0% found this document useful (0 votes)
4 views147 pages

Statement of Requirements: Technical Specifications and Compliance Data Sheet

The document outlines the technical specifications and requirements for the supply, installation, testing, and commissioning of a solar PV system at Aksum University, Ethiopia. It emphasizes the government's commitment to renewable energy and reducing reliance on fossil fuels, detailing the scope of work, equipment needed, and training for local technicians. The document includes specific power requirements, equipment descriptions, and compliance standards necessary for the project.

Uploaded by

Samuel Tesfay
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views147 pages

Statement of Requirements: Technical Specifications and Compliance Data Sheet

The document outlines the technical specifications and requirements for the supply, installation, testing, and commissioning of a solar PV system at Aksum University, Ethiopia. It emphasizes the government's commitment to renewable energy and reducing reliance on fossil fuels, detailing the scope of work, equipment needed, and training for local technicians. The document includes specific power requirements, equipment descriptions, and compliance standards necessary for the project.

Uploaded by

Samuel Tesfay
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 147

Statement of Requirements

TECHNICAL SPECIFICATIONS AND COMPLIANCE DATA SHEET


Procurement Reference Number: _________________

Project title: - Supply, Installation, testing and commissioning of solar PV System for Aksum university.

1. Introduction and Briefings (General)


The Government of Ethiopia is giving high priority to promote renewable energy access for modern energy, protecting deforestation for energy and
lighting use, and moderating its economy from increasing volatility in the international fuel markets. Actions aimed at reducing dependency on
imported fossil fuel will also help decrease greenhouse gas (GHG) emissions, and on the road of a sustainable and exemplary development.

The overall objective of the promotion of the use of renewable energy resources through the implementation of cost effective, equitable, reliable,
accessible, affordable, secure and environmentally sustainable energy resource. In this particular bid, the implementation of supply and installation
of Photovoltaic Solar Power System (solar power generator) and other related services, including all related items, spares and accessories for Aksum
university seen as a step towards achieving the above objective.

2. Scope of Work

Equipment for electric generation from solar (PV system) and others related are request for the implementation of the desired application and services
in Aksum University. The requested equipment shall be supplied, installed, tested and commissioned.

In addition to supply, installation, test and commissioning, the successful bidder shall provide training to the local technicians and operators in charge
of operation & maintenance (O&M) including user manuals.

1|Page
3. LOT ONE: Supply, Installation, testing and commissioning of Solar PV system
3.1. Total power and daily energy consumption for main campus

Building/ Load Power(KW) Energy(KWH)

Baking Oven 50 300

Block-26 35.844 240.214

Registrar 38.090 264.790

ICT (HUAWEI) Data Center 164.544 987.264

ICT (Main) Data Center 194.225 1,160.670

Digital Library main campus 100 600

Total 582.703 3,552.938

N.B. Since the system is a hybrid solar system and the price of the battery is expensive, the system must work with battery mode for a few hours. During
day time (sunshine hour) the system will use from PV; during cloud or night time, if there is a grid, it will use from a grid, but (in worst scenario) if there
is no grid, it will use from battery. The backup batteries can support the load for 1 hour for buildings (Baking Oven, Block-26, Registrar, Digital Library),
and 2 hours for buildings (ICT (HUAWEI) Data Center, ICT (Main) Data Center) when their loads are operating at maximum power.

 Use peak sun hour (PSH) = 6hrs.


 Use safety factor for inverter = 1.3
 Please note that the design and installation for each building must be independent.

2|Page
Supply, Installation, testing and commissioning of solar PV System for main campus

No Items Name Items with their description (detail Standards Unit Qty Unit Total price
specification ) price
1. Baking Oven
1.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5
(Monocrystalline 1000w/m2 @ 250c
Solar Module half-  Type: Monocrystalline silicon, half-
cell) cell,
 Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V IEC 61215,
 Short-circuit current (Isc): 13.98A IEC 61730 pcs
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters
 Operational temperatures: -400c - +
850c or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized

3|Page
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy
frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc:
+0.048% / °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a
speed of 23m/s
Warranty=5 years
With all accessories
1.2 DC circuit combiner board with all necessary safety and protection IEC 60950- Set
devices 1, EN
60950-1
1.3 Mounting racks for Adjustable Aluminum Alloy 6000 Series or ISO Set
PV module array
Galvanized steel Waterproof mounting 9001/SGS/
Rack including support frame with at least CE/ISO450
four tamper-proof fasteners; with complete 01
set of stainless screw, bolt & nut. Rack
frames should be able to hold all PV arrays
and should resist any movement.

4|Page
Warranty : 15 Years
With all accessories

1.4 Three phase hybrid PV string input data


solar inverter(built in  Maximum PV input power (W):
MPPT charge 45,500W
controller), high  Maximum PV input voltage (V):
voltage battery 1000V
supported  Start-up Voltage (V): 180V
 MPPT voltage range (V): 150- 850 IEC 61727, Pcs
 Rated PV input voltage (V): 600 IEC 62116,
 Maximum operating PV input current EN 50549,
(A): 36+36+ 36 IEC/EN
61000-6-
 Max. Input Short-Circuit Current (A):
1/2/3/4,
55+55+55
IEC/EN
 No. of MPP Trackers/No. of Strings
62109-1,
per MPP Tracker: 3/2+2+2
IEC/EN
Battery input data
62109-2
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 +
50
 Maximum discharging current (A):
50+ 50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active
Power(W): 35,000
 Max. AC Input/output Apparent
Power(VA): 38,000
 Rated AC Input/output Current(A):
53.1/50.8

5|Page
 Max. AC Input/output Current(A):
58.4/55.8
 Max. Three-phase Unbalanced Output
Current (A): 60
 Max. Continuous AC Pass through
(grid to load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion
THDi: <3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: >= 97.0%
 MPPT Efficiency: >= 99%
Equipment Protection
Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
6|Page
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support multiple batteries parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)
7|Page
 Cabinet Size (WxHxD mm): less than
or equal to 527×894×294(Excluding
Connectors and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
1.5 High voltage LiFePO4 Main Parameter
battery  Battery Type : LiFePO4(LFP)
 Nominal Voltage: 51.2Vdc
 Rated Capacity: 100Ah
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current : UN38.3/C Pcs
100A E/
 Peak. Discharge Current:125A CE-EMC/
 DOD=90%, 0.3C charging and IEC/62040
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power
On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
8|Page
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
1.6 High Voltage Battery Operating Voltage: 120-1000Vdc
cluster control box Nominal Charge/Discharge Current: 100A
with all accessory Maximum Charge/Discharge Current:
125A UN38.3/C
DC Input Rating: 12±2%V/4.15A E/ Pcs
Operating Temperature Range: -20~65°C CE-EMC/
or higher IEC/62040
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
1.7 Battery Cabinet with all accessories UL 9540 Pcs
1.8 Earthing for PV Solar Earthing system must be separated of the Set
System: main earthing system to obtain 2-ohm max
resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with IEC/EN
cast iron cover (5 Ton) with hinge, earth 61000-6-
joints, clamps, ducts, conduits and 50 1/2/3/4
mm2 flexible earthing copper wires and
cables from the PV system components
and steel structure to the electrode to
complete the system as specifications,
drawings and as per the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV
panels.For steel structure 16mm2 flexible
9|Page
earthing copper wires shall be from 3 different
points in each string.
With all accessories
1.9 Cables and connectors required to wire the whole system as the wire IEC 60228 Meter
size and quantity difference depending the connection point UL 44
1.10 Document Preparation (design, manual and installation drawing )
1.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel (if
necessary).
1.12 If any
2. Block 26
2.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5
(Monocrystalline 1000w/m2 @ 250c
Solar Module half-  Type: Monocrystalline silicon, half-cell
cell)  Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95 IEC 61215, Pcs
V IEC 61730
 Maximum power current (Imp):
13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters
 Operational temperatures: -400c - +
850c or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
10 | P a g e
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy
frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc:
+0.048% / °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a
speed of 23m/s
Warranty=5 years
With all accessories
2.2 DC circuit combiner board with all necessary safety and protection IEC 60950- Set
devices 1, EN
60950-1
2.3 Mounting racks for Adjustable Aluminum Alloy 6000 Series or ISO Set
PV module array
Galvanized steel Waterproof mounting 9001/SGS/
Rack including support frame with at least CE/ISO450
four tamper-proof fasteners; with complete 01
set of stainless screw, bolt & nut. Rack

11 | P a g e
frames should be able to hold all PV arrays
and should resist any movement.
Warranty : 15 Years
With all accessories
2.4 Three phase hybrid PV string input data
solar inverter(built in  Maximum PV input power (W):
MPPT charge 65,000W
controller), high  Maximum PV input voltage(V): IEC 61727,
voltage battery 1000V IEC 62116, Pcs
supported  Start-up Voltage (V): 180V EN 50549,
 MPPT voltage range (V): 150- 850 IEC/EN
 Rated PV input voltage (V): 600 61000-6-
 Maximum operating PV input current 1/2/3/4,
(A): 36+36+ 36+36 IEC/EN
62109-1,
 Max. Input Short-Circuit Current (A):
IEC/EN
55+55+55+55
62109-2
 No. of MPP Trackers/No. of Strings
per MPP Tracker: 4/2+2+2+2
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 +
50
 Maximum discharging current (A):
50+ 50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active
Power(W): 50,000
 Max. AC Input/output Apparent
Power(VA): 55,000

12 | P a g e
 Rated AC Input/output Current(A):
75.8/72.5
 Max. AC Input/output Current(A):
83.4/79.8
 Max. Three-phase Unbalanced Output
Current (A): 83.4
 Max. Continuous AC Pass through
(grid to load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion
THDi: less than or equal to 3% (of
nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: ≥ 99%
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
13 | P a g e
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher
efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
14 | P a g e
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC
II(DC), OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
527×894×294(Excluding Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
2.5 High voltage LiFePO4 Main Parameter
battery  Battery Type : LiFePO4(LFP)
 Nominal Voltage: 51.2Vdc
 Rated Capacity: 100Ah
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current :
100A
 Peak. Discharge Current:125A UN38.3/C Pcs
E/
 DOD=90%, 0.3C charging and
discharging@ 250c CE-EMC/
IEC/62040
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power
On
15 | P a g e
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle-Life:25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
2.6 High Voltage Battery Operating Voltage: 120-1000Vdc UN38.3/C Pcs
cluster control box Nominal Charge/Discharge Current: 100A E/
with all accessory Maximum Charge/Discharge Current: CE-EMC/
125A IEC/62040
DC Input Rating: 12±2%V/4.15A
Operating Temperature Range: -20~65°C
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
2.7 Battery Cabinet with all accessories UL 9540 Pcs
2.8 Earthing for PV Solar Earthing system must be separated of the set
System: main earthing system to obtain 2-ohm
max resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with IEC/EN
cast iron cover (5 Ton) with hinge, earth 61000-6-
joints, clamps, ducts, conduits and 50 1/2/3/4
mm2 flexible earthing copper wires and
cables from the PV system components
and steel structure to the electrode to
16 | P a g e
complete the system as specifications,
drawings and as per the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV
panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points in
each string.
With all accessories
2.9 Cables and connectors required to wire the whole system as the wire IEC 60228 Meter
size and quantity difference depending the connection point UL 44
2.10 Document Preparation (design, manual and installation drawing )
2.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel (if
necessary).
2.12 If any
3. Registrar
3.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215, Pcs
(Monocrystalline 1000w/m2 @ 250c IEC 61730
Solar Module half-  Type: Monocrystalline silicon, half-cell
cell)  Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp):
13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters
 Operational temperatures: -400c - +
850c or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher

17 | P a g e
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy
frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc:
+0.048% / °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a
speed of 23m/s
Warranty=5 years
With all accessories
3.2 DC circuit combiner board with all necessary safety and protection IEC 60950- Set
devices 1, EN
60950-1

18 | P a g e
3.3 Mounting racks for Adjustable Aluminum Alloy 6000 Series or ISO Set
PV module array
Galvanized steel Waterproof mounting 9001/SGS/
Rack including support frame with at least CE/ISO450
four tamper-proof fasteners; with complete 01
set of stainless screw, bolt & nut. Rack
frames should be able to hold all PV arrays
and should resist any movement.
Warranty : 15 Years
With all accessories
3.4 Three phase hybrid PV string input data IEC 61727, Pcs
solar inverter(built in  Maximum PV input power (W): IEC 62116,
MPPT charge 65,000W EN 50549,
controller), high  Maximum PV input voltage (V): IEC/EN
voltage battery 1000V 61000-6-
supported  Start-up Voltage (V): 180V 1/2/3/4,
 MPPT voltage range (V): 150- 850 IEC/EN
 Rated PV input voltage (V): 600 62109-1,
 Maximum operating PV input current IEC/EN
(A): 36+36+ 36+36 62109-2
 Max. Input Short-Circuit Current (A):
55+55+55+55
 No. of MPP Trackers/No. of Strings
per MPP Tracker: 4/2+2+2+2
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 +
50
 Maximum discharging current (A):
50+ 50
 Charging strategy for LiFePo4: self-
adaption to BMS
19 | P a g e
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active
Power(W): 50,000
 Max. AC Input/output Apparent
Power(VA): 55,000
 Rated AC Input/output Current(A):
75.8/72.5
 Max. AC Input/output Current(A):
83.4/79.8
 Max. Three-phase Unbalanced Output
Current (A): 83.4
 Max. Continuous AC Pass through
(grid to load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion
THDi: less than or equal to 3% (of
nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99%
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
20 | P a g e
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher
efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
21 | P a g e
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC
II(DC), OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
527×894×294(Excluding Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
3.5 High voltage LiFePO4 Main Parameter UN38.3/C Pcs
battery  Battery Type : LiFePO4(LFP) E/
 Nominal Voltage: 51.2Vdc CE-EMC/
 Rated Capacity: 100Ah IEC/62040
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current :
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20

22 | P a g e
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power
On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
3.6 High Voltage Battery Operating Voltage: 120-1000Vdc UN38.3/C Pcs
cluster control box Nominal Charge/Discharge Current: 100A E/
with all accessory Maximum Charge/Discharge Current: CE-EMC/
125A IEC/62040
DC Input Rating: 12±2%V/4.15A
Operating Temperature Range: -20~65°C
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: 17kg
Warranty: 5 years
With all accessories
3.7 Battery Cabinet With all accessories UL 9540 Pcs
3.8 Earthing for PV Solar Earthing system must be separated of the set
System: main earthing system to obtain 2-ohm
max resistance.

23 | P a g e
The item includes (3copper electrodes
15mm2 driven into ground, manholes with IEC/EN
cast iron cover (5 Ton) with hinge, earth 61000-6-
joints, clamps, ducts, conduits and 50 1/2/3/4
mm2 flexible earthing copper wires and
cables from the PV system components
and steel structure to the electrode to
complete the system as specifications,
drawings and as per the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV
panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points in
each string.
With all accessories
3.9 Cables and connectors required to wire the whole system as the wire IEC 60228 Meter
size and quantity difference depending the connection point UL 44
3.10 Document Preparation (design, manual and installation drawing )
3.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel (if
necessary).
3.12 If any
4. ICT (HUAWEI) Data Center
4.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215, Pcs
(Monocrystalline 1000w/m2 @ 250c IEC 61730
Solar Module half-  Type: Monocrystalline silicon, half-cell
cell)  Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp):
13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters

24 | P a g e
 Operational temperatures: -400c - +
850c or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy
frame
 Dimensions: 2256 x 1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc:
+0.048% / °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a
speed of 23m/s
25 | P a g e
Warranty=5 years
With all accessories
4.2 DC circuit combiner board with all necessary safety and protection IEC 60950- Set
devices 1, EN
60950-1
4.3 Mounting racks for Adjustable Aluminum Alloy 6000 Series or ISO Set
PV module array
Galvanized steel Waterproof mounting 9001/SGS/
Rack including support frame with at least CE/ISO450
four tamper-proof fasteners; with complete 01
set of stainless screw, bolt & nut. Rack
frames should be able to hold all PV arrays
and should resist any movement.
Warranty : 15 Years
With all accessories
4.4 Three phase hybrid PV string input data IEC 61727, Pcs
solar inverter(built in  Maximum PV input power (W): IEC 62116,
MPPT charge 65,000W EN 50549,
controller), high  Maximum PV input voltage (V): IEC/EN
voltage battery 1000V 61000-6-
supported  Start-up Voltage (V): 180V 1/2/3/4,
 MPPT voltage range (V): 150- 850 IEC/EN
 Rated PV input voltage (V): 600 62109-1,
 Maximum operating PV input current IEC/EN
(A): 36+36+ 36+36 62109-2
 Max. Input Short-Circuit Current (A):
55+55+55+55
 No. of MPP Trackers/No. of Strings
per MPP Tracker: 4/2+2+2+2
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 160-800

26 | P a g e
 Maximum charging current (A): 50 +
50
 Maximum discharging current (A):
50+ 50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active
Power(W): 50,000
 Max. AC Input/output Apparent
Power(VA): 55,000
 Rated AC Input/output Current(A):
75.8/72.5
 Max. AC Input/output Current(A):
83.4/79.8
 Max. Three-phase Unbalanced Output
Current (A): 83.4
 Max. Continuous AC Pass through
(grid to load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion
THDi: less than or equal to 3% (of
nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
27 | P a g e
 MPPT Efficiency: ≥99%
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
28 | P a g e
 High voltage battery, higher
efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC
II(DC), OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
527×894×294(Excluding Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
4.5 High voltage LiFePO4 Main Parameter UN38.3/C Pcs
battery  Battery Type : LiFePO4(LFP) E/
 Nominal Voltage: 51.2Vdc CE-EMC/
 Rated Capacity: 100Ah IEC/62040
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current :
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
29 | P a g e
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power
On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
4.6 High Voltage Battery Operating Voltage: 120-1000Vdc UN38.3/C Pcs
cluster control box Nominal Charge/Discharge Current: 100A E/
with all accessory Maximum Charge/Discharge Current: CE-EMC/
125A IEC/62040
DC Input Rating: 12±2%V/4.15A
Operating Temperature Range: -20~65°C
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: 17kg
Warranty: 5 years

30 | P a g e
With all accessories
4.7 Battery Cabinet With all accessories UL 9540 Pcs
4.8 Earthing for PV Solar Earthing system must be separated of the set
System: main earthing system to obtain 2-ohm max
resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with IEC/EN
cast iron cover (5 Ton) with hinge, earth 61000-6-
joints, clamps, ducts, conduits and 50 1/2/3/4
mm2 flexible earthing copper wires and
cables from the PV system components
and steel structure to the electrode to
complete the system as specifications,
drawings and as per the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV
panels.For steel structure 16mm2 flexible
earthing copper wires shall be from 3
different points in each string.
With all accessories
4.9 Cables and connectors required to wire the whole system as the wire IEC 60228 Meter
size and quantity difference depending the connection point UL 44
4.10 Document Preparation (design, manual and installation drawing )
4.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel (if
necessary).
4.12 If any
5. ICT (Main) Data Center
5.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215, Pcs
(Monocrystalline 1000w/m2 @ 250c IEC 61730
Solar Module half-  Type: Monocrystalline silicon, half-cell
cell)  Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V

31 | P a g e
 Maximum power current (Imp):
13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters
 Operational temperatures: -400c - +
850c or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy
frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc:
+0.048% / °C
32 | P a g e
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a
speed of 23m/s
Warranty=5 years
With all accessories
5.2 DC circuit combiner board with all necessary safety and protection IEC 60950- Set
devices 1, EN
60950-1
5.3 Mounting racks for Adjustable Aluminum Alloy 6000 Series or ISO Set
PV module array
Galvanized steel Waterproof mounting 9001/SGS/
Rack including support frame with at least CE/ISO450
four tamper-proof fasteners; with complete 01
set of stainless screw, bolt & nut. Rack
frames should be able to hold all PV arrays
and should resist any movement.
Warranty : 15 Years
With all accessories
5.4 Three phase hybrid PV string input data IEC 61727, Pcs
solar inverter(built in  Maximum PV input power (W): IEC 62116,
MPPT charge 65,000W EN 50549,
controller), high  Maximum PV input voltage (V): IEC/EN
voltage battery 1000V 61000-6-
supported  Start-up Voltage (V): 180V 1/2/3/4,
 MPPT voltage range (V): 150- 850 IEC/EN
 Rated PV input voltage (V): 600 62109-1,
 Maximum operating PV input current IEC/EN
(A): 36+36+ 36+36 62109-2
 Max. Input Short-Circuit Current (A):
55+55+55+55
33 | P a g e
 No. of MPP Trackers/No. of Strings
per MPP Tracker: 4/2+2+2+2
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 +
50
 Maximum discharging current (A):
50+ 50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active
Power(W): 50,000
 Max. AC Input/output Apparent
Power(VA): 55,000
 Rated AC Input/output Current(A):
75.8/72.5
 Max. AC Input/output Current(A):
83.4/79.8
 Max. Three-phase Unbalanced Output
Current (A): 83.4
 Max. Continuous AC Pass through
(grid to load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE

34 | P a g e
 Total Current Harmonic Distortion
THDi: less than or equal to 3% (of
nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99%
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase

35 | P a g e
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher
efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC
II(DC), OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
527×894×294(Excluding Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
5.5 High voltage LiFePO4 Main Parameter UN38.3/C Pcs
battery  Battery Type : LiFePO4(LFP) E/
 Nominal Voltage: 51.2Vdc
36 | P a g e
 Rated Capacity: 100Ah CE-EMC/
 Rated Energy : 5.12kWh IEC/62040
 Nominal Charge/Discharge Current :
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power
On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
5.6 High Voltage Battery Operating Voltage: 120-1000Vdc UN38.3/C Pcs
cluster control box Nominal Charge/Discharge Current: 100A E/
with all accessory Maximum Charge/Discharge Current: CE-EMC/
125A IEC/62040
37 | P a g e
DC Input Rating: 12±2%V/4.15A
Operating Temperature Range: -20~65°C
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
5.7 Battery Cabinet With all accessories UL 9540 Pcs
5.8 Earthing for PV Solar Earthing system must be separated of the Set
System: main earthing system to obtain 2-ohm
max resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with IEC/EN
cast iron cover (5 Ton) with hinge, earth 61000-6-
joints, clamps, ducts, conduits and 50 1/2/3/4
mm2 flexible earthing copper wires and
cables from the PV system components
and steel structure to the electrode to
complete the system as specifications,
drawings and as per the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV panels.
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points in
each string.
With all accessories
5.9 Cables and connectors required to wire the whole system as the wire IEC 60228 Meter
size and quantity difference depending the connection point UL 44
5.10 Document Preparation (design, manual and installation drawing )
5.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel (if
necessary).

38 | P a g e
5.12 If any
6. Digital Library @ main campus

6.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215, Pcs
(Monocrystalline 1000w/m2 @ 250c IEC 61730
Solar Module half-  Type: Monocrystalline silicon, half-cell
cell)  Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp):
13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters
 Operational temperatures: -400c - +
850c or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass

39 | P a g e
 Frame: Anodized aluminum alloy
frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc:
+0.048% / °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a
speed of 23m/s
Warranty=5 years
With all accessories

6.2 DC circuit combiner board with all necessary safety and protection IEC 60950- Set
devices 1, EN
60950-1
6.3 Mounting racks for Adjustable Aluminum Alloy 6000 Series or ISO Set
PV module array
Galvanized steel Waterproof mounting 9001/SGS/
Rack including support frame with at least CE/ISO450
four tamper-proof fasteners; with complete 01
set of stainless screw, bolt & nut. Rack
frames should be able to hold all PV arrays
and should resist any movement.
With all accessories

40 | P a g e
Warranty : 15 Years
6.4 Three phase hybrid PV string input data IEC 61727, Pcs
solar inverter(built in  Maximum PV input power (W): IEC 62116,
MPPT charge 65,000W EN 50549,
controller), high  Maximum PV input voltage (V): IEC/EN
voltage battery 1000V 61000-6-
supported  Start-up Voltage (V): 180V 1/2/3/4,
 MPPT voltage range (V): 150- 850 IEC/EN
 Rated PV input voltage (V): 600 62109-1,
 Maximum operating PV input current IEC/EN
(A): 36+36+ 36+36 62109-2
 Max. Input Short-Circuit Current (A):
55+55+55+55
 No. of MPP Trackers/No. of Strings
per MPP Tracker: 4/2+2+2+2
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 +
50
 Maximum discharging current (A):
50+ 50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active
Power(W): 50,000
 Max. AC Input/output Apparent
Power(VA): 55,000
 Rated AC Input/output Current(A):
75.8/72.5
 Max. AC Input/output Current(A):
83.4/79.8

41 | P a g e
 Max. Three-phase Unbalanced Output
Current (A): 83.4
 Max. Continuous AC Pass through
(grid to load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion
THDi: less than or equal to 3% (of
nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99%
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
42 | P a g e
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher
efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC
II(DC), OVC III(AC)
43 | P a g e
 Cabinet Size less than or equal to
(WxHxD mm):
527×894×294(Excluding Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories

6.5 High voltage LiFePO4 Main Parameter UN38.3/C Pcs


battery  Battery Type : LiFePO4(LFP) E/
 Nominal Voltage: 51.2Vdc CE-EMC/
 Rated Capacity: 100Ah IEC/62040
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current :
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power
On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
44 | P a g e
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
6.6 High Voltage Battery Operating Voltage: 120-1000Vdc UN38.3/C Pcs
cluster control box Nominal Charge/Discharge Current: 100A E/
with all accessory Maximum Charge/Discharge Current: CE-EMC/
125A IEC/62040
DC Input Rating: 12±2%V/4.15A
Operating Temperature Range: -20~65°C
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
6.7 Battery Cabinet with all accessory UL 9540 Pcs
6.8 Earthing for PV Solar Earthing system must be separated of the Set
System: main earthing system to obtain 2-ohm
max resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with IEC/EN
cast iron cover (5 Ton) with hinge, earth 61000-6-
joints, clamps, ducts, conduits and 50 1/2/3/4
mm2 flexible earthing copper wires and
cables from the PV system components
and steel structure to the electrode to
complete the system as specifications,
drawings and as per the approval.

45 | P a g e
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV
panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points in
each string.
With all accessories
6.9 Cables and connectors required to wire the whole system as the wire IEC 60228 Meter
size and quantity difference depending the connection point UL 44
6.10 Document Preparation (design, manual and installation drawing )
6.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel (if
necessary).
6.12 if any

Note
Any minor equipment and material may not be specifically mentioned in these specifications but the bidders are required to make the system complete in
a every respect in accordance with technical specification and the same shall be deemed to have been covered under the scope of these specifications and
shall be provided by the bidder / supplier within the quoted price.

46 | P a g e
3.2. Total power and daily energy consumption of referral hospital
Type of building Total power rate(kw) Total energy(kwh)

Pathology, ICU, OR and Labor 20 160


Rooms
Virology & NICU 20 160

Emergency/Laboratory/Imaging 20 160

Card room and Medical Management 5 40


Rooms
Drug room 5 40

Blood bank 20.166 125.59

Baking Oven 50 300

Total 140.166 985.59

N.B Since our system is a hybrid solar system and the price of battery is expensive the system must work with battery mode for a few hours. During day
time (sunshine hour) the system will use from PV: during cloud or night time, if there is a grid, it will use from a grid, but (in worst scenario) if there is
no grid it will use from battery. The backup batteries can support the load for 2 hours for building (Pathology/ICU/OR/Labor Rooms, Nicu/virology
Rooms, Emergency/Laboratory/Imaging, Card room/Medical Management Rooms, Drug room and blood bank) when their loads are operating at
maximum power. But for baking oven the backup batteries will support for 1hr when the load are operating at maximum power.

 Use peak sun hour (PSH) = 6hrs.


 Use safety factor for inverter = 1.3
 Please note that the design and installation for each building must be independent.

47 | P a g e
Supply, Installation, testing and commissioning of Solar PV System for referral hospital

No Items Name Items with their description Standards & Unit Qty Unit Total price
Recommend price
ations
1, Pathology, ICU, OR and Labor Rooms
1.1 550W Solar Electrical characteristics at STC: A.M 1.5
Panel 1000w/m2 @ 250c
(Monocrystalli  Type: Monocrystalline silicon, half-cell
ne Solar  Maximum power (Pmax): 550W
Module half-  Open-circuit voltage (Voc): 49.80 V
cell)  Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1% IEC 61215, pcs
Classification Class A IEC 61730
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
48 | P a g e
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc: +0.048%
/ °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a speed
of 23m/s
Warranty=5 years
With all accessories
1.2 DC circuit combiner board with all necessary safety and protection IEC 60950-1, set
devices EN 60950-1
1.3 Mounting racks Adjustable Aluminum Alloy 6000 Series or ISO Set
for PV module
Galvanized steel Waterproof mounting 9001/SGS/CE/IS
array
Rack including support frame with at least O45001
four tamper-proof fasteners; with complete
set of stainless screw, bolt & nut. Rack
frames should be able to hold all PV arrays
and should resist any movement.
Warranty : 15 Years
With all accessories

49 | P a g e
1.4 Three phase PV string input data
hybrid solar  Maximum PV input power (W): 39,000W
inverter(built  Maximum PV input voltage (V): 1000V
in MPPT  Start-up Voltage (V): 180V
charge  MPPT voltage range (V): 150- 850
controller),  Rated PV input voltage (V): 600 IEC 61727, IEC
high voltage  Maximum operating PV input current (A): 62116, EN pcs
battery 36+36+ 36 50549,
supported  Max. Input Short-Circuit Current (A): IEC/EN 61000-
55+55+55 6-1/2/3/4,
 No. of MPP Trackers/No. of Strings per MPP IEC/EN 62109-
Tracker: 3/2+2+2 1, IEC/EN
Battery input data 62109-2
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 + 50
 Maximum discharging current (A): 50+
50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active Power(W):
30,000
 Max. AC Input/output Apparent
Power(VA): 33,000
 Rated AC Input/output Current(A):
45.5/43.5
 Max. AC Input/output Current(A): 50/47.9
 Max. Three-phase Unbalanced Output
Current (A): 60
 Max. Continuous AC Pass through (grid to
load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s

50 | P a g e
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
less than or equal to 3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: 99% or higher
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface

51 | P a g e
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
527×894×294(including Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
52 | P a g e
Warranty: 5 Years
With all accessories

1.5 High voltage Main Parameter


LiFePO4  Battery Type : LiFePO4(LFP)
battery  Nominal Voltage: 51.2Vdc
 Rated Capacity: 100Ah UN38.3/CE/
 Rated Energy : 5.12kWh CE-EMC/ pcs
 Nominal Charge/Discharge Current : IEC/62040
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension less than or equal to
(W/D/H): 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
53 | P a g e
With all accessories

1.6 High Voltage Operating Voltage: 120-1000Vdc


Battery cluster Nominal Charge/Discharge Current: 100A
control box Maximum Charge/Discharge Current:
125A UN38.3/CE/ Pcs
DC Input Rating: 12±2%V/4.15A CE-EMC/
Operating Temperature Range: -20~65°C IEC/62040
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
1.7 Battery Cabinet with all accessories UL 9540 Pcs

1.8 Earthing for PV Earthing system must be separated of the


Solar System: main earthing system to obtain 2-ohm max
resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with
cast iron cover (5 Ton) with hinge, earth IEC/EN 61000- set
joints, clamps, ducts, conduits and 50 mm2 6-1/2/3/4
flexible earthing copper wires and cables
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as per
the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV panels
for steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points
in each string.
With all accessories

54 | P a g e
1.9 Cables and connectors required to wire the whole system as the IEC 60228 meter
wire size and quantity difference depending the connection point UL 44
1.10 Document Preparation (design, manual and installation drawing )

1.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for
the solar panel (if necessary).
1.12 if any

2, NICU and virology Rooms

2.1 550W Solar Electrical characteristics at STC: A.M 1.5 IEC 61215, pcs
Panel 1000w/m2 @ 250c IEC 61730
(Monocrystall  Type: Monocrystalline silicon, half-cell
ine Solar  Maximum power (Pmax): 550W
Module half-  Open-circuit voltage (Voc): 49.80 V
cell)  Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification Class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)

55 | P a g e
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal 2256 x
1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc: +0.048%
/ °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a speed
of 23m/s
Warranty=5 years
With all accessories
2.2 DC circuit combiner board with all necessary safety and protection IEC 60950-1, set
devices EN 60950-1
2.3 Mounting racks Adjustable Aluminum Alloy 6000 Series or ISO Set
for PV module
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/IS
array
including support frame with at least four O45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames

56 | P a g e
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
2.4 Three phase PV string input data
hybrid solar  Maximum PV input power (W): 39,000W
inverter(built  Maximum PV input voltage (V): 1000V
in MPPT  Start-up Voltage (V): 180V
charge  MPPT voltage range (V): 150- 850
controller),  Rated PV input voltage (V): 600 IEC 61727, IEC
high voltage  Maximum operating PV input current (A): 62116, EN pcs
battery 36+36+ 36 50549,
supported  Max. Input Short-Circuit Current (A): IEC/EN 61000-
55+55+55 6-1/2/3/4,
 No. of MPP Trackers/No. of Strings per MPP IEC/EN 62109-
Tracker: 3/2+2+2 1, IEC/EN
Battery input data 62109-2
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 + 50
 Maximum discharging current (A): 50+
50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active Power(W):
30,000
 Max. AC Input/output Apparent
Power(VA): 33,000
 Rated AC Input/output Current(A):
45.5/43.5
 Max. AC Input/output Current(A): 50/47.9

57 | P a g e
 Max. Three-phase Unbalanced Output
Current (A): 60
 Max. Continuous AC Pass through (grid to
load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
less than or equal to 3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: 99% or higher
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
58 | P a g e
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)

59 | P a g e
 Cabinet Size (WxHxD mm): less than
or equal to 527×894×294(including
Connectors and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
2.5 High voltage Main Parameter
LiFePO4  Battery Type : LiFePO4(LFP)
battery  Nominal Voltage: 51.2Vdc
 Rated Capacity: 100Ah UN38.3/CE/
 Rated Energy : 5.12kWh CE-EMC/ pcs
 Nominal Charge/Discharge Current : IEC/62040
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
60 | P a g e
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
2.6 High Voltage Operating Voltage: 120-1000Vdc
Battery cluster Nominal Charge/Discharge Current: 100A
control box Maximum Charge/Discharge Current:
125A UN38.3/CE/ Pcs
DC Input Rating: 12±2%V/4.15A CE-EMC/
Operating Temperature Range: -20~65°C IEC/62040
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
2.7 Battery Cabinet with all accessories UL 9540 Pcs
2.8 Earthing for Earthing system must be separated of the
PV Solar main earthing system to obtain 2-ohm max
System resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with
cast iron cover (5 Ton) with hinge, earth IEC/EN 61000- Set
joints, clamps, ducts, conduits and 50 mm2 6-1/2/3/4
flexible earthing copper wires and cables
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as per
the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV panels
for steel structure 16mm2 flexible earthing

61 | P a g e
copper wires shall be from 3 different points
in each string.
With all accessories

2.9 Cables and connectors required to wire the whole system as the IEC 60228 meter
wire size and quantity difference depending the connection point UL 44
2.10 Document Preparation (design, manual and installation drawing )

2.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for
the solar panel (if necessary).
2.12 if any

3, Emergency/Laboratory/Imaging

3.1 550W Solar Electrical characteristics at STC: A.M 1.5 IEC 61215, pcs
Panel 1000w/m2 @ 250c IEC 61730
(Monocrystall  Type: Monocrystalline silicon, half-cell
ine Solar  Maximum power (Pmax): 550W
Module half-  Open-circuit voltage (Voc): 49.80 V
cell)  Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification Class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
62 | P a g e
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. Kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc: +0.048%
/ °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a speed
of 23m/s
Warranty=5 years
With all accessories
3.2 DC circuit combiner board with all necessary safety and protection IEC 60950-1, set
devices EN 60950-1

63 | P a g e
3.3 Mounting racks Adjustable Aluminum Alloy 6000 Series or ISO Set
for PV module
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/IS
array
including support frame with at least four O45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
3.4 Three phase PV string input data
hybrid solar  Maximum PV input power (W): 39,000W
inverter(built  Maximum PV input voltage (V): 1000V
in MPPT  Start-up Voltage (V): 180V
charge  MPPT voltage range (V): 150- 850
controller),  Rated PV input voltage (V): 600 IEC 61727, IEC
high voltage  Maximum operating PV input current (A): 62116, EN pcs
battery 36+36+ 36 50549,
supported  Max. Input Short-Circuit Current (A): IEC/EN 61000-
55+55+55 6-1/2/3/4,
 No. of MPP Trackers/No. of Strings per MPP IEC/EN 62109-
Tracker: 3/2+2+2 1, IEC/EN
Battery input data 62109-2
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 + 50
 Maximum discharging current (A): 50+
50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data

64 | P a g e
 Rated AC Input/output Active Power(W):
30,000
 Max. AC Input/output Apparent
Power(VA): 33,000
 Rated AC Input/output Current(A):
45.5/43.5
 Max. AC Input/output Current(A): 50/47.9
 Max. Three-phase Unbalanced Output
Current (A): 60
 Max. Continuous AC Pass through (grid to
load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
less than or equal to 3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: 99%
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
65 | P a g e
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
66 | P a g e
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
527×894×294(including Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
3.5 High voltage Main Parameter
LiFePO4  Battery Type : LiFePO4(LFP)
battery  Nominal Voltage: 51.2Vdc UN38.3/CE/
 Rated Capacity: 100Ah CE-EMC/
 Rated Energy : 5.12kWh IEC/62040 pcs
 Nominal Charge/Discharge Current :
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
0
discharging@ 25 c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power On
67 | P a g e
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
3.6 High Voltage Operating Voltage: 120-1000Vdc
Battery cluster Nominal Charge/Discharge Current: 100A
control box Maximum Charge/Discharge Current:
125A UN38.3/CE/ Pcs
DC Input Rating: 12±2%V/4.15A CE-EMC/
Operating Temperature Range: -20~65°C IEC/62040
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
3.7 Battery Cabinet with all accessories UL 9540 Pcs
3.8 Earthing for Earthing system must be separated of the
PV Solar main earthing system to obtain 2-ohm max
System resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with
cast iron cover (5 Ton) with hinge, earth IEC/EN 61000- set
joints, clamps, ducts, conduits and 50 mm2 6-1/2/3/4
flexible earthing copper wires and cables
from the PV system components and steel
68 | P a g e
structure to the electrode to complete the
system as specifications, drawings and as per
the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV panels
for steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points
in each string.
With all accessories
3.9 Cables and connectors required to wire the whole system as the IEC 60228 meter
wire size and quantity difference depending the connection point UL 44
3.10 Document Preparation (design, manual and installation drawing )

3.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the
solar panel (if necessary).
3.12 if any

4, Card room and Medical Management Rooms

4.1 550W Solar Electrical characteristics at STC: A.M 1.5 IEC 61215, pcs
Panel 1000w/m2 @ 250c IEC 61730
(Monocrystalli  Type: Monocrystalline silicon, half-cell
ne Solar  Maximum power (Pmax): 550W
Module half-  Open-circuit voltage (Voc): 49.80 V
cell)  Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification Class A
Operating parameters
 Operational temperatures: -400c - +
850c or higher

69 | P a g e
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. Kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc:
+0.048% / °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a speed
of 23m/s
Warranty=5years
With all accessories
70 | P a g e
4.2 DC circuit combiner board with all necessary safety and protection IEC 60950-1, set
devices EN 60950-1
4.3 Mounting racks Adjustable Aluminum Alloy 6000 Series or ISO Set
for PV module
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/IS
array
including support frame with at least four O45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
4.4 Three phase PV string input data IEC 61727, IEC pcs
hybrid solar  Maximum PV input power (W): 12,000W 62116, EN
inverter(built in  Maximum PV input voltage (V): 800V 50549,
MPPT charge  Start-up Voltage (V): 160V IEC/EN 61000-
controller)  MPPT voltage range (V): 200-650 6-1/2/3/4,
 Rated PV input voltage (V): 550 IEC/EN 62109-
 Maximum operating PV input current (A): 1, IEC/EN
20+20 62109-2
 Max. Input Short-Circuit Current (A): 30+30
 No. of MPP Trackers/No. of Strings per MPP
Tracker: 2/1+1
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 40-60
 Maximum charging current (A): 135
 Maximum discharging current (A):135
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: 1
AC input /output data

71 | P a g e
 Rated AC Input/output Active Power(W):
8000
 Max. AC Input/output Apparent
Power(VA): 8800
 Rated AC Input/output Current(A):
12.2/11.6
 Max. AC Input/output Current(A):
13.4/12.8
 Max. Continuous AC Pass through (grid to
load) (A): 45
 Peak Power (off-grid)(W): 2 times of rated
power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
less than or equal to 3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99% or higher
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
72 | P a g e
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Support multiple batteries in parallel
 Max. charging/discharging current of
100A
 higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 3000m
 Noise (dB): ≤55
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated

73 | P a g e
 Over Voltage Category: OVC II(DC),
OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
386×660×250(including Connectors
and Brackets)
 Weight (kg): less than or equal to 35.2
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
4.5 Battery Main Parameter
LiFePO4  Battery Type : LiFePO4(LFP)
 Nominal Voltage: 51.2Vdc
 Rated Capacity: 100Ah UN38.3/CE/
 Rated Energy : 5.12kWh CE-EMC/ pcs
 Nominal Charge/Discharge Current: IEC/62040
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
0
discharging@ 25 c
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
74 | P a g e
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
4.6 Battery cluster Operating Voltage: 40-60Vdc
control box Nominal Charge/Discharge Current: 100A
Maximum Charge/Discharge Current:
125A UN38.3/CE/ Pcs
DC Input Rating: 12±2%V/4.15A CE-EMC/
Operating Temperature Range: -20~65°C IEC/62040
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
4.7 Battery Cabinet with all accessories UL 9540 Pcs
4.8 Earthing for Earthing system must be separated of the
PV Solar main earthing system to obtain 2-ohm max
System: resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with
cast iron cover (5 Ton) with hinge, earth IEC/EN 61000- set
joints, clamps, ducts, conduits and 50 mm2 6-1/2/3/4
flexible earthing copper wires and cables
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as per
the approval.

75 | P a g e
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV panels
for steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points
in each string.
With all accessories

4.9 Cables and connectors required to wire the whole system as the IEC 60228 meter
wire size and quantity difference depending the connection point UL 44
4.10 Document Preparation (design, manual and installation drawing )

4.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the
solar panel (if necessary).
4.12 if any

5, Drug Store

5.1 550W Solar Electrical characteristics at STC: A.M 1.5 IEC 61215, pcs
Panel 1000w/m2 @ 250c IEC 61730
(Monocrystalli  Type: Monocrystalline silicon, half-cell
ne Solar  Maximum power (Pmax): 550W
Module half-  Open-circuit voltage (Voc): 49.80 V
cell)  Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification Class A
Operating parameters
 Operational temperatures: -400c - +
850c or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
76 | P a g e
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. Kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc:
+0.048% / °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a speed
of 23m/s
Warranty=5years
With all accessories
5.2 DC circuit combiner board with all necessary safety and protection IEC 60950-1, set
devices EN 60950-1

77 | P a g e
5.3 Mounting racks Adjustable Aluminum Alloy 6000 Series or ISO Set
for PV module
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/IS
array
including support frame with at least four O45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
With all accessories
Warranty : 15 Years
5.4 Three phase PV string input data IEC 61727, IEC pcs
hybrid solar  Maximum PV input power (W): 12,000W 62116, EN
inverter(built in  Maximum PV input voltage (V): 800V 50549,
MPPT charge  Start-up Voltage (V): 160V IEC/EN 61000-
controller)  MPPT voltage range (V): 200-650 6-1/2/3/4,
 Rated PV input voltage (V): 550 IEC/EN 62109-
 Maximum operating PV input current (A): 1, IEC/EN
20+20 62109-2
 Max. Input Short-Circuit Current (A): 30+30
 No. of MPP Trackers/No. of Strings per MPP
Tracker: 2/1+1
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 40-60
 Maximum charging current (A): 135
 Maximum discharging current (A):135
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: 1
AC input /output data
 Rated AC Input/output Active Power(W):
8000

78 | P a g e
 Max. AC Input/output Apparent
Power(VA): 8800
 Rated AC Input/output Current(A):
12.2/11.6
 Max. AC Input/output Current(A):
13.4/12.8
 Max. Continuous AC Pass through (grid to
load) (A): 45
 Peak Power (off-grid)(W): 2 times of rated
power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
less than or equal to 3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99%
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
79 | P a g e
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Support multiple batteries in parallel
 Max. charging/discharging current of
100A
 higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 3000m
 Noise (dB): ≤55
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)

80 | P a g e
 Cabinet Size (WxHxD mm): less
than or equal to
386×660×250(including Connectors
and Brackets)
 Weight (kg): less than or equal to 35.2
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
5.5 Battery Main Parameter
LiFePO4  Battery Type : LiFePO4(LFP)
 Nominal Voltage: 51.2Vdc
 Rated Capacity: 100Ah UN38.3/CE/
 Rated Energy : 5.12kWh CE-EMC/ pcs
 Nominal Charge/Discharge Current : IEC/62040
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
0
discharging@ 25 c
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
81 | P a g e
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
5.6 Battery cluster Operating Voltage: 40-60Vdc
control box Nominal Charge/Discharge Current: 100A
Maximum Charge/Discharge Current:
125A UN38.3/CE/ Pcs
DC Input Rating: 12±2%V/4.15A CE-EMC/
Operating Temperature Range: -20~65°C IEC/62040
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
5.7 Battery Cabinet with all accessories UL 9540 Pcs

5.8 Earthing for Earthing system must be separated of the


PV Solar main earthing system to obtain 2-ohm max
System: resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with
cast iron cover (5 Ton) with hinge, earth IEC/EN 61000- set
joints, clamps, ducts, conduits and 50 mm2 6-1/2/3/4
flexible earthing copper wires and cables
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as per
the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV panels

82 | P a g e
for steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points
in each string.
With all accessories
5.9 Cables and connectors required to wire the whole system as the IEC 60228 meter
wire size and quantity difference depending the connection point UL 44
5.10 Document Preparation (design, manual and installation drawing )

5.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the
solar panel (if necessary).
5.12 if any

6, Blood bank

6.1 550W Solar Electrical characteristics at STC: A.M 1.5 IEC 61215, pcs
Panel 1000w/m2 @ 250c IEC 61730
(Monocrystall  Type: Monocrystalline silicon, half-cell
ine Solar  Maximum power (Pmax): 550W
Module half-  Open-circuit voltage (Voc): 49.80 V
cell)  Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95
V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification Class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher

83 | P a g e
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. Kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc: +0.048%
/ °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a speed
of 23m/s
Warranty=5 years
With all accessories
6.2 DC circuit combiner board with all necessary safety and protection IEC 60950-1, set
devices EN 60950-1

84 | P a g e
6.3 Mounting racks Adjustable Aluminum Alloy 6000 Series or ISO Set
for PV module
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/IS
array
including support frame with at least four O45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
6.4 Three phase PV string input data
hybrid solar  Maximum PV input power (W): 39,000W
inverter(built  Maximum PV input voltage (V): 1000V
in MPPT  Start-up Voltage (V): 180V
charge  MPPT voltage range (V): 150- 850
controller),  Rated PV input voltage (V): 600 IEC 61727, IEC
high voltage  Maximum operating PV input current (A): 62116, EN pcs
battery 36+36+ 36 50549,
supported  Max. Input Short-Circuit Current (A): IEC/EN 61000-
55+55+55 6-1/2/3/4,
 No. of MPP Trackers/No. of Strings per MPP IEC/EN 62109-
Tracker: 3/2+2+2 1, IEC/EN
Battery input data 62109-2
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 + 50
 Maximum discharging current (A): 50+
50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data

85 | P a g e
 Rated AC Input/output Active Power(W):
30,000
 Max. AC Input/output Apparent
Power(VA): 33,000
 Rated AC Input/output Current(A):
45.5/43.5
 Max. AC Input/output Current(A): 50/47.9
 Max. Three-phase Unbalanced Output
Current (A): 60
 Max. Continuous AC Pass through (grid to
load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
less than or equal to 3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: 99% or higher
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
86 | P a g e
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support high voltage multiple
batteries in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
87 | P a g e
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
527×894×294(including Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
6.5 High voltage Main Parameter
LiFePO4  Battery Type : LiFePO4(LFP)
battery  Nominal Voltage: 51.2Vdc
 Rated Capacity: 100Ah UN38.3/CE/
 Rated Energy : 5.12kWh CE-EMC/ pcs
 Nominal Charge/Discharge Current : IEC/62040
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
0
discharging@ 25 c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power On
88 | P a g e
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
6.6 High Voltage Operating Voltage: 120-1000Vdc
Battery cluster Nominal Charge/Discharge Current: 100A
control box Maximum Charge/Discharge Current:
125A UN38.3/CE/ Pcs
DC Input Rating: 12±2%V/4.15A CE-EMC/
Operating Temperature Range: -20~65°C IEC/62040
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
6.7 Battery Cabinet with all accessories UL 9540 Pcs

6.8 Earthing for Earthing system must be separated of the


PV Solar main earthing system to obtain 2-ohm max
System: resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with
cast iron cover (5 Ton) with hinge, earth IEC/EN 61000- set
joints, clamps, ducts, conduits and 50 mm2 6-1/2/3/4
flexible earthing copper wires and cables
89 | P a g e
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as per
the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV panels
for steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points
in each string.
With all accessories
6.9 Cables and connectors required to wire the whole system as the IEC 60228 meter
wire size and quantity difference depending the connection point UL 44
6.10 Document Preparation (design, manual and installation drawing )
6.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for
the solar panel (if necessary).
6.12 if any
7. Baking oven
7.1 550w Solar Electrical characteristics at STC: A.M 1.5
Panel 1000w/m2 @ 250c
(Monocrystallin  Type: Monocrystalline silicon, half-cell
e Solar Module  Maximum power (Pmax): 550W
half-cell)  Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A IEC 61215, IEC
 Maximum power voltage (Vmp): 41.95 61730 Pcs
V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to
±5w
 Voc and Isc: less than or equal to ±3%

90 | P a g e
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256
x 1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -
0.270% / °C
 Temperature coefficient of Isc: +0.048%
/ °C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading:
2400pa
 Hailstone test; 25mm hailstone at a speed
of 23m/s
Warranty=5 years
With all accessories

91 | P a g e
7.2 DC circuit combiner board with all necessary safety and protection IEC 60950-1, Set
devices EN 60950-1

7.3 Mounting racks Adjustable Aluminum Alloy 6000 Series or ISO Set
for PV module
Galvanized steel Waterproof mounting 9001/SGS/CE/IS
array
Rack including support frame with at least O45001
four tamper-proof fasteners; with complete
set of stainless screw, bolt & nut. Rack
frames should be able to hold all PV arrays
and should resist any movement.
Warranty : 15 Years
With all accessories
7.4 Three phase PV string input data
hybrid solar  Maximum PV input power (W): 45,500W
inverter(built in  Maximum PV input voltage (V): 1000V
MPPT charge  Start-up Voltage (V): 180V
controller), high  MPPT voltage range (V): 150- 850
voltage battery  Rated PV input voltage (V): 600
supported  Maximum operating PV input current (A): IEC 61727, IEC Pcs
36+36+ 36 62116, EN
50549,
 Max. Input Short-Circuit Current (A):
IEC/EN 61000-
55+55+55
6-1/2/3/4,
 No. of MPP Trackers/No. of Strings per
IEC/EN 62109-
MPP Tracker: 3/2+2+2
1, IEC/EN
Battery input data
62109-2
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 + 50
 Maximum discharging current (A): 50+
50

92 | P a g e
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active Power(W):
35,000
 Max. AC Input/output Apparent
Power(VA): 38,000
 Rated AC Input/output Current(A):
53.1/50.8
 Max. AC Input/output Current(A):
58.4/55.8
 Max. Three-phase Unbalanced Output
Current (A): 60
 Max. Continuous AC Pass through (grid
to load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
<3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99% or higher
Equipment Protection
Integrated with
 DC Polarity Reverse Connection
Protection,
93 | P a g e
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and
off-grid operation;
 Support multiple batteries parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
94 | P a g e
 Operating Temperature Range (℃): -
40 to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)
 Cabinet Size (WxHxD mm): less
than or equal to
527×894×294(including Connectors
and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
7.5 High voltage Main Parameter
LiFePO4  Battery Type : LiFePO4(LFP)
battery  Nominal Voltage: 51.2Vdc
 Rated Capacity: 100Ah
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current : UN38.3/CE/ Pcs
100A CE-EMC/
 Peak. Discharge Current:125A IEC/62040
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to
55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20

95 | P a g e
 Dimension (W/D/H): less than or equal
to 440*570*133mm
 Weight: Approximate less than or equal
to 44kg
Status Indicator
 Yellow: Battery High Voltage Power On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
7.6 High Voltage Operating Voltage: 120-1000Vdc
Battery cluster Nominal Charge/Discharge Current: 100A
control box Maximum Charge/Discharge Current:
with all 125A UN38.3/CE/
accessories DC Input Rating: 12±2%V/4.15A CE-EMC/ Pcs
Operating Temperature Range: -20~65°C IEC/62040
or higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
7.7 Battery Cabinet with all accessories UL 9540 Pcs

96 | P a g e
Earthing for PV Earthing system must be separated of the set
7.8 Solar main earthing system to obtain 2-ohm max
System: resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with IEC/EN 61000-
cast iron cover (5 Ton) with hinge, earth 6-1/2/3/4
joints, clamps, ducts, conduits and 50 mm2
flexible earthing copper wires and cables
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as
per the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV
panels For steel structure 16mm2 flexible
earthing copper wires shall be from 3
different points in each string.
With all accessories
7.9 Cables and connectors required to wire the whole system as the IEC 60228 Meter
wire size and quantity difference depending the connection point UL 44
7.10 Document Preparation (design, manual and installation drawing )
7.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the
solar panel (if necessary).
7.12 If any

Note:
Any minor equipment and material may not be specifically mentioned in these specifications but the bidders are required to make the system complete in
a every respect in accordance with technical specification and the same shall be deemed to have been covered under the scope of these specifications and
shall be provided by the bidder / supplier within the quoted price.

97 | P a g e
3.3. Total power and daily energy consumption for shire campus
No Building/load Total Power(KW) Total Energy(KWH)

1 Water Pump 1 4.5 27

2 Water Pump 2 5.5 33

3 Water Pump 3 11 66

4 Management 36.638 255.918

5 Baking Oven 50 300

Total 107.638 681.918

N.B. Since the system is a hybrid solar system and the price of the battery is expensive, the system must work with battery mode for a few hours. During
day time (sunshine hour) the system will use from PV; during cloud or night time, if there is a grid, it will use from a grid, but (in worst scenario) if there
is no grid, it will use from battery. The backup batteries can support the load for 1 hour for management building and baking oven, when their loads are
operating at maximum power, while water pumps will operate without battery supported.

 Use peak sun hour (PSH) = 6hrs.


 Use safety factor for inverter = 1.3
 Please note that the design and installation for each building must be independent

98 | P a g e
Supply, Installation, testing and commissioning of Solar PV System for shire campus
No Items Name Items with their description (detail Standards Unit Qt Unit Total
specification ) y price price
1. Water pump 1
1.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215, Pcs
(Monocrystalline Solar 1000w/m2 @ 250c IEC 61730
Module half-cell)  Type: Monocrystalline silicon, half-cell
 Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95 V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification Class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to ±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
99 | P a g e
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256 x
1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -0.270%
/ °C
 Temperature coefficient of Isc: +0.048% /
°C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading: 2400pa
 Hailstone test; 25mm hailstone at a speed of
23m/s
Warranty=5 years
With all accessories
1.2 DC circuit combiner board with all necessary safety and protection devices IEC 60950-1, Set
EN 60950-1
1.3 Mounting racks for PV Adjustable Aluminum Alloy 6000 Series or ISO Set
module array
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/I
including support frame with at least four SO45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
1.4 Three phase Solar Solar pump DC input IEC61727, Pcs
pumping inverter  Maximum Voc voltage: 900V IEC/EN
 Minimum Vmp voltage: 400V 62109-1,
100 | P a g e
 Recommended Vmp voltage: ≥ 500V IEC/EN
(solar only), ≥ 560V (hybrid power) 62109-2
 Minimum MPPT efficiency: 99%
 Maximum input current: 20A
 Number of string: 2
 Overload power: 9900w
 Automatic MPPT function to identify
the VOC and Vmp of solar panel without
programming
Hybrid AC/ generator input
 Maximum input current: 16A
 Automatic Ac supplement automatic
while solar in low power mode and AC
disconnect automatically while solar
power recovery
 Maximum adopted AC pump horse
power (HP): 7.5HP
 Maximum adopted Ac pump power:
5500W
AC output (for pump)
 driver mode: three phase variable
frequency driver
 Maximum output voltage:
380/400/440V
 Maximum output frequency: 50-60Hz
(support program range 15to 60 Hz)
 Maximum output current: 21A
Minimum efficiency: 97%
With have Water level sensor
(borehole/tanker)
With have GPRS SMS monitor and controller
It Support remote monitoring & control system
(SPMCS)
With have LCD Displayer
Noise <50dB
Water proof: IP65

101 | P a g e
Cooling method: force cooling by fun (IP68)
Operating environment
 Operating environment temperature:
-100C to 600c above 600c need to derate
load
 Maximum humidity: 95%RH
 Using altitude <3000m above 3000m
need to derate load
 Others: prohibiting the installation
location, direct sun light, thick dust,
corrosive gas or oil mist, flammable
gas, liquid etc…
Warranty: 5 Years
With all accessories

1.5 Earthing for Solar PV Earthing system must be separated of the IEC/EN set
System: main earthing system to obtain 2-ohm max 61000-6-
resistance. 1/2/3/4
The item includes (3copper electrodes
15mm2 driven into ground, manholes with
cast iron cover (5 Ton) with hinge, earth
joints, clamps, ducts, conduits and 50 mm2
flexible earthing copper wires and cables
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as
per the approval.
For PV solar 10 mm2 flexible earthing copper
wires shall be in-between PV panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points in
each string.
With all accessories
1.6 Cables and connectors required to wire the whole system as the wire size and IEC 60228 Meter
quantity difference depending the connection point UL 44
1.7 document Preparation (design, manual and installation drawing )

102 | P a g e
1.8 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel
(if necessary).
1.9 if any
2. Water pump 2
2.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215,
(Monocrystalline Solar 1000w/m2 @ 250c IEC 61730
Module half-cell)  Type: Monocrystalline silicon, half-cell
 Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95 V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification Class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to ±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame

103 | P a g e
 Dimensions: less than or equal to 2256 x
1133 x 35 mm)
 Weight: less than or equal to 27. Kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -0.270%
/ °C
 Temperature coefficient of Isc: +0.048% /
°C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading: 2400pa
 Hailstone test; 25mm hailstone at a speed of
23m/s
Warranty=5years
With all accessories
2.2 DC circuit combiner board with all necessary safety and protection devices IEC 60950-1, Set
EN 60950-1
2.3 Mounting racks for PV Adjustable Aluminum Alloy 6000 Series or ISO Set
module array
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/I
including support frame with at least four SO45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
2.4 Three phase Solar Solar pump DC input IEC61727, pcs
pumping inverter  Maximum Voc voltage: 900V IEC/EN
 Minimum Vmp voltage: 400V 62109-1,

104 | P a g e
 Recommended Vmp voltage: ≥ 500V IEC/EN
(solar only), ≥ 560V (hybrid power) 62109-2
 Minimum MPPT efficiency: 99%
 Maximum input current: 20A
 Number of string: 2
 Overload power: 9900w
 Automatic MPPT function to identify
the VOC and Vmp of solar panel without
programming
Hybrid AC/ generator input
 Maximum input current: 16A
 Automatic Ac supplement automatic
while solar in low power mode and AC
disconnect automatically while solar
power recovery
 Maximum adopted AC pump horse
power (HP): 7.5HP
 Maximum adopted Ac pump power:
5500W
AC output (for pump)
 driver mode: three phase variable
frequency driver
 Maximum output voltage:
380/400/440V
 Maximum output frequency: 50-60Hz
(support program range 15to 60 Hz)
 Maximum output current: 21A
minimum efficiency: 97%
With have Water level sensor
(borehole/tanker)
With have GPRS SMS monitor and controller
It Support remote monitoring & control system
(SPMCS)
With have LCD Displayer
Noise <50dB
Water proof: IP65

105 | P a g e
Cooling method: force cooling by fun (IP68)
Operating environment
 Operating environment temperature:
-100C to 600c above 600c need to derate
load
 Maximum humidity: 95%RH
 Using altitude <3000m above 3000m
need to derate load
 Others: prohibiting the installation
location, direct sun light, thick dust,
corrosive gas or oil mist, flammable
gas, liquid etc…
Warranty: 5 Years
With all accessories

2.5 Earthing for Solar PV Earthing system must be separated of the IEC/EN set
System: main earthing system to obtain 2-ohm max 61000-6-
resistance. 1/2/3/4
The item includes (3copper electrodes
2
15mm driven into ground, manholes with cast
iron cover (5 Ton) with hinge, earth joints, clamps,
ducts, conduits and 50 mm2 flexible earthing
copper wires and cables from the PV system
components and steel structure to the electrode to
complete the system as specifications, drawings
and as per the approval.
For PV solar 10 mm2 flexible earthing copper
wires shall be in-between PV panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points in
each string.
With all accessories
2.6 Cables and connectors required to wire the whole system as the wire size IEC 60228 Meter
and quantity difference depending the connection point UL 44
2.7 document Preparation (design, manual and installation drawing )

106 | P a g e
2.8 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel
(if necessary).
2.9 if any
3. Water Pump 3
3.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215,
(Monocrystalline Solar 1000w/m2 @ 250c IEC 61730
Module half-cell)  Type: Monocrystalline silicon, half-cell
 Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95 V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification: Class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to ±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame

107 | P a g e
 Dimensions: less than or equal to 2256 x
1133 x 35 mm)
 Weight: less than or equal to 27. Kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -0.270%
/ °C
 Temperature coefficient of Isc: +0.048% /
°C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading: 2400pa
 Hailstone test; 25mm hailstone at a speed of
23m/s
Warranty=5 years
With all accessories
3.2 DC circuit combiner board with all necessary safety and protection devices IEC 60950-1,
EN 60950-1 Set
3.3 Mounting racks for PV Adjustable Aluminum Alloy 6000 Series or ISO Set
module array
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/I
including support frame with at least four SO45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
Warranty : 15 Years
With all accessories
3.4 Three phase Solar Solar pump DC input IEC61727, Pcs
pumping inverter  Maximum Voc voltage: 900V IEC/EN
 Minimum Vmp voltage: 400V 62109-1,
 Recommended Vmp voltage: ≥ 500V IEC/EN
(solar only), ≥ 560V (hybrid power) 62109-2

108 | P a g e
 Minimum MPPT efficiency: 99%
 Maximum input current: 36A
 Number of string: 2
 Overload power: 17.6KW
 Automatic MPPT function to identify
the VOC and Vmp of solar panel without
programming
Hybrid AC/ generator input:
 Maximum input current: 27A
 Automatic Ac supplement automatic
while solar in low power mode and AC
disconnect automatically while solar
power recovery
 Maximum adopted AC pump horse
power (HP): 15HP
 Maximum adopted Ac pump power:
11KW
AC output (for pump)
 driver mode: three phase variable
frequency driver
 Maximum output voltage:
380/400/440V
 Maximum output frequency: 50-60Hz
(support program range 15to 60 Hz)
 Maximum output current: 35.5A
Minimum efficiency: 97%
With have Water level sensor
(borehole/tanker)
With have GPRS SMS monitor and controller
It Support remote monitoring & control system
(SPMCS)
With have LCD Displayer
Noise <50dB
Water proof: IP65
Cooling method: force cooling by fun (IP68)
Operating environment

109 | P a g e
 Operating environment temperature:
-100C to 600c above 600c need to derate
load
 Maximum humidity: 95%RH
 Using altitude: <3000m above 3000m
need to derate load
 Others: prohibiting the installation
location, direct sun light, thick dust,
corrosive gas or oil mist, flammable
gas, liquid etc…
Warranty: 5 Years
With all accessories

3.5 Earthing for Solar PV Earthing system must be separated of the IEC/EN set
System: main earthing system to obtain 2-ohm max 61000-6-
resistance. 1/2/3/4
The item includes (3copper electrodes
15mm2 driven into ground, manholes with cast
iron cover (5 Ton) with hinge, earth joints, clamps,
ducts, conduits and 50 mm2 flexible earthing
copper wires and cables from the PV system
components and steel structure to the electrode to
complete the system as specifications, drawings
and as per the approval.
For PV solar 10 mm2 flexible earthing copper
wires shall be in-between PV panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points in
each string.
With all accessories
3.6 Cables and connectors required to wire the whole system as the wire size IEC 60228 Meter
and quantity difference depending the connection point UL 44
3.7 document Preparation (design, manual and installation drawing )
3.8
A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel
(if necessary).

110 | P a g e
3.9 if any
4. Management building
4.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215, Pcs
(Monocrystalline Solar 1000w/m2 @ 250c IEC 61730
Module half-cell)  Type: Monocrystalline silicon, half-cell
 Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95 V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification: Class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to ±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256 x
1133 x 35 mm)
 Weight: less than or equal to 27. Kg

111 | P a g e
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -0.270%
/ °C
 Temperature coefficient of Isc: +0.048% /
°C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading: 2400pa
 Hailstone test; 25mm hailstone at a speed of
23m/s
Warranty=5 years
With all accessories
4.2 DC circuit combiner board with all necessary safety and protection devices IEC 60950-1, Set
EN 60950-1
4.3 Mounting racks for PV Adjustable Aluminum Alloy 6000 Series or ISO Set
module array
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/I
including support frame with at least four SO45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
4.4 Three phase hybrid PV string input data IEC 61727, IEC Pcs
solar inverter(built in  Maximum PV input power (W): 65,000W 62116, EN
MPPT charge  Maximum PV input power (V): 1000V 50549,
controller), high voltage  Start-up Voltage (V): 180V IEC/EN
battery supported  MPPT voltage range (V): 150- 850 61000-6-
 Rated PV input voltage (V): 600 1/2/3/4,
IEC/EN
112 | P a g e
 Maximum operating PV input current 62109-1,
(A): 36+36+ 36+36 IEC/EN
 Max. Input Short-Circuit Current (A): 62109-2
55+55+55+55
 No. of MPP Trackers/No. of Strings per
MPP Tracker: 4/2+2+2+2
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 + 50
 Maximum discharging current (A): 50+
50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active Power(W):
50,000
 Max. AC Input/output Apparent
Power(VA): 55,000
 Rated AC Input/output Current(A):
75.8/72.5
 Max. AC Input/output Current(A):
83.4/79.8
 Max. Three-phase Unbalanced Output
Current (A): 83.4
 Max. Continuous AC Pass through (grid to
load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
113 | P a g e
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
less than or equal to 3% (of nominal
power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99% or higher
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
114 | P a g e
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and off-
grid operation;
 Support high voltage multiple batteries
in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -40
to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)
 Cabinet Size (WxHxD mm): less than
or equal to 527×894×294(Excluding
Connectors and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air Cooling
Warranty: 5 Years
With all accessories
4.5 High voltage LiFePO4 Main Parameter UN38.3/CE/ Pcs
battery  Battery Type : LiFePO4(LFP) CE-EMC/
 Nominal Voltage: 51.2Vdc IEC/62040
 Rated Capacity: 100Ah
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current : 100A
 Peak. Discharge Current:125A
115 | P a g e
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to 55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal to
440*570*133mm
 Weight: Approximate less than or equal to
44kg
Status Indicator
 Yellow: Battery High Voltage Power On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
4.6 High Voltage Battery Operating Voltage: 120-1000Vdc UN38.3/CE/ Pcs
cluster control box Nominal Charge/Discharge Current: 100A CE-EMC/
with all accessory Maximum Charge/Discharge Current: 125A IEC/62040
DC Input Rating: 12±2%V/4.15A
Operating Temperature Range: -20~65°C or
higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: minimum 17kg
Warranty: 5 years
116 | P a g e
With all accessories

4.7 Battery Cabinet with all accessories UL 9540 Pcs

4.8 Earthing for Solar PV Earthing system must be separated of the set
System: main earthing system to obtain 2-ohm max
resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with IEC/EN
cast iron cover (5 Ton) with hinge, earth 61000-6-
joints, clamps, ducts, conduits and 50 mm2 1/2/3/4
flexible earthing copper wires and cables
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as
per the approval.
For PV solar 10 mm2 flexible earthing copper
wires shall be in-between PV panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points
in each string.
With all accessories
4.9 Cables and connectors required to wire the whole system as the wire size IEC 60228 Meter
and quantity difference depending the connection point UL 44
4.10 Document Preparation (design, manual and installation drawing )

4.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel.
4.12 if any

5. baking oven
5.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215, IEC Pcs
(Monocrystalline Solar 1000w/m2 @ 250c 61730
Module half-cell)  Type: Monocrystalline silicon, half-cell
 Maximum power (Pmax): 550W

117 | P a g e
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95 V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to ±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame
 Dimensions: less than or equal to 2256 x
1133 x 35 mm)
 Weight: less than or equal to 27. kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -0.270%
/ °C
 Temperature coefficient of Isc: +0.048% /
°C
118 | P a g e
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading: 2400pa
 Hailstone test; 25mm hailstone at a speed
of 23m/s
Warranty=5 years
With all accessories
5.2 DC circuit combiner board with all necessary safety and protection IEC 60950-1, set
devices EN 60950-1
5.3 Mounting racks for Adjustable Aluminum Alloy 6000 Series or ISO set
PV module array 9001/SGS/CE/IS
Galvanized steel Waterproof mounting Rack
O45001
including support frame with at least four
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
5.4 Three phase hybrid PV string input data IEC 61727, IEC Pcs
solar inverter(built in  Maximum PV input power (W): 45,500W 62116, EN
MPPT charge  Maximum PV input voltage (V): 1000V 50549,
controller), high  Start-up Voltage (V): 180V IEC/EN 61000-
voltage battery  MPPT voltage range (V): 150- 850 6-1/2/3/4,
supported  Rated PV input voltage (V): 600 IEC/EN 62109-
 Maximum operating PV input current (A): 1, IEC/EN
36+36+ 36 62109-2
 Max. Input Short-Circuit Current (A):
55+55+55
 No. of MPP Trackers/No. of Strings per MPP
Tracker: 3/2+2+2
Battery input data
 Battery type: LiFePo4
119 | P a g e
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 + 50
 Maximum discharging current (A): 50+ 50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active Power(W):
35,000
 Max. AC Input/output Apparent
Power(VA): 38,000
 Rated AC Input/output Current(A):
53.1/50.8
 Max. AC Input/output Current(A):
58.4/55.8
 Max. Three-phase Unbalanced Output
Current (A): 60
 Max. Continuous AC Pass through (grid to
load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
<3% (of nominal power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99% or higher
Equipment Protection
120 | P a g e
Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and off-
grid operation;
 Support multiple batteries parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency

121 | P a g e
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -40
to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-
100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)
 Cabinet Size (WxHxD mm): less than
or equal to 527×894×294(including
Connectors and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air
Cooling
Warranty: 5 Years
With all accessories
5.5 High voltage LiFePO4 Main Parameter UN38.3/CE/ Pcs
battery  Battery Type : LiFePO4(LFP) CE-EMC/
 Nominal Voltage: 51.2Vdc IEC/62040
 Rated Capacity: 100Ah
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current :
100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to 55°C

122 | P a g e
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): less than or equal to
440*570*133mm
 Weight: Approximate less than or equal to
44kg
Status Indicator
 Yellow: Battery High Voltage Power On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
5.6 High Voltage Battery Operating Voltage: 120-1000Vdc UN38.3/CE/ Pcs
cluster control box Nominal Charge/Discharge Current: 100A CE-EMC/
with all accessories Maximum Charge/Discharge Current: 125A IEC/62040
DC Input Rating: 12±2%V/4.15A
Operating Temperature Range: -20~65°C or
higher
Ingress Protection: IP20
Dimension (W/D/H): less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
5.7 Battery Cabinet with all accessories UL 9540 Pcs

123 | P a g e
5.8 Earthing for PV Solar Earthing system must be separated of the IEC/EN 61000- set
System: main earthing system to obtain 2-ohm max 6-1/2/3/4
resistance.
The item includes (3copper electrodes
15mm2 driven into ground, manholes with
cast iron cover (5 Ton) with hinge, earth
joints, clamps, ducts, conduits and 50 mm2
flexible earthing copper wires and cables
from the PV system components and steel
structure to the electrode to complete the
system as specifications, drawings and as per
the approval.
For PV solar 10 mm2 flexible earthing
copper wires shall be in-between PV panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points
in each string.
With all accessories
5.9 Cables and connectors required to wire the whole system as the wire size IEC 60228 Meter
and quantity difference depending the connection point UL 44
5.10 Document Preparation (design, manual and installation drawing )

5.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar panel
(if necessary).
5.12 If any

Note:
Any minor equipment and material may not be specifically mentioned in these specifications but the bidders are required to make the system complete in
a every respect in accordance with technical specification and the same shall be deemed to have been covered under the scope of these specifications and
shall be provided by the bidder / supplier within the quoted price.

124 | P a g e
3.4. Total power and daily energy consumption of Adwa campus
No Building/load Total Power(KW) Total Energy(KWH)

1 Management 36.757 251.392

N.B. Since the system is a hybrid solar system and the price of the battery is expensive, the system must work with battery mode for a few hours. During
day time (sunshine hour) the system will use from PV; during cloud or night time, if there is a grid, it will use from a grid, but (in worst scenario) if there
is no grid, it will use from battery. The backup batteries can support the load for 1 hour for management building when their loads are operating at
maximum power.

 Use peak sun hour (PSH) = 6hrs.


 Use safety factor for inverter = 1.3

125 | P a g e
Supply, Installation, testing and commissioning of solar PV System for Adwa campus
No Items Name Items with their description (detail Standards Unit Qty Unit Total
specification ) price price
1, Adwa campus Management building
1.1 550w Solar Panel Electrical characteristics at STC: A.M 1.5 IEC 61215, Pcs
(Monocrystalline Solar 1000w/m2 @ 250c IEC 61730
Module half-cell)  Type: Monocrystalline silicon, half-cell
 Maximum power (Pmax): 550W
 Open-circuit voltage (Voc): 49.80 V
 Short-circuit current (Isc): 13.98A
 Maximum power voltage (Vmp): 41.95 V
 Maximum power current (Imp): 13.12A
 Module efficiency: greater than 21.1%
Classification: class A
Operating parameters
 Operational temperatures: -400c - + 850c
or higher
 Power tolerance: less than or equal to ±5w
 Voc and Isc: less than or equal to ±3%
 Maximum system voltage: DC1500
[IEC/UL] or higher
 Maximum series fuse rating: 25A
 Normal operating cell temperature:
45±20c
 Protection class: Class II
 Fire rating: UL type 1&2
 Cell orientation: 144 (6 x24)
 Junction box: IP68, three diodes
 Output cable: 4mm2, positive 400
/negative 200mm length can be
customized
 Glass: single glass, 3.2mm coated
tempered glass
 Frame: Anodized aluminum alloy frame

126 | P a g e
 Dimensions: : less than or equal to 2256 x
1133 x 35 mm)
 Weight: less than or equal to 27 kg
Temperature rating (STC)
 Temperature coefficient of Pmax: -
0.350% / °C
 Temperature coefficient of Voc: -0.270%
/ °C
 Temperature coefficient of Isc: +0.048% /
°C
Mechanical loading
 Front maximum static loading: 5400pa
 Rear side maximum static loading: 2400pa
 Hailstone test; 25mm hailstone at a speed of
23m/s
Warranty=5 years
With all accessories
1.2 DC circuit combiner board with all necessary safety and protection devices IEC 60950-1, Set
EN 60950-1

1.3 Mounting racks for PV Adjustable Aluminum Alloy 6000 Series or ISO Set
module array
Galvanized steel Waterproof mounting Rack 9001/SGS/CE/I
including support frame with at least four SO45001
tamper-proof fasteners; with complete set of
stainless screw, bolt & nut. Rack frames
should be able to hold all PV arrays and
should resist any movement.
Warranty : 15 Years
With all accessories
1.4 Three phase hybrid PV string input data IEC 61727, IEC Pcs
solar inverter(built in  Maximum PV input power (W): 65,000W 62116, EN
MPPT charge  Maximum PV input power (V): 1000V 50549,

127 | P a g e
controller), high voltage  Start-up Voltage (V): 180V IEC/EN
battery supported  MPPT voltage range (V): 150- 850 61000-6-
 Rated PV input voltage (V): 600 1/2/3/4,
 Maximum operating PV input current IEC/EN
(A): 36+36+ 36+36 62109-1,
 Max. Input Short-Circuit Current (A): IEC/EN
55+55+55+55 62109-2
 No. of MPP Trackers/No. of Strings per
MPP Tracker: 4/2+2+2+2
Battery input data
 Battery type: LiFePo4
 Battery voltage range(V): 160-800
 Maximum charging current (A): 50 + 50
 Maximum discharging current (A): 50+
50
 Charging strategy for LiFePo4: self-
adaption to BMS
 Number of battery input: two (2)
AC input /output data
 Rated AC Input/output Active Power(W):
50,000
 Max. AC Input/output Apparent
Power(VA): 55,000
 Rated AC Input/output Current(A):
75.8/72.5
 Max. AC Input/output Current(A):
83.4/79.8
 Max. Three-phase Unbalanced Output
Current (A): 83.4
 Max. Continuous AC Pass through (grid to
load) (A): 200
 Peak Power (off-grid)(W): 1.5 times of
rated power, 10s
 Power Factor Adjustment Range: 0.8
leading to 0.8 lagging

128 | P a g e
 Rated Input/output Voltage/Range (V):
220/380V, 230/400V 0.85Un-1.1Un
 Rated Input/output Grid
Frequency/Range(Hz): 50/45-55
 Grid Connection Form: 3L+N+PE
 Total Current Harmonic Distortion THDi:
less than or equal to 3% (of nominal
power)
 DC Injection Current: <0.5% In
Efficiency:
 Maximum efficiency: 97.60% or higher
 Euro Efficiency: 97.0% or higher
 MPPT Efficiency: >99%
Equipment Protection Integrated with
 DC Polarity Reverse Connection
Protection,
 AC Output Overcurrent Protection
 AC Output Overvoltage Protection,
 AC Output Short Circuit Protection,
 Thermal Protection
 DC Terminal Insulation Impedance
Monitoring,
 DC Component Monitoring,
 Ground Fault Current Monitoring
 Power Network Monitoring,
 Island Protection Monitoring,
 Earth Fault Detection,
 DC Input Switch
 Overvoltage Load Drop Protection,
 Residual Current (RCD) Detection,
 Surge protection level
Surge Protection Level
 TYPE II(DC), TYPE II(AC)
Interface
 Communication Interface
RS485/RS232/CAN
129 | P a g e
 Monitor Mode:
GPRS/WIFI/Bluetooth/4G/LAN
General Data
 100% unbalanced output, each phase
 AC couple to retrofit existing solar
system
 Max. 10 pcs parallel for on-grid and off-
grid operation;
 Support high voltage multiple batteries
in parallel
 Max. charging/discharging current of
100A
 High voltage battery, higher efficiency
 6 time periods for battery
charging/discharging
 Support storing energy from diesel
generator
 Operating Temperature Range (℃): -40
to +60℃, >45℃ Derating
 Permissible Ambient Humidity: 0-100%
 Permissible Altitude: 2000m
 Noise (dB): ≤65
 Ingress Protection(IP) Rating: IP 65
 Inverter Topology: Non-Isolated
 Over Voltage Category: OVC II(DC),
OVC III(AC)
 Cabinet Size (WxHxD mm): : less than
or equal to 527×894×294(Excluding
Connectors and Brackets)
 Weight (kg): less than or equal to 80
 Type of Cooling: Intelligent Air Cooling
Warranty: 5 Years
With all accessories

130 | P a g e
1.5 High voltage LiFePO4 Main Parameter UN38.3/CE/ Pcs
battery  Battery Type : LiFePO4(LFP) CE-EMC/
 Nominal Voltage: 51.2Vdc IEC/62040
 Rated Capacity: 100Ah
 Rated Energy : 5.12kWh
 Nominal Charge/Discharge Current : 100A
 Peak. Discharge Current:125A
 DOD=90%, 0.3C charging and
discharging@ 250c
 Battery Module Qty In Series up to: 17
 Charge Temperature: 0 up to 55°C
 Discharge Temperature: -20℃ up to 55°C
 Storage Temperature: 0℃ up to 35°C
 Ingress Protection: IP20
 Dimension (W/D/H): : less than or equal to
440*570*133mm
 Weight: Approximate less than or equal to
44kg
Status Indicator
 Yellow: Battery High Voltage Power On
 Red: Battery System Alarm
 Communication Port: CAN2.0/ RS485
 Humidity: 5%~85%RH
 Altitude: ≤2000m
 IP Rating of Enclosure: IP20
 Installation Location: Rack Mounting
 Storage Temperature (°C): 0~35
 Recommend Depth of Discharge: 90%
 Cycle Life: 25±2°C,0.5C/0.5C,
EOL70%≥6000
Warranty: 5 years
With all accessories
1.6 High Voltage Battery Operating Voltage: 120-1000Vdc UN38.3/CE/ Pcs
cluster control box Nominal Charge/Discharge Current: 100A CE-EMC/
with all accessary Maximum Charge/Discharge Current: 125A IEC/62040
DC Input Rating: 12±2%V/4.15A
131 | P a g e
Operating Temperature Range: -20~65°C or
higher
Ingress Protection: IP20
Dimension (W/D/H): : less than or equal to
440*570*150mm
Weight Approximate: less than or equal to
17kg
Warranty: 5 years
With all accessories
1.7 Battery Cabinet with all accessories UL 9540 Pcs

1.8 Earthing for Solar Earthing system must be separated of the IEC/EN set
PV System: main earthing system to obtain 2-ohm max 61000-6-
resistance. 1/2/3/4
The item includes (3copper electrodes
15mm2 driven into ground, manholes with cast
iron cover (5 Ton) with hinge, earth joints, clamps,
ducts, conduits and 50 mm2 flexible earthing
copper wires and cables from the PV system
components and steel structure to the electrode to
complete the system as specifications, drawings
and as per the approval.
For PV solar 10 mm2 flexible earthing copper
wires shall be in-between PV panels
For steel structure 16mm2 flexible earthing
copper wires shall be from 3 different points
in each string.
With all accessories
1.9 Cables and connectors required to wire the whole system as the wire size IEC 60228 Mete
and quantity difference depending the connection point UL 44 r
1.10 document Preparation (design, manual and installation drawing )

1.11 A complete and reliable fence that protects the solar panels and concrete basement (shoe) for the solar
panel (if necessary).
1.12 if any

132 | P a g e
Knowledge transfer and Experience sharing: Bidders must facilitate knowledge transfer and experience sharing
from solar PV manufacturers for a group of 6 trainees
Transportation, Supply, Installation, testing, commissioning and training for all campuses

Total cost(including VAT, tax)

Note:
Any minor equipment and material may not be specifically mentioned in these specifications but the bidders are required to make the system complete in
a every respect in accordance with technical specification and the same shall be deemed to have been covered under the scope of these specifications and
shall be provided by the bidder / supplier within the quoted price.

133 | P a g e
4. LOT TWO: Supply, Installation, Testing and Commissioning Streetlight for Aksum University (to be
installed in main campus, shire campus and Referral Hospital)

No Items Name Items with their description (detail specification ) Stand Unit Qty Unit Total
ards price price
Streetlight
1 Luminaire: 80W LED with LDR solar street lamp Pcs 200
(Light), System voltage 24VDC, Luminous Flux
12,000lm with efficiency 150lm/W, LED Light
Source Bat-wing type (150°*75°), Color Rendering
Index ≥Ra70, Color. Temperature
3000K/4000K/5000K/5700K, Lamp head: 6063 Die-
casting aluminum and PC, fast lamp, housing heat
dissipation ,corrosion prevention, Working Ambient
Temperature -40℃ ~ +60℃, Work Life >50000Hrs.
Warranty 3 years,
With all accessories.
Panel: Mono Crystalline Solar Panel, Maximum Pcs 200
power at STC: 205W, power tolerance 0% ~+3 %,
All in two Solar LED Operating Temperature -40oC - 50oC, Surface
Streetlight Maximum Load Capacity 5400Pa, Allowable Hail
Load Ø25mm_23m•s¹ ,ֿ Module Efficiency > 18%, ISO
Cell efficiency >18.56%and more than 25 years life and CE
time
Warranty: 3 year
With all accessories.
Battery: 3072WH Lithium FePO4 Battery, 120AH, Pcs 200
Max. Charging Current 15A, Self-consumption (Av.)
≤5.0mA, Operating Temp. Range minus -20 °C
~75°C, Max. Rated Load Current 15A, Efficiency
95%, Cycle life 3000~5000 times, and 4-period
Energy Saving Mode available.
134 | P a g e
Warranty: 3 years,
With all accessories.

Charge controller: type MPPT (maximum power Pcs 200


point tracking) Rated voltage DC 24VDC, Max.
charging current 15A, Self-consumption Average static
power consumption 17mA, Efficiency 99%, Maximum
Solar panel input 400W Maximum, Solar panel voltage
input 60VDC, Charging conversion efficiency 90% ~
96%, Load transfer efficiency 90% ~ 96%, Current
output 70mA~56000mA. Over voltage protection 34V
DC, Float charge 15V~31V, Temperature
compensation 3.0mV/℃/2V, Working temperature -35
°C ~65°C. All fault protection and anti-rust and anti-
corrosion,
Warranty: 3 year
With all accessory.
Single Arm Standard and Pipe Type bracket Pcs 200
1500mm long and 60mm diameter and water proof
solar Panel bracket which supports the battery and
Solar Panel to be install on the existing pole. The price
includes work to replace the existing AC LED Light to
Solar Street light,
With all accessory.
2 if any
Transportation, Supply, Installation, testing and commissioning for all campuses

Total cost(including VAT, tax)

Note:
Any minor equipment and material may not be specifically mentioned in these specifications but the bidders are required to make the system complete in
a every respect in accordance with technical specification and the same shall be deemed to have been covered under the scope of these specifications and
shall be provided by the bidder / supplier within the quoted price.
135 | P a g e
5. TECHNICAL EVALUATION AND PRE-QUALIFICATION CRITERIA FOR LOT ONE (SOLAR PV
SYSTEM)
5.1. Pre-qualification requirement for lot one
i. The bidders should specify material brand name, model, manufacturer company name and origin of country.
ii. Bidders must have at least Electromechanical contractor Grade one – (1) Certificate of Competence.
iii. The bidders shall fulfill relevant trade license for the assignment to the national by-laws and decrees.
iv. Bidders must include manufacturer authorization and datasheets for each items. Test certificates for each item from an authorized institution
(accredited laboratory) with their submission.
v. Site assessment is must.
vi. Bidders must meet the specifications.
vii. The bidder must have relevant work experience in solar power system projects, starting from September 2011 E.C up to the date of tender
opening. This means the bidder must have successfully completed at least one project (contract) during this specified period.
viii. The bidder must provide evidence of liquid assets amounting to 60,000,000 (sixty million) ETB or greater, verified by an official statement
from a recognized bank or financial institution.
ix. Subcontracts have to be properly and lawfully signed.
x. Each page of the offer document shall be properly signed and stamped.
xi. Bidder should supply, transport, install, test and commission in all specified sites, and allocate adequate man power and machinery.
xii. System Type: must be hybrid system
xiii. As part of the bidding process, all bidders are mandated to submit comprehensive engineering design and system layout documentation for
each building separately. Additionally, all bidders are required to deliver a presentation of their design and system layout to the evaluation
committee. Failure to submit the required documentation or deliver the presentation will result in immediate disqualification from bidding
process.
136 | P a g e
xiv. Inspections and commissioning Tests
The following inspections and commissioning tests shall be performed:
Inspection of the supply sets of materials, transportation and delivery condition shall be conducted by Aksum university technical officers prior
to arrival and transportation to the final destination as appropriate carried at the supplier’s premises, in Addis Ababa or beneficiary sites.
Tests for proper installation for the main apparatus and the complementary stands, as well as, product commissioning shall be conducted by
authorized and responsible parties.
Inspect all sets of goods and materials incorporated are new, unused, and of the most recent or current models, and check for recent improvements
and amendments whether incorporate in design of the supply.

xv. Warranty
At the time of contract execution, the Contractor must provide warranties and guarantees for the PV installation. Bid respondent shall fully define in its
document the warranty offered.
Bidders must meet warranty requirements with the following:
I. System warranty:
 The number of system breakdowns over three (3) years should be less than ten per cent (10%) of the number of systems installed to each building.
 The number of system breakdowns per year should be less than three per cent (3%) of the number of systems installed to each building.
 Should any faults arise, this warranty shall be covered for the necessary component replacement free of charge for full functionality to be restored
within seven (7) working days.
 Should any faults arise, this warranty shall be covered for the necessary maintenance free of charge for one (1) year.
II. Annual energy performance warranty:
The bidder should provide the warranty for the performance of the energy for One year (1year)
xvi. Documentation and operation manual:
Successful bidders should have to provide manufacturer’s documents of technical specifications, maintenance and operation and users manuals of each
component installed.

137 | P a g e
List of installed components and including spare parts, tools, associated manufactures literature and warranty claim should be handover to users of each
installed components.
The supplier should have to prepare and provide user’s manual intended for the users. The user’s manual should be in local language if possible otherwise
in English and has to be simple and easy to understand.
The user manual shall consist at least the following:
• Briefing of signal indication on charge control: battery charging, battery low voltage, and battery overcharge. The relationship between energy
available on a daily basis and sunlight conditions clearly and easily shall be explained.
• Description of disconnect breakers and routine attendance.
• Proper system operation including load limitation; suggested operation, weather condition load management during periods of inclement weather.
• Briefing shutdown procedures in cases of fault,
• User level troubleshooting guide.
• Contact information for warranty claim, maintenance and access to spare parts.
xvii. Training
The training will be split into three major components: System installation, system operation and maintenance and demand side management.
User training should provide to the users at each installed site. Bidders for high voltage hybrid PV system projects must demonstrate a comprehensive
understanding of solar energy fundamentals, specifically related to hybrid systems that integrate both photovoltaic and energy storage technologies. They
should have hands-on experience in the design and sizing of high voltage systems, including site assessments and compliance with relevant electrical
codes and safety standards. Proficiency in installation practices, safety protocols, and the permitting process is essential. Additionally, bidders must exhibit
skills in performance monitoring, maintenance procedures, and troubleshooting. An understanding of financial aspects such as cost analysis, ROI, and
project financing options is crucial. Strong customer engagement and project management capabilities, along with awareness of emerging technologies in
high voltage solar applications, are required.
xviii. Knowledge transfer and Experience sharing
Bidders must facilitate knowledge transfer and experience sharing from solar PV manufacturers for a group of 6 trainees. This requirement includes
providing a detailed schedule and location for factory training sessions. Additionally, bidders are expected to obtain a letter of acceptance from the

138 | P a g e
manufacturer, confirming participation in the training. This letter should be addressed to the Contractor and must reference Aksum University, along
with its procurement number and Lot Number for this specific contract.
xix. The Contractor shall install in the system room warning signs for general and personal safety.

5.2. Technical evaluation and qualification criteria for lot one

This section contains all the factors, methods and criteria that the employer shall use to evaluate a bid and determine whether a bidder has the required
qualifications. No other factors, methods or criteria shall be used.
To qualify for award of the Contract, bidders shall meet the minimum qualifying criteria for each Item:
Technical Evaluation Criteria Weight Remark
No. %
1 Annual turnover The peak annual turnover of the bidder over the last five years must be greater than or 10
equal to 90,000,000 (ninety million) ETB. Bidders meeting this criterion will receive full
marks, while other bidders will be scored proportionally with respect to the specified value.
2 Engineering Standard design procedures (procedures and formulas) 20
System Design Sizing of solar PV array, (4%)
Sizing of battery, (4%)
Sizing of inverter (built in MPPT charge controller), (4%)
Sizing of cable size and all protection devices. (4%)
Additional technology and future expansions (4%)

2 Engineering Panel layout (8%) 20


System lay out Battery layout and Inverter layout (6%)
System set up (6%)
4 Completion and Planning, scheduling and methodology to supply, installation, testing and commissioning 5
submissions of (2%). The better performance gets full mark, while other bidders' scores will be calculated
the system proportionally. Training delivery and methodology (3%). The better training delivery and

139 | P a g e
planning, methodology will get full mark, while other bidders' scores will be calculated
scheduling and proportionally.
methodology,
training
5 Capabilities of Experience: Attach the authorized document for the largest solar power system project 22
the contractor (in kW) you have either completed or are currently working-on projects; with ongoing
(Bidder's Work solar power system projects required to be at least 70% complete. For ongoing solar power
Experience, system project, an authorized letter from the client confirming the 70% completion must
personal be provided. The bidder with the largest solar power system project will receive full points,
qualification, while other bidders' scores will be calculated proportionally. (12%)
equipment and Any award related to solar power system projects granted to your company, with a system
machinery) size of 20 kW or greater, including contributions in system size, quality, and overall
activities, will be taken into consideration. Any award for a solar power system projects
with a system size of less than 20 kW will not be considered. (5%) bidders who have a
number of authorized awards will get full mark, while other bidders' scores will be
calculated proportionally.
Availability of personnel in local agent trained for any particular brand (for any solar
system brand) (5%). Bidders must submit the authorized personnel’s training certificate
and personal profile for any particular brand. Bidders who have a number of authorized
availability of personnel in local agent trained for any particular brand will get full mark,
while other bidders' scores will be calculated proportionally.
Technical Expertise: 10
One Project Manager: with a minimum of BSc. degree in electrical, electromechanical
engineering, or renewable energy engineering at least five (5) years of total work
experience, including a minimum of three (3) years in solar power system projects. (3%)
Four Electrical Engineers: each with a minimum of BSc. degree in electrical,
electromechanical or renewable energy engineering, at least four (4) years of total work
experience, including a minimum of three (3) years in solar system projects. And one civil
engineer: with a minimum of BSc. degree in Civil Engineering, at least 5 years work
experience in civil engineering projects. (3%).
Four Electricians: each with a minimum of BSc. degree in electrical engineering, at least
four (4) years total work experience, including a minimum of two(2) years in solar power
system projects. (2%)

140 | P a g e
Two Junior Electricians: each with a minimum of diploma in electricity from technical
school, at least four (4) years total work experience, including a minimum of two(2) years
in solar power system projects. (1%)
One Surveyor: with a minimum of diploma in surveying from technical school, at least
four (4) years’ work experience in civil engineering projects. (1%)
Technical experts who have maximum educational background and maximum work experience
in solar power system projects will get full point, while other bidders' scores will be calculated
proportionally. Technical experts must attach work experience and educational background
document. Work experience must provide a valid salary document from their current or
previous employer, confirm their status as legal tax payer, and submit official documentation
to validate their work experience.

Machinery and Equipment: 13


1. Loader minimum capacity 3m3................ 1 in number (1%)
2. Truck mounted crane above 2 ton....................... 1 in number (2%)
3. Light Duty Truck min 3-5 ton.................. 1 in number (1%)
4. Pick up min of 5 quintal............................. 1 in number (1%)
5. Concrete Mixer 350lit................................ 2 in number (1%)
6. Concrete Vibrator.......................................2 in number (1%)
7. Electrical Toolkit…………………………3 in number (1%)
8. Mechanical Toolkit……………………….2 in number (1%)
9. Welding Machine....................................... 2 in number (1%)
10. Total Station............................................... 1 in number (1%)
11. Steel scaffolding....................................... 250m2 (1%)
12. Forklift min 2 ton......................................... 1 in number (1%)

With every work accessories to complete the project. The bidders must submit the required
documents (such as Lib-re) of the machinery. If the equipment and machinery is not owned by
the supplier, the bidder must submit a valid contract giver and contract receiver agreement
document. The bidder has to attach a copy of the renewed ownership document of the
Machinery/Equipment, and during opening of tender the original ownership document must
be available to authenticate with the copy document submitted, If the original ownership
document is held in a bank or other financial institutions, an original letter must be provided
written within six months before opening of the tender by the bank or institution that holds the
original document explaining this fact during the opening of the tender and verifies its copy. In
141 | P a g e
addition, the bidders must ensure that all machines used for the project have undergone annual
inspection and possess valid renewal certificates from the relevant regulatory authorities. Proof
of compliance, including inspection reports and renewal documents, must be submitted as part
of the bid.
Total mark (%)

N.B
Every document submitted will be checked by the tender. If found fake, the bidder will automatically be rejected.
Bidders should come and visit the site for design and solar system installation in Aksum University buildings on the Roof, but if the
roof is not enough give priority to Car Parking and on the Ground respectively according to master plan of the university.
The production date of the battery must not exceed twelve (12) months from the date the bidders is awarded the contract.
The bidders after passing the pre-qualification criteria, if they get 70% or more in the technical evaluation criteria they will pass to
the next financial evolution, otherwise, it will be rejected.

5.3. Final score for lot one


Evolution criteria Weight Score Remark
Technical Evaluation and Qualification 70%
Financial Evaluation 30%
Total score (100%)
The final score for each bidder will be calculated as = Technical Evaluation and Qualification Score (70%) + financial (30%) should be ranked based
on their score.

142 | P a g e
6. TECHNICAL EVALUATION AND PRE-QUALIFICATION CRITERIA FOR LOT TWO (SOLAR

STREETLIGHT)

6.1. Pre-qualification requirement for lot Two


I. The bidders should specify material brand name, model, manufacturer company name and origin of country.
II. Bidders must have at least Electromechanical contractor Grade one – (1) Certificate of Competence.
III. The bidders shall fulfill relevant trade license for the assignment to the national by-laws and decrees.
IV. The bidder must provide evidence of liquid assets amounting to 6,100,000 (six million, one hundred thousand) ETB or greater, verified by
an official statement from a recognized bank or financial institution.
V. Site assessment is must.
VI. Bidders must meet the specifications.
VII. The bidder must submit a technical datasheet for the package, a test report, and an ISO and CE authorized certificate related to the sample
provided by an authorized supplier.
VIII. Before commencing the project, the winning bidder must submit a sample that fully complies with all specifications provided in the bid
within a maximum of 4.5 months. Additionally, the sample must operate continuously for 24 hours or two days of autonomy after being
fully charged, without receiving any solar input, while producing a light output of 12,000 lumens and maintaining at least 30% battery
capacity. The sample will undergo a thorough technical evaluation to ensure compliance with these performance standards before final
approval.
IX. The sample of the solar streetlight package must be submitted along with the Ethiopian Ministry of Trade and Regional Integration
(MoTRI) pre-export verification of conformity (COC).
X. The bidder must have relevant work experience in solar power system projects, starting from September 2011 E.C up to the date of tender
opening. This means the bidder must have successfully completed at least one project (contract) during this specified period.

XI. Subcontracts have to be properly and lawfully signed.

143 | P a g e
XII. Each page of the offer document shall be properly signed and stamped.
XIII. Bidder should supply, transport, install, test and commission in all specified sites, and allocate adequate man power and machinery.
XIV. Inspections and commissioning Tests
The following inspections and commissioning tests shall be performed:
Inspection of the supply sets of materials, transportation and delivery condition shall be conducted by Aksum university technical officers prior
to arrival and transportation to the final destination as appropriate carried at the supplier’s premises, in Addis Ababa or beneficiary sites.
Tests for proper installation for the main apparatus and the complementary stands, as well as, product commissioning shall be conducted by
authorized and responsible parties.
Inspect all sets of goods and materials incorporated are new, unused, and of the most recent or current models, and check for recent improvements
and amendments whether incorporate in design of the supply.
XV. Warranty
At the time of contract execution, the Contractor must provide warranties and guarantees for the streetlight solar system installation. Bid respondent shall
fully define in its document the warranty offered.
Bidders must meet warranty requirements with the following:
i. System warranty:
 The number of system breakdowns over three (3) years should be less than ten per cent (10%) of the number of systems installed for this lot.
 The number of system breakdowns per year should be less than three per cent (3%) of the number of systems installed for this lot.
 Should any faults arise, this warranty shall be covered for the necessary component replacement free of charge for full functionality to be restored
within seven (7) working days.
 Should any faults arise, this warranty shall be covered for the necessary maintenance free of charge for one (1) year.
ii. Annual energy performance warranty:
The bidder should provide the warranty for the performance of the energy for One year (1year)

144 | P a g e
6.2. Technical evaluation and qualification criteria for lot two

No Factor Evaluation and Qualification Criteria

1 Annual Turnover The peak annual turnover of the bidder over the last five years must be greater than or equal to 48,257,000 (forty
eight million, two hundred fifty seven thousand) ETB. Bidders meeting this criterion will receive full marks, while
other bidders will be scored proportionally with respect to the specified value. Total Weight (15%).
2 Specific Experience Participation as a prime contractor, sub-contractor or joint venture in the supply, installation, testing, and
commissioning successfully and substantially completed projects that is similar to the proposed works (Solar LED
streetlight). The similarity shall be based on the number of awards, performance, complexity, methods/technology
or other characteristic describes in the bill quantity employer’s requirements. The bidder with the maximum number
of completed similar projects will receive twenty five (25) mark, while other bidders' scores will be calculated
proportionally. Bidders must submit authorized documents detailing their specific work experience. Total Weight
(25%).
3 General Experience Participation as a prime contractor, sub-contractor or joint venture in the supply, installation, testing, and
commissioning in successfully and substantially completed projects that is related to the proposed works (Solar PV
system, solar pump, streetlight and other electromechanical works). The related experience shall be based on the
physical size, number of awards, performance, complexity, methods/technology or other characteristic describes in
the bill quantity employer’s requirements. The bidder with the maximum number of completed related projects will
receive fifteen (15) points, while other bidders' scores will be calculated proportionally. Bidders must submit
authorized documents detailing their related work experience. Total Weight (15%).
4 Personnel One Project Manager: with a minimum of BSc. Degree in Electrical, electromechanical or renewable energy
engineering, at least five (5) years of total work experience, including a minimum of three (3) years in solar power system
projects. (7%).
One Site Manager: with a minimum of BSc. in electrical, electromechanical or renewable energy Engineering, at
least four (4) years of total work experience, including a minimum of three (3) years in solar power system projects.
(7%).
Two Electricians: each with a minimum of a Diploma from technical school, at least three (3) years of total work
experience, including a minimum of two (2) years in solar power system projects. (6%).

Technical experts who have maximum level of education and work experience in solar power system projects will get
full point, while other bidders' scores will be calculated proportionally. Technical experts must attach work experience
and educational background document. Work experience must provide a valid salary document from their current or
previous employer, confirm their status as legal tax payer, and submit official documentation to validate their work
experience. Total Weight (20%).

145 | P a g e
5 work methodology Work methodology (2.5%) and Material & Equipment schedule (2.5%). The better performance work methodology,
material and equipment schedule will get full point, while other bidders' scores will be calculated proportionally.
Total Weight (5%).
6 Equipment and Truck mounted crane above 2 ton ………….……one in number (8%).
machinery Pick up min of 5 quintal..............................one in number (4%).
Welding Machine ………………………....one in number (4%)
Electrical Toolkit………………………….3 in number (2%)
Mechanical Toolkit………………………..2 in number (2%)
With every work accessories to complete the project.

The bidders must submit the required documents (such as Lib-re) of the machinery. If the equipment and machinery is
not owned by the supplier, the bidder must submit a valid contract giver and contract receiver agreement document. The
bidder has to attach a copy of the renewed ownership document of the Machinery/Equipment, and during opening of
tender the original ownership document must be available to authenticate with the copy document submitted, If the
original ownership document is held in a bank or other financial institutions, an original letter must be provided written
within six months before opening of the tender by the bank or institution that holds the original document explaining this
fact during the opening of the tender and verifies its copy. In addition, the bidders must ensure that all machines used for
the project have undergone annual inspection and possess valid renewal certificates from the relevant regulatory
authorities. Proof of compliance, including inspection reports and renewal documents, must be submitted as part of the
bid. Total Weight (20%).
Total mark (100%)

N.B
Every document submitted will be checked by the tender. If found fake, the bidder will automatically be rejected.
The production date of the battery must not exceed twelve (12) months from the date the bidders is awarded the contract.
The bidders after passing the pre-qualification criteria, if they get 70% or more in the technical evaluation criteria they will pass to the
next financial evolution, otherwise, it will be rejected.

146 | P a g e
6.3. Final score for lot two
Evolution criteria Weight Score Remark
Technical Evaluation and Qualification 70%
Financial Evaluation 30%
Total score (100%)
The final score for each bidder will be calculated as = Technical Evaluation and Qualification Score (70%) + financial (30%) should be ranked based
on their score.

147 | P a g e