S14 - Interlocking With Metal To Metal Relays - Siemens - A4 - September 2022 - 1727180541459
S14 - Interlocking With Metal To Metal Relays - Siemens - A4 - September 2022 - 1727180541459
INTERLOCKING WITH
METAL--METAL RELAYS (SIEMENS)
The Material Presented in this IRISET Notes is for guidance only. It does not over
rule or alter any of the Provisions contained in Manuals or Railway Board’s
directives
Revision History
S28 A1 -----
A2
A3 October 2013
A4 September 2022
Version No A4
In case of any suggestions please write to LS2/PS1 or mail to LS2/PS1 at email address
[email protected]/ [email protected]
© IRISET
“This is the Intellectual property for exclusive use of Indian Railways. No part of
this publication may be stored in a retrieval system, transmitted or reproduced in
any way, including but not limited to photo copy, photograph, magnetic, optical or
other record without the prior agreement and written permission of IRISET,
Secunderabad, India”
http://www.iriset.indianrailways.gov.in
CONTENTS
CHAPTER 1: INTRODUCTION .................................................................................................. 1
1.1 Classifications of Relay Interlocking .............................................................................. 1
1.2 Unique Features of Siemens practice .......................................................................... 1
Review Questions ………………………………………………………………………………………. 3
CHAPTER 2: CONTROL PANEL ............................................................................................... 4
2.1 Features of Siemens Panel Domino Strips.................................................................... 4
2.2 Panel Controls & Operations ........................................................................................ 5
2.3 Description of Counters ................................................................................................ 7
2.4 Visual Indications on Panel ........................................................................................... 8
2.5 Observation or Description of Panel Illumination ........................................................... 8
Review Questions .................................................................................................................... 24
CHAPTER 3: RELAY GROUPS AND ITS ARRANGEMENT .................................................... 27
3.1 SIEMENS Relay groups.............................................................................................. 27
3.2 Classification of Siemens Relay Groups ..................................................................... 28
3.3 Description of Siemens Relay Groups ........................................................................ 29
3.4 Features of K-50 Relays / Relay Groups: .................................................................... 31
3.5 Mini Groups: ............................................................................................................... 33
3.6 Minor Signal Groups: .................................................................................................. 40
3.7 Minor Route Group: Universal Route Group ............................................................... 47
3.8 Minor group DRS-II Panel Point Group: ...................................................................... 49
3.9 Point Major Group (R.R.I.): ......................................................................................... 52
3.10 Point Switching Group: ............................................................................................... 55
3.11 Point Chain Group: ..................................................................................................... 56
3.12 Relay room arrangement and installation: ................................................................... 57
3.13 Intermediate Distribution Frame (IDF): ........................................................................ 57
Review Questions ………………………………………………………………………………… .. 60
CHAPTER 4: ROUTE SECTION PLAN .................................................................................... 63
4.1 Features of Route Section Plan .................................................................................. 63
Review Questions .................................................................................................................... 72
CHAPTER 5: PRINCIPLES OF OPERATION FOR VARIOUS GEARS .................................... 74
5.1 Stages of Operation .................................................................................................... 74
5.2 Operation of Points ………………………………………………………………………… 74
5.3 Signal and Route Initiation .......................................................................................... 75
5.4 Normalisation of Route ............................................................................................... 76
5.5 Release of Crank Handle & Return: ............................................................................ 77
5.6 Release of Level Crossing Gate Slot & Return: .......................................................... 78
Review Questions …………………………………………………………………………………… 79
CHAPTER 6: SYMBOLS AND NOMENCLATURE ................................................................... 81
6.1 Description of Symbols ............................................................................................... 81
6.2 Representation of Relay Contact ................................................................................ 84
6.3 Nomenclature of Siemens Relays ............................................................................... 84
Review Questions …………………………………………………………………………………… 87
CHAPTER 7: EXTRACTS FROM SPECIFICATIONS FOR RELAY INTER LOCKING SYSTEM
................................................................................................................................................. 91
7.1 Extract of IRS S 36 ...................................................................................................... 91
7.2 Relay Interlocking Systems.......................................................................................... 91
7.3 Relay Interlocking: ...................................................................................................... 91
7.4 Control Panel: .............................................................................................................. 91
7.5. Control Panel Indications: ............................................................................................ 92
7.6 Interlocking And Circuit Requirements: ....................................................................... 94
7.7 Route Release Circuits: .............................................................................................. 95
7.8 Signal Control Circuits: ............................................................................................... 95
7.9 Cross Protection: ........................................................................................................ 96
7.10 Relays: ....................................................................................................................... 96
7.11 Route Indicator: .......................................................................................................... 96
7.12 Points: ........................................................................................................................ 96
7.13 Track Circuits:............................................................................................................. 97
7.14 Cables: ....................................................................................................................... 97
7.15 Wiring ......................................................................................................................... 97
7.16 Fuses:........................................................................................................................ 98
7.17 Power Supply: ........................................................................................................... 98
7.18 General:...................................................................................................................... 98
CHAPTER 8: CONTACT ANALYSIS OF FUNCTIONAL RELAY GROUPS............................ 100
8.1 Contact Analysis of K 50 mini- Group Relays on a Rack ........................................... 100
Review Questions ………………………………………………………..……………………..… 117
CHAPTER 1: INTRODUCTION
1.1 Classifications of Relay Interlocking
Relay control of railway signalling gears made the following things possible:-
In the “Non-route setting type Relay Interlocking” system, points in the route, overlaps,
isolation are to be set individually by pressing concern point buttons and finally for clearance of
signal, the signal button along with the route button to be pressed.
In “Route Setting Type Relay Interlocking” system, one single operation of pressing
simultaneously signal button and concern route button will initiate the points in route, in overlap,
and isolation to set, and signal to get cleared if all the conditions for taking off signal are
satisfied.
A practice of these systems prevailing on our railways, called the continental practice is
introduced by M/s Siemens of Germany. Their first installation which is of route setting type
(RRI) came up in 1958 at Church gate, Mumbai on Western Railway. Subsequently, even as
more installations of this type are provided in large yards as well as for small yards.
Both the British and Siemens practices of Relay Interlocking Systems fulfil the
requirements laid down in the IRS: S-36/87 Amendment No.2. Also, their requirements are
specified as in Indian Railways Signal Engineering Manual.
Entrance - Exit principle (NX) in which two controls, one at the entry point of route and the other
near to its exit have to be operated simultaneously, is adopted in Siemens practice.
1. Modular assembly type construction of control panels with small sections called
“DOMINO STRIPS” fixed on a frame of suitable size. This considerably reduces the
panel size and also makes its modification easy to suit changes in the yard from time
to time.
2. Control buttons are of self restoring type Push buttons, need only feather touch
operation. For any vital operation two buttons are to be pressed simultaneously. They
are geographically located on the panel in similar positions to those of their connected
gears in the yard. This makes the job of operator fast and less tiresome to improve
his efficiency.
4. Relays used are K-50 metal to metal contact relays of proved type. Once Relay is
picked up, proved de-energised before picking up again.
5. The main advantages of these 60V DC metal to metal contact Relays over the
conventional carbon to metal contact relay are their quicker operation and low coil
current rating. Also their small size suits the concept of modular relay units called
groups for each function control.
8. Group unit construction of relays which facilitates uniform gear control independent of
the peculiarities of local layouts. This improves safety in their operation as the group
wiring is factory tested under ideal conditions. Also the wiring is well protected in its
enclosed casing. Due to this, the external wiring needed for interconnection and
inclusion of other controls is greatly minimised resulting in the saving of installation
and commissioning time.
9. Indications on relay groups facilitate quicker fault finding as they appear according to
the relay operation sequence in progress.
10. Interlocking and other vital conditions are proved in more than one stages of
operation. This prevents the energisation of final control affecting the gear unless the
required conditions are retained till the end of operation. This is essential especially
with the use of interlocked relays for control.
12. “Emergency full route release”, “Emergency Sub route release” and “Emergency
Point Operation” features with counters are introduced with this system. These
features facilitate for quicker traffic management.
13. All wires are terminated on ‘Tag Blocks’ fixed on distribution frames which saves the
required space for terminations and facilitates for easy identification for attending the
failures.
14. Provision of main and intermediate distribution frames for wiring connections between
various relay groups and operating panel as well external cables.
15. Fuses with indication tags in bottle type holders occupy less space and their failures
can be easily detected.
17. Used Mercury type flasher relay. This is capable of working for ages.
18. Uses Clock worked Timer relay. This gives fixed time as per set value irrespective of
no. of continuous operations unlike thermal timer.
***
Subjective Questions
Objectives Questions
This is made up of rectangular panel sections called ‘DOMINO STRIPS’ having sizes either of
63mm X 38mm (2½” x 1½”) or 54mm X 34mm (2 ⅛” X 1⅜”). Each panel section has a base
and a top plate.
The aluminium cast base has fifteen compartments with removable fibre separators
between them. Each compartment has an individual contact at its bottom centre and a common
contact plate in the middle connecting all compartments. This plate is connected to the
sixteenth terminal at the bottom of the strip. This common terminal carries the neutral
connection of supply for indication lamps.
A pencil type 24V 1.2W indication lamp, where provided, occupies one compartment
Red and White indication lamps are available. In new panels, Red, Yellow and Green LEDs are
used for indication purposes.
A button fixed on the top plate above has a steel bridge. Its vertical limbs extend below
into any two adjacent base compartments and rest close to the contacts at the bottom. These
contacts are bridged when the button above is pressed. The button is of self restoring type
opening the contact normally.
The top plate of the strip actually contains two aluminium and one steel plate one above
the other. They are clipped together on all four sides, the top one being painted with slate grey
above. The top plate according to its location may carry track, point or signal demarcation with
slits cut to size and shape. Transparent white or green films are placed between the lower two
plates, as required, give the needed colours to the indications through these slits. Buttons may
be fixed on the top plate in a suitable location as required. The top plates situated in the middle
of the panel can be removed from their bases with the help of a magnet. The plates can be
changed or modified as per alterations effected in the yard layout anytime.
The numbering of base components when viewed from the top and of contact terminals
when the domino strip is released from the frame and turned over upside down for accessing is
given below :-
The location of any panel section is identified by its column number followed by its row
number. For example, the shaded section in the panel above bears the number of (04.03). The
contact terminal number 08 of this section is identified by the number (08.04.03).
The panel sections are generally assembled in multiples of five both horizontally and
vertically as per need.
The dull finished grey colour of the panel surface eliminates undesirable reflections. The
panel is mounted horizontally in an inclined plane for the convenience of operation.
Warning buzzers are fixed inside the panel. All the panel strip wiring is terminated on
tag blocks mounted inside the panel.
All Signalling functions having manual control will be operated by pressing two buttons
simultaneously and releasing them within ten/fifteen seconds i.e. In the case of route setting,
buttons shall be kept pressed till the last pair of points in the route start operating. Whereas
main signals clear after the buttons are released, for a shunt signal buttons shall be released
after the signal has come off. In other operations, buttons can be released immediately after
pressing. Buttons required for a vital operation can only be accessed with both hands. This
ensures conscious operation by the operator. There are individual control buttons for each gear
located near to their panel demarcation and common buttons are located at the top of the panel.
Buttons EWN and EUYN are normally obstructed for operation by a sealed disc.
Before operation, seal has to be broken, seal wire has to be removed and the disc
turned to free the button by the operator. In case of EUYN button a key control also
provided in addition to the seal. After each operation, the operator has to get resealing
done on the disc by the signalling staff.
To record each emergency operation Counters of emergency operations are provided close
to the concerned buttons at the top of the panel as below:-
Whether
S.No. Counter Description common or individual
Common
4. OYZ Overlap Release Counter
Some panels do not have Overlap Release Button (OYN). In its place, EUUYN was
utilised instead of OYN.
The various panel operations and changes on panel indication consequent upon
operation or change of gear conditions are detailed below:-
6) ERMERGENCY POINT
OPERATION:
After ensuring non-
occupation of point
track circuits break the
seal on disc beneath
EWN and turn it to free
EWN.
i) Press EWN with the Normal steady Red
concerned WN and indication disappears.
release to operate Reverse indication
points from Normal to flashes during
Reverse. operation and become
steady after operation
(Red).
17) Release of point group crank handles control & its return:-
When no route or
overlap is set involving Crank handle slot
the points of which the indication disappears
crank handle is to be and Crank Handle
released, ask for co- Position indication
operation from site that becomes flashing
i) will be given by Red.
pressing CHPB (Crank
Handle Push Button) in
CH Box at the location.
ii) On seeing the Red CH Key is extracted
flashing indication that from the CH Box.
indicating co-operation
is required to release On the CH position,
CH Key form CH Box, steady Red indication
Press CHYN of appears when crank
concerned CH Group handle slot is
along with YYN and released.
release.
iii) After CH is released Crank handle position
from the Point Machine Red indication
and the key is disappears.
reinserted in the Key Crank handle slot
Lock Relay of CH Box White indication starts
Key Lock Relay picks flashing.
up and it gets locked.
***
Subjective Questions
1. Write down the numbering of base components of domino when viewed from the top for left
to right and right to left movement?
Objective Questions
16. Normal Indication for Track Circuit on Panel without route initiation
a) No Indication.
b) Turn to Red with route initiation.
c) Turn to Yellow with route initiation.
d) Flashes with route initiation.
17. Indication on panel, If DG lamp of home Signal with cascading gets fused ……,
a) Signal displays HG aspect since cascading control.
b) Green indication starts flashing and steady Yellow indication appears on signal
demarcation.
c) Only Green Indication flashes.
d) Red Steady indication appears on signal demarcation.
18. Indication on panel, If HG lamp of home Signal with cascading gets fused ……,
a) Yellow flashing and Red Steady indication appears on signal demarcation.
b) Red Steady indication appears on signal demarcation.
c) Only Green Indication flashes.
d) Green indication starts flashing and steady Yellow indication appears on signal
demarcation.
20. Indication on panel, when point failed without any route and overlap…
a) Steady indication over point strip.
b) Flashing indication over point strips.
c) Locking Indication flashes.
d) Both Locking and strip indication flashes.
9. (b) 10. (c) 11. (d) 12. (a) 13 (a) 14. (d) 15. (d) 16. (a)
17. (b) 18. (a) 19. (a) 20. (b) 21. (c)
The following types of relays / relay groups are used in these systems of Siemens practice.
K-50 relays are available only in group units of different sizes. Depending upon the unit
size, these groups are broadly classified as:
(1) Mini groups
(2) Minor Groups
(3) Major group
The capacities of various groups are as follows:-
The various signalling gears are controlled in these systems by relay groups as shown
below:-
Neutral Relays
Neutral Relays
Indications
Class of
Designatio
Transformer
Resistances
Condensers
Double Coil
Group &
Interlocked
Gears
Contactors
S.
Single Coil
n & Usage
Terminals
Rectifiers
No Controlled Drg. No
Signal 2
Minor
1 One 2-Asp Group in PI, ON(R)
RsSp 10 - - - 2 3 2 100 -
Main Signal RRI or lever OFF(G)
3525/2
Control
Signal 2
Minor
2 One 3-Asp Group in PI, ON(R)
RsSp 13 - - - 2 3 3 100 -
Main Signal RRI or lever OFF(G)
3525/46
control
Signal 4
Minor
3 Two Shunt Group in ON (R,R)
RsSp 13 - - - 2 2 4 100 -
Signals PR, RRI or OFF
3525/67
lever control (Y,Y)
2
R/S
Universal
Minor set(R) &
4 Two Route Route -
RsSp 5 - 3 - - - - 100 Sub-
Sections Group in PI,
31/00021 Route is
RRI
locked
(Y)
Two
Siemens 1
Minor
5 Point Drs II Point
RsSp 3 4 2 1 11 1 1 100 -
Machine Group for PI Point
31/0001
(Successive Detection
Controls) (R)
3
One or Two
successively Pt
Detection
controlled
Major Drs Point (Y) - 1
Siemens
6 RsPs Group for 7 6 5 1 11 1 1 180 -
Point Pt Lock
3515/19 RRI
Machines (Y) - 1
with DC Track
Motor Fail
(R) - 1
Neutral Relays
Neutral Relays
Transformer
Resistances
Condensers
Double Coil
Interlocked
Contactors
Indications
Single Coil
Terminals
Rectifiers
Relays
One or
7 Two
successi
vely
controlle Univers
Major
d Simens al Point
RsPs 7 6 5 1 11 1 1 180 -do- 3
Point Group
31/0015
Machine for RRI
s with
AC 3 –
Phase
Motor
8 One or
Two
successi
vely
controlle
3Ø
d Minor
Point
Siemens RsSk 3 4 2 1 11 1 1 100 1 (R) 1
Group
Point 31/0003
for PI
Machine
s with
AC 3 –
Phase
Motor
9 One or
Two
successi
Minor Drs
vely
RsSk Point
controlle
3515/22 switchi
d Point
(to be ng
Machine
used Group 4 1 3 1 - - - 100 1 (R) 1
s of other
with for PI,
than
Main RRI or
Siemens
Points lever
make
Group) control
with AC
3Phase
Motor
10 Successi
ve
Point
operation Minor
Chain
control of RsSk 8 - - - - - - - - -
Group
eight 3515/3
for RRI
point
groups
IRISET Page 30 INTERLOCKING WITH
METAL-METAL RELAYS (SIEMENS)
3.4 Features of K-50 Relays / Relay Groups:
1) On the basis of thickness of residual pin / separating pin, relays are classified as:
A type : Residual pin thickness is 0.35mm a) Non AC Immunised Neutral relays
b) Interlocked relays
B type : Residual pin thickness is 0.15mm a) AC Immunised Neutral relays
b) Special or double coil relays
c) UECR
E type : Residual pin thickness a) RECR
is0.45mm
b) HECR / DECR
2) Maximum Contacts available = 8 Nos.
3) Standard Contact Configuration:
i) Neutral / Interlocked Relays = 4F/4B, 5F/3B, 6F/2B.
ii) ON & OFF ECR = 3F/3B.
iii) UECR = 5F/1B.
iv) WJR (Point group) = 2F/2B.
4) Current carrying capacity:
Switching current = 5 Amps.
Continuous current = 3 Amps
5) All contacts are Independent; series double make double break contacts.
6) Contact resistance = 0.05 Ohms.
7) Working voltage = 60V DC
8) For Neutral Relays: Pick up time = 25ms to 60ms
Drop away time = 7ms to 15ms.
9) For AC immunized relays: Pick up time = 200ms
Drop away time = 50ms
10) Code pins are provided to prevent the plugging of wrong relay in a base.
11) Guide pins are provided to prevent plugging of relay in a wrong direction i.e., inverting the
position of relay.
12) The armature operation is assisted by proving action and hence more positive.
13) Size of the relay is small. It occupies less space and operation is very fast.
14) Contact resistance of metal-to-metal relay is less so that more contacts can be proved in
one circuit.
Contact
Sl No Type Relay coil Resistance
configuration
4F/4B 1260 Ω
Non AC immunised Neutral
5F/3B 1260 Ω
1 Relays
6F/2B 1840 Ω
615 Ω
4F/4B, 5F/3B,
2 Interlocked relay (To overcome friction)
6F/2B
52.3
10 WKR2 5F/3B
(Pickup current is 120mA)
60 (Pickup current is 1 A
WR and Holding current is 100
12 2F/2B
Heavy Duty contactor Relay mA±10mA with 600, 25W
Resistor in series)
Fig:3.1 Fig:3.2
TOP RELAY
Terminal No. CONTACT No. CONTACT No. Terminal No.
01-02 91-92
01 (Spare ) 11 (Coil)
(sp) (coil)
11-12 02 12 81-82
21-22 03 13 71-72
31-32 04 14 61-62
41-42 05 15 51-52
Contact Numbering is identical for both the Top & Bottom relays.
BOTTOM RELAY
Terminal No. CONTACT No. CONTACT No. Terminal No.
03-04 01 (Spare 93-94
11 (1st Coil)
(sp) / 2nd coil , if any) (coil)
13-14 02 12 83-84
23-24 03 13 73-74
33-34 04 14 63-64
43-44 05 15 53-54
It consists of two nos. of K50 Relays, arranged one on Top and another on Bottom
positions. Top Relay position No. is 1 and Bottom Relay position No. is 2. Each neutral relay is
capable of working independently. This Relay group has contact configuration of 4F/4B, 5F/3B
& 6F/2B. In this group top and bottom relays has same contact configuration.
AC immunity level of Non-AC immunised K-50 Neutral relay is shown in the table below:
Note: AC Induced voltage per KM length of parallelism is 35V as per old norms and it is 95 V in
double line sections and 116V in single line sections as per new norms.
Two neutral K-50 relays are latched mechanically to form an Interlocked Relay. It works
as a memory device to detect the last operation. Top coil is called Reverse coil and Bottom coil
is called as Normal coil. Bottom Relay is Normally UP and Top Relay is Normally DOWN
position.
Picking of one relay de-latches (drops) the other relay. In this process both the relay front
contacts are available for a few milli seconds. i.e In Interlocked relays, Front contacts of the one
relay breaks only after picking up of the other relay. To cut of feed to the Reverse (top relay) coil
after its armature is latched, bottom relay front contact is connected in series with the Reverse
(top relay) coil in its external energisation circuit. Similarly, to cut off feed to the Normal (bottom)
relay) coil after its armature is latched, Top relay front contact is connected in series with the
Normal (bottom) relay) coil in its external energisation circuit. These front contacts are called as
an economizer contacts, since these contacts cut-off the power supply to the latched relay coils
after their picking up.
When one relay is picked up there is possibility of picking of other relay, but both coils can
never be in dropped condition. Normally Front contact of top relay is equivalent to a Back
contact of bottom relay and vice versa. But in a few circuits front and back contact variation
varies. All Inter locked relays are Normalized after completion of movement, but in Point group
circuit (R)WLR relay remains in the last operated position.
Inter locked relay groups are available with 4F/4B, 5F/3B and 6F/2B contact configurations.
For Neutral relays, Front Contact and Back Contact are used as per requirement. But for
interlocked relays, in one Circuit UP contact is used then in next circuit it’s conflicting relay
DOWN contact is used.
Originally Point / Route Group Inter locked relays are used but not in Signal Group, on demand
it was provided at outside signal group.
It comprises of a current transformer, bridge rectifier and a neutral relay of K50. Relay is
provided on top position and Power conversion unit provided on bottom position. ECRs are
supplied separately for ON aspect, OFF aspect and Route indicator.
ON ECR:
It is used for proving the ON aspect of the signal. In case of double pole lamps, it picks up
when both filaments of the signal lamp are lit and it drops when the any one of the filament of
signal lamp is fused. But in case of triple pole lamps, it picks up when any one of 33W rated
filament is litting and it drops only when both the filaments are fused or not litting. It is not
suitable for LED signals.
OFF ECR:
It is used for proving the OFF aspect of the signal. It picks up Whenever OFF aspect lamp
is litting and drops when OFF aspect lamp is fused or not litting. It is suitable for LED signals.
Guide pins are provided on rear side of the mini group to prevent plugging of relay in inverted
position and will enable plugging of the relay in proper alignment.
Holes for Code pins are provided on rear side of the mini group in 8 positions. Code pins
provided on the relay terminal board (plug board) prevents the plugging of wrong configuration
and type relays.
Positions of code pins for various Mini group relays are given in the table below:
Code pins are shown in the figure by shaded circles provided on the relay back plates. Open
holes on back plate corresponding with pin positions. It shall be ensured that blocking screws
are not missing in the holes not corresponding with pin positions of the relay group back plate.
Otherwise relays can get plugged in wrong bases also, causing unsafe conditions.
For more details on Mini groups please refer IRISET Notes: S19 (Signalling Relays and Cables)
In this group 13 Relays & 2 condenser and resistor units are provided.
GR1 picks up only when concerned route and signal is initiated and route is locked. It is
made slow to release, by connecting a 500Mfd and 100Ω in series with relay coil, to prevent
the cleared signal going to danger in case of ahead signal is changing the aspects or power
fluctuations or momentarily bobbing of track circuit.
GR1 and GR2 relays together control the ‘OFF’ aspect of the Signal. GR3 is used to control
the Green aspect of the Signal. GR1, GR2 and GR3 must be in pick up condition to take
‘OFF’ the signal to Green aspect.
In this group 10 Relays & 2 condenser and resistor units are provided.
GR1 picks up only when concerned route and signal is initiated and route is locked. It is
made slow to release, by connecting a 500Mfd and 100Ω in series with relay coil, to prevent
the cleared signal going to danger in case of ahead signal is changing the aspects or power
fluctuations or momentarily bobbing of track circuit.
GR1 and GR2 relays together control the ‘OFF’ aspect of the Signal.
Pickup of GPR1 cut off the feed to the GLSR. In addition, it provides supply to route
indicator lamps.
4 Shunt signal is taken OFF and GR1 , GR2 , HECR HKE Flashing
OFF Aspect lamp fused at site
Note: Above four types of indications are for Independent shunt signal. In case of dependent
shunt signal S.No 1& 2 will not be available since concern ON aspect LED unit of SH RECR
were not wired in shunt group relay.
RKE DKE
RE(M)CR HECR
GR1
DECR HHECR
GLSR
There are two sets of route setting relays in each universal route group and cater for two
route sections. It is an interlocked relay, when the upper/top coil is latched, it indicates that
the route section is set and when the lower armature (bottom relay) latched it indicates that
the route section is not set.
In RRI ‘A’ route section setting relay AU(R)S latched, it controls the setting of points in the
sub-route for straight route and ‘B’ route section setting relay [‘B’ U(R)S] controls the setting
of point in the diverging route.
In PI, U(R)S picks up only after ensuring that the points for the route section are set and
locked in the required position. This relay locks the point group electrically.
If the sub-route is having more than two route sections, for additional route sections, such
type of one relay is separately provided externally by using the Mini group with Interlocked
relays.
This is a neutral and common sub-route clear indication relay for all the route sections of a
sub-route. It picks up when a route section is set and all the track circuits in the set Route
Section are clear. One UDKR is required for each sub-route irrespective of no. of route
sections in that sub-route. This relay helps in sequential proving of sub-route track circuits
for automatic route release by passage of the Train.
UDKR is checked for its operation at this signal clearance stage. This is later required to
operate again in the route release stage for releasing back locking on the Route Section
when a train passes over it.
This is neutral relay and normally de-energised condition. It picks up only when ‘A’ Route
section is set and ensures that the points in the concerned route sections and isolation are
correctly set and locked. It is provided for each route section of the sub-route.
This is neutral relay and normally de-energised condition. It picks up only when ‘B’ Route
section is set and ensures that the points in the concerned route sections and isolation are
correctly set and locked. It is provided for each route section of the sub-route.
If the sub-route is having more than two route sections, for additional route sections, such
type of one relay is separately provided externally by using the Mini group with neutral
relays.
This is an interlocked relay used for locking the sub-route when it is engaged in a signalled
move. This is common relay for all the route sections in a sub-route.
The latching of upper relay locks the sub-route. Once U(R)LR picks UP, no other
simultaneous movement is possible in that sub route. U(N)LR is an interlocked relay for
normalizing the locking of the ‘sub route’, indicates that the sub-route is free.
Picking up of this U(R)LR ensures that:
a) The concerned route section setting relay U(R)S is latched
b) Route section is clear of a train
c) Relevant DUCR is up (relevant route section is checked)
d) Concerned buttons are released
These are neutral relays and operate and stick when a train passes over the sub-route
proving that the track circuits are actuated in a predetermined sequence. These relays in
conjunction with UDKR release the route section after the passage of the train, thus
permitting the sectional route release.
4 5 6 70 - - -- -- -- -- -- -- -- -- - - 61
W(R)R (R)WLR WKR2 60 - - -- -- -- -- -- -- -- -- - - 51
7 8 9 50 - - -- -- -- -- -- -- -- -- - - 41
W(N)R (N)WLR WKR1
40 - - -- -- -- -- -- -- -- -- - - 31
10 11 12 30 - - -- -- -- -- -- -- -- -- - - 21
WKR3
WR WJR
20 - -
10 - -
-- -- -- -- -- -- -- --
- - - - - - - - - - - - - - - - - - 01
- - 11
13 14 15 09 08 07 06 05 04 03 02
This is the first relay to pick-up in a point group for point operation. It is a double coil relay.
This relay is to initiate the point switching group where the points are operating by other
than Siemens Point Machine.
This is an interlocked relay. It is used to bring the point group to either operation mode or
detection mode.
3. Normal Point Initiating Relay (Z1NWR): This is a double coil relay. This relay switches
‘ON’ Normal Point Controlling Relay, (N)WLR. Once energized, it drops only when the point
buttons are released and (N)WLR is picked up.
4. Reverse Point Initiating Relay (Z1RWR): This is a double coil relay. This relay switches
‘ON’ Reverse Point Controlling Relay, (R)WLR. Once energized, it drops only when the
point buttons are released and (R)WLR is picked up.
This relay detects the correct setting and locking of point in either position. This relay
energises only when the point is set, locked and is in correspondence with point group.
This relay continuously monitors healthiness of point at site. Independently it cannot
indicate the position of the point.
7. WKR2: Point Detection Relay-2 to prove the out of correspondence and cross
protection arrangement.
This is also called as “Cross Protection Relay”. It picks up whenever Z 1RWR or Z 1NWR is
picked up during the point’s group initiation sequence and switches ‘ON’ Point Time
element Relay. Once WKR2 picks up, it drops only after the energisation of WKR3 at the
end of point operation. It energizes when the points at site and the point group is out of
correspondence. It also energizes when the point detection circuit draws more than 120mA
current due to false feed / cable fault. Once WKR2 is picked up, results WKR1 drops which
provides flashing indication.
It is double coil relay. It is also called as an “End Position Proving Relay”. This relay
operates:
i. When the point at site and point group is in correspondence on completion of point
operation through point operation supply (i.e. 110V DC). Once energized at the end of
Point Operation, stick through its 2nd coil till such time W(N)R is latched.
ii. It operates during sequence of relay operation in point group when the point operation
from Normal to Reverse is initiated to destroy the point detection through WKR1.
This is a neutral relay. It is made slow to release for a time period of not less than 10
seconds. To make it slow to release a 2500Mfd condenser in a series with 39Ω resistance
connected across the relay coil. This relay controls the point contactor relay for a period of
not less than 10 Seconds to prevent the overloading of point machine in case of obstruction
in point. This relay drops as soon as the WKR3 picked up at the end of point operation. It
operates during sequence of relay operation in point group when the point operation from
Reverse to Normal is initiated to disconnect the point detection supply of WKR1.
This is a contactor Relay having Heavy-duty front contacts with current rating of 10Amps. It
is used for the point operation circuits. Points Motor feed is switched ‘ON’ through these
relay front contacts.
Coil Resistance is 60 Ohms only. Once the relay is energised, it will hold through its own
front contact in series with 600Ω resistance to reduce the holding current.
It is normally de-energised relay. This is the first relay to pick-up in a point major group for
automatic point operation under route setting conditions. It has two coils but only one coil is
used. This relay does not respond for individual point operation.
This is a double coil relay. It checks that the point group is initiated due to route setting only
and not due to accidental lifting of U(R)S or OVZ2U(R)R. It checks the track locking
condition. It switches on the point chain group and helps in sequential operation of points.
It is normally de-energised relay. This is the first relay to pick-up in a point major group for
individual point operation. It has two coils.
This is an interlocked relay. When W(N)R latched point detection circuit is closed and
W(R)R latched point operation circuit is closed.
This is a double coil relay. This relay switched on Normal point controlling relay [(N)WLR].
Once energized, it drops only when the point buttons are released and (N)WLR is
energized.
This is a double coil relay. This relay switched on Reverse point controlling relay [(R)WLR].
Once energized, it drops only when the point buttons are released and Reverse Point
controlling relay [(R)WLR] is energized.
Three numbers of relays are used for obtaining the required number of contacts. The
functions of these relays are same as in the case of minor point group.
This relay detects the correct setting and locking of point in either position. These relay
energies only when the point is correctly set, locked and in correspondence with point
group and the points group is in detection mode. This relay continuously monitors
healthiness of the points at site.
9. WKR2: Point Detection Relay No.2 to prove the out of correspondence and cross
protection arrangement
It picks up whenever Z 1RWR or Z 1NWR is picked up during the point’s group initiation
sequence and switches ‘ON’ Point Time element Relay. Once WKR2 picks up, it drops only
after the energisation of WKR3 at the end of point operation.
It energizes when the points at site and the point group is out of correspondence. It also
energizes when the point detection circuit draws more than 120 mA current due to false
feed / cable fault. Once WKR2 is picked up, results WKR1drops.
10. WKR3: Point Detection Relay No.3 to prove correspondence established at the end of
operation
It is double coil relay. This relay operates, when the point at site and point group is in
correspondence on completion of operation through point operation supply (i.e. 110 V DC).
Once energized at the end of Point Operation, stick through its 2nd coil till such time W(N)R
is latched. It operates during sequence of relay operation in point group when the point
operation from Normal to Reverse is initiated to destroy the point detection through WKR1.
This is a neutral relay. It is made slow to release for a time period of not less than 10
seconds. This relay controls the point contactor relay for a period of not less than 10
Seconds to prevent the overloading of point machine in case of obstruction in point. This
relay drops as soon as the WKR3 picked up at the end of point operation. It operates during
sequence of relay operation in point group when the point operation from Reverse to
Normal is initiated to disconnect the point detection supply of WKR1.
This is a contactor Relay having Heavy-duty front contacts with current rating of 10Amps. It
is used for the point operation circuits. Points Motor feed is switched ‘ON’ through these
relay front contacts.
This relay picks up when the point is operated during route setting to give indications on
point zone tracks in the route or overlap set for more important move.
This relay picks up when the point is operated during route setting to give indications on
point zone track in the route or overlap set for less important move.
17. W(R/N)LR: Point Group Locking Relay/ Point Group Lock Normalizing Relay
Rest all relays function is same as in the case of Minor Point Group.
This group is provided at the point location for controlling of point machine other than Siemen’s
type. This group functions in conjunction with the main point group located at the central relay
room.
When the Z1WR1 relay operates in the main point group, it switches on the point switching
group by closing the Z1WR relay coil circuit. This relay opens the circuit of WKR1 of both
main point group and point switching group.
These relays help in switching over point control circuit and point detection circuits.
It is a repeater relay of WJR and WR relay of main point group. This is a neutral relay.
This is an interlocked relay. When (R)WR picks up controls reverse operation of point; and
(N)WR picks up controls normal operation of point.
This relay operates at the end of each operation and indicate that the completion of point
operation. It causes WKR2 & WR drops and W(N)R and W(N)PR operates.
It controls the feed to point machine and it is having heavy duty front contacts.
One chain group is provided with eight numbers of WWR neutral relays. WWR is normally
drop relay. The circuit is designed in such a way that these relays will picks up one after the
other and also drops one after the other. Normally, one chain group can cater eight numbers of
major point groups. The pickup contact of 1st relay (1WWR) is used for one major point group to
energize Z1WR relay during automatic operation of point to initiate the point group.
For further details of chain group operation please refer IRISET Notes S16.
The relay racks are erected on pedestal, which are anchored to anchor bolts. Proper
side and back supports by means of single irons from the adjoining walls are provided. Ladders
are fixed at the side and top of the rack to run the cables and wiring. The distance from the
parallel wall to the first row of relay rack should be 1.5M and also from the sidewall it shall not
be less than 1.5 meters. The distance between two intermediate rows of racks should not be
less than 1 meter so as to enable free movement of maintenance staff in between two rows of
racks.
In small installations, the tag blocks are provided in rear of relay rack. Copper wires do
the connection between the relay groups and tag blocks.
In case of major yards, the tag blocks are fixed on a separate row of racks called as
Intermediate Distribution Frames (IDF), numbered according to the relay rack numbering. 60
core and 40 core in door cables are used to makes connection between the relay groups and
tag blocks. Inter wiring between one group to another group and to the external connections
such as panel, external cables termination is done at the tag blocks by using 0.6.mm diameter
jumper wires. More than two wires shall not be terminated on tag block pins. 0.6 mm diameter
wires are used for all circuits and 1mm diameter wires are used for point control and signal lamp
circuits.
The arrangement as a whole gives a neat appearance and renders alteration to wirings,
localisation of faults, etc. extremely easy with minimum disturbance to the working installation.
All the connections to terminal boards, IDF, relay groups are done by soldering. The solder
joints have proved to be satisfactory in practice.
Two types of tag blocks are available one with 200 terminals and the other one is 160
terminals. One tag block of 200 terminal can accommodate one number of major group or two
numbers of minor groups or five numbers of mini-groups. One tag block of 160 terminals is
sufficient for four mini-groups.
In IDF row, each pillar contains maximum 10 tag blocks of 200 pins. The numbering of a 200-
way tag block termination is shown in the diagram block.
This is generally used for terminating the wiring of one major group or two minor groups
or five mini-groups. The counting is done from the rear towards the front as shown.
The numbering of a 96-way tag block which is generally used to terminate the wiring at
Cable Termination Rack and in the Control Panel is shown bellow.
***
IRISET Page 59 INTERLOCKING WITH
METAL-METAL RELAYS (SIEMENS)
Review Questions
Subjective Questions
Objective Questions
10. For any combination of K-50 Relays contact number 05 and 15 are always
a) always Front contact
b) always Back contact
c) inter changeable contact
d) None of above
11. For any combination of K-50 Relays contact number 02 and 12 are always
a) Always Front contact
b) always Back contact
c) inter changeable contact
d) None of above
12. For any combination of K-50 Relays contact number 04 and 14 are always
a) always Front contact
b) always Back contact
c) inter changeable contact
d) None of above
21. This relay detects the correct setting and locking of point in either position
a) WKRI b) WKR2 c) WKR3 d) Z3WR
25 . This is the first relay to pick-up in a point major group for automatic point operation under
route setting conditions.
a) WKRI b) WKR2 c) Z1WR d) Z3WR
9. (b) 10. (b) 11. (a) 12. (c) 13. (a) 14. (a) 15. (a) 16.(d)
17. (a) 18. (a) 19. (a) 20. (b) 21. (a) 22. (b) 23. (c) 24. (d)
25. (c)
The route section plan shows the entrance and exit buttons with their designation at their
geographical location. The buttons are represented by small circles in the plan.
The entire layout is divided into a signal route and further into a sub-route to facilitate the
sectional route release.
Each sub-route includes one or more point in it. Sometimes, sub-routes without point
can also exist for achieving special condition of interlocking. Sub-routes are numbered as per
the number of any one of the points which exist in it. If there is no point, such sub-route will be
numbered as per the signals controlled by it.
Sub-route which includes one or more points are so formed by combining route sections
so that only one movement is possible over that sub-route at a time. This is ensured by using a
common sub-route locking relay U(R)LR. For a crossover point, in which parallel movements
are possible, there will be two sub-routes. Each sub-route is further divided into route sections.
Each route section usually giving certain specified setting of points. The straight movement
over a sub-route requiring points in normal position is called "A" route section and the diverging
route requiring points in reverse is called B or C or D route section. A sub-route can have one
route section or more number of route sections.
The Route sections are marked with solid lines. Route section marking will always starts
from the Block Joint of 1st track circuit controlling that point or points and ends at the last Track
circuit Block joint controlling that point or points as the case may be. Sometimes adjoining Track
circuits also added in the route sections particularly towards Home signal.
Route section names will be written generally in a box attached to the Route section
demarcations. Route section name should be written at such a place where it is exclusive for
that route section and not at common demarcated portion with other route sections of that Sub-
route.
The following examples illustrate the principles involved in demarcation of route sections
and formation of sub-route:
Case No.1:
At any point of time physically there will be only one movement is possible over point No.101.
This satisfies the condition for considering the movements over point No. 101 and the route
settings to be in one sub route as only one movement is possible.
Locking of Normal route setting (Point No.101 Normal) by Sub-route lock relay [U(R)LR] will lock
other diversion route setting (Point No.101 Reverse) and vice-versa.
This sub-route will be named after the point number it is controlling, in this case it is 101Sub-
route.
In this 101 Sub-route there are two route settings i.e. ‘101 Normal’ route between S1 and S2
and ‘101 Reverse’ route between S1 and S3. These two routes are sub divisions of 101 sub
route with definite setting of point or points.
The route set with 101 Normal will be one route section of Sub-route 101 named as 101A route
section. The route set with 101 Reverse will be another route section of Sub-route 101 named
as 101B route section. Now the sub route is known as 101A/B sub-route.
Point No. 101 sub-route is 101A/B. Route sections are 101A with point setting 101 Normal with
track circuit 101AT and 101B with point setting 101 Reverse with track circuit 101AT.
Case No.2:
Case No.3:
Fig : 4.3
Case No.4:
Fig : 4.4
In this case, at some point of time there will be two movements possible over cross over
Point number 111 with point 111 in Normal position. Hence all the movements over the cross
over Point number 111 cannot be in one sub-route. Each simultaneous possible parallel
movement over Point No.111 requires one Sub-route. Route section 111A and 111a can be set
simultaneously with points in Normal for parallel movements. Hence, there are two sub-routes
for the crossover shown.
Point No. 111 sub-routes are 111A/B and 111a’. In this ‘111 A/B’ is one sub route having
two route sections and ‘111a’ is second Sub route having only one route section.
Now the new Sub-route will be named after same point number but with one route
section with Point No.111 Normal. This route section is named as “111a” (as it is also with point
in normal condition) and the Sub-route will be ‘111a’. In some railways this route section and
sub-route are named as ‘111z’
In some installation, the crossover point above is given dual number, 111/112. This is
for the purpose of assigning separate number for the two sub-routes on the crossover distinctly.
Case No.5:
Point Sub-route Route Section Point setting in the Track circuits in the
No. Name Name Route Section Route section
101A 101N & 102N 101AT,102AT
101
101 A/B/C 101B 101R& 102N 101AT,101BT
102
101C 101N & 102R 101AT,102AT,102BT
Case No.6: (Same yard of Case 5 with Sectional Route Release facility)
With full “Sectional Route Release” feature the same yard will be redesigned with two
Sub-Routes as shown here.
For utilizing “Sectional Route Release” arrangement over these points, track circuits
should be provided separately for each point and each point may be provided with separate
sub-route with two route sections in each Sub-Route. So that on clearance of each point by the
IRISET Page 66 INTERLOCKING WITH
METAL-METAL RELAYS (SIEMENS)
train, released points could be used for other movements as permitted by that station
interlocking.
Point No. 101&102 sub-routes are 101A/B and 102A/B. One Sub-route 101A/B will be
marked with two route sections 101A towards Mainline and 101B towards Loop line No.1.
Another Sub-route 102A/B will be marked with two route sections 102A towards mainline and
102B towards Loop line No.2.
In sub-route 101A/B, Route sections are 101A with point setting 101 Normal 101AT,
101B Route section with point setting 101 Reverse with track circuit 101AT, 101BT.
In sub-route 102A/B, Route sections are 102A with point setting 102 Normal with track
circuit 102AT, 102B Route section with point setting 102 Reverse with track circuit 102AT,
102BT.
Route
Point Sub-route Point setting in Track circuits in
Section
No. Name the Route section the Route section
Name
101A 101N 101AT
101 101 A/B
101B 101R 101AT, 101BT
102A 102N 102AT
102 102 A/B
102B 102R 102AT,102BT
In sub-route 102A/B, Route sections are 102A with point setting 101 Normal & 102
Normal, 102B Route section with point setting 102 Reverse.
Case No.8:
There are some route sections without points in them to control. In single line section
this route section will be provided between Home signal and Advanced starter signal. In case of
Double Line Section these route sections will be provided after Home Signal and after
Advanced Starter Signal. These route sections are provided for route holding and will be helpful
in simplifying the indication locking proving, while releasing the route sections. While route
releasing, in each route section the signals, their aspects and their controlling relays on both
sides of the route section are proved in normal condition.
Route sections without points are numbered as per the signal (in case of Double line) or
signals (in case of single line) controlled by it.
This single line section example shows one route section without points, falling between
the Home Signal S1and Last Stop Signal S3 is numbered as S1/3U(R)S, since it is controlled by
the signals S1 and S3.
This double line section example shows two route sections without points. One route
section falling after the Home Signal S2, named as S2U(R)S, since it is controlled by S2 signal.
Another route section falling after the Last Stop Signal S15, is named as S15 U(R)S, since it is
controlled by S15.
Overlaps:
Overlap is the adequate distance kept to ensure safety. It is part of complete signal
route. Setting of overlap ensures correct setting of points falling in the overlap.
Signal Overlaps are marked in the route section plan. This helps to identify the
interlocking required for an overlap with other overlap and route sections. Overlaps are
numbered as per the signal numbers beyond which they fall. These are required to be set
along with the route for Main signal in rear.
In route section plan route sections are marked in bold lines preferably with different
colours and overlaps are marked in dotted lines. This facilitates their easy identification from
one another in big yards with many routes and signals.
Each overlap is provided with one Interlocked relay called OVZ2U(R/N)R. Latching of
Reverse coil indicates that the relevant overlap is set and this relay will lock the overlap points.
This relay will ensure normal position only after the specified time delay, after the train has
entered the berthing track.
Subjective Questions
2. Explain Route section Plan? What are the various signalling gears are shown on RSP.
3. Write short notes on (a) Sub route (b) Route section
4. How sub route and overlap are named and marked on Route section plan?
5. Make a Route Section Plan for typical 4-Line station of your Railway?
Objective Questions
1.-b, 2.-a, 3.-b, 4.-b, 5.-a, 6.-c, 7.-a, 8.-b, 9.-b, 10.-a
11.-c, 12.-a, 13.-a, 14.-a,
Operation of the first three functions takes place in four stages, viz
1. Initiation
2. Control
3. Checking and Locking
1. Points
2. Routes
3. Signals and
4. Slots.
In the ‘INITIATION’ stage, interlocking and other safe conditions are verified and
confirmed before changing the position of controlled gear.
In the ‘CONTROL’ stage, initiation is proved and operating feed is connected to the gear
after checking the integrity of relays involved in the process.
In the ‘CHECKING & LOCKING’ stages, the changed condition of gear is ascertained and
this condition is locked, i.e., retained undisturbed until after the movement of train or fulfilment of
the necessary safe conditions in emergencies.
In the INITIATION stage, it is proved that the point is free from route locking as well as
track locking and that the necessary panel operation is done.
In PI, this panel operation is always individual for each point.
In RRI, either individual operation of points or route setting for a signal collectively.
2. The CONTROL stage following initiation ensures cross protection and overload
protection to the machine before starting the motor operation.
In RRI, this also requires setting successive control of all concerned points of the route
and overlap in motion soon after the simultaneous beginning of their initiation. This ensures that
only two point machines can start moving at a time. It is necessary to limit the load on point feed
rectifier and ensure its full output voltage during operation.
The culmination of this stage is in the machine changing the position of points. This
happens if only proof of safe conditions established during initiation is not disturbed throughout
this stage.
LOCKING of this detected condition of points takes place only when a route is set
involving this point in RRI. The point becomes free to be operated again after the set route is
normalised.
Failure of point track circuit creates an emergency when track locking on point prevents
their operation. In that case, a recorded and cautions panel operation is done after physical
verification of track conditions to save heavy detentions. An emergency common point’s button
(EWN) is pressed along with the individual point button (WN). This initiates point operation by-
passing track locking conditions (But no signal clearance other than calling ON Signal is
possible over the points in this connection)
1. Signal Initiation and Route Initiation take place at a time as signal button and route button are
pressed together and released. In these initiations, it is proved that the previous route setting in
the location is normalised, be it of the same route or a conflicting route or overlap.
Availability of all the route sections to be set is checked for the purpose of making a
traffic movement in a particular direction only. Once the direction is established, it is not possible
to initiate any other signal on the same route in opposite direction.
Also, interlocking between a main signal and conflicting shunt signals is achieved at this
stage by means of a ‘shunt signal selection relay’. Overlap is also set for main signals.
2. Route initiation is followed by Route Setting which takes place section wise.
Setting of a route section makes points lying within it, its isolation points and slots
inoperative until the route setting is normalised again. This is called ‘Route locking of points and
slots.
In RRI, setting of a route section includes operation of the concerned points, if they are
not already lying in the required position, before locking them.
3. Route Checking involves proving of correct point detection along with route setting and free
condition of route section track circuits. The route section does not get normalised unless this
locking is released after the passage of train or a cancellation operation in emergency. This
takes place only after signal & route buttons are released.
4. The set and checked route section is locked by the operation of a common locking relay of
the sub-route. The route section does not get normalised unless this locking is released after
the passage of train or a cancellation operation in emergency.
2. Signal control is followed by Signal Locking. In this process, a signal engages or locks a
route setting before its clearance. This enforces signal to signal interlocking in the yard directly
in addition to the directional and other route locking in the initiation stage.
For shunt signal, all the main signal control conditions except setting of overlap, point
detection in overlap and non-occupation of last track circuit are proved. In this case, the
interlocking provided in the initiation stage is considered sufficient due to the cautions speed
permitted by the signal. No second stage locking on the route setting or direct signal locking is
proved. Also, shunt signal gets cleared before the buttons are released after operation.
For calling on signal control, operation is done only after the occupation of Calling ON
signal approach track circuit. No signal initiation takes place for this Calling ON signal. Route
initiation and setting take place as in the case of main signal concerned. After the necessary
time delay, proving the route point detection, the ‘Calling ON’ signal gets cleared. Signal locking
is not considered necessary.
Regular normalisation of a set route takes place after train movement over it
automatically. In this process, signal assuming ‘ON’ aspect with route occupation releases
indication locking on all the route sections. Approach locking and back locking gets free for each
route section individually one after the other, when track occupation and clearance take place
progressively. This culminates in the release of route locking, route normalisation and release of
locking on concerned points. This process is referred to as Automatic Route Release.
The process ends with overlap release in case of main signals 1 minute after the last
route section is released for a halting, train. Overlap gets released along with route section
ahead for a run through train with its passage.
5.4.2 In Emergencies:
In emergencies, the various locking releases of route are affected by specified operation
on the panel.
EGGN is pressed with the concerned GN to release indication locking on all sections of
the route set. Then, a process known as ‘manual route release’ is initiated by the operator by
means of three buttons, viz, EUUYN, GN & UN. This operation releases locking and normalises
all the route sections as well as the overlap if set at the same time. The locking becomes free
soon after the panel operation for route release, in case track circuits in approach of signal are
not occupied, nor failed. If they are not clear, the release takes place when the three button
operation is repeated after a safe time lapse of 120 seconds, as read from a stabilised panel
indication which started flashing after the first three button operation.
The route and overlap release leads to the release of signal locking and point locking.
In case of track circuit failure in any section of the route set, the route section concerned
cannot get released either in the process of automatic route release or manual route release.
This situation calls for a joint action of the panel operator along with some responsible official of
signalling department to normalise this route section and avoid heavy traffic detentions.
After getting a specific written request from the operator, S&T key is inserted and turned
on the panel. Then the operator breaks the seal, turns the disc to free EUYN and presses it
along with the specific route section point button, WN. With this, the route section gets
unlocked and normalised. Consequently its points get free from route locking and the signal
locking relay concerned also gets normalised.
In case, a signal overlap has to be released in emergency, the pressing of ‘OYN’ along
with the ‘UN’ concerned behind the signal, releases the overlap instantly provided the last
section of the route concerned is already normal. If OYN is not provided on the panel, EUYN is
used instead of OYN for this purpose
With the concerned route sections and overlaps normal, the panel operator advises the
man at site to cooperate for crank handle release. At site, a push button on the Crank Handle
Key lock relay Box is pressed.
Then, the white indication near CHYN on the panel extinguished & Red indication
flashes. The operator now presses CHYN along with the common Slot Release Button, YYN.
At site, with the button still pressed, a steady red indication appears on the box. The key
can now be taken out from the Key Lock Relay to operate the point machines concerned.
When the key is extracted, the steady red indication on the box & control panel continues to be
displayed.
When the key is re-inserted on the Key lock Relay after use and turned, the relay drops.
The red indication at site disappears.
On the panel also, the steady red indication disappears and flashing white indication
reappears. Seeing this, the panel operator has to press CHYN along with common Slot Return
Button, YRN. This normalises the slot and the concerned white indication on the panel
becomes steady.
When route sections and overlaps involving the gate are normal, the panel operator
presses LXN along with YYN. The steady white indication near LXN on the panel starts
flashing.
A steady red indication appears on the level crossing Key lock Relay box at site. When
the push button on the box is pressed, the key lock relay picks up and releases the key. When
the key is extracted, the steady red indication on the box remains.
The flashing white indication near LXN on the panel disappears and a flashing red
indication appears. After the gate is closed, when the key is reinserted in the Key lock Relay
and turned, the relay drops.
The flashing red indication at LXN on the panel disappears, and the flashing white
indication reappears.
On seeing this, when the panel operator presses LXN alongwith YRN, the slot gets
withdrawn and the white indication becomes steady.
The operations on the panel and at site are similar in this case and the indications
displayed are also the same to those of gate slot explained above. The button operated for
point slot release is KLN instead of LXN along with the common buttons YYN and YRN.
***
Subjective Questions
Objective Questions
1. Under normal or back lock track clear condition route of the signal can also release
with….
a) EUYN, GN & WN
b) EUUYN, GN & OYN.
c) EUYN, GN & WN
d) EUUYN, GN & UN.
5. An emergency common point’s button (EWN) is pressed along with the individual Button
a) GN b) UN c) WN d) WWN
6. To take of any signal along with Signal button and ______ button to be pressed and
released.
a) GN b) UN c) WN d) WWN
7. In case of track circuit failure in any section of the route set, the route section concerned
can be released by the process of
a) Automatic route release
b) Manual route release.
c) With OYN Cancellation.
d) Sub Route cancellation only.
Sl.
Symbol Description / Nomenclature
No.
4 Neutral Relay
7 Track Relay
15 Make Contact
16 Break Contact
Diagonal line inside the relay circle from left top to right bottom
25
indicates that the relay is used in Point circuit
Horizontal line inside the relay circle indicates that the relay is
26
used for Route circuit.
Diagonal line inside the relay circle from right top to left bottom
27
indicates that the relay is used in Signal circuit
Objective Questions
1.
Symbol Indicates……………
a) Neutral Relay, Normally Picked up, Make Contact i.e Front Contact
b) Neutral Relay, Normally Picked up, Break Contact i.e Back Contact
c) Panel Key IN Contact
d) Track Relay.
2.
Symbol Indicates……………
a) Neutral Relay, Normally Picked up, Make Contact i.e Front Contact
b) Neutral Relay, Normally Picked up, Break Contact i.e Back Contact
c) Panel Key IN Contact
d) Track Relay.
3.
Symbol Indicates……………
a) Neutral Relay, Normally Picked up, Make Contact i.e Front Contact
b) Neutral Relay, Normally Picked up, Break Contact i.e Back Contact
c) Panel Key IN Contact
d) Neutral Relay, Normally Dropped, Make Contact i.e Back Contact
4.
Symbol Indicates……………
a) Neutral Relay, Normally Picked up, Make Contact i.e Front Contact
b) Neutral Relay, Normally Picked up, Break Contact i.e Back Contact
c) Neutral Relay, Normally Dropped, Break Contact i.e Front Contact
d) Neutral Relay, Normally Dropped, Make Contact i.e Back Contact
a) Neutral Relay, Normally Picked up, Make Contact i.e Front Contact
b) Neutral Relay, Normally Picked up, Break Contact i.e Back Contact
c) Neutral Relay, Normally Dropped, Break Contact i.e Front Contact
d) Interlocked Relay, Normally Picked up, Break Contact i.e Back Contact
6.
Symbol Indicates……………
7.
Symbol Indicates……………
a) Track Relay
b) Panel Key IN Contact
c) Neutral Relay, Normally Dropped, Break Contact i.e Front Contact
d) Interlocked Relay, Normally Picked up, Break Contact i.e Back Contact.
8.
Symbol Indicates……………
a) Track Relay
b) Panel Key IN Contact
c) Point Contactor Relay
d) Interlocked Relay, Normally Picked up, Break Contact i.e Back Contact.
9.
Symbol Indicates……………
a) Track Relay
b) Panel Key IN Contact
c) Interlocked Relay Reverse Coil (Top Relay).
d) Interlocked Relay, Normally Picked up, Break Contact i.e Back Contact.
12. WKR1
a) Point final detection Relay.
b) Prove Point and Points group out of correspondence and cross protection arrangement.
c) Point group Initiation Relay (with route setting)
d) Point Operation Circuit Switching Relay.
13. Z1UR1
a) Diversion Selection Initiating Relay
b) Zonal Route Permissibility Checking Relay
c) Main Signal control Initiating Relay.
d) Route section Initiating Relay (Common for a Sub route)
14. MN-GZR……..
a) Main Signal control Initiating Relay
b) Zonal Route Permissibility Checking Relay
c) Route section Initiating Relay (Common for a Sub route)
d) Shunt Signal control Initiating Relay.
16. UDKR…
a) Tracks in the sub route Clear Indication Relay
b) Sub-Route Clear Indication Relay
c) Calling ON Signal Route Locking Relay-1
d) Shunt Signal control Initiating Relay.
18. G(R/N)LR ……
a) Signal Locking / Unlocking relay
b) Signal Lamp Failure Alarm Timer Relay.
c) Overlap Setting / Releasing Relay.
d) (Reverse/Normal) Direction Setting Relay.
19. OVZ2U(R/N)R ……
a) (Reverse/Normal) Direction Setting Relay.
b) Overlap Setting / Releasing Relay.
c) Sub-Route Locking/Releasing Relay.
d) Overlap Release Button Relay.
20. OYNR ……
a) Overlap Release Button Relay.
b) Overlap Release Time Setting Relay.
c) Overlap Setting / Releasing Relay.
d) Emergency Route Release Button Relay.
9. (c) 10.(b) 11.(a) 12.(a) 13.(a) 14.(a) 15. (a) 16. (a)
1. IRS-S-36/87 refers to IRS, IS, BS & BRS Specifications for signalling materials, cables,
relays, point machine and various IRS design drawings.
White (Normal) and Green (Reverse) near point switch/button or by White strip light on
the leg of point switch; if needed by purchaser, indication lights to flash till points are correctly
set and locked. If point does not set with in predetermined time, warning bell to be given which
can be stopped on acknowledgement but flashing indication to continue till defect is set right.
Point locked in route to be indicated by a small Red or White light near the point or respective
switch/button which gets extinguished when point is free. If needed by purchaser, point free
indication also to be provided.
A row of white lamps to show setting and locking of routes, to get extinguished when route
is not set. If needed by purchaser one or more first track circuits in route to flash till route is
correctly set and locked. When track is occupied colour of indication to change to red and to go
back to white when track is free and to get extinguished when route is released.
Unless automatic route release by passage of train is asked for, route + overlap to be
released when signal put to "ON" and corresponding route switch/button is operated to
normalise the route.
If route has number of route sections, route section should not release only by
picking up of the concerned track relay. Same is released only after the next track
circuit is also dropped and picked up, except where last track is a berthing track. If
route is controlled by single track, route release after pre-determined time delay.
Route release circuit to be effective only if two track circuits' drops and pick up in
sequence.
In route setting type, sectional route release is to be provided where required. Sub
route already released can be used in other routes, if permitted by interlocking.
In Non-Route setting system, sectional route release not required unless specifically
asked for. The complete route is to be released after signal put back to "ON" and
corresponding route switch/button operated to normalise the route.
Emergency route release after suitable time delay is to be possible when approach
track is occupied (or dead approach locked), if signal put back to danger and the
train has not passed the signal during this time interval.
Overlap points to be released only after lapse of one minute after occupation and
clearance of last point track circuit of the route. On cancellation of route, the overlap
points also to be released simultaneously along with the main route.
If required by purchaser, facility for emergency route / sub route cancellation in case
of track circuit failure. Emergency cancellation of route/ sub- route shall be possible
by cooperation of two persons, one representative of Signal Department and other
from Traffic Department and every such cancellation shall be recorded on a
counter.
7.10 Relays:
Time element relays electronic type confirming to IRS/BS/BRS Specification shall
be used. When electronic timers are used, two numbers are to be used and their
contacts are to be in series with each other.
All plug-in relays and relay groups to be fitted with non- interchangeable interlocking
device.
Removal of relays/relay groups from relay racks during operation shall not cause
any unsafe condition in the circuits.
Maximum possible number of relays to be housed in relay room itself.
Wherever possible, all relays except track relays to have 10% of working contacts to
be spare subject to a minimum of 1F and 1B. Relay rack to have space to
accommodate repeater relays in future as required by purchaser.
Flasher relay shall be used preferably a mercury flasher. Electronic flasher shall not
be used for point operation or route setting operation and it can be used for other
indications.
7.12 Points:
Point machine can be with plunger type locking, rotary locking or point clamp type
locking.
7.14 Cables:
Unscreened, screened, power cables, axle counter quad cables.
In each main cable spares to the extent of 20% of total conductors used to be
provided up to point zone and 10% spares beyond, no spares required if total
number of conductors used is < 3.
Conductor size such that voltage drop on line is > 10%.
Cable termination or jointing outdoor, same to be done in water tight junction boxes.
2 Cores of cable for telephone communication from relay to end to yard for
maintenance purposes, if in different directions, one pair for each direction; in RE
area, communication by telecom. Cable.
ELD's (multi-channel) optional for detecting leakage to earth.
7.15 Wiring
All wiring in cabin & locations to be terminated on terminal blocks/tag blocks.
Single Core 1mm., multi-core each 1mm., multi-core each 0.6mm or flexible wire
16/0.2mm to be used for internal wiring.
Relay rack to relay rack wiring by 1.6/1.5 Sq.mm.
For shelf & plug-in type relays, 16/0.2 Sq.mm.
Proved type relays, 0.6 Sq.mm. single strand.
Cable termination to tag blocks and indicators, 1 mm. Single strand.
CB's, lever locks, etc., single strand 1.5 /1.6 Sq.mm.
Relay to relay wiring in same rack to be direct without tag blocks/terminals, as far as
possible.
Relay rack to have spare capacity to take 15% more.
7.18 General:
Big yards, busy junction stations where large number of movements take place,
relay room shall be Air conditioned, optional in wayside stations.
Relay rooms in areas prone to dust, fumes, extreme temperatures, etc. may be Air
conditioned.
Route setting type installations, fire detector and alarm of approved design to be
provided. All installations are to be provided with fire fighting arrangements.
Adequate spare relays and other equipments to be provided with each installation.
Quartz clock shall be provided on indication panel, if required.
Proper earthing shall be provided for relay racks, panel, power supply, switch board,
transformers, inverters, etc.
In case of major Route Relay Interlocking and Electronic Interlocking Installations,
Data Logger shall be provided. At wayside Panel Interlocked Installations, provision
of Data Logger is optional.
OPTIONS: To be specified.
1. RRI or Pl.
2. Control & indication panel separate or not.
3. Three position signal switch in Pl.
4. Point switches two or three position.
5. Voltage control on panel indication.
6. Voltage control on signal supply.
7. SM's lock.
8. Provision of voltmeter.
9. Requirement of approach warning.
10. Lamp failure indication.
11. Sectional route release.
12. Double cutting in internal circuits.
***
8 Mini-Groups in each of 8 rows are fixed on a rack. The groups are numbered as below,
as seen from the rear of the rack where the wiring is. The group position on the rack is as
shown below:
08 07 06 05 04 03 02 01
18 17 16 15 14 13 12 11
28 27 26 25 24 23 22 21
38 37 36 35 34 33 32 31
48 47 46 45 44 43 42 41
58 57 56 55 54 53 52 51
68 67 66 65 64 63 62 61
78 77 76 75 74 73 72 71
The contact distribution of each mini group is shown in the above numbered slots as shown
below
91
100 74
76
12.12 80
UDKR
12.14
94 75 95
13.12
15.6 15.4
UYR1 98 UDKR
B A 03.13
05.10 49 87
U(N)S U(N)S 05.8 15.14
U(N)LR
U(R)LR 11.9 11.8 11.10
A
DUCR UYR1
58
12.10 03.1 12.3 05.9 15.15
A B B A B 04.12 13.14
92 97 U(R)LR U(R)S U(R)S DUCR DUCR U(R)LR DUCR UYR2
11.1 11.3 11.13 11.4 11.6 25 96 05 19 67 UDKR UYR1
02.15
A B A B
U(R)S U(R)S U(N)LR U(N)S U(N)S 78 99 79 UYR2
77
05.14
05.12 02.14 13.15 15.12
72 02.12
UYR1
05.15
UDKR UYR1 UYR2 UDKR
UDKR
UYR2 12.15
12.4
A 11.12 11.14 11.15
UYR2
U(N)S
12.6
B UDKR UYR1 UYR2
U(N)S
73 01 03 81
A B
U(R)S U(R)S
13 14 15
U(N)LR UYR1 UYR2
61
SR.NO. GROUP 91,71,92,97,72,73,76,98,58,77 94, 25 75, 96 95, 05 100,74,80,78,99,79 49, 19 87, 67 81,61,62,82
01 101A/B 53 54 54 53 54 53 54 79
02 102A 55 56 56 55 56 55 56 79
03 103A/B 57 58 58 57 58 57 58 79
04 104A 59 60 60 59 60 59 60 79
05 112A/B 61 62 62 61 62 61 62 79
06 115A 63 64 64 63 64 63 64 79
07 116A/B 65 66 66 65 66 65 66 79
08
09
10
11
12
13
14
15
16
51 52 54 50 21 26 22 23 24
02.1 12.1 04.4 05.1 15.1 04.1 02.4 13.4 03.4
A A A A A A A A A
U(R)S U(R)S U(N)S U(R)S U(R)S U(R)S U(N)S U(N)S U(N)S
31 32 34 20 01 06 02 03 04
45 48 93 88 89 46 84 47 30
12.8 14.8 04.8 13.8 03.8 13.10 15.13 04.13 14.13
A A A A A
DUCR DUCR DUCR DUCR DUCR U(R)LR U(N)LR U(N)LR U(N)LR
RACK NO.43 15 18 53 68 69 16 64 17 10
SR.NO. GROUP 51.31 52.32 54.34 50.20 21.01 26.06 22.02 23.03 24.04 45.15 48.18 93.53 88.68 89.69 84.64 47.17 30.10
46.16
01 101A/B 83 54 714 22 152 53 132 136 132 136 713
02 102A 83 TMS 85 53 360 22 57 152 55 132 136 132 136 713
03 103A/B 83 85 53 714 22 152 193 57 132 136 132 136 713
04 104A 85 141 57 152 22 195 195 59 132 136 136 713
05 112A/B 87 166 360 45 21 61 132 136 132 136 713
06 115A 91 166 65 360 21 152 63 132 136 132 136 713
07 116A/B 89 65 91 66 21 152 49 554 65 554 132 136 132 136 713
08
09
10
11
12
13
14
15
16
59 90 55 56 33 28 60 41 57
03.3 14.3 04.6 14.6 04.3 05.3 15.3 02.6
B B B B SP B B B B
U(R)S U(R)S U(N)S U(N)S TER. U(R)S U(R)S U(R)S U(N)S
39 70 35 36 08 40 11 37
27 42 43 44 83 38 86 85 29
14.9 02.9 13.9 03.9 04.9 04.10 02.13 13.13
B B B B B SP
DUCR DUCR DUCR DUCR DUCR TER. U(R)LR U(N)LR U(N)LR
07 12 13 14 63 66 65 09
SR.NO. GROUP 59.39 90.70 55.35 56.36 33. 28.08 60.40 41.11 57.37 27.07 42.12 43.13 44.14 83.63 38. 86.66 85.65 29.09
01 101A/B 83 166 55 57 152 22 53 132 136 165 98
02 102A 98
03 103A/B 141 85 166 55 59 152 22 57 132 136 165 98
04 104A 98
05 112A/B 61 87 166 113 15 21 360 152 61 132 136 98
06 115A 99
07 116A/B 45 89 91 166 63 21 45 567 65 136 136 165 98
08
09
10
11
12
13
14
15
16
5
19 20
23 24 27 28 29 30
03.13 12.15 02.6 02.8 14.6 13.11
GPR1 26 GPR1
04.7 03.9 02.1 02.4 02.3 13.9
15.7 14.8 11.9 05.8
EGNR 90 GR1 RE(Mn) DECR HECR GR1
CR EGNR GLSR R2 GLSR
100
11.6 11.7 11.10 11.12 11.13 11.15 11.8 GR1 11.11 41
R1 100
05.7 14.13
C3 C2
RE(Mn) C1 EGNR DECPR
GNR EGNR GPR1 DECPR HECPR GLSR 250mfd 500mfd GR2
CPR
14.15
22 6 HECPR
1 3 2 05.9
GR1
12.14 04.14 94 02.11 03.11
15.10
11 GR3 GR3 GR2 GR2
4 GPR1
12 05.13 04.13 05.14 02.14 03.14
04.4 05.11 04.11
DECPR DECPR GR3 GR3 GR3
DECR GR2 42
GR2
04.3 02.9 04.9 14 100 15.13
15.14
HECR GR1 GR1 13 DECPR
GR3
97
03.3
Tr.1 1 Gr.1 1 Gr.2 Tr.3 1 Gr.3
5 Tr.2 7 7 HECR 13.1
2 2 2
8 8
3 3 3 RE(Mn)CR
11.1 11.3 11.4
6 9 9
4 4 4 12.12
91 95 98 13.6
RE(Mn)CR HECR DECR RE(Mn)CPR
93
GNR 51
92 96 99 52 10
56
15.9
58
40
01 03
GR1 39 RE
11.14 (Mn)CR HECR
15.8
04 06
12.1 02.13 02.15 GR3 DECR GNR
GLSR RE(Mn)CR DECPR HECPR
50 07 08 09
46
48 ERNR GLSR GR1
03.1
12.13 13.3
RE(Mn)CR 14.9 10 11 12
DECPR HECR RE(Mn)
GR1 GPR1 GR2
CPR
14.12
59 60
89 13 14 15
RE(Mn)CPR
DECPR GR3 HECPR
49
57 61 67 64 83 65 66 17 37 53 54 55
12.6 04.6 15.6 13.7 14.7 13.8 04.8 12.11 03.10 12.10 13.10 14.10
GNR GNR GNR EGNR EGNR GLSR GLSR GR2 GPR1 GPR1 GPR1 GPR1
47 71 21 74 84 75 76 18 38 43 44 45
RACK NO : 46
SR.NO. GROUP 57,47 61,71 67,21 64,74 83,84 65,75 66,76 17,18 37,38 53,43 54,44 55,45
01 S11 01 707 168 694 182 694 165 163 694
02 S13 01 707 694 182 154 694
03 S15 01 707 129 168 694 694 694
04 S17 01 707 168 694 182 694 165 163 694
05 S42 01 707 155 182 155 694
06 S44 01 707 168 695 182 155 165 164 695
07 S50 01 707 129 168 695 165 164 695
08 A386 707 695 695 695
09 A388 707 695 156 695
10
11
12
13
14
15
16
7 8
15 85 81 69
14.4 12.3 12.4
05.10 13.4 03.4 03.12
31 34
L1 rd L2 gn
SR.NO. GROUP 15,16 85,86 81,82 69,79 70,80 62,72 63,73 68,78 87,88 7,8,9,31,32,33,34,35,36
01 S11 27 694 06 196 53 694 160
02 S13 27 694 06 197 55 694 160
03 S15 26 07 199 694 26 160
04 S17 26 694 26 07 202 694 26 160
05 S42 27 08 08 695 563 57 08 161
06 S44 27 695 08 695 564 59 695 161
07 S50 26 09 26 09 695 565 09 26 161
08 A386 74 09 09 695 149 74 09 161
09 A388 76 10 10 695 76 10 162
10
11
12
13
14
15
16
Objective Questions
i) UDKR _______________________________________________________
ii) ZDUCR_______________________________________________________
v) WKR1 _________________________________________________________
1.
i) iv)
ii) v)
iii) vi)
3.
i)
ii)
iii)
iv)
v)
www.iriset.indianrailways.gov.in