0% found this document useful (0 votes)
23 views4 pages

6ES73311KF020AB0 Datasheet en

The document provides a detailed data sheet for the SIMATIC S7-300 Analog Input SM 331, which features 8 isolated analog inputs with a resolution of 13 bits. It outlines specifications such as input ranges for voltage, current, and resistance measurements, as well as power requirements and operational error limits. Additionally, it includes information on dimensions, weights, classifications, and approvals for hazardous locations.

Uploaded by

niepengerwo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
23 views4 pages

6ES73311KF020AB0 Datasheet en

The document provides a detailed data sheet for the SIMATIC S7-300 Analog Input SM 331, which features 8 isolated analog inputs with a resolution of 13 bits. It outlines specifications such as input ranges for voltage, current, and resistance measurements, as well as power requirements and operational error limits. Additionally, it includes information on dimensions, weights, classifications, and approvals for hazardous locations.

Uploaded by

niepengerwo
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 4

Data sheet 6ES7331-1KF02-0AB0

SIMATIC S7-300, Analog input SM 331, Isolated 8 AI, resolution 13 bits


U/I/resistor/Pt100, NI100, NI1000, LG-NI1000, PTC/KTY, 66 ms conversion time;
1x 40-pole

Input current
from backplane bus 5 V DC, max. 90 mA
Power loss
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 8
● For resistance measurement 8
permissible input voltage for voltage input (destruction limit), 30 V; 12 V continuous, 30 V for max. 1 s
max.
permissible input current for current input (destruction limit), 40 mA
max.
Input ranges
● Voltage Yes
● Current Yes
● Thermocouple No
● Resistance thermometer Yes
● Resistance Yes
Input ranges (rated values), voltages
● 0 to +10 V Yes
— Input resistance (0 to 10 V) 100 kΩ
● 1 V to 5 V Yes
— Input resistance (1 V to 5 V) 100 kΩ
● 1 V to 10 V No
● -1 V to +1 V Yes
— Input resistance (-1 V to +1 V) 100 kΩ
● -10 V to +10 V Yes
— Input resistance (-10 V to +10 V) 100 kΩ
● -2.5 V to +2.5 V No
● -250 mV to +250 mV No
● -5 V to +5 V Yes
— Input resistance (-5 V to +5 V) 100 kΩ
● -50 mV to +50 mV Yes
— Input resistance (-50 mV to +50 mV) 100 kΩ
● -500 mV to +500 mV Yes
— Input resistance (-500 mV to +500 mV) 100 kΩ
● -80 mV to +80 mV No
Input ranges (rated values), currents
● 0 to 20 mA Yes
— Input resistance (0 to 20 mA) 100 Ω
● -10 mA to +10 mA No

6ES73311KF020AB0 Subject to change without notice


6/6/2025
Page 1/4 © Copyright Siemens
● -20 mA to +20 mA Yes
— Input resistance (-20 mA to +20 mA) 100 Ω
● -3.2 mA to +3.2 mA No
● 4 mA to 20 mA Yes
— Input resistance (4 mA to 20 mA) 100 Ω
Input ranges (rated values), thermocouples
● Type B No
● Type C No
● Type E No
● Type J No
● Type K No
● Type L No
● Type N No
● Type R No
● Type S No
● Type T No
● Type U No
● Type TXK/TXK(L) to GOST No
Input ranges (rated values), resistance thermometer
● Cu 10 No
● Ni 100 Yes; Standard/climate
— Input resistance (Ni 100) 100 MΩ
● Ni 1000 Yes
— Input resistance (Ni 1000) 100 MΩ
● LG-Ni 1000 Yes; Standard/climate
— Input resistance (LG-Ni 1000) 100 MΩ
● Ni 120 No
● Ni 200 No
● Ni 500 No
● Pt 100 Yes; Standard/climate
— Input resistance (Pt 100) 100 MΩ
● Pt 1000 No
● Pt 200 No
● Pt 500 No
Input ranges (rated values), resistors
● 0 to 150 ohms No
● 0 to 300 ohms No
● 0 to 600 ohms Yes
— Input resistance (0 to 600 ohms) 100 MΩ
● 0 to 6000 ohms Yes
— Input resistance (0 to 6000 ohms) 100 MΩ
Thermocouple (TC)
Temperature compensation
— parameterizable No
— internal temperature compensation No
— external temperature compensation with No
compensations socket
Characteristic linearization
● parameterizable Yes
— for thermocouples No
— for resistance thermometer yes; Pt100 standard/air con.; Ni100 standard/air con.; Ni1000 standard/air con.;
LG-Ni1000 standard/air con.
Cable length
● shielded, max. 200 m; max. 50 m at 50 mV
Analog value generation for the inputs
Integration and conversion time/resolution per channel
● Resolution with overrange (bit including sign), max. 13 bit
● Integration time, parameterizable Yes; 60 / 50 ms
● Basic conversion time (ms) 66 / 55 ms
● Interference voltage suppression for interference 50 / 60 Hz
frequency f1 in Hz

6ES73311KF020AB0 Subject to change without notice


6/6/2025
Page 2/4 © Copyright Siemens
Encoder
Connection of signal encoders
● for voltage measurement Yes
● for current measurement as 2-wire transducer Yes; with external supply
● for current measurement as 4-wire transducer Yes
● for resistance measurement with two-wire connection Yes
● for resistance measurement with three-wire connection Yes
● for resistance measurement with four-wire connection Yes
Errors/accuracies
Operational error limit in overall temperature range
● Voltage, relative to input range, (+/-) 0.6 %; ±0.6 % (±5 V, 10 V, 1 to 5 V, 0 to 10 V); ±0.5 % (±50 mV, 500 mV, 1 V)
● Current, relative to input range, (+/-) 0.5 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
● Resistance, relative to input range, (+/-) 0.5 %; 0 to 6 kohms, 0 to 600 kohms
● Resistance thermometer, relative to input range, (+/-) 1 Kelvin (Pt100, Ni100, climatic; Ni1000, LG-Ni1000, standard; Ni1000, LG-
Ni1000, climatic); 1.2 Kelvin (Pt100, Ni100, standard)
Basic error limit (operational limit at 25 °C)
● Voltage, relative to input range, (+/-) 0.4 %; 0.4% (±5 V, 10 V, 1 to 5 V, 0 to 10 V); 0.3% (±50 mV, 500 mV, 1 V)
● Current, relative to input range, (+/-) 0.3 %; ±20 mA, 0 to 20 mA, 4 to 20 mA
● Resistance, relative to input range, (+/-) 0.3 %; 0 to 6 kohms, 0 to 600 kohms
● Resistance thermometer, relative to input range, (+/-) 1 Kelvin (Pt100, Ni100, standard); 0.8 Kelvin (Pt100, Ni100, climatic; Ni1000,
LG-Ni1000, standard; Ni1000, LG-Ni1000, climatic)
Interrupts/diagnostics/status information
Diagnostics function No
Alarms
● Diagnostic alarm No
● Limit value alarm No
Diagnoses
● Diagnostic information readable No
Diagnostics indication LED
● Group error SF (red) No
Potential separation
Potential separation analog inputs
● between the channels No
● between the channels and backplane bus Yes
Isolation
Isolation tested with 500 V DC
connection method
required front connector 40-pin
Dimensions
Width 40 mm
Height 125 mm
Depth 117 mm
Weights
Weight, approx. 250 g
Classifications
Version Classification

eClass 14 27-24-22-01
eClass 12 27-24-22-01
eClass 9.1 27-24-22-01
eClass 9 27-24-22-01
eClass 8 27-24-22-01
eClass 7.1 27-24-22-01
eClass 6 27-24-22-01
ETIM 9 EC001420
ETIM 8 EC001420
ETIM 7 EC001420
IDEA 4 3562
UNSPSC 15 32-15-17-05

6ES73311KF020AB0 Subject to change without notice


6/6/2025
Page 3/4 © Copyright Siemens
Approvals / Certificates
General Product Approval

Manufacturer Declara- Miscellaneous Metrological Approval


tion

General Product Ap-


EMV For use in hazardous locations
proval

FM

For use in hazardous locations Maritime application

Miscellaneous CCC-Ex

Maritime application

NK / Nippon Kaiji Ky- CCS (China Classifica-


okai tion Society)

last modified: 4/7/2025

6ES73311KF020AB0 Subject to change without notice


6/6/2025
Page 4/4 © Copyright Siemens