Distillation Column Chemical Engineering Design For A HPPO Process Plant
Distillation Column Chemical Engineering Design For A HPPO Process Plant
1
Contents
Acknowledgements................................................................................................................ 2
Executive Summary:............................................................................................................... 5
1. Design Project Introduction:............................................................................................. 6
1.1 Gantt Chart:.................................................................................................................. 6
2. Chemical Engineering Design:......................................................................................... 7
Updated Mass Balances:..................................................................................................... 7
Updated Energy Balances:.................................................................................................. 8
Operating Pressure:............................................................................................................. 8
Operating Temperatures:..................................................................................................... 9
FUG Method to obtain Number of Theoretical Stages, N:..................................................10
Volatility Calculations:....................................................................................................... 10
Fenske Equation, Nmin:....................................................................................................... 10
Underwood Equations, and Rmin:........................................................................................ 11
Theoretical Number of Stages, N Calculations:.................................................................12
Gilliland Correlation for Number of Stages, N:................................................................12
Molkanov Equation for Number of Theoretical Stages, N:..............................................12
Feed Location using Kirkbride’s Equation:.........................................................................13
Packing Selection:............................................................................................................. 13
Column Diameter Design, DC:............................................................................................ 15
Maximum Vapour Velocity, VW*:......................................................................................... 15
Column Pressure Drop, ΔP:................................................................................................ 16
Internals Design and Column Height, ZC:...........................................................................18
Feed Distributor Design:.................................................................................................... 18
Other internals:................................................................................................................. 19
Total Column Height, ZT:.................................................................................................... 19
3. Mechanical Design:........................................................................................................ 20
Maximum Operation Conditions:....................................................................................... 20
Material Selection.............................................................................................................. 20
Vessel Thickness Calculations........................................................................................... 20
Domed End Head Thickness:............................................................................................. 21
Vessel Dead weight Calculations:...................................................................................... 21
Vessel Stresses.................................................................................................................. 22
Bending Stress.................................................................................................................. 23
Resultant Longitudinal Stress, σz:...................................................................................... 23
Evaluation of Principal Stresses............................................................................................ 24
Additional Unit Design.......................................................................................................... 27
Condenser Thermal Design............................................................................................... 27
2
Condenser Flowrates & Duty.......................................................................................... 27
Shell- side Design.............................................................................................................. 31
Tube Side Pressure Drop.................................................................................................... 32
Reboiler Design................................................................................................................. 33
Reboiler Duty..................................................................................................................... 34
Heat Transfer Area and Number of Tubes..........................................................................34
Control & Instrumentation.................................................................................................... 36
3
Executive Summary:
This report provides an overview of the design methodology of a packed distillation column, T-102, and
its corresponding units relative to the Hydrogen Peroxide- Propylene Oxide (HPPO) process in Ras
Laffan, Qatar. The column operates at 3 bar absolute and serves as a preliminary separation unit from
the mixed bottoms of F-101 and T-101, propylene flash separation unit and first distillation column,
respectively. The distillate serves as S-101 feed, further propylene oxide (PO) separation, and the
bottoms as T-104 feed, methanol recycle. The key components of separation desired are PO in the
distillate and methanol in the bottoms. Preliminary condenser and reboiler design are discussed but are
not optimised because of time constraints.
Unit operating conditions, mass and energy balances were optimised based on the front-end engineering
Design for the plant conducted in Teaching Period 1 ensured the product specification was met for the
Ras Laffan plan. Industry recognised methods for column design and pressure drop, such as the
Fenske-Underwood and Gilliland method, were used and calculated 15 column stages, and Ergun’s
equation for a 0.023 bar pressure drop, are employed for accurate design.
Packed columns were preferred over tray columns for low liquid holdup applications, preventing
propylene oxide (PO) hotspots and consequent product polymerisation. Further advantages included
improved economics regarding replacements, especially considering the risks hydrogen peroxide can
arise during operation.
Structured packing Mellapak 250Y is selected for its versatility in industry-wide applications, in addition
to its excellent packing efficiency, requiring a smaller packing height of 7.5m. The column diameter was
designed to account for a 69% flooding factor, ensuring operation alongside standard sizing. A gravity-
fed distributor requiring 106 distributors per metre square allowed for optimal distribution, each hold
being 7mm wide and 15cm spacing between them. Column dimensions for inner diameter and height are
2.7 m and 9.95 m, which accounts for packing height, distributor spacing and a vapour- liquid
disengagement zone.
Stainless steel 316 was the selected material for a 10mm thick column, as the alloy is fairly corrosion
resistant’ to hydrogen peroxide whilst considering the material’s economic implications. Safety factors
and worst- case scenario stresses were considered for conservative design. Maximum stress incurred to
the vessel, 47.11 N mm-2, is less than the material maximum allowable stress, 116.257 N mm -2, so is
acceptable to use. An 8mm thick skirt is designed so the vessel remains upright when faced against
worst- case natural disasters Qatar can encounter.
Design could be improved by calculating packing effective areas specific to the column and comparing
them between several types of packing to identify the best packing for separation. Cost of implementing
different reflux ratios against operation for an economical application to the optimum reflux ratios would
be conducted if more time were granted.
4
1. Design Project Introduction:
This project requires the design & optimisation of a unit operation part of the (HPPO) process, with a
packed distillation column chosen. The primary objective is to separate PO from the methanol
downstream, sent from the combined F-101 & T-101 bottoms. The design of the unit will consider
the climate and availability of materials in Qatar.
The chemical engineering design will focus on improving the mass & energy balances from TP1,
followed by design of a cylindrical packed column under process operation; steady-state conditions are
assumed, alongside further considerations of packed column internals. Additional thermal design of a
condenser & preliminary reboiler are considered, with corresponding calculations found in
‘220178574_Final_Design_Project_Spreadsheet’.
The mechanical design considers worst-case scenario to ensure the column can withstand the rigours of
operations regarding Qatar’s harsh climate.
AutoCAD was used to produce the unit P&ID, developed with control loops to ensure safe operation.
Reputable sources like Aspen Plus, Perry’s Chemical Engineering Handbook, and NIST have been used
to obtain stream thermodynamic & transport properties. All values used in this report are rounded to
three decimal places, unless shown in standard form. Percentages are to two decimal places, except
adjusted flood factor for accuracy. For detailed calculations and accurate values, refer to the
spreadsheet mentioned previously.
1.1 Gantt Chart:
A Gantt Chart, Appendix 1, was curated in the first week to monitor progress, allowing the project to be
broken into manageable parts, ensuring an efficient approach to the project. Key parts of the report are
outlined with reasonable deadlines set to avoid burn out. A non-negotiable internal deadline one day
before submission, 24th March, was set to avoid late submission. Chemical Engineering Design took
longer than expected. Mechanical Design was started earlier to mitigate project bottlenecks.
5
2. Chemical Engineering Design:
A design of a counter- current packed distillation column, ensuring realistic PO- methanol separation,
maintaining a low pressure drop. Structured packing is used to offer efficient separation while
maintaining a reasonable height for the size of the column. Equation notations can be found in the
nomenclature list. All conversions are present in Appendix _. Figure 1 shows the method for initial
column design:
Value Units
Specification Requirement 80,000 T Year-1
80,000,000 kg Year-1
Days of Operation 330 Days Year-1
24 Hours Day-1
PO Specification in Distillate 10101.010 kg h-1
LK and HK Fractional Recovery in Distillate, FRD 0.89 0.01
LK and HK Fractional Recovery in Bottoms, FRB 0.11 0.99
PO and methanol are selected as LK and HK respectively, to purify the desired product and for solvent
recycle and separation. 89% PO recovery in the distillate is assumed to ensure significant presence in
the bottoms. 99% methanol recovery in the bottoms is assumed to maximise solvent recovery.
Mass balances for the key components are the product of the feed flowrate and the fractional recovery in
distillate and bottoms, an example with PO is shown in Equations 2 and 3:
6
0.89 ∙ x f ∙ F=x d ∙ D , ( Eq 2 ) 0.11∙ x f ∙ F=x b ∙ B ,(Eq 3)
Non- key component final location at the outlets is assumed 100% regarding average relative volatilities
in Table 3. Components with volatilities lower than the HK are assumed to fully leave through the
bottoms. Components more volatile than the LK are assumed entirely in the distillate. Although trace
amounts of these components are found in opposing streams, these are neglected for simpler design.
Mass balances from TP1 with fractional recovery alterations are in Appendix 1.
Enhancing fractional recovery improves unit operation efficiency, however the specification is not met.
The Appendix 1 PO distillate is compared to the specification PO in Table 1; thus, a scale factor is
obtained, 10101.010 kg h-1 / 9218.169 kg h-1 = 1.096.
Initial feed flowrates from TP1 for each component are multiplied by the scale factor ensuring PO
distillate flowrate meets the specified amount, 1.096 * x kg h -1 = 1.096x kg h-1. This should be done in
reverse order from T-104 to F-101 for the process to meet the 80,000 Tonnes of PO per Annum.
Appendices 2-5 shows updated mass balances, applying the scale factor and new fractional recoveries.
Updated Energy Balances:
In TP1, it was assumed that F-101 bottoms temperature would dominate when mixed with T-101 bottoms
because of a substantially larger flowrate, assuming a feed temperature of 313K. However, the feed
quality, q, is a saturated liquid, 1. Table 2 shows the feed saturation temperature is 354.45K. The top and
bottom of the column were recalculated and temperatures of 337.15K and 379.55K were obtained. Both
streams will be heated before mixing so heat exchanger is considered as T-101 design. Specific heat
capacity, Cp are derived at the new temperatures from Aspen Plus.
In Appendices _-_, this invalid assumption is corrected, showing a 2972.327 kJ s -1 column energy
requirement for continuous operation at 3 bar. The column is an energy sink and is insulated to minimise
energy losses.
Operating Pressure:
Operating pressure and volatility are the main driving forces in separation, dictating the vapour- liquid
equilibria between components. At higher pressures, components become less volatile, making it harder
to separate. The T-xy diagrams in Appendices _-_ demonstrate a smaller area of separation between the
key components as pressure increases, resulting in higher pressure operation undesirable.
Appendix _ is at vacuum pressure, where separation is the greatest, however the dew point falls below
the lowest temperature on the graph, 17°C. Qatar’s average temperature is 29.4°C, so using cooling
water as a utility fluid would heat the distillate, requiring refrigerants for condenser operation. This
combined with the expensive operating cost of vacuum distillation makes this uneconomical. If the plant
was in a cooler climate such as Germany, cooling water usage would make vacuum distillation feasible.
At moderate pressures, Appendix _ shows an increased operating temperature range, with a 49.141°C
midpoint temperature increase, compared to vacuum operation. At higher temperatures, hydrogen
peroxide decomposes at faster rates. Despite being feedstock, hydrogen peroxide is considered as
wastewater and is not of major importance in terms of process efficiency. Although it’s insignificant
presence, 255.799 kg h-1 is still processed and its decomposition to pure oxygen and water can increase
column pressure. Although hydrogen peroxide is in trace quantities relative to the other components, it’s
decomposition must not be overlooked. Good liquid distribution and temperature control reduces this
risk.
PO polymerisation can occur ‘as low as room temperature’. Even at vacuum pressures, separation
occurs within room temperature. This issue cannot be resolved at very low pressures. Although
polymerisation occurs after prolonged periods of time, ‘15% after 35 hours’, fractional recovery of PO in
distillate is lower relative to methanol’s recovery in the bottoms to account for potential losses and
reboiler fouling caused by polymer formation. (Pierre and Price, 1956)
However, the temperature range allows for cooling water and high-pressure steam to be used as
condenser and reboiler utilities therefore 3 bar will be used as a compromise pressure. 3 bar
7
temperatures are significantly higher than vacuum and is still below extreme conditions which could put
human life in danger.
Ras Laffan is a coastal area, so ocean water will be used as the source of utilities because of Qatar’s
high clean water scarcity. Seawater will be processed to clean requirements in situ.
Operating Temperatures:
Feed enters as a saturated liquid, requiring it to be at the bubble point. The distillate leaves at the dew
point, where the first drop of liquid forms, ensuring the LK leaves as a saturated vapour. Bottoms leave
the column at bubble point, where the first bubble forms, so the HK leaves as a saturated liquid.
Temperature is iterated using Raoult- Dalton’s Law at saturated vapour pressure. Vapour pressures were
derived using Design Institute for Physical Properties and Antoine’s equation are shown below: (Perry,
Green and Maloney (1997, p.Table 2-8)), (NIST, 2018)
C2 C B
ln P sat =C1 + +C3 ln T + C 4 T , P sat =Pa ( Eq 4 ) log 10 P sat = A−
5
(Eq 5)
T T +C
Saturated vapour pressures of propylene and PO are calculated using equations 4 and 5 for the feed at
354.45K:
¿¿
Psat , C =e
3 H6
802.487
3.55046−
Psat C 3 H 6O =10 354.45 K +(−81.348)
=4.093 ¯¿
Constants are acceptable for the temperature ranges shown in (‘3.5. Saturated Vapour Pressure’, Sheet
‘3. Properties & Assumptions’, ‘220178574_ Final_Design_Project_Spreadsheet’). Hydrogen peroxide
and nitrogen constants were difficult to find, so were estimated on Aspen Plus using the PENG- ROB
property method. PG constants were found and gave unreliable values approximately 20% differences
from Aspen, so were estimated using simulation software. All estimated components were insignificant
regarding mole fractions, having negligible effects on saturation temperatures.
Temperatures were often outside the accepted temperature range, so were extrapolated and compared
to Aspen estimates. The least accurate extrapolation was 8% lower than what Aspen reported, deeming
reasonable extrapolations.
Vapour and liquid mole fractions must equal 1 to satisfy vapour- liquid equilibrium. Due to phase, feed
and bottoms follow equation 6 and the distillate applies to equation 7.
Mole fractions in Appendix 6 are used. Pressure is 3 bar. For bottoms, the sum of the column pressure
drops and operating pressure, 3.023 bar, is used.
yi Psat
y i=K i ∙ x i ( Eq 6 ) x i= (Eq 7) K i= (Eq 8)
Ki PT
TP1 temperatures were used as the first feed trial. The selected temperature was too low, indicated by
the 0.39 liquid mole fraction (‘Feed Saturation Temperature- 1 st Attempt’, Sheet ‘6. Operating
Temperatures, ‘220178574_ Final_Design_Project_Spreadsheet’). 360K was used for the 2nd Attempt,
resulting in a mole fraction 15% of 1. Goal seek was employed to calculate a temperature which
allows for the sum of gas mole fractions to equal 1, 354.45K.
This process is repeated for the distillate and bottoms. For an accurate and detailed breakdown of each
iteration, consult ‘Sheet ‘6. Operating Temperatures’, ‘220178574_ Final_Design_Project_Spreadsheet’.
Rounding errors led to less accurate values. Feed temperature is shown below. Distillate and bottoms
are calculated using the same principle as the feed and is found in Appendices _-_.
Table 3 shows volatilities of the distillate, bottoms and average relative volatilities.
Table 3: Average Volatility calculation.
Component αd αb α i ,avg
C3H6 27.677 13.557 19.371
H2O2 0.024 0.044 0.032
H2O 0.245 0.288 0.266
CH3OH 1.000 1.000 1.000
C3H6O 2.607 1.679 2.092
C3H6O2 4.50E-03 0.012 7.35E-03
N2 1307.230 389.382 713.451
8.047 stages obtained from equation 12 assumes infinite reflux which is not realistic. The Underwood
equations are used to calculate a minimum reflux ratio to calculate number of theoretical stages.
Underwood Equations, and Rmin:
Underwood equations are deployed to calculate the smallest reflux, at the cost of infinite stages.
Equations 13 and 14 form the basis of calculating R min. Quality of feed is associated with feed mole
fractions in the first equation. Reflux is associated with the quantity of distillate returning to the column
therefore distillate mole fractions are used in the second equation below.
α i ,avg ∙ x i , f α i ,avg ∙ x i , d
∑ α i ,avg −θ
=1−q ( Eq 13 ) , ∑
α i , avg−θ
=1+ Rmin ( Eq 14 )
i i
where HK <θ< LK
i,avg from Table 3, and mole fractions from Appendix 6 are used. The liquid feed is saturated, q=1,
therefore the left-hand side is equivalent to 0. The parameter is assumed to be in between PO and
methanol’s relative volatilities, initially assumed 1.5. Goal seek function was deployed to iterate to
1.833 to satisfy the constraint to three decimal places. The result is shown in Table 5.
Table 5: Underwood Equation, Final Iteration for .
is within the 1 - 2.092 range, so is deemed acceptable. Theta is substituted into equation 14 to obtain
the minimum reflux ratio shown in Table 6.
Table 6: Underwood Equation to determine minimum reflux ratio.
The minimum reflux required for separation is 4.944. This is large to ensure high HK fractional recovery.
This value decreases if fractional recovery of HK in bottoms was assumed lower. A reflux ratio is
10
established to estimate a realistic N. Optimal economic reflux ratios are typically ‘1.2-1.5 times the
minimum reflux.’ (Chen and Lin, 2001). Figure 2 compares the economic reflux ratio range and N using
the Molkanov equation, 1.3 was selected as the best value, resulting in a 6.415 reflux.
Theoretical Number of Stages, N Calculations:
As reflux ratio increases, energy demand supplied to process more intensive flowrates, requiring a lower
N. More liquid in the column leads to higher pressure drops, so a trade-off between N and energy
consumption is considered. Increasing the reflux ratio from 1.2 to 1.3 warrants an 11.11% N reduction. A
21.69% A further reduction is achieved by increasing the reflux ratio to 1.5, both ensure reasonable
separation design.
.
11
Higher reflux ratios reduce column capital costs. On the contrary, excessive energy costs lead to higher
total costs, which is not process efficient. Figure 2 shows R at each reflux ratio against N. The sharpest
gradient falls in the 1.2-1.3 Rmin range, so the greatest value is taken.1.3 R min is considered as the
optimised reflux ratio as it compromises the best energy consumption with number of stages.
Calculated Molkanov equation using the optimised reflux ratio is shown below:
( ) [( ) ( ) ( ) ]
2
N B x x
log E =0.206 log ∙ f , HK ∙ b , LK (Eq 16)
NS D x f , LK x d , HK
Criteria Value
NE 12.859 stages
NS 2.141 stages
Values are not rounded to whole numbers at this point as HETP has not been considered. Table 7 values
are reasonable as the feed is methanol rich, so more stages in the rectifying section are expected to
increase the purity of PO in the distillate.
Packing Selection:
Packing is used to offer a large surface area for vapour- liquid contact to occur, enhancing mass transfer,
resulting in high quality separation. Packing choice plays a pivotal role in column performance, directly
influencing column capacity (diameter), pressure drop, packing factor and column height. Selected
packing must be able to withstand corrosion of column components. Packing material must be
considered alongside. Three packing materials are considered: ceramic, metal and plastic.
Ceramic packings offer the best wettability, using its surface area effectively. This would lower the
chances of channelling in the column, leading to effective mass transfer and reducing liquid
maldistribution. Ceramic is also corrosion resistant, important for processing hydrogen peroxide.
However, ceramic is brittle and breaks easily on impact, which is not ideal for tall columns unless
installed layer by layer. To ensure packings do not break from potential column stresses, regular checks
would be required. If installation is conducted without caution, the possible costs saved by increased unit
efficiency may be outweighed by the cost of packing checks and replacement if excessive stress
constantly acts on the column.
Plastic packings are light in weight, providing easy transport and handling in bulk. Plastic is one of the
largest mass-produced materials worldwide making it easier to find manufacturers, so is the least
12
expensive of the three. However, production of plastic is environmentally polluting as it is heavily reliant
on non-renewable sources such as oil. A mitigation is using biodegradable or recyclable plastic packings
to prolong the packing lifetime. Plastic also lacks the ability to wet, making it a poor choice for a high
degree of separation, a fundamental requirement and often non- compatible with hydrogen peroxide.
Metal packings are the strongest out of the three, offering elevated temperature resistance. Metal
wettability offers better wettability than plastic and worse than ceramic. Hydrogen peroxide has a
tendency of corroding metals as well as reacting with many, limiting metal packing usage. However,
hydrogen peroxide is in trace quantities, making some metals more compatible with others, typically
alloys.
A price compromise metal that is compatible with hydrogen peroxide is SS304 at quantities the column
will encounter. The decision matrix below determines metal to be the selected material for this
application. This is subjective based on the information above.
Table 8: Material Selection Decision Matrix, where 5 is the Best, 1 is the Worst.
Two types of packing are considered in columns: random and structured. Random packings are
irregularly shaped pieces of plastic, metal or ceramic which are cost- effective to manufacture. These are
normally dumped into the column and tend to have higher surface areas than structured packing.
Increasing packing size reduces its effective surface area. Figure 3 shows a general guide for the size of
packing compared to the column diameter.
Although offering a higher surface area, random packings are prone to uneven liquid distribution
because liquid films around each packing will be different. Liquid maldistribution leads to a higher
pressure drop, ‘0.08-0.65 kPa/ m packing’, increasing column energy consumption. (Woods, 2007)
Structured packings are geometrically intricate, requiring higher manufacturing costs, and are placed in
the column in an arranged formation to ensure maximum vapour- liquid contact is taken advantage of.
Although more expensive, structured packing allows a lower pressure drop, ‘0.02-0.5 kPa/ m packing.’
and a lower HETP, reducing the capital costs of the column. (Woods, 2007) Random packings are
optimised for packed columns with diameters less than 1m.
Figure 3 recommends 50mm packings for the diameter obtained in section 2.4 of the report. If random
packing were used, packing height would fall in the range of 11.25 - 15m. Equation 17 shows a rule of
thumb for HETP that Kister developed for structured packing. Using Table 9 data, HETP equals 0.5,
resulting in a 7.5m packing height, reducing height by a third considering 11.25m. For this reason,
structured packing is preferred. (Kister, 1992)
Table 9: Mellapak 250Y Packing Specification Data.
100 100
HETP= +0.1 ( Eq 17 ) , HETP= +0.1=0.5 m
a 2 −3
250 m m
F=u s ∙ √ ρV ( Eq 18 ) , F=1.202 m s−1 ∙ √ 3.908 kg m−3=2.38 Pa0.5
Superficial gas velocity, uS, is obtained equation Table 15, equation 28. F- factor sits within the range, so
is reasonable to use. from Y- type corrugated, 45°, structured packing is selected over X-type
corrugated, 60°. High fractional recovery of methanol in the bottoms puts a greater importance on mass
transfer performance than pressure drop. (Colintery.com, 2023)
Mellapak 250Y is selected as it was one of the first Y- type structured packing developed, so vendors
have optimised geometry, voids and overall mass transfer performance. Hydrogen peroxide- metal
compatibility must be considered when selecting packing material. This has been determined in section
3.2 of the report.
If more time were granted, effective area calculations of types of random and structured packing using
gas and liquid mass transfer coefficients would be conducted to enhance design. Reliable methods such
as Onda’s method for random packing and Billet & Schultes model for structured packing would be
calculated, further refining packing selection for metal and ceramic packings. Structured packing
methods require rigorous simulations and analysis.
Column Diameter Design, DC:
Internal traffic and stream properties are used to design an appropriate column diameter which avoids
flooding, the point where the column is unable to operate counter- currently. To avoid excessive
resistances against gas flow, reducing its ability to move upward, column vapour mass velocity at
flooding is calculated to ensure the column area does not flood. Column operation is 60-80% flooding is
commonplace in industry, so 70% flooding was assumed initially.
Design assumes steady- state operation, so internal traffic calculations are assumed constant flowrates.
Table 10 shows internal traffic calculations. Equations 19 and 20 apply to the rectifying section, and
equations 21 and 22 apply to the stripping section. ‘q’ equals1, so V = V’. F, D and B are total flowrates
of the corresponding letters in kg s-1 and kmol s-1, tabled values are divided by 3600. Mixture stream
properties were estimated using Aspen Plus. It was advised to find properties at feed, distillate and
bottoms at the temperatures calculated earlier and then average. Table 11 shows the stream properties
used in the report.
Table 10: Internal Traffic calculations.
−3 −3 −2 −2
ρ L , kg m ρV , kg m μL , N s m μG , N s m
Feed 757.972 3.095 2.867E-04 1.20E-05
Distillate 685.067 6.007 1.394E-04 1.04E-05
Bottoms 740.898 2.623 2.491E-04 1.30E-05
Average 727.979 3.908 2.251E-04 1.18E-05
14
Maximum Vapour Velocity, VW*:
Flow factor, FLV, is a parameter that assesses column performance in the rectifying and stripping section
of the column to obtain K4 at flooding. The larger value is selected to avoid flooding. The stripping section
should have a larger value as it has a larger liquid flowrate.
Table 12: FLV calculations
( LV ,,VL'' )∙( ρρ )
23 O V
0.5 0.063 0.117
F LV =
L
As mentioned previously, FLV, Stripping is larger and is applied to the graph in Appendix _ and the red line is
used to obtain K4 at flooding, 3.1. K4, properties from Table 12 and the packing factor are used to derive
equation 24, the maximum vapour velocity, accounting for densities instead of volume occupied.
( ) ( )
0.5
¿
K 4 ∙ ρV ∙ ( ρ L− ρV ) −3
3.1 ∙ 3.908 kg m ∙ ( 727.979−3.908 ) kg m
−3 0.5
VW = ( Eq 24 ) , V W ¿ =
( ) ( )
0.1 −2 0.1
μ −1 2.251E-04 N s m
13.1∙ F P ∙ L 13.1∙ 66 m ∙ −3
ρL 727.979 kg m
VW* equals 6.740 kg m-2 s-1. The greatest vapour flowrate in Table 10 is divided by the maximum vapour
velocity to calculate the largest minimum area to avoid flooding. The assumed flooding factor, initially
70% was selected. Goal seek was used to adjust the flooding factor to 69.993% ensure standard
diameter usage.
Table 13: Column Areas & Diameter.
( )
27 0.5 2.716 m
4 ∙ Af
DC=
π
Designed DC is inaccurate because of rounding errors. 2.701 m and 5.733 m2 will be used. (‘8.7- Column
Diameter, DC’, Sheet ‘8. Column Diameter’, ‘220178574_Final_Design_Project_Spreadsheet’) Packing
changes will alter FP, diameter is altered as a result.
Column Pressure Drop, ΔP:
Low pressure drops are vital for effective packed column operation. Heuristic states an acceptable
pressure drop of ‘0.02-0.5 kPa/ m packing’. (Woods, 2007) Two methods are conducted and compared
for accurate pressure drop design. The first method is applicable to both structured and random packing,
highlighting possible inaccuracies, nonetheless is still used in industry.
Equation 25 is rearranged, and maximum vapour velocity is recalculated with the optimised column area.
Equation 24 is rearranged for K4 at 68.993% flooding. Intersection of the orange and F LV lines in
Appendix _ is interpolated for the column pressure drop. Table 14 outlines the derivation of the graphical
method pressure drop.
Table 14: Graphical Pressure Drop
15
25 (Rearr) ¿ V' 4.698 kg m-2 s-1
VW =
Af
( )
24 (Rearr) ¿ 2 μ
0.1 1.506 Unitless
13.1 ∙ ( V W ) ∙ L
ρL
K4=
ρV ( ρL −ρV )
26 Z P=HETP ∙ N 7.5 m
Appendix _ estimates a pressure drop of 50mm H2O/m packing. Interpolation errors arise, so was
reviewed by someone else. 1mm H2O is equivalent to 9.8E-03 kPa, converting to 0.49 kPa/m packing.
This is deemed acceptable by heuristic above. With a 3675 Pa, 0.037 bar column pressure drop.
A second pressure drop method involving an adjusted Ergun’s equation for Mellapak 250Y is deployed to
validate the previous pressure drop. Stichlmair’s model is the simplest, proving ‘most effective in a study
between air and water’. Rocha Bravo & Fair and Billet & Schultes model are ‘more complex’ and pose
‘more robust for a multicomponent systems’, however, ‘intense simulation efforts’ with specialist software
are required. Given the time restraints, Stichlmair’s method was selected. (Madsen et al., 2023)
Stichlmair’s correlation requires the system to be below loading point. It is assumed that the column
operates under the appropriate conditions as operation is below flooding. Unlike the graphical method,
Stichlmair’s method accounts for non-wetted and irrigated pressure drops.
Non- wetted pressure drop is calculated in Table 15, which considers gas Reynold’s number and friction
factor per particle, 0. These are ‘dependent on C1, C2 and C3, constants specific to Mellapak 250Y’
where ‘C1 = 5, C2 = 3 and C3=0.45.’ (Madsen et al., 2023) V’ from Table 10 is volumetric flowrate, so is
divided by average gas density. Non- wetted pressure drop is expected to be lower compared to wetted
because gas flow faces no liquid resistance, only by packing in the column.
Table 15: Non- wetted Pressure Drop.
Irrigated pressure drop incorporates Froude’s number to assess column liquid holdup ‘accounting for the
same gas flow as non- wetted pressure drop’. (Madsen et al., 2023) ‘Froude’s number indicates the
influence of gravity on fluid motion’. (Editors of Encyclopaedia Britannica, 2023) ‘c’ is a constant for
structured packings, c = -0.38. Table 16 shows the pressure drop over an irrigated column, considering
the non- wetted column.
Table 16: Irrigated & Total Pressure Drop/m packing.
[ ]
35 2+c 3.165
(
1−ε 1−
hL
) 3
( )
− 4.65
∆P ε hL
= ∙ 1−
∆ Pd 1−ε ε
Low Froude’s number and turbulent Reynold’s number suggests a good degree of mixing, allowing
sufficient vapour- liquid contact. Contribution of irrigated column pressure drop is 3.165 times greater
than non-wetted, which agrees with the previous statement. The ratio and non- wetted column pressure
drop are multiplied to obtain total pressure drop per metre packing.
Pa Pa
3.165 ∙ 95.474 =302.175 , 0.302 kPa /m packing. This value also satisfies the
m packing m packing
heuristic previously stated.
Both methods give acceptable pressure drops, even though the graphical method is 38.37% greater than
Stichlmair’s method. The latter is selected for final pressure drop as constants were optimised for
Mellapak 250Y.
Internals Design and Column Height, ZC:
Column internals are just as important as column design. If designed poorly, then maldistribution will
arise. Column internals must be spaced appropriately from packing to avoid distribution hotspots. If the
distance is large, feed will be distributed at higher velocities. Typical ‘trouble- free range from 120-
160mm’. (Mach Engineering, 2024). 150mm is selected to minimise liquid holdup.
Feed Distributor Design:
Feed distributors main design intent is to ‘maximise liquid interface surface area’. (Mach Engineering,
2024) Strigle recommends ‘60-100 distribution points per square metre’. However, ‘a larger distributor
number helps to improve packing efficiency in structured packings.’ ‘More than 120, and 160 distributors
are recommended for 350, and 500 m2 m-3 packing areas.’ Minimum number of distributors for 250 m2 m-3
were ‘extrapolated’, requiring at least 93 distributors. Liquid load calculations are shown below. (Green
and Southard (2019, pp.14–71), (Cook, n.d.) Figure 4 comfortably indicates distributor design is not
limited by liquid loads.
Ḟ Q
Qfeed = ( Eq 36 ) , u L= Feed ( Eq 37 )
ρL Af
−1 3 −1
70489.875 kg h 3 −1 92.998 m h −1
Q̇ Feed = −3
=92.998 m h ,u L = 2
=16.222 mh
757.972 kg m 5.733 m
Figure 4: Liquid load capacities that specific distributors allow. (Mach Engineering, 2024)
A factor of 20% is applied to the minimum distributor number per square metre to increase packing
efficiency, providing a requirement of at least 106 redistributors per square metre for a feed distributor.
This is more than the 93 extrapolated from earlier.
Other internals:
‘Redistributors are required every 5-10 m to avoid maldistribution.’ Based on packing height in equation
26, a redistributor is required. When considering redistributors, the reflux flowrate must be considered
due to the high quantity reintroduced to the column. The redistributor will sit under the feed distributor at
6.705m, to ensure uniform feed distribution. A seventh of the stages sit below the feed, requiring even
liquid distribution entering the stripping section for efficient HK bottoms fractional recovery.
Packing must be held in place by supports to ‘restrict packed bed movement’ under operation. (Jaya and
Kolmetz, 2020). This helps to improve column mechanical integrity as stresses acting on the vessel are
less likely to affect packing efficiency.
Internals considered in this section must be determined via rigorous testing and simulation design
considerations have not been made.
Total Column Height, ZT:
Total cylindrical height considers appropriate spacing between internals and accounts for a vapour- liquid
disengagement zone, which has been advised as an additional 1 m at the column ends. This zone is
considered to ‘reduce chances of liquid entrainment in distillate’, improving separation efficiency. There
are three distances between distributors and packing in the column, demonstrated in Figure 5, so the
0.15m spacing is considered three times. Total cylindrical height is calculated below using equation 41.
ZC =Z P +Z L + Z G + ( Z Distributor ∙ N Z Distributor
) ( Eq 41 ) , Z C=7.5 m+1 m+1 m+ ( 3 ∙0.15 m )=9.95 m
This height is tall enough to ensure sufficient separation, while maintaining reasonable distribution with
respect to liquid and vapour flowrates.
18
3. Mechanical Design:
In this section, design operating conditions are developed from section 3, serving as the basis for
refining ‘internal pressure vessel’ dimensions based on stresses incurred, whilst accounting for
geographical challenges, such as windspeed and heat as the column is located outside. This was
decided as column height makes it difficult to fit inside.
Packing with lower HETP would allow for column construction within the plant building. Skirt support for
the vertical vessel at full loading is designed to ensure the vessel remains upright in the event of future
extreme conditions that Qatar may be exposed to. For relevant conversions, refer to Appendix _
Maximum Operation Conditions:
Worst-case operation must be considered when designing a column’s mechanical integrity, so a 10%
safety factor is applied to the highest operating conditions. These are assumed to be the bottoms bubble
point temperature and the liquid disengagement zone pressure. The disengagement zone density is the
bottoms liquid density in Table 11 is assumed full and is calculated below using equations 42 and 43.
Ptotal=P operating + Phydrostatic ( Eq 42 ) , P hydrostatic=ρgh( Eq 43)
−3 −1
¯ ¯¿ 3.073 .̄
Phydrostatic =740.898 kg m ∙9.81 m s ∙ 1 m=7268.209 Pa , 0.073 ,̄ P total=3 +0.073
Applying the safety factor, design temperature, T i, and pressure, Pi, are 3.38 bar, 0.350 N mm-2 and
117.04°C/242.672°F, respectively.
Material Selection
The selected vessel construction material must be inert eliminating further reactions. The main factors
for the chosen material is the hydrogen-peroxide compatibility and corrosion resistance. Economics is
considered, even though these materials are typically expensive. ‘10% hydrogen peroxide compatibility’
is considered. (Industrial Specialties Mfg. and IS MED Specialties, 2019)
Carbon steel is cost-effective, so was considered despite corroding easily. Higher corrosion allowance is
a consideration, leading to lower stress effects. However, would lead to higher capital costs, requiring
expensive joins, rendering it as uneconomical. Appendix _ specifies ‘severe effect’, so was disregarded.
Stainless steel vessels are commonplace in industry, suggesting multiple available standard sizes. It is
‘easy to shape and thin sheets can be used’ making vessel construction viable. (Makkus et al., 2000)
Figure 5 shows that stainless steels 304, 316 and 416 ‘face slights effects to corrosion.’ However, SS304
is rated ‘B’ until 48°C, so is inappropriate for use. SS316 outperforms SS416 and has more readily
available data, so SS316 is selected for design ease.
Although SS316 is expensive compared to other steels, the higher capital cost will save money on
replacements when considering plant lifetime. Qatar is a rich country, so even more corrosion resistant
materials such as Hastelloy could be considered but would require a cost-benefit analysis .
A 2mm corrosion allowance will be implemented across all thickness calculations to account for ‘slight
corrosion’ . (Industrial Specialties Mfg. and IS MED Specialties, 2019) Selected material properties are
found in Appendix _.
Vessel Thickness Calculations
Vessel thicknesses are determined to accommodate for stresses by extreme pressures the vessel will
face under operation, accounting for SS316 MAST, S, at the design temperature. Values from Appendix
_ are interpolated at the design temperature and is determined as 16.861 ksi, 116.257 N mm -2. (Cook,
n.d.) The minimum thickness column diameter including corrosion allowance is benchmarked at 10mm
by Appendix _. A ‘double- welded butt joint with spot checks’, giving an E of 0.85 is selected to balance
joint specialisation requirement and cost.
19
Longitudinal and hoop thicknesses, equations 44 & 45 consider stresses incurred to the vessel in the
vertical and circumferential axes, which are driven by internal pressure. Calculations including a
corrosion allowance are shown in Table 18.
Table 18: Vessel Thickness Calculations.
Calculations are less than the minimum thickness because of the low design pressure to MAST ratio. ‘t L
and ‘th’ are compared to the guideline minimum thickness. The largest, 10mm is taken as vessel
thickness.
Domed End Head Thickness:
Thicknesses above consider the cylindrical section of the vessel. Three types of domed end heads;
‘hemispherical, ellipsoidal and torispherical heads’ are considered.
Ellipsoidal is the ‘most economical at pressures above 15 bar’. Design pressure is more than four times
smaller, rendering its use. Hemispherical head is ‘capable of resisting twice the pressure of a
torispherical head’. This would be the best design choice if design pressure was close to the material
MAST. The system maximum pressure is over three hundred times smaller, causing overdesign.
Torispherical head is the ‘best for pressures under 15 bar.’ For this reason, torispherical head is selected.
The domed end thickness is calculated in Table 19.
‘Crown radius should not exceed column diameter’ so R C.=Di, 2702 mm. The knuckle to crown radii
should not be less than 0.06 to avoid buckling.’ The lower bound of the acceptable limit is used to
calculate the largest allowable domed end thickness. Torispherical depth per end is doubled for top and
bottom ends and added to total cylindrical height from section 2.6.3 to obtain total vessel height.
Table 19: Domed End & Total Column Height Calculations.
√[( ]
48 361.930 mm
hi =R i− Ri−
Di
2 )(
Ri +
Di
2 )
+2 r i
Rounding errors led to domed end thickness being higher than minimum thickness. Domed ends will
assume the minimum to ensure a uniform vessel. If sufficient time for detailed design, domed end depth
would be determined for accurate Hsk.
Vessel Dead weight Calculations:
Total empty vessel deadweight must be considered to ensure vessel will not fail under full loading. The
following dead-weights are considered significant; empty vessel, packing, insulating material, and caged
ladder classified as auxiliary. Dead weight for feed distributors and liquid redistributors were considered.
Time constraints will assume for them to be considered under the constant Cw,
20
‘Cw = 1.15 for distillation columns, accounting for multiple fittings such as support rings or equivalent
fittings.’ ZC is used as HV.
Table 20: Empty vessel dead weight.
Packing deadweight above and below the feed is calculated by splitting the packed height based on the
rectifying and stripping sections. Packed height per section combines Table 7 and Z P. Packings are
assumed to be loaded; total packed height dead weight is ‘multiplied by 1.2 kN’. Bulk material density is
considered to account for packing voidage.
Table 21: Packing dead weight.
Empty and loaded packing dead weight is calculated as 84.613 and 101.536 kN.
Table 22: Insulation dead weight.
Insulation is deployed to ensure Qatar’s climate does not interfere with column temperature control. This
is ‘doubled to account for attachments, fittings, and moisture absorption.’ Initial insulation dead weight
from Table 22 is doubled, showing a final 21.542 kN insulation dead weight, Wi.
Auxiliary fittings externally attached to the vessel is considered significant dead weight. A caged ladder
was selected to ensure safe climbing in extreme weather. A rough guide for caged ladder weight is 360N
per metre length. The ladder is assumed to be the same length as Hv, so total caged ladder weight, WCL,
is derived as 3.842 kN.
Total vessel deadweight, WZ, is calculated using equation 56. All units are in kN.
W Z =W v +W P . L + W i +W CL ( Eq56 ) ,W Z =93.193+ 101.536+21.542+3.842=220.113 kN
Vessel Stresses
Stresses imposed on the vessel caused by weight under loading, and internal pressures in both vertical
and horizontal axes, whilst addressing Qatar’s geographical challenges such as wind speed are
considered in this section. All stress calculations use the units N mm-2.
Weight stresses assume the vessel is fully filled with water, W W, and combines WZ for worst- case
scenario, WT. Water’s density is assumed 1000 kg m -3 for design ease. The highest liquid density in
Table 11 is less than water, so column operating stresses will be lower than calculations, ensuring the
column will experience less severe weight stresses. Circumferential, longitudinal and weight bearing
stresses are shown in Table 23.
1.1.1. Primary Stresses
21
Table 23: Stress calculations
The higher dead weight stress will be considered from this point for calculations involving σ w will use
10.342 N mm-2. Hoop stresses are expected to be half of the stresses acting longitudinally because of
the nature of the equation.
Bending Stress
As stated previously, the vessel will be out in the open so will be prone to wind speed loading. Qatar
does not experience high winds regularly. However, its desert location makes it vulnerable to sandstorms
so is considered for design. High wind speeds induce bending stresses on the vessel. Ras Laffan is
located near to the coast, so is more vulnerable to higher speeds as coastal areas face worst storm
conditions. Vessel effective diameter accounts for a 0.4m caged ladder allowance. ‘Maximum wind
speed recorded in Ras Laffan, Qatar was 16.5 m s -1,’ which is equivalent to 59.4 km h-1. (Aboobacker et
al., 2021) Bending stresses are considered at 160 km h-1 to ensure the column can withstand extreme
wind loading. Coefficient 0.07 in equation 64 is ‘adjusted for caged ladder’. Adjusted diameter
dimensions for wind loading calculations are in Appendix _
‘Total bending moment’, and the ‘second moment of area of the vessel are used to calculate maximum
bending stress imposed on the column in Table 25. Hv considers domed end depths and ZC.
Table 24: Bending stress calculations.
( )
68 M x Di 5.892 N mm-2
σ b=± +t
lv 2
Bending stress is four times smaller than longitudinal stress, having minimal effect on resultant
longitudinal stress.
Resultant Longitudinal Stress, σz:
Upwind and downwind vessel stresses along the vertical axis are determined for resultant longitudinal
stresses. The equation assumes ‘σw is compressive, and therefore negative’.
Table 25: Resultant longitudinal stresses, σz.
22
Both resultant values are positive, showing σ w and σb to be insignificant compared to σL. This may be
caused by condition overestimation, where a lower thickness being tolerable to increase compressive
stresses for economical vessel design. However, if plant expansion is considered, the column would still
be mechanically operable.
Compressive stresses have negligible effect, so critical buckling stress, equation 74, is not of major
importance and is found in Appendix _ and compared with the sum of the compressive stresses, σ w and
σb, 16.324 N mm-2. Vertical vessels are more prone to buckling than horizontal vessels, so is still
considered.
[ √ ]
σ 1, upwind =0.5 ∙ σ h+ σ z + ( σ h−σ z )2+ 4 τ 2 ( Eq 71 ) , σ 1=0.5∙ ¿
Table 26: Principal stresses.
72 σ =0.5 ∙ [ σ + σ −√ ( σ −σ ) +4 τ ]
2 h z h z
2 2 19.193 7.409 N mm-2
Evaluation of Appendix _ compares maximum stress differences and SS316’s MAST to ensure the
column will not fail. The largest difference, 47.11 N mm-2, is compared to 116.257 N mm-2. Calculations
use equations 75- 77 to obtain the maximum governing stress and is shown below.
Table 27: Evaluation of Principal Stresses.
The maximum governing stress to the vessel from Appendix _ is 47.11 N mm -2. This is lower than the
MAST, demonstrating stress will not weaken the column’s mechanical integrity.
1.2. Skirt Support
Vertical vessels require skirt support to remain upright as ‘they do not impose concentrated loads on the
shell vessel.’ SS316 is considered as skirt support. Process fluid will not contact skirt, so CS was
considered initially. As the column is out in the open, it is exposed to Ras Laffan’s typography, which is
predominantly sand. Sand may contain salts or low concentrations of materials which are corrosive to
carbon steel, weakening the skirt.
Assumed skirt height is 3 m as reboiler tubes are assumed to be ‘standard 2.44 m.’ 3 m accounts for
tubes and its corresponding heads. Skirt thickness is assumed 8 mm. Stainless steel young’s modulus at
ambient conditions is 200000 N mm-2. Skirt angle is assumed 90° for design ease. D S is assumed DC at
90°. Joint efficiency is assumed to be 0.85. SS is assumed to be the
23
‘Weight of the liquid to fill the vessel will be transferred directly to the skirt’, so vessel weight is only
considered for operating dead- weight stress. Test weight considers the maximum weight of the vessel to
account for worst- case loading. Skirt bending stress applies skirt diameter, thickness and the maximum
bending moment, Ms, at, 13.674 m. Using equation 65, Ms = 556540838.5 N mm. Skirt stresses are
calculated are shown below.
Table 28: Skirt stresses calculations.
Tensile resultant force is solved by finding the smallest difference between bending and dead weight
stresses, and the compressive resultant force is the largest sum. These worst- case resultant forces are
( )
83 t sk 92.524 N mm-2
0.125 ∙ EY ∙ ∙ sin θs
Ds
Resultant compressive and tensile stresses satisfy the criterion, therefore acceptable. Lower thicknesses
can be reduced to the minimum, 6mm, for economical design by changing the Excel spreadsheet.
1.3. Pipe Diameter Sizing
For fluid flow, pipe diameters are determined based on mass flow and density. Equations give an optimal
diameter and assume stream turbulence since they are optimised for case specific streams. Specialised
pipes would incur unnecessary costs, so standard diameters are selected.
Stainless steel is selected as pipe material for best fabrication to the vessel and multiple standard sizes
available. Table 30 and 31 shows optimal diameters developed for feed, distillate, bottoms and reflux
streams. Bottoms quantity that returns as vapour is not known, because of time constraints for reboiler
design. Reflux density is assumed at distillate composition at condenser outlet temperature and is
obtained from Aspen Plus. Equation 83 obtains diameter in mm. Densities are in Table 11.
Table 30: Optimum diameters and their counterparts.
24
86 t 6.02 17.48 7.11 6.55 mm
62 (Rearr) d i=d o−2 t 108.28 778.04 154.08 128.2 mm
Eq Number Units
Standard pipe sizes that process liquid, do, are 4.5, 6.625 and 5.56 inches respectively. Standard pipe
sizes which process vapour, distillate pipes, are sized at 32 inches. Pipe sizes processing vapours are
larger than liquid process pipes as gases occupy more volume, so need more space to move through
pipes under turbulent flow. Thicker pipes were selected to account for corrosion as SS316 faces ‘slight
corrosion’.
25
Additional Unit Design
This section considers preliminary design for units associated with T-102, condenser and reboiler.
Condenser Thermal Design
Column distillate faces condensation to serve the purpose for reflux to enter as a liquid. The condenser
is designed as a total condenser, where all fluids condense compared to distillate state. This section
explores condenser thermal design, considering a shell & tube, counter- current operation, as it transfers
heat between fluids effectively. Mass flowrate condensed is V’ from internal traffic from Table 10, 26.933
kg s-1.
Condensation occurs shell side, with the utility stream being cooling water. Ras Laffan’s proximity to the
sea considers seawater as a cheaper and more ethical alternative to using clean water. Sea water is
assumed to be processed to a clean standard in situ, assuming minimal fouling for efficient heat transfer.
Condensers are gravity- driven, so operation is more effective if mounted at the top of the column. This
design ignores this consideration.
Condenser Flowrates & Duty
Vapour leaves the column and enters the condenser from the rectifying section, so V’ from internal traffic
calculated in Table 10 is assumed to be the flowrate condensed, 26.933 kg s -1 or 0.509 kmol s-1. Inlet
temperature tube side is assumed column dew point, 64°C. Tube side outlet temperature is assumed to
be liquid at 54°C. Cooling water is assumed to receive a 5°C increase from Qatar’s average
temperature, 29.4°C, so the process fluid via reflux enters as liquid. Condenser temperatures are in
shown below.
Table 32: Condenser Temperature Data
TH, in 337.15 K
TH, out 327.15 K
TC, in 302.55 K
TC, out 307.55 K
T Shell, Avg 332.15 K
T Tube, Avg 305.05 K
Condenser duty is calculated based on the enthalpy change of the distillate vapour flowrate at dew point
as it condenses at the tube outlet temperature. Duty obtained is the requirement for the service fluid
required to cool the process fluid. Vapour and liquid enthalpies are found in Appendix _. C p does not
change significantly across service fluid temperatures, so is assumed 4.18 kJ kg-1 K-1.
Table 33: Condenser duty & service fluid flowrate calculations
Condenser duty requires an energy supply of 12461.899 kW, an energy sink, for a 10°C process fluid
reduction using CW. 596.623 kg s-1 is required for the condenser to cool the process fluid to a specific
temperature. This would require excessive monitoring and high energy to process substantial amounts of
sea water to meet clean specifications, which is process inefficient. Use of a heat transfer fluid, or a fluid
with higher heating capacities offer lower service fluid flowrate requirements.
Total heat transfer area utilises condenser duty, log mean temperature and assumes an overall heat
transfer coefficient, U. Assumed U is based off ranges determined by the fluids used in the heat
26
exchanger. Figure 5 show acceptable U ranges. U is iterated until the assumed U is within a 30% design
range of calculated U.
630 W m-2 °C is the final assumed U. 500-700 W m -2 °C is considered as nitrogen, although in trace
quantities, is non- condensable so is considered for conservative design. A temperature correction factor
is applied to the log mean temperature to ensure an accurate estimation, found in Appendix _. Overall
heat transfer area calculations are shown in Table 34.
93 ∆ T M =Ft ∙ ∆ T LM 26.699 K
94 Q̇ 740.881 m2
A=
U assumed ∙ ∆ M
95 At =π ∙d o ∙ Lt 0.491 m2
96 A 1509 Tubes
Nt=
At
( )
97 N 1 1182 mm
Db =d o t n1
K1
98 pt =1.25 ∙ d o 26.708 mm
99 Db 45
Nr=
pt
Tube outer diameters and lengths were iterated at standard sizes. A compromise number of tubes was
achieved using a 21.336 mm do and 7.32 m tube length for acceptable tube flow is shown in Table 34. N t
is rounded up it is impossible to have a decimal number of tubes.
Total tube diameter is grouped as bundle diameter as all calculations per tube would require excessive
calculations. K1 and n1 are 0.215 and 2.207 as the exchanger is assumed to have 1 pass both shell and
tube side.
Tubes assume a square pitch 25% larger than the outer diameter and is used to obtain the average
number of tube rows that experience condensation. A 2/3 correction factor is applied to equation 99,
giving 30 tubes per row on average. Row number and bundle diameter are rounded up for design ease.
1.3.1. Shell- Side Coefficient, (hc)b
Cooling water flows tube side. Shell side average and wall temperatures are averaged to calculate
condensate average temperature for the distillate. Table 35 shows properties for the shell condensate.
Condensing coefficient is assumed 1500 W m-2 °C.
27
Table 35: Wall temperature.
( )
100 ( T shell , avg−T tube ,avg ) ∙ U assumed 320.77 K
T w = T shell , avg−
U condensing
Process stream and cooling water properties used in this section will be at the average condensate
temperature, shown in Table 36.
Table 36: Condenser Stream Properties (Aspen Plus, 2025)
WC 26.933 kg s
−1
−1 −1
Γh= ( Eq102 ) , Γ h= =2.44E-03 kg s m /tube
Lt ∙ N t 7.32 m∙ 1509 tubes
Condensate tube loading, average number of rows and process fluid data from Table 36 derive the Shell-
side heat transfer coefficient, which is calculated below.
[ ]
1
ρL ( ρL −ρV ) g 3
−1
6
( h c ) b=0.95 ∙ k L μL Γ h
∙ Nr ( Eq 103 ) ,
[ ]
1
709.989 kg m ∙ ( 709.989 kg m −6.375 kg m ) ∙ 9.81m s
−3 −3 −3 −2 1
−2 3 −1
6
( h c ) b=0.95 ∙ 0.134 mN s m ∙ −3 −2 −1 −1
∙ 30 =1654.593 W m ℃
0.167 × 10 mN s m ∙ 2.44E-03 kg s m
Shell- side coefficient is 10.31% greater than Ucondensate, so no correction to Tw is needed.
1.3.3. Tube- side Coefficient, hi
Tube- side heat transfer is driven by tube- side velocity and tube cross- sectional area. Turbulent flow is
preferred tube- side so cooling water at one point in a tube is replaced constantly, taking heat from the
process fluid. Inner diameter, di, is 17.12 mm. CW flowrate from Table 33 is the mass flowrate, 596.263
kg s-1. Equations required for tube- side coefficient and their constituent results are tabulated below.
28
Table 37: Tube- side heat transfer coefficient, hi.
29
1
=
1
+
1
+
0.021366 ln ( 0.021366
0.01712 ) 0.021366
+ ∙
1
+
0.021366
∙
1
U O 1654.593 5000 2 ∙ 45 0.01712 6000 0.01712 7696.410
1 −1 −1 −1 −1
¿ m ℃ W =814.908W m K
1.227E-03
Uassumed is 29.35% smaller than UO, which is in the 30% acceptable range, therefore U assumed is deemed
valid. UO could be further for a lower difference, but calculated is within the range. U O is used to optimise
the heat exchanger, for new total heat transfer area, number of tubes and bundle diameter which will be
used going forward. These are tabulated below.
Table 38: Optimised Heat Exchanger Calculations using U O.
( )
97 (Optimised) Nt
1
n1
1051 mm
Db , O=d o
K1
30
Shell cross flow area is calculated with respect to shell diameter and baffle spacing. Cros- flow area is
used to obtain the mass velocity, Gs, and is divided by vapour density to obtain shell -side velocity. Shell
side is within an acceptable range of 0.6-1.5 m s-1, so is acceptable.
Equivalent diameter is calculated to use an equivalent diameter, taking baffles and head type into
account for fluid flow and is considered as the diameter for Reynolds number calculation below. Viscosity
is assumed to be in N s m-2.
Table 40: Shell- side Reynolds number.
( )
114 Lt ρ v us 2 101.815, N m-2,
∆ P=8 j f ∙ ∙ 0.0102 bar
de 2
This is less than 0.07 bar, therefore is acceptable. Pressure drop is negligible, so further considerations
are unnecessary.
Tube Side Pressure Drop
Fluid flow tube side is liquid, so a pressure drop will occur so is calculated. Tube side velocity was
calculated in Table 37.
Table 42: Tube side Reynolds number.
Reynolds number is turbulent like shell side. Figure 7 shows a tube side correlation between Reynolds
number and friction factor. The graph is interpolated to obtain a friction factor of 3.1E-03.
31
Figure 7: Tube- side friction factor.
[ () ]
116 Lt ρ ut
2 19903.724, N m-2,
∆ Pt =N p 8 j f ∙ +2.5 0.199 bar
di 2
Acceptable pressure drop range is 0.05 – 0.2 bar. This proves design is acceptable for operation in
accordance with standard sizes used. Tube- side could be optimised better to ensure it is not so close to
the upper bound of the accepted range, but process efficiency is not as important than in T-102 as it is
not the focal point of report.
Cooling water return can be used as waste heat in other aspects of the process for example, pre-heating
feedstock before it enters the reactor or use as a source of cooling water for a cooling jacket for the
reactor. T-103 and T-104 operate at atmospheric pressure, so the waste heat from the condenser can be
used to heat the feed until saturation.
Reboiler Design
V’ from the column stripping section is partially vapourised before it is re-introduced into the column, so
is considered as reboiler flowrate. A natural thermosiphon reboiler, with a minimum circulation ratio of 3
to avoid reboiler drying, is considered for preliminary design as it can manage higher flowrates.
Vaporisation is assumed to occur tube side. Natural thermosiphon reboilers are density- driven, so pump
requirement is eliminated; improving process efficiency as pump operation would be expensive due to
large process requirements. Reboiler is assumed to operate at 3.023 bar, the sum of the pressure drop
from section 4.3, 0.023 bar to the column operating pressure, 3 bar. Bottoms mass flowrate is divided by
its corresponding molar flowrate, giving a 26.444 kg kmol-1 molecular weight.
Design is limited as mixtures that leave the reboiler as a vapour- liquid mixture require extensive
simulation and testing. Design methods require rigorous modelling to develop and would not be possible
to conduct unless a longer period were granted. Increased PO polymerisation at higher temperatures
may cause reboiler fouling and should be taken into consideration when commissioning the plant. This
section consists of a preliminary design calculating reboiler duty and number of tubes.
32
Reboiler Duty
Quantity re-entering the distillation column as vapour is calculated below.
−1 −1
Liquid entering the reboiler=L’−B ( Eq 117 ) , Liquid entering thereboiler =42.919 kg s −15.986 kg s =26.933 kg s
Vaporised flowrate in the reboiler, V’, is assumed initially. This value did not satisfy the minimum
recirculation rate of 3, so V’ was iterated using goal seek until the condition was met on the
‘220178574_Final_Design_Project_Spreadsheet’. V’ used from this point is 0.252 kmol s -1. L’ is the liquid
leaving the reboiler as a liquid, 0.756 kmol s-1. The products of V’ and L’ with xb give V’i. and L’i
respectively. Refer to Appendix _ and _ for vapourisation enthalpies and average Cp data
Table 44: Condenser Duty Calculations
Reboiler duty considers energy required to vaporise V’ and considers the sensible energy to heat liquid
leaving the reboiler, L’, from the reference, 298K to the bottoms temperature, 379.15K at 3.023 bar.
Reboiler duty is more intensive than condenser despite the stream changing phase entirely. 81 mole %
of condenser components are considered liquid at reference state, requiring less energy to condense.
Reboiler considers a larger temperature change and vaporises assumed bottoms components that are
liquid at reference state. Trace components present in opposite streams in reality are not considered.
Heat Transfer Area and Number of Tubes
Condenser is compared to a common maximum heat transfer flux, q’ max to obtain the heat transfer area.
Q reboiler 17038862W 2
AO = ( Eq 119 ) , AO= −2
=449.574 m
q ' max 37900 W m
Maximum heat transfer flux ‘recommendation for vertical thermosiphon reboilers are 37900 W m-2’. Tube
inner diameter and length are assumed to be at ‘typical reboiler standard sizes, 25.4 mm and 2.44 m’
respectively. Tube area and number of tube calculations follow equations 95 and 96 and are shown
below. Tube number is rounded up as stated previously.
33
2
At =π ∙2.44 m∙ 0.0254 m=0.195 m
2
449.574 m
Nt= 2
=2306 tubes(rounded )
0.195 m
2306 tubes are preliminary, using the assumed reboiler standard tube sizes. Longer pipes and larger
diameters can optimise tube number. Tube number acquired is only for preliminary design and is not
accurate. If more time was allowed, reboiler design and optimisation would be completed in more depth.
The assumed heat transfer flux is assumed high for calculation ease and would be accurately assumed
for the same reason mentioned previously.
34
Control & Instrumentation
A Piping and Instrumentation Diagram (P&ID) for T-102 has been produced, outlining key operation
indicators, valves and control loops which work simultaneously for efficient column operation. All pipes
are insulated for good temperature control and are constructed using the same vessel material to ensure
easier fabrication. Standard pipe sizes mentioned in Tables 30 and 31 are shown on the P&ID as stream
labels. The P&ID considers ISO standards. Primary process lines are thicker than the secondary process
lines, such as utility streamlines. At least one person should always be occupying the control room when
the plant is operating for quick emergency shut down in the worst- case.
The following control loops have been implemented in the T-102 P&ID:
A level element (LE) monitors fluid accumulation at the bottom of the liquid disengagement zone. The
value is reported to a level transmitter (LT) which compares the level to a 50% set point. The primary
function of the control loop uses the level control valve, adjusting the bottoms flowrate related to the
level. If the level exceeds this, lower than 0.25 m or higher than 0.75 m, the control loops secondary
function sets off the alarms in the control room, notifying control room personnel to act accordingly.
One issue with distillation column operation is that reflux flowrates tend to get larger and larger as the
column operates. A flowrate control loop that limits the snowball effect of the reflux drum is considered.
Flowrate element (FE) reads the flowrate and sends it to a flowrate transmitter (FT). FT transmits it into
an electrical signal, which compares the process flowrate to the highest and lowest allowable ones. If it is
significantly out of the range, alarms will go off in the control room to alert operators of the issue. The
electrical signal is transmitted to a flowrate relay (FY) which dictates the flow control valve opening.
35
36
Ideally finish all design by here
37
38
39
40
41
42
43
44
Appendices:
Component Stream
Feed, kg h-1 Distillate, kg h-1 Bottoms, kg h-1
C3H6 2204.915 2204.915 0.000
H2O2 233.442 0.000 233.442
H2O 15108.788 0.000 15108.788
CH3OH 36188.747 316.887 35826.860
C3H6O 10357.493 9218.169 1139.324
C3H6O2 210.176 0.000 210.176
N2 25.477 25.477 0.000
Total 64329.038 11765.448 52518.59
Molecular Weight, Mr
Component Value Units
C3H6 42.080 kg kmol-1
H2O2 34.015 kg kmol-1
H2O 18.015 kg kmol-1
CH3OH 32.042 kg kmol-1
C3H6O 58.079 kg kmol-1
45
C3H6O2 76.094 kg kmol-1
N2 28.013 kg kmol-1
46
N2 4.10E-04 4.074E-03 0.000
Total 0.996 ≈ 1 1.002 ≈ 1 1.000
47
Total 1682.134
48
Appendix 7: Final Iteration for Column Bubble Point, 379.55K, 106.4°C at 3.023 bar.
49
Appendix _: Molkanov Equation for Number of Theoretical Stages Against Economic Reflux Ratios
50
Appendix _: Feed Properties
51
Appendix _: Hydrogen Peroxide Compatibility Chart
(Industrial Specialties Mfg. and IS MED Specialties, 2019)
52
Appendix _: Additional diameter dimensions to calculate wind loading per linear millimetre.
( )
74 t 73.475 N mm-2
σ c =2× 104
DO
91 S=¿ ¿ ¿ 0.145
92 1−S ¿ 0.988
F t=( √ R +1)¿ ln [
2
]
[ ]
1−RS
2−S [ R+1−( √ R +1 ) ]
2
(R−1) ln
2−S [ R+1+ √( R +1 ) ]
2
53
Ft used in report taken from ‘220178574_Final_Design_Project_Spreadsheet’ for calculation ease.
55
56
57