Marley Series 10 - Series 15: Cooling Tower

The Marley Series 10 and Series 15 cooling towers are engineered for efficient operation in both clean and dirty water systems, featuring optimized fan designs and durable materials. They offer lower operating and maintenance costs, a five-year drivetrain warranty, and proven thermal performance. The towers are designed for flexibility in cooling capacity and include components that work compatibly to ensure long service life.

Uploaded by

Anupam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
90 views12 pages

Marley Series 10 - Series 15: Cooling Tower

The Marley Series 10 and Series 15 cooling towers are engineered for efficient operation in both clean and dirty water systems, featuring optimized fan designs and durable materials. They offer lower operating and maintenance costs, a five-year drivetrain warranty, and proven thermal performance. The towers are designed for flexibility in cooling capacity and include components that work compatibly to ensure long service life.

Uploaded by

Anupam
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 12

/ Marley Series 10 – Series 15 Cooling Tower /

œœˆ˜}Ê/iV ˜œœ}ˆiÃ
>VŽiÊNÊ>“œ˜Ê ÀÞÊ œœˆ˜}ÊNÊ>ÀiÞ
/ The Marley Difference /

Series 10 and Series 15 cooling towers are field n Fan Design is optimized for the static pressure
constructed, splash fill, crossflow wood cooling towers, imposition and airflow requirements of the tower.
designed to serve all normal cooling water systems—as n Fan Cylinders and their associated eased inlets,
well as those “dirty water” systems which would place augment fan operation.
the long term operation of a film-fill tower in jeopardy. n Fill and Fan Combinations are mutually supportive
These tower designs have evolved from the crossflow for maximum thermal performance in system
configuration.
concept of cooling towers pioneered by Marley® in 1938
and incorporate over 65 years of design advancements.
n Nozzles and Water Distribution systems provide
uniform fill coverage without excessive contribution to
Since 1922, customers have trusted the Marley air pressure losses.
brand for high quality, dependable products. The n The Geareducer® provides consistently optimum fan
principle reason for this reputation is our recognition that speeds, and operates reliably in a saturated air/vapor
each component of a cooling tower must perform at its mixture of corrosive nature.
peak—and all work compatibly toward overall efficiency. n Fan Motors are designed to Marley specifications
Accordingly, each performance-related component for extra demands of cooling tower duty. Motors are
insulated with extra protection from moisture.
of a Marley cooling tower is designed and manufactured
n Driveshafts are designed to absorb operational
in the context of the overall cooling tower system.
shock loads, thereby increasing the service life of
these critical components.

Marley Series 10


/ The Quality Advantage /

Marley Series 15

n Lower operating costs. Adjustable pitch fans with n Single-source parts availability. All tower
true airfoil blades and 98% efficient Geareducer components except the electric motors are designed,
drive assure maximum utilization of applied fan manufactured, guaranteed, and stocked by Marley.
power. Computer optimized fill configurations and You always know who to call for any parts you need.
low pressure-drop drift eliminators afford maximum You're also assured that all components of the
cooling with minimum power input. Gravity flow water cooling tower will work together, because they were
distribution minimizes pump power requirements. designed to work together!
n Lower maintenance costs. Heavy-duty aluminum n Flexible Cooling Capacity. Twenty-four tower
alloy fans, cast-iron Geareducers, and stainless models with capacities to 6720 GPM per fan cell,
steel driveshafts require only periodic maintenance. provide the flexibility to fit almost any job. Greater
Low-maintenance materials are used throughout capacity is available with multiple fan-cells.
the cooling tower. Wide-spaced splash-fill helps n Extremely Low Drift. XCEL®plus drift eliminators
prevent clogging. The fill area is readily accessible for really get rid of the costly nuisance of drift spotting on
cleaning. objects around the tower. The corrosion resistance of
n Five-year drivetrain warranty. What other PVC assures you that you’ll probably never have to
manufacturer will guarantee your tower's mechanical replace eliminators for the life of the tower.
equipment for five full years? You'll save valuable n Longer Service Life. Pressure-treated Douglas fir
equipment maintenance dollars. structure and splash-fill bars, FRP fill support grids,
n Proven Performance. SPX Cooling Technologies PVC drift eliminators, and all other tower components
stands by its responsibility for reliable thermal are designed for years of service.
performance. We designed it. We rate it. We
guarantee it!


/ Series 10 Schematic /

▲ C A U T I O N
The cooling tower must be located at such distance and direction
to avoid the possibility of contaminated tower discharge air
4" being drawn into building fresh air intake ducts. The purchaser
should obtain the services of a Licensed Professional Engineer or
Registered Architect to certify that the location of the tower is in
compliance with applicable air pollution, fire, and clean air codes.

W
TOP OF
PERIMETER
GUARDRAIL

H
L BASE OF
PERIMETER
TOWER COLUMNS
TOP OF
SUPPORTING
STEEL
4" 6 1/4"
Plan Endwall Elevation

ˆ“i˜Ãˆœ˜Ã
/œÜiÀÊœ`i *Ê«iÀÊ i
œÌiÊ£  7  >˜Ê`ˆ>“iÌiÀ
361-101 £Îx‡£äää n¿‡ä¸ £™¿‡Ó¸ £ä¿‡£äÊ56M¸ ÇÓ¸
ÎÈӇ£ä£ £Èx‡£ÓÎx n¿‡ä¸ Ó£¿‡Ó¸ £ä¿‡£äÊ56M¸ ÇÓ¸
ÎÈ·£ä£ £Îx‡£äää n¿‡ä¸ £™¿‡Ó¸ £Ó¿‡£äÊ56M¸ ÇÓ¸
ÎÈ{‡£ä£ £Èx‡£ÓÎx n¿‡ä¸ Ó£¿‡Ó¸ £Ó¿‡£äÊ56M¸ ÇÓ¸
ÎÈx‡£ä£ £™ä‡£{xx n¿‡ä¸ Óο‡Ó¸ £Ó¿‡£äÊ56M¸ ÇÓ¸
ÎÈȇ£ä£ Óäx‡£xää £Ó¿‡ä¸ Ó£¿‡Ó¸ £ä¿‡£äÊ56M¸ ™È¸
ÎÈLJ£ä£ Ó{x‡£nxä £Ó¿‡ä¸ Óο‡Ó¸ £ä¿‡£äÊ56M¸ ™È¸
ÎÈn‡£ä£ Óäx‡£xää £Ó¿‡ä¸ Ó£¿‡Ó¸ £Ó¿‡£äÊ56M¸ ™È¸
Îș‡£ä£ Ó{x‡£nxä £Ó¿‡ä¸ Óο‡Ó¸ £Ó¿‡£äÊ56M¸ ™È¸
ÎÇä‡£ä£ Ónx‡Ó£nx £Ó¿‡ä¸ Óx¿‡Ó¸ £Ó¿‡£äÊ56M¸ ™È¸
ÎÇ£‡£ä£ ÓÇä‡Óäää £È¿‡ä¸ Ó£¿‡Ó¸ £Ó¿‡£äÊ56M¸ ™È¸
ÎÇӇ£ä£ ÎÓx‡Ó{Èx £È¿‡ä¸ Óο‡Ó¸ £Ó¿‡£äÊ56M¸ ™È¸
ÎÇ·£ä£ Înä‡Ó™£ä £È¿‡ä¸ Óx¿‡Ó¸ £Ó¿‡£äÊ56M¸ ™È¸
ÎÇ{‡£ä£ Î{ä‡Óxää Óä¿‡ä¸ Óο‡Ó¸ £Ó¿‡£äÊ56M¸ £Óä¸
ÎÇx‡£ä£ {£ä‡Îänä Óä¿‡ä¸ Óx¿‡Ó¸ £Ó¿‡£äÊ56M¸ £Óä¸
ÎÇȇ£ä£ {Çx‡ÎÈ{ä Óä¿‡ä¸ ÓÇ¿‡Ó¸ £Ó¿‡£äÊ56M¸ £Óä¸

Note
1. The last number of the model indicates number of cells. Change 4. All tower installations require a minimum of 4'-0" from the tower
as appropriate for your selection. endwall to any vertical obstruction at the tower ladder location.
2. Overall length of the tower is: fan cells × L + 8. Primary engi- 5. Use this bulletin for preliminary layouts only. Do not use for
neering data is per cell. construction. Obtain current drawings from your Marley sales
3. Tower installations with an elevation of 20'-0" or more from top representative.
of the tower fan deck to the grade or roof level require a safety
cage on the tower ladder in accordance with OSHA standards.
Safety cage is an available option.


/ Series 15 Schematic /

3"

W
TOP OF
PERIMETER
GUARDRAIL

L 18' 6"

BASE OF
PERIMETER
TOWER COLUMNS
TOP OF
SUPPORTING
STEEL
3"
Plan 6 1/4"
Endwall Elevation

ˆ“i˜Ãˆœ˜Ã
/œÜiÀÊœ`i *Ê«iÀÊ i
œÌiÊ£  7 >˜Ê`ˆ>“iÌiÀ
{x£‡Óä£ Ó䣇Ó{ää £Ó¿‡ä¸ Óx¿‡ä¸ £Óä¸
{xӇÓä£ ÓÇä‡ÎÓää £È¿‡ä¸ ÓÇ¿‡ä¸ £{{¸
{x·Óä£ Î{ä‡{äää Óä¿‡ä¸ Ó™¿‡ä¸ £Èn¸
{x{‡Óä£ {£ä‡{nää Ó{¿‡ä¸ ә¿‡ä¸ £Èn¸
{xȇÓä£ Ónx‡ÎÎÈä £Ó¿‡ä¸ ә¿‡ä¸ £Óä¸
{xLJÓä£ Înä‡{{nä £È¿‡ä¸ Σ¿‡ä¸ £{{¸
{xn‡Óä£ {Çx‡xÈää Óä¿‡ä¸ Îο‡ä¸ £Èn¸
{x™‡Óä£ xÇä‡ÈÇÓä Ó{¿‡ä¸ Îο‡ä¸ £Èn¸

Note
1. The last number of the model indicates number of cells. Change 4. All tower installations require a minimum of 4'-0" from the tower
as appropriate for your selection. endwall to any vertical obstruction at the tower ladder location.
2. Overall length of the tower is: fan cells × L + 6. Primary engi- 5. Use this bulletin for preliminary layouts only. Do not use for
neering data is per cell. construction. Obtain current drawings from your Marley sales
3. Tower installations with an elevation of 20'-0" or more from top representative.
of the tower fan deck to the grade or roof level require a safety
cage on the tower ladder in accordance with OSHA standards.
Safety cage is an available option.


/ Series 10 Concrete Basin /

W 6" MIN TYP

11 1/2" 6 1/2" OPERATING WATER


LEVEL RECOMMENDED
A SPACES AT 4' 0" = L

SUMP
SEE NOTE 7

Section–Flat Slab Basin

11 1/2" 6 1/2" OPERATING WATER


LEVEL RECOMMENDED

OPTIONAL
PARTITION WALL

Section–Deep Basin
Plan

Dimensions Operating Weight


Tower Model lb
Note 4 L W A Single Fan Cell Each Cell Add
361-101 8'-0" 15'-0" 2 9,240 7,880
362-101 8'-0" 17'-0" 2 10,660 9,160
363-101 8'-0" 13'-0" 2 11,210 9,580
364-101 8'-0" 15'-0" 2 12,690 10,780
365-101 8'-0" 17'-0" 2 14,210 12,140
366-101 12'-0" 17'-0" 3 13,380 11,820
367-101 12'-0" 19'-0" 3 15,440 13,740
368-101 12'-0" 15'-0" 3 16,260 14,370
369-101 12'-0" 17'-0" 3 18,340 16,170
370-101 12'-0" 19'-0" 3 20,540 18,210
371-101 16'-0" 15'-0" 4 20,280 18,400
372-101 16'-0" 17'-0" 4 23,010 20,840
373-101 16'-0" 19'-0" 4 25,870 23,560
374-101 20'-0" 17'-0" 5 25,700 23,650
375-101 20'-0" 19'-0" 5 29,060 26,700
376-101 20'-0" 21'-0" 5 32,580 30,100

Note
1. Use this bulletin for preliminary layouts only. Do not use for 5. All anchor bolts complete with nut and washer will be furnished by
construction. Obtain current drawings from your Marley sales others. Bolts are to be Z\x" diameter with 1Z\x" all thread projection.
representative. 6. Maintain no less than 2'-0" of clear space at tower endwalls for
2. Tower weight is total wet operating weight of tower only excluding construction purposes. Louvered faces must have unobstructed
water in concrete basin. air supply. If obstructions exist nearby, consult your Marley sales
3. Purchaser to design, construct and furnish concrete basin com- representative.
plete to suit the general dimensions of current Marley drawings. 7. Other contractors or purchaser must design, locate, construct, and
4. Last number of model indicates number of cells. Change as ap- furnish sump(s) and overflow(s) to suit requirements. The sump(s)
propriate for your selection. Primary engineering data is per cell. should be designed according to the pump manufacturer’s recom-
mendations. Other design sources: ANSI/HI specifications 1.1-1.5
for centrifugal pumps, 2.1-2.5 for vertical pumps, and 9.8 for pump
intake design.


/ Series 15 Concrete Basin /

W 6" MIN TYP


1' 4" 11" OPERATING WATER
LEVEL RECOMMENDED
A SPACES AT 4' 0" = L

SUMP
SEE NOTE 7 Section–Flat Slab Basin

1' 4" 11" OPERATING WATER


LEVEL RECOMMENDED

OPTIONAL
PARTITION WALL

Section–Deep Basin
Plan

Dimensions Operating Weight


Tower Model lb
Note 4 L W A Single Fan Cell Each Cell Add
451-201 12'- 0" 18'- 0" 3 28,560 26,460
452-201 16'- 0" 20'- 0" 4 36,280 33,440
453-201 20'- 0" 22'- 0" 5 45,140 41,850
454-201 24'- 0" 22'- 0" 6 52,410 48,900
456-201 12'- 0" 22'- 0" 3 35,060 32,460
457-201 16'- 0" 24'- 0" 4 44,820 41,520
458-201 20'- 0" 26'- 0" 5 55,660 51,900
459-201 24'- 0" 26'- 0" 6 64,960 60,960

Note
1. Use this bulletin for preliminary layouts only. Do not use for 5. All anchor bolts complete with nut and washer will be furnished by
construction. Obtain current drawings from your Marley sales others. Bolts are to be ⁵⁄₈" diameter with 1¹⁄₂" all thread projec-
representative. tion—partition wall anchor bolts must have 3¹⁄₂" projection.
2. Tower weight is total wet operating weight of tower only excluding 6. Maintain no less than 2'-0" of clear space at tower endwalls for
water in concrete basin. construction purposes. Louvered faces must have unobstructed
3. Purchaser to design, construct and furnish concrete basin com- air supply. If obstructions exist nearby, consult your Marley sales
plete to suit the general dimensions of current Marley drawings. representative.
4. Last number of model indicates number of cells. Change as ap- 7. Other contractors or purchaser must design, locate, construct, and
propriate for your selection. Primary engineering data is per cell. furnish sump(s) and overflow(s) to suit requirements. The sump(s)
should be designed according to the pump manufacturer’s recom-
mendations. Other design sources: ANSI/HI specifications 1.1-1.5
for centrifugal pumps, 2.1-2.5 for vertical pumps, and 9.8 for pump
intake design.


/ Series 10 Wood Basin Support /

A SPACES AT 4' 0" = L


7 3/4"

4" MIN.

B
W OVERALL OF WOOD BASIN

NORMAL
GAGE

SUMP
Section–Steel Beam
C
OVERFLOW
8"

7 3/4" Plan Section–Concrete Beam

Dimensions Operating Weight


Tower Model lb
Note 4 L W A B C Single Fan Cell Each Cell Add
361-101 8'-0" 15'-556O" 2 5'-1" 4'-0" 13,980 11,880
362-101 8'-0" 17'-556O" 2 6'-1" 4'-0" 15,990 13,660
363-101 8'-0" 14'-156O" 2 5'-1" 2'-8" 15,520 13,240
364-101 8'-0" 16'-156O" 2 6'-1" 2'-8" 17,640 14,960
365-101 8'-0" 18'-156O" 2 7'-1" 2'-8" 19,720 16,800
366-101 12'-0" 17'-556O" 3 5'-1" 6'-0" 20,960 18,570
367-101 12'-0" 19'-556O" 3 6'-1" 6'-0" 23,880 21,270
368-101 12'-0" 16'-156O" 3 5'-1" 4'-8" 23,240 20,610
369-101 12'-0" 18'-156O" 3 6'-1" 4'-8" 26,220 23,190
370-101 12'-0" 20'-156O" 3 7'-1" 4'-8" 29,240 25,980
371-101 16'-0" 16'-156O" 4 5'-1" 4'-8" 29,390 26,760
372-101 16'-0" 18'-156O" 4 6'-1" 4'-8" 33,260 30,240
373-101 16'-0" 20'-156O" 4 7'-1" 4'-8" 37,230 33,960
374-101 20'-0" 18'-156O" 5 5'-1" 6'-8" 38,300 35,400
375-101 20'-0" 20'-156O" 5 6'-1" 6'-8" 42,940 39,650
376-101 20'-0" 22'-156O" 5 7'-1" 6'-8"º 48,100 44,550

Note
1. Use this bulletin for preliminary layouts only. Do not use for 5. If steel beams are used, they must include ⁵⁄₈" diameter holes to
construction. Obtain current drawings from your Marley sales accept ¹⁄₂" diameter anchor bolts provided.
representative. 6. If concrete beams or walls are used, ¹⁄₂" diameter anchor bolts
2. Operating weights include 5" of water in the collection basin. This with 8" projection and 2" minimum thread must be provided by the
is the recommended operating water level. Total collection basin contractor or purchaser. Bolts must be imbedded in the concrete.
depth is 11¹⁄₈". 7. Maintain no less than 2'-0" of clear space at tower endwalls for
3. Purchaser to design, construct and furnish tower support complete construction purposes. Louvered faces must have unobstructed
to suit the general dimensions of current Marley drawings. air supply. If obstructions exist nearby, consult your Marley sales
4. Last number of model indicates number of cells. Change as ap- representative.
propriate for your selection. Primary engineering data is per cell. 8. Except for “W” overall of wood basin, all dimensions are to the
centerline of the anchor bolts.


/ Series 15 Wood Basin Support /

A SPACES AT 4' 0" = L

1'-8 7/8"

B
W OVERALL OF WOOD BASIN

SUMP

C
OVERFLOW

1'-8 7/8"

Plan
8 1/2"
4" MIN.

NORMAL
GAGE

Section–Steel Beam Section–Concrete Beam

Dimensions Operating Weight


Tower Model lb
Note 4 L W A B C Single Fan Cell Each Cell Add
451-201 12'-0" 19'-2" 3 5'-6" 4'-856M" 37,280 34,110
452-201 16'-0" 21'-2" 4 5'-6" 6'-856M" 48,700 44,720
453-201 20'-0" 23'-2" 5 5'-6" 8'-856M" 61,860 57,300
454-201 24'-0" 23'-2" 6 5'-6" 8'-856M" 72,220 67,440
456-201 12'-0" 23'-2" 3 7'-6" 4'-856M" 45,560 41,730
457-201 16'-0" 25'-2" 4 7'-6" 6'-856M" 59,560 54,880
458-201 20'-0" 27'-2" 5 7'-6" 8'-856M" 75,220 69,950
459-201 24'-0" 27'-2" 6 7'-6" 8'-856M" 88,090 82,620

Note
1. Use this bulletin for preliminary layouts only. Do not use for 5. If steel beams are used, they must include ⁵⁄₈" diameter holes to
construction. Obtain current drawings from your Marley sales accept ³⁄₄" diameter anchor bolts provided.
representative. 6. If concrete beams or walls are used, ³⁄₄″ diameter anchor bolts with
2. Operating weights include 1" of water in the collection basin. This 8¹⁄₂" projection and 1¹⁄₂" minimum thread must be provided by the
is the recommended operating water level. Total collection basin contractor or purchaser. Bolts must be imbedded in the concrete.
depth is 1'-1³⁄₄". 7. Maintain no less than 2'-0" of clear space at tower endwalls for
3. Purchaser to design, construct and furnish tower support complete construction purposes. Louvered faces must have unobstructed
to suit the general dimensions of current Marley drawings. air supply. If obstructions exist nearby, consult your Marley sales
4. Last number of model indicates number of cells. Change as ap- representative.
propriate for your selection. Primary engineering data is per cell. 8. Except for “W” overall of wood basin, all dimensions are to the
centerline of the anchor bolts.


/ External Piping Plans /

C D
TYPICAL MULTI-CELL
FACE OF A DIA CL COLUMN CL INLET CL INLET
INLET FLANGE

G MIN
E

CL TOWER
Typical Plan–Side Inlet

E FACE OF A DIA
B DIA FLOW CL TOWER INLET FLANGE
CONTROL VALVE
B DIA FLOW
CONTROL VALVE
CL

H TO BASE
B DIA OF PERIMETER
TOWER COLUMNS
CROSSOVER PIPE

Section–Series 10 Distribution System

Dimensions
Tower Model GPM per Cell
A B C D E F G H
361-101 135-1000 8" 6" 4'-0" 8'-0" 7'-1" 8'-10 6M" 10'-7" 7'-10 56O"
362-101 165-1235 8" 6" 4'-0" 8'-0" 7'-1" 9'-10 6M" 11'-7" 7'-10 56O"
363-101 135-1000 8" 6" 4'-0" 8'-0" 7'-1" 8'-10 6M" 10'-7" 9'-10 56O"
364-101 165-1235 8" 6" 4'-0" 8'-0" 7'-1" 9'-10 6M" 11'-7" 9'-10 56O"
365-101 190-1455 8" 6" 4'-0" 8'-0" 7'-1" 10'-10 6M" 12'-7" 9'-10 56O"
366-101 205-1500 10" 8" 6'-0" 12'-0" 8'-2" 9'-10 6M" 11'-7" 7'-10 56O"
367-101 245-1850 10" 8" 6'-0" 12'-0" 8'-2" 10'-10 6M" 12'-7" 7'-11 56O"
368-101 205-1500 10" 8" 6'-0" 12'-0" 8'-2" 9'-10 6M" 11'-7" 9'-11 56O"
369-101 245-1850 10" 8" 6'-0" 12'-0" 8'-2" 10'-10 6M" 12'-7" 9'-11 56O"
370-101 285-2185 10" 8" 6'-0" 12'-0" 8'-2" 11'-10 6M" 13'-7" 9'-11 56O"
371-101 270-2000 10" 8" 8'-0" 16'-0" 8'-2" 9'-10 6M" 11'-7" 9'-11 56O"
372-101 325-2465 10" 8" 8'-0" 16'-0" 8'-2" 10'-10 6M" 12'-7" 9'-11 56O"
373-101 380-2910 10" 8" 8'-0" 16'-0" 8'-2" 11'-10 6M" 13'-7" 9'-11 56O"
374-101 340-2500 12" 10" 10'-0" 20'-0" 9'-256M" 10'-10 6M" 12'-7" 10'-0 56O"
375-101 410-3080 12" 10" 10'-0" 20'-0" 9'-256M" 11'-10 6M" 13'-7" 10'-0 56O"
376-101 475-3640 12" 10" 10'-0" 20'-0" 9'-256M" 12'-10 6M" 14'-7" 10'-0 56O"

10
/ External Piping Plans /

C D
TYPICAL MULTI-CELL
OUT OF HEADER
FACE OF A DIA CL COLUMN CL INLET CL INLET
INLET FLANGE

F MAX
E

CL TOWER
Typical Plan–End Inlet

E FACE OF A DIA
INLET FLANGE
B DIA FLOW CL TOWER
CONTROL VALVE
B DIA FLOW
CONTROL VALVE

CL

H TO BASE
OF PERIMETER
B DIA TOWER COLUMNS
CROSSOVER PIPE

Section–Series 15 Distribution System

Dimensions
Tower Model GPM per Cell
A B C D E F G H
451-201 201-2400 10" 8" 6'-0" 12'-0" 9'-0 56O" 10'-9" 13'-6" 14'-5 6M"
452-201 270-3200 10" 8" 8'-0" 16'-0" 10'-0 56O" 11'-9" 14'-6" 14'-5 6M"
453-201 340-4000 12" 10" 10'-0" 20'-0" 11'-4 56O" 12'-9" 15'-6" 14'-4 6M"
454-201 410-4800 12" 10" 12'-0" 24'-0" 11'-4 56O" 12'-9" 15'-6" 14'-4 6M"
456-201 285-3360 10" 8" 6'-0" 12'-0" 9'-0 56O" 12'-9" 15'-6" 14'-5 6M"
457-201 380-3690 10" 8" 8'-0" 16'-0" 10'-0 56O" 13'-9" 16'-6" 14'-5 6M"
457-201 3691-4480 12" 8" 8'-0" 16'-0" 10'-6 56O" 13'-9" 16'-6" 14'-5 6M"
458-201 475-5600 12" 10" 10'-0" 20'-0" 11'-4 56O" 14'-9" 17'-6" 14'-4 6M"
459-201 570-5300 12" 10" 12'-0" 24'-0" 11'-4 56O" 14'-9" 17'-6" 14'-4 6M"
459-201 5301-6720 14" 10" 12'-0" 24'-0" 11'-4 56O" 14'-9" 17'-6" 14'-4 6M"

Note
1. Use this bulletin for preliminary layouts only. Do not use for 4. Supports on tower for header and crossover pipe are part of the
construction. Obtain current drawings from your Marley sales tower design. Riser piping must be supported externally.
representative. 5. Marley piping terminates at the face of a cast iron flat face flange.
2. Pumping head contributed by the tower is static lift “H”. Actual Inlet and bolt circle dimensions conform to class 125 lb. ANSI
pumping head will vary according to tower circulating GPM. Total specifications.
pumping head will be furnished at time of proposal. 6. If your application requires a bypass system, recommended
3. Header should be located opposite fan motor when possible for location is through tower endwall into plenum area. Review of the
better distribution of tower loads. system by SPX Cooling Technologies engineering is required.

11
/ Additional Services /

SPX Cooling Technologies is dedicated to satisfying the needs of our customers—needs which begin far in advance of the actual purchase of a
new Marley cooling tower, and vary over the operating lifetime of the project. Here is a partial listing of the additional services offered by SPX Cooling
Technologies to help you do your job most effectively:

Application/Sizing/Layout Services—Sales Engineers are Reconstruction Service—Due to operating or atmospheric


trained to help you choose the proper type and size conditions, or age, sooner or later your tower will be in
of cooling tower, and will guide you in its appropri- need of repairs above and beyond those categorized
ate location on site. They will also help you write the as normal maintenance. Our reconstruction service can
specifications for its purchase. As the only manufacturer return your tower to as new condition
who makes all types of cooling products, SPX Cooling Performance Improvement Service—Systems served by
Technologies can offer you a wide range of options to cooling towers grow in response to demand for the
meet your requirements. product produced by that system. Most customers find
Construction Service—We can supply supervision only—or a that they could produce more product if the cooling
complete, experienced crew to handle construction. tower could deliver colder water. Fortunately, cooling
Parts Service—We maintain a stock of spare parts specific tower technology advances with time, and we can ap-
to your Marley tower. ply this increased technology to upgrade your tower’s
thermal performance.
Maintenance Service—In addition to providing complete
instructions and continuing guidance, we will provide Tower Replacement Service—Occasionally, customers will
as much “hands on” maintenance as you require, or will benefit from replacing an installed tower, rather than
recommend a local service contractor for your consider- refurbishing it. SPX Cooling Technologies stands ready
ation. to assist you in that endeavor—and, in most cases, the
replacement will require little or no change to your con-
Condition Inspection Service—From time to time, for your
crete basin or support structure.
peace of mind, our engineers can give your tower a
thorough inspection to evaluate its current condition.
This usually allows you to foresee and forestall problems
before they become serious.