Technical Specification of 315 2500 KVA Distribution Transformer - PDF 01.06.17
Technical Specification of 315 2500 KVA Distribution Transformer - PDF 01.06.17
2000KVA & 2500 KVA, 11/0.433 KV, 22/0.433 KV, 33/0.433 KV, Star-1, Star-2, Star-3, Star-
4 & Star-5, THREE PHASE, DISTRIBUTION TRANSFORMERS OUTDOOR TYPE OIL IMMERSED
WITHOUT CSP FEATURE.
TECHNICAL SPECIFICATION
FOR
CE/MMC/MSC-II/3Phase/DT/T/2017/03,
INDEX
Clause No. Contents
1 Scope
2 System Particulars
3 Service Condition
4 Applicable Standards
5 Specific Technical requirement
6 Design & Construction
6.1 Core
6.2 Windings
6.3 Losses
6.4 Insulation Material & Clearances
6.5 Impedance Value
6.6 Tank
6.7 Off Load Taps
7 Efficiency
8 Heat Dissipation
9 Total minimum oil volume
10 Conservator.
11 Breathers.
12 Terminals
13 Bushing and connections
14 Internal Connections
15 Tank base channel
16 Terminal Marking Plate & Rating Plate
17.1 Fittings
17.2 Fasteners
18 Lightning Arrestor
19 Transformer Oil
20 Tests & Inspection
21 Challenge Testing
22 Type Tests
23 Drawings
24 Rejection
25 Cleaning & Painting
26 Guaranteed Technical Particulars
27 Testing facilities
28 Submission of Routine Test Certificate
29 Stage Inspection
Testing of all distribution transformers for losses at 50 %
30
load and 100 % load
31 Random Sample Testing
32 Inspection & Testing of Transformer Oil
33 Quality Assurance
34 Qualifying Requirements
35 Final Inspection
36 Performance Guarantee
37 Cost Data Sheet
38 Schedule
Schedule A Guaranteed and Other Technical Particulars
Schedule B Tenderer‘s experience
Annexure-I Air Pressure Test
Annexure-II Unbalance Current Test
Annexure-III Temperature Rise Test
TECHNICAL SPECIFICATION FOR 315 kVA & above and upto 2500 kVA,
11/0.433 , 22/ 0.433 & 33 /0.433 kV, Star-1, Star-2, Star-3, Star-4 & Star-5, THREE
PHASE, DISTRIBUTION TRANSFORMERS WITHOUT CSP FEATUTRE.
CE/MMC/MSC-II/3Phase/DT/T/2017/03 (Rev.)
1 Scope:-
1.1 This specification covers design, manufacturing, testing and delivery of 315 kVA &
above and upto 2500 kVA, 11/0.433 , 22/ 0.433 kV & 33/0.433 kV, Star-1, Star-
2, Star-3, Star-4 & Star-5, three phase distribution transformers without CSP
feature oil immersed, Oil Natural (ONAN) suitable for 11 kV, 22 kV & 33 kV,
50 Hz, Distribution system.
1.2 The equipment offered shall be complete with all parts necessary for their effective
and trouble-free operation. Such parts will be deemed to be within the scope of the
supply irrespective of whether they are specifically indicated in the commercial
order or not.
1.3 It is not the intent to specify herein complete details of design and construction. The
equipment offered shall conform to the relevant standards and be of high quality,
sturdy, robust and of good design and workmanship complete in all respects and
capable to perform continuous and satisfactory operations in the actual service
conditions at site and shall have sufficiently long life in service as per statutory
requirements.
1.4 The design and constructional aspects of materials shall not withstanding any
anomalies, discrepancies, omissions, in-completeness, etc. in these specifications
and will be subject to good engineering practice in conformity with the required
quality of the product, and to such tolerances, allowances and requirements for
clearances etc. as are necessary by virtue of various stipulations in that respect in
the relevant Indian Standards, IEC standards, I.E. Rules, I.E. Act and other
statutory provisions.
1.5 The Bidder/supplier shall bind himself to abide by these considerations to the entire
satisfaction of the purchaser and will be required to adjust such details at no extra
cost to the purchaser over and above the tendered rates and prices.
1.6 Tolerances:
The tolerance of guaranteed performance figures shall be as specified in the (Part-I)
table 1 of latest issue of IS 2026 except losses or relevant International Standard
except wherever specified otherwise in this specification.
2 System Particulars:-
The transformers shall be suitable for outdoor installation with following system
particulars and they should be suitable for service under fluctuations in supply
voltage as permissible under Indian Electricity Rules
3.3 The equipment shall be for use in moderately hot and humid tropical climate
conducive to rust and fungus growth.
3.4 The Distribution Transformer shall be mark with standard mark governed by BIS as
per clause 13.4 of IS 1180(Part 1):2014] .
3.5 The Distribution Transformer shall bear Star 1 or 2 or 3 or 4 or 5 ratings label
approved by BEE ( Bureau of Energy Efficiency).
3.6 The Distribution Transformer shall bear level 2 (star 1 of BEE) or level 3 (star 2 of
BEE) ratings label approved by BIS (Bureau of Indian Standard) as per IS 1180
(Part-1):2014.
3.7 The Bidder/ Manufacturer shall possess the BIS license for offered product.
4 APPLICABLE STANDARDS:-
4.1 The design, manufacture and performance of the equipment shall comply with all
currently applicable statutes, regulations and safety codes. Nothing in this
specification shall be construed to relieve the bidder off his responsibilities.
4.2 The Distribution Transformers shall conform to IS: 1180 (Part 1) : 2014 amended
up to date or other International Standards for equal or better performance. Unless
otherwise modified in this specification the Distribution Transformers shall comply
with the Indian Standard Specification IS 1180 latest.
4.3 Unless otherwise specified, the equipment offered shall conform to amended up to
date Indian, IEC, British or U.S.A. Standards and in particular, to the following:-
4.4 The applicable standards are as follows :
Sr.No. IS number IS name
6.1 Core
i The core shall be stacked/ wound type.
a) For Stack core :- The core shall be of high grade cold rolled grain
oriented (C.R.G.O) annealed steel lamination having low loss and good
grain properties, coated with hot oil proof insulation, bolted together to
the frames firmly to prevent vibration or noise. All core clamping bolts
shall be effectively insulated. The complete design of core must ensure
The core shall be ‗C‘ type construction of high grade cold rolled grain
oriented (C.R.G.O.) annealed steel lamination having low loss and good
grain properties, coated hot oil proof insulation. The complete design of core
must ensure permanency of the core losses with continuous working of the
transformers. The core material shall not be brittle in case of CRGO
material.
1. Core clamping shall be with top and bottom U- shaped core clamps
made of sheet steel clamped.
3. Suitable provision shall be made in the bottom core clamp / bottom plate
of the transformer to arrest movement of the active part.
4. Core shall be clamped by 16 mm diameter MS Tie rods.
ii The grade of core laminations shall be M4 or better.
iii The successful bidder, shall be required to submit the manufacturer‘s test
report showing the Watt Loss per kg and the thickness of the core
lamination, to ascertain the quality of Core materials.
The purchaser reserves the right to get sample of the core material tested at
any Government recognized laboratory.
iv The transformer core shall not be saturated for any value of V/f ratio to the
extent of 112.5% of the rated value of V/f ratio (i.e. 11000/50 or 22000/50)
(due to combined effect of voltage and frequency) up to 12.5% without
injurious heating at full load conditions and will not get saturated. The
bidder shall furnish necessary design data in support of this situation.
v Flux density:-
The maximum flux density in any part of the core and yoke at rated voltage
and frequency shall be such that the flux density with +12.5 % combined
voltage and frequency variation with rated voltage and frequency does not
exceed 1.9 Tesla. Flux density should not be more than 1.55 Tesla at rated
voltage and frequency.
vi The No load current at rated voltage shall not exceed the percentage as given
below.
The no load current of 315 kVA & above and upto 2500 kVA transformer
shall not exceed 2% the full load current and will be measured by energizing
the transformer at rated voltage and frequency. Increase of 12.5 percent of
rated voltage shall not increase the no load current by 5% of full load
current.( As per IS 1180 (Part1):2014)
Number of steps of core shall be minimum of
Sr. No. Rating (kVA) Number of steps
1 315 Min. 7 standard steps
2 630 Min. 9 standard steps
3 1000 Min. 9 standard steps
4 1250 Min. 11 standard steps
5 1600 Min. 11 standard steps
6 2000 Min. 13 standard steps
7 2500 Min. 13 standard steps
Rating Impedance Maximum total losses in watts up to 11 kV Class ( For ratings above 200 kVA)
( Percent)
Star 1 Star 2 Star 3 Star 4 Star 5
50% 100% 50% 100% 50% 100% 50% 100% 50% 100%
Load Load Load Load Load Load Load Load Load Load
315 4.50 1025 3100 955 2750 890 2440 829 2164 772 1920
630 4.50 1860 5300 1745 4850 1637 4438 1536 4061 1441 3717
1000 5.00 2790 7700 2620 7000 2460 6364 2310 5785 2170 5259
1250 5.00 3300 9200 3220 8400 3142 7670 3066 7003 2991 6394
1600 6.25 4200 11800 3970 11300 3753 10821 3547 10363 3353 9924
2000 6.25 5050 15000 4790 14100 4543 13254 4309 12459 4088 11711
2500 6.25 6150 18500 5900 17500 5660 16554 5430 15659 5209 14813
Tolerances:
No positive tolerance shall be allowed on the maximum losses given in the above
table for both 50 % & 100 % loading values. In case the actual loss values exceed
the above guaranteed values, the transformers shall be rejected at the risk, cost
and responsibility of the supplier. The bidder should guarantee individual No load
losses without any positive tolerance.
The values guaranteed in G.T.P. for flux density, no load current at rated voltage,
no load current at 100 % & 112.5% of rated voltage and no load loss at rated
voltage shall be individually met.
The percentage impedance at 75 º C. for different ratings shall be as per Table-1 above.
6.6 Tank
6.6.1 The transformer tank shall be made up of prime quality M.S. sheets of rectangular
shape. No other shape will be accepted. The transformer tank shall be of robust
construction. All joints of tank and fittings should be oil tight and no bulging shall
occur during service. The tank design shall be such that the core and windings can
be lifted freely. The tank plates shall be of such strength that the complete
transformer when filled with oil may be lifted bodily by means of the lifting lugs
provided. Tank inside shall be painted by varnish or oil resistant paint. Top cover
plate shall be slightly sloping; approximately 5 to 10 deg. towards HV bushing and
edges of cover plate should be bent downwards so as to avoid entry of water
through the cover plate gasket. The width of bend plate shall be 25 mm min. The
top cover shall have no cut at point of lifting lug. The rectangular tank shall be
fabricated by welding at corners.
6.6.2 The transformer tank of corrugation is also acceptable, however shape of tank shall
be rectangular only. The corrugation sheets thickness shall be of minimum 1.6 mm.
Corrugation panel shall be used for cooling. The transformer shall be capable of
giving continuous rated output without exceeding the specified temperature rise.
Bidder shall submit the detailed calculation sheet alongwith offer. The safe guard
angle frame 50X50X5 mm shall be welded for corrugated side to the tank.
6.6.3 In rectangular shape tanks, horizontal or vertical joints in tank side walls and its
bottom or top cover will be not allowed. In addition the cover of the main tank shall
be provided with an air release plug to enable air trapped within to be released.
Side wall thickness : 4 mm. (min.)
Top and bottom plate thickness : 6 mm. (min.) from 315 kVA to
1600 kVA
: 10 mm (min) from 2000 kVA &
2500 kVA
a)The pressure deflection, when tank without oil is subjected to a vaccum of 500 mm of
mercury for rectangular tank and 760 mm of mercury for round tank.
b)The permanent deflection shall be as below.
(All figures in mm)
Horizontal length of flat Plate Permanent deflection
Up to and including 750 mm 5.0 mm
751 to 1250 mm 6.5 mm
1251 to 1750 mm 8.0 mm
Above 1751 mm 9.0 mm
c)The tank shall further be capable of withstanding a pressure of 0.8 kg/sq.cm and
vaccum of 0.7 kg/sq.cm(g) without any deformation.
d)The height of the tank shall be such that minimum vertical clearance up to the top
cover plate of 120 mm is achieved from top yoke / from the top of tap changer if tap
is provided.
6.6.4 Reinforced by welded angle 50X75X5 MM upto 1250 kVA & 70X75X5 MM upto
2500 kVA on all the outside walls on the edge of tank to form two equal
compartments
6.6.5 When transformer tank without oil is subject to air pressure of 35 KPa above
atmospheric pressure for 30 min. Pressure test shall be performed carefully at the
time of 1st stage inspection only to confirm the adequacy of reinforcement angle and
gauge of the tank and certified by E.E. (IW).
6.6.6 All welding operations to be carried out by MIG process.( Metal Inert Gas Welding)
6.6.7 Lifting lugs: 4 nos. welded heavy duty lifting lugs of MS plate of 12mm thickness
upto 1600 kVA & 16 mm thickness upto 2500 kVA , suitably reinforced by vertical
supporting flat of same thickness as of lug welded edgewise below the lug on the
side wall, up to reinforcing angle and for top cover 8 mm thickness upto 1600 kVA
and 10 mm thickness upto 2500 kVA. They shall be so extended that cutting of
bend plate is not required.
6.6.8 Pulling lugs: 4 nos. of welded heavy duty pulling lugs of MS plate of 8mm & 10
mm thickness for upto 1600 kVA & 2500 kVA respectively, shall be provided to
pull the transformer horizontally.
6.6.9 All bolts / nuts / washers exposed to atmosphere shall be as follows:
a) Size 12mm or below—stainless steel.
b) Above 12mm--- steel with suitable finish like electro galvanized with
passivation or hot dip galvanized.
6.6.10 Top cover fixing bolts: GI nut bolts of 1/2‖ diameter with one plain washer shall be
used for top cover fixing, spaced at 4‖ apart. 6 mm neoprene bonded cork oil
resistance gaskets conforming to type B/C IS 4253 Part-II amended up to date will
be placed between tank and cover plate.
6.6.11 Vertical clearance: - The height of the tank shall be such that minimum vertical
clearance up to the top cover plate of 120 mm is achieved from top yoke.
6.6.12 The transformer tank shall be of adequate mechanical strength to withstand positive
and negative pressures built up inside the tank while the transformer is in operation.
6.6.13 The tank design shall be such that the core and windings can be lifted freely.
6.6.14 Plain tank shall be capable of withstanding a pressure of 80kPa for 30 minutes and a
vacuum of 500 mm of mercury for 30 minutes (Type Test). The permanent
deflection of flat plates shall not exceed the values given in IS 1180(Part 1): 2014
clause no. 21.5.2.1.
6.6.15 All bolts /nuts /washers exposed to atmosphere shall be as follows:-
a) Size 12 MM or below – Stainless steel
b) Size above 12 MM – steel with suitable finish like electro galvanised with
passivation.
6.6.16 Thermometer pocket must be located at centre of top cover or high side of tank
height for true valve of max top oil temperature
6.6.17 Air release plug must be placed at top cover of explosion vent pipe, testing at
lkg/sq.cm carried out on sample at first lot to know correct material used for
diaphragm and it must burst before pre determined pressure.
6.7.3 Tapping Method: Off circuit tap-changing arrangement shall be either by means of
links or by means of an externally-operated switch with mechanical locking device
and a position indicator. Arrangement for pad-locking shall be provided. ( As per IS
1180 (Part1):2014 Clause 7.7.2)
6.7.4 The Transformer shall be capable of being operated without danger on any tapping at
the rated kVA with voltage variation ± 10% corresponding to the voltage of that
tapping.
7.0 Efficiency:
The efficiency is the ratio of output in KW to the input in KW.
Sr.No. KVA Oil in liters (exclusive of oil absorbed in core & coil
rating assembly)
Voltage rating Voltage rating Voltage rating
11/0.433 kV 22/0.433 kV 33/0.433 kV
1 315 500 550 580
2 630 750 800 840
3 1000 850 900 950
4 1250 1000 1050 1100
5 1600 1300 1350 1400
6 2000 1550 1600 1650
7 2500 1900 1950 2000
10.0 Conservator:
a) The total volume of conservator shall be such as to contain 10% of total quantity of
oil. Normally 3% quantity of the total oil will be contained in the conservator.
Dimension of the conservator shall be indicated on the General Arrangement
Drawing. The capacity of the conservator tank shall be designed keeping in view
the total quantity of oil and its contraction and expansion due to the temperature
variations.
b) Oil level indicator shall be provided on the side which will be with fully covered
detachable flange with single gasket and tightened with MS nut-bolt. Level
indication by colour shall not be accepted.
c) The inside diameter of the pipe connecting the conservator to the main tank shall be
within 20 to 32 mm and it should be project into the conservator in such way that its
13.2 The bushing shall be made in two parts. The outer bushing shall be of porcelain.
The dimensions of the outer bushing shall confirm to the relevant Part/Section of IS
3347 depending on the voltage class. The internal bushing shall be of either
porcelain or tough insulating material, like epoxy and shall have embedded stem.
Metal portion of the internal HV and LV bushing inside the tank shall remain
dipped in oil in all operating conditions.
13.3 Gaskets shall be made of synthetic rubber or synthetic rubberized cork resistant to
hot transformer oil.
13.4 For 11 kV class 12 kV bushing, for 22 kV class 24 kV & 33 kV class 36 kV bushing
shall be used and for 433 volts 1.0 kV bushing shall be used. Bushings of the same
voltage class shall be interchangeable. Bushings with plain shed shall be as per relevant
IS:3347 amended up to date. HV bushings shall be mounted on the top of the
transformer tank & LV bushings shall be mounted on side of the transformer tank.
13.5 HV bushings shall be mounted on curvature shaped embossed plate and not on welded
M.S ring. Supporting clamps for LT cable should be provided to avoid the weight of
cable on the Bushing.
13.6 The minimum creepage distance for both HV & LV Bushings shall not be less than 25
mm per kV.
ISI Mark.
BEE Energy Efficiency Star label
BIS Energy Efficiency level.
Order No. – Month & year.
Sr. No. of transformer.
Date of manufacturing – Month & year.
17.1 Fittings:
17.2 Fasterners.
All bolts, studs, screw threads, pipe threads, bolt heads and nuts shall comply
with the appropriate Indian standards for metric threads or the technical
equivalent.
Bolts or studs shall not be less than 6 mm in diameter except when used for
small wiring terminals.
All nuts and pins shall be adequately locked.
Wherever possible bolts shall be fitted in such a manner that in the event of
failure of locking resulting in the nuts working loose and falling off, the bolt
will remain in position.
All ferrous bolts, nuts and washers placed in outdoor positions shall be treated
to prevent corrosion by hot dip galvanizing except high tensile steel bolts and
spring washers, which shall be Electro, galvanized. Appropriate precautions
shall be taken to prevent electrolytic action between dissimilar materials.
Each bolt or stud shall project at least one thread but not more than three threads
through the nut, except when otherwise approved for terminal board studs or
relay stems. If bolts are provided at inaccessible places for ordinary spanners,
special spanners shall be provided.
The length of screwed portion of the bolts shall be such that no screw thread
may form part of a sheer plane between members.
Taper washers may be provided where necessary. Protective washers of suitable
material shall be provided front and back of the securing screws.
LT side should be of Pad type terminal.
Transformer oil to be used in all the Distribution transformers shall comply with the
requirements of latest IS 335/1983 amended up to date thereof. In addition the oil
should conform to `Ageing Characteristics‘ specified below for New Oil and Oil in
Transformers. Type test certificates of oil being used shall be produced to EE (IW)
at the time of stage inspection.
New oil - Ageing characteristics after accelerated ageing test 96 hrs at 115° C (open
beaker method with copper catalyst):
20.0 Test and Inspection:- All routine, type and special tests as described in Clause
21.2 to 21.4 of IS 1180 (Part 1):2014 shall be performed as per relevant parts of
IS 2026. Pressure and oil leakage test shall be conducted as per Clause 21.5 of IS
1180 (Part1):2014.
20.1 Routine Tests (to be conducted on all units):- The following shall
constitute the routine tests:
a) Measurement of winding resistance [ IS 2026 (Part 1)].
b) Measurement of voltage ratio and check of phase displacement [ IS 2026 (Part
1)].
c) Measurement of short circuit impedance ( principal tapping, when applicable)
and load loss at 50 percent and 100 percent load [ IS 2026 (Part 1)].
d) Measurement of no load loss and current [ IS 2026 (Part 1)].
e) Measurement of insulation resistance [ IS 2026 (Part 1)].
f) Induced over-voltage withstand test [ IS 2026 (Part 3)].
g) Separate-source voltage withstand test [ IS 2026 (Part 3)].
h) Pressure test
i) Oil leakage test
20.2 Type Tests (to be conducted on one unit):- The following shall constitute
the type tests:
a) Lightening impulse test [ IS 2026 (Part 3)].
b) Temperature-rise test [ IS 2026 (Part 2)].
Note – Maximum measured total loss ( No load at rated excitation + load loss
at maximum current tap converted to 75 Deg.Celcius reference temperature) at
100 percent loading shall be supplied during temperature rise test.
c) Short-circuit withstand test [ IS 2026 (Part 5)]. ( above 200 kVA)
d) Pressure test.
In addition to that the successful bidder shall submit the type test report of
transformer Oil & HV/LV bushings as per relevant IS with offer.
20.3 Special Tests (to be conducted on one unit):- The following shall
constitute the special tests which shall be carried out by mutual agreement between
the user and the supplier.
a) Determination of sound levels [ IS 2026 (Part 10)].
b) Short-circuit withstand test [ IS 2026 (Part 5)]. ( above 200 kVA).
NOTE :- Routine tests before and after short circuit test shall be conducted as
per IS 2026 ( Part 1)
c) No load current 112.5 percent voltage [refer clause 7.9.2 of IS 1180(Part 1):
2014].
d) Paint adhesion tests: The test is performed as per ASTM D 3359 ( Standard
Test Methods for measuring adhesion by Tape Test).
e) BDV and moisture content of oil in the transformer ( IS 335).
Note:Tests at (d) and (e) may be carried out on more than one unit subject to
agreement between user and supplier.
20.4 Pressure and Oil leakage Test :-
20.4.1 Pressure Test ( Type Test) : For non-sealed and sealed type transformers,
the transformer tank subjected to air pressure of 80 kPa for 30 min and vacuum of
500 mm of mercury for 30 min. The permanent deflection of flat plate, after
pressure/vacuum has been released, shall not exceed the values given below.
Up to 750 mm 5.0 mm
a) Plain tanks : The transformer tank with welded / bolted cover shall be tested at
a pressure of 35 kPa above atmospheric pressure maintained inside the tank for 10
min. There should be no leakage at any point .
b) Corrugated tanks : The corrugated transformer tank shall be tested for air
pressure of 15 kPa above atmospheric pressure maintained inside the tank for 10
min. There should be no leakage at any point .
20.4.3 Oil leakage Test ( routine Test) : The assembled transformer for non-
sealed and sealed type with all fittings including bushing in position shall be
tested at a pressure equivalent to twice the normal head measured at the base of the
tank for 8 h. There should be no leakage at any point. Tank with corrugations shall
be tested for oil leakage test a pressure of 15 kPa measured at the top of the tank
for 6 h. There should be no leakage at any point.
All the routine tests shall be conducted in the suppliers' laboratory at their own
cost.
i) Heat run test shall be arranged free of cost on the unit selected from the 1 st
lot by Executive Engineer/Authorized Representative.
22.2 The type test reports should be submitted and got approved from the Chief Engineer
(MMC) before commencement of supply.
22.3 In case of any of the following, the offer may be considered for
evaluation only.
i) If above tests are carried out beyond 5 years
ii) Impulse Voltage Withstand test ,Dynamic Short Circuit test,
Temperature rise Test & Pressure Test carried out not from
NABL approved Laboratory.
iii) If there is any change in the design/ type of old type tested
transformers to be offered against this specification.
Note: However, In that case successful bidders have to carry out the type tests at the
laboratories accredited by NABL before commencement of supply at their own
expense on the sample drawn by the purchaser from the lot offered for first Stage
Inspection.
22.4 In respect of the successful bidder, the purchaser reserves the right to demand
repetition of some or all the type tests in presence of the purchaser‘s representative.
In case the unit fails in the type tests, the complete supply shall be rejected. The
bidders are therefore requested to quote unit rates for carrying out each type test,
which however, will not be considered for evaluation of the offer.
23.0 Drawings & Calculation sheet:-
23.1 A set of following drawings with all dimensions shall be submitted by the Bidder
along with the offer:
23.2 The drawings shall be of A-3 (420 x 297 mm) size only. The bidder should also
supply along with his offer the pamphlets/literatures etc. for fittings / accessories.
23.3 The bidder should not change design once offered as per A/T, Approved drawings
and Type Test Reports.
23.4 The successful Bidders shall submit complete set of Drawings (as listed in
Cl.No.23.1) of transformer in triplicate indicating dimensions to CE (MMC) for
approval and get approved it before offering Ist stage inspection.
24.0 Rejection :-
24.1 Apart from rejection due to failure of the transformer to meet the specified test
requirements the transformer shall be liable for rejection on any one of the
following reasons.
i. Maximum load losses at 50 % load & 100% Load loss exceeds the specified
values mentioned in Cl. No.6.3 above.
ii. Impedance voltage value exceeds the Guaranteed value plus tolerances as
mentioned at Cl..No.6.5 above.
iii Type test are not carried out as per clause no. 22.0 of the specification.
iv. Drawings are not submitted as per clause no. 23.0 of the specification.
v. GTP not submitted as per clause no. 26.0 of the specification.
vi Heat dissipation calculation sheet are not submitted as per clause no.8.0 of the
specification.
25.0 Cleaning and Painting.
i. The external surfaces shall be painted with one coat of thermo setting powder
paint or one coat of epoxy primer followed by two coats of polyurethane (finish
coat)for (outside) and hot oil resistant paint/varnish with one coat (inside) with
dry film thickness as mentioned in Table 12, clause 15.5 of IS 1180(Part 1):2014.
ii. The certificate shall be produce by the manufacturer if seven tank facilities are
availed from the other vendor about availability of the adequate size of tank for
treatment.
iii.The test of measurement of paint thickness shall be carried out cross hatch test,
chemical test and other as per IS 13871:1993
iv. The surface of the tank shall be properly pre-treated / phosphated in a seven tank
process and shall be applied with a powder coating of 40 micron thickness. The
powder coating shall be of Aircraft Blue colour ( shade No. 108) for
transformers. Powder coating shall be suitable for outdoor use. The seven tank
process facility shall be enhance to ensure proper quality for outdoor application.
v. The month and year of supply shall be painted in red bold Marathi lettering at
two places, one on conservator and other at sum conspicuous place on the
transformer which shall be clearly visible from the ground.
29.2 Chief Engineer (MM Cell) will depute representatives from testing and inspection
wing at the time of Stage inspection.
29.3 10 % of the transformers from the offered lot will be tested for acceptance tests at
factory, in the presence of purchaser's representative before dispatch.
29.4 The inspection may be carried out by the purchaser at any stage of manufacture. The
successful bidder shall grant free access to the purchaser's representatives at a
reasonable time when the work is in progress. Inspection and acceptance of any
equipment under this specification by the purchaser shall not relieve the supplier of
his obligation of furnishing equipment in accordance with the specifications and
shall not prevent subsequent rejection if the equipment is found to be defective.
29.5 The purchaser may at its option, open a transformer supplied to the Stores, in
presence of supplier at site or at Stores. If any of the technical particulars are seen
to be in variance than the guaranteed technical particulars, the whole lot of
transformer will be rejected without any liability on purchaser.
29.6 In addition to the above, the purchaser may pick up any transformer and decide to
get it type tested from any laboratory accredited by NABL at purchaser's cost. The
Bidder will have to organize packing of the transformer at company's Stores for
which they will be paid necessary charges. If the transformer fails to meet the
requirement of type tests, the quantity of transformers ordered on them will be
forthwith rejected and the purchaser may purchase these transformers at the risk and
cost of the supplier.
30.0 Testing of all Distribution Transformers for losses at 50% load and 100% load:
After inspection of new transformers at factory for acceptance of the lot, all
distribution transformers from the lot will be tested for 50% load and 100% load at
all stores. Tenderer has liberty to be present at the time of testing.
All transformers supplied against this specification shall be guaranteed for a period
of 66 months from the date of receipt at the consignee‘s Stores Center or 60 months
from the date of commissioning, whichever is earlier. However, any engineering
error, omission, wrong provisions, etc. which do not have any effect on the time
period, shall be attended to as and when observed/ pointed out without any price
implication.
37.0 COST DATA SHEET:-
The bidders shall submit the cost data sheets indicating the break up prices and
quantity of each raw material and components along with the unit rates required for
manufacture the offered transformers along with the offer. The cost data sheet
format is enclosed herewith.. If the rates quoted are not justified with the cost data
sheets, the offer shall not be considered for evaluation and placement of the order.
The cost data sheets shall be scrutinized by MM Cell section.
FORMAT FOR COST DATA
ITEM ------ KVA , ------- KV DISTRIBUTION TRANSFORMER
UNIT
Sr.
PARTICULARS UNIT RATES QTY AMT (Rs.)
No.
Rs.
1 CORE (M4 or better ) KG
ALUMINIUM/COPPER WITH
2 KG
DPC FOR HV WINDING
ALUMINIUM/COPPER WITH
3
DPC FOR LV WINDING
3 INSULATION PAPER Meter
4 OIL LTRS
5 TANK NO
6 CHANNELS KG
7 INSULATORS/BUSHINGS KG
LUMP
8. OTHERS
SUM
TOTAL
WASTAGE @ %
38.0 Schedules
38.1 The bidder shall fill in the following schedules which form part of the tender
specification and offer. If the schedules are not submitted duly filled in with the
offer, the offer shall be rejected.
Schedule `A'
GUARANTEED TECHNICAL PARTICULARS
As indicated in E-Tendering GTP Parameter
SCHEDULE – ‗B‘
Tenderer shall furnish here a list of similar orders executed/under execution by him to
whom a reference may be made by Purchaser in case he considers such a reference
necessary.
--------------------------------------------------------------------------------------------------------------
Sr. Name of client Value Period of supply Name & Address to
No. & Description. Of Order & commissioning whom reference may
(along with cap. be made.
of T/F)
--------------------------------------------------------------------------------------------------------------
1 2 3 4 5
--------------------------------------------------------------------------------------------------------------
DESIGNATION____________________________________
DATE____________________________________________
Annexure I
Air Pressure Test
Name of Supplier:
Order No.:
Capacity & Voltage Ratio of Distribution Transformer : ______ kVA, ____/0.433 kV
Vector Group Dyn11
Sr. No. of equipment Tested:
Date of Testing:
Reference Standard
All the opening of the transformer tank were closed with suitable gasket, bushing,
valves and plugs. The compressor pipe connected at oil filling hole on conservator and a
pressure guage was fitted at air vent plug. The parallel string were places around the tank,
the distance between string and tank as shown in following diagram were recorded before
applying the pressure and after releasing pressure.
Annexure II
Unbalance Current Test
Name of Supplier:
Order No.:
Capacity & Voltage Ratio of Distribution Transformer : ______ kVA, ____/0.433 kV
Vector Group Dyn11
Sr. No. of equipment Tested:
Date of Testing:
Reference Standard
Transformer Secondary terminals 2U, 2V & 2W are shorted. The shorted 2U, 2V &
2W is connected to 2N through Ammeter. The primary terminals 1U, 1V & 1W are
connected to supply. The rated current _____ A is fed to primary and unbalance current is
noted on Ammeter.
Annexure III
Temperature Rise Test
Name of Supplier:
Order No.:
Capacity & Voltage Ratio of Distribution Transformer : ______ kVA, ____/0.433 kV
Vector Group Dyn11
Sr. No. of equipment Tested:
Date of Testing:
Reference Standard
H. V. Winding L. V. Winding
Rated Line Current in Amp
P. T. Ratio : _______/____ =
C. T. Ratio : _______/_____ =
Wattmeter Constant =
Total Multiplying Factor (MF) =
Ambient Temp.
Rise in Top Oil Temp. °C
W1+W2+W3 watt
Top Oil Temp. °C
Average °C
Total Watt
W1 watts
W2 watts
W3 watts
TIME
T1 °C
T2 °C
T3 °C
Time Resistance
SCHEDULE - A
GURANTEED TECHNICAL PARTICULARS
Sr. Remark
GTP Parameters
No.
1 Name of Manufacturer T
2 Reference Standards T
3 Rating of Transformer in KVA N
4 Primary voltage in kV N
5 Secondary voltage in Kv N
6 Transformer shall be Oil Natural Air Natural (ONAN) type Yes/No B
7 Transformer shall be suitable for Outdoor/ Indoor application. (Yes/No) B
8 Transformer shall be Oil Natural cooled type (yes/No) B
9 Highest System Voltage in Kv N
10 Frequency in HZ. N
11 Transformer shall be suitable for solid neutral earthing (Yes/No) B
12 Service condition shall be applicable as per Technical specification clause no. 3 B
13 Transformer Colour as per IS:5 (Shade no. 108) T
14 Type of connection for H.V. Winding (Delta) (Yes/No). B
15 Type of connection for L.V. Winding (Star) (Yes/No) B
16 Vector Group Dyn-11 (Yes/No) B
17 Name Plate details are as per the requirement specified in tender (Yes/No) B
18 Thickness of Name plate (in SWG) N
19 Maximum temperature rise of Windings over an Ambient temp. of 50°C in °C in N
20 Maximum temperature rise of oil over an Ambient temp. of 50°C in °C in N
21 Approximate overall length of the Transformer in mm N
22 Approximate overall breadth of the Transformer in mm N
23 Approximate overall height of the Transformer in mm N
24 Approximate length of the Transformer tank in mm N
25 Approximate breadth of the Transformer tank in mm N
26 Approximate height of the Transformer tank in mm N
27 Thickness of the side of transformer tank plates in mm N
28 Thickness of the bottom of transformer tank plates in mm N
29 Thickness of the top of transformer tank plates in mm N
30 Size of reinforced welded angle to the Transformer Tank in mm. T
31 Degree of slope to the top plate of Transformer T
32 Shape of transformer Tank T
33 Type of Tank (Corrugated/ Conventional) T
34 In case of corrugated tank, thickness of corrugated sheet (in mm) T
35 Size of Transformer Base Channel in mm. T
36 Size (diameter & width) and No. of Rollers provided to the Transformer T
37 Conservator tank to the transformer with oil level indicator (showing three levels) and drain B
115 Inter layer insulation provided in L.V winding to design for Top & bottom layer T
116 Inter layer insulation provided in between all layer in H.V winding T
117 Inter layer insulation provided in between all layer in L.V winding T
118 Details of end insulation (thickness in mm) N
119 Whether wedges are Provided at 50% turns of the Coil (Yes/ No) B
120 Thickness of insulating paper N
121 Regulation at 0.8 P.F. lag ( in %) N
122 Regulation at 0.8 P.F. leading ( in %) N
123 Regulation at unity P.F.. (in %) N
124 Reference standard of Bushing T
125 Material of HV and L.V Bushings T
126 Makes of HV and L.V Bushings T
127 Rating of HV Bushing ( in KV,A) T
128 Rating of LV Bushing (in KV,A) T
129 Minimum Creepage Distance of HV Bushings in mm (min 25mm/kV) N
130 Minimum Creepage Distance of LV Bushings in mm (min 25mm/kV) N
131 Power frequency withstand voltage dry & wet in kV(rms) for HV Bushings N
132 Dry lighting impulse withstand voltage test in kV (Peak) stating the waveform adopted T
133 for HV Bushing. T
134 Separate source power frequency withstand test for HV for 1minute in kV(min) T
135 Separate source power frequency withstand test for LV for 1minute in kV(min) T
136 Induced over voltage withstand test for 1 min. specify voltage frequency, time for test. T
137 Impulse test value (in kVp) . T
4P 3-G air filled cable box shall be suitable to 3.5 core PVC aluminum cable with copper
138 flats filled on L.T. studs to connect XLPE cable shall be provided on L.V. side (Yes/No) & T
size of cable in sq.mm (shall be mentioned)
139 Efficiency at 75 º C at unity P.F. at 125 % Load N
140 Efficiency at 75 º C at unity P.F at 100 % Load N
141 Efficiency at 75 º C at unity P.F. at 75 % Load N
142 Efficiency at 75 º C at unity P.F. at 50 % Load N
143 Efficiency at 75 º C at 0.8 P.F. lag at 125 % Load N
144 Efficiency at 75 º C at 0.8 P.F. lag at 100 % Load N
145 Efficiency at 75 º C at 0.8 P.F. lag at 75 % Load N
146 Efficiency at 75 º C at 0.8 P.F. lag at 50 % Load N
147 Efficiency at 75 º C at 0.8 P.F. lag at 25 % Load N
148 Efficiency at 75 º C at 0.8 P.F. leading at 125 % Load N
149 Efficiency at 75 º C at 0.8 P.F. leading at 100 % Load N
150 Efficiency at 75 º C at 0.8 P.F. leading at 75 % Load N
151 Efficiency at 75 º C at 0.8 P.F. leading at 50 % Load N
152 Efficiency at 75 º C at 0.8 P.F. leading at 25 % Load N
153 The test certificates of copper conductors, core , insulating paper, porcelain Bushings, steel B
plate used for enclosure of the offered transformer are enclosed with the offer(Yes/No)
All type test report carried out on transformer at NABL laboratory shall be submitted along
154 with the offer as per cl. XXII (c) of Section (I) i.e. Instructions to tenderers. (Yes/No). Firm B
may attach online.
Unbalance current test, Air pressure test and temperature rise test shall be conducted as per
155 B
format enclosed with the technical specification along with the offer (Yes/ No)
All drawings shall be furnished for each offered item separately along with this offer (Yes/
156 B
No)
157 Oil absorption calculation sheet shall be furnished for each offered item separately along B
with this offer (Yes/ No)
158 Heat dissipation calculation shall be furnished for each offered item separately along with B
this offer (Yes/ No)
Calculation sheet submitted for Flux density calculations (stating HV & LV turns) for each
159 B
offered item separately along with the offer (Yes/No)
Calculation sheet for 112% of rated V/f ratio (Over fluxing) calculation sheet shall be
160 B
furnished for each item separately along with this offer (Yes/No)
161 Required documents, plant and machinery, testing equipment , list of order executed/under B
execution shall be furnished for each offered item separately along with this offer (Yes/ No)
162 The information required under Quality Assurance shall be submitted with the offer in B
physical format & soft copy(Yes/ No)
163 The cost data in the prescribed format shall be submitted with offer in physical format & B
soft copy (Yes/ No)
164 The performance Guarantee of the transformers in years NUMERIC N