Modul 6 Kanan LF Etap

The document is a Load Flow Report detailing the electrical parameters of various buses in a power system. It includes information on voltage levels, generation, load, and transformer data for each bus. The report is part of a study case labeled 'LF' and is dated August 5, 2024.

Uploaded by

roisgustidewa007
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views2 pages

Modul 6 Kanan LF Etap

The document is a Load Flow Report detailing the electrical parameters of various buses in a power system. It includes information on voltage levels, generation, load, and transformer data for each bus. The report is part of a study case labeled 'LF' and is dated August 5, 2024.

Uploaded by

roisgustidewa007
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

Project: ETAP Page: 1

Location: 19.0.1C Date: 08-05-2024

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: Deku Config.: Normal

LOAD FLOW REPORT

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

* Bus1 13.800 100.000 0.0 7.961 4.781 0.000 0.000 Bus2 7.961 4.781 388.5 85.7

Bus2 150.000 99.052 -0.9 0.000 0.000 0.000 0.000 Bus4 10.557 6.059 47.3 86.7

Bus6 -2.601 -1.442 11.6 87.5

Bus1 -7.955 -4.618 35.7 86.5

* Bus3 13.800 100.000 0.0 7.958 4.787 0.000 0.000 Bus4 7.958 4.787 388.5 85.7

Bus4 150.000 99.051 -0.9 0.000 0.000 0.000 0.000 Bus2 -10.556 -6.059 47.3 86.7

Bus7 -5.355 -3.174 24.2 86.0

Bus10 23.864 13.857 107.2 86.5

Bus3 -7.952 -4.623 35.7 86.5

* Bus5 13.800 100.000 0.0 7.962 4.780 0.000 0.000 Bus6 7.962 4.780 388.5 85.7

Bus6 150.000 99.052 -0.9 0.000 0.000 0.000 0.000 Bus2 2.601 1.442 11.6 87.5

Bus7 5.355 3.174 24.2 86.0

Bus5 -7.956 -4.616 35.7 86.5

Bus7 150.000 99.052 -0.9 0.000 0.000 0.000 0.000 Bus6 -5.355 -3.174 24.2 86.0

Bus4 5.355 3.174 24.2 86.0

Bus8 0.000 0.000 0.0 0.0

Bus8 20.000 99.052 -0.9 0.000 0.000 0.000 0.000 Bus7 0.000 0.000 0.0 0.0

Bus9 20.000 94.541 -5.4 0.000 0.000 0.000 0.000 Bus12 13.816 5.613 455.4 92.6

Bus14 0.343 0.151 11.4 91.5

Bus11 -14.158 -5.765 466.8 92.6

Bus10 20.000 94.596 -5.4 0.000 0.000 0.000 0.000 Bus11 14.168 5.765 466.8 92.6

Bus18 9.399 5.521 332.6 86.2

Bus20 0.194 0.115 6.9 86.0

Bus4 -23.760 -11.401 804.2 90.2

Bus11 20.000 94.541 -5.4 0.000 0.000 0.000 0.000 Bus10 -14.158 -5.765 466.8 92.6

Bus9 14.158 5.765 466.8 92.6

Bus12 20.000 61.448 3.4 0.000 0.000 8.193 4.930 Bus9 -8.316 -4.979 455.4 85.8

Bus13 0.123 0.049 6.2 92.9

Bus13 0.380 59.465 1.4 0.000 0.000 0.121 0.043 Bus12 -0.121 -0.043 328.7 94.1

Bus14 20.000 94.540 -5.4 0.000 0.000 0.000 0.000 Bus16 0.163 0.045 5.2 96.4

Bus9 -0.343 -0.151 11.4 91.5


Project: ETAP Page: 2

Location: 19.0.1C Date: 08-05-2024

Contract: SN:

Engineer: Revision: Base


Study Case: LF
Filename: Deku Config.: Normal

Bus Voltage Generation Load Load Flow XFMR


ID kV % Mag. Ang. MW Mvar MW Mvar ID MW Mvar Amp %PF %Tap

Bus15 0.179 0.106 6.4 86.0

Bus15 0.380 90.165 -7.9 0.000 0.000 0.175 0.094 Bus14 -0.175 -0.094 334.8 88.2

Bus16 20.000 94.540 -5.4 0.000 0.000 0.000 0.000 Bus14 -0.163 -0.045 5.2 96.4

Bus17 0.163 0.045 5.2 96.4

Bus17 0.380 91.966 -7.9 0.000 0.000 0.161 0.037 Bus16 -0.161 -0.037 272.4 97.5

Bus18 20.000 94.559 -5.4 0.000 0.000 9.071 5.474 Bus10 -9.394 -5.520 332.6 86.2

Bus19 0.323 0.046 10.0 99.0

Bus19 0.390 93.867 -6.7 0.000 0.000 0.322 0.038 Bus18 -0.322 -0.038 510.8 99.3

Bus20 20.000 94.595 -5.4 0.000 0.000 0.000 0.000 Bus10 -0.194 -0.115 6.9 86.0

Bus21 0.194 0.115 6.9 86.0

Bus21 0.380 89.872 -8.1 0.000 0.000 0.189 0.100 Bus20 -0.189 -0.100 361.7 88.3
* Indicates a voltage regulated bus ( voltage controlled or swing type machine connected to it)
# Indicates a bus with a load mismatch of more than 0.1 MVA