networking application

(A) PV string (B) SUN2000 (C) AC power distribution unit

(D) Step-up transformer (E) Power grid -

NOTE

The SUN2000 is powered by a dedicated power transformer instead of connecting to low-


voltage overhead power lines.

Supported Earthing Systems


The SUN2000 supports the IT earthing system.

Figure 2-3 Earthing system

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 14


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

NOTE

The SUN2000 supports the IT earthing system in PV-only scenarios. The use of the
SUN2000 in other types of earthing systems, such as TT, TN-C, and TN-C-S, is not
recommended. (If such an earthing system is encountered, contact the Company's
engineers.)

2.2 Appearance

Dimensions

Front View

(1) PV connection (2) Grid connection (3) Communication


indicator indicator indicator
(4) Alarm/Maintenance (5) Panel (6) Maintenance
indicator compartment

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 15


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

Table 2-2 LED indicator description


Category Indicator Status Description

PV indication LED1 LED4 -

Steady - At least one PV string is properly connected, and


green the DC input voltage of the corresponding MPPT
circuit is higher than or equal to 500 V.

Blinking Red An environmental fault occurred on the DC side.


green fast

Off - The inverter disconnects from all PV strings, or the


DC input voltages of all MPPT circuits are less than
500 V.

Grid LED2 LED4 -


connection
indication Steady - The inverter is in grid-tied mode.
green

Blinking Red An environmental fault occurred on the AC side.


green fast

Off - The inverter is not in grid-tied mode.

Communicatio LED3 -
n indication
Blinking green fast The inverter receives data over RS485 or MBUS.

Off The inverter has not received data over RS485 or


MBUS for 10 seconds.

Alarm/ LED4 -
Maintenance
indication Steady red A major alarm was generated.
If neither the PV connection indicator nor the grid
connection indicator is blinking green fast, replace
components or the inverter as instructed by the
SUN2000 app.

Blinking red fast A minor alarm was generated.

Blinking red slowly A warning alarm was generated.

Steady green The local maintenance is successful.

Blinking green slowly The device is under local maintenance or shut


down after receiving a command.

Blinking green fast The local maintenance failed.

Off There is no alarm, and no local maintenance


operations are performed.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 16


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

NOTE

● Local maintenance refers to operations performed after a USB flash drive or USB data
cable is inserted into the USB port of the inverter. For example, import and export
configurations using a USB flash drive, or connect to the SUN2000 app using a USB data
cable.
● If the alarming and the local maintenance happen concurrently, the alarm/maintenance
indicator shows the local maintenance state first. After the USB flash drive or USB data
cable is removed, the indicator shows the alarm state.
● iOS mobile phones do not support connection to the app using a USB data cable. You
are advised to use the SmartLogger for O&M.

Bottom View

(1) DC input terminals (controlled by DC (2) DC switch 1 (DC SWITCH 1)


SWITCH 1)
(3) Reset button 1 (RESET 1) (4) DC input terminals (controlled
by DC SWITCH 2)
(5) DC switch 2 (DC SWITCH 2) (6) Reset button 2 (RESET 2)
(7) DC input terminals (controlled by DC (8) DC switch 3 (DC SWITCH 3)
SWITCH 3)
(9) Reset button 3 (RESET 3) (10) Ventilation valve
(11) USB port (USB) (12) Communications port (COM)
(13) AC output power cable hole (14) Tracking system power cable
hole

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 17


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

DC Switch Description

DANGER

● The DC switches automatically turn off when the inverter reports the String
Reverse Connection or String Current Backfeed alarm. Check the fault type
on the mobile app. After the fault is rectified, press down the RESET button
and then turn on the switches. For details, see 8.6 Resetting and Turning On
the DC SWITCH.
● The DC switches automatically turn off if a fault occurs in the inverter (LED4 is
steady red, and the three DC switches are off). In this case, contact technical
support and do not turn on the DC switches by yourself.

Table 2-3 DC switch description

Switch Description

DC ON The DC switch is on and can be automatically turned


SWITCH off for protection.

The DC switch is on but cannot be automatically turned


off for protection.

OFF The DC switch is off.

RESET ● When the DC switch is automatically turned off for protection,


the RESET button will be released.
● If the RESET button is not pressed, the DC switch can only be
turned to the marked position and cannot be set to the
ON position.

2.3 Label Description

2.3.1 Enclosure Labels

Symbol Name Meaning

Operation warning Potential hazards exist after the


inverter is powered on. Take
protective measures when operating
the inverter.

High temperature Do not touch the inverter when it is


hazard running because its enclosure is hot.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 18


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

Symbol Name Meaning

Electric shock hazard Hazardous voltage exists after the


device is powered on. Take protective
measures during operation and
maintenance (O&M).

Delayed discharge ● High voltage exists after the


inverter is powered on. Only
qualified and trained electrical
technicians are allowed to
perform operations on the
inverter.
● Residual voltage exists after the
inverter is powered off. It takes 15
minutes for the inverter to
discharge to the safe voltage.

Refer to Reminds operators to refer to the


documentation documentation for the device. Losses
caused by operations that do not
comply with the requirements of site
selection, storage, or mounting
specified in the user manual are not
covered under the warranty.

Grounding Indicates the position for connecting


the protective earthing (PE) cable.

Operation warning Do not remove the DC input


connector when the inverter is
running.

Switch operation If the energy of the DC switch is


warning discharged, it may fail to switch off
automatically.

Switch energy This position indicates that the


discharge warning energy of the DC switch is
discharged. Do not set the DC switch
to this position.

Fan operation warning High voltage exists after the inverter


is powered on. Do not touch the fans
when the inverter is working.

Fan replacement Before replacing the fan, disconnect


warning its power connector.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 19


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

Symbol Name Meaning

Inverter SN label Indicates the inverter serial number.

Weight label The inverter needs to be carried by


four persons or using a forklift.

2.3.2 Product Nameplate

Figure 2-4 Nameplate (SUN2000-196KTL-H3 is used as an example)

(1) Trademark and product model (2) Important technical specifications

(3) Compliance symbols (4) Company name and country of


manufacture

NOTE

The nameplate figure is for reference only.

2.4 Working Principles

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 20


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

2.4.1 Circuit Diagram


The inverter receives inputs from 14 PV strings. Then the inputs are grouped into
three MPPT circuits inside the inverter to track the maximum power point of the
PV strings. The DC power is then converted into three-phase AC power through an
inverter circuit. Surge protection is supported on both the DC and AC sides.

Figure 2-5 Inverter conceptual diagram

2.4.2 Working Modes


The SUN2000 can work in Standby, Operating, or Shutdown mode.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 21


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

Figure 2-6 Working modes

Table 2-4 Working mode description


Working Description
Mode

Standby The SUN2000 enters Standby mode when the external


environment does not meet the operating requirements. In
Standby mode:
● The SUN2000 continuously performs status check and enters
the Operating mode once the operating requirements are met.
● The SUN2000 enters Shutdown mode after detecting a
shutdown command or a fault after startup.

Operating In Operating mode:


● The SUN2000 converts DC power from PV strings into AC power
and feeds the power to the power grid.
● The SUN2000 tracks the maximum power point to maximize
the PV string output.
● If the SUN2000 detects a fault or a shutdown command, it
enters the Shutdown mode.
● The SUN2000 enters Standby mode after detecting that the PV
string output power is not suitable for connecting to the power
grid for generating power.

Shutdown ● In Standby or Operating mode, the SUN2000 enters Shutdown


mode after detecting a fault or shutdown command.
● In Shutdown mode, the SUN2000 enters Standby mode after
detecting a startup command or that the fault is rectified.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 22


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 2 Overview

2.5 Smart I-V Curve Diagnosis


The inverter supports the Smart I-V Curve Diagnosis function. For details, see the
iMaster NetEco V600R023C00 Smart I-V Curve Diagnosis User Manual.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 23


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 3 Storage Requirements

3 Storage Requirements

NOTICE

Store the device according to the storage requirements. Device damage caused by
unqualified storage conditions is not covered under the warranty.

If inverters will not be put into use immediately, store them according to the
requirements specified in this section. Device damage caused by unqualified
storage conditions is not covered under the warranty.
● Do not store the device without outer packaging.
● Do not remove the outer packaging. Check the packaging regularly
(recommended: once every three months). Replace any packaging that is
damaged during storage. If the inverter is unpacked but will not be used
immediately, put it back to the original packaging with the desiccant, and seal
with tape.
● Inverters must be stored in a clean and dry environment with appropriate
temperature and humidity. The air must not contain corrosive or flammable
gases.

Figure 3-1 Storage temperature and humidity

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 24


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 3 Storage Requirements

● When temporarily storing inverters outdoors, do not stack them on a pallet.


Take rainproof measures such as using tarpaulins to protect inverters from
rain and water.
● Do not tilt a packing case or place it upside down.
● To avoid personal injury or device damage, stack inverters with caution to
prevent them from falling over.

Figure 3-2 Maximum number of stacking layers

● Do not store inverters for more than two years. If inverters have been stored
for two years or longer, they must be checked and tested by professionals
before being put into use.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 25


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

4 Installation

4.1 Checking Before Installation


Outer Packing Materials
Before unpacking the inverter, check the outer packing materials for damage, such
as holes and cracks, and check the inverter model. If any damage is found or the
inverter model is not what you requested, do not unpack the package and contact
your supplier as soon as possible.

NOTE

You are advised to remove the packing materials within 24 hours before installing the
inverter.

Package Contents

NOTICE

● After placing the equipment in the installation position, unpack it with care to
prevent scratches. Keep the equipment stable during unpacking.

After unpacking the inverter, check that the contents are intact and complete. If
any damage is found or any component is missing, contact your supplier.

NOTE

For details about the number of contents, see the Packing List in the packing case.

4.2 Preparing Tools

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 26


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Type Tool

Hammer drill Drill bit (Ф14 mm Insulated torque Diagonal pliers


and Ф16 mm) socket wrench
(including an
extension bar)

Wire stripper Flat-head insulated Rubber mallet Utility knife


torque screwdriver
Head: 0.6 mm x 3.5
mm
Installation
tools

Cable cutter Crimping tool Removal wrench Vacuum cleaner


Model: PV- Model: 13001462;
CZM-41100; manufacturer:
manufacturer: Staubli
Staubli

Multimeter Marker Measuring tape Bubble or digital


DC voltage level
measurement range
≥ 1500 V DC

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 27


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Type Tool

Hydraulic pliers Heat shrink tubing Heat gun Cable tie

Personal
protective Protective gloves Safety goggles Dust mask Safety boots
equipment
- - -
(PPE)

Insulated gloves

4.3 Determining the Installation Position

4.3.1 Environment Requirements

Basic Requirements
● Do not install the inverter in working or living areas to avoid personal injury
or property loss caused by accidental contact by non-professionals or other
reasons during device operation.
● Do not install the inverter in noise-sensitive areas (such as residential areas,
office areas, and schools) to avoid complaints. If the preceding areas are
unavoidable, the distance between the installation position and noise-
sensitive areas must be greater than or equal to 40 m. Alternatively, use other
low-noise models.
● If the inverter is installed in public places (such as parking lots, stations, and
factories) other than working and living areas, install a protective net outside
the device and set up a safety warning sign to isolate the device. This is to
avoid personal injury or property loss caused by accidental contact by non-
professionals or other reasons during device operation.
● If the inverter is installed in a place with abundant vegetation, in addition to
routine weeding, harden the ground underneath the inverter using cement or
gravel (the area shall be greater than or equal to 3 m x 2.5 m).

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 28


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

● Do not install the inverter in areas containing flammable materials (such as


sulfur, phosphorus, liquefied petroleum gas, marsh gas, flour, and cotton) to
avoid personal injury or property loss caused by fire or other reasons.
● Do not install the inverter in areas containing explosives (such as blasting
agents, display shells, fireworks, and firecrackers) to avoid personal injury or
property loss caused by explosion or other reasons.
● Do not install the inverter in areas with corrosive substances (such as sulfuric
acid, hydrochloric acid, nitric acid, hydrogen sulfide, and chlorine) to avoid
inverter failure caused by corrosion, which is not covered under the warranty.
● Do not install the inverter in an easily accessible place, because the voltage is
high and its enclosure and heat sink are hot during device operation. This is to
avoid personal injury or property loss caused by accidental contact by non-
professionals or other reasons during device operation.
● Install the inverter in a well-ventilated environment to ensure good heat
dissipation. The inverter provides self-protection in high-temperature
environments. If the inverter is installed in a poorly ventilated environment,
its energy yield may decrease as the ambient temperature increases.
● Do not install the equipment in an area with strong vibration, noise, or
electromagnetic interference. The equipment shall be installed in an
environment with a magnetic field strength less than 4 Gauss. If the magnetic
field strength is greater than or equal to 4 Gauss, the equipment may fail to
work properly. If the magnetic field strength is high, for example, in a
smeltery, you are advised to use a gauss meter to measure the magnetic field
strength of the equipment installation position when the smelting equipment
is running normally.
● If the inverter is installed in an enclosed environment, a heat dissipation
device or ventilation device shall be installed. The indoor ambient
temperature must not be higher than the outdoor ambient temperature. The
inverter provides self-protection in high-temperature environments. Its energy
yield may decrease as the ambient temperature increases.
● Install the inverter in a sheltered place to prevent exposure to direct sunlight.
The inverter provides self-protection in high-temperature environments. If the
inverter is installed in a place subject to direct sunlight, its energy yield may
decrease as the temperature increases.
● If you need to install the inverter outdoors in salt-affected areas that may
cause corrosion, contact technical support. A salt-affected area refers to a
region within 500 m of the coast or prone to sea breeze. Regions prone to sea
breeze vary with weather conditions (such as typhoons and monsoons) or
terrains (such as dams and hills).
● The positive and negative DC PV string cables within 1.5 m of the inverter
shall be routed in separate pipes to prevent cable damage and short circuits
caused by improper operations during construction. For details, see Figure
5-1.
● The distance between each inverter and the AC combiner box or the low-
voltage panel of the transformer station must be at least 10 m, or the total
distances from two adjacent inverters to the AC combiner box or the low-
voltage panel of the transformer station must be at least 20 m. The inverter
provides output resonance self-protection. Its energy yield may decrease if
protection against resonance is triggered as the length of the inverter output
cables decreases.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 29


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

● Take waterproof and insulation measures for unused DC power cables. High
voltage may exist in unused DC power cables. Take measures to prevent
personal injury or property damage caused by accidental contact with high
voltage or other reasons.
● Cables must be vertically routed into combiner boxes and wiring terminals to
avoid damage caused by horizontal stress on the terminals, which is not
covered under the warranty.
● If an inverter has not been running for six months or longer after being
mounted, it may have failed and must be checked and tested by professionals
before being put into operation.
● To prevent the inverter from being corroded by moisture, PV terminals that
will not be used for a long time must be sealed with dedicated PV terminal
plugs. Inverter failure due to not using dedicated PV terminal plugs is not
covered under the warranty.

Mounting Structure Requirements


● The mounting structure for the inverter must be fireproof. Do not install the
inverter on flammable building materials to avoid personal injury or property
loss caused by fire or other reasons.
● Do not install the inverter on flammable building materials.
● Ensure that the installation surface is solid enough to bear the weight of the
inverter to avoid personal injury or property loss caused by the collapse of the
mounting structure or other reasons.
● In residential areas, do not install the inverter on a drywall or wall made of
similar materials which have a weak sound insulation performance because
the inverter generates noise during operation.

Figure 4-1 Mounting structure

4.3.2 Clearance Requirements


● Reserve sufficient clearance around the inverter for installation and heat
dissipation. The inverter provides self-protection in high-temperature
environments. The impact of environment changes on the clearance for heat
dissipation needs be considered during design. The clearance around the
inverter may become insufficient for reasons such as rotation axis change. The
energy yield of the inverter may decrease if heat cannot be effectively
dissipated.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 30


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Figure 4-2 Clearance

NOTE

The clearance from the bottom must meet the requirements on the bending radius of
the AC output power cables.

Figure 4-3 Installation angle

● When installing multiple SUN2000s, install them in horizontal mode if


sufficient space is available and install them in triangle mode if no sufficient
space is available. Stacked installation is not recommended.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 31


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Figure 4-4 Horizontal installation (recommended)

Figure 4-5 Triangle installation mode (recommended)

Figure 4-6 Stacked installation mode (not recommended)

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 32


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

4.4 Installing the Mounting Bracket


Installation Precautions
Figure 4-7 shows the inverter mounting bracket dimensions.

Figure 4-7 Mounting bracket dimensions

NOTE

The inverter mounting bracket has four groups of tapped holes, each group containing four
tapped holes. Mark any hole in each group based on site requirements and mark four holes
in total. The two round holes are recommended.

Before installing the mounting bracket, remove the security torx wrench from the
mounting bracket and set it aside.

Figure 4-8 Removing a security torx wrench

4.4.1 Support-mounted Installation

Support-mounted Installation
Step 1 Install the mounting bracket.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 33


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Figure 4-9 Installing the mounting bracket

NOTE

The M12x40 bolt assemblies are delivered with the SUN2000 (bound to the mounting
bracket). If the bolt assembly length does not meet the installation requirements, prepare
M12 bolt assemblies by yourself and use them together with the delivered M12 nuts.

----End

4.4.2 Wall-mounted Installation

Wall-mounted Installation
Step 1 Install the mounting bracket.

WARNING

Avoid drilling holes in the water pipes and power cables buried in the wall.

NOTICE

● To prevent dust inhalation or contact with eyes, wear safety goggles and an
anti-dust respirator when drilling holes.
● Clean up any dust in and around the holes using a vacuum cleaner and
measure the distance between holes. If the holes are inaccurately positioned,
drill a new set of holes.
● Level the head of the expansion sleeve with the concrete wall after removing
the bolt, spring washer, and flat washer. Otherwise, the mounting bracket will
not be securely installed on the wall.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 34


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Figure 4-10 Securing the mounting bracket

----End

4.5 Installing the Inverter


Preparing for the Installation
Before installing the inverter, take it out from the packing case and move it to the
installation position.

NOTE

● Handles are packed in a fitting bag and are not delivered with the inverter.
● Secure the lifting handles (with the steel washers of the lifting handles closely fitted to
the device).
● If the stud of a lifting handle is bent, replace the lifting handle in time.

Figure 4-11 Taking out and moving the inverter

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 35


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

NOTICE

● Move the inverter with the help of other three persons or using an appropriate
transportation tool.
● Do not place the inverter with its wiring terminals at the bottom contacting the
floor or any other objects because the terminals are not designed to bear the
weight of the inverter.
● When you need to temporally place the inverter on the ground, use foam,
paper, or other protection material to prevent damage to its cover.
● Do not lift or hoist the inverter using the bottom holes of the handles to
prevent the handles from cracking.

Figure 4-12 Lifting positions

Installing the Inverter


Step 1 Mount the inverter on the mounting bracket.
Step 2 Tighten the two screws at the bottom of the inverter.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 36


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Figure 4-13 Installation

----End

Supplementary Notes
If the inverter is installed in a high position, you can hoist it.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 37


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Figure 4-14 Hoisting the inverter

4.6 (Optional) Installing a Protective Tray


Preparations

NOTICE

● If the ground under the inverter cannot be hardened, it is recommended that a


protective tray be installed.
● The protective tray needs to be purchased by the customer. Contact the
Company's service engineers to obtain the dimensions drawing.
● The protective tray is not recommended for wall-mounted installation.

● The inverter needs to be powered off if it has been powered on before you
install the tray.
● The clearance under the inverter must be at least 600 mm to ensure sufficient
space for installation and heat dissipation.

Procedure
Step 1 Install the left and right side panels for the inverter.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 38


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 4 Installation

Figure 4-15 Installing the side panels

Step 2 Install and secure the bottom panel.

Figure 4-16 Installing the bottom panel

----End

Cable Binding
Cables can be routed through the slots reserved on the tray and bound using the
holes around the slots. 300 mm x 3.6 mm cable ties are recommended.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 39


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

5 Electrical Connections

5.1 Precautions

DANGER

When exposed to sunlight, the PV arrays supply DC voltage to the inverter. Before
connecting cables, ensure that all DC SWITCH on the inverter are OFF. Otherwise,
the high voltage of the inverter may result in electric shocks.

DANGER

● The site must be equipped with qualified fire fighting facilities, such as fire sand
and carbon dioxide fire extinguishers.
● Wear personal protective equipment and use dedicated insulated tools to avoid
electric shocks or short circuits.

WARNING

● The equipment damage caused by incorrect cable connections is beyond the


warranty scope.
● Only certified electrician can perform electrical terminations.
● Operation personnel must wear PPE when connecting cables.
● Before connecting cables to ports, leave enough slack to reduce the tension on
the cables and prevent poor cable connections.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 40


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

CAUTION

● Stay away from the equipment when preparing cables to prevent cable scraps
from entering the equipment. Cable scraps may cause sparks and result in
personal injury and equipment damage.
● The positive and negative DC PV string cables within 1.5 m of the inverter shall
be routed in separate pipes to prevent cable damage and short circuits caused
by improper operations during construction.

Figure 5-1 Cable routing in different pipes

NOTE

The cable colors shown in the electrical connection diagrams provided in this section are for
reference only. Select cables in accordance with local cable specifications (green-and-yellow
cables are only used for protective earthing).

5.2 Crimping an OT or DT Terminal


Requirements on an OT or DT Terminal
● If a copper cable is used, use copper wiring terminals.
● If a copper-clad aluminum cable is used, use copper wiring terminals.
● If an aluminum alloy cable is used, use copper-to-aluminum wiring terminals,
or aluminum wiring terminals along with copper-to-aluminum washers.

NOTICE

● Do not connect aluminum wiring terminals to the terminal block. Otherwise


electrochemical corrosion may occur, affecting the reliability of cable
connections.
● Comply with the IEC 61238-1 requirements when using copper-to-aluminum
wiring terminals, or aluminum wiring terminals along with copper-to-
aluminum washers.
● Do not mix up the aluminum and copper sides of a copper-to-aluminum
washer. Ensure that the aluminum side of the washer contacts the aluminum
wiring terminal, and that the copper side contacts the terminal block.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 41


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-2 Requirements on an OT or DT terminal

Crimping an OT or DT Terminal

NOTICE

● Avoid scratching the core wire when stripping a cable.


● The cavity formed after the conductor crimp strip of the OT or DT terminal has
been crimped must wrap around the core wire completely. The core wire must
make close contact with the OT or DT terminal.
● Wrap the wire crimping area with heat shrink tubing, cold shrink tubing, or
insulation tape. The heat shrink tubing is used as an example.
● Use a heat gun carefully to avoid heat damage to the equipment.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 42


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-3 Crimping an OT terminal

(1) Cable (2) Core wire (3) Heat shrink tubing

(4) OT terminal (5) Hydraulic pliers (6) Heat gun

Figure 5-4 Crimping a DT terminal

(1) Cable (2) Core wire (3) Heat shrink tubing

(4) DT terminal (5) Hydraulic pliers (6) Heat gun

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 43


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

5.3 Opening the Maintenance Compartment Door


Precautions

NOTICE

● Do not open the host panel cover of the inverter.


● Before opening the maintenance compartment door, ensure that no electrical
connections are made for the inverter on the AC or DC side.
● If you need to open the maintenance compartment door in rainy or snowy
days, take protective measures to prevent rain or snow entering the
maintenance compartment. If unavoidable, do not open the maintenance
compartment door.
● Do not leave unused screws in the maintenance compartment.

Procedure
Step 1 Partially loosen the two screws on the maintenance compartment door.

Step 2 Open the maintenance compartment door and install a support bar.

Figure 5-5 Opening the maintenance compartment door

Step 3 Remove the accessories that are bound in the maintenance compartment for
future use.
NOTE

A three-hole rubber plug is bound in the maintenance compartment. After removing the
rubber plug, save it properly for future use.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 44


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-6 Removing the accessories from the maintenance compartment

(1) Crimping modules

----End

5.4 (Optional) Replacing the Crimping Module


Procedure
NOTE

If the AC output power cable has a single core, replace the crimping module.

Step 1 Replace the crimping module.

Figure 5-7 Replacing the crimping module

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 45


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

5.5 (Optional) Installing the Power Cable of the


Tracking System
Precautions

NOTICE

● A switch-disconnector-fuse or fuse-switch-disconnector with a voltage of no


less than 800 V, current of 16 A, and protection type of gM needs to be
installed between the inverter and the tracker controller for protection.
● The cable between the wiring terminal on the power cable and the switch-
disconnector-fuse or fuse-switch-disconnector should be less than or equal to
2.5 m.
● Connect the power cable of the tracking system before the AC output power
cable. Otherwise, reworking will be caused.

Cable Specifications
Recommended: dual-layer three-core outdoor copper cable with a conductor
cross-sectional area of 10 mm2 and a cable outer diameter of 15–18 mm.

Procedure
Step 1 Connect the power cable of the tracking system to the terminal block.

Figure 5-8 Cable connection

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 46


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

5.6 Connecting the AC Output Power Cable


Precautions
A three-phase AC switch should be installed on the AC side of the inverter. To
ensure that the inverter can safely disconnect itself from the power grid when an
exception occurs, select a proper overcurrent protection device in compliance with
local power distribution regulations.

WARNING

● Do not connect loads between an inverter and an AC switch that directly


connects to the inverter. Otherwise, the switch may trip by mistake.
● If an AC switch is used with specifications beyond local standards, regulations,
or the Company's recommendations, the switch may fail to turn off in a timely
manner in case of exceptions, causing serious faults.

CAUTION

Each inverter shall be equipped with an AC output switch. Multiple inverters shall
not connect to the same AC switch.

The inverter is integrated with a comprehensive residual current detection unit to


distinguish fault current from residual current. Upon detecting that the residual
current exceeds the threshold, the inverter immediately disconnects from the
power grid.

Cable Connection Precautions

NOTICE

● The cable outer diameter can be measured using the ruler sticker in the
maintenance compartment.
● Ensure that the cable jacket is in the maintenance compartment.
● Ensure that the AC output power cable is secured. Failing to do so may cause
the solar inverter to malfunction or damage to its terminal block by issues such
as overheating.

● The ground point on the enclosure is preferred to connect to the PE cable for
the inverter.
● The PE point in the maintenance compartment is used for connecting to the
PE cable included in the multi-core AC power cable.
● There are two ground points on the chassis shell and you only need either of
them.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 47


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

● It is recommended that the PE cable of the inverter be connected to a nearby


ground point. For a system with multiple inverters connected in parallel,
connect the ground points of all inverters to ensure equipotential connections
to ground cables.

Cable Specifications
● If you connect a ground cable to the ground point on the chassis shell, you
are advised to use a three-core (L1, L2, and L3) outdoor cable or three single-
core outdoor cables.
● If you connect a ground cable to the ground point in the maintenance
compartment, you are advised to use a four-core (L1, L2, L3, and PE) outdoor
cable.
● You need to prepare the OT or DT terminal that matches the cable.

Table 5-1 AC power cable specifications


Cable Type Conductor Cross- Cable Outer OT/DT
Sectional Area Diameter Terminal

Copper-core cable 50–240 mm2 ● Multi-core M10 (PE)


cable: 24–66 M12
Copper-clad ● Multi-core cable: mm (L1/L2/L3)
aluminum cable 70–240 mm2
● Single-core
and aluminum
● Single-core cable: cable: 14–32
alloy cable
70–240 mm2[2] mm[1]

Note [1]: For some models, the outer diameter of a single-core cable ranges
from 14 mm to 36 mm based on the label in the maintenance compartment.
Note [2]: For some models, when the OT/DT terminal is crimped as shown in
the following figure and the rubber baffle plate of the AC wiring terminal is 112
mm, the maximum conductor cross-sectional area of the single-core cable can
be 400 mm2.

Figure 5-9 Specifications of the Crimped OT/DT Terminal

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 48


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-10 Specification of the Rubber Baffle Plate

NOTE

● The cable diameter must comply with local cable standards. The factors that affect
cable selection include the rated current, cable type, routing mode, ambient
temperature, and maximum expected line loss.
● When the MBUS is used for communication, it is recommended that the multi-wire
cable be used. The maximum communication distance is 1000 m. If other types of AC
power cables are used, contact Huawei technical support.

Table 5-2 PE cable specifications


Conductor Cross-Sectional Conductor Cross-Sectional OT/DT
Area S of the AC Power Cable Area SP of the PE Cable Terminal
(Unit: mm2) (Unit: mm2)

S > 35 SP ≥ S/2 M10

The specifications are valid only if the conductors of the PE cable and AC power
cable use the same material. If the materials are different, ensure that the
conductor cross-sectional area of the PE cable produces a conductance
equivalent to that of the cable specified in this table. The specifications of the
PE cable are subject to this table or calculated according to IEC 60364-5-54.

Connecting the PE Cable


Step 1 Connect the PE cable to the ground point. To enhance the corrosion resistance of a
ground terminal, apply silicone grease or paint on it after connecting the PE cable
to the ground point on the enclosure.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 49


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-11 Cable connection

----End

Connecting the AC Output Power Cable (Multi-core)


Step 1 Connect the AC cable to the terminal block.

NOTICE

Sufficient slack should be provided in the PE cable to ensure that the last cable
bearing the force is the PE cable when the AC output power cable bears pulling
force due to force majeure.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 50


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-12 Cable connection

----End

Connecting the AC Output Power Cable (Single-core)


Step 1 Connect the AC cable to the terminal block.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 51


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-13 Cable connection

----End

NOTE

The 32–36 mm cable is supported only by some models. Refer to the corresponding label to
get the supported size.

Bending Radius

Figure 5-14 Bending Radius

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 52


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Multi-Core Cable Single-Core Cable

Unarmored Armored Unarmored Armored

R ≥ 15D R ≥ 12D R ≥ 20D R ≥ 15D

R indicates the bending radius, and D indicates the outer diameter of the cable.

NOTE

The AC power cable must be routed vertically into the maintenance compartment.

5.7 Connecting DC Input Power Cables


Precautions

DANGER

● Before connecting the DC input power cables, ensure that the DC voltage is
within the safe range (lower than 60 V DC) and that the three DC switches (DC
SWITCH) on the inverter are OFF. Otherwise, the high voltage may result in
electric shocks.
● In the scenario where the installation is complete but the inverter is not
connected to the power grid, the three DC switches (DC SWITCH) must be
turned on if DC input power cables are connected to the inverter. After turning
on the switches, check the inverter status. If any fault occurs, rectify it in a
timely manner.
● When the inverter operates in grid-tied mode, do not perform maintenance or
operations on the DC input power cables, such as connecting or disconnecting
a PV string or a PV module in the PV string. Otherwise, electric shocks or arcing
(which may cause fire) may occur.

WARNING

Ensure that the following conditions are met. Otherwise, the inverter may be
damaged or even a fire may occur.
● The maximum open-circuit voltage of each PV string must be lower than or
equal to 1500 V DC under any circumstances.
● The polarities of electric connections must be correct on the DC input side. The
positive and negative terminals of a PV string must be connected to
corresponding positive and negative DC input terminals of the inverter.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 53


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

WARNING

During the installation of PV strings and the inverter, the positive or negative
terminals of PV strings may be short-circuited to ground if the power cables are
not properly installed or routed. In this case, an AC or DC short circuit may occur
and damage the inverter. The resulting device damage is not covered under any
warranty.

NOTICE

● Ensure that the PV module output is well insulated to ground.


● The PV strings connecting to the same MPPT circuit shall use the same model
and quantity of PV modules. If the quantity of PV modules in a PV string is over
10% less than that in other PV strings, any resulting damage to the PV
modules will not be covered by the warranty.
● The inverter does not support full parallel connection for PV strings (full
parallel connection: PV strings connect to one another in parallel outside the
inverter and then connect to it separately).

Terminal Description
The inverter provides 14 DC input terminals, which are controlled by its three DC
switches. DC SWITCH 1 controls DC input terminals 1–4, DC SWITCH 2 controls DC
input terminals 5–9, and DC SWITCH 3 controls DC input terminals 10–14.

Figure 5-15 DC terminals

Requirements for selecting DC input terminals:


1. DC input terminal PV1 must be connected to a PV string.
2. You are advised to connect PV strings to PV1, PV3, PV4, PV6, PV8, PV9, P11,
PV13, and PV14 preferentially.
For example, if there are 9 to 14 PV strings, you are advised to connect DC input
terminals as follows.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 54


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Num Terminal Selection Num Terminal Selection


ber ber
of PV of
Strin PV
gs Strin
gs

9 1, 3, 4, 6, 8, 9, 11, 13, 14 10 1, 2, 3, 4, 6, 8, 9, 11, 13, 14

11 1, 2, 3, 4, 5, 6, 8, 9, 11, 13, 14 12 1, 2, 3, 4, 5, 6, 8, 9, 10, 11, 13, 14

13 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 14 1, 2, 3, 4, 5, 6, 7, 8, 9, 10, 11, 12,


13, 14 13, 14

NOTE

If a SUN2000-196KTL-H3, SUN2000-200KTL-H3, or SUN2000-215KTL-H3 inverter is used,


do not connect each individual PV string in parallel or connect them using Y-branch
connectors. Otherwise, the inverter may be damaged.

Cable Specifications
Cable Type Conductor Cross- Cable Outer
Sectional Area (Unit: Diameter (Unit:
mm2) mm)

1500 V copper multi-strand 4–6 4.7–6.4


twisted PV cable

NOTICE

● Cables with high rigidity, such as armored cables, are not recommended,
because poor contact may be caused by the bending of cables.
● Do not connect aluminum or aluminum alloy DC power cables directly to the
DC terminals of the inverter.
● The 1500 V PV cables must comply with IEC 62930 or EN 50618.

Procedure

NOTICE

● Use the MC4 EVO2 PV connectors delivered with the inverter. If the PV
connectors are lost or damaged, purchase the connectors of the same model.
The device damage caused by incompatible PV connectors is not covered under
any warranty.
● For models of the crimping tool and removal wrench, use the recommended
model or contact the Staubli vendor.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 55


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Step 1 Connect DC input power cables.

NOTICE

● The DC voltage measurement range of the multimeter must be at least 1500 V.


● If the voltage is a negative value, the DC input polarity is incorrect. Rectify the
connection.
● If the voltage is greater than 1500 V, too many PV modules are connected to
the same string. Remove some PV modules.
● Connect the connectors on the PV strings to the connectors on the inverter, and
pull back the connectors on the PV strings along the axial direction to check
whether the connectors are securely installed.
● Ensure that the connectors are properly connected. Any connector damage due
to improper connection is not covered by the warranty.

Figure 5-16 Cable connection

Figure 5-17 Connector connection

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 56


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

NOTICE

When installing DC input power cables, leave at least 150 mm of slack. The axial
tension on PV connectors must not exceed 80 N. Radial stress or torque must not
be generated on PV connectors.

Figure 5-18 DC input power cabling requirement

----End

5.8 Installing the Communications Cable


Precautions
When routing communications cables, separate communications cables from
power cables to prevent communication from being affected.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 57


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Pin Definitions of Communications Ports

Figure 5-19 Communications ports

Port Pin Definition Pin Definition Description

RS485-1 1 RS485A IN, RS485 2 RS485A OUT, RS485 Used for cascading
differential signal+ differential signal+ inverters or
connecting to
3 RS485B IN, RS485 4 RS485B OUT, RS485 devices such as the
differential signal– differential signal– SmartLogger.

PE 5 PE, shielding ground 6 PE, shielding ground -

RS485-2 7 RS485A, RS485 8 RS485B, RS485 Used for connecting


differential signal+ differential signal– to RS485 slave
devices.

Procedure
Step 1 Install the communications cable.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 58


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-20 Cable connection (4–8 mm four-hole rubber plug)

NOTICE

Block unused cable holes using plugs and tighten cable glands.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 59


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-21 Cable connection (4–8 mm two-hole rubber plug)

NOTICE

● If three communications cables are to be connected, use the three-hole rubber


plug that is bound in the maintenance compartment.
● Block unused cable holes using plugs and tighten cable glands.

----End

5.9 Closing the Maintenance Compartment Door


Procedure
Step 1 Adjust the support bar, close the maintenance compartment door and tighten the
two screws on the door.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 60


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 5 Electrical Connections

Figure 5-22 Closing the door

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 61


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 6 System Commissioning

6 System Commissioning

6.1 Checking Before Power-On


1. Check that the inverter is installed correctly and securely.
2. Check that the DC switches and downstream AC output switch are OFF.
3. Check that all ground cables are connected securely and reliably.
4. Check that all AC output power cables are connected correctly and securely,
without open circuits or short circuits.
5. Check that all DC input power cables are connected correctly and securely,
without open circuits or short circuits.
6. Check that the communications cables are connected correctly and securely.
7. Check that the maintenance compartment interior is clean and tidy, without
foreign matter.
8. Check that the maintenance compartment door is closed and that the door
screws are tightened.
9. If there are DC input terminals that are not connected to PV strings, use
sealing plugs with snap-fits (models: CT75A-FJB6/HY024-FHG-3 and
CT75AFJB5/HY024-FHG-4) to seal the terminals. Device damage caused by
the absence of sealing plugs is not covered by warranty.

Figure 6-1 Sealing plugs with snap-fits

10. Check that idle USB ports are plugged with waterproof plugs.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 62


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 6 System Commissioning

6.2 System Power-On


Precautions

DANGER

● Wear personal protective equipment and use dedicated insulated tools to avoid
electric shocks or short circuits.

WARNING

When LED2 is steady green (meaning that the inverter is grid-tied), do not turn on
any DC switch. Otherwise, the inverter may be damaged because the insulation
resistance is not detected.

NOTICE

● Before the equipment is put into operation for the first time, ensure that the
parameters are set correctly by professional personnel. Incorrect parameter
settings may result in noncompliance with local grid connection requirements
and affect the normal operations of the equipment.
● Before turning on the AC switch between the inverter and the power grid,
check that the AC voltage is within the specified range using a multimeter.
● If the inverter has not been running for more than half a year after being
mounted, it must be checked and tested by professionals before being put into
operation.
● When powering on the system, you must switch on DC SWITCH 1 first, and
then switch on DC SWITCH 2 and DC SWITCH 3 after LED 1 is steady on.
Huawei shall not be held liable for damages caused by failing to follow this
sequence.
● The DC switches support automatic disconnection. Reverse polarity or improper
PV module configuration will trigger automatic disconnection of DC switches.
In this case, do not forcibly turn on the switches before the faults are fixed.
Otherwise, damages caused by the forced switch-on will not be covered under
any warranty.

● Do not turn the DC switch to the unloaded position .


● When the system is powered on or running, do not place obstacles (such as
cables) to block the rotation of the handle or manually hold the handle.
Otherwise, the DC switch cannot be automatically disconnected.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 63


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 6 System Commissioning

Procedure
Step 1 Turn on the AC switch between the SUN2000 and the power grid.

NOTICE

If you perform Step 2 before Step 1, the inverter reports a fault about abnormal
shutdown. The inverter can start normally after the fault is automatically cleared.

Step 2 Set DC SWITCH 1 at the bottom of the SUN2000 chassis to ON. When you hear a
click sound, the switch is ON.
Step 3 Check the status of LED 1.
● If it is steady green, set DC SWITCH 2 and DC SWITCH 3 to ON.
● Wait one minute after power-on, if LED 1 is off, do not turn on other DC
switches. At the same time, turn off DC SWITCH 1 and check whether the
input power cables are correctly connected.
Step 4 Observe the LED indicators to check the SUN2000 operating status.

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 64


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

7 Man-Machine Interactions

7.1 App Operations

NOTICE

● When you set inverter parameters on the app, if the AC switch between the
inverter and the power grid is turned on but the three DC switches (DC
SWITCH) of the inverter are not in the ON position, certain parameters cannot
be displayed on the app. Set the three DC switches (DC SWITCH) to the ON
position and then set related parameters again.
● Changing the grid code may restore some parameters to factory defaults. After
the grid code is changed, check whether the previously set parameters are
affected.
● Sending a reset, shutdown, or upgrade command to the inverter may cause
power grid connection failure, which affects the energy yield.
● Only professionals are allowed to set the grid parameters, protection
parameters, feature parameters, and power adjustment parameters of the
inverter. If the grid parameters, protection parameters, and feature parameters
are incorrectly set, the inverter may not connect to the power grid. If the power
adjustment parameters are incorrectly set, the inverter may not connect to the
power grid as required. In these cases, the energy yield will be affected.

NOTE

● Configurable parameters vary depending on the grid code.


● The parameter names, value ranges, and default values are subject to change. The
actual display may vary.

7.1.1 Downloading and Installing the App


For details, see Downloading and Installing the App in the FusionSolar App and
SUN2000 App Device Commissioning Guide.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 65


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

7.1.2 Logging In to the App


For details, see Connecting to a Device in the FusionSolar App and SUN2000 App
Device Commissioning Guide.

7.1.3 Operations Related to the Advanced User


If you log in to the app as Advanced User, you can set grid parameters, protection
parameters, and feature parameters for the SUN2000.

7.1.3.1 Setting Grid Parameters

Procedure
Step 1 Choose Function Menu > Settings > Grid Parameters to access the parameters
setting screen.

Figure 7-1 Grid parameters (advanced user)

----End

Parameters
No. Parameter Description

1 Grid Code Set this parameter based on the grid code of the country or
region where the inverter is used and the inverter application
scenario.

2 Isolation settings Set the working mode of the inverter based on the grounding
status at DC side and the connection to the power grid.

7.1.3.2 Setting Protection Parameters

Procedure
Step 1 Choose Function Menu > Settings > Protection parameters to access the
parameters setting screen.

Figure 7-2 Protection parameters (advanced user)

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 66


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

Parameters
No. Parameter Description

1 Insulation resistance To ensure device safety, the inverter detects the insulation
protection threshold (MΩ) resistance of the input side with respect to ground when it
starts a self-check. If the detected value is less than the
preset value, the inverter does not connect to the grid.

NOTE

The insulation resistance protection threshold of the inverter must be set to a value in the
range of 0.05 to 1.5.

7.1.3.3 Setting Feature Parameters

Procedure
Step 1 Choose Function Menu > Settings > Feature Parameters to access the settings
screen.

Figure 7-3 Feature parameters (advanced user)

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 67


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

Parameters
No. Parameter Description Remarks

1 MPPT multi-peak When the inverter is used in -


scanning scenarios where PV strings are
greatly shaded, set this parameter
to Enable, and then the inverter
will perform MPPT scanning at
regular intervals to locate the
maximum power.

2 MPPT multi-peak Specifies the MPPT scanning This parameter is displayed


scan interval (min) interval. when MPPT multi-peak
scanning is set to Enable.

3 RCD enhancement RCD refers to the residual current -


of the inverter to the ground. To
ensure device and personal safety,
RCD should be limited to the
specified value in the standard. If
an AC switch with a residual
current detection function is
installed outside the inverter, this
function should be enabled to
reduce the residual current
generated when the inverter is
running, thereby preventing the
AC switch from misoperations.

4 Night-time In some specific application This parameter is displayed


reactive power scenarios, a power grid company when Isolation settings is set
output requires that the inverter can to Input ungrounded, with
perform reactive power TF.
compensation at night to ensure
that the power factor of the local
power grid meets requirements.

5 PID protection at When the inverter outputs -


night reactive power at night and this
parameter is set to Enable, the
inverter will shut down
automatically if it detects
abnormal status of the PID
compensation.

6 Power quality If this parameter is set to Enable, -


optimization mode the inverter output current
harmonics will be optimized.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 68


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

7 PV module type This parameter is used to set ● If this parameter is set to


different types of PV modules and Crystalline silicon or Film,
the shutdown time of the the inverter automatically
concentration PV module. If the detects the power of PV
concentration PV modules are modules when they are
shaded, the power drops shaded and shuts down if
drastically to 0 and the inverter the power is too low.
shuts down. The energy yield ● When concentration PV
would be affected since it takes modules are used:
too long for the power to resume
and inverter to restart. The – If this parameter is set to
parameter does not need to be CPV 1, the inverter can
set for crystalline silicon and filmy quickly restart in 60
PV modules. minutes if the input
power of PV modules
drops drastically due to
shading.
– If this parameter is set to
CPV 2, the inverter can
quickly restart in 10
minutes if the input
power of PV modules
drops drastically due to
shading.

8 Built-in PID When the external PID module -


compensation compensates the PID voltage for
direction the PV system, set Built-in PID
compensation direction to the
actual compensation direction of
the PID module so that the
inverter can output reactive
power at night.

9 String connection Specifies the connection mode of ● When PV strings connect to


mode PV strings. the inverter separately (All
PV strings separated), there
is no need to set this
parameter. The inverter can
automatically detect the
connection mode of the PV
strings.
● When PV strings connect to
one another in parallel
outside the inverter and
then connect to it
independently (All PV
strings connected), set this
parameter to All PV strings
connected.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 69


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

10 Automatic OFF The standards of certain countries If Automatic OFF due to


due to and regions require that the communication interrupted is
communication inverter must shut down after the set to Enable and the inverter
interrupted communication is interrupted for communication is interrupted
a certain time. for a specified time (set by
Communication interruption
duration), the inverter will
automatically shut down.

11 Automatic ON due If this parameter is set to Enable, This parameter is displayed


to communication the inverter automatically starts when Automatic OFF due to
resumed after communication recovers. If communication interrupted is
this parameter is set to Disable, set to Enable.
the inverter needs to be started
manually after communication
recovers.

12 Communication Specifies the duration for -


interruption determining communication
duration (min) interruption. Used for automatic
shutdown for protection in case of
communication interruption.

13 Soft start/boot Specifies the duration for the -


time (s) power to gradually increase when
the inverter starts.

14 Shutdown gradient Specifies the power change speed -


(%/s) when the inverter shuts down.

15 Night-time The inverter monitors PV strings -


hibernation at night. If this parameter is set to
Enable, the monitoring function
of the inverter will hibernate at
night to reduce power
consumption.

16 MBUS For inverters that support RS485 -


communication communication and MBUS
communication, you are advised
to set this parameter to Disable
to reduce power consumption.

17 Delay upgrade This parameter is mainly used in After the inverter starts to
the upgrade scenarios where the upgrade, if Delay upgrade is
PV power supply is disconnected set to Enable, the upgrade
at night due to no sunlight or package is loaded first. After
unstable at dawn or dusk due to the PV power supply recovers
poor sunlight. and the activation conditions
are met, the inverter
automatically activates the
upgrade.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 70


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

18 RS485-2 If this parameter is set to Enable, -


communication the RS485-2 port can be used. If
the port is not used, you are
advised to set this parameter to
Disable to reduce power
consumption.

19 Duration for The standards of certain countries


determining short- and regions require that the
time grid inverter should not disconnect
disconnection (ms) from the power grid if the power
-
grid experiences a short-time
failure. After the fault is rectified,
the inverter output power needs
to be quickly restored.

7.1.4 Operations Related to the Special User


If you log in to the app as Special User, you can set grid parameters, protection
parameters, feature parameters, and power adjustment parameters for the
SUN2000.

7.1.4.1 Setting Grid Parameters

Procedure
Step 1 Choose Function Menu > Settings > Grid Parameters to access the parameters
setting screen.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 71


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

Figure 7-4 Power grid parameters (special user)

----End

Parameters
No. Parameter Description

1 Grid Code Set this parameter based on the grid code of the country
or region where the inverter is used and the inverter
application scenario.

2 Isolation settings Set the working mode of the inverter based on the
grounding status at DC side and the connection to the
power grid.

3 Output mode Specifies whether the inverter output has a neutral wire
based on the application scenario.

4 Automatically start upon Specifies whether to allow the inverter to automatically


grid recovery start after the power grid recovers.

5 Grid connected recovery Specifies the time after which the inverter begins
time from grid faults (s) restarting after the power grid recovers.

6 Grid reconnection voltage The standards of certain countries and regions require
upper limit (V) that after the inverter shuts down for protection due to a
fault, if the power grid voltage is higher than Grid
reconnection voltage upper limit, the inverter is not
allowed to reconnect to the grid.

7 Grid reconnection voltage The standards of certain countries and regions require
lower limit (V) that after the inverter shuts down for protection due to a
fault, if the power grid voltage is lower than Grid
reconnection voltage lower limit, the inverter is not
allowed to reconnect to the grid.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 72


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description

8 Grid reconnection frequency The standards of certain countries and regions require
upper limit (Hz) that after the inverter shuts down for protection due to a
fault, if the power grid frequency is higher than Grid
reconnection frequency upper limit, the inverter is not
allowed to reconnect to the grid.

9 Grid reconnection frequency The standards of certain countries and regions require
lower limit (Hz) that after the inverter shuts down for protection due to a
fault, if the power grid frequency is lower than Grid
reconnection frequency lower limit, the inverter is not
allowed to reconnect to the grid.

10 Reactive power Specifies the voltage threshold for triggering reactive


compensation (cosφ-P) power compensation based on the cosφ-P curve.
trigger voltage (%)

11 Reactive power Specifies the voltage threshold for exiting reactive power
compensation (cosφ-P) exit compensation based on the cosφ-P curve.
voltage (%)

7.1.4.2 Setting Protection Parameters

Procedure
Step 1 Choose Function Menu > Settings > Protect Parameters to go to the parameter
setting screen.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 73


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

Figure 7-5 Protection parameters (special user)

----End

Parameters
No. Parameter Description

1 Voltage unbalance protection Specifies the inverter protection threshold when the
threshold (%) power grid voltage is unbalanced.

2 10-min overvoltage protection Specifies the 10-minute overvoltage protection


threshold (V) threshold.

3 10-min overvoltage protection Specifies the 10-minute overvoltage protection


duration (ms) duration.

4 Level-N overvoltage protection Specifies the level-N grid overvoltage protection


threshold (V) threshold.

5 Level-N overvoltage protection Specifies the level-N grid overvoltage protection


duration (ms) duration.

6 Level-N undervoltage Specifies the level-N grid undervoltage protection


protection threshold (V) threshold.

7 Level-N undervoltage Specifies the level-N grid undervoltage protection


protection duration (ms) duration.

8 Level-N overfrequency Specifies the level-N grid overfrequency protection


protection threshold (Hz) threshold.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 74


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description

9 Level-N overfrequency Specifies the level-N grid overfrequency protection


protection duration (ms) duration.

10 Level-N underfrequency Specifies the level-N grid underfrequency protection


protection threshold (Hz) threshold.

11 Level-N underfrequency Specifies the level-N grid underfrequency protection


protection duration (ms) duration.

7.1.4.3 Setting Feature Parameters

Procedure
Step 1 Choose Function Menu > Settings > Feature Parameters to access the settings
screen.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 75


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

Figure 7-6 Feature parameters (special user)

----End

Parameters
No. Parameter Description Remarks

1 LVRT LVRT is short for low voltage ride-through. -


When the grid voltage is abnormally low for a
short time, the inverter cannot disconnect from
the power grid immediately and has to work for
some time.

2 Threshold for Specifies the threshold for triggering LVRT. The This parameter is
triggering threshold settings should meet the local grid displayed when LVRT
LVRT (V) standard. is set to Enable.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 76


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

3 LVRT gradient During LVRT, the solar inverter needs to


K1 generate positive-sequence reactive power to
support the power grid. This parameter is used
to set the positive-sequence reactive power
generated by the solar inverter.
For example, if you set LVRT gradient K1 to 2,
the increment of positive-sequence reactive
current generated by the solar inverter is 20%
of the rated current when the AC voltage
decreases by 10% during LVRT.

4 LVRT gradient During LVRT, the solar inverter needs to


K2 generate negative-sequence reactive power to
support the power grid. This parameter is used
to set the negative-sequence reactive power
generated by the solar inverter.
For example, if you set LVRT gradient K2 to 2,
the increment of negative-sequence reactive
current generated by the solar inverter is 20%
of the rated current when the AC voltage
decreases by 10% during LVRT.

5 Percentage of During LVRT, the solar inverter needs to limit


LVRT reactive the reactive current.
current For example, if you set Percentage of LVRT
limiting reactive current limiting to 50, the reactive
current upper limit of the solar inverter is 50%
of the rated current during LVRT.

6 Threshold of When Zero current due to power grid fault is


LVRT zero- enabled, if the power grid voltage is less than
current mode the value of Threshold of LVRT zero-current
mode during LVRT, the zero current mode is
used. Otherwise, the mode configured in LVRT
mode is used.

7 LVRT mode Sets LVRT mode. The options are Zero-current


mode, Constant current mode, Reactive
power priority mode, and Active power
priority mode.

8 LVRT Specifies the low voltage ride-through


characteristic capability of the inverter.
curve

9 HVRT HVRT is short for high voltage ride-through. -


When the grid voltage is abnormally high for a
short time, the inverter cannot disconnect from
the power grid immediately and has to work for
some time.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 77


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

10 Threshold for Specifies the threshold for triggering HVRT. The This parameter is
triggering threshold settings should meet the local grid displayed when HVRT
HVRT (V) standard. is set to Enable.

11 HVRT During HVRT, the solar inverter needs to


gradient K1 generate positive-sequence reactive power to
support the power grid. This parameter is used
to set the positive-sequence reactive power
generated by the solar inverter.
For example, if you set HVRT gradient K1 to 2,
the increment of positive-sequence reactive
current generated by the solar inverter is 20%
of the rated current when the AC voltage
increases by 10% during HVRT.

12 HVRT During HVRT, the solar inverter needs to


gradient K2 generate negative-sequence reactive power to
support the power grid. This parameter is used
to set the negative-sequence reactive power
generated by the solar inverter.
For example, if you set HVRT gradient K2 to 2,
the increment of negative-sequence reactive
current generated by the solar inverter is 20%
of the rated current when the AC voltage
increases by 10% during HVRT.

13 Grid voltage Specifies whether to shield the undervoltage This parameter is


protection protection function during LVRT or HVRT. displayed when LVRT
shield during or HVRT is set to
VRT Enable.

14 VRT exit Specifies the LVRT/HVRT recovery threshold. ● This parameter is


hysteresis displayed when
threshold LVRT or HVRT is
set to Enable.
● LVRT recovery
threshold =
Threshold for
triggering LVRT +
VRT exit hysteresis
threshold
● HVRT recovery
threshold =
Threshold for
triggering HVRT -
VRT exit hysteresis
threshold

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 78


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

15 Grid voltage Specifies the LVRT or HVRT threshold for -


jump triggering a transient voltage jump of a power
triggering grid. A transient voltage jump indicates that the
threshold (%) inverter cannot immediately disconnect from
the power grid when the power grid is
abnormal due to transient changes.

16 Zero current Certain countries and regions have This parameter is


due to power requirements on the output current during displayed when LVRT
grid fault high/low voltage ride-through. In this case, set or HVRT is set to
this parameter to Enable. After this parameter Enable.
is set to Enable, the output current is less than
10% of the rated current during high/low
voltage ride-through.

17 Active Specifies whether to enable the active islanding -


islanding protection function.
protection

18 Automatic The standards of certain countries and regions -


OFF due to require that the inverter must shut down after
communicati the communication is interrupted for a certain
on time.
interrupted

19 Automatic If this parameter is set to Enable, the inverter -


ON due to automatically starts after communication
communicati recovers. If this parameter is set to Disable, the
on resumed inverter needs to be started manually after
communication recovers.

20 Communicati Specifies the duration for determining -


on communication interruption. Used for
interruption automatic shutdown for protection in case of
duration communication interruption.
(min)

21 Soft start/ Specifies the duration for the power to -


boot time (s) gradually increase when the inverter starts.

22 Soft start Specifies the time for the power to gradually -


time after increase when the inverter restarts after the
grid failure power grid recovers.
(s)

23 TCP Specifies the TCP link timeout period for the -


heartbeat solar inverter to connect to the management
interval (s) system.

24 TCP frame Specifies the maximum length of the TCP frame -


length sent by the northbound device to the solar
inverter.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 79


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

25 Heartbeat Specifies the timeout period for the solar -


period at inverter to connect to the management system.
application
layer (min)

7.1.4.4 Setting Power Adjustment Parameters

Procedure
Step 1 Choose Function Menu > Settings > Power Adjustment to go to the parameter
setting screen.

Figure 7-7 Power adjustment parameters (special user)

----End

Parameters
No. Parameter Description Remarks

1 Remote power If this parameter is set to Enable, -


schedule the inverter responds to the
scheduling instruction from the
remote port. If this parameter is
set to Disable, the inverter does
not respond to the scheduling
instruction from the remote port.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 80


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

2 Schedule instruction Specifies the time for maintaining When this parameter is set
valid duration (s) the scheduling instruction. to 0, the scheduling
instruction takes effect
permanently.

3 Maximum active Specifies the output upper -


power (kW) threshold for the maximum active
power to adapt to different market
requirements.

4 OFF at 0% power If this parameter is set to Enable, -


limit the inverter shuts down after
receiving the 0% power limit
command. If this parameter is set
to Disable, the inverter does not
shut down after receiving the 0%
power limit command.

5 Active power Specifies the change speed of the -


change gradient inverter active power.
(%/s)

6 Derated by fixed Adjusts the active power output of


-
active power (kW) the inverter by fixed value.

7 Derated by active Adjusts the active power output of If this parameter is set to
power % (%) the inverter by percentage. 100, the inverter outputs
based on the maximum
output power.

8 Night-time reactive In some specific application -


power output scenarios, a power grid company
requires that the inverter can
perform reactive power
compensation at night to ensure
that the power factor of the local
power grid meets requirements.

9 Enable reactive When this parameter is set to This parameter is displayed


power parameters Enable, the inverter outputs when Night-time reactive
at night reactive power based on the power output is set to
setting of Reactive power Enable.
compensation at night.
Otherwise, the inverter executes
the remote scheduling command.

10 Night-time reactive During the reactive power This parameter is displayed


power compensation at night, the when Night-time reactive
compensation reactive power is scheduled by power output and Enable
(kVar) fixed value. reactive power parameters
at night are set to Enable.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 81


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

11 Reactive power Specifies the change speed of the -


change gradient inverter reactive power.
(%/s)

12 Plant active power Specifies the rate of active power -


gradient (min/ rise due to sunlight changes.
100%)

13 Average active Specifies the period of active -


power filtering time power rise due to sunlight
(ms) changes. This parameter is used
with Plant active power gradient.

14 Power factor Specifies the power factor of the -


inverter.

15 Reactive power Specifies the reactive power output -


compensation (Q/S) by the inverter.

16 Overfrequency If this parameter is set to Enable, -


derating the active power of the inverter
will be derated according to a
certain slope when the grid
frequency exceeds the frequency
that triggers overfrequency
derating.

17 Frequency for The standards of certain countries


triggering and regions require that the
overfrequency output active power of inverters be
derating (Hz) derated when the power grid
frequency exceeds a certain value. ● This parameter is
displayed when
18 Frequency for Specifies the frequency threshold Overfrequency derating
exiting for exiting overfrequency derating. is set to Enable.
overfrequency ● When setting this
derating (Hz) parameter, ensure that
19 Cutoff frequency of Specifies the frequency threshold the following condition is
overfrequency for cutting off overfrequency met: Frequency for
derating (Hz) derating. exiting overfrequency
derating ≤ Frequency
20 Cutoff power of Specifies the power threshold for for triggering
overfrequency cutting off overfrequency derating. overfrequency derating
derating (%) < Cutoff frequency of
overfrequency derating.
21 Power recovery Specifies the recovery rate of the
gradient of overfrequency derating power.
overfrequency
derating (%/min)

22 PF (U) voltage Specifies the time for filtering the -


detection filtering grid voltage in the PF-U curve.
time (s)

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 82


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

No. Parameter Description Remarks

23 Apparent power Adjust the apparent output -


baseline (kVA) baseline of the inverter.

24 Active power Adjusts the active output baseline -


baseline (kW) of the inverter.

25 Power percentage Specifies the reference apparent -


for triggering Q-U power, in percentage. When the
scheduling actual apparent power of the
inverter is greater than the value
of this parameter, the Q-U
characteristic curve scheduling
function is enabled.

26 Q-U characteristic The inverter adjusts Q/S (the ratio -


curve of the output reactive power to
apparent power) in real time
based on U/Un(%) (the ratio of
the actual power grid voltage to
the rated power grid voltage).

27 Q-P characteristic The inverter adjusts Q/Pn (the -


curve ratio of the output reactive power
to the rated active power) in real
time based on P/Pn(%) (the ratio
of the actual active power to the
rated active power).

28 Cosφ-P/Pn The inverter adjusts the output -


characteristic curve power factor cosφ in real time
based on P/Pn(%).

7.2 Upgrading the Inverter


USB flash drives of SanDisk, Netac, and Kingston are recommended. Other brands
may be incompatible.

NOTE

● Delete the script file immediately after use to reduce information disclosure risks.
● The file system format of the USB flash drive must be FAT32.

Procedure
Step 1 Download the required software upgrade package from the technical support
website.

Step 2 Decompress the upgrade package and copy all files to the root directory of the
USB flash drive.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 83


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 7 Man-Machine Interactions

NOTICE

Do not modify the content in the upgrade package. All files in the upgrade
package contain RSA signature verification. Modifying the content in the upgrade
package will cause an upgrade failure.

Step 3 Connect the USB flash drive to the USB port. The system automatically identifies
the USB flash drive and executes all commands specified in the boot script file.
View the LED indicators to determine the operating status.

Table 7-1 LED indicator description


LED Indicator Status Description

Off No USB flash drive-


related operation is
performed.

Blinking green slowly USB flash drive-related


operations are being
performed.

Blinking green fast An operation with a


USB flash drive has
failed.

Steady green USB flash drive-related


operations succeeded.

Step 4 The system automatically restarts when the upgrade is completed. All indicators
are off during the restart. After the restart, the preceding indicator is blinking
green slowly for one minute until becoming steady on, which indicates that the
upgrade is successful.

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 84


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

8 Maintenance

DANGER

● Wear personal protective equipment and use dedicated insulated tools to avoid
electric shocks or short circuits.

WARNING

● Before performing maintenance, power off the equipment, follow the


instructions on the delayed discharge label, and wait for a period of time as
specified to ensure that the equipment is not energized.

8.1 System Power-Off


Precautions

WARNING

● If two inverters share the same AC switch on the AC side, power off the two
inverters.
● After the inverter powers off, the remaining electricity and heat may still cause
electric shocks and body burns. Therefore, put on personal protective
equipment (PPE) and begin servicing the inverter fifteen minutes after power-
off.

Procedure
Step 1 Run a shutdown command on the SUN2000 app, SmartLogger, or network
management system (NMS).

For details, see the user manual of the corresponding product.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 85


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

Step 2 Turn off the AC switch between the inverter and the power grid.
Step 3 Set the three DC switches to OFF.

----End

8.2 Power-Off for Maintenance


Context
To prevent personal injury and equipment damage, perform the following
procedure to power off the inverter for troubleshooting or replacement.

CAUTION

● If the inverter is faulty, do not stand in front of it if possible.


● If the LED1 indicator on the inverter is off and the DC switches are OFF, do not
operate the DC switches. For details, see Step 4.
● Do not operate the DC switches on the inverter before you perform Step 3 to
Step 5.
● When the inverter detects a fault, it triggers automatic DC disconnection
protection. Do not turn on the DC switches before the fault is rectified.
● If the AC switch between the inverter and the power grid has been turned off
automatically, do not turn it on before the fault is rectified.
● Before power-off for maintenance, do not touch the energized components of
the inverter. Otherwise, electric shocks or arcs may occur.

Procedure
Step 1 Wear proper PPE.
Step 2 If the inverter does not shut down due to a fault, send a shutdown command on
the SUN2000 app, SmartLogger, or management system. If the inverter has shut
down due to a fault, go to the next step.
Step 3 Turn off the AC switch between the inverter and the power grid.
Step 4 Use a clamp meter to measure the DC current of each PV string input to the
inverter.
● If the current is less than or equal to 0.01 A, go to the next step.
● If the current is higher than 0.01 A, wait until the solar irradiance decreases
and the PV string current decreases below 0.01 A at night, and then go to the
next step.
Step 5 Open the maintenance compartment door, install a support strut, and use a
multimeter to check the voltage between the AC terminal block and the ground.
Ensure that the AC side of the inverter is powered off.
Step 6 Set all DC switches of the inverter to OFF. If the DC switches are automatically
turned off, go to the next step.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 86


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

Figure 8-1 Power-off for maintenance

Step 7 Wait for 15 minutes and troubleshoot or repair the inverter.

WARNING

● Do not open the panel for maintenance if the inverter is emitting abnormal
smell or smoke, or has obvious exceptions.
● If the inverter does not emit abnormal smell or smoke and is intact, repair or
restart it based on the alarm handling suggestions. Do not stand in front of the
inverter during the restart.

----End

8.3 Routine Maintenance

Maintenance Items
To ensure that the inverter can operate properly for a long term, you are advised
to perform routine maintenance on it as described in this section.

CAUTION

● Before cleaning the inverter, connecting cables, and checking the grounding
reliability, power off the inverter and ensure that each DC SWITCH on the
inverter is set to OFF.
● Do not open the maintenance compartment door on rainy or snowy days. If
you need to, take protective measures to prevent rain or snow from entering
the maintenance compartment. If protective measures cannot be taken, do not
open the maintenance compartment door.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 87


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

Table 8-1 Maintenance checklist


Item Check Method Maintenance
Interval

● Cleanness of ● Check whether there is dust on Once every 6 to 12


air intake and the air intake and exhaust vents. months
exhaust vents If necessary, remove the baffle
● Fans plates from the vents and clean
up dust.
● Check whether the fans
generate abnormal noise during
operation.

System running ● Check whether the inverter is Once every 6 months


status damaged or deformed.
● Check whether the inverter
generates abnormal sound
during operation.
● Check whether all inverter
parameters are correctly set
during operation.

Electrical ● Check whether cables are 6 months after the


connections securely connected. first commissioning
● Check whether cables are and once every 6 to
damaged, especially whether 12 months after that
the cable sheath that contacts a
metal surface is damaged.
● Check whether the sealing plugs
of unused DC input terminals
fall off.
● Check whether the unused COM
and USB ports are locked by
waterproof caps.

Grounding Check whether ground cables are 6 months after the


reliability securely connected. first commissioning
and once every 6 to
12 months after that

Vegetation ● Perform inspection and weeding Based on the local


around the as required. wilting season
inverter
● Clean the site promptly after
weeding.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 88


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

Removing the Baffle Plate from the Air Intake Vent

Figure 8-2 Removing the baffle plate

8.4 Replacing a Fan

CAUTION

● Before replacing a fan, power off the inverter.


● When replacing a fan, use insulation tools and wear personal protective
devices.

NOTE

If the fan tray gets stuck when being pulled or pushed, slightly lift it.

Step 1 Remove the screw on the fan tray and save it. Pull out the fan tray until the fan
baffle plate aligns with the inverter chassis.

Figure 8-3 Pulling out fan tray (1)

Step 2 Remove the cable ties shared by the cables, unscrew the connectors, and
disconnect the cables.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 89


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

Figure 8-4 Disconnecting cables

Step 3 Pull out the fan tray.

Figure 8-5 Pulling out fan tray (2)

Step 4 Remove cable ties from the faulty fan.


● FAN 1 Faulty

Figure 8-6 Removing the FAN 1 cable ties

● FAN 2 Faulty

Figure 8-7 Removing the FAN 2 cable ties

● FAN 3 Faulty

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 90


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

Figure 8-8 Removing the FAN 3 cable ties

Step 5 Remove the faulty fan (FAN 1 is used as an example).

Figure 8-9 Removing the fan

Step 6 Install the new fan (FAN 1 is used as an example).

Figure 8-10 Installing a new fan

Step 7 Bind the fan cables.


● Binding positions for fan 1

Figure 8-11 Binding the FAN 1 cables

● Binding positions for fan 2

Figure 8-12 Binding the FAN 2 cables

● Binding positions for fan 3

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 91


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

Figure 8-13 Binding the FAN 3 cables

Step 8 Push the fan tray into the slot until the fan baffle plate aligns with the inverter
chassis.

Figure 8-14 Pushing the fan tray in

Step 9 Connect the cables correctly according to the cable labels and bind the cables.

Figure 8-15 Reconnecting and binding the cables

Step 10 Push the fan tray into the slot and tighten the screw.

Figure 8-16 Reinstalling the fan tray

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 92


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

8.5 Alarm Reference


For details about alarms, see the Inverter Alarm Reference.

8.6 Resetting and Turning On the DC SWITCH


Prerequisites
If string backfeed, string connection in reverse polarity, or an internal inverter fault
is displayed on the mobile app or remote monitoring system and the DC SWITCH
is in the OFF position, the DC SWITCH has been automatically turned off. In this
case, rectify the fault based on the alarm handling suggestions before turning on
the DC SWITCH.

Procedure
Step 1 Loosen the caps of the RESET buttons for the three DC switches, and press the
RESET buttons inwards until you cannot go any further.
Step 2 Set the DC switches to ON.
Step 3 Tighten the caps of the RESET buttons.

Figure 8-17 Resetting and Turning On the DC Switch (DC SWITCH 1 is used as an
example)

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 93


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

8.7 Locating Insulation Resistance Faults

NOTICE

The inverter supports insulation resistance detection:


● If reactive power output at night is enabled for the inverter, log in to the
SmartLogger WebUI, choose Monitoring > Inverter > Running Param. >
Power Adjustment and set Insulation resistance inspection during reactive
power output at night to Enable. Then, the inverter will perform insulation
resistance detection once a day. (This parameter can be set only for
SUN2000HA V500R023C00SPC110, SmartLogger V300R023C10SPC550, and
later versions.)
● If reactive power output at night is disabled, the inverter performs insulation
resistance detection by default when it is started.

If the ground resistance of a PV string connected to the SUN2000 is too low, the
SUN2000 generates a Low insulation resistance alarm.
The possible causes are as follows:
● A short circuit occurs between the PV array and the ground.
● The ambient air of the PV array is damp and the insulation between the PV
array and the ground is poor.
After the Low insulation resistance alarm is generated, the SUN2000
automatically triggers insulation resistance fault location. If the fault location is
successful, the location information is displayed on the Alarm details screen of
the Low insulation resistance alarm on the FusionSolar app.
Log in to the FusionSolar app, choose Alarm > Active alarm, and choose Low
insulation resistance to enter the Alarm details screen.

NOTE

● The positive and negative terminals of a PV string are connected to the PV+ and PV–
terminals of the SUN2000, respectively. The 0% position corresponds to the PV–
terminal, and the 100% position corresponds to the PV+ terminal. Other percentages
indicate that the fault occurs on a PV module or cable in the PV string.
● Possible fault position = Total number of PV modules in a PV string x Percentage of
possible short-circuit positions. For example, if a PV string consists of 14 PV modules
and the percentage of the possible short-circuit position is 34%, the possible fault
position is 4.76 (14 x 34%), indicating that the fault is located near PV module 4,
including the adjacent PV modules and their cables. The SUN2000 has a detection
precision of ±1 PV module.
● For details about the PV strings corresponding to the MPPT that may be faulty, see
Table 8-2. The fault can be located only to the MPPT level. Perform the following steps
to connect the PV strings corresponding to the faulty MPPT to the SUN2000 one by one
to further locate and rectify the fault.
● When a non-short-circuit fault occurs, the possible short-circuit percentage is not
displayed. If the insulation resistance is greater than 0.001 MΩ, the fault is not related
to short circuit. Check all PV modules in the faulty PV string one by one to locate and
rectify the fault.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 94


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

Figure 8-18 Definition of the percentage of the short-circuit position

Table 8-2 Mapping between MPPTs and PV strings


MPPTn PV String MPPTn PV String

MPPT1 PV1–PV4 MPPT2 PV5–PV9

MPPT3 PV10–PV14 MPPT4 PV15–PV18

MPPT5 PV19–PV23 MPPT6 PV24–PV28

Procedure

NOTICE

If the irradiance or the PV string voltage is too high, the insulation resistance fault
location may fail. In this case, the fault location status on the Alarm details
screen is Conditions not met. Perform the following steps to connect PV strings to
the SUN2000 one by one to locate the fault.

Step 1 Ensure that the AC connections are normal. Log in to the FusionSolar app, choose
Maintenance > Inverter ON/OFF on the home screen, and send a shutdown
command. Set the DC SWITCH of the SUN2000 to OFF.
Step 2 Connect a PV string to the SUN2000 and set the DC SWITCH to ON. If the
SUN2000 status is Shutdown: Command, choose Maintenance > Inverter
ON/OFF on the home screen and send a startup command.
Step 3 Choose Alarm on the home screen, enter the Active alarm screen, and check
whether a Low insulation resistance alarm is reported.
● If no Low insulation resistance alarm is reported 1 minute after the DC side
is powered on, choose Maintenance > Inverter ON/OFF on the home screen
and send a shutdown command. Set the DC SWITCH to OFF. Go to Step 2
and check the other PV strings one by one.
● If a Low insulation resistance alarm is reported 1 minute after the DC side is
powered on, check the percentage of possible short-circuit positions on the
Alarm details screen and calculate the location of the possibly faulty PV
module based on the percentage. Then go to Step 4.
Step 4 Choose Maintenance > Inverter ON/OFF on the home screen and send a
shutdown command. Set the DC SWITCH to OFF. Check whether the connectors
or DC power cables between the possibly faulty PV modules and adjacent PV
modules are damaged.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 95


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 8 Maintenance

● If yes, replace the damaged connectors or DC power cables and then set the
DC SWITCH to ON. If the SUN2000 status is Shutdown: Command, choose
Maintenance > Inverter ON/OFF on the home screen and send a startup
command. View alarm information.
– If no Low insulation resistance alarm is reported 1 minute after the DC
side is powered on, the insulation resistance fault location of the PV
string is complete. Choose Maintenance > Inverter ON/OFF on the
home screen and send a shutdown command. Set the DC SWITCH to
OFF. Go to Step 2 and check the other PV strings one by one. Then, go to
Step 7.
– If the Low insulation resistance alarm is still reported 1 minute after the
the DC side is powered on, choose Maintenance > Inverter ON/OFF on
the home screen and send a shutdown command. Set the DC SWITCH to
OFF and go to Step 5.
● If no, go to Step 5.
Step 5 Disconnect the possibly faulty PV module from the PV string, and use a DC
extension cable with MC4 connectors to connect the adjacent PV modules. Set the
DC SWITCH to ON. If the SUN2000 status is Shutdown: Command, choose
Maintenance > Inverter ON/OFF on the home screen and send a startup
command. View alarm information.
● If no Low insulation resistance alarm is reported 1 minute after the DC side
is powered on, the fault occurred on the disconnected PV module. Choose
Maintenance > Inverter ON/OFF on the home screen, send a shutdown
command, and set the DC SWITCH to OFF. Go to Step 7.
● If the Low insulation resistance alarm is still reported 1 minute after the DC
side is powered on, the fault did not occur on the disconnected PV module.
Go to Step 6.
Step 6 Choose Maintenance > Inverter ON/OFF on the home screen and send a
shutdown command. Set the DC SWITCH to OFF, reconnect the disconnected PV
module, and repeat Step 5 to check the adjacent PV modules at the possible fault
position.
Step 7 Set the DC SWITCH to ON. If the SUN2000 status is Shutdown: Command,
choose Maintenance > Inverter ON/OFF on the home screen and send a startup
command.

----End

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 96


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 9 Handling the Inverter

9 Handling the Inverter

9.1 Removing the SUN2000

NOTICE

Before removing the SUN2000, disconnect both AC and DC connections.

Perform the following operations to remove the SUN2000:


1. Disconnect all cables from the SUN2000, including RS485 communications
cables, DC input power cables, AC output power cables, and PGND cables.
2. Remove the SUN2000 from the mounting bracket.
3. Remove the mounting bracket.

9.2 Packing the SUN2000


● If the original packing materials are available, put the SUN2000 inside them
and then seal them by using adhesive tape.
● If the original packing materials are not available, put the SUN2000 inside a
suitable cardboard box and seal it properly.

9.3 Disposing of the SUN2000


If the SUN2000 service life expires, dispose of it according to the local disposal
rules for electrical equipment waste.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 97


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 10 Technical Specifications

10 Technical Specifications

Efficiency
Item SUN2000-196KTL SUN2000-200KTL SUN2000-215KTL
-H3 -H3 -H3

Maximum ≥ 99.0% ≥ 99.0% ≥ 99.0%


efficiency

Chinese efficiency ≥ 98.4% - -

European - ≥ 98.8% ≥ 98.8%


efficiency

Input
Item SUN2000-196KTL SUN2000-200KTL SUN2000-215KTL
-H3 -H3 -H3

Maximum input 1500 V


voltage

Maximum input 100 A


current (per
MPPT)

Maximum short- 32.5 A


circuit current
(per PV string)

Maximum 0A
backfeed current
to the PV array

Minimum 500 V/550 V


operating voltage/
startup voltage

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 98


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 10 Technical Specifications

Item SUN2000-196KTL SUN2000-200KTL SUN2000-215KTL


-H3 -H3 -H3

MPPT voltage 500–1500 V


range

Full-load MPPT 930–1300 V


voltage range

Rated input 1080 V


voltage

Number of inputs 14

Number of MPPT 3
circuits

Output
Item SUN2000-196KTL SUN2000-200KTL SUN2000-215KTL
-H3 -H3 -H3

Rated active 196 kW 185 kW 200 kW


power

Maximum 216 kVA 215 kVA 215 kVA


apparent power

Maximum active 216 kW 215 kW 215 kW


power (cosφ = 1)

Rated output 800 V AC, 3W+PE


voltage

Rated output 141.5 A 133.5 A 144.4 A


current

Supported power 50 Hz 50 Hz/60 Hz 50 Hz/60 Hz


grid frequency

Maximum output 155.9 A 155.2 A 155.2 A


current

Power factor 0.8 leading to 0.8 lagging

Maximum total < 3%


harmonic
distortion (rated
power)

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 99


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 10 Technical Specifications

Typical Noise Value


Item SUN2000-196KTL SUN2000-200KTL SUN2000-215KTL
-H3 -H3 -H3

Typical noise 65 dB(A)


value

NOTE

The typical noise value is the test result obtained under typical working conditions in a lab.
To avoid complaints, do not install the inverter in a noise-sensitive area.

Protection
Item SUN2000-196KT SUN2000-200KTL SUN2000-215KTL
L-H3 -H3 -H3

Input DC switch Supported

Anti-islanding Supported
protection

Output Supported
overcurrent
protection

Input reverse Supported


connection
protection

PV string fault Supported


detection

DC surge Type II
protection

AC surge Type II
protection

Insulation Supported
resistance
detection

Residual current Supported


monitoring unit
(RCMU)

Overvoltage PV II/AC III


category

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 100


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual 10 Technical Specifications

Display and Communication


Item SUN2000-196KTL SUN2000-200KTL SUN2000-215KT
-H3 -H3 L-H3

Display LED indicator; USB data cable + App

RS485 Supported

MBUS Supported

USB Supported

General Specifications
Item SUN2000-196KT SUN2000-200KTL SUN2000-215KT
L-H3 -H3 L-H3

Dimensions (W x 1035 mm x 700 mm x 365 mm


H x D)

Net weight 86 kg

Operating –25ºC to +60ºC


temperature

Cooling mode Smart air cooling

Maximum 5000 m (derated when the altitude is greater than 4000


operating altitude m)

Relative humidity 0%–100% RH

Input terminal MC4 EVO2

Output terminal Waterproof terminal+OT/DT terminal

IP rating IP66

Topology Transformerless

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 101


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual A String Access Detection

A String Access Detection

Function Description
● Applies to large-scale commercial ground PV plants with PV strings facing the
same direction.
● In AC or DC power limiting scenarios:
– If the PV string access type is not identified, the value of PV Status will
keep being displayed as Not connected. The PV string access type can be
identified only when the inverters restore to the non-power limiting state
and the current of all connected PV strings reaches the startup current.

Procedure
Step 1 Log in to the SUN2000 app as Advanced User. The initial password is 00000a.
NOTE

Use the initial password upon first power-on and change it immediately after login. To
ensure account security, change the password periodically and keep the new password in
mind. Not changing the initial password may cause password disclosure. A password left
unchanged for a long period of time may be stolen or cracked. If a password is lost, devices
cannot be accessed. In these cases, the user is liable for any loss caused to the PV plant.

Step 2 Choose Function Menu > Maintenance > String Access Detection to go to the
parameter setting screen.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 102


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual A String Access Detection

Figure A-1 String Access Detection

----End

Parameters
N Parameter Description Remarks
o.

1 String Access The default value is Disable. After the -


Detection inverter is connected to the power grid, you
can set String Access Detection to Enable.

2 Startup current When the current of all connected PV This


strings reaches the preset value, the PV paramet
string connection detection function is er is
enabled. displayed
NOTE only
Startup current setting rules: when
● Startup current = Isc (Stc) × 0.6 (rounded up). String
For details about Isc (Stc), see the PV module Access
nameplate. Detectio
● Default startup current (5 A): applicable to
n is set
the scenarios where the short-circuit current to
Isc (Stc) is greater than 8 A for the Enable.
monocrystalline and polycrystalline PV
modules.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 103


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual A String Access Detection

N Parameter Description Remarks


o.

3 Startup current When the current of a PV string reaches


for 2 in 1 Startup current for 2 in 1 detection, the
detection PV string is automatically identified as 2 in
1.
You are advised to use the default value.
NOTE
The SUN2000-196KTL-H3, SUN2000-200KTL-H3,
and SUN2000-215KTL-H3 inverters do not
support Y-branch connectors. The 2-in-1 string
detection function is unavailable.

4 PV string N Set this parameter based on the type of the


access type PV string connected to DC input terminal N
NOTE of the inverter. Currently, the options are as
N is the DC input follows: Automatic identification (default
terminal number value), Disconnection, Single PV string,
of the inverter. and 2 in 1.
You are advised to retain the default value.
If the value is incorrectly set, the PV string
access type may be incorrectly identified
and alarms may be generated by mistake
for the PV string connection status.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 104


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual B Domain Name List of Management Systems

B Domain Name List of Management


Systems

NOTE

The list is subject to change.

Table B-1 Domain names of management systems


Domain Name Data Type Scenario

intl.fusionsolar.huawei.co Public IP address FusionSolar SmartPVMS


m NOTE
The domain name is
compatible with
cn.fusionsolar.huawei.com
(Chinese mainland).

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 105


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual C Grid Codes

C Grid Codes

No. Grid Code Description SUN2000 SUN200 SUN2000


-196KTL- 0-200KT -215KTL-
H3 L-H3 H3

1 CHINA_MV800 China medium-voltage Supporte - -


power grid d

2 G59-England-MV800 G59 medium-voltage power - - Supporte


grid d

3 AS4777-MV800 Australia medium-voltage - - Supporte


power grid d

4 INDIA-MV800 India medium-voltage - Supporte -


power grid d

5 IEC61727-MV800 IEC 61727 medium-voltage - Supporte Supporte


power grid (50 Hz) d d

6 ABNT NBR 16149- Brazil medium-voltage - - Supporte


MV800 power grid d

7 UTE C 15-712-1-MV800 France medium-voltage - - Supporte


power grid d

8 Chile-MV800 Chile medium-voltage - - Supporte


power grid d

9 Mexico-MV800 Mexico power grid - - Supporte


d

10 EN50438-TR-MV800 Türkiye medium-voltage - - Supporte


power grid d

11 TAI-PEA-MV800 Thailand PEA medium- - - Supporte


voltage power grid d

12 Philippines-MV800 Philippines medium-voltage - - Supporte


power grid d

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 106


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual C Grid Codes

No. Grid Code Description SUN2000 SUN200 SUN2000


-196KTL- 0-200KT -215KTL-
H3 L-H3 H3

13 Malaysian-MV800 Malaysia medium-voltage - - Supporte


power grid d

14 NRS-097-2-1-MV800 South Africa medium- - Supporte -


voltage power grid d

15 SA_RPPs-MV800 South Africa RPPs medium- - Supporte Supporte


voltage power grid d d

16 Jordan-Transmission- Jordan power transmission - Supporte -


MV800 network medium-voltage d
power grid

17 Jordan-Distribution- Jordan power distribution - Supporte -


MV800 network medium-voltage d
power grid

18 Egypt ETEC-MV800 Egypt medium-voltage - Supporte -


power grid d

19 DUBAI-MV800 Dubai medium-voltage - Supporte -


power grid d

20 SAUDI-MV800 Saudi Arabia medium- - Supporte -


voltage power grid d

21 EN50438_IE-MV800 Ireland medium-voltage - - Supporte


power grid d

22 EN50549-MV800 Ireland power grid - Supporte Supporte


d d

23 Northern Ireland-MV800 Northern Ireland medium- - - Supporte


voltage power grid d

24 CEI0-21-MV800 Italy medium-voltage power - - Supporte


grid (CEI0-21) d

25 IEC 61727-MV800-60HZ General medium-voltage - Supporte Supporte


power grid d d

26 Pakistan-MV800 Pakistan medium-voltage - Supporte -


power grid d

27 BRASIL-ANEEL-MV800 Brazil medium-voltage - - Supporte


power grid d

28 Israel-MV800 Israel power grid - - Supporte


d

29 CEI0-16-MV800 Italy medium-voltage power - - Supporte


grid d

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 107


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual C Grid Codes

No. Grid Code Description SUN2000 SUN200 SUN2000


-196KTL- 0-200KT -215KTL-
H3 L-H3 H3

30 ZAMBIA-MV800 Zambia medium-voltage - Supporte -


power grid d

31 KENYA_ETHIOPIA_MV80 Kenya low-voltage and - Supporte -


0 Ethiopia medium-voltage d
power grid

32 NAMIBIA_MV800 Namibia medium-voltage - Supporte -


power grid d

33 Cameroon-MV800 Cameroon medium-voltage - Supporte -


power grid d

34 NIGERIA-MV800 Nigeria medium-voltage - Supporte -


power grid d

35 ABUDHABI-MV800 Abu Dhabi medium-voltage - Supporte -


power grid d

36 LEBANON-MV800 Lebanon medium-voltage - Supporte -


power grid d

37 ARGENTINA-MV800 Argentina medium-voltage - - Supporte


power grid d

38 Jordan-Transmission- Jordan high-voltage and - Supporte -


HV800 medium-voltage power grid d

39 TUNISIA-MV800 Tunisia medium-voltage - Supporte -


power grid d

40 AUSTRALIA-NER-MV800 Australia NER standard - - Supporte


medium-voltage power grid d

41 VDE-AR-N4120-HV800 VDE 4120 standard - - Supporte


medium-voltage power grid d

42 Nicaragua-MV800 Nicaragua medium-voltage - - Supporte


power grid d

43 Custom-MV800-50Hz Reserved - Supporte Supporte


d d

44 RD1699/661-MV800 Spain medium-voltage - - Supporte


power grid d

45 PO12.3-MV800 Spain medium-voltage - - Supporte


power grid d

46 Vietnam-MV800 Vietnam medium-voltage - - Supporte


power grid d

47 CHILE-PMGD-MV800 Chile PMGD medium- - - Supporte


voltage power grid (800 V) d

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 108


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual C Grid Codes

No. Grid Code Description SUN2000 SUN200 SUN2000


-196KTL- 0-200KT -215KTL-
H3 L-H3 H3

48 GHANA-MV800 Ghana medium-voltage - Supporte -


power grid (800 V) d

49 TAIPOWER-MV800 Taiwan Power medium- - - Supporte


voltage power grid (800 V) d

50 OMAN-MV800 Oman medium-voltage - Supporte -


power grid d

51 KUWAIT-MV800 Kuwait medium-voltage - Supporte -


power grid d

52 BANGLADESH-MV800 Bangladesh medium- - - Supporte


voltage power grid d

53 BAHRAIN-MV800 Bahrain medium-voltage - Supporte -


power grid d

54 KAZAKHSTAN-MV800 Kazakhstan medium- - - Supporte


voltage power grid d

55 Oman-PDO-MV800 Oman PDO medium- - Supporte -


voltage power grid d

56 TAI-MEA-MV800 Thailand medium-voltage - - Supporte


power grid d

57 C10/11-MV800 Belgium medium-voltage - - Supporte


power grid d

58 G99-TYPEB-HV-MV800 UK G99-TYPEB-HV medium- - - Supporte


voltage power grid d

59 G99-TYPEC-HV-MV800 UK G99-TYPEC-HV medium- - - Supporte


voltage power grid d

60 G99-TYPED-MV800 UK G99-TYPED medium- - - Supporte


voltage power grid d

61 CEA-MV800 India CEA power grid - Supporte -


d

62 VDE-AR-N4110-MV800 Germany medium-voltage - - Supporte


power grid (800 V) d

63 Panama-MV800 Panama medium-voltage - - Supporte


power grid (800 V) d

64 Macedonia-MV800 North Macedonia medium- - - Supporte


voltage power grid (800 V) d

65 SINGAPORE-MV800 Singapore medium-voltage - - Supporte


power grid d

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 109


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual C Grid Codes

No. Grid Code Description SUN2000 SUN200 SUN2000


-196KTL- 0-200KT -215KTL-
H3 L-H3 H3

66 Cambodia-MV800 Cambodia medium-voltage - - Supporte


power grid d

67 GREG060-MV800 Colombia medium-voltage - - Supporte


power grid d

68 PERU-MV800 Peru medium-voltage - - Supporte


power grid d

69 PORTUGAL-MV800 Portugal medium-voltage - - Supporte


power grid d

70 NTS-MV800 Spain medium-voltage - - Supporte


power grid d

71 KOREA-MV800 South Korea medium- - - Supporte


voltage power grid (800 V) d

72 Israel-HV800 Israel high-voltage power - - Supporte


grid (161 kV) d

73 AUSTRIA-MV800 Austria medium-voltage - - Supporte


power grid (type B) d

74 AUSTRIA-HV800 Austria medium-voltage - - Supporte


power grid (type D) d

75 POLAND-EN50549- Poland medium-voltage - - Supporte


MV800 power grid d

76 IRELAND-EN50549- Ireland power grid - - Supporte


MV800 d

77 DENMARK-EN50549- Denmark power grid - - Supporte


MV800 d

78 FRANCE-RTE-MV800 France RTE power grid - - Supporte


d

79 UZBEKISTAN-MV800 Uzbekistan power grid - Supporte -


d

80 CZECH-EN50549-MV800 Czech Republic power grid - - Supporte


d

81 MAURITIUS-MV800 Mauritius power grid - Supporte -


d

82 CHINA-GBT19964- China GB/T 19964 standard Supporte - -


MV800 power grid d

83 CHINA-GBT29319- China GB/T 29319 standard Supporte - -


MV800 power grid d

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 110


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual C Grid Codes

No. Grid Code Description SUN2000 SUN200 SUN2000


-196KTL- 0-200KT -215KTL-
H3 L-H3 H3

84 ITALY-A68-800 Italy medium-voltage power - - Supporte


grid d

85 AUSTRIA-TYPEC-MV-800 Austria medium-voltage - - Supporte


power grid (type C) d

86 TAI-EGAT-800 Thailand EGAT medium- - - Supporte


voltage power grid d

NOTE

The grid codes are subject to change. The listed codes are for reference only.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 111


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual D Resetting Password

D Resetting Password

Step 1 Check that the AC and DC sides of the inverter are both powered on, and
indicators and are steady green or blinking slowly for more than 3 minutes.
Step 2 Turn off the AC switch, set the DC SWITCH at the bottom of the inverter to OFF,
and wait until all LED indicators on the inverter panel turn off.
Step 3 Complete the following operations within 4 minutes:
1. Turn on the AC switch and wait for about 90s or until the inverter indicator
blinks.
2. Turn off the AC switch and wait about 30s or until all LED indicators on the
inverter panel turn off.
3. Turn on the AC switch and wait for about 90s or until the inverter indicator
blinks.
Step 4 Log in to the app and reset the password within 10 minutes. (If no operation is
performed within 10 minutes, all parameters of the inverter remain unchanged.)

----End

NOTICE

● SUN2000HA V300R001C00SPC133 and later versions support password reset.


● You are advised to reset the password in the morning or at night when the
solar irradiance is low.

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 112


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual E Contact Information

E Contact Information

If you have any questions about this product, please contact us.

https://digitalpower.huawei.com
Path: About Us > Contact Us > Service Hotlines

To ensure faster and better services, we kindly request your assistance in providing
the following information:
● Model
● Serial number (SN)
● Software version
● Alarm ID or name
● Brief description of the fault symptom

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 113


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual E Contact Information

NOTE

EU Representative Information: Huawei Technologies Hungary Kft.


Add.: HU-1133 Budapest, Váci út 116-118., 1. Building, 6. floor.
Email: [email protected]

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 114


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual F Digital Power Customer Service

F Digital Power Customer Service

https://digitalpower.huawei.com/robotchat/

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 115


SUN2000-(196KTL-H3, 200KTL-H3, 215KTL-H3)
User Manual G Acronyms and Abbreviations

G Acronyms and Abbreviations

LED light emitting diode

MBUS monitoring bus

MPP maximum power point

MPPT maximum power point


tracking

PID potential induced


degradation

PV photovoltaic

RCMU residual current


monitoring unit

Issue 16 (2025-03-30) Copyright © Huawei Technologies Co., Ltd. 116