02 141 CFP 16 NZ Datasheet Rev C

The Notifier CFP-16 is a conventional fire alarm control panel designed for small to medium buildings, compliant with New Zealand standards. It features 8 zones expandable to 16, a user-friendly LCD display, and compatibility with various fire detection devices. The panel includes programmable outputs, an occupant warning system, and is available in different cabinet sizes with specific electrical specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
64 views2 pages

02 141 CFP 16 NZ Datasheet Rev C

The Notifier CFP-16 is a conventional fire alarm control panel designed for small to medium buildings, compliant with New Zealand standards. It features 8 zones expandable to 16, a user-friendly LCD display, and compatibility with various fire detection devices. The panel includes programmable outputs, an occupant warning system, and is available in different cabinet sizes with specific electrical specifications.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 2

CFP-16

Conventional Fire Alarm Control Panel

Conventional Fire Systems

GENERAL

The Notifier CFP-16 conventional fire control panel is designed


to be used as a component of a fire alarm control system.

The CFP-16 system is suitable for small to medium sized


buildings and is fully compliant with the New Zealand standard
NZS4512:2010 and New Zealand building code.

The standard panel is equipped with 8 Zones but may be


extended to 16 Zones by the addition of an 8 Zone expansion
module.

The CFP-16 is extremely flexible and can be programmed to


meet the demands of a wide variety of building types.

The CFP-16 panel is compatible with the Notifier range of


conventional heat detectors, manual call points and System
Sensor smoke detectors plus a variety of other conventional
fire detection products.
Initiating Device Circuits (Zones)
FEATURES
• 8 or 16 zone interface circuits
• 8 Zones - expandable to 16 Zones
• Compatible with SYSTEM SENSOR 100 series devices
• 2 x 40 character LCD display providing a simple user
(refer to CFP-16 manual for complete list of compatible
friendly interface
devices)
• 24 character plain English zone descriptor
• Smart menu driven display for clear annunciation, Notification Applicance Circuits (NACs)
simple interrogation, configuration and control
• Flexible full featured programmability • Three independently programmable output circuits
• Each zone can be configured for a range of different • All circuits are power-limited and supervised by 4k7
device type functions Ohm End of Line (EOL) resistor.
• Each output can be programmed for different functional • Up to 1A power per NAC
and cause & effect requirements
• Compact 5.6 or 11 Amp system power supply and Auxiliary Outputs
charger
• Inbuilt programmable Occupant Warning System 30, • Three independently programmable relay outputs,
60 or 120 Watts preconfigured for Alarm, Fault (normally energized)
• Optional 8 way programmable relay modules and Disable.
• Optional OWS control, display and microphone module • Auxiliary power output (internal only).
• Front or Rear service options • One Door Holder output circuit, fused at 3A.
• Two cabinet sizes 650 mm and 900 mm
• ACM-ZM - LED Zone mimic interface module NOTE: The total power requirement of the FACP and any additional
• Remote slim LED mimic options (425mm or 900mm) NAC and Auxiliary outputs must not exceed the capacity of the
installed power supply system.

DOC-02-141:rev C - Page 1 of 2
PRODUCT LINE INFORMATION Electrical Specifications

FG-32-001 - CFP-16/650-8Z-PS5: CFP-16 Base Panel 650mm cab, 8 AC Power: NPS-5 fitted: 240vac, 0.8A, 50Hz. NPS-11 fitted: 240vac,
Zone, 5A PSU (Including: EBCO switches, Door switch and ACM-ZM 1.5A, 50Hz. Input Fuse: M205 8.0A, 250V.
8 Zone mimic interface Module)
Current Draw: Quiescent: 100mA, Defect: 110mA, Alarm: 240mA (for
FG-32-002 - CFP-16/900-8Z-PS5: CFP-16 Base Panel 900mm cab, 8 8 zone panel)
Zone, 5A PSU (Including: EBCO switches, Door switch and ACM-ZM
8 Zone mimic interface Module) Battery: Two 12V Sealed lead Acid batteries. Battery charger capacity:
7AH-85AH (CAB650 and CAB900 enclosures hold maximum of two
FG-32-003 - CFP-16/650-8Z-PS11: CFP-16 Base Panel 650mm cab, 33AH batteries)
8 Zone, 11A PSU (Including: EBCO switches, Door switch and ACM-
ZM 8 Zone mimic interface Module) Initiating Device Circuits: Power-limited, supervised circuit. End-of-
Line Resistor: 4k7 ohm, ½ watt.
FG-32-004 - CFP-16/900-8Z-PS11: CFP-16 Base Panel 900mm cab,
8 Zone, 11A PSU (Including: EBCO switches, Door switch and ACM- Notification Appliance Circuits: Power-limited, supervised circuit.
ZM 8 Zone mimic interface Module) Maximum current per circuit: 1.0A. End-of-Line Resistor: 4k7 ohm,
½ watt.
FG-72-021 - NZ Acrylic (FS) kit: inc Annun.Plates CAB650 (CFP-16)
Programmable Relays: Contact Rating: 1.0A @ 30V DC (resistive)
FG-72-022 - NZ Acrylic (FS) kit: inc Annun.Plates CAB900 (CFP-16)
Door Holder Output: Powered output protected by automotive fuse.
FG-72-026 - CAB650 Rear Service Mimic Surround Kit Rating: 3.0A @ 30V DC (resistive)

FG-72-027 - CAB900 Rear Service Mimic Surround Kit Auxiliary Power (internal only): 24VDC power limited output for
auxiliary devices installed within enclosure.
ASY-01-039 - ZEM-8: Eight zone expansion module; to expand from
Cabinet Specifications
8 to 16 zones

CAB650: 650mm(h) x 450mm(w) x 190mm(d)


ASY-02-022 - ACM-8RA: Relay module which provides eight
individually configurable (C/NO/NC) relay contacts.
CAB900: 900mm(h) x 450mm(w) x 190mm(d)

ASY-01-026 - AEM-ZM: IFS-721 8 zone mimic expansion card


CAB650/BB: 300mm(h) x 450mm(w) x 190mm(d)

ASY-01-048 - SGD: SGD interface to suit CFP-16NZ


Material: 1.2mm Zinc Sealed Steel

ASY-01-043 - ANP: Annuciator name plate


All cabinets are powder-coated charcoal texture. Dulux code: 88351

For further variants please contact your nearest Notifier Sales Office. Temperature And Humidity

This system has been certified for operation at 0o to 55oC and at a


SPECIFICATIONS relative humidity 10% to 93%

System Capacity
AGENCY LISTINGS AND APPROVALS
• Initiating device circuits (zones) . . . . . . . . 8 or 16
• ACM-ZM . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Certified to NZS4512:2010
• ACM-8RA . . . . . . . . . . . . . . . . . . . . . . . . . 28 FPA Register # NI/102
• Expansion modules (total) . . . . . . . . . . . . 32

This document is not intended for installation purposes. We try to


For more information please contact your
keep our product information up-to-date and accurate. We cannot
nearest Notifier Office or Distributor
cover all specific applications or anticipate all requirements. All
specifications are subject to change without notice.
www.notifier.com.au | www.notifier.co.nz
ISO9001
FS 520324
© 2014 Honeywell Ltd
ENGINEERING & MANUFACTURING

QUALITY SYSTEMS

DOC-02-141:rev C - Page 2 of 2