Seci-cg100-Dwg-civ-080g-Calc-r1-Design Report For String Inverter Foundation and Mounting Structure - Cat IV

The document presents the design report for the string inverter foundation and mounting structure for a 100 MW solar PV power plant in Rajnandgaon, Chhattisgarh. It includes calculations for wind and seismic loads, dead loads, and structural details using specific IS codes. The report concludes with the adoption of a 300mm diameter and 1.2m length pile based on load comparisons.

Uploaded by

shubhamnec95
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
301 views8 pages

Seci-cg100-Dwg-civ-080g-Calc-r1-Design Report For String Inverter Foundation and Mounting Structure - Cat IV

The document presents the design report for the string inverter foundation and mounting structure for a 100 MW solar PV power plant in Rajnandgaon, Chhattisgarh. It includes calculations for wind and seismic loads, dead loads, and structural details using specific IS codes. The report concludes with the adoption of a 300mm diameter and 1.2m length pile based on load comparisons.

Uploaded by

shubhamnec95
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 8

TATA POWER SOLAR SYSTEM LIMITED

SECI-CG100-DWG-
CIV-080G-CALC DESIGN REPORT FOR STRING INVERTER
FOUNDATION AND MOUNTING STRUCTURE GA AND
DETAILS

TATA POWER SOLAR SYSTEM LIMITED

100 MW (AC) SOLAR PV POWER PLANT AT


RAJNANDGAON, CHHATTISGARH

APPROVAL CATEGORY: CAT IV

STRING INVERTER FOUNDATION AND MOUNTING


STRUCTURE GA AND DETAILS

REV. NO. R0 R1
ISSUE
INITIALS SIGN. INITIALS SIGN.

PPD. BY DM DM

CHD. BY GB GB
R1
APD. BY DMP DMP

DATE 14-12-2023 06-12-2024


TATA POWER SOLAR SYSTEM LIMITED
SECI-CG100-DWG-
CIV-080G-CALC DESIGN REPORT FOR STRING INVERTER
FOUNDATION AND MOUNTING STRUCTURE GA
AND DETAILS

STRING MONITORING BOX STRUCTURE DESIGN & DETAIL

PREFACE:

The purpose of this document is to furnish the design calculation for string
monitoring box mounting structure. We used ISMC 100 Section (C1) for columns,
ISMC 75 Section (B1) for beams and angle section for lateral bracing.

WIND LOAD CALCULATION.


EQUIPMENT WIND LOAD CALCULATION:
Equipment length= 1.18 m
Equipment width= 0.35 m
Equipment height= 0.733 m
Equipment weight= 1.3 kN (130kG as per specification)
No. of supporting the equipment= 4 nos

Wind Load Calculation:


Basic wind speed, Vb= 39 m/s Cl.6.2, IS:875_3
Probabilty factor, k1= 1 Cl.6.3.1, IS:875_3
Terrain roughness and height factor, k2= 1.05 Cl.6.3.2, IS:875_3
Topography factor, k3= 1 Cl.6.3.3, IS:875_3
Importance factor for cyclonic region, k4= 1 Cl.6.3.4, IS:875_3
Design wind speed, Vz= Vb*k1*k2*k3*k4 Cl.6.3, IS:875_3
40.95 m/s
2
Wind pressure, pz= 0.6*Vz Cl.7.2, IS:875_3
2
1.01 kN/m
Wind directionality factor, Kd= 0.9 Cl.7.2.1, IS:875_3
Area averaging factor, Ka= 1 Cl.7.2.2, IS:875_3
Combination factor, Kc= 1
Design wind pressure, pd= Kd*Ka*Kc*pz Cl.7.2, IS:875_3
0.91

Using co-efficient of free standing walls,


Width to height ratio= 1.61
Drag co-fficient, Cf= 1.2 Table 26, IS:875_3
Wind force on equipment along-X= 0.28
Wind force on equipment along-Z= 0.94
Wind force on equipment along-X= 0.07
Wind force on equipment along-Z= 0.23
TATA POWER SOLAR SYSTEM LIMITED
SECI-CG100-DWG-
CIV-080G-CALC DESIGN REPORT FOR STRING INVERTER
FOUNDATION AND MOUNTING STRUCTURE GA
AND DETAILS

SEISMIC LOAD DETAILS (EQX)

SEISMIC LOAD DETAILS (EQZ)


TATA POWER SOLAR SYSTEM LIMITED
SECI-CG100-DWG-
CIV-080G-CALC DESIGN REPORT FOR STRING INVERTER
FOUNDATION AND MOUNTING STRUCTURE GA
AND DETAILS

Dead load of SMB is 130 kG as per GTP So for design considered 130 kG and equally distributed in 4
nodes.
DEAD LOAD DETAILS

WIND LOAD ‘Z’ DETAILS


TATA POWER SOLAR SYSTEM LIMITED
SECI-CG100-DWG-
CIV-080G-CALC DESIGN REPORT FOR STRING INVERTER
FOUNDATION AND MOUNTING STRUCTURE GA
AND DETAILS

WIND LOAD ‘X’ DETAILS

UTILIZATION RATIO
TATA POWER SOLAR SYSTEM LIMITED
SECI-CG100-DWG-
CIV-080G-CALC DESIGN REPORT FOR STRING INVERTER
FOUNDATION AND MOUNTING STRUCTURE GA
AND DETAILS

MAXIMUM DEFLECTION.

HEIGHT OF COLUMN IS = 1555 mm.


ALLOWABLE DEFLECTION IS = HEIGHT/240
ALLOWABLE DEFLECTION IS = 1555/240 = 6.47mm.
ACTUAL MAXIMUM DEFLECTION IS = 1.09 mm < 6.47mm. HENCE O.K

WELD DESIGN.
Max moment between vertical & horizontal member= 0.180kN-m
Max shear between vertical & horizontal member = 0.365 kN
Depth of horizontal member(d) = 75mm.
M/d = 0.180/0.075= 2.4kN
Total force for weld = 2.4+0.365= 2.765kN
Weld thickness = 4mm (assumed)
Weld length required = 2.765x10^3/(0.707x4x110) =8.89 mm.
So all round weld on both flange and webs are provided.
TATA POWER SOLAR SYSTEM LIMITED
SECI-CG100-DWG-
CIV-080G-CALC DESIGN REPORT FOR STRING INVERTER
FOUNDATION AND MOUNTING STRUCTURE GA
AND DETAILS

FOUNDATION DESIGN CALCULATION.


SUPPORT REACTION:

Horizontal Vertical Horizontal Moment


Node L/C Fx kN Fy kN Fz kN Mx kN-m My kN-m Mz kN-m
39 201 1.0(DL) 0 1.657 -0.001 -0.001 0 0
202 1.0(DL+EQX) -0.157 1.657 -0.001 -0.001 0 0.219
203 1.0(DL+EQZ) 0 1.865 -0.024 -0.012 0 0
204 1.0(DL-EQX) 0.157 1.657 -0.001 -0.001 0 -0.219
205 1.0(DL-EQZ) 0 1.45 0.023 0.01 0 0
206 1.0(DL+WLZ) -0.098 3.414 -0.534 -0.225 0 0.152
207 1.0(DL+WLX) -0.437 1.809 -0.001 -0.001 0 0.558
208 1.0(DL+WL-Z) 0.098 -0.179 0.571 0.237 0 -0.152
209 1.0(DL+WL-X) 0.437 1.505 0 0 0 -0.558
42 201 1.0(DL) 0 0.054 0.001 0 0 0
202 1.0(DL+EQX) 0 0.054 0.001 0 0 0
203 1.0(DL+EQZ) 0 -0.154 -0.133 0 0 0
204 1.0(DL-EQX) 0 0.054 0.001 0 0 0
205 1.0(DL-EQZ) 0 0.261 0.134 0 0 0
206 1.0(DL+WLZ) -0.098 -1.703 -1.244 0 0 0
207 1.0(DL+WLX) -0.115 -0.098 -0.195 0 0 0
208 1.0(DL+WL-Z) 0.098 1.89 1.296 0 0 0
209 1.0(DL+WL-X) 0.115 0.206 0.196 0 0 0
TATA POWER SOLAR SYSTEM LIMITED
SECI-CG100-DWG-
CIV-080G-CALC DESIGN REPORT FOR STRING INVERTER
FOUNDATION AND MOUNTING STRUCTURE GA
AND DETAILS

From the above table, Comparing the maximum loads with Pile capacity, so
we are adopting 300mm diameter and 1.2m length pile.