Amps X 10 Bus1 (Nom. kV=20, Plot Ref.
kV=20)
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
1K 1K
FLA WC02-Q01 Cable1
500 ABB SACE PR112 500
o
Sensor = 4000 OCR HEDNO
300 LT Pickup = 0.93 (3720 Amps) CB3 300
Bus1
LT Band = 9
CB2
ST Pickup = 3.7 (14800 Amps) o
CA11-JA01-Q12
ST Band = 0.4 (I^x)t = IN OCR
100 T1 100
2.5 MVA
50 50
WC02-Q01
Bus2
30 30
T1
2.5 MVA (Secondary) 6 %Z
Delta-Wye Solid Grd
10 ANSI Curve Shift = 0.58 10
HEDNO - P
5 OC1 5
CT Ratio 100:1
3 3
IEC - C Extremely Inverse
Pickup = 1.875 (0.1 - 4 xCT Sec)
Time Dial = 0.25
Inst = 14 (0.1 - 40 xCT Sec)
1 1
Time Delay = 0.15 s
.5 ∆ 0.12 s .5
.3 CA11-JA01-Q12 - P .3
OC1
CT Ratio 100:1
IEC - Extremely Inverse
.1 Pickup = 0.9 (0.1 - 4 Sec - 1A) .1
Time Dial = 1.1 Inrush
Inst = 13 (0.1 - 35 Sec - 1A)
.05 .05
Time Delay = 0.1 s
HEDNO - 3P
.03 .03
CA11-JA01-Q12 - 3P
WC02-Q01 - 3P
.01 .01
.5 1 3 5 10 30 50 100 300 500 1K 3K 5K 10K
Amps X 10 Bus1 (Nom. kV=20, Plot Ref. kV=20)
.25 .5 1 3 5 10 30 50 100 300 500 1K 3K 5K
Amps X 1000 Bus2 (Nom. kV=0.4, Plot Ref. kV=0.4)
Proposed