WTW Qi284 Iqsn Fieldbus Ysi
WTW Qi284 Iqsn Fieldbus Ysi
ba76148e05 05/2017
IQ SENSORNET
Fieldbus linking
LINKING THE IQ S ENSORNET TO A FIELDBUS
Fieldbus linking
Contact YSI
1725 Brannum Lane
Yellow Springs, OH 45387 USA
Tel: +1 937-767-7241
800-765-4974
Email: [email protected]
Internet: www.ysi.com
2 ba76148e05 05/2017
Fieldbus linking Contents
ba76148e05 05/2017 3
Contents IQ SENSORNET Fieldbus linking
6 What to do if ... . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.1 PROFIBUS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 56
6.2 Modbus RTU . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 57
6.3 Ethernet fieldbuses . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 58
7 Contact Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
7.1 Ordering & Technical Support . . . . . . . . . . . . . . . . . . . . 59
7.2 Service Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 59
4 ba76148e05 05/2017
IQ SENSORNET Fieldbus linking Linking the IQ SENSORNET to a fieldbus
ba76148e05 05/2017 5
Linking the IQ SENSORNET to a fieldbus IQ SENSORNET Fieldbus linking
6
IQ SENSORNET Fieldbus linking Installing the interface in the IQ SENSORNET
Connecting the Profibus The Profibus / Modbus cable is connected to the IQ SENSORNET using
/ Modbus cable a 9-pin D-SUB connector on the top of the housing.
To remove the blind plug, lift the safety bracket with a suitable screw
driver at both clamps on the left and right side (see Fig. 2-1).
ba76148e05 05/2017 7
Installing the interface in the IQ SENSORNET IQ SENSORNET Fieldbus linking
1
1 Safety bracket
OK
er !
Pow
CAUTION
If water gets into the enclosure of a module with internal power
supply, there is danger of an electric shock.
If water gets into the enclosure of an MIQ module, there is a risk
of short circuits.
To prevent the enclosures of the IQ SENSORNETfrom being pene-
trated by water the following must be observed:
Follow the safety instructions of the IQ SENSORNET system op-
erating manual.
Use connectors recommended by YSI only.
When the connector is removed, the connection socket of the
IQ SENSORNET must be closed with the blind plug and secured
with the safety bracket.
8
IQ SENSORNET Fieldbus linking Installing the interface in the IQ SENSORNET
approx. 100 mm
M C S
USB
M C S
OK
appro
ESC
ba76148e05 05/2017 9
Installing the interface in the IQ SENSORNET IQ SENSORNET Fieldbus linking
10
IQ SENSORNET Fieldbus linking Installing the interface in the IQ SENSORNET
When plugged in, the RJ45 socket is not sufficiently protected against
moisture. With outdoor installation, the Ethernet cable must therefore
be clamped directly on the PCB of the MIQ/MC2 or MIQ/MC3 controller
to ensure a safe Ethernet communication. For this purpose there is a
4-pole LSA terminal strip and a shielding terminal on the main PCB. An
LSA punch down tool is required for the assembly.
ba76148e05 05/2017 11
Installing the interface in the IQ SENSORNET IQ SENSORNET Fieldbus linking
MIQ/MC2 1
2
Fig. 2-3 Ethernet connection with RJ45 socket (MIQ/MC2)
MIQ/MC3 1
2
Fig. 2-4 Ethernet connection with RJ45 socket (MIQ/MC3)
12
IQ SENSORNET Fieldbus linking Installing the interface in the IQ SENSORNET
Rx-
Rx+
Tx-
Tx+
SHIELD CLAMP
ENTHERNET CABLE
3
Fig. 2-5 Ethernet connection via terminal strip
(example: MIQ/MC2, MIQ/MC3 likewise)
5 Strip the Ethernet cable for approx. 2 cm and untwist the Rx+,
Rx-, Tx+ and Tx wires.
6 Carefully slash the cable shield (foil + netting) lengthwise and
put it backwards over the cable sheath (pos. 3 in Fig. 2-5).
7 Feed the Ethernet cable through the cable gland into the mod-
ule housing.
8 Where the cable shield was put backwards, press the Ethernet
cable into the shielding terminal (pos. 4 in Fig. 2-5). The shield-
ing terminal must contact the cable shield across a wide area.
9 Connect the Rx+, Rx-, Tx+ and Tx- wires to the LSA terminal
strip with the aid of an LSA punch down tool. Make sure that
the cable assignment agrees with the specification on the ter-
minal label under the terminal strip.
10 Fasten the cap nut of the screwed cable gland.
11 Close the module.
ba76148e05 05/2017 13
Configuring the IQ SENSORNET IQ SENSORNET Fieldbus linking
Checking the A functioning Profibus data connection is displayed in the menu for Pro-
connection (general) fibus settings (see above).
14
IQ SENSORNET Fieldbus linking Configuring the IQ SENSORNET
MIQ/MC2
1 2
Fig. 3-1 LEDs on the Profibus module (MIQ/MC2)
1 lights up green: Data connection OK
2 lights up green: Voltage OK
MIQ/MC3
1 2
Fig. 3-2 LEDs on the Profibus module (MIQ/MC3)
1 lights up green: Data connection OK
2 lights up green: Voltage OK
ba76148e05 05/2017 15
Configuring the IQ SENSORNET IQ SENSORNET Fieldbus linking
The GSD file contains all necessary information on the Profibus module
and is required by the configuration program of the Profibus master.
The current GSD file is provided on the Internet at www.YSI.com.
Settings
Setting Selection/Valu Explanation
es
Device 1 ... 247 Instrument address of the
address IQ SENSORNET in the Modbus
RTU
Baud rate 1200 Baud rate
2400
4800
9600
19200
38400
57600
Parity None Parity
Even
None
Odd
(2 stop bits)
Even
(1 stop bit)
Odd
(1 stop bit)
16
IQ SENSORNET Fieldbus linking Configuring the IQ SENSORNET
ba76148e05 05/2017 17
Configuring the IQ SENSORNET IQ SENSORNET Fieldbus linking
18
IQ SENSORNET Fieldbus linking Configuring the IQ SENSORNET
ba76148e05 05/2017 19
Configuring the IQ SENSORNET IQ SENSORNET Fieldbus linking
1 Carry out a system start without any sensors (see system oper-
ating manual).
2 Connect the sensors to the system in the required order.
After connecting each sensor, wait until the sensor is recog-
nized by the system (see system operating manual, chapter
Installation).
20
IQ SENSORNET Fieldbus linking Configuring the IQ SENSORNET
Disconnecting / You can also change the sensor numbers in the system by disconnect-
connecting all sensors ing all sensors, erasing any inactive datasets and then reconnecting all
of the IQ SENSORNET sensors in the correct order.
When the inactive datasets are deleted, all settings for the
sensors are deleted as well.
ba76148e05 05/2017 21
Configuring the IQ SENSORNET IQ SENSORNET Fieldbus linking
USB interface
1 Save the configuration from the model to a USB memory
device (see system operating manual of your system).
2 Connect the USB memory device with the configuration data to
the target system and load the configuration
(see system operating manual of your system).
Network connection
1 Save the configuration from the model to a PC via a network
connection (see system operating manual of your system).
2 Connect the PC to the target system via a network and load the
configuration.
MIQ/MC2, MIQ/TC 2020 XT:
see operating manual IQ Software Pack CONNECT.
MIQ/MC3, MIQ/TC 2020 3G, DIQ/S 28X-E[F]:
see system operating manual of your system (section
IQ WEB CONNECT).
22
IQ SENSORNET Fieldbus linking Communication with fieldbuses
ba76148e05 05/2017 23
Communication with fieldbuses IQ SENSORNET Fieldbus linking
4.1.3 Configuration
24
IQ SENSORNET Fieldbus linking Communication with fieldbuses
ba76148e05 05/2017 25
Communication with fieldbuses IQ SENSORNET Fieldbus linking
4.1.5 Example
Querying sensors 2 Corresponding to the sensor numbers (Sxx) in the IQ SENSORNET, the
and 5 slots have to be assigned gap-free to the last sensor to be queried.
Profibus Slots for sensors not required have to be assigned to the module empty
slot.
Configuration
Slot Module
1 empty slot (only Profibus; leave unoccupied for Profinet)
2 SensorData
3 empty slot
4 empty slot
5 SensorData
26
IQ SENSORNET Fieldbus linking Communication with fieldbuses
12 8 C2h
13 9 00h Secondary 00000000h (Float 32)
measured value --> 0
14 10 00h but measured value invalid (MISSING),
15 11 00h see byte 11 (measured value status)
16 12 00h
ba76148e05 05/2017 27
Communication with fieldbuses IQ SENSORNET Fieldbus linking
The IQ SENSORNET provides the sensor data for read access only.
Write access is not possible.
The data to be queried with Profibus DPV1 are addressed via slot,
index and length data.
Data query
Slot 0
Index Sensor number of the first sensor to be queried
Length Number of bytes to be queried
SensorData compact Each sensor in the IQ SENSORNET is assigned an index in slot 0 of the
PLC. Data required for the query:
Data query
Slot 0
Index 100 + sensor number of the first sensor to be queried
Length Number of bytes to be queried
28
IQ SENSORNET Fieldbus linking Communication with fieldbuses
The data block contains the data of the sensors in the order of their reg-
istering to the IQ SENSORNET (Sxx number).
ba76148e05 05/2017 29
Communication with fieldbuses IQ SENSORNET Fieldbus linking
4.2.4 Example
30
IQ SENSORNET Fieldbus linking Communication with fieldbuses
Sxx
12 8 C2h
13 9 00h Secondary 00000000h (Float 32) --> 0
measured but measured value invalid
14 10 00h value (MISSING),
15 11 00h see byte 11 (measured value sta-
tus)
16 12 00h
17-32 13-24 ... ... ...
03
ba76148e05 05/2017 31
Communication with fieldbuses IQ SENSORNET Fieldbus linking
4.3 EtherNet/IP
The sensor data are transferred as data blocks of 16 bytes per each
sensor. The data of up to 30 sensors are transferred (30 * 16 bytes =
480 bytes).
You can also query the sensor data individually (see sec-
tion 4.4).
4.3.2 Configuration
Connection GetSensorDataAll
Use the following configuration data if you do not use the EDS file.
The data block contains the data of the sensors corresponding to the
sensor number (Sxx number) in the IQ SENSORNET.
32
IQ SENSORNET Fieldbus linking Communication with fieldbuses
ba76148e05 05/2017 33
Communication with fieldbuses IQ SENSORNET Fieldbus linking
4.3.4 Example
Configuration
Connection GetSensorDataAll
1h --> VALID
Secondary measured
value (bits 3-0):
4h --> MISSING
see section 5.3
9 42h Main mea- 429E46C2h (Float 32)
sured value --> 79,1382
10 9Eh Measured parameter and
11 46h unit,
see byte 10 (measuring
12 C2h mode)
13 00h Secondary 00000000h (Float 32)
measured --> 0
14 00h value but measured value
15 00h invalid (MISSING),
see byte 11 (measured
16 00h value status)
17- ... ... ...
02
32
34
IQ SENSORNET Fieldbus linking Communication with fieldbuses
number
Sensor
Sxx
Value Information Meaning of the value
03
48
49- ... ... ...
04
64
... ... ... ... ...
465
-
30
480
ba76148e05 05/2017 35
Communication with fieldbuses IQ SENSORNET Fieldbus linking
Start
36
IQ SENSORNET Fieldbus linking Communication with fieldbuses
4.4.1 Configuration
Use the following configuration data if you do not use the EDS file.
Connection GetSensorData2B
Use the following configuration data if you do not use the EDS file.
ba76148e05 05/2017 37
Communication with fieldbuses IQ SENSORNET Fieldbus linking
4.4.2 Data block for sensor selection (output data of the PLC)
38
IQ SENSORNET Fieldbus linking Communication with fieldbuses
4.4.4 Example
Querying sensor 02
Configuration
Byte Valu Information Meaning of the value
e
1 02h Sensor number 02h (Int 8) --> 2
(Sxx) in the Sensor number S02
IQ SENSORNET
Sensor data
Byte Value Information Meaning of the value
1 02h Sensor number 02h (Int 8) --> 2
Sensor number S02
2 02h Sensor status 02h (Int 8) --> MEASURE
see section 5.2
3 04h Sensor model 0401h (Int 16)
--> VisoTurb 700 IQ
4 01h Sensor model see section 5.5
5 00h Status info 0000h (Int 16)
--> no errors
6 00h Status info see section 5.6
7 00h Measuring mode 00h (Int 8) --> FNU Turb
see section 5.7
8 14h Measured value 14h (Int 8)
status Main measured value (bits 7-4):
1h --> VALID
Secondary measured value (bits 3-0):
4h --> MISSING; see section 5.3
9 42h Main measured 429E46C2h (Float 32)
value --> 79,1382
10 9Eh Measured parameter and unit,
11 46h see byte 10 (measuring mode)
12 C2h
13 00h Secondary mea- 00000000h (Float 32)
sured value --> 0
14 00h but measured value invalid (MISSING),
15 00h see byte 11 (measured value status)
16 00h
ba76148e05 05/2017 39
Communication with fieldbuses IQ SENSORNET Fieldbus linking
On each query of sensor data with the Modbus protocol, a block of con-
secutive registers is read.
Query and response Data transmission takes place via query and response telegrams. The
telegram form of the telegrams is determined by the Modbus RTU protocol.
The Modbus master transmits a query telegram with a Modbus com-
mand to the Modbus slave (here, the IQ SENSORNET). The Modbus
slave transmits a response telegram with the requested data or an error
message.
Supported The IQ SENSORNET provides the data block for read access only. Writ-
Modbus commands ing Modbus commands are not carried out.
The following commands are available:
For a query of sensor data, determine the first register and the number
of registers to be read.
Determining the first The first register to be read depends on the sensor number (Sxx):
register to be read R = [(Sxx - 1) * 8] + 1.
Example: Determine the first register with data block for the sensor
S02:
R = [(2 - 1) * 8] + 1 = 9
The number of registers to be read for one sensor data block is 8 reg-
isters.
With one Modbus query, up to 125 registers (15 data blocks) can be
read.
40
IQ SENSORNET Fieldbus linking Communication with fieldbuses
The data block contains the data of the sensors in the order of their reg-
istering to the IQ SENSORNET (Sxx number).
ba76148e05 05/2017 41
Communication with fieldbuses IQ SENSORNET Fieldbus linking
Modbus Usually
Count start of the register 1 0
MSB* allocation of the register Bit 1 Bit 15
LSB* allocation of the register Bit 16 Bit 0
4.5.4 Example
Modbus response
Byte Value Information Meaning of the value
1 01h Modbus address of the 01h --> 1
IQ SENSORNET
42
IQ SENSORNET Fieldbus linking Communication with fieldbuses
Modbus response
Byte Value Information Meaning of the value
2 04h Function 04h --> 4
Read Input Register
3 10h Number of bytes 10h --> 16
16 bytes (8 registers)
4 02h Contents of register 9 02h (Int 8) --> 2
(HI) = sensor number Sensor number S02
5 02h Contents of register 9 02h (Int 8) --> MEASURE
(LO) = sensor status see section 5.2
6 04h Contents of register 10 0401h (Int 16)
(HI) = sensor model --> VisoTurb 700 IQ
see section 5.5
7 01h Contents of register 10
(LO) = sensor model
8 00h Contents of register 11 0000h (Int 16)
(HI) = status info --> no errors
see section 5.6
9 00h Contents of register 11
(LO) = status info
10 00h Contents of register 12 00h (Int 8) --> FNU Turb
(HI) = measuring see section 5.7
mode
11 14h Contents of register 12 14h (Int 8)
(LO) = measured Main measured value (bits
value status 7-4):
1h --> VALID
Secondary measured
value (bits 3-0):
4h --> MISSING
see section 5.3
ba76148e05 05/2017 43
Communication with fieldbuses IQ SENSORNET Fieldbus linking
Modbus response
Byte Value Information Meaning of the value
12 42h Contents of register 13
(HI) = main measured 429E46C2h (Float 32)
value --> 79,1382
Measured parameter and
13 9Eh Contents of register 13 unit,
(LO) = main measured see byte 10 (measuring
value mode)
14 46h Contents of register 14
(HI) = main measured
value
15 C2h Contents of register 14
(LO) = main measured
value
16 00h Contents of register 15
(HI) = secondary mea- 00000000h (Float 32)
sured value --> 0
but measured value invalid
17 00h Contents of register 15 (MISSING),
(LO) = secondary see byte 11 (measured
measured value value status)
18 00h Contents of register 16
(HI) = secondary mea-
sured value
19 00h Contents of register 16
(LO) = secondary
measured value
20 23h CRC (HI) Checksum (CRC)
21 5Eh CRC (LO)
44
IQ SENSORNET Fieldbus linking Encoded data for fieldbus communication
If not all of the bits of the exponent are 0, the value is calculated accord-
ing to:
If all of the bits of the exponent are 0, the value is calculated according
to:
A value is 0 if all the bits of both the exponent as well as the mantissa
are 0.
Evaluation Meaning
Measured value 0 Check the measured value status
Measured value <> 1 The measured value is invalid (error)
status
ba76148e05 05/2017 45
Encoded data for fieldbus communication IQ SENSORNET Fieldbus linking
Sensor model The data for the sensor model and status info is transmitted as INT16,
Status info i.e. consists of 2 bytes. The assignment is carried out in Motorola for-
(INT16) mat (the higher value byte first).
Measured value status The data for the measured value status of the main and secondary
(Int8) measured values are encoded jointly into a single byte. Bits 7-4 encode
the status of the main measured value, bits 3-0 encode the status of the
secondary measured value.
Other data (INT8) All other data always consist of only a single byte (Int8).
46
IQ SENSORNET Fieldbus linking Encoded data for fieldbus communication
The UNUSED_ID status also occurs when the fieldbus interface of the
IQ SENSORNET does not receive any data from the IQ SENSORNET
controller for more than 2 minutes. Possible cause: Communication
malfunction or controller failure. The data transmitted last remain fro-
zen for the two minutes delay time.
01h INACTIVE The sensor is currently inactive. The sensor number (ID) and respec-
tive setting dataset are available in the IQ SENSORNET system. The
sensor was removed from the IQ SENSORNET system or the commu-
nication does not work.
The measured value status of the main and secondary measured
value is MISSING (4h) (see section 5.3 MEASURED VALUE STATUS).
The measured value display on the terminal indicates Init or Error.
02h MEASURE The sensor is in measuring mode.
The measured value status can be VALID, OFL or INVALID.
The measured value display on the terminal indicates the valid mea-
sured value, OFL or "----" (invalid measured value).
For the measured value to be evaluated, e.g. by a superordinate con-
trol system, the sensor status and measured value status also have to
be taken into account together with the measured value (see also sec-
tion 5.3 MEASURED VALUE STATUS)
03h CALIBRATE The sensor is being calibrated. No measured value is available.
The measured value status of the main and secondary measured
value is MISSING (4h) (see section 5.3 MEASURED VALUE STATUS).
The measured value display on the terminal indicates Cal.
04h ERROR The sensor is in a serious error status.
ba76148e05 05/2017 47
Encoded data for fieldbus communication IQ SENSORNET Fieldbus linking
48
IQ SENSORNET Fieldbus linking Encoded data for fieldbus communication
- The combination of sensor status and measured value status is not possi-
ble
"..." Displayed text
UNUSED_ID 0 (zero)
INACTIVE
CALIBRATE For the measured value 0 (zero) to be evaluated by a superordinate con-
ERROR trol system, the measured value always has to be taken into account
MAINTENANCE together with the sensor status and measured value status.
ba76148e05 05/2017 49
Encoded data for fieldbus communication IQ SENSORNET Fieldbus linking
Code Model
0101h SensoLyt700IQ
0201h TetraCon700IQ
0301h TriOxmatic700IQ
0302h TriOxmatic701IQ
0303h TriOxmatic702IQ
0304h SC FDO 700 (FDO700IQ)
0305h SC FDO 701 (FDO700IQ)
0401h VisoTurb700IQ
0402h ViSolid700IQ
0501h AmmoLyt700IQ
0503h AmmoLyt+ (AmmoLyt+700IQ)
0907h AmmoLyt+K (AmmoLyt+700IQ)
0601h NitraLyt700IQ
0602h NitraLyt+ (NitraLyt+700IQ)
0701h NitraVis700/1IQ
0702h NitraVis700/5IQ
0703h CarboVis700/5IQ
0704h SolidVis700IQ (UV/VIS sensors with TSS option)
0705h NitraVis700/5IQ (NiCaVis700IQ)
0706h CarboVis700/5IQ (NiCaVis700IQ)
0707h CarboVis700/1IQ
0801h MIQ/IC2, current input 1
0802h MIQ/IC2, current input 2
0901h VARiON A (VARiON700IQ)
0902h VARiON N (VARiON700IQ)
0905h VARiON A (VARiON+700IQ)
0906h VARiON N (VARiON+700IQ)
50
IQ SENSORNET Fieldbus linking Encoded data for fieldbus communication
Code Model
0907h VARiON K (VARiON+700IQ)
0A01h NitraVis701 IQ (+ NiCaVis701IQ NI)
0A02h NitraVis705 IQ (+ NiCaVis705IQ + NiCaVis705IQ NI)
0A03h CarboVis701 IQ (+ NiCaVis701IQ NI)
0A04h CarboVis705 IQ (+ NiCaVis705IQ + NiCaVis705IQ NI)
0A05h UV701 IQ SAC
0A06h UV705 IQ SAC
0A07h SolidVis701 IQ (UV/VIS sensors with TSS option)
0A08h SolidVis705 IQ (UV/VIS sensors with TSS option)
0A09h UV701 IQ NOx
0A0A UV705 IQ NOx
0A1Ah Virtual N sensor - NitraVis701IQ NI
0A1Bh Virtual N sensor - NitraVis705IQ NI
0A1Ch Virtual C sensor 1 - CarboVis701 IQ
0A1Dh Virtual C sensor 2 - CarboVis701 IQ
0A1Eh Virtual C sensor 3 - CarboVis701 IQ
0A1Fh Virtual C sensor 4 - CarboVis701 IQ
0A20h Virtual C sensor 1 - CarboVis705 IQ
0A21h Virtual C sensor 2 - CarboVis705 IQ
0A22h Virtual C sensor 3 - CarboVis705 IQ
0A23h Virtual C sensor 4 - CarboVis705 IQ
0B01h P 700 IQ
0C01h IFL 700 IQ
0C02h IFL 701 IQ
ba76148e05 05/2017 51
Encoded data for fieldbus communication IQ SENSORNET Fieldbus linking
TriOxmatic702IQ - -
SC FDO 700 Measurement interfered - -
SC FDO 701 Measurement interfered - -
VisoTurb700IQ SensCheck: Sensor con- SensCheck: Ultra- -
taminated sound cleaning sys-
ViSolid700IQ tem has failed -
AmmoLyt700IQ - - -
AmmoLyt+ - - -
AmmoLyt+K - - -
NitraLyt700IQ - - -
NitraLyt+ - - -
NitraVis700/xIQ - - -
CarboVis700/xIQ - - -
SolidVis700IQ - - -
NitraVis70xIQ Component hardware Optical measuring -
defective xxx range exceeded
CarboVis70xIQ -
SolidVis70xIQ -
UV70x IQ SAC
UV70x IQ NOx
MIQ/IC2 - - -
* The SensLeck function is not available with the sea water model
(-SW variant)
52
IQ SENSORNET Fieldbus linking Encoded data for fieldbus communication
continued
Note
The status info must be evaluated for each bit individually.
ba76148e05 05/2017 53
Encoded data for fieldbus communication IQ SENSORNET Fieldbus linking
Code
Model 00h 01h 02h 03h 04h 05h 06h 07h 08h
SensoLyt700IQ pH mV
TriOxmatic700IQ mg/l % O2
TriOxmatic701IQ O2
TriOxmatic702IQ
SC FDO 700 mg/l % O2
SC FDO 701 O2
ViSolid700IQ g/l TSS % g/l TSS % g/l SiO2 % SiO2 g/l SiO2 % SiO2
(M11) TSS (M21) TSS (M11) (M11) (M21) (M21)
(M11) (M21)
AmmoLyt+K mg/l K mV
54
IQ SENSORNET Fieldbus linking Encoded data for fieldbus communication
Code
Model 00h 01h 02h 03h 04h 05h 06h 07h 08h
NitraVis700/xIQ mg/l mg/l mg/l
NitraVis70xIQ NO3-N NO3 NO3-N4
CarboVis700/xIQ mg/l mg/l mg/l mg/l mg/l Abs/m Abs/m mg/l UVT
CarboVis70xIQ CODto CODd TOC BOD DOC SACto SACds CSB4 2545
s
SolidVis700IQ (m)g/l
SolidVis70xIQ TSS 2
VARiON K mg/l K mV
IFL 70x IQ m
1
M1 = matrix type 1, M2 = matrix type 2
matrix types: see ViSolid 700 IQ sensor operating manual
2
The measurement unit depends on the settings of the main sensor
3
The measured parameter and measurement unit depend on the set-
tings of the display values (see MIQ/IC2 sensor operating manual).
4
Only xxxVis700/xIQ: Test measurement with standards
5
Only CarboVis70xIQ
ba76148e05 05/2017 55
What to do if ... IQ SENSORNET Fieldbus linking
6 What to do if ...
Here you will find causes and actions to take of errors con-
cerning the PROFIBUS and Modbus communication only.
General errors of the IQ SENSORNET system are dealt with
in the IQ SENSORNET system operating manual.
6.1 PROFIBUS
56
IQ SENSORNET Fieldbus linking What to do if ...
ba76148e05 05/2017 57
What to do if ... IQ SENSORNET Fieldbus linking
58
Field bus linking Contact Information
7 Contact Information
7.1 Ordering & Technical Support
Email: [email protected]
Internet: www.ysi.com
When returning a product for service, include the Product Return form
with cleaning certification. The form must be completely filled out for an
YSI Service Center to accept the instrument for service. The Product
Return form may be downloaded at www.ysi.com and clicking on the
‘Support‘ tab.
ba76148e05 05/2017 59
Contact Information Field bus linking
60 ba76148e05 05/2017
Xylem |'zīləm|
1) The tissue in plants that brings water upward from the roots;
2) a leading global water technology company.
YSI
1725 Brannum Lane
Yellow Springs, OH 45387
Tel: +1 937-767-7241; 800-765-4974
Fax: +1 937-767-1058
Email: [email protected]
Web: www.ysi.com
©Xylem Inc