Spec - 2017-02 - A00 HVAC For Offshore Installations (AMendments - Supplements To ISO 15318)
Spec - 2017-02 - A00 HVAC For Offshore Installations (AMendments - Supplements To ISO 15318)
DEP 37.76.10.10-Gen.
February 2017
DEM1
All rights reserved. No part of this document may be reproduced, stored in a retrieval system, published or transmitted, in any form or by any means, without the prior
written permission of the copyright owner or Shell Global Solutions International BV.
PREFACE
DEP (Design and Engineering Practice) publications reflect the views, at the time of publication, of Shell Global Solutions
International B.V. (Shell GSI) and, in some cases, of other Shell Companies.
These views are based on the experience acquired during involvement with the design, construction, operation and
maintenance of processing units and facilities. Where deemed appropriate DEPs are based on, or reference international,
regional, national and industry standards.
The objective is to set the standard for good design and engineering practice to be applied by Shell companies in oil and
gas production, oil refining, gas handling, gasification, chemical processing, or any other such facility, and thereby to help
achieve maximum technical and economic benefit from standardization.
The information set forth in these publications is provided to Shell companies for their consideration and decision to
implement. This is of particular importance where DEPs may not cover every requirement or diversity of condition at each
locality. The system of DEPs is expected to be sufficiently flexible to allow individual Operating Units to adapt the
information set forth in DEPs to their own environment and requirements.
When Contractors or Manufacturers/Suppliers use DEPs, they shall be solely responsible for such use, including the
quality of their work and the attainment of the required design and engineering standards. In particular, for those
requirements not specifically covered, the Principal will typically expect them to follow those design and engineering
practices that will achieve at least the same level of integrity as reflected in the DEPs. If in doubt, the Contractor or
Manufacturer/Supplier shall, without detracting from his own responsibility, consult the Principal.
The right to obtain and to use DEPs is restricted, and is typically granted by Shell GSI (and in some cases by other Shell
Companies) under a Service Agreement or a License Agreement. This right is granted primarily to Shell companies and
other companies receiving technical advice and services from Shell GSI or another Shell Company. Consequently, three
categories of users of DEPs can be distinguished:
1) Operating Units having a Service Agreement with Shell GSI or another Shell Company. The use of DEPs by these
Operating Units is subject in all respects to the terms and conditions of the relevant Service Agreement.
2) Other parties who are authorised to use DEPs subject to appropriate contractual arrangements (whether as part of
a Service Agreement or otherwise).
3) Contractors/subcontractors and Manufacturers/Suppliers under a contract with users referred to under 1) or 2)
which requires that tenders for projects, materials supplied or - generally - work performed on behalf of the said
users comply with the relevant standards.
Subject to any particular terms and conditions as may be set forth in specific agreements with users, Shell GSI disclaims
any liability of whatsoever nature for any damage (including injury or death) suffered by any company or person
whomsoever as a result of or in connection with the use, application or implementation of any DEP, combination of DEPs
or any part thereof, even if it is wholly or partly caused by negligence on the part of Shell GSI or other Shell Company. The
benefit of this disclaimer shall inure in all respects to Shell GSI and/or any Shell Company, or companies affiliated to these
companies, that may issue DEPs or advise or require the use of DEPs.
Without prejudice to any specific terms in respect of confidentiality under relevant contractual arrangements, DEPs shall
not, without the prior written consent of Shell GSI, be disclosed by users to any company or person whomsoever and the
DEPs shall be used exclusively for the purpose for which they have been provided to the user. They shall be returned
after use, including any copies which shall only be made by users with the express prior written consent of Shell GSI. The
copyright of DEPs vests in Shell Group of companies. Users shall arrange for DEPs to be held in safe custody and Shell
GSI may at any time require information satisfactory to them in order to ascertain how users implement this requirement.
All administrative queries should be directed to the DEP Administrator in Shell GSI.
TABLE OF CONTENTS
PART I INTRODUCTION ....................................................................................................... 4
1.1 SCOPE ....................................................................................................................... 4
1.2 DISTRIBUTION, INTENDED USE AND REGULATORY CONSIDERATIONS ......... 4
1.3 DEFINITIONS ............................................................................................................. 4
1.4 CROSS-REFERENCES ............................................................................................. 5
1.5 SUMMARY OF MAIN CHANGES ............................................................................... 5
1.6 COMMENTS ON THIS DEP ....................................................................................... 5
1.7 DUAL UNITS............................................................................................................... 5
1.8 NON NORMATIVE TEXT (COMMENTARY) .............................................................. 5
PART II GENERAL .................................................................................................................. 6
PART III AMENDMENTS/SUPPLEMENTS TO ISO 15138:2007 ............................................ 7
2 Normative references ............................................................................................... 7
4 Abbreviated terms .................................................................................................... 8
5 Design ........................................................................................................................ 8
5.2 Development of design basis ...................................................................................... 8
5.3 System design – General ......................................................................................... 17
5.4 Area-specific system design ..................................................................................... 23
Annex A Equipment and bulk selection .............................................................................. 30
A.1 General ..................................................................................................................... 30
A.2 Louvres and hoods ................................................................................................... 30
A.3 Moisture separators and filters ................................................................................. 30
A.4 Heating coils and unit heaters .................................................................................. 31
A.5 Cooling coils and fan-coil units ................................................................................. 32
A.6 Humidifiers ................................................................................................................ 33
A.7 Fans .......................................................................................................................... 35
A.8 Sound attenuation ..................................................................................................... 38
A.9 Fire dampers ............................................................................................................. 38
A.10 General Dampers...................................................................................................... 40
A.11 Grilles and diffusers .................................................................................................. 41
A.12 Air-handling units (AHUs) ......................................................................................... 41
A.13 Refrigeration packages ............................................................................................. 43
A.16 Ducts ......................................................................................................................... 44
A.17 Equipment nameplates ............................................................................................. 52
A.18 Lifting facilities ........................................................................................................... 52
Annex E Standard data for flanges ...................................................................................... 53
Annex F Temporary refuge leak testing .............................................................................. 55
F.1 General ..................................................................................................................... 55
F.2 Leak testing ............................................................................................................... 55
F.3 Leak test procedure .................................................................................................. 56
F.4 Treatment of test results ........................................................................................... 57
F.5 Documentation .......................................................................................................... 59
PART IV REFERENCES ........................................................................................................ 60
PART I INTRODUCTION
1.1 SCOPE
This DEP specifies requirements and provides guidance for the design, installation, testing
and commissioning of Heating, Ventilation and Air-conditioning (HVAC) systems for
offshore installations of the petroleum and natural gas industries.
This DEP is based on ISO 15138:2007. The design of HVAC systems will be particular to
each installation; therefore, this DEP is written to provide both requirements and guidance
in a similar way to ISO 15138:2007.
This DEP contains mandatory requirements to mitigate process safety risks in accordance
with Design Engineering Manual (DEM) 1 – Application of Technical Standards.
This DEP is not applicable retroactively.
This is a revision of the DEP of the same number dated February 2014; see (1.5) regarding
the changes.
1.3 DEFINITIONS
1.3.1 General definitions
The Contractor is the party that carries out all or part of the design, engineering,
procurement, construction, commissioning or management of a project or operation of a
facility. The Principal may undertake all or part of the duties of the Contractor.
The Manufacturer/Supplier is the party that manufactures or supplies equipment and
services to perform the duties specified by the Contractor.
The Principal is the party that initiates the project and ultimately pays for it. The Principal
may also include an agent or consultant authorised to act for, and on behalf of, the
Principal.
The word shall indicates a requirement.
The capitalised term SHALL [PS] indicates a process safety requirement.
The word should indicates a recommendation.
The word may indicates a permitted option.
1.4 CROSS-REFERENCES
Where cross-references to other parts of this DEP are made, the referenced section or
clause number is shown in brackets ( ). Other documents referenced by this DEP are listed
in (Part IV).
Section/Clause Change
All Restructured and clarified requirements, enforced shall/should.
Feedback that has been registered in the DEP Feedback System by using one of the above
options will be reviewed by the DEP Custodian for potential improvements to the DEP.
PART II GENERAL
1. Part III of this DEP is written as amendments and supplements to ISO 15138:2007.
Wherever reference is made to ISO 15138, it shall be understood to mean
ISO 15138:2007 as amended/supplemented by this DEP.
2. For ease of reference, the clause numbering of ISO 15138 has been used throughout
(Part III) of this DEP.
3. Clauses and Annexes of ISO 15138, which are not mentioned in this DEP, shall
remain valid as written.
2 Normative references
Add the following:
EN 14986, Design of Fans Working in Potentially Explosive Atmospheres.
Area Classification Code for Installations Handling Flammable Fluids. Part 15 of the
IP Model Code of Practice in the Petroleum Industry.
B&ES DW144, Specification for sheet metal ductwork, low, medium & high
pressure/velocity air systems.
EN 13779, Ventilation for buildings, performance requirements for ventilation and air-
conditioning systems.
EN 288-3: Specification and approval of welding procedures for metallic materials.
Welding procedure tests for the arc welding of steels.
EN 378 (parts 1, 2 and 3): Refrigerating Systems and Heat Pumps – Safety and
Environmental Requirements.
BS 5422: Method for Specifying Thermal Insulating Materials for Pipes, Tanks,
Vessels, Ductwork and Equipment.
BS 5970: Code of Practice for Thermal Insulation of Pipework and Equipment.
ASHRAE 62.1, Ventilation for Acceptable Indoor Air Quality.
ANSI/SMACNA 006: HVAC Duct Construction Standards - Metal and Flexible.
SOLAS, International convention for the Safety of Life at Sea, latest version and
amendments.
NMD, Norwegian Maritime Directorate regulations.
4 Abbreviated terms
Add:
AHU Air Handling Unit
CBM Condition-based maintenance.
CFC Chlorofluorocarbon (refrigerant gas).
DX Direct Expansion
F&G Fire and Gas.
GWP Global Warming Potential
HCFC Hydro-chlorofluorocarbon (refrigerant gas).
HFC Hydro-fluorocarbon (refrigerant gas).
HMI Human-machine interface.
HVAC Heating, Cooling and Air Conditioning
HVCA Heating and ventilation Contractors’ association.
IPF Instrumented protective function.
LBL Lawrence Berkeley Laboratory
MS Mild steel.
ODP Ozone Depletion Potential
RSA Rolled steel angle.
SMACNA Sheet metal and air conditioning Contractors’ national association.
TEWI Total Equivalent Warming Impact.
TR Temporary Refuge.
5 Design
5.2.5.3.1 General
Delete first two paragraphs. Insert new paragraph:
1. For new installations, or major changes to existing installations, the HVAC
controls shall be arranged as follows:
a. HVAC controls, logic, alarms, status indication and HMI be incorporated into
the installation control/monitoring/safety systems (by the main automation
Contractor), except for specialist HVAC equipment packages.
b. Local HVAC interface panels be included (e.g., in HVAC plant rooms, living
quarters, non-hazardous modules).
c. Local panel provide as a minimum; local status indication of HVAC plant,
fire/gas dampers and to enable local manual switching for maintenance
purposes.
d. Status indication be provided by means of a serial link.
2. For small installations, or those not normally manned, the HVAC controls shall be
arranged as follows:
a. Local HVAC control panels with HMI providing logic, alarms and status
indication.
b. Interfaces between HVAC control panel and installation control/safety
systems for transmission of alarms, equipment status and permissive
signals.
3. All control system arrangements shall include the following:
a. The HMI to provide a mimic diagram of the HVAC system, including fire/gas
dampers.
b. Controls for specialist packaged equipment such as chillers, direct-
expansion cooling systems and humidifiers may use the Manufacturer’s
standard controls as stand-alone units with interfaces to the HVAC controls
for alarms, permissive signals and status indication.
c. The fire & gas sub-section of the installation controls to override normal
HVAC controls to close fire dampers and shut-down fans and other
equipment in accordance with the Cause and Effect logic.
d. The status of fire dampers to be monitored at the F&G sub-section with
signals handed-off to the local HVAC panel and the main control system.
e. Refer to DEP 32.30.20.11-Gen. for F&G system requirements.
4. Motor starters may be included in local HVAC control panels only if they can be
isolated and accessed separately from the controls section of the panel.
5. Distributed electric re-heaters shall be controlled by thermostats located within
the controlled space, which are to be energised by means of a permissive
interlock that is enabled by adequate airflow.
5.4.2.3.1 General
st
Amend 1 sentence to read:
1. In the absence of local legislation or code of practice, the requirements given in
(5.2.3) shall apply, except that the design minimum internal relative humidity level
at winter.
outside design temperature shall be 35%.
nd
Amend 2 paragraph to read:
1. Fresh air flow rates shall be in accordance with section 5.3.2.3.6.
rd
Add to end of 3 paragraph ‘The main supply.... emergency operation’:
1. Recirculation of ‘clean’ air should be used where feasible because of the
substantial reduction in energy demand.
2. Extract air that is likely to be foul or contaminated, such as toilet, smoking area,
galley, medical or laundry extract shall not be recirculated.
3. Any smoking areas shall be clearly defined and served by an appropriate extract
system.
4. Corridors shall be designed to be maintained at an over-pressure relative to
cabins to reduce the likelihood of their being contaminated with smoke from an
internal incident.
a. Cabin doors shall not have transfer grilles because of the corridor pressure
requirement and to prevent noise transfer.
5.4.4.3.1 General
nd
Add new paragraph after 2 paragraph:
1. Drilling facilities shall be designed so that personnel can carry out normal work
activities without respiratory protection.
2. Airborne potential hazards shall be enclosed and extracted to a location where
personnel will not be exposed them.
Add new sub-clause:
5.4.13 HVAC equipment drainage
1. HVAC equipment that produces moisture, such as filters, moisture separators and
cooling coils, shall be provided with permanent drains and manometric traps.
a. Each drain trap shall have sufficient depth of water seal to withstand the
maximum differential pressure to which it could be exposed, including abnormal
system operation with dampers closed or filters blocked.
2. All traps shall be of a type that can be removed and dismantled for cleaning.
a. ‘Open’ traps may be used when located in a non-hazardous area.
3. Drains that handle small quantities of water, such as those from filters may terminate
locally.
a. Condensation drains should be connected to the installation’s drains system.
A.1 General
st
Add to end of 1 paragraph:
1. Data sheets may be used in other formats provided that they include relevant
requirements of the examples in Annex D.
A.6 Humidifiers
A.6.1 Functional requirements
nd
Replace 2 paragraph ‘Humidifiers ……obstructions’ with:
1. Humidifiers shall be electrically powered and generate fresh, odourless, sterile
steam from the installation’s potable water supply system.
a. To avoid moisture drop-out, steam shall be introduced to the ducted
airstream by means of dispersion tubes.
b. Multiple steam dispersion tubes (e.g., in matrix form) shall be used where it
is necessary for steam to be absorbed in a short distance.
2. Humidifier designs and installation shall be based on the type of water that will be
used on the installation. Particular attention shall be given to following:
a. Selecting the appropriate type of water level control.
Electronic controls might not be suitable for water of high purity.
b. Avoiding problems with mineral deposits from heated water.
Scale might affect float valves and heater elements.
3. Reverse osmosis units may be considered for treating humidifier supply water.
This is in order to reduce maintenance requirements and optimise equipment
life.
th
Replace 4 paragraph ‘Each humidifier should be ……control system’ with:
1. Humidifiers shall meet the following requirements:
a. Be designed for industrial/marine use and continuous operation at full
output.
b. Electrical equipment to be located in compartments that are segregated from
water or steam carrying components.
This is to prevent them from being exposed to water or vapour during
either normal operation or maintenance.
i. Such compartments and any stand-alone electrical or instruments
equipment to have a suitable moisture ingress protection ratings.
c. The main electrical connections be capable of accepting glanded cables.
d. No exposed hot surfaces that are normally accessible.
e. All components be enclosed in a sheet steel casing and insulation to be
used where required to prevent surface temperatures from exceeding safe
levels.
f. The package to include all necessary safety devices and the controls be
capable of operating in conjunction with the HVAC or installation control
system by allowing for an operation permissive input signal, transmitting
alarm signals and receiving trip signals.
g. Heater elements be of the resistive type.
i. Electrode type not to be used.
h. Steam chambers be of stainless steel and easily accessible for
maintenance.
i. Humidifiers be provided with water skimming/flushing systems to prevent
accumulations of solids.
j. Humidifiers to operate only when system airflow has been established.
k. Be capable of being controlled in sequence from a single humidity detector
incases where humidifiers are installed as multiple units.
l. Installation design to allow for Manufacturer’s requirements, including air
velocities at steam dispersion point, balance pipes for steam chamber
pressure, feed-water pressure, drainage, cooling of control panels.
A.7 Fans
Delete existing section A.7.2 and subclauses, insert new section as follows:
A.7.2 Functional requirements
A.7.2.1 Fan general requirements
The main fan types are centrifugal, mixed-flow and axial.
1. The type to be used should include consideration of functional requirements,
efficiency, space requirements, maintainability and installation lifetime.
2. Fans for all area classifications shall comply with EN 14986 except for
internally-located non-hazardous extract fans.
a. Fans for use in extract systems where there is a possibility of fouling by
particulate matter shall have motors located outside the airstream.
b. Plug fans may be used in air handling units.
3. Fans shall have steep performance curves to minimise performance changes in
adverse wind conditions.
a. Fan performance and the effect on module ventilation and pressurisation shall be
checked in relation to the likely sustained maximum wind speeds for the
installation.
4. Where feasible, fans should be direct-drive to eliminate belt maintenance
requirements.
a. Use of direct-drive fans may require suitable capacity adjusting devices and
allowances in system design to ensure that minimum duty requirement can be
obtained.
5. Inlet guide vane dampers shall not be used because of susceptibility to seizure and
blade detachment.
6. Fans to be located externally or handling moist or corrosive air shall have casings
manufactured from stainless steel UNS S31603 unless located within an enclosure.
a. Fans in other situations shall be manufactured from mild steel galvanised after
manufacture or with epoxy paint coating.
b. For belt-drive fans the frame shall incorporate facilities for drive belt tensioning
and alignment of pulleys.
7. Fan support frames shall be welded from rolled mild steel sections and be galvanised
after manufacture.
a. Lifting lugs shall be incorporated in the frame.
8. Fans should not be selected to have excessive velocities and rotational speeds.
This is because this creates excessive noise and reduce operational life.
a. This situation should be avoided by improving system design to reduce fan
duties. Discharge velocities should not exceed 15 m/s (50 ft/s).
9. Fan shafts shall be of high-tensile steel and designed to withstand fatigue.
a. The shaft’s first critical speed should be at least 20% in excess of the
recommended maximum fan operating speed.
Delete second part of paragraph (c) ‘Actuator selection...’ and insert new paragraph:
1. Actuators shall be designed for six year service without requiring any
maintenance and for the normal mode of fire damper operation where the spring
is fully compressed all the time except during testing.
2. Actuator minimum torque output shall be at least 40% above the damper’s
maximum requirement, which is usually at the closing position.
3. Pneumatic actuators shall have NAMUR standard details for the drive connection,
actuator mounting and fittings.
4. Pneumatic actuators shall be of stainless steel UNS S31603 and internal
components shall be steel.
5. Actuator springs shall be made of spring steel with a flexible corrosion-resistant
coating.
Add to end of sub-clause (d):
1. All instruments and electrical components fitted to fire dampers shall be classified
for use in a hazardous area unless it can be established that the damper would
never have to operate in a hazardous situation.
Add new sub-clause (e):
e). All instruments and electrical components fitted to fire dampers shall be classified
for use in a hazardous area unless it can be established that the damper would never
have to operate in the presence of gas and that this would not prevent black-start or
purging operation.
Add new paragraph after (e):
1. The design of blade shaft bearings shall recognise that fire dampers operate
infrequently and might be subjected to corrosive environment.
2. Plain bush designs tend to become stiff over time and sintered bronze bushes
suffer corrosion, therefore bushes shall be maintainable or replaceable in-situ.
3. The potential for friction should be minimised by reducing the contact area
between shaft and bearing to the minimum that is functionally required.
4. Fire dampers shall be manufactured from stainless steel UNS S31603 and
casings be flanged to connect to adjacent ductwork.
Delete last paragraph ‘A thermal…components’, add new paragraph:
1. Each fire damper shall include a reliable, fail-safe, thermal device that will cause
the damper to close in the event of the temperature in the duct reaching a pre-
determined level (as indication of possible fire).
2. Thermal devices shall be replaceable from outside the damper casing.
A.9.2.3 Performance
Add new paragraph:
1. Where electric actuators are used the motor-driven cycle time shall be minimised
and not to exceed 40 seconds.
6. Relief valves shall be of a type that does not permit the full charge of refrigerant
to escape in the event of over-pressure.
a. Diaphragm types shall not be used.
7. All refrigerant systems shall undergo a strength test and pressure test.
a. The pressure test shall be at not less than 1.1 times the normal maximum
working pressure unless the design code requires a higher level of pressure.
8. Nameplates attached to equipment containing refrigerant gas shall include details
of the type and quantity of refrigerant.
9. A refrigeration service kit shall be provided and retained on-board so that it is not
necessary to transport such equipment for every maintenance visit.
a. This shall include refrigerant recovery equipment, test gauges and other
common service items appropriate for the installation.
A.13.2.5 Air-cooled condensers
Add new paragraph:
1. Refer to A.5.2.2.
Add new sub-section:
A.13.2.8 Cooling systems on unmanned installations
1. Designs of cooling systems for unmanned installations shall make allowance for the
infrequency of scheduled maintenance visits and reduce the likelihood of requiring
maintenance intervention.
2. The following requirements shall be included:
a. Air filter capacities and differential pressure switch settings be designed for
extended service intervals.
b. Comprehensive status and fault information be available remotely to enable
remote diagnosis of faults and preparation for remedial work.
c. System operation inhibits be minimised to those that are essential to prevent
equipment damage or refrigerant leakage.
d. Fan belts be designed and arranged for extended service by including
redundancy in ratings or numbers of belts.
Delete existing section A.16, insert new section and tables:
A.16 Ducts
A.16.1 Functional requirements
1. The material and type of construction for ductwork shall be selected to be suitable for
the operating conditions and design life of the installation.
Duct
Material Construction Application
class
A Stainless steel All-welded, 3 mm (0.12 in) duct wall. External duct, high-
UNS S31603 See Table A.3 strength duct, fire-rated
duct. Risk of
mechanical damage or
high strain.
Exposed to weather,
wind buffeting and
saliferous atmosphere.
B Stainless steel HVCA DW144. Internal duct in
UNS S31603 corrosive environments
such as laboratories,
battery rooms, paint
stores, etc.
Not exposed to risk of
mechanical damage.
C1 Stainless steel All-welded, rectangular and circular, 2 mm (0.08 in) Internal duct in
UNS S31603 duct wall. production and utility
See Table A.3 areas.
Exposed to moisture or
saliferous atmosphere.
Risk of mechanical
damage or high strain.
C2 Stainless steel Rectangular and circular. As C1, but low risk of
UNS S31603 See Table A.3 mechanical damage
and low strain.
Duct
Material Construction Application
class
C3 Pre-galvanised Rectangular and circular. Alternative to class C2
sheet steel See Table A.3 where duct is not
subject to moisture
(internal and external
surfaces) or corrosion.
D Carbon steel Welded construction, painted or hot-dipped High-strength duct, fire-
galvanised. rated duct, or to suit
4 mm (0.16 in) minimum penetrations. Duct not
exposed to corrosive
environment.
E Pre-galvanised Rectangular and circular. Internal duct in
sheet steel Based on HVCA DW144 controlled environments
such as living quarters
See Table A.3
and offices.
F Stainless steel Circular. Fire-rated internal duct
UNS S31600 or 0.8 mm (0.03 in) for 80 to 200 mm (3 to 8 in) dia. for living quarters and
1.0 mm (0.04 in) for 250 to 315 mm (10 to 13 in) dia. offices, used with fire-
UNS S31603
1.2 mm (0.05 in) for 400 to 630 mm (16 to 25 in) dia. rated expanding
1.5 mm (0.06 in) for > 800 mm (32 in) dia. joints/gaskets approved
by certifying authority.
2. Refer Table A.3 for details of minimum duct construction standards for classes A, C
and E.
3. Refer to HVCA Specification for Sheet Metal Ductwork DW144 for duct of non-welded
construction
a. Alternative standards such as SMACNA may be used provided that there is no
reduction in specification.
4. Refer (Annex E) for standard details for duct flanges.
A.16.2 Design and construction requirements
A.16.2.1 Duct dimensions
1. Duct lengths shall be based on handling considerations, stiffening requirements and
support arrangements.
2. For welded duct spools, maximum length should be based on the size of sheet from
which they are made plus 5mm (0.2 in) per flange to allow space for the internal flange
weld.
Example: Ducts fabricated from the typical sheet size 2500 mm × 1250 mm (100 in
x 50 in) could have max lengths of either 2510 mm (100-3/8 in) or 1260 mm (50-3/8
in).
Duct nominal sizes are based on internal dimensions for fabricated rectangular and
circular ducts.
3. Refer to Manufacturer’s information for factory-made spiral-wound ductwork.
A.16.2.2 Flanges
1. All duct cross-joints shall be made using welded RSA flanges of same material as the
duct walls.
a. Exception for certain smaller size ducts where jointing methods may be as
indicated in Table A.3.
2. For welded ductwork, flanges shall be attached by full welds externally and 25 mm
(1 in) stitch welds internally.
a. For lock-formed ductwork, flanges shall be attached by close-spaced rivets or
spot welds and sealed to the duct with mastic.
3. Flange details shall be in accordance with amendments to (Annex E).
4. The back-mark shall be referenced to the duct nominal dimensions (normally the
internal size).
5. Flange drilling details shall be given to vendors of flanged HVAC equipment in order to
ensure alignment of boltholes.
A.16.2.3 Stiffeners
1. Stiffeners shall be attached by stitch-welding for welded duct construction and bolted
for other construction methods.
Class Material Duct longest side or Wall Duct Flange/Joint Flange Stiffening max
diameter Thickness seam Attachment spacing
A – Rect’r 3.0 mm (0.12 in) Flange Welded 1250 mm (50 in)
St/stl 1000 (40 in) Welded Appendix E
3.0 mm (0.12 in) 850 mm (34 in)
>1000 to 1500 mm (40 to 60 in)
3.0 mm (0.12 in) 600 mm (24 in)
>1500 mm (60 in)
Circ’r All diameters 3.0 mm (0.12 in) Max length 2500 mm
(100 in)
C1 – Rect’r 2.0 mm (0.08 in) Flange Welded 1250 mm (50 in)
St/stl Up to 500 mm (20 in) Welded Appendix E
2.0 mm (0.08 in) 1000 mm (40 in)
>500 to 750 mm (20 to 30 in)
2.0 mm (0.08 in) 800 mm (32 in)
>750 to 1250 mm (30 to 50 in)
2.0 mm (0.08 in) 600 mm (24 in)
>1250 mm (50 in)
Circ’r All diameters 2.0 mm (0.08 in) Max length 2500 mm
(100 in)
C2 – Rect’r 1.2 mm (0.05 in) Flange Riveted or spot 1250 mm (50 in)
St/stl Up to 350 mm (14 in) Pittsburgh Appendix E welded at 75 mm
1.2 mm (0.05 in) lock (3 in) crs 1000 mm (40 in)
>500 to 1000 mm (20 to 40 in)
1.2 mm (0.05 in) 800 mm (32 in)
>1000 to 1500 mm (40 to 60 in)
2.0 mm (0.08 in) Welded Ditto Welded 800 mm (32 in)
>1500 mm (60 in)
C2 – Circ’r Spigot/socket Max length 3000 mm
St/stl, spiral- Up to 200 mm (8 in) 0.8 mm (0.03 in) Pittsburgh DW 144 Figs 37 & 44 (120 in)
wound or lock Flange Appendix E or equivalent
rolled >200 to 400 mm (8 to 16 in) 1.0 mm (0.04 in)
>400 to 800 mm (16 to 32 in) 1.2 mm (0.05 in)
Welded
>800 mm (32 in) 1.5 mm (0.06 in)
C3 – Rect’r Flange Riveted or spot 1250 mm (50 in)
Pre-galv MS Up to 350 mm (14 in) 1.2 mm (0.05 in) Pittsburgh Appendix E welded at 75 mm
steel sheet lock (3 in) crs 1000 mm (40 in)
>500 to 1000 mm (20 to 40 in) 1.2 mm (0.05 in)
800 mm (32 in)
>1000 to 1500 mm (40 to 60 in) 1.2 mm (0.05 in)
625 mm (25 in)
>1500 mm (60 in) 1.2 mm (0.05 in)
Class Material Duct longest side or Wall Duct Flange/Joint Flange Stiffening max
diameter Thickness seam Attachment spacing
C3 – Circ’r Spigot/socket DW 144 Figs 37 & Max length 3000 mm
Pre-galv MS Up to 200 mm (8 in) 0.8 mm (0.03 in) Pittsburgh 44 or equivalent (120 in)
sheet, spiral- lock Flange, Appendix E
wound or >200 to 400 mm (8 to 16 in) 1.0 mm (0.04 in)
rolled >400 to 800 mm (16 to 32 in) 1.2 mm (0.05 in)
Welded
>800 mm (32 in) 1.5 mm (0.06 in)
E – Rect’r Pre-galv MS, Up to 350 mm (14 in) 0.8 mm Slide-on flange DW144 DW144
DW144 high- (0.03 in) min DW144
pressure >350 mm (14 in) 1.0 mm Flange,
(0.04 in) min Appendix E
E – Circ’r Spigot/socket DW 144 Figs 37 & DW144
Pre-galv MS, Up to 200 mm (8 in) DW144 DW144 44 or equivalent
DW144 high- Flange,
pressure >200 mm (8 in) Appendix E
Nominal duct dia. ‘D’ Back mark Flange *1, *2 Bolt Size Bolt Hole No. of
Size bolts
mm in mm (in) mm (in) metric (in) mm (in)
Up to 160 Up to 6 3/8 23 (7/8) 40 × 4 (1.5 × 3/16) M8 (5/16) 10 (7/16) 4
>160 to 355 >6 3/8 to 14 23 (7/8) 40 × 4 (1.5 × 3/16) M8 (5/16) 10 (7/16) 8
>355 to 500 >14 to 20 30 (1-3/16) 50 × 5 (2 × 3/16) M10 (7/16) 12 (1/2) 12
>500 to 710 >20 to 28 30 (1-3/16) 50 × 5 (2 × 3/16) M10 (7/16) 12 (1/2) 16
>710 to 1000 >28 to 40 30 (1-3/16) 50 × 5 (2 × 3/16) M10 (7/16) 12 (1/2) 24
>1000 to 1100 >40 to 44 40 (1-5/8) 70 × 6 (3 × ¼) M12 (1/2) 14 (9/16) 24
>1100 to 1500 >44 to 60 40 (1-5/8) 70 × 6 (3 × ¼) M12 (1/2) 14 (9/16) 32
Nominal diameter D
Table E.2 – Standard data for rectangular flanges (see note *1)
Duct longest side Back mark Flange Bolt Size Bolt Hole Size
mm in mm (in) mm (in) metric (in) mm (in)
Up to 350 Up to 14 23 (7/8) 40 × 40 × 4 RSA M8 (5/16) 10 (7/16)
(1.5 × 1.5 × 3/16)
>350 to 1500 >14 to 60 30 (1-3/16) 50 × 50 × 5 RSA M10(7/16) 12 (1/2)
(2 × 2 × 3/16)
>1500 >60 40 (1-5/8) 70 × 70 × 6 RSA M12 (1/2) 14 (9/16)
(3 × 3 × ¼)
NOTE: *1. Inch sizes are nearest appropriate size, they are not exact conversions of metric dimensions. Do not
mix metric and inch sizes.
F.1 General
1. This Section describes the methodology that shall be applied to temporary refuge leak
testing and the treatment of test results.
The main objectives are:
To prove that TR air-tightness does not exceed values stated in the installation
safety case
During initial testing after construction, to establish the lowest leak rate that the
TR is normally be capable of
During operation, to periodically re-test the TR to either confirm that leakage is
within acceptable limits or identify that remedial work is required.
To verify that door seal maintenance is effective.
To express test leakage rates in a form that better represents the leakage that
would occur under wind effect.
2. The procedure shall include the following steps:
a. Seal the TR as it would be in emergency mode by switching off HVAC systems
and closing doors and fire dampers
b. Attach a test fan to a selected doorway to pressurise (and depressurise) the TR,
measure leakage at positive and negative pressures
c. Apply the LBL correction methodology to test data to indicate the leakage that
would occur under wind effect.
The methodology was developed by Shell in the 1990s based on parts of
ASTM E 779 and ASHRAE. There are similarities with later methodologies for
leak-testing onshore buildings, such as CIBSE TM23, but such standards are
not applicable because of different objectives and different use of test results.
Leakage, Q3
Leakage, Q1
Leakage, Q4
The objective is to determine leak rates under wind effect so that they can be related to
time-based wind occurrence and probability, thus making it relevant to technical safety
work. The LBL correction method, taken from ASHRAE, provides a method for doing this
and the method is described below.
F.4.2 LBL corrected leakage
1. The following information shall be provided for the calculations:
a. Tested leakage airflow rates at test pressures for both positive and negative
pressurisation tests: Qtest (m³/s) at Ptest (Pascals).
b. Seasonal average values of wind speed, internal module temperature and
outside temperature that will apply to the module when in use offshore.
c. For reference, tests should also record the wind speed prevailing during tests.
2. Each of the following calculations shall be performed for both positive and negative
pressurisation test results.
a. The measured airflow leakage rates are normalised to a reference pressure that
is usually taken to be 4 Pascals (Pa) as a pressure differential at which leakage
will start to occur.
The formula1 is based on a standard square law relationship.
b. Calculate leakage area using the formula 2 for flow through an orifice.
0.5
ρ 1
L = leakage area (cm²)
L Q0 Qo = airflow (m³/s) at reference pressure value
2Δ P0 Cd 104
ρ = density (kg/m³)
Formula 2 Cd = discharge coefficient, normally taken as 1.0
c. Apply the LBL correction to adjust leakage according to the applicable seasonal
average wind speed and temperature differential.
i. Refer below table for coefficients A and B.
d. The calculation shall be based on particular values of wind speed and differential
temperature.
e. The values used should be seasonal averages, not those pertaining at the time of
the test, so that the leak rate is calculated for average conditions.
f. These same values should be used for any further calculations for the particular
installation so that the results of different tests can be compared.
g. The corrected leak rates shall then be expressed in air changes per hour where
the airflow expressed in m³/s × 3600 is divided by the TR’s net volume (m³).
h. Net volume shall be obtained by applying a factor to the gross volume to allow for
the space occupied by bulkheads, floor structures, furniture, etc., 80% is a typical
value for the factor.
i. Leak rates calculated in this way should always include a reference to ‘LBL-
corrected’.
j. Offshore modules constructed with welded profiled steel cladding should achieve
LBL-corrected leak rates well within the value of 0.25 air changes per hour with
10 m/s wind speed.
F.5 Documentation
F.5.1 Test procedure
1. A procedure document shall be written for each enclosed Temporary Refuge module
and be retained by the asset operator to use for future tests.
2. The test procedure document shall record all relevant information about the test
procedure and details such as:
a. Test equipment location.
b. List of fans to be switched off for the test.
c. List of boundary fire dampers that must be closed for the test.
d. List of boundary doors to be kept closed for the test.
e. List of any internal doors to be kept open for the test.
f. Any other relevant items, such as timing to suit galley operations, no laundry
operation during the test, areas where lack of ventilation during the test could
cause heat build-up.
g. Requirement to express results with the LBL correction.
h. TR dimensions to be used in calculations.
3. The test procedure shall include the results of the first test for use as the criteria for
future tests.
4. A margin of +20% may be allowed for subsequent tests provided that this does not
exceed leakage values used in the safety case.
F.5.2 Test report
1. A test report shall be written following each TR test and include calculations of the
LBL-corrected leak rate.
PART IV REFERENCES
In this DEP, reference is made to the following publications:
NOTES: 1. Unless specifically designated by date, the latest edition of each publication shall be used,
together with any amendments/supplements/revisions thereto.
2. The DEPs and most referenced external standards are available to Shell staff on the SWW (Shell
Wide Web) at http://sww.shell.com/standards/.
SHELL STANDARDS
AMERICAN STANDARDS
BRITISH STANDARDS
Method for specifying thermal insulating materials for pipes, tanks, BSI BS 5422
vessels, ductwork and equipment operating within the temperature
o o o
range - 40 °C (- 40 F) – 700 C (1292 F)
EUROPEAN STANDARDS
INTERNATIONAL STANDARDS
International Convention for the Safety of Life at Sea SOLAS IMO DH110
Issued by: IMO - International Maritime Organization
Mechanical vibration – Balance quality requirements for rotors in a ISO 1940-1
constant (rigid) state – Part 1: Specification and verification of balance
tolerances
Industrial fans – Performance testing using standardized airways ISO 5801
Industrial fans – Mechanical safety of fans – Guarding ISO 12499
Industrial fans – Specifications for balance quality and vibration levels ISO 14694
Petroleum and natural gas industries – Offshore production ISO 15138
installations – Heating, ventilation and air-conditioning
NORWEGIAN STANDARDS