r0 - R.C.C Layout & Detail of Cabin Slab Lvl. - 24!05!2023

The document outlines the construction details for a bungalow project, including specifications for concrete grades, reinforcement bar sizes, and spacing for slabs and beams. It emphasizes the importance of adhering to specified dimensions, quality control for materials, and safety measures during construction. Additionally, it includes general notes on formwork, curing, and responsibilities of the contractor and engineer in charge.

Uploaded by

Bhaumik Gajjar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views1 page

r0 - R.C.C Layout & Detail of Cabin Slab Lvl. - 24!05!2023

The document outlines the construction details for a bungalow project, including specifications for concrete grades, reinforcement bar sizes, and spacing for slabs and beams. It emphasizes the importance of adhering to specified dimensions, quality control for materials, and safety measures during construction. Additionally, it includes general notes on formwork, curing, and responsibilities of the contractor and engineer in charge.

Uploaded by

Bhaumik Gajjar
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

BUNGLOW FOR KIRITBHAI

PROJECT
(KURSAN)
R.C.C LAYOUT & DETAIL OF CABIN SLAB LVL.

REGULAR ZONE : DIA 8 @ 150 C/C


TITLE

CONFINE ZONE : TOR 8 @ 75 C/C


Remarks

LATERAL TIES SPACING


PROJ. NO - DRG NO ST-03
DEVELOPMENT LENGTH
CONCRETE GRADE
DIA
M25
OF
TENSION

8 @ 175 C/C 8 @ 100 C/C


8 @ 175 C/C 8 @ 125 C/C
8 @ 175 C/C 8 @ 125 C/C
8 @ 175 C/C 8 @ 125 C/C
8 @ 175 C/C 8 @ 125 C/C
8 @ 175 C/C 8 @ 100 C/C
8 @ 175 C/C 8 @ 100 C/C
8 @ 175 C/C 8 @ 100 C/C
8 @ 175 C/C 8 @ 100 C/C
8 @ 175 C/C 8 @ 100 C/C
BARS

Right (mm)
Ldt (MM)
8 388
10 485
12 583

8mm 2 legged if not specified


16 777
20 971
25 1214
C5 B6 C6
S2 GENERAL NOTES :-

Mid (mm)
S1

STIRRUPS
1. CONCRETE MIIX FOR ALL SLABS & BEAM SHALL BE M-25.
2. CLEAR COVER TO REINFORCEMENT SHALL BE AS FOLLOWS:-
B5 FOOTING : 50 MM
COLUMN : 40 MM

5 SET
BEAM : 25 MM

LATERAL TIES
SLAB : 25 MM

B8
3. ALL DIMENSION ARE IN MM UNLESS OTHERWISE SPECIDFIED.
B4 S2 S2 4. ONLY WRITTEN DIMENSION SHALL BE FOLLOWED, ALL DRAWINGS

B5

B5
ARE NOT TO SCALE.
S2 5. STRIPPING TIME OF FORM WORK FOR CONCRETE WORK SHALL BE AS
FOLLOWS :
a) VERTICAL FORM WORK TO COLUMNS, WALLS, BEAMS : 24 HOURS

SHAPE
b) SOFFIT FORMWORK AND PROPS TO SLABS
S2

8 @ 100 C/C
8 @ 125 C/C
8 @ 125 C/C
8 @ 125 C/C
8 @ 125 C/C
8 @ 100 C/C
8 @ 100 C/C
8 @ 100 C/C
8 @ 100 C/C
8 @ 100 C/C
* SPANNING UP TO 4.5 M : 7 DAYS

Left (mm)
* SPANNING OVER 4.5 M : 14 DAYS
c) SOFFIT FORMWORK AND PROPS TO BEAMS
* SPANNING UP TO 6.0 M : 14 DAYS
* SPANNING OVER 6.0 M : 21 DAYS
B5

B10
6. ALL CONCRETE WORK SHALL BE MACHINE MIXED & MACHINE VIBRATED.

B7
TESTING OF CUBES SHALL BE AS PER IS 456:2000. CONCRETE TEST
B3 S2

B9
RESULT SHALL BE SUBMITTED TO US PERIODICALLY.

TOR 16
TOR 12
7. FOR ALL CONCRETE WORK HIGH STRENGTH OPC OF GRADE 53 COMPLAYING
S1 TO IS 8112 & IS 12269 SHALL BE USED. IF REQUIRED SPECIAL QUALITY OF

SCHEDULE OF COLUMNS 2ND TO CABIN SLAB LVL. (M-25, Fe-500)


CEMENT OR OTHER CEMENTATIOUS MATERAILS COULD BE USED.
B5 8. CEMENT,AGGREGATE ALL MATERIAL USED IN CONCRETE SHALL BE TESTED
ACCORDING TO RELATED IS STANDARDS PROCEDURE & REPORT SHALL
BE SUBMITTED TO US.

IB2 S2 S2 9. MAXIMUM SIZE OF AGGREGATE IS 20MM.

Length
(Right)
10. FORMWORK SHALL BE SUFFICIENTLY RIGID DURING PLACING & COMPACTION

LATERAL TIES
B5
B5
OF CONCRETE & BE WATER TIGHT TO PREVENT LOSS OF SLURRY FROM
CONCRETE, ENSURE SHAP,LINE & DIMENSION. FORMWORK SHALL BE

B8

B8
S2 S2 SUPPORTED BY THE WOODEN OR STEEL BASE PLATE TO SUPPORT FRESHLY
PLACED CONCRETE SAFELY TILL IT GET HARDENS TO CARRY WEIGHT WITHIN

PATTERN
PERMISSIBLE SAG.
11. PLAIN CEMENT CONCRETE(P.C.C) SHALL BE OF GRADE 1: 4 :8 / 1: 3 :6 WITH
MIN. THICKNESS OF 75 MM OR SPECIFIED.
12. ALL REINFORCEMENT SHALL BE FE500 GRADE TMT BARS.
13. HIGH STRENGTH DEFORM BARS CONFORMING TO IS 1786 WITH STRESS NOT
IB2 LESS THAN 500 N/MM2 TMT BAR SHALL BE PREFFRED.

EXTRA REINFORCEMENT
B5 14. ALL REINFORCEMENT SHALL BE THORUGHLY CLEANED OF ALL GREASE,

AT
S1 MILL SCALE, LOOSE RUST OR ANYTHING LIKELY TO DESTROY THE ADHESION
OF THE STEE TO THE CONCRETE.
S2 15. NO CONCRETEING SHALL BE START UNTILL BARS HAVE BEEN PLCED

NO. OF BARS
PROPERLY, TIED, COVER IS PLACED TO THE BARS & INSPECTED & APPROVED
C3 C4 BT THE ENGINEER IN CHARGE.
16. PROVIDE SUFFICENT CHAIRS & SPACERS TO KEEP THE BARS IN PROPER

+8- TOR 12
4- TOR 16
POSITION.
B1 17. MAXIMUM PERMISSILBLE FREE FALL OF CONCRETE IS 1.2 M.
18. ANY HOLE/POCKETS OR CORE CUTTING SHALL NOT BE DONE WITHOUT THE

Length
PERMISSION OF STRUCTURE ENGINEER.

(left)
19. ANY AMBIGUITY BETWEEN THE ARCHITECTURAL DRAWINGS AND

TOP REINFORCEMENT
STRUCTURAL DRGS MUST BE BROUGHT TO THE NOTICE OF THE
ARCHITECT / STRUCTURAL CONSULTANTS BEFORE THE WORK
PLAN OF CABIN SLAB COMMENCES..
20. EXPOSE SURFACE OF CONCRETE SHALL BE KEPT WET BY WATERING OR
COVEREDWITH A LAYER OF SACKING, CANVAS OR SIMILAR MATERIAL & KEPT
CONSTANTY WET FOR ATLEAST 7 DAYS FROM THE CASTING.
21. AT ALL COLD CONSTRUCTION JOINTS THE HARDEN CONCRETE SHALL BE

1ST SLAB LVL.


FOOTING LVL.
CHIPPED TO REMOVE ALL LOOSE MATERAILS. BEFORE POURING FRESH
CONCRETE THE SURFACE SHALL BE CLEANED WITH A WATER JET & LAYER
OF RICH CEMENT GROUT WITH BONDING AGENT SHALL BE USED.

Dia.
22. IT IS CONTRACOTORS RESPONSIBILITY TO STRICTLY ADHARE TO DRAWINGS

FROM
& DETAIL PROVIDED AS OUR RESPONSIBILITY IS LIMITTED TO PERIODIC

TO
SUPERVISION.
23. CONCRETE & STEEL QUALITY REPORTS IS SUBMITTED TO THE OWNER &
CONSULTANT.
24. TO MAINTAIN QUALITY OF WORK IS THE RESPONSIBILITY OF
CONTRACTOR/OWNER AT SITE.
25. ALL ARCHITECTURAL DIMENSION, SHAPE, ALINGNMENT ETC. SHALL BE
VARIFIED & GET IT EXECUTED AT SITE BY CONTRACOTOR & IT IS HIS
RESPONSIBILITY TO GET THEM VERIFIED WITH ARCHITECT.

Nos.
26. SAFETY OF ADJOINING BUILDING, STABILITY OF EXISTING STRUCTURE ,

C3,C4,C5,C6 230 X 525


SAFETY OF CONSTRUCTION WOK/PERSON WORKING ON SITE, ANY ACCIDENT

SIZE
OCCURE SUE TO PREMETURE DESHUTTERING, ANY COLLAPSE OF STRUCTURE
DURING CONSTRUCTION NOT DESIGN BY US THIS ALL FALLS IN
RESPONSIBILITY OF CONTRACTOR / OWNER IT IS NOT OUR RESPONSIBILITY.
27. COPYRIGHT OF THIS DRAWING IS BELONG TO CONSULTANT & NODUPLICATION OR
CHANGES IS MADE WITHOUT PERMISSION OF STRUCTURAL CONSULTANT.
28. COLUMN REDUCTIONS SHALL BE DONE IN THE DIRECTION OF ARROW AS
PER RELATED DRAWINGS.
29. WHEREVER SLAB IS SUNK, DENSITY OF SUNK MATERIAL SHALL BE LESS
THAN 16 KN/CU.M. PREFERABLY SUNK FILLING SHALL BE DONE BY USING

Dia.
COAL ASHES.

COL. NO.
12
10
12
10
12
12
12
12
12
12
STRAIGHT
30. IF LAPS ARE UNAVOIDABLE THAN NOT MORE THAN 50% OF BARS SHALL
BE LAPED AT ONE SECTION.

Nos.

NO.
2
2
2
2
2
2
2
2
2
2

SR.

3
BOTTOM EXTRA (CURTAIL)
Length

0.7L

0.7L

0.7L
0.7L
Dia.

16

12

12
16
SCHEDULE OF SLAB DETAIL (M:25,Fe-500)
Bars parallel Bars parallel to
Mark Thick. to short span long span Remark
Nos.

#8-175 C/C #8-200 C/C

2
1

1
S1 115 ONE WAY
ALT. BENT UP STRAIGHT
BOTTOM REINFORCEMENT

#8-175 C/C #8-200 C/C ONE WAY


S2 115
STRAIGHT STRAIGHT (TOP BOT. JALI)
L/4

L/4
L/4
R
AT

NOTE:- # 8/10 - 300 C/C TOP EXT.@ DISCONTINOUS EDGE


L/4

L/4
L/4
L
Dia.
BENT UP BAR

16

16
1-12+1-10
SCHEDULE OF BEAM CABIN SLAB LVL. (M-25, Fe-500)

Nos.

2
Dia.

12
12
12
12

12
16
STRAIGHT

2-12 + 1-10

2-12 + 1-10
2-12 + 1-10

2-12 + 1-10
Nos.

2
2
2
2

2
4
(mm)

415
450

450
375
375
450
450
450
450
450
D

GOOD FRO CONSTRUCTION


R0 24-05-23 BHAVESH C-01
SIZE

REV. DATE DESCRIPTION DRAWN COPY

ARCHITECT -
R.C.C LAYOUT & DETAIL OF
TITLE
(mm)

CABIN SLAB LVL.


230

230
230

230
230
115
115
115
115

115

DRG NO. DESIGN NEEL


B

ST-04 DRAWN BHAVESH


DATE 24-05-2023 CHECKED NEEL
to creation

from concept

CONSULTANT
BEAM

B10
NO

IB2
B1

B3

B5

B7
B8
B4

B6

B9

THE EDIFICE CONSULTANT


NEEL J. PATELM.Tech (Structure)

THE
22,WESTERN VILLA,OPP. SAURABH POLICE CHOKI,
ADAJAN,SURAT-395009.
EMAIL ID :- [email protected]
MO. No. :- 8980660536 EDIFICE

You might also like