Technical data sheet GRC230G-5
Rotary actuator for rotary valves and butterfly
valves
• Torque motor 40 Nm
• Nominal voltage AC 100...240 V
• Control Open/close
• Running time motor 35 s
• Optimum weather protection for use outdoors
Technical data
Electrical data Nominal voltage AC 100...240 V
Nominal voltage frequency 50/60 Hz
Nominal voltage range AC 85...265 V
Power consumption in operation 6W
Power consumption in rest position 1W
Power consumption for wire sizing 11 VA
Connection supply / control Cable 1 m, 3x 0.75 mm² (halogen-free)
Parallel operation Yes (note the performance data)
Functional data Torque motor 40 Nm
Manual override with push-button, can be locked
Running time motor 35 s / 90°
Sound power level, motor 35 dB(A)
Position indication Yes
Safety data Protection class IEC/EN II, reinforced insulation
Protection class UL II, reinforced insulation
Degree of protection IEC/EN IP66/67
Degree of protection NEMA/UL NEMA 4X
Enclosure UL Enclosure Type 4X
EMC CE according to 2014/30/EU
Low voltage directive CE according to 2014/35/EU
Certification IEC/EN IEC/EN 60730-1 and IEC/EN 60730-2-14
Type of action Type 1
Rated impulse voltage supply / control 2.5 kV
Pollution degree 4
Ambient humidity Max. 100% RH
Ambient temperature -30...50°C [-22...122°F]
Ambient temperature note -40...50°C for actuator with integrated heating
Storage temperature -40...80°C [-40...176°F]
Servicing maintenance-free
Mechanical data Connection flange F05
Weight Weight 3.4 kg
www.belimo.com GRC230G-5 • en-gb • 2023-12-12 • Subject to change 1/5
Technical data sheet GRC230G-5
Safety notes
• This device has been designed for use in stationary heating, ventilation and air-conditioning
systems and must not be used outside the specified field of application, especially in aircraft
or in any other airborne means of transport.
• Caution: Power supply voltage!
• Only authorised specialists may carry out installation. All applicable legal or institutional
installation regulations must be complied with during installation.
• Junction boxes must at least correspond with enclosure IP degree of protection!
• The cover of the protective housing may be opened for adjustment and servicing. When it is
closed afterwards, the housing must seal tight (see installation instructions).
• The switch for changing the direction of rotation may not be adjusted.
• The angle of rotation is not permitted to be subjected to mechanical limitation. It is
forbidden to alter the mechanical end stops.
• The device may only be opened at the manufacturer's site. It does not contain any parts that
can be replaced or repaired by the user.
• The device contains electrical and electronic components and must not be disposed of as
household refuse. All locally valid regulations and requirements must be observed.
• The device is not designed for applications where chemical influences (gases, fluids) are
present or for utilisation in corrosive environments in general.
• The actuator may not be used in plenary applications (e.g. suspended ceilings or raised
floors).
• The materials used may be subject to external influences (temperature, pressure,
construction fastening, effect of chemical substances, etc.), which cannot be simulated in
laboratory tests or field trials. In case of doubt, we definitely recommend that you carry out
a test. This information does not imply any legal entitlement. Belimo will not be held liable
and will provide no warranty.
• Flexible metallic cable conduits or threaded cable conduits of equal value are to be used for
UL (NEMA) Type 4X applications.
• When used under high UV loads, e.g. extreme sunlight, the use of flexible metallic or
equivalent cable conduits is recommended.
Product features
Fields of application The actuator is particularly suitable for utilisation in outdoor applications and is protected
against the following weather conditions:
- UV radiation
- Rain / Snow
- Dirt / Dust
- Air humidity
- Alternating climate / frequent and severe temperature fluctuations (Recommendation: use
the actuator with integrated factory-installed heating which can be ordered separately to
prevent internal condensation)
Simple direct mounting Simple direct mounting on the rotary valve or butterfly valve with mounting flange. The
mounting orientation in relation to the fitting can be selected in 90° steps.
Manual override Manual override with push-button possible (the gear train is disengaged for as long as the
button is pressed or remains locked).
The housing cover must be removed for manual override.
Adjustable angle of rotation Adjustable angle of rotation with mechanical end stops. Standard setting 0...90°. The housing
cover must be removed to set the angle of rotation.
High functional reliability The actuator is overload protected, requires no limit switches and automatically stops when
the end stop is reached.
www.belimo.com GRC230G-5 • en-gb • 2023-12-12 • Subject to change 2/5
Technical data sheet GRC230G-5
Accessories
Electrical accessories Description Type
Auxiliary switch 2x SPDT add-on, grey S2A GR
Feedback potentiometer 140 Ω add-on P140A
Feedback potentiometer 1 kΩ add-on P1000A
Feedback potentiometer 10 kΩ add-on P10000A
Options ex works only Description Type
Heater, with adjustable thermostat HT230-MG
Heater, with mechanical humidistat HH230-MG
Electrical installation
Caution: Power supply voltage!
Parallel connection of other actuators possible. Observe the performance data.
Direction of rotation switch is covered. Factory setting: Direction of rotation Y2.
3-point control only allowed with ball valves, not allowed with butterfly valves.
Wire colours:
1 = blue
2 = brown
3 = white
Wiring diagrams
AC 230 V, open/close
www.belimo.com GRC230G-5 • en-gb • 2023-12-12 • Subject to change 3/5
Technical data sheet GRC230G-5
Operating controls and indicators
1 Direction of rotation switch
Switch over: Direction of rotation changes
2 Push-button and LED display green
Off: No power supply or malfunction
On: In operation
Press button: Triggers angle of rotation adaptation, followed by standard mode
3 Push-button and LED display yellow
Off: Standard mode
On: Adaptation or synchronisation process active
Press button: No function
4 Manual override button
Press button: Gear train disengages, motor stops, manual override possible
Release button: Gear train engages, standard mode
5 Service plug
For connecting parametrisation and service tools
Check power supply connection
2 Off and 3 On Possible wiring error in power supply
www.belimo.com GRC230G-5 • en-gb • 2023-12-12 • Subject to change 4/5
Technical data sheet GRC230G-5
Dimensions
Further documentation
• The complete product range for water applications
• Data sheets for rotary valves and butterfly valves
• Installation instructions for actuators and/or rotary valves and butterfly valves
• General notes for project planning
www.belimo.com GRC230G-5 • en-gb • 2023-12-12 • Subject to change 5/5