Surtensionoltages and Insulation Coordination SH
Surtensionoltages and Insulation Coordination SH
connecting spindle
flange
(aluminium alloy)
elastic stirrup
fault indication
plate
spacer
thermal shield
exhaust pipe
porcelain enclosure
compression spring
flange
rubber seal
prestressed tightness
device
Figure 5-48: example of the structure of a ZnO surge arrester in a porcelain enclosure
for 20 kV networks
peak kV
U
600
500
400 Zn O
300
200
linear
SiC
100
SiC : non-linear resistor type gapped surge arrester made up of a silicon carbide resistor
ZnO : zinc oxide surge arrester
linear : U curve proportional to I
Figure 5-49: characteristics of two surge arresters having the same 550 kV/10 kA protection level
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Figure 5-35: transient voltage on circuit-breaker opening during a permanent phase-earth fault
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly orpartly, of this document are not allowed without our written consent.
n recapitulative table of touch voltages and overvoltages which occur for each earthing
system
TN − a IT − a TT − a IT − b TN − b TT − b IT − c
Touch voltage Y Y N N N N N
Overvoltage of LV
N N Y Y N N N
installation exposed
conductive parts
Overvoltage of
N N N N Y Y Y
substation exposed
conductive parts
Y : yes
N : no
The level of overvoltages transferred in LV depends on the clipped value Ursd and the earth
electrode values.
To ensure protection of the LV switchgear against these overvoltages, LV surge arresters must
be installed and the resistance of the substation earth electrode limited so that the equipment
lightning impulse withstand voltage is not exceeded.
As for the case of the MV earth fault, the limit values of the earth electrode impedances are
calculated for each earthing system.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
This corresponds to the equipment withstand to power frequency overvoltages likely to occur
on the network and the duration of which depends on the network operating and protection
mode.
This characterises the equipment withstand to switching impulses (only for equipment with a
standard voltage above or equal to 300 kV).
The equipment test (see IEC 60-1) is performed by applying a wave with a front time of 250 µs
and a time to half-value of 2500 µs.
This characterises the equipment withstand to the 1.2 µs / 50 µs lightning voltage wave.
This withstand voltage concerns all voltage ranges, including low voltage.
(1) Um is the highest rms value of the phase-to-phase voltage for which the equipment is specified.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
R(1) = RT = 0.056 Ω
X(1) = XT = 1.22 Ω
R(0)
= 1.28
X(1)
X(0 )
= 0.70
X(1)
R(0)
= 1.34
X(1)
X( 0)
= 1.37
X(1)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
- making lightning impulses flow to earth by a first clipping operation (surge arrester or spark-
gap at the entrance to the substation) with limitation of the earth electrode resistances and
pylon impedances
- limiting the residual voltage from the first clipping operation by HV surge arrester which is
transferred to the downstream network by providing a second protection level on the
transformer secondary
The values of rises in potential of the substation or LV installation exposed conductive parts
depend on the values of the earth electrode resistances, the fault current values and the
earthing system.
- the exposed conductive parts of high voltage and low voltage equipment
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Table 5-5: standard withstand voltages for 3.6 kV < U m < 72.5 kV
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The general method for choosing a zinc oxide surge arrester in HV consists in determining its
characteristic parameters using the network data, at the place where it will be installed.
- U C , steady-state voltage
- U r , rated voltage
- mechanical characteristics.
The choice of the surge arrester involves making a compromise between the equipment
protection levels and the energy capacity of the surge arrester.
The protection level must be as low as possible for the equipment withstand. This involves the
lowest voltage rating possible and thus greater difficulty withstanding temporary overvoltages.
o determining U C and U r
The voltages U C and U r may be directly determined using the highest voltage for the
equipment Um :
Um
UC ≥
3
Ur = 1.25 × UC
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n de-energizing loads
o inductive load
single-phase circuit
Let us consider the equivalent single-phase diagram in figure 5-25 with an ideal circuit-breaker
CB which has a zero arc resistance the instant the contacts separate and which carries out
interruption when the current crosses zero. Before operation of the circuit-breaker, between
points A and B, there is a voltage drop due to the load current flowing through Ls .
At the instant of interruption, the voltage at B suddenly reaches the voltage at A and the
capacitance Cs is charged through Ls . The energy exchanges between Cs and Ls make
voltage oscillations at frequencies of 5 to 10 kHz occur.
The voltage at C suddenly decreases to zero and the capacitance C p is then discharged
through L . The energy exchanges between Cp and L create voltage oscillations at
frequencies going from 1 to 100 KHz.
A Is CB
B ID C IL
Ls
VA Cs Cp L
I0
Lp
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In the case of VT with a single secondary, a charging resistor is installed on each phase
(see fig. 5-19).
100
A resistance value equal to 68 Ω is recommended for a secondary voltage of V .
3
VT VT VT
r
r
r
measurements
Figure 5-19: protection against risks of ferro-resonance using resistors with single secondary VT
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
When lightning strikes the line protection rope, part of the current flows through the pylon since
the protection rope is connected to it (see fig. 5-42).
This results in a potential rise at the top of the pylon the value of which depends on the self
inductance L of the pylon and the resistance R of the earth electrode:
di ( t )
U (t ) = k R i (t ) + L
dt
k : ratio of the current shunted into the pylon by the incident current
lightning strike
i
k.i
U protection rope
k .i
di
U = k R × I + L
dt
The voltage U may reach the impulse sparkover voltage of the insulators and cause a
breakdown. This is "back-flashover". Part of the current is then propagated along the affected
phase(s) towards the users. This current is in general greater than that of a direct lightning
strike.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction , either partly of this document are not allowed without our written consent.
We can see that reactance earthing of the neutral (case with restrike) clearly increases the
magnitude of the overvoltages. Resistance earthing is thus preferable. In the latter case, we
see that the overvoltages do not exceed 240 % when the ratio of the current in the earthing
resistor to the network capacitive current is equal to 2 (see fig. 5-34). In networks with
resistance earthing, the following relation should therefore always be respected if possible:
I rN > 2 I C
ZN C C C
or r If
N
CB : circuit-breaker
V1 , V2 , V3 : single-phase voltages
Xnet CB
~
ZN C
or r
N
If
IC
I rN
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In high voltage, the substation earth electrode value ( Re ) is very low compared with the
transformer and line impedances. The fault current is thus independent of Re ; it is thus
considered to be a source of current with a value of I f .
The equivalent Thevenin’s diagram of the current source I f with an internal impedance of
Re is shown in figure 5-11.
Re
equivalent
If Re Ve Re I f
Figure 5-11: equivalent Thevenin’s diagram of the current source I f with an internal impedance of Re
Re Rc Lc
Z MV Z MV Z MV
Ve Re I f
C C C
Figure 5-12: equivalent MV network diagram on occurrence of an earth fault on the substation HV side
The transformer and cable impedances are negligible compared with the cable phase-earth
1
capacitance: Z MV << .
Cω
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n symbols
In the following paragraphs, the symbols used have the following signification:
Im : part of the earth fault current in the high voltage installation which flows through the earth electrode of the
transformer substation exposed conductive parts
Re : transformer substation earth electrode resistance
V : low voltage installation phase-to-neutral voltage
U : low voltage installation phase-to-phase voltage
U f : fault voltage in the low voltage installation, between the exposed conductive parts and earth
U1 : stress-voltage in the transformer substation low voltage equipment
U 2 : stress-voltage in the installation low voltage equipment
In these two systems, the substation, neutral and installation earth electrodes are the same.
Inside the equipotential area, the ground and exposed conductive part potentials increase
simultaneously. The touch voltage U f is then zero.
On the other hand, outside this area, the ground potential remains equal to that of the remote
earth, while the potential of the exposed conductive parts increases to U f = Re I m .
Thus, when there are exposed conductive parts outside of the equipotential area and the
touch voltage U f = Re I m cannot be cleared in the time defined in tables 2-3-a and 2-3-b, the
TN − a and IT − a earthing systems are not acceptable in relation to the protection of
persons.
TN − b and IT − b earthing systems allow dangerous touch voltages to be cleared but make
overvoltages occur:
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n characteristics
- the rated voltage, which is the maximum specified value of the power frequency rms voltage
permitted between its terminals for which the surge arrester is designed to function
correctly. This voltage can be continuously applied to the surge arrester without this
modifying its operating characteristics.
- the sparkover voltages for the different wave forms (power frequency, switching impulse,
lightning impulse, etc.).
n operating principle
Figure 5-48 shows that, unlike the non-linear resistor type gapped surge arrester, the zinc
oxide surge arrester is only made up of a highly non-linear variable resistor.
The resistance goes from 1.5 MΩ at the duty voltage (which corresponds to a leakage current
below 10 mA) to 15 Ω during discharge.
Following the passage of the discharge current, the voltage at the terminals of the surge
arrester become equal to the network voltage. The current which flows through the surge
arrester is very weak and is stabilised around the value of the earth leakage current.
Because of the high non-linearity of the ZnO surge arrester a high current variation causes a
low voltage variation (see fig. 5-49).
For example, when the current is multiplied by 107, the voltage is only multiplied by 1.8.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
This gives us an idea of the way a lightning wave spreads along a conductor. Figure 5-45
shows how a lightning wave spreads along an overhead line in relation to time and space.
development
in time V front : 200 kV / µs
400 kV
2 µs
t (to x constant)
spread in
space V front : 0.66 kV / m
400 kV
600 m = 300 x 2 µs
x (to t constant)
Figure 5-45: diagram showing how a lightning wave spreads along an overhead line
in relation to time and space
Let us closely examine the phenomenon that is produced at a point M , where a change of
impedance exists, separating two circuits with characterstic impedances of Z1 and Z 2
(see fig. 5-46).
v1 v2
i1 i2
Z1 M Z2
v 1'
'
i1
1 1
J = + + j Cω U
R j Lω
U
= − jCωU
j Lω
L C ω2 =1
We thus have U = R J ; the inductance and capacitance behave like an open circuit.
For given values of L and C , the angular frequency ω r such that LC ω 2r = 1 is said to be
a resonant angular frequency.
- between the voltage that is produced at the terminals of the parallel R , L, C circuit when
the resonance occurs
- and the voltage that would be produced on occurrence of the resonance if the inductance
(or capacitance) were the only circuit element
RJ
f =
Lω r J
R
f = = RCωr
Lω r
The most current example of parallel resonance is the case of a network having harmonic
currents (patterned by current sources) and reactive energy compensation capacitors
(see § 8.1.5).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
o example
Let us consider a YNyn, 33 kV/11 kV transformer with a power rating of Sn = 24 MVA (see
IEC 909-2 table 3 A) supplying a network with 240 mm² aluminium cables the longest outgoing
feeder of which is 5 km. The neutral earth electrode resistance is 0.5 Ω.
- transformer characteristics:
Usc = 24.2 %
RT
= 0.046
XT
X(0 )T
= 0.7
XT
we can deduce
U2
XT = Usc × n = 0.242 ×
11 × 10 3
= 1.22 Ω
( )
Sn 24 × 10 6
RT = 0.056 Ω
X(0 )T = 0.85 Ω
Note: the value of Usc is extremely high in relation to the transformers feeding a network with a
limiting resistor earthed neutral. The transformer here is a United Kingdom transformer adapted
to the solidly earthed neutral system.
The short-circuit voltage has been chosen high on purpose so as to minimise the short-circuit
( )
R(0)
current. Indeed, if Usc is high, the value is minimised since X(1) = XT + XC , which
X(1)
decreases the overvoltage factor (see fig. 5-3 and 5-4).
- cable characteristics:
ρ L 0.036 × 1000
RC = = = 0.15 Ω / km
S 240
XC = 0.1 Ω / km
Note: the value of X( 0 )C is highly variable (from 0.2 to 4 X(1) ) depending on what the cable is made
of and the return via the earth (remote earth, screen or earthing conductor).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
R L
V C VA
I V VA
n fuse interruption
On occurrence of a short circuit, the value of the current flowing through the fuse is higher than
its nominal fusing value.
Interruption can thus occur at any instant and not necessarily the moment the current crosses
zero.
Figure 5-24 gives an example of a transient overvoltage which occurs on the network after a
wire fuse has fused.
Volts
1000
225
t
~ 1 ms
For a transformer or a cable in low voltage, we can take the zero-sequence impedance to be
approximately equal to the positive-sequence impedance: Z(0)T = ZT and Z(0)C = ZC .
Z(1) = ZT + ZC
a 3 Z PE a Z PE
whence kM = 1− = 1− for a solid fault ( R f = 0 )
3 ( ZT + Z C + Z PE ) Z PE + ZT + Z C
j 2π
a=e 3 : rotation operator of 120°
The overvoltage will be maximum when Z T is negligible compared with Z PE + ZC , which is the
case for a long length cable.
a Z PE
Thus kM ≤ 1−
Z PE + ZC
For an aluminium cable cross-sectional area smaller than 120 mm², the reactance can be
neglected compared with the resistance, which thus gives us:
Z PE RPE 2
≅ = since RPE = 2 RC
Z PE + ZC RPE + RC 3
2
whence kM ≤ 1− a
3
2 1 3
kM ≤ 1− − + j
3 2 2
k M ≤ 1.45
We can show that for a cable with a large cross-sectional area (> 120 mm²), the overvoltage
will be lower than in the case of a small cross-sectional area.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
On saturation, L ( I ) becomes very weak and the voltage almost stops increasing when I
rises.
The network operating point is located at the intersection of curve (b) having the equation:
I
v = VL −
Cω
v = V 2 − R2 I 2
There are three possible operating points: M , N , P . M and P are stable, N is unstable.
A voltage disturbance can make the circuit move from point M to point P . This results in a
high current and high overvoltages at the inductance and capacitance terminals. Ferro-
resonance can be avoided if the resistance R is sufficiently high for ellipse (a) to stay within
zone OSA , even when there is a high overvoltage.
VL
resonance
VC
V ''' (a''')
X (b)
V
' S (a') T
V N (a)
M P
''
V Q A
(a'')
O IQ IM IS IN IA IP IT IX I
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
V2
I = IT2 − (a)
R2
I = C ω V − IL (b)
For any value of IT , the intersection of curves (a) and (b) gives the V solutions of equation
(3); figure 5-15 shows the graphic resolution of this equation.
V2
2
+ I 2 = IT2
R
and having one half axis which is equal to IT and the other to R IT . An ellipse corresponds
to each total current value IT .
Curve I L (V ) presents a very steep slope when V increases owing to the saturation of the
V
coil's iron core: I L (V ) = .
L (V ) ω
On saturation, L (V ) becomes very weak and the current then highly increases (see fig. 5-15).
The OSA portion of curve (b) corresponds to a lead current in relation to the voltage owing to
the preponderance of the capacitive current. On the other hand, the AB part corresponds to a
lag current, since the inductive current is preponderant. The intersection of ellipse (a) and
curve (b) can give:
- an operating point Q if ellipse (a) is inside ellipse (a") passing through point A
- three operating points M , N , P if ellipse (a) is between ellipses (a') and (a")
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The clearance is directly related to the withstand of the equipment to different overvoltages.
distance
in air
creepage
distance
distance
in air
n overvoltage withstand
The overvoltage withstand depends on the type of overvoltage applied (magnitude, wave form,
frequency and duration, etc.).
- ageing
n withstand voltage
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
It is impossible to make such an ideal device, but with the interrupting techniques being based
on the behaviour of the electric arc in different dielectric media we can come close to it.
n circuit-breaker interruption
The instant the current is interrupted, an electric arc is created between the terminals of the
switching device. The conductive electric arc tends to be held by the ionizing phenomenon of
the dielectric caused by the energy dissipated.
Around current zero crossing, the dissipated energy decreases dropping below the thermal
energy supplied to the medium, the arc cools down and its resistance increases.
When the current crosses zero, the arc resistance becomes infinite and the arc is interrupted.
Between the start and end of interruption, the voltage between the poles of the switching
device goes from zero to the network voltage. This change gives rise to a high frequency
transient phenomenon called the transient recovery voltage (see fig. 5-23).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Similarly, the steepness of the wave front varies according to a log-normal distribution law. Let us
determine the probability of exceeding a given front steepness (see fig. 5-38). We can see that the
probability of exceeding a front steepness of 50 kA/µs of a negative stroke of lightning is 20 %.
Figure 5-38: probability of exceeding the front steepnesses of positive and negative
lightning currents according to IEEE (experimental statistic)
The lightning impulse wave form given by IEC 71-1 is a 1.2/50 µs wave (see fig. 5-39):
Figure 5-39: standard lightning impulse voltage wave form (IEC 71-1)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly orpartly, of this document are not allowed without our written consent.
When the supply voltage reverses back, a half period later, the potential difference at the
device terminals then reaches 4 V$n . Such an overvoltage can obviously cause renewed
restrike between the device contacts, and the previously described oscillation mechanism is
renewed with increased magnitude, leading to a new rise in the phase-neutral voltage of the
capacitances 5 V$ . ( n)
The cumulative effect of multiple restrike is obviously highly dangerous for the network
components as for the device itself.
This rise in overvoltages can be avoided by choosing the appropriate equipment, i.e. which
does not allow restrike.
VC 5V$n
V 20 ms
VC V$n
V$n 2 V$n
t
4 V$n
interruption
VC 3V$n
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
multiple restrike
If we consider the single-phase diagram in figure 5-25, we can see that in the case of restrike,
the voltage at point C almost instantaneously reaches the voltage at point B .
The capacitance C p is charged by a high frequency current (roughly 1 MHz) circulating in the
L p , Cs , CB and C p circuit.
If the circuit-breaker manages to interrupt the current at that moment, the restrike phenomenon
is repeated as the distance between the circuit-breaker contacts is still very small.
The overvoltage increase makes the occurrence of a second breakdown highly probable.
Indeed, the increase in dielectric withstand through the increase in the distance between the
circuit-breaker contacts may be lower than the increase in overvoltage.
This is why a multiple restrike phenomenon occurs with overvoltages of increasing magnitude
(see fig. 5-28).
In theory, such a phenomenon may generate overvoltages having a peak value equal to the
dielectric withstand limit of the open device, without a definite interruption of the current being
obtained. In practice, this case remains exceptional as it is enough for one of the restrikes to
allow the power frequency current to be restored; a new current half wave then flows through
the circuit-breaker. The circuit-breaker interrupts this half-wave the moment it crosses zero
when the distance between the contacts is sufficient. Thus the types of circuit-breakers
undergoing multiple restrike usually manage to interrupt the current without causing
overvoltages of very high magnitude.
VC
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
substation LV installation
U1 U2
MV ph 1 LV
ph 2
ph 3
PEN
Uf 0 Uf Re I m
equipotential zone outside
zone
U1 V U2 U1 V
Im Re
TN − a
U1 U2
MV LV
Uf 0
Uf Re I m
equipotential zone outsite zone
Im Re
U1 V 3*
U2 U1 V 3*
(*) a first LV fault is present
IT − a
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In these two cases the substation earth electrode and that of the neutral are common.
The LV installation earth electrode is separate.
The earth fault current flows through the common earth electrode (neutral/substation).
As shown in figure 5-56, we can see that there is a risk of breakdown for the LV equipment
whose earth electrode is separate from that of the substation.
whence UtM − V
Re < Im
for the TT − a earthing system
UtM − V 3
Re < for the IT − b earthing system
Im
where:
U tM : power frequency withstand voltage of the installation LV equipment equal to 2V + 1000 for V = 220 to
250 V, i.e. 1500 V
TT − a IT − b
I m = 300 A 4Ω 3.5 Ω
I m = 1000 A 1.2 Ω 1Ω
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In this case, the network is equivalent to the diagram in figure 5-33 which corresponds to the
case examined in paragraph 5.1.2.1.
At the start of contact separation, the arc voltage is weak and remains constant.
On the other hand, just before interruption, this voltage, called the extinction voltage, increases
to a more or less high value which may exceed V$n . This voltage depends on the type of
circuit-breaker (air, oil, SF6 , vacuum) as well as the arc extinction technique (cooling,
lengthening, rotating arc).
When the current crosses zero, the arc is extinguished and the recovery voltage magnitude
will depend on the extinction voltage as follows:
- for the case of neutral earthing via resistance (the fault current is in phase in relation to the
voltage), the extinction voltage limits the magnitude of recovery voltage oscillations
π
- for the case of neutral earthing via reactance (the fault current is phase shifted by in
2
relation to the voltage), the extinction voltage increases the magnitude of oscillations.
After interruption, restrike may take place if re-generation of the dielectric medium is not fast
enough in relation to the rise in recovery voltage. In this case, the magnitude of oscillations
may reach double the size of the first recovery voltage.
If we neglect the transformer and line impedances, the voltage at the terminals of the neutral
earthing impedance (VN ) is equal to the difference between the supply voltage and the
voltage at the circuit-breaker terminals. The voltage V N is vectorially added to the voltage of
the healthy phases and may lead to the latter reaching higher overvoltages than the
overvoltages observed on the fault phase.
The curves in figure 5-34 give the overvoltage levels recorded on occurrence of an earth fault
in relation to the network characteristics and the earthing impedance.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
1
j Lω I = −
j Cω
LC ω 2 = 1
We thus have U = R I ; the series inductance and capacitance behave like a short circuit.
For given values of L and C , the angular frequency ω r such that LC ω 2r = 1 is said to be
a resonant angular frequency.
An overvoltage factor f is thus defined which is the ratio of the voltage U L (or U C ) to the
supply voltage U :
U L Lω r I
f = =
U RI
Lω r 1
f = =
R RC ω r
parallel resonance
Figure 5-9 shows a parallel R , L, C circuit at the terminals of which a current source J is
applied.
IR IL IC
J C
L U
R
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
When lightning strikes the phase conductor of a line, the current i (t ) is shared out in equal
quantities on either side of the point of impact and is spread along the conductors. These have
a wave impedance Z the value of which is between 300 and 500 Ω. This impedance is that
seen by the wave front, is independent of the length of the line and of a different type from the
impedance at 50 Hz.
i (t )
U (t ) = Z .
2
U i
i
U =Z
2
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction , either partly of this document are not allowed without our written consent.
substation LV installation
U1 U2
MV L1 LV
L2
L3
N
U1 V U2 R e Im V
Uf
Uf 0
Im Re RA
TT − a
U1 U2
MV LV
*
U1 V 3
Uf
U2 Re Im V 3*
Im Re Uf RA If UL If RA
IT − b
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
electrical switchboard
disconnecting
circuit-breaker
equipment to
be protected
surge arrester
PEN
Ph1
Ph2
Ph3
PEN
electrical switchboard
disconnecting
circuit-breaker
equipment to
be protected
surge arrester
PE
PE
Ph1
Ph2
Ph3
N
PE
LV neutral
main earth (entrenched load earth
earth electrode
terminal loop) electrode
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
5.2.2. Spark-gaps
n operation
The spark-gap is a simple device made up of two electrodes, the first connected to the
conductor to be protected and the second connected to earth.
At the place where it is installed in the network, the spark-gap constitutes a weak point where
overvoltages can flow to earth and thus protects the equipment.
The sparkover voltage of the spark-gap is set by adjusting the distance in the air between the
electrodes so as to obtain a margin between the impulse withstand of the equipment to be
protected and the impulse sparkover voltage of the spark-gap (see fig. 5-47). For example,
B = 40 mm on French public EDF 20 kV networks.
45° 45°
electrode B
holder
rigid
anchoring chain
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
ZT ZC
V3
ZT ZC
V2
ZT ZC
V1
If
load 1 load 2
If
VN Re VM1 RM1 R M2
We want to know the overvoltage of the healthy phases in relation to the exposed conductive
part, which determines whether or not an insulation fault may occur on the other load:
V − VM V − VM
kM = 2 = 3
Vn Vn
In low voltage, the neutral and load earth electrode resistances are very high in relation to the
transformer and cable impedance ( Z T and Z C are roughly several tens of mΩ).
V1
If = and ( ZT + ZC ) I f ≅0
Re + RM1
The exposed conductive part of load 1 is connected to phase 1 by the fault (zero impedance).
The voltage of one healthy phase of this load in relation to the frame is V2 − V1 or V3 − V1
(since ( Z T + ZC ) I f ≅ 0 ) , whence k M = 3 = 1.73 .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Depending on the magnitude of the lightning current, two cases may occur:
I
If the maximum voltage U max = Z max is below the sparkover voltage U a of the insulator
2
string, the entire (full) wave spreads along the line.
In the case where U max ≥ U a , as a first approximation, insulator sparkover occurs at the value
of U a , and a phase-earth fault occurs at 50 Hz due to the arc being maintained. The lightning
that is propagated is thus broken at the maximum value corresponding to U a .
The lightning current causing this flashover, for a given line, is called the critical current IC
such that:
U
IC = 2 a
Z
- 5.5 kA at 225 kV, which corresponds to a probability of exceeding the magnitude according
to the IEEE method of 95 % (see figure 5-37)
- 8.5 kA at 400 kV, which corresponds to a probability of exceeding the magnitude according
to the IEEE method of 92 % (see figure 5-37).
In medium voltage, flashover is systematic in the case of a stroke of lightning occurring due to
the small distances in the air of the insulator string. This flashover of the insulator gives rise to
a phase-earth fault current, called a follow current, which is held at the power frequency of 50
Hz until it is cleared by the protections.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction , either partly of this document are not allowed without our written consent.
The physical phenomenon of lightning corresponds to a source of impulse current the actual
form of which is highly variable: it consists of a front rising up to the maximum magnitude of
several miscroseconds to 20 µs followed by a decreasing tail of several tens of µs (see
figure 5-36).
The magnitude of strokes of lightning varies according to a log-normal distribution law. We can
thus determine the probability of a given magnitude being exceeded (see figure 5-37). We can
see, for example, that for the average curve (IEEE), the probability of exceeding a magnitude
of 100 kA is 5 %. This means that 95 % of lightning strokes have a magnitude less than
100 kA.
Figure 5-37: probability of exceeding positive and negative lightning stroke magnitudes,
according to IEEE (experimental statistic)
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly orpartly, of this document are not allowed without our written consent.
In extra high voltage (> 220 kV), back-flashover is unlikely (the flashover level of the insulators
is high), which is why it is useful to install protection ropes thus limiting the number of service
interruptions. But below 90 kV back-flashover occurs even if the value of the earth electrode
resistance is low (< 15 Ω); the usefulness of protection ropes is thus limited (more frequent
service interruptions).
o induced impulse
A stroke of lightning that falls anywhere on the ground behaves like an electromagnetic field
radiation source.
The steeper the rising front of the lightning current the greater the radiation.
For front steepnesses of 50 to 100 kA/µs, the effects of this field will be felt several hundreds
of metres, if not kilometres, away.
The magnetic field H at a point located at a distance of r from a circuit through which a
current I flows, is given in the relation:
I
H=
2π r
This field creates induced voltages in the neighbouring circuits which are able to reach
dangerous values both for equipment and persons.
case of a loop
Let us consider the loop formed by the supply cable and the telecommunication link in figure
5-43, with a surface S and located 100 m from the lightning impact which has a current rising
front steepness of 80 kA/µs.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction , either partly of this document are not allowed without our written consent.
Numerical application:
5.5
Vn = = 3175
. kV
3
I f (63 kV ) = 3 kA
Re = 0.5 Ω
L ω
Q= c =4
Rc
VC = 1500 × 4 = 6 000 V
VC = 1.89 Vn
The overvoltage in the cables is roughly twice the nominal phase-earth voltage.
It can be dangerous if the substation earth electrode is of poor quality. Indeed, for Re = 3 Ω
we will have VC = 11.3 Vn .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Numerical application:
125 − 75
we then have D ≤ × 300
2 × 300
D ≤ 25 m
The surge arrester must therefore be installed less than 25 m away from the transformer for
the overvoltage not to exceed the lightning impulse withstand value.
lightning impulse
transformer
D
A B
overhead line ZC ZC
surge arrester
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
By applying an electro-geometrical model to a vertical rod with a height (see fig. 5-40-a),
we can show that there are two distinct zones:
- zone 1 : this is located between the ground and the parabola which is the locus of the
equidistant points of and the ground; the instant the flash occurs, any leader
located in this zone will touch the ground since it is nearer to this than to
- zone 2 : this is located above the parabola; the instant the flash occurs, any leader located
in this zone will be picked up by point on the vertical rod as soon as the
distance between and the leader is less than the striking distance .
For a lightning current with a value of , and thus a given striking distance, the distance x between
the point of impact on the ground and the point where the rod is fixed to the ground (called the rod
pick-up radius) is:
if
if
The rod pick-up radius is thus all the greater the more intensive the lightning stroke.
For very weak currents, the pick-up radius becomes less than the height of the rod which is then
able to pick up the current along its length. This has been experimentally proved.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly orpartly, of this document are not allowed without our written consent.
n ferro-resonance
Let us take a circuit made up of a parallel-connected capacitance, a coil with a saturable iron
core and a resistance. Let R be the resistance, C the capacitance and L the inductance
which varies with the current flowing through the coil and the voltage at the circuit terminals.
IT
IR IL IC
R L C V
The total current IT flowing through the circuit is then given by the relation (1):
V
IT = + j (C ω V − I L ) (1)
R
V2
+ (C ω V − I L )
2
IT2 = 2
(2)
R
V2 (3)
I T2 − 2
= C ω V − IL
R
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Re Rc Lc
VL
Ve Re I f 3C VC
Lc ω
We have VL =
( )
Ve
Re + Rc + j Lc ω − 3 C1ω
In the case of a Petersen coil earthed neutral, (resonance) tuning between the inductance and
1
the MV cable capacitance is aimed at as far as possible. We thus have : Lc ω ≈ and
3Cω
VC ≈ VL whence VL = Lc ω Ve .
Re + Rc
To minimise the rise in substation earth potential (Ve ), the resistance earth electrode must be
as weak as possible (of the order of 0.5 Ω).
L ω
VL = VC = c Ve = Q Ve
Rc
VC = Q Re I f
The coil quality factor must not therefore be too high in order to avoid the risk of a very high
overvoltage.
This is why, in some cases, a resistor must be connected in parallel with the coil, in order to
reduce the quality factor.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
If the phases are perfectly balanced, the voltage system is not disturbed.
In the event of load unbalance, the neutral point is displaced and the phase-neutral voltages
move close to the phase-to-phase voltage for the least loaded phases, while for the loaded
phases (weak impedance), they drop below the single-phase voltage.
Z3
V3
Z2
V2
Z1
V1 N
neutral breakdown
Z1 // Z2 Z1 // Z 3 Z2 // Z3
VN = V3 + V2 + V1 (1)
Z3 + Z1 // Z2 Z2 + Z1 // Z 3 Z1 + Z 2 // Z3
The voltage applied to the terminals of a single-phase load on phase 3, for example, will be:
V3 N = V3 − V N
1 3
If we know that V2 = a 2 V1 and V3 = a V1 , a = − + j
2 2
Z1 = R
Z2 = 2 R
Z 3 = 10 R
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The simplified method has a drawback as it does not take into account the real requirements
Um
of the network which are generally lower than .
3
- overvoltages due to a phase-earth fault the clearance time of which depends on the
protection system (see table 5.1 - the earth overvoltage factor is equal to 1.73 for unearthed
or impedance earthed networks)
The temporary overvoltage value to be taken into account is the product of the earth fault
overvoltage and load shedding factors.
- specific case
- general case
T : overvoltage duration
TOV : overvoltage value
This formula allows the 10 second overvoltage which would cause the same stress on the
surge arrester to be calculated for each temporary overvoltage.
The duration of the temporary overvoltage must be between several seconds and two to three
hours ( U10s = 0.97 × TOV for T = 2 s and U10 s = 114
. × TOV for T = 2 hours ).
The rated voltage of the surge arrester will be chosen to be above or equal to the maximum
value of the equivalent 10 second voltages: U r ≥ max (U10s ) .
Um
We will take UC ≥
3
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
three-phase circuit
When the three-phase circuit in figure 5-27 is interrupted, the first phase which sees the
current crossing zero interrupts this current. There follows a transient current circulating in the
two uninterrupted phases. Thus, if phase 1 interrupts the current first a transient voltage is
obtained between points C1 , C2 and earth which is capable of reaching a value of 2 V$n for
an ideal circuit-breaker. For an actual circuit-breaker, the overvoltage coefficient is higher than
or equal to 2.
Note: the current crosses zero on the following phase after 1/3 of a period (7 ms at 50 Hz), while the
period of oscillations is roughly 1 ms.
Ls B1 C1 L1
A1 V1
Cs Cp
Lp
Ls B2 C2 L2
A2 V2 N
Cs Cp
Lp
Ls B3 C3 L3
A3 V3
Cs Cp
Lp
restrike phenomenon
The instant a circuit is interrupted, the voltage at the terminals of the circuit-breaker quickly
increases (roughly from 0.1 to 0.5 kV/µs). If the circuit-breaker poles separate shortly before
the current reaches zero (for an inductive circuit, this corresponds to the maximum voltage),
regeneration of the dielectric medium may not be sufficient to withstand the stress-voltage.
Indeed, in this case, the voltage is maximum and the poles are closer together.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The transients generated by the first phase that creates overvoltages may cause, owing to the
capacitive coupling between the phases, oscillating currents inside circuits L p , C p, Cs of the
other phases.
It is thus possible to obtain zero current in these phases, immediately (several hundreds of a
microsecond) after interruption of the first phase.
If the circuit-breaker interrupts such currents, a chopping current phenomenon is then created
with very high chopping current and overvoltage values.
Overvoltages caused by current chopping can themselves lead to restrike. They are almost
systematic in the case of the virtual chopping current.
Interruption of capacitive circuits, such as a capacitor bank or off-load cable, raises less
difficulties than the interruption of inductive circuits.
Indeed, the capacitances remain charged at the peak value of the 50 Hz wave after extinction
of the arc when the current reaches zero and the recurrence of voltage at the switchgear
terminals is accompanied by a 50 Hz wave.
Nevertheless, one half period after interruption, the device is subjected to a voltage equal to
twice the 50 Hz peak voltage 2 V$n . ( )
If the speed and dielectric withstand of the device are not sufficient to withstand this stress,
restrike may occur. It is followed by a voltage reversal at the terminals of the capacitances,
raising them to a phase-neutral voltage equal to 3 V$n maximum (if damping is neglected).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Non-linear resistor type gapped surge arresters are especially found in HV and MV
installations which have been in operation for several years. The current tendency is to use
zinc oxide surge arresters which provide better performance.
n definitions
5.2.3.1. Non-linear resistor type gapped surge arresters (see IEC 99-1)
n operating principle
In this type of surge arrester, a variable resistor (varistor), which limits the current after the
passage of the impulse wave, is associated with a spark gap.
After evacuation of the impulse wave to earth, the surge arrester is only subjected to the
network voltage and the follow current is limited by the varistor.
The arc is systematically extinguished after the 50 Hz wave of the single-phase-to-earth fault
current has reached zero.
Owing to the variation of the resistance, the residual voltage is maintained close to the
sparkover level. Indeed, this resistance decreases with the increase in current.
Various techniques have been used to make non-linear resistor type gapped arresters. The
most conventional method uses a silicon carbide (SiC) resistor.
Some surge arresters also have voltage grading systems (resistive or capacitive dividers) and
arc blowing systems (magnets or blow-out coils).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The overvoltage factor and fault duration influence the choice of equipment insulation voltage
level.
Rapid clearance of the fault, and thus a short overvoltage time, means that the switchgear
phase-earth insulation level does not have to be higher than the nominal single-phase voltage.
Since the power supply does not have to be interrupted on occurrence of a first fault, the
overvoltage is likely to occur for a long period of time (several hours). It is therefore advisable
to choose switchgear with a phase-earth insulation level that is suitable for the nominal phase-
to-phase voltage.
Note: some manufacturers give a phase-earth insulation withstand equal to the single-phase voltage,
but stipulate that their switchgear can be implemented in an unearthed neutral network. There
are also switchgear standards that specify an insulation level compatible with use in an
unearthed neutral network.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The overvoltage at a point on the network where the impedance changes is given in the
relation:
Z2
v2 = 2 v1 (see § 5.1.4)
Z1 + Z2
We thus have:
Ze
v2 = . 2 Ursd
Zc + Ze
The equipment lightning impulse voltage U tc must be above the overvoltage v2 , whence:
Ze
Utc ≥ . 2 Ursd
Zc + Z e
Zc
Ze ≤
( 2 Ursd
Utc −1 )
For U rsd = 120 kV
and Z c = 330 Ω , the impulse impedance Z e is equal to 1.5 times the
Z
resistance Re measured in low frequency: Re = e .
1.5
The condition on the value of the substation earth electrode impedance is thus:
Zc
Re ≤
( U
1.5 × Ursd − 1
tc
)
The maximum values of Re for the different earthing systems are given in table 5-9.
Earthing system TN − b , TT − b , IT − c TT − a , IT − b
U tc (kV) 4 8 20 3
Table 5-9: maximum values of the MV/LV substation earth electrode resistances
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
we can determine:
R(1) = RT + RC
X(1) = XT + XC
R(0) = 3 Re + RT + RC
X(0 ) = X(0 )T + X(0)C
Note: A factor 3 appears before Re . The reason for this is explained in figure 4-11 of the Industrial
network protection guide.
R(0) 8
X (1)
7
k = 1.7
6
5 k = 1.6
3
k = 1.5
2
k = 1.4
1
k = 1.3
k = 1.2
X(0)
1 2 3 4 5 6 7 8
X (1)
X(0 ) R(0)
Figure 5-3: earth fault factor in relation to ratios and
X(1) X(1)
for R(1) = 0 and R f = 0
R(0) 8
X (1)
7 k = 1.7
k = 1.6
6 k = 1.5
4
k = 1.4
3
2 k = 1.3 k = 1.5
k = 1.2
1
X(0)
1 2 3 4 5 6 7 8
X (1)
X(0 ) R(0)
Figure 5-4: earth fault factor in relation to ratios and
X(1) X(1)
for R(1) = 0.5 X(1) and R f = 0
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Different types of overvoltage may occur in industrial networks. Devices must therefore be
installed to reduce their magnitude and the insulation level of equipment must be chosen so
that fault risks are reduced to an acceptable level.
5.1. Overvoltages
An overvoltage is any voltage between one phase conductor and earth, or between phase
conductors having a peak value exceeding the corresponding peak of the highest voltage for
equipment, defined in standard IEC 71-1.
n origin of overvoltages
o internal origin
These overvoltages are caused by a given network element and only depend on the
characteristics and structure of the network itself.
For example, the overvoltage that occurs when a transformer's magnetizing current is
interrupted.
o external origin
These overvoltages are caused or transmitted by elements outside the network, for example:
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
series resonance
Figure 5-7 shows a series R , L, C circuit at the terminals of which a voltage U is applied.
I R L C
The voltage U is the vectorial sum of the voltages at the terminals of each element:
U = U R + U L + UC
1
= R I + j Lω I +
jCω
The vectorial diagram in figure 5-8 shows that for certain values of L and C , the voltages at
the terminals of the inductance and capacitance may be higher than the network voltage U :
jL I
1
I
jC
RI
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
dφ dB dH
e=− = −S = − µ0 S
dt dt dt
dH 1 dI 1 103
now = = × 80 × −6 = 127 × 106 A / m / s
dt 2 π r dt 2 π × 100 10
A phase-earth overvoltage of 19 kV thus occurs on the loop. This has a very short duration
( ≈ 1µs ) but can cause insulation breakdown.
lightning impulse
front steepness = 80 kA/µs telecommunication link computer
circuit
loop
surface = 120 m²
supply cable
magnetic field
100 m
printer
phase-earth insulation
subjected to 19 kV ( 1 µs)
earth
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction , either partly of this document are not allowed without our written consent.
- hazard to man and animals following rises in potential and occurrence of step and touch
voltages.
- an earth fault
- resonance or ferro-resonance
Figure 5-1 shows that on occurrence of a solid earth fault, the voltage between the neutral
point and earth becomes equal to the single-phase voltage:
VNeutral = Vn
The phase-earth voltage of healthy phases thus becomes equal to the phase-to-phase
voltage:
V2 E = VNeutral + V2 = V2 − V1
V3E = VNeutral + V3 = V3 − V1
whence V2 E = V3E = 3 Vn
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
5.3.1. General
Co-ordinating the insulation of an installation consists in determining the insulation
characteristics necessary for the various network elements, in view to obtaining a withstand
level that matches the normal voltages, as well as the different overvoltages.
Optimal insulation co-ordination gives the best cost-effective ratio between the different
parameters depending on it:
- cost of failures (loss of operation and destruction of equipment), taking into account their
probability of occurrence.
With the cost of overinsulating equipment being very high, the insulation cannot be rated to
withstand the stress of all the overvoltages studied in paragraph 5.1.
Overcoming the damaging effects of overvoltages supposes an initial approach which consists
in dealing with the phenomena that generate them, which is not always very easy. Indeed, if
using the appropriate arc interruption techniques the switchgear switching overvoltages can be
limited, it is impossible to prevent lightning strikes.
- gas clearance (air, SF6, etc.), which is the shortest path between two conductive parts.
- creepage distance: this is also the shortest path between two conductors, but following the
outer surface of a solid insulating material (e.g. insulator).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Figure 5-21 shows a solidly earthed network feeding a three-phase transformer having a delta-
connected primary. This can also apply to a star-connected transformer with an unearthed
neutral. If, when the switch is closed, one of the poles remains accidentally open or closes
late, for example the pole of phase 1, series ferro-resonance may occur in the circuit including:
Very high overvoltages can occur at the transformer terminals and between phase 1 and the
earth.
This type of ferro-resonance has frequently been encountered on HV networks with solidly
earthed neutral. It may also occur when a switch is opened. The means of protecting against
this type of ferro-resonance consists in inserting a resistor in the supply transformer neutral
point earthing. This solution does not however provide total protection since ferro-resonance
can, for example, occur in the circuit including the transformer AC winding and the
capacitances of phases 1 and 3 in relation to earth.
V3 switch
A
V2 Ph 3
L
L
V1 Ph 2 B L
Ph 1 If C
C C C
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In the case of VT with two secondaries, a resistor is installed in the open delta of one of the
two (see fig. 5-20).
100
For a secondary voltage of V , on occurrence of a solid earth fault, the voltage at the
3
resistor terminals is equal to 100 V; the resistance value is then determined:
R≤
(100) 2
50
R ≤ 200 Ω
VT VT VT
measurements r
Figure 5-20: protection against the risks of ferro-resonance via a resistor with two-secondary VT
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The lightning conductor diverts lightning to itself in order to protect equipment. Its principle is
based on the striking distance; tapered rods are placed at the top of equipment to be
protected, they are connected to the earth by the most direct path (the lightning conductors
surrounding the structure to be protected and interconnected with the earthing network).
The electrogeometric model allows the zone to be protected to be determined using the fictive
sphere method.
The point of impact of the lightning is determined by the object on the ground the closest to the
leader starting distance d . Everything happens as if the leader was surrounded by a fictive
sphere with a radius d moving with it. For good protection, the fictive sphere rolling on the
ground reaches the lightning conductor without touching the objects to be protected
(see fig. 5-40-b).
Protection against direct lightning strikes is approximately good in a cone the top of which is
the top of the lightning conductor and the half-angle at the top is 45 °.
leader
protected
zone fictive
(cone) sphere
lightning
conductor
45°
lightning density
On a world-wide scale, 63 billion discharges are recorded on average each year which
corresponds to 100 discharges per second. In France, this figure varies from 1.5 to 2 million
lightning strokes per year.
We then define the lightning density as being the number of days per year on which
thunder has been heard in a place.
In France, the average value of is 20 with a variation range going from 10 in channel
coastal regions up to over 30 in mountainous regions.
The value of may be much higher and reach 180 in tropical Africa or Indonesia.
The lightning strike density represents the number of lightning strikes per km2 per year,
whatever their current value levels.
The lightning impact mechanism begins with a leader from a cloud which approaches the
ground at a low speed. When the electric field is sufficient, sudden conduction is established
giving rise to the lightning discharge.
An experimental practical approach has enabled the relation linking the current of the
lightning strike to the distance between the starting point (leader position) and discharge point
(point of impact connected to the earth) to be found:
: striking distance, in m
: lightning current, in kA
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly orpartly, of this document are not allowed without our written consent.
n protection distance
The wave propagation phenomenon studied in § 5.1.5. shows that at the point of reflection
(e.g. MV/LV transformer), the overvoltage reaches double the value of the incident wave.
The surge arrester peaks at a sparkover voltage U rsd (equal to the residual voltage for ZnO
surge arresters).
If it is located a considerable distance away, the maximum voltage at the location of the
equipment to be protected will thus be 2 U rsd . Now, the equipment impulse withstand is
generally lower than 2 U rsd .
To overcome this drawback, the surge arrester is installed at a shorter distance away than the
"protection" distance D . The surge arrester then undergoes the sum of the incident wave and
the reflected wave. It is thus sparked for an incident wave below U rsd .
Assuming that at the equipment termination point, the wave is totally reflected, we can show
D
that the overvoltage in relation to the equipment is limited to U = U rsd + 2 r
v
dV
r= : rise front steepness of the voltage wave, kV/µs
dt
v : wave propagation speed, m/µs
For a lightning impulse withstand voltage Ul , the surge arrester must therefore be located at
a distance D such that:
D
Ursd + 2 r ≤ Ul
v
U − U rsd
whence D≤ l ⋅v
2r
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The earth and the electrosphere, the conductive area in the atmosphere (about 50 to 100 km
thick), constitute a natural spherical capacitor which is charged by ionization, thus producing
an electric field directed towards the ground of roughly several hundred volts/metre
Since air is not very conductive, there is thus an associated permanent conduction current, of
roughly 1 500 A for the entire earth's globe. Electrical balance is ensured during discharges by
rain and strokes of lightning.
The formation of storm clouds, masses of water in the form of aerosols, is accompanied by
charge separation electrostatic phenomena: the positively charged light particles are driven by
the rising air currents, and the negatively charged heavy particles fall because of their weight.
At the base of the cloud, there may also be islets of positive charges where heavy rains are
located.
When the breakdown withstand limit gradient is reached, a discharge is produced inside the
cloud or between clouds or between the cloud and the ground. In the latter case, it is referred
to as lightning.
The cloud-ground electric field can reach 15 to 20 kV/metre on flat ground. But the presence of
obstacles deforms and locally increases this field by a factor of 10 to 100 or even 1 000
depending on the form of the obstacles (also called the "peak effect"). The atmospheric air
ionizing threshold is thus reached, i.e. roughly 30 kV/cm, and corona effect discharges are
produced. When these discharges are located on fairly high objects (tower, chimney, pylon)
they may divert lightning to this objects.
Strokes of lightning are classed according to the origin of the discharge (or leader) and their
polarity.
- either descending from the clouds to the ground in the case of fairly flat land
- or ascending from the ground to the clouds in the case of mountainous land.
Depending on the polarity the following distinctions between lightning strokes are made:
- negative when the negative part of the cloud is discharged, which represents 80 % of cases
in temperate countries
- positive when the positive part of the cloud is discharged.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly orpartly, of this document are not allowed without our written consent.
The loads affected by these phenomena are off-load transformers, neutral point coils (neutral
reactance earthing) and motors during the starting period for inductive circuits as well as
capacitor banks for capacitive circuits.
Transformers undergo impulse wave dielectric tests; because of this, they are better built than
motors to be able to withstand the transients caused by restrike (see IEC 76-3).
The case of motors is different. At each start, they must withstand the transients caused by
prestrike. Moreover, even if interruption during the starting period does not occur very often, it
is nevertheless a possibility and they are then subjected to multiple restrike.
Motors are thus especially sensitive to multiple prestrike, because of its high rate of
occurrence, as well as to multiple restrike, due to the magnitude of the overvoltages produced.
These overvoltages cause deterioration of the insulation of the first turns.
In order to limit overvoltages, Zn0 type surge arresters can be connected in parallel with the
load.
But the best method consists in using switching devices suitable for the type of application.
Table 5-3 gives the behaviour of medium voltage switchgear with respect to the phenomena
relating to the switching overvoltages studied.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Let us take a series circuit made up of a resistance, a coil with a saturable iron core and a
capacitance. We have:
I
V = R I + j VL − (1)
Cω
2
I
V 2 = R 2 I 2 + VL − (2)
Cω
2
I
or: V 2 − R2 I 2 = VL − (3)
Cω
I
V 2 − R2 I 2 = Lω I − (4)
Cω
R L C
I
VR VL VC
As for the parallel circuit, this equation can be graphically resolved as a function of I ,
by plotting curves (see fig. 5-17):
v = V 2 − R2 I 2
I
and v = VL −
Cω
Curve VL ( I ) presents a very small slope when I increases owing to the saturation of the
coil's iron core VL ( I ) = L ( I ) ω V .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
- surge diverters designed to protect telephone networks, LV terminal boxes and loads.
- zener diodes
Zener diodes have the drawback of only ensuring the protection of a precise point in the
network. The gas discharge tube requires the addition of a varistor to prevent follow current.
Variable resistor-type surge arresters are currently the most cost-effective solution owing to
their simplicity and reliability
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
For phases 2 and 3, the capacitance-inductance assembly behaves like an inductance, and for
phase 1, like a capacitance. If we plot the voltage vector diagram, we can see:
- that the voltages in relation to earth of the other two phases are very high
- that there is a very high potential difference between the neutral point and earth
(see fig. 5-18).
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In lightning impulse conditions, the transformer behaves like a capacitive divider with a ratio of
s ≤ 0.4 . It is equivalent to a capacitance Ct (see figure 5-44-a).
equivalent Ct
lightning wave
U0 sU1
U1 U0 sU1
U 0 represents the no-load overvoltage, i.e. when the secondary outgoing terminals are not
connected to any cables or lines. This overvoltage is generally not acceptable by the
transformer.
In reality, the transformer is connected to a network with a capacitiance Cs . This plays the
role of a voltage divider with the transformer capacitance Ct (see fig. 5-44-b).
Ct
U 0 = sU1 Cs U2
Ct
U2 = s U1
Ct + Cs
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction , either partly of this document are not allowed without our written consent.
These overvoltages will cause a breakdown in equipment insulation if provisions to limit them
are not taken.
V3
Ph 3
V2
Ph 2
V1
Ph 1
N
v1T C C C
L L L
V1
vN
v3T
v2T
N
V3 V2
- they must not be too weak, so that the VT are not overcharged and their accuracy is
maintained.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
With the circuit being initially unused, the total current IT is zero, as well as the voltage V , and
ellipse (a) is reduced to point O . If the current increases, the length of the axes of ellipse (a)
increases and the voltage rises, the operating point M moves along branch OS of curve (b).
When the total current exceeds the value I T' for which ellipse (a') cuts curve (b) at S , the
operating point suddenly jumps from point M to point T located on branch AB of curve (b), it
then moves along this branch. The voltage thus suddenly increases, going from VS to VT , and
then it continues to increase if the current IT increases.
If the total current now decreases, the operating point moves along branch AB and stays
there, even if the current drops below the value I T' corresponding to ellipse (a'). When the
current reaches the value IT , the operating point is P instead of M . It only returns to
branch OS if the current drops below the value I T'' corresponding to ellipse (a") passing
through point A . When this occurs, the operating point suddenly jumps from A to Q , and
the voltage from V A to VQ .
We can thus see that two stable operating conditions, for which the voltage at the circuit
terminals takes very different values, for example V M and VP , can correspond to the same
rms current value IT .
Finally, if the initial operating conditions correspond to a weak voltage (branch OS ), with a
resulting capacitive current, it is possible that, following a sudden change in operating
conditions leading to a transient phenomenon (overcurrent or overvoltage), the resulting
current becomes inductive and the voltage maintains a high value, even once the disturbance
has disappeared.
Ferro-resonance can be avoided if the resistance R is sufficiently weak for ellipse (a) to
remain within zone OSA , even when there is a high overcurrent.
IC C V
(b)
resonance C V IL
capacitive operating B
conditions
X (a''')
IT'''
' S T (a')
IT
IT P (a)
M N
IT''
Q (a'') A
O VQ VM VS V N VA V P VT V
If the bank is energized shortly afterwards, a breakdown due to the application of a voltage of
opposite polarity may give rise to an overvoltage of 3 V$n .
L CB
U C
To ensure the safety of persons, the capacitor banks are fitted with a discharging resistor
having a time constant allowing 75 V to be reached after 3 minutes in LV and 10 minutes in
HV.
The phenomena created by de-energizing (or energizing) loads, which we have studied, lead
to transient overvoltages which may be dangerous for both loads and other network elements.
Table 5-2 gives the level of overvoltages and their characteristics for each phenomenon
studied.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The values of Ct are generally between 1 and 10 nF. The capacitance of a cable is close to
0.4 nF/m. Thus, several tens of metres of cable will greatly reduce the overvoltage transferred
to the secondary.
In general, the network is sufficiently widespread for the overvoltage transferred not to raise
any difficulties.
However, in the case of a short cable, e.g. between a specific transformer and a load (arc
furnace, etc.), the overvoltage transferred may be unacceptable for the equipment on the low
voltage side.
- use a surge arrester with a lower sparkover voltage on the high voltage side
- install a surge arrester on the low voltage side between each phase and earth
- increase the capacitance between each phase and earth on the low voltage side.
For high frequencies (case of switching and lightning overvoltages), the line is characterised by
its so-called "characteristic" or "wave" impedance:
L
Zc ≈
C
L : line inductance
C : line capacitance
We can see that this impedance is independent of the length of the line.
The speed of the wave propagation on an overhead line is close to the speed of light:
c
for cables, it is equal to v =
εr
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction , either partly of this document are not allowed without our written consent.
Figure 5-10 shows the diagram of a Petersen coil earthed HV/MV substation when an HV
earth fault flows through the common earth electrode.
HV HV / MV transformer Z MV
If C
Lc , Rc
Re1
Ve Re
Figure 5-10: HV earth fault in an HV/MV substation with a Petersen coil earthed neutral
The symmetrical component method gives us the fault current value as (see § 4.2.2 of the
Network protection guide):
3 Vn
If =
Z(1) + Z( 2 ) + Z( 0 )
where Z(1) = ZT + Z l
Z( 2 ) = Z T + Z l
(0 Z( )T + Z 0)l + e Re1
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In practice, for the voltage range 1 kV ≤ U m ≤ 52 kV , two values of I nd are available: 5 kA and
10 kA.
o mechanical characteristics
The IEC 99-4 and 99-5 standards fix the allowable pressure limit (expressed in "kA") which
must be met for the three-phase short circuit at the surge arrester terminals.
- the altitude
The protection level of the surge arrester at the installation point corresponds to the residual
voltage (U rsd ) at its terminals when its nominal discharge current flows through it.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The equipment is only protected properly if certain installation rules are followed:
- rule 1
The length of the connection between the surge arrester and its disconnecting circuit-breaker
must be below 0.5 m.
disconnecting
circuit-breaker
L < 50 cm load to be
protected
- rule 2
The outgoing feeders of the protected conductors must be connected to the terminals of the
surge arrester and its disconnecting circuit-breaker.
- rule 3
The loop surfaces must be reduced by tightly grouping together the incoming, phase, neutral
and PE wires.
- rule 4
the incoming wires of the surge arrester (polluted) must be moved away from the protected
outgoing wires (healthy) in order to avoid any possible electromagnetic coupling.
- rule 5
The cables must be flattened against the metal structures of the box in order to reduce frame
loops and thus benefit from a reduction in disturbances.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In figures 5-52-a and 5-52-b the connection layouts of the LV surge arrester are shown for
different earthing systems.
electrical switchboard
disconnecting
RCD circuit-breaker
equipment
to be protected
surge arrester
PE
PE
Ph1
Ph2
Ph3
N
LV neutral
main earth load earth
earth electrode (entrenched
terminal electrode
loop)
TT earthing system
electrical switchboard
disconnecting
circuit-breaker
equipment
to be protected
surge
arrester
PE
PE
Ph1
Ph2
Ph3
N
PIM overvoltage
limiter
main earth (entrenched load
LV neutral terminal earth
earth electrode loop)
electrode
IT earthing system
Figure 5-52-a: connection layout of an LV surge arrester for TT and IT earthing systems
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The objective is to avoid a direct impact on structures by catching the lightning and directing it
towards designated flow points, via:
- lightning conductors, whose principle is based on the striking distance; a rod placed at the
top of a structure to be protected captures the lightning and evacuates it through the
earthing network (see fig. 5-40-b)
Its aim is to ensure that the basic impulse level (BIL) of the substation components has not
been exceeded.
In HV, this type of protection is established using elements ensuring that the lightning wave
flows to earth, such as:
- spark-gaps
- HV surge arresters.
It uses:
- series filters
- overvoltage limiters
- LV surge arresters.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
U1 U2
MV ph 1 LV
ph 2
ph 3
PEN
U1 Re Im V
Uf
Im Re RB U2 V
Uf 0
TN − b
U1 U2
MV ph 1 LV
ph 2
ph 3
N
U1 Re Im V
Im
Uf
Re RB RA
U2 V
Uf 0
TT − b
U1 U2
MV LV
U1 Re I m V 3 *
U2 V 3
Im Re Z If RA U f
Uf RA If UL
IT − c
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
When weak currents, notably lower than the nominal current of the circuit-breaker, are
interrupted, the arc which occurs occupies a small volume. It consequently undergoes
considerable cooling linked to the circuit-breaker's capacity to interrupt much higher currents.
Owing to this fact, the arc becomes unstable and its voltage may present relatively large
variations, while its absolute value remains lower than the network voltage (case of SF6 or
vacuum). These voltage variations may generate high frequency oscillating currents, with a
magnitude that may reach 10% of the current at 50 Hz, in the nearby capacitances ( Cs , L p , C p
circuit in figure 5-25). Superposing these high frequency currents on the current at 50 Hz
results in multiple crossings of the current through zero around zero of the fundamental wave
(see fig. 5-29).
The circuit-breaker interrupts the current the first time it crosses zero while the load current
(only the current at 50Hz) is not zero. The value of this current represents what we call the
chopping current Ichop . ( )
current in the
circuit-breaker
I chop
"chopping"
current
extinction
possible
50 Hz wave
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n TN earthing system
The current of an earth fault circulates in the protective conductor. The neutral earth electrode
resistance is thus not used to determine the zero-sequence impedance
(see fig. 5-5).
ZT ZC
V3
ZT ZC
V2
V3 VM
ZT ZC
V1
V2 VM
Z PE VM
Re
V1 , V2 , V3 : single-phase voltages
ZT : transformer impedance
ZC : cable impedance
Z PE : protective conductor impedance
VM : potential of exposed conductive parts (masses) in relation to earth
Re : neutral earth electrode resistance
We are interested in the overvoltage of the healthy phases in relation to the exposed
conductive part, which determines whether or not an insulation fault may occur on the other
V − VM V − VM
load: k M = 2 = 3 .
Vn Vn
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n classification of overvoltages
Standard IEC 71-1 gives the classification of overvoltages according to their duration and form.
According to the duration, a distinction is made between temporary overvoltages and transient
overvoltages:
. slow-front overvoltage
. fast-front overvoltage
. very-fast-front overvoltage.
Standard IEC 71-1 gives the standardised wave forms used to carry out tests on equipment:
- switching impulse: this is an impulse voltage having a time to peak of 250 µs and a time to
half-value of 2500 µs.
- lightning impulse: this is an impulse voltage having a front time of 1.2 µs and a time to
half-value of 50 µs.
n consequences of overvoltages
The consequences can be very varied depending on the type of overvoltages, their magnitude
and their duration. They are summed up as follows:
- breakdown in the insulating dielectric of equipment in the case where the overvoltage
exceeds the specified withstand
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
On occurrence of an earth fault on one network phase, a high current is generated which
circulates in the circuit formed by the fault phase, earth and neutral earth electrode
(see fig. 5-2).
At the fault point, the three-phase voltage system is disturbed. The fault phase voltage in
relation to earth is almost zero if we neglect the fault resistance. The voltages of the other two
phases in relation to earth are higher than the single-phase voltage, while remaining lower
than the phase-to-phase voltage.
V3
ZT ZC
V2
ZT ZC
V1
ZT ZC
fault
V1E V2 E V3E
Re Rf
V1 , V2 , V3 : single-phase voltages
ZT : transformer impedance
ZC : cable impedance
Re : neutral earth electrode resistance
Rf : fault resistance
Figure 5-2: equivalent diagram of a phase-earth fault when the neutral is solidly earthed
Thus, we can define an earth fault factor k characterising the phase-earth overvoltage
occurring on the healthy phases:
V2 E = V3E = k Vn
The symmetrical component calculation method (see § 4.2.2. of the Protection guide) can be
used to determine the value of k in relation to the positive, negative and zero-sequence
impedances:
Z(1) + a 2 Z( 2 ) + a Z( 0 )
k = 1−
Z(1) + Z( 2) + Z( 0 ) + 3 R f
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n advantages
n drawbacks
- The sparkover characteristics of the spark-gap are highly variable (up to 40 %) depending
on the atmospheric conditions (temperature, humidity, pressure) which modify the ionization
of the dielectric medium (air) between the electrodes.
- spark-gap sparkover causes a power frequency phase-to-earth short circuit owing to the arc
being maintained. The short circuit lasts until it is cleared by the switching devices (this
short circuit is called a follow current). This means that it is necessary to install shunt circuit-
breakers or rapid reclosing system on the circuit-breaker located upstream. Because of this,
the spark-gaps are unsuitable for the protection of an installation against switching
overvoltages.
- the sparkover caused by a steep front overvoltage is not instantaneous. Due to this delay,
the voltage actually reached in the network is higher than the chosen protection level. To
take this phenomenon into account, it is necessary to study the voltage-time curves of the
spark-gap.
- sparkover causes the appearance of a steep front broken wave which could damage the
windings of the transformers or motors located nearby.
Although still used in certain public networks, spark-gaps are currently being replaced by surge
arresters.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In these three systems, we can see a rise in potential of the exposed conductive parts of the
substation U1 such that:
Depending on the maximum current value Im , the values of Re must be limited so that U1
remains below the power frequency withstand voltage U tp of the substation equipment.
U1 ≤ U tp
Table 5-6 gives the maximum values of Re for different values of I m and U tp .
TN − b ; TT − b IT − c TN − b ; TT − b ; IT − c TN − b ; TT − b ; IT − c
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
V3
3
V2
2
V1
1
earth
VNeutral ZNeutral fault V1E V2E V3E
V2 V3
Neutral
V2E V3E
V1
V1E 0
V1 , V2 , V3 : phase-neutral voltages
V1E , V2 E , V3E : phase-earth voltages
Z Neutral : earthing impedance ( Z Neutral = ∞ for an unearthed neutral)
Note 1 : for an impedance earthed neutral, the value of Z Neutral is much greater than the value of the
transformer and cable impedances and the fault resistance, which is why VNeutral = − V1 .
Note 2 : in overhead public distribution networks, there are highly resistive faults (several kΩ), having a
value close to or higher than the earthing impedance. In this case, a highly resistive fault will
cause an overvoltage lower than 3 Vn .
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
4 a2 + 9
VN = V1
16
we then have V3 N = V3 − VN = a V1 − VN
− 15 + j 10 3
V3 N = V1
16
whence V3 N = 1.43 Vn
We can see that once the most sensitive single-phase loads have broken down, there are
successive breakdowns, following the development of the phenomenon which worsens the
unbalance ( Z 3 increases after the breakdowns and consequently V3 N increases); this is an
avalanche phenomenon.
This risk thus underlines that it is preferable to well balance the loads on the three phases.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n characteristics
- the steady-state voltage which is the permitted specified value of the power frequency rms
voltage that can be continuously applied between the terminals of the surge arrester
- the rated voltage which is the maximum power frequency rms voltage permitted between its
terminals for which the surge arrester is designed to operate correctly in the temporary
overvoltage conditions defined in the operating tests (a power frequency overvoltage of 10
seconds is applied to the surge arrester - see IEC 99-4)
- the protection level defined at random as being the residual voltage of the surge arrester
when it is subjected to a given current impulse (5,10 or 20 kA according to the class), with a
wave form of 8/20 µs
- steep front current impulse (1 µs), lightning impulse (8/20 µs), long duration impulse, and
switching impulse withstand
Table 5-4 gives an example of the characteristics of a phase-to-earth ZnO surge arrester for
a 20 kV public distribution network (with tripping on occurrence of the first fault).
Rated voltage 24 kV
Table 5-4: example of the characteristics of a ZnO surge arrester for a 20 kV network
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
n energizing a load
o inductive circuit
When a device closes, on an inductive circuit (no-load transformer, motor on starting), there is
a moment when the dielectric withstand between its contacts drops below the applied voltage.
This is accompanied by oscillations with stray capacitances which cause high frequency
currents to circulate in the circuit-breaker.
Depending on the speed of the device, prestrikes may or may not occur up to complete closing
of the poles.
Multiple prestrike is accompanied by successive overvoltages which decrease until the device
is completely closed.
When a capacitor bank is energized via a slow operating device, prestrike occurs between the
contacts close to the wave peak of 50 Hz.
A damped oscillation in the system in figure 5-31 then occurs at a frequency above
LC
50 Hz concentrated around the peak. In this case the maximum overvoltage is 2 V$n . It
corresponds to the maximum overvoltage admissible by the capacitors (see IEC 831-1 for LV
and 871-1 for MV or HV).
With a faster device, prestrike does not necessarily occur around the 50 Hz peak and
consequently the overvoltage is smaller.
When put out of service, the bank remains charged at a voltage going from 0 to the peak
voltage of the network.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The current is then interrupted as in the case in figure 5-25 except for the peak-to-peak
1
magnitude of the oscillations, due to the presence of energy stored in L L I a2 which is
2
1
added to that in the capacitance C p C p V$n2 .
2
If V$ is half the peak-to-peak maximum value of the oscillation at point C, we can write:
c max
1 1 1
C p V$c2max = C p V$n2 + L I a2
2 2 2
L 2
V$c max = V$n2 + I a in single-phase.
Cp
V$n : phase-neutral nominal voltage peak value
For a three-phase circuit V$n must be added in order to take into account the transient
operating conditions linked to the non-simultaneous interruption of the phases, whence:
L 2
V$c max = V$n + V$n2 + Ia
Cp
This phenomenon is notably problematic in the case of an arc furnace transformer power
supply.
Indeed, the transformer is generally connected not very far away from the busbar. Thus the
value of C p is very weak and therefore the value of V$c max high.
Schneider carried out an analysis for a single-phase arc furnace transformer where:
15000 V
Vn = ; L = 8.26 H ; C p = 14.75 nF ; Ia = 4.36 A
3
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
VA
VB
VC
Is
ID
IL
VD = VB − VC
t
t0 t1
t0 : separation of contacts
t1 : zero current
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
The exposed conductive part of load 2 is at the same potential as the remote earth.
The voltage of one healthy phase of this load in relation to the exposed conductive part is
therefore V2 − VNeutral or V3 − VNeutral :
Re V1 Re a Re
V2 − VNeutral = V2 − Re I f = V2 − = V2 − a V2 = V2 1 −
Re + RM Re + RM Re + RM
a Re
whence kM = 1 −
Re + RM
for RM = Re , k M = 1.32
The earth electrode resistance of a group of loads is in general higher than the substation
earth electrode resistance. The overvoltage coefficient will thus be lower than 1.32 on load 2.
The overvoltage factor is maximum in the TT earthing system for a load having an exposed
conductive part connected to the same earth electrode as the fault load, we thus have
kM = 3
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
Upstream of M , we have:
immediately downstream of M :
v 2 = Z 2 i2 (2)
at point M :
v2 = v1 + v1' = v1 − Z1 i1' = v1 − Z1 ( i2 − i1 )
whence Z2
v2 = × 2 v1
Z 2 + Z1
In particular:
- for a line short-circuited to earth, Z 2 = 0 ; we can deduce from this that v2 = 0 and v1' = − v1
- for a conductor without a change of impedance, Z 2 = Z1 ; we can deduce from this that
v2 = v1 and v1' = 0
- for an open line, Z 2 = ∞ ; we can deduce from this that v2 = 2 v1 and v1' = v1 .
To conclude, at the point of change of impedance, the maximum voltage value may reach
double the incident wave. This is the case of a line feeding a transformer as its impedance in
relation to the lightning wave is very high in relation to the characteristic impedance of the line.
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction , either partly of this document are not allowed without our written consent.
High resistance earthing with restrike in the Limiting resistor earthing with restrike in the
fault or circuit-breaker, case of industrial fault or circuit-breaker, case of public
networks for which IrN < 20 to 30 A distribution networks for which I rN is equal
(see Protection guide - § 10.1.1.). to several hundred to 1 000 A. The overvoltage
I rn rN
The overvoltage depends on the ratio depends on the ratio
IC Xd
transient voltage as transient voltage as
% of the nominal % of the nominal
single-phase voltage single-phase voltage
peak value peak value
%
%
250
healthy
460
phases
200
300
260 healthy 150 neutral
240 phases
200
100 fault
neutral phase
100 fault 50
phase
I rN rN
0.5 1 1.5 2 2.5 IC 3 4 5 6 8 10 20 30 50 70 90 X (1)
I rN = Vn / rN : current in the neutral resistor during rN : neutral point earthing resistance
the fault X(1) : network positive-sequence reactance
I C = 3 Cω Vn : vectorial sum of current in the phase-
earth capacitances
If I rN ≥ 2 I C , the overvoltage does not exceed 240 %
Reactance earthing, case of public distribution networks for which I XN is equal to 1 000 to
several thousand amps
Case without restrike in the circuit-breaker Case with restrike in the circuit-breaker
transient voltage as transient voltage as
% of the nominal % of the nominal
single-phase voltage single-phase voltage
peak value peak value
%
% 500
400 400
B
C
300 theoretical limits 300 theoretical limits
B
without without
damping A damping
200 A 200
C
N
100 N 100
XN XN
0 2 4 6 8 10 12 14 16 X (1) 0 2 4 6 8 10 12 14 16 X (1)
X(1) : network positive-sequence reactance B, C : healthy phases
X N : neutral point earthing reactance N : voltage at reactance terminals
A : earth fault phase
Figure 5-34: transient overvoltages depending on the type of neutral earthing
during a phase-earth fault
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.
In most networks, generators are sufficiently far away to take the approximation Z(1) = Z( 2 ) ; we
thus have:
k = 1+
(
a Z(1) − Z( 0) )
2 Z(1) + Z(0 ) + 3 R f
Nomographs can be used to determine factor k for a zero fault resistance ( R f = 0 ) in relation
R(0) X(0 )
to the ratios and for R(1) = 0 and R(1) = 0.5 X(1) (see fig. 5.3. et 5.4.).
X(1) X(1)
where:
When the fault resistance is not zero, we can see in the formula expressing k that the
overvoltage is weaker. The calculation of the overvoltage with a zero fault resistance thus
provides an excess value.
If we again use the diagram in figure 5-2, we can determine these impedances for a practical
case:
by taking:
ZT = RT + j XT
positive - sequence impedances
ZC = RC + j XC
Z( 0 )T = RT + j X( 0 )T
zero - sequence impedances
Z( 0 )C = RC + j X( 0 )C
Publication, traduction et reproduction totales ou partielles de ce document sont rigoureusement interdites sauf autorisation écrite de nos services.
The publication, translation and reproduction, either wholly or partly, of this document are not allowed without our written consent.