Marley Series 10 - Series 15: Cooling Tower
Marley Series 10 - Series 15: Cooling Tower
}Ê/iV }iÃ
>ViÊNÊ>Ê ÀÞÊ }ÊNÊ>ÀiÞ
/ The Marley Difference /
Series 10 and Series 15 cooling towers are field n Fan Design is optimized for the static pressure
constructed, splash fill, crossflow wood cooling towers, imposition and airflow requirements of the tower.
designed to serve all normal cooling water systems—as n Fan Cylinders and their associated eased inlets,
well as those “dirty water” systems which would place augment fan operation.
the long term operation of a film-fill tower in jeopardy. n Fill and Fan Combinations are mutually supportive
These tower designs have evolved from the crossflow for maximum thermal performance in system
configuration.
concept of cooling towers pioneered by Marley® in 1938
and incorporate over 65 years of design advancements.
n Nozzles and Water Distribution systems provide
uniform fill coverage without excessive contribution to
Since 1922, customers have trusted the Marley air pressure losses.
brand for high quality, dependable products. The n The Geareducer® provides consistently optimum fan
principle reason for this reputation is our recognition that speeds, and operates reliably in a saturated air/vapor
each component of a cooling tower must perform at its mixture of corrosive nature.
peak—and all work compatibly toward overall efficiency. n Fan Motors are designed to Marley specifications
Accordingly, each performance-related component for extra demands of cooling tower duty. Motors are
insulated with extra protection from moisture.
of a Marley cooling tower is designed and manufactured
n Driveshafts are designed to absorb operational
in the context of the overall cooling tower system.
shock loads, thereby increasing the service life of
these critical components.
Marley Series 10
/ The Quality Advantage /
Marley Series 15
n Lower operating costs. Adjustable pitch fans with n Single-source parts availability. All tower
true airfoil blades and 98% efficient Geareducer components except the electric motors are designed,
drive assure maximum utilization of applied fan manufactured, guaranteed, and stocked by Marley.
power. Computer optimized fill configurations and You always know who to call for any parts you need.
low pressure-drop drift eliminators afford maximum You're also assured that all components of the
cooling with minimum power input. Gravity flow water cooling tower will work together, because they were
distribution minimizes pump power requirements. designed to work together!
n Lower maintenance costs. Heavy-duty aluminum n Flexible Cooling Capacity. Twenty-four tower
alloy fans, cast-iron Geareducers, and stainless models with capacities to 6720 GPM per fan cell,
steel driveshafts require only periodic maintenance. provide the flexibility to fit almost any job. Greater
Low-maintenance materials are used throughout capacity is available with multiple fan-cells.
the cooling tower. Wide-spaced splash-fill helps n Extremely Low Drift. XCEL®plus drift eliminators
prevent clogging. The fill area is readily accessible for really get rid of the costly nuisance of drift spotting on
cleaning. objects around the tower. The corrosion resistance of
n Five-year drivetrain warranty. What other PVC assures you that you’ll probably never have to
manufacturer will guarantee your tower's mechanical replace eliminators for the life of the tower.
equipment for five full years? You'll save valuable n Longer Service Life. Pressure-treated Douglas fir
equipment maintenance dollars. structure and splash-fill bars, FRP fill support grids,
n Proven Performance. SPX Cooling Technologies PVC drift eliminators, and all other tower components
stands by its responsibility for reliable thermal are designed for years of service.
performance. We designed it. We rate it. We
guarantee it!
/ Series 10 Schematic /
▲ C A U T I O N
The cooling tower must be located at such distance and direction
to avoid the possibility of contaminated tower discharge air
4" being drawn into building fresh air intake ducts. The purchaser
should obtain the services of a Licensed Professional Engineer or
Registered Architect to certify that the location of the tower is in
compliance with applicable air pollution, fire, and clean air codes.
W
TOP OF
PERIMETER
GUARDRAIL
H
L BASE OF
PERIMETER
TOWER COLUMNS
TOP OF
SUPPORTING
STEEL
4" 6 1/4"
Plan Endwall Elevation
iÃÃ
/ÜiÀÊ`i *Ê«iÀÊ i
ÌiÊ£ 7 >Ê`>iÌiÀ
361-101 £Îx£äää n¿ä¸ £¿Ó¸ £ä¿£äÊ56M¸ ÇÓ¸
ÎÈÓ£ä£ £Èx£ÓÎx n¿ä¸ Ó£¿Ó¸ £ä¿£äÊ56M¸ ÇÓ¸
ÎÈÎ£ä£ £Îx£äää n¿ä¸ £¿Ó¸ £Ó¿£äÊ56M¸ ÇÓ¸
ÎÈ{£ä£ £Èx£ÓÎx n¿ä¸ Ó£¿Ó¸ £Ó¿£äÊ56M¸ ÇÓ¸
ÎÈx£ä£ £ä£{xx n¿ä¸ ÓοӸ £Ó¿£äÊ56M¸ ÇÓ¸
ÎÈÈ£ä£ Óäx£xää £Ó¿ä¸ Ó£¿Ó¸ £ä¿£äÊ56M¸ ȸ
ÎÈÇ£ä£ Ó{x£nxä £Ó¿ä¸ ÓοӸ £ä¿£äÊ56M¸ ȸ
ÎÈn£ä£ Óäx£xää £Ó¿ä¸ Ó£¿Ó¸ £Ó¿£äÊ56M¸ ȸ
ÎÈ£ä£ Ó{x£nxä £Ó¿ä¸ ÓοӸ £Ó¿£äÊ56M¸ ȸ
ÎÇä£ä£ ÓnxÓ£nx £Ó¿ä¸ Óx¿Ó¸ £Ó¿£äÊ56M¸ ȸ
ÎÇ££ä£ ÓÇäÓäää £È¿ä¸ Ó£¿Ó¸ £Ó¿£äÊ56M¸ ȸ
ÎÇÓ£ä£ ÎÓxÓ{Èx £È¿ä¸ ÓοӸ £Ó¿£äÊ56M¸ ȸ
ÎÇÎ£ä£ ÎnäÓ£ä £È¿ä¸ Óx¿Ó¸ £Ó¿£äÊ56M¸ ȸ
ÎÇ{£ä£ Î{äÓxää Óä¿ä¸ ÓοӸ £Ó¿£äÊ56M¸ £Óä¸
ÎÇx£ä£ {£äÎänä Óä¿ä¸ Óx¿Ó¸ £Ó¿£äÊ56M¸ £Óä¸
ÎÇÈ£ä£ {ÇxÎÈ{ä Óä¿ä¸ ÓǿӸ £Ó¿£äÊ56M¸ £Óä¸
Note
1. The last number of the model indicates number of cells. Change 4. All tower installations require a minimum of 4'-0" from the tower
as appropriate for your selection. endwall to any vertical obstruction at the tower ladder location.
2. Overall length of the tower is: fan cells × L + 8. Primary engi- 5. Use this bulletin for preliminary layouts only. Do not use for
neering data is per cell. construction. Obtain current drawings from your Marley sales
3. Tower installations with an elevation of 20'-0" or more from top representative.
of the tower fan deck to the grade or roof level require a safety
cage on the tower ladder in accordance with OSHA standards.
Safety cage is an available option.
/ Series 15 Schematic /
3"
W
TOP OF
PERIMETER
GUARDRAIL
L 18' 6"
BASE OF
PERIMETER
TOWER COLUMNS
TOP OF
SUPPORTING
STEEL
3"
Plan 6 1/4"
Endwall Elevation
iÃÃ
/ÜiÀÊ`i *Ê«iÀÊ i
ÌiÊ£ 7 >Ê`>iÌiÀ
{x£Óä£ Óä£Ó{ää £Ó¿ä¸ Óx¿ä¸ £Óä¸
{xÓÓä£ ÓÇäÎÓää £È¿ä¸ ÓÇ¿ä¸ £{{¸
{xÎÓä£ Î{ä{äää Óä¿ä¸ Ó¿ä¸ £Èn¸
{x{Óä£ {£ä{nää Ó{¿ä¸ Ó¿ä¸ £Èn¸
{xÈÓä£ ÓnxÎÎÈä £Ó¿ä¸ Ó¿ä¸ £Óä¸
{xÇÓä£ Înä{{nä £È¿ä¸ Î£¿ä¸ £{{¸
{xnÓä£ {ÇxxÈää Óä¿ä¸ ÎÎ¿ä¸ £Èn¸
{xÓä£ xÇäÈÇÓä Ó{¿ä¸ ÎÎ¿ä¸ £Èn¸
Note
1. The last number of the model indicates number of cells. Change 4. All tower installations require a minimum of 4'-0" from the tower
as appropriate for your selection. endwall to any vertical obstruction at the tower ladder location.
2. Overall length of the tower is: fan cells × L + 6. Primary engi- 5. Use this bulletin for preliminary layouts only. Do not use for
neering data is per cell. construction. Obtain current drawings from your Marley sales
3. Tower installations with an elevation of 20'-0" or more from top representative.
of the tower fan deck to the grade or roof level require a safety
cage on the tower ladder in accordance with OSHA standards.
Safety cage is an available option.
/ Series 10 Concrete Basin /
SUMP
SEE NOTE 7
OPTIONAL
PARTITION WALL
Section–Deep Basin
Plan
Note
1. Use this bulletin for preliminary layouts only. Do not use for 5. All anchor bolts complete with nut and washer will be furnished by
construction. Obtain current drawings from your Marley sales others. Bolts are to be Z\x" diameter with 1Z\x" all thread projection.
representative. 6. Maintain no less than 2'-0" of clear space at tower endwalls for
2. Tower weight is total wet operating weight of tower only excluding construction purposes. Louvered faces must have unobstructed
water in concrete basin. air supply. If obstructions exist nearby, consult your Marley sales
3. Purchaser to design, construct and furnish concrete basin com- representative.
plete to suit the general dimensions of current Marley drawings. 7. Other contractors or purchaser must design, locate, construct, and
4. Last number of model indicates number of cells. Change as ap- furnish sump(s) and overflow(s) to suit requirements. The sump(s)
propriate for your selection. Primary engineering data is per cell. should be designed according to the pump manufacturer’s recom-
mendations. Other design sources: ANSI/HI specifications 1.1-1.5
for centrifugal pumps, 2.1-2.5 for vertical pumps, and 9.8 for pump
intake design.
/ Series 15 Concrete Basin /
SUMP
SEE NOTE 7 Section–Flat Slab Basin
OPTIONAL
PARTITION WALL
Section–Deep Basin
Plan
Note
1. Use this bulletin for preliminary layouts only. Do not use for 5. All anchor bolts complete with nut and washer will be furnished by
construction. Obtain current drawings from your Marley sales others. Bolts are to be ⁵⁄₈" diameter with 1¹⁄₂" all thread projec-
representative. tion—partition wall anchor bolts must have 3¹⁄₂" projection.
2. Tower weight is total wet operating weight of tower only excluding 6. Maintain no less than 2'-0" of clear space at tower endwalls for
water in concrete basin. construction purposes. Louvered faces must have unobstructed
3. Purchaser to design, construct and furnish concrete basin com- air supply. If obstructions exist nearby, consult your Marley sales
plete to suit the general dimensions of current Marley drawings. representative.
4. Last number of model indicates number of cells. Change as ap- 7. Other contractors or purchaser must design, locate, construct, and
propriate for your selection. Primary engineering data is per cell. furnish sump(s) and overflow(s) to suit requirements. The sump(s)
should be designed according to the pump manufacturer’s recom-
mendations. Other design sources: ANSI/HI specifications 1.1-1.5
for centrifugal pumps, 2.1-2.5 for vertical pumps, and 9.8 for pump
intake design.
/ Series 10 Wood Basin Support /
4" MIN.
B
W OVERALL OF WOOD BASIN
NORMAL
GAGE
SUMP
Section–Steel Beam
C
OVERFLOW
8"
Note
1. Use this bulletin for preliminary layouts only. Do not use for 5. If steel beams are used, they must include ⁵⁄₈" diameter holes to
construction. Obtain current drawings from your Marley sales accept ¹⁄₂" diameter anchor bolts provided.
representative. 6. If concrete beams or walls are used, ¹⁄₂" diameter anchor bolts
2. Operating weights include 5" of water in the collection basin. This with 8" projection and 2" minimum thread must be provided by the
is the recommended operating water level. Total collection basin contractor or purchaser. Bolts must be imbedded in the concrete.
depth is 11¹⁄₈". 7. Maintain no less than 2'-0" of clear space at tower endwalls for
3. Purchaser to design, construct and furnish tower support complete construction purposes. Louvered faces must have unobstructed
to suit the general dimensions of current Marley drawings. air supply. If obstructions exist nearby, consult your Marley sales
4. Last number of model indicates number of cells. Change as ap- representative.
propriate for your selection. Primary engineering data is per cell. 8. Except for “W” overall of wood basin, all dimensions are to the
centerline of the anchor bolts.
/ Series 15 Wood Basin Support /
1'-8 7/8"
B
W OVERALL OF WOOD BASIN
SUMP
C
OVERFLOW
1'-8 7/8"
Plan
8 1/2"
4" MIN.
NORMAL
GAGE
Note
1. Use this bulletin for preliminary layouts only. Do not use for 5. If steel beams are used, they must include ⁵⁄₈" diameter holes to
construction. Obtain current drawings from your Marley sales accept ³⁄₄" diameter anchor bolts provided.
representative. 6. If concrete beams or walls are used, ³⁄₄″ diameter anchor bolts with
2. Operating weights include 1" of water in the collection basin. This 8¹⁄₂" projection and 1¹⁄₂" minimum thread must be provided by the
is the recommended operating water level. Total collection basin contractor or purchaser. Bolts must be imbedded in the concrete.
depth is 1'-1³⁄₄". 7. Maintain no less than 2'-0" of clear space at tower endwalls for
3. Purchaser to design, construct and furnish tower support complete construction purposes. Louvered faces must have unobstructed
to suit the general dimensions of current Marley drawings. air supply. If obstructions exist nearby, consult your Marley sales
4. Last number of model indicates number of cells. Change as ap- representative.
propriate for your selection. Primary engineering data is per cell. 8. Except for “W” overall of wood basin, all dimensions are to the
centerline of the anchor bolts.
/ External Piping Plans /
C D
TYPICAL MULTI-CELL
FACE OF A DIA CL COLUMN CL INLET CL INLET
INLET FLANGE
G MIN
E
CL TOWER
Typical Plan–Side Inlet
E FACE OF A DIA
B DIA FLOW CL TOWER INLET FLANGE
CONTROL VALVE
B DIA FLOW
CONTROL VALVE
CL
H TO BASE
B DIA OF PERIMETER
TOWER COLUMNS
CROSSOVER PIPE
Dimensions
Tower Model GPM per Cell
A B C D E F G H
361-101 135-1000 8" 6" 4'-0" 8'-0" 7'-1" 8'-10 6M" 10'-7" 7'-10 56O"
362-101 165-1235 8" 6" 4'-0" 8'-0" 7'-1" 9'-10 6M" 11'-7" 7'-10 56O"
363-101 135-1000 8" 6" 4'-0" 8'-0" 7'-1" 8'-10 6M" 10'-7" 9'-10 56O"
364-101 165-1235 8" 6" 4'-0" 8'-0" 7'-1" 9'-10 6M" 11'-7" 9'-10 56O"
365-101 190-1455 8" 6" 4'-0" 8'-0" 7'-1" 10'-10 6M" 12'-7" 9'-10 56O"
366-101 205-1500 10" 8" 6'-0" 12'-0" 8'-2" 9'-10 6M" 11'-7" 7'-10 56O"
367-101 245-1850 10" 8" 6'-0" 12'-0" 8'-2" 10'-10 6M" 12'-7" 7'-11 56O"
368-101 205-1500 10" 8" 6'-0" 12'-0" 8'-2" 9'-10 6M" 11'-7" 9'-11 56O"
369-101 245-1850 10" 8" 6'-0" 12'-0" 8'-2" 10'-10 6M" 12'-7" 9'-11 56O"
370-101 285-2185 10" 8" 6'-0" 12'-0" 8'-2" 11'-10 6M" 13'-7" 9'-11 56O"
371-101 270-2000 10" 8" 8'-0" 16'-0" 8'-2" 9'-10 6M" 11'-7" 9'-11 56O"
372-101 325-2465 10" 8" 8'-0" 16'-0" 8'-2" 10'-10 6M" 12'-7" 9'-11 56O"
373-101 380-2910 10" 8" 8'-0" 16'-0" 8'-2" 11'-10 6M" 13'-7" 9'-11 56O"
374-101 340-2500 12" 10" 10'-0" 20'-0" 9'-256M" 10'-10 6M" 12'-7" 10'-0 56O"
375-101 410-3080 12" 10" 10'-0" 20'-0" 9'-256M" 11'-10 6M" 13'-7" 10'-0 56O"
376-101 475-3640 12" 10" 10'-0" 20'-0" 9'-256M" 12'-10 6M" 14'-7" 10'-0 56O"
10
/ External Piping Plans /
C D
TYPICAL MULTI-CELL
OUT OF HEADER
FACE OF A DIA CL COLUMN CL INLET CL INLET
INLET FLANGE
F MAX
E
CL TOWER
Typical Plan–End Inlet
E FACE OF A DIA
INLET FLANGE
B DIA FLOW CL TOWER
CONTROL VALVE
B DIA FLOW
CONTROL VALVE
CL
H TO BASE
OF PERIMETER
B DIA TOWER COLUMNS
CROSSOVER PIPE
Dimensions
Tower Model GPM per Cell
A B C D E F G H
451-201 201-2400 10" 8" 6'-0" 12'-0" 9'-0 56O" 10'-9" 13'-6" 14'-5 6M"
452-201 270-3200 10" 8" 8'-0" 16'-0" 10'-0 56O" 11'-9" 14'-6" 14'-5 6M"
453-201 340-4000 12" 10" 10'-0" 20'-0" 11'-4 56O" 12'-9" 15'-6" 14'-4 6M"
454-201 410-4800 12" 10" 12'-0" 24'-0" 11'-4 56O" 12'-9" 15'-6" 14'-4 6M"
456-201 285-3360 10" 8" 6'-0" 12'-0" 9'-0 56O" 12'-9" 15'-6" 14'-5 6M"
457-201 380-3690 10" 8" 8'-0" 16'-0" 10'-0 56O" 13'-9" 16'-6" 14'-5 6M"
457-201 3691-4480 12" 8" 8'-0" 16'-0" 10'-6 56O" 13'-9" 16'-6" 14'-5 6M"
458-201 475-5600 12" 10" 10'-0" 20'-0" 11'-4 56O" 14'-9" 17'-6" 14'-4 6M"
459-201 570-5300 12" 10" 12'-0" 24'-0" 11'-4 56O" 14'-9" 17'-6" 14'-4 6M"
459-201 5301-6720 14" 10" 12'-0" 24'-0" 11'-4 56O" 14'-9" 17'-6" 14'-4 6M"
Note
1. Use this bulletin for preliminary layouts only. Do not use for 4. Supports on tower for header and crossover pipe are part of the
construction. Obtain current drawings from your Marley sales tower design. Riser piping must be supported externally.
representative. 5. Marley piping terminates at the face of a cast iron flat face flange.
2. Pumping head contributed by the tower is static lift “H”. Actual Inlet and bolt circle dimensions conform to class 125 lb. ANSI
pumping head will vary according to tower circulating GPM. Total specifications.
pumping head will be furnished at time of proposal. 6. If your application requires a bypass system, recommended
3. Header should be located opposite fan motor when possible for location is through tower endwall into plenum area. Review of the
better distribution of tower loads. system by SPX Cooling Technologies engineering is required.
11
/ Additional Services /
SPX Cooling Technologies is dedicated to satisfying the needs of our customers—needs which begin far in advance of the actual purchase of a
new Marley cooling tower, and vary over the operating lifetime of the project. Here is a partial listing of the additional services offered by SPX Cooling
Technologies to help you do your job most effectively:
Cooling Technologies
Balcke | Hamon Dry Cooling | Marley
/ 7401 W 129 Street // Overland Park, KS USA 66213 // +1 913 664 7400 // [email protected] // www.spxcooling.com /
In the interest of technological progress, all products are subject to design and/or material change without notice
©2005 SPX Cooling Technologies, Inc. | Printed in USA
S-10/15-05