WIN – IO – 4DI1DOM CE
Technical Datasheet Input / Output Modules with Modbus RTU
Protocol with RS485 Interface
The IO modules communicate via RS485. The port can drive distances up to max
700 meters without the use of any repeater (this feature however also depends
on the signal strength of the Modbus Master Device).
The RS485 Digital IO module is sturdy, low power usage and easy to use.
4 Port 4 DI + 1 DO Module: -
The IO modules are mounted on DIN rail mountable casing and with exposed
connectors and LED indicators. The DIP switch for Slave ID and Baud rate are
placed inside the enclosure.
The design of the modules incorporates ‘resettable Fuses’ to safeguard against
reverse polarity connection both for Power and Communication port.
Specifications
General –
I/O Connectors 12 Pin 5.08 mm pitch pluggable screw Terminal Block,
2 Pin 5.08 mm pitch pluggable screw terminals.
Dimensions 110 mm L x 70 mm B x 50 mm H
Power Input Power – 12 - 24 VDC or V 24 AC/DC
Typical – 12V DC @ 110mA
Operating Temperature 0 – 60 C (32 ~ 140F)
Storage Temperature -20 - 70 C (-4 ~ 158F)
WIN – IO – 4DI1DOM CE AUGMATIC TECHNOLOGIES PVT. LTD.
WIN – IO – 4DI1DOM CE
Storage Humidity 5 ~ 95 % RH, non – Condensing
Certifications
DI Inputs –
Channels 4
Sense Voltage 3.3 – 30 VDC
Sense Logic Logic ‘0’ = <1 VDC, Logic ‘1’ = >3.3 VDC
Isolation Optically isolated
Response Time 2 msec, Max 6 msec
Relay Output –
Channels 1
Contact Form 1A, 1C
Contact Material Ag Alloy
Contact Capacity 10A @ 240VAC, 10A @ 28VDC
Coil Voltage 5 – 48 VDC
Coil Power 0.36 W
Insulation Resistance 250M
Electrical Life 1 x 10^5
Mechanical Life 1 x 10^7
Operating Time 7 msec, Max 15 msec
Release Time 2 msec, Max 6 msec
Additional Features: -
Communication port isolated
Input power reverse polarity safety
ESD Safety IEC 61000-4-2, 30KV contact, 30KV air
EFT IEC 61000-4-4, 50A (5/50ms)
750V isolation.
CRC Error check.
No configuration needed on the IO board
Configuration Settings: -
Communication Speed 9600 – 115200 (DIP SW selectable)
Data Bits 8
Parity None
Stop bit 1
CRC Yes
WIN – IO – 4DI1DOM CE AUGMATIC TECHNOLOGIES PVT. LTD.
WIN – IO – 4DI1DOM CE
Slave ID 1 – 15 (DIP SW selectable)
Function code DI 0x02 Read discrete Input
DI Register Address 0,1,2,3.
Function code 0x05 and 0x0F (5 Single coil & 15 multiple coil)
DO Register Address 1.
Modbus
Function Register Data
ID Function Protocol
Description Description Type
Code
DI 1(With & Without
1 10001 0X02 RS485 1 Bit Boolean
Potential)
DI 2(With & Without
2 10002 0X02 RS485 1 Bit Boolean
Potential)
DI 3(With & Without
3 10003 0X02 RS485 1 Bit Boolean
Potential)
DI 4(With & Without
4 10004 0X02 RS485 1 Bit Boolean
Potential)
Modbus
Function Register Data
ID Function Protocol
Description Description Type
Code
1 DO 1 00001 0X05,0X0F RS485 1 Bit Boolean
Note: -
For MODBUS communications, a shielded and twisted pair cable is used. One
example of such cable is Belden 3105A.
Recommended Cable Electrical Characteristics: -
22 AWG Cable Shielded and twisted pair should be used.
Tinned Copper Recommended
Nominal Conductor DCR 14.7 ohm / 1000 ft
Nominal Capacitance 11 pf / feet (conductor to conductor)
High Frequency Non-Insertion Loss 0.5db / 100ft
Connection Instruction FOR WIN - IO – 4DI1DOM CE
WIN – IO – 4DI1DOM CE AUGMATIC TECHNOLOGIES PVT. LTD.
WIN – IO – 4DI1DOM CE
• For Digital Input Potential Free Contact Detection 12V & + terminals should be connected to the WIN - IO
– 4DI1DOM - CE Module DI Pins.
•
• For Digital Input with Potential (3V to 30V) Contact + & - terminals should be connected to WIN - IO –
4DI1DOM - CE Module DI Pins.
SLAVE ID DESCRIPTION
MSB
LSB
For Slave ID Selection SW is used to Set The SLAVE ID .
For Slave ID DIP Switch LSB is “1” follow through “4” is MSB.
Slave ID Confirmed through below Device ID table .
IF Eg. Slave ID 1 is Needed to be selected Switch number 1 should pulled up other three should be
selected down side. So”1 0 0 0” will be selected as Slave ID 1.
DIP SWITCH OUTPUT OUTPUT
Slave
(Binary) (Decimal)
ID 1 2 3 4
0 OFF(0) OFF(0) OFF(0) OFF(0) 0001 1
1 ON(1) OFF(0) OFF(0) OFF(0) 0001 1
2 OFF(0) ON(1) OFF(0) OFF(0) 0010 2
3 ON(1) ON(1) OFF(0) OFF(0) 0011 3
4 OFF(0) OFF(0) ON(1) OFF(0) 0100 4
5 ON(1) OFF(0) ON(1) OFF(0) 0101 5
6 OFF(0) ON(1) ON(1) OFF(0) 0110 6
7 ON(1) ON(1) ON(1) OFF(0) 0111 7
8 OFF(0) OFF(0) OFF(0) ON(1) 1000 8
9 ON(1) OFF(0) OFF(0) ON(1) 1001 9
10 OFF(0) ON(1) OFF(0) ON(1) 1010 10
11 ON(1) ON(1) OFF(0) ON(1) 1011 11
12 OFF(0) OFF(0) ON(1) ON(1) 1100 12
13 ON(1) OFF(0) ON(1) ON(1) 1101 13
14 OFF(0) ON(1) ON(1) ON(1) 1110 14
15 ON(1) ON(1) ON(1) ON(1) 1111 15
WIN – IO – 4DI1DOM CE AUGMATIC TECHNOLOGIES PVT. LTD.
WIN – IO – 4DI1DOM CE
Modbus Input
RS485 24 AC-
DC
SLAVE ID
LSB
MSB
LSB
MSB
BAUD
RATE
DI4 DI3 DI2 DI1 +12 V 1 DO
DI Inputs DI Ref Port
WIN – IO – 4DI1DOM CE AUGMATIC TECHNOLOGIES PVT. LTD.
WIN – IO – 4DI1DOM CE
SLAVE ID DESCRIPTION
MSB
LSB
• For Baud rate Selection, DIP SW is used as per the diagram.
• Pulling up the switch will make Baud rate active.
• If no selection is made 9600 will be default Baud rate.
• When u change the Baud rate in the Module power ‘ON’ condition,
pls press the reset button to get Change to affect.
Baud Rate DIP SWITCH
1 2 3 4
9600 OFF OFF OFF OFF
19200 ON OFF OFF OFF
38400 OFF ON OFF OFF
57600 OFF OFF ON OFF
115200 OFF OFF OFF ON
Contact us: -
Augmatic Technologies Pvt. Ltd.,
Plot no 6, Shah Industrial Estate II,
Kotambi,
Vadodara – 391510.
Email –
[email protected] WIN – IO – 4DI1DOM CE AUGMATIC TECHNOLOGIES PVT. LTD.