0% found this document useful (0 votes)
72 views5 pages

1.25 MW GTP - Medha

The Medha Solar Central Inverter model MCI-0760-10-1000kW/1250kW features a rated power of 1000kW with a maximum DC voltage of 1000V and an efficiency of 98.88%. It includes advanced protection mechanisms, a user-friendly interface, and enhanced technology for optimal performance in various environmental conditions. The inverter is designed for long service life, with a warranty of up to 10 years and a service life of 25 years.

Uploaded by

Markelytics
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
72 views5 pages

1.25 MW GTP - Medha

The Medha Solar Central Inverter model MCI-0760-10-1000kW/1250kW features a rated power of 1000kW with a maximum DC voltage of 1000V and an efficiency of 98.88%. It includes advanced protection mechanisms, a user-friendly interface, and enhanced technology for optimal performance in various environmental conditions. The inverter is designed for long service life, with a warranty of up to 10 years and a service life of 25 years.

Uploaded by

Markelytics
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 5

Medha Solar Central Inverter

1. General Typical Parameters

Model: MCI-0760-10-1000kW/1250kW
S.No Description Units Value/Remarks
1 Rating of Inverter kW 1000 1250
A. DC Parameters
1 Max. DC voltage V 1000
2 Voltage Operating Range V 550-950 640-950
3 MPPT voltage range V 550-850 640-850
4 DC start voltage V 575 640
5 Max. Recommended PV Power kWp 1250 1562
6 No. of MPPT trackers NUM 1 1
7 Maximum MPPT power kWp 1215 1410
8 MPPT Efficiency % >99.9 >99.9
9 Max Operating DC current A 2050 2050
10 Max Short Circuit DC current A 2600 2600
11 Maximum Inverter backfeed A < 3200 < 3200
current to the array
12 Maximum number of Protected 12 12
DC Inputs
13 DC connection type Through cables with Lug fixing, Bolt & nut
type
B. AC Parameters
1 Rated AC power (Cos Φ =0.95, kVA 1000 1316
Ambient = 50°C)
2 Rated AC power (Cos Φ =0.95, kVA 1197 1387
Ambient = 40°C)
3 Rated power factor at rated >0.99/ Adjustable from 0.8 Lead to 0.8 Lagg
power / Displacement factor
adjustable range
4 Rated AC Voltage V 380 440
5 AC Voltage range V 380 (+10% , -15%) 440 (+10% , -15%)
6 Rated frequency / frequency Hz 50 ± 5%
range
7 Rated AC current A 1520 1726
@ Ambient = 50°C

1 of 5 Medha Servo Drives Pvt. Ltd, Hyderabad


Medha Solar Central Inverter
Model: MCI-0760-10-1000kW/1250kW
8 Rated AC current A 1820 1820
@ Ambient = 40°C
9 AC Current (In rush) A < 400A, 100msec < 600A, 100msec
10 Maximum output fault current A 3200A, 250uSec
11 Maximum output over current A 2850A, <250uSec
protection
12 Max. distortion factor THD at % <3%
rated power conditions
13 DC current Injection % < 0.5%
14 Grid Feeding off at kW 5
[Standby mode power]
15 AC connection type 3-phase, 3 wire
Through cables with Lug fixing, Bolt & nut
type
Transformer less design.
16 Distribution Network type TN (Source side) - IT/Grounded (Inverter side)
(Inverter can be floating or Grounded system)
C. PROTECTION
1 Input side Disconnection device DC contactor
2 Output side Disconnection AC Circuit Breaker
device
3 Over voltage category DC: Class-II
AC: Class-III
4 Anti islanding - loss of mains Yes
5 DC reverse polarity protection Yes

6 AC and DC short circuit and Yes


over load protection
7 AC and DC Surge Protection Yes
(DC-Side Type-I,
AC-Side- Type-II )
8 AC over and under voltage Yes
protection
9 DC over voltage protection Yes
10 Earth fault protection Yes
11 Insulation monitoring and Yes
protection

2 of 5 Medha Servo Drives Pvt. Ltd, Hyderabad


Medha Solar Central Inverter
Model: MCI-0760-10-1000kW/1250kW
12 Ground Fault monitoring and Yes
protection
13 Monitoring of dc current Yes
injection into grid
14 AC Over/Under frequency Yes
protection
15 Imbalance/Negative sequence Yes
protection
16 Loss of synchronisation Yes
17 Over Temperature Yes
18 Cooling Failure Yes
D. Operating Performance
1 Maximum Efficiency (Excluding % 98.88%
Auxiliary Supply)
2 Weighted Efficiency % 98.71% / 98.76%
EURO/CEC(Excluded Auxiliary
for both parameters)
3 MPPT Efficiency % 99.9%
4 Auxilliary Power Consumption W <2900W
5 Night mode power consumption W <100W
E. Environmental Data
1 Installation Indoor
2 Ambient temperature range -25°C to 60°C
3 Pollution Degree II
4 Relative humidity 0 to 95% Non-condensing
5 Maximum altitude 2000m (above mean sea level)
>2000m(With Power deration)
6 Maximum Noise Emission <85 dB(A) 1m away from unit
F. Mechanical
1 Dimensions (H x W x D) (in 2000 x3200x 657
mm)
2 Degree of protection IP20
3 Cooling Method Forced Air cooled based on Temperature
4 Fresh Air consumption 2880 CMH

3 of 5 Medha Servo Drives Pvt. Ltd, Hyderabad


Medha Solar Central Inverter
Model: MCI-0760-10-1000kW/1250kW
5 Weight <1710 kg
6 Mounting system On concrete base
7 DC side Termination Al. Busbar with Ø17 hole, Gland plate 5mm
8 AC side Termination Al. Busbar with Ø17 hole, 7 per phase, Gland plate
5mm
G. User interface and communications
1 Local user interface 128 x 64 dot matrix User Interactive LCD and keypad
2 Field bus connectivity Ethernet
H. Compliance
1 Efficiency Measurements IEC61683:First Edition,1999-11
2 Environmental Testing IEC 60068-2-1 Cold test, -2-2 Dry Heat Test, -2-14
Change of Temperature, -2-30 Damp Heat Cycle Test
3 Electromagnetic Compatibility IEC 61000-6
(EMC)
4 Electrical Safety IEC62109-1:Edition 1.0,2010-04 and
IEC62109-2 :Edition-1,2011-06
5 Protection against Islanding of IEC61727:Edition2,2004-12 and IEEE 1547.1
Grid
6 Photovoltaic (PV) Systems IEC61727:Edition2,2004-12
Characteristics of the utility
Interface

2. Key Features:

Better User interface /Smart user interface


• Monitoring of system parameters through 128 x 64 dot matrix User Interactive Display and
user configuration, faults, data download through Ethernet using PC based application
software
• Ethernet system for interfacing the web-based monitoring system
• 30days Internal memory of data and fault information with associated data packs for the
triggered event

Enhanced Technology
• Three level topology provides highest efficiency over wide operation range
• Configurable reactive and power factor adjustment
• Grid side fault monitoring and support (LHVRT, anti-islanding, reactive power control,
LHFRT, configurable power factor option)
• Supports the grid during the unbalanced grid voltages, and allows upto some rated

4 of 5 Medha Servo Drives Pvt. Ltd, Hyderabad


Medha Solar Central Inverter
imbalance in the grid voltages. This value can be user settable.
• Integrated feeding grid current Lower Harmonic control algorithm

Enhanced Yield and Availability


• 5 Years warranty, optionally extended upto 10 years, Service life of the inverters shall be 25
years.
• Highest efficiency of 98.88% with Euro/CEC efficiency of 98.71% / 98.76%
• Wide operating Temperature range.
• Optimized cooling fan control for energy savings as well as longer fan life
• Power Regulation during Thermal Overloading

Enhanced Features/Additional Features

• DC insulation monitoring and protection


• Low harmonic grid current output
• Input and output isolation through automatic control of contactor and ACB through control
computer respectively.
• Automatic wakeup and sleep mode operation

3. General Arrangement Drawing

5 of 5 Medha Servo Drives Pvt. Ltd, Hyderabad