MPPT Solar Charger Manual PDF en
MPPT Solar Charger Manual PDF en
Rev 09 - 02/2025
This manual is also available in HTML5
MPPT solar charger manual
Table of Contents
1. Safety precautions ................................................................................................................... 1
1.1. General safety precautions ................................................................................................. 1
1.2. Wiring safety precautions ................................................................................................... 1
1.3. Symbols used on the enclosure ........................................................................................... 2
1.4. FCC and Industry Canada compliance ................................................................................... 2
2. Introduction ........................................................................................................................... 3
2.1. Battery voltage, PV voltage and current rating ........................................................................... 3
2.2. TR or MC4 model ............................................................................................................ 3
3. Features ................................................................................................................................ 4
3.1. Automatic battery voltage detection ....................................................................................... 4
3.2. Outstanding MPPT algorithm .............................................................................................. 4
3.3. Outstanding conversion efficiency ......................................................................................... 4
3.4. Extensive electronic protection ............................................................................................ 4
3.5. VictronConnect app ......................................................................................................... 4
3.6. Display ........................................................................................................................ 5
3.7. VE.Direct port ................................................................................................................ 6
3.8. VE.Can ports ................................................................................................................. 6
3.9. Load output .................................................................................................................. 6
3.9.1. Virtual load output ................................................................................................. 6
3.9.2. BatteryLife .......................................................................................................... 6
3.10. Battery charging ............................................................................................................ 6
3.10.1. Adaptive 3-stage battery charging ............................................................................. 6
3.10.2. Flexible charge algorithm ....................................................................................... 7
3.10.3. Equalization charging ........................................................................................... 7
3.11. Temperature sensing ...................................................................................................... 7
3.11.1. Internal temperature sensor .................................................................................... 7
3.11.2. External temperature and voltage sensor ..................................................................... 7
3.12. Voltage sensing ............................................................................................................ 8
3.13. Remote on/off .............................................................................................................. 8
3.14. Programmable relay ....................................................................................................... 8
3.15. WireBox ..................................................................................................................... 9
4. Installation ........................................................................................................................... 10
4.1. Mounting .................................................................................................................... 10
4.2. Battery ...................................................................................................................... 10
4.3. PV array .................................................................................................................... 10
4.4. Grounding .................................................................................................................. 12
4.5. Connection overview ...................................................................................................... 12
4.6. Electrical connections ..................................................................................................... 13
4.7. VE.Can ports ............................................................................................................... 14
4.8. Install the optional SmartSolar Control display ......................................................................... 14
4.9. Connect the MPPT Control display ...................................................................................... 15
6. Operation ............................................................................................................................ 37
6.1. Start up ..................................................................................................................... 37
6.2. Battery charging ........................................................................................................... 37
6.3. Automatic equalization .................................................................................................... 38
6.4. Lithium batteries ........................................................................................................... 38
6.5. Shutdown and restart procedure ........................................................................................ 38
6.6. Maintenance procedure ................................................................................................... 39
7. Monitoring ........................................................................................................................... 40
7.1. LED indications ............................................................................................................ 40
7.2. Error codes ................................................................................................................. 41
7.3. Monitoring via the VictronConnect app ................................................................................. 41
7.3.1. VictronConnect app status screen ............................................................................ 41
7.3.2. VictronConnect app history screen ............................................................................ 42
7.3.3. VictronConnect app error reporting ........................................................................... 43
7.4. Monitoring via a GX device and VRM ................................................................................... 43
8. Troubleshooting .................................................................................................................... 45
8.1. Solar charger is damaged ................................................................................................ 45
8.2. Solar charger is unresponsive ........................................................................................... 45
8.3. Solar charger is off ........................................................................................................ 46
8.3.1. PV voltage too low .............................................................................................. 46
8.3.2. Settings being edited on an external display ................................................................. 47
8.3.3. Disabled in the settings ......................................................................................... 48
8.3.4. Disabled by remote or BMS .................................................................................... 48
8.3.5. Low lithium battery temperature ............................................................................... 48
8.4. Solar charger is externally controlled ................................................................................... 48
8.5. Batteries are not charged ................................................................................................. 49
8.5.1. Battery is full ..................................................................................................... 49
8.5.2. Battery not connected .......................................................................................... 50
8.5.3. Reverse battery polarity ........................................................................................ 51
8.5.4. Battery settings too low ......................................................................................... 51
8.5.5. PV voltage too high ............................................................................................. 52
8.5.6. Reverse PV polarity ............................................................................................. 52
8.6. Batteries are undercharged .............................................................................................. 53
8.6.1. Insufficient solar supply ......................................................................................... 53
8.6.2. DC load too high ................................................................................................ 54
8.6.3. Battery cable voltage drop ..................................................................................... 54
8.6.4. Temperature compensation setting incorrect ................................................................ 55
8.6.5. Temperature difference between solar charger and battery ................................................ 55
8.7. Batteries are overcharged ................................................................................................ 56
8.7.1. Battery voltage setting too high ................................................................................ 56
8.7.2. Battery charge voltage settings too high ...................................................................... 56
8.7.3. Battery unable to deal with equalisation ...................................................................... 56
8.7.4. Battery old, faulty or undersized ............................................................................... 56
8.8. Solar charger not achieving full output .................................................................................. 57
8.8.1. PV yield lower than expected .................................................................................. 57
8.8.2. Maximum output power relates to battery voltage ........................................................... 58
8.8.3. Temperature above 40°C ....................................................................................... 59
8.8.4. PV connections burned or melted ............................................................................. 59
8.9. Communication Issues .................................................................................................... 59
8.9.1. Bluetooth ......................................................................................................... 59
8.9.2. VE.Direct port .................................................................................................... 60
8.9.3. VE.Smart Networking ........................................................................................... 60
8.10. Miscellaneous issues .................................................................................................... 61
8.10.1. Unable to operate as a DC-DC charger or power supply ................................................. 61
8.10.2. Interrupted firmware update .................................................................................. 61
8.10.3. Ground current ................................................................................................. 61
8.10.4. Programmable relay issues ................................................................................... 61
8.10.5. PV Short relay reset procedure .............................................................................. 61
8.11. Error code overview ...................................................................................................... 63
8.11.1. Error 1 - Battery temperature too high ....................................................................... 63
8.11.2. Error 2 - Battery voltage too high ............................................................................. 63
8.11.3. Error 17 - Solar charger overheated despite reduced output current .................................... 63
8.11.4. Error 18 - Solar charger over-current ........................................................................ 63
8.11.5. Error 20 - Maximum bulk time exceeded .................................................................... 63
8.11.6. Error 21 - Current sensor issue .............................................................................. 63
8.11.7. Error 26 - Terminal overheated ............................................................................... 63
MPPT solar charger manual
1. Safety precautions
• Install the product in a heatproof environment. Ensure therefore that there are no chemicals, plastic parts,
curtains or other textiles, etc. in the immediate vicinity of the equipment.
• Ensure that the equipment is used under the correct operating conditions. Never operate it in a wet
environment.
• Never use the product at sites where gas or dust explosions could occur.
• Ensure that there is always sufficient free space around the product for ventilation.
• Refer to the specifications provided by the manufacturer of the battery to ensure that the battery is suitable
for use with this product. The battery manufacturer's safety instructions should always be observed.
• Protect the solar modules from incident light during installation, e.g. cover them.
• This product is designed and tested in accordance with international standards. The equipment should be
used for the designated application only.
• Connections must always be made in the sequence described in the Installation [10] chapter of this
manual.
• The installer of the product must provide a means for cable strain relief to prevent the transmission of stress
to the connections.
• In addition to this manual, the system operation or service manual must include a battery maintenance
manual applicable to the type of batteries used.
• The diameter of the individual strand of the cable used should not exceed 0.4mm (0.016 inch) or have a
surface area exceeding 0.125mm² (AWG26).
• For MC4 models only: The maximum current rating of a MC4 connector is 30A.
• A 25mm² cable, for example, should have at least 196 strands (class 5 or higher stranding according to
VDE 0295, IEC 60228 and BS6360). An AWG2 gauge cable should have at least 259/26 stranding (259
strands of AWG26). Example of suitable cable: class 5 “Tri-rated” cable (it has three approvals: American
(UL), Canadian (CSA) and British (BS)).
• In case of thicker strands the contact area will be too small and the resulting high contact resistance will
cause severe overheating, eventually resulting in fire. See below figure for examples of what cable to use
and not to use.
Hot surface warning Do not touch the surface of the appliance, while it is running, it will get hot.
IP43 - The electronic components are protected from tools and small wires
Ingress protection value greater than 1 millimetre and protected from water spray less than 60 degrees
from vertical.
2. This device must accept any interference received, including interference that may cause undesired operation.
Le présent appareil est conforme aux CNR d'Industrie Canada applicables aux appareils radio exempts de licence. L'exploitation
est autorisée aux deux conditions suivantes : (1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit
accepter tout brouillage radioélectrique subi, même si le brouillage est susceptible d’en compromettre le fonctionnement.
Changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to
operate the equipment.
Note: This equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to part 15 of
the FCC Rules. These limits are designed to provide reasonable protection against harmful interference when the equipment
is operated in a commercial environment. This equipment generates, uses, and can radiate radio frequency energy and, if not
installed and used in accordance with the instruction manual, may cause harmful interference to radio communications. Operation
of this equipment in a residential area may cause radio interference in which case the user will be required to correct the
interference at his own expense.
To comply with FCC and Industry Canada RF radiation exposure limits for general population, the antenna(s) used for this
transmitter must be installed such that a minimum separation distance of 20cm is maintained between the radiator (antenna) and
all persons at all times and must not be co-located or operating in conjunction with any other antenna or transmitter.
2. Introduction
The Victron Energy SmartSolar charge controller is an ultra fast Maximum Power Point Tracking (MPPT) solar charger with an
outstanding conversion efficiency and is suitable for a wide range of battery and PV voltages.
The product name of the solar charger incorporates the maximum PV voltage and the maximum battery charge current.
For example: A 150/70 model has a maximum PV voltage of 150V and can charge the battery with a maximum of 70A.
The table below indicates the maximum PV voltage and maximum battery charge current of the solar chargers that are covered
by this manual:
Solar charger model Maximum PV voltage Maximum battery charge current Suitable battery voltages
MPPT 150/70 150V 70A 12, 24, 36 and 48V
MPPT 150/85* 150V 85A 12, 24, 36 and 48V
MPPT 150/100* 150V 100A 12, 24, 36 and 48V
MPPT 250/70 250V 70A 12, 24, 36 and 48V
MPPT 250/85 250V 85A 12, 24, 36 and 48V
MPPT 250/100 250V 100A 12, 24, 36 and 48V
The 70A MC4 model has 2 MC4 male and female connector pairs.
The 85A and 100A MC4 models have 3 MC4 male and female connector pairs.
From left to right: Example of solar chargers with screw terminals and MC4 PV connections
Page 3 Introduction
MPPT solar charger manual
3. Features
The solar charger contains an ultra fast MPPT controller. This is especially beneficial when the solar light intensity is constantly
changing, as is the case during cloudy weather. Because of the ultra fast MPPT controller, 30% more energy is harvested
compared to solar chargers with a PWM controller and up to 10% more compared to slower MPPT controllers.
The solar charger has an innovative tracking algorithm. It will always maximize energy harvest by locking to the optimum MPP
(Maximum Power Point). If partial shading occurs, two or more maximum power points may be present on the power-voltage
curve. Conventional MPPTs tend to lock to a local MPP, which may not be the optimum MPP.
The solar charger is equipped with PV reverse polarity protection and PV reverse current protection.
• Monitor the solar charger and view real-time solar and battery data.
• Update firmware.
Screenshot of the VictronConnect app, showing real-time data and historical data.
The VictronConnect app can be downloaded from app stores or from the Victron Energy downloads page.
Page 4 Features
MPPT solar charger manual
• Android.
• Apple iOS, note that USB is not supported, it is only possible to connect via Bluetooth.
• MacOs.
• Windows, note that Bluetooth is not supported, it is only possible to connect via USB.
The app can connect to the solar charger in the following ways:
• Via internet or LAN, through the VRM portal, using an optional GX device or GlobalLink 520.
3.6. Display
There are a number of display options:
• A GX device.
• The SmartSolar Control display - an (optional) external display that plugs into the front of the solar charger.
• The MPPT Control - an (optional) external display that connects to the VE.Direct port. Note that the required VE.Direct cable is
not included with the MPPT Control.
Page 5 Features
MPPT solar charger manual
• VE.Direct to USB interface - used to connect via USB to the VictronConnect app.
• VE.Direct Bluetooth Smart dongle - used to connect via Bluetooth to the VictronConnect app.
• VE.Direct TX digital output cable - used for streetlight control or to create a virtual load output.
• VE.Direct non inverting remote on/off cable - used to remotely switch the solar charger on or off.
• Multiple VE.Can solar chargers, other VE.Can products, and/or a GX device - for a range of applications.
• Use the VE.Direct TX cable and enable it to act as a virtual load output via the VictronConnect App RX port function. Refer to
the RX port settings [31] chapter.
The virtual load output can be set up within the VictronConnect app and controlled using battery voltages or the BatteryLife
algorithm. For details on the configuration process, please consult the Load output settings [24] chapter.
3.9.2. BatteryLife
This chapter only applies if the virtual load output is used.
When the solar charger is not able to recharge the battery to its full capacity within one day, the result is often that the battery will
continually be cycled between a ‘partially charged’ state and the ‘end of discharge’ state. This mode of operation (no regular full
recharge) will destroy a lead-acid battery within weeks or months.
The BatteryLife algorithm will monitor the state of charge of the battery and, if needed, day by day slightly increase the load
disconnect level (i.e. disconnect the load earlier) until the harvested solar energy is sufficient to recharge the battery to nearly the
full 100%. From that point onward, the load disconnect level will be modulated so that a nearly 100% recharge is achieved about
once every week.
Bulk
Page 6 Features
MPPT solar charger manual
During the bulk stage, the solar charger delivers the maximum charge current, to rapidly charge the batteries. During this stage,
the battery voltage will slowly increase. Once the battery voltage has reached the set absorption voltage, the bulk stage stops and
the absorption stage commences.
Absorption
During the absorption stage, the solar charger has switched to constant voltage mode. The current flowing to the battery will
gradually decrease. Once the current has dropped below 2A (tail current), the absorption stage stops and the float stage will
commence.
When only shallow discharges occur the absorption time is kept short. This is to prevent overcharging of the battery. But if the
battery was deeply discharged, the absorption time is automatically increased, to make sure that the battery is fully recharged.
Float
During the float stage, the voltage is reduced, and the battery's fully charged state is maintained.
A storage stage is not needed for solar chargers, unlike for AC chargers, since at night there is no solar
power, so battery charging will stop.
Temperature compensated battery charging is needed when charging lead-acid batteries in hot or cold environments.
The temperature compensation can be enabled or disabled in the solar charger settings and the amount of compensation, the
compensation coefficient (mV/°C), is adjustable.
The internal temperature is used to set the temperature compensated charge voltages. For this, the internal temperature when
the solar charger is "cold" is used. The solar charger is "cold" when there is only little current flowing into the battery. Be aware
that this is only an estimation of the ambient and the battery temperature. Should a more accurate battery temperate be needed,
consider using an external battery temperature sensor, see chapter External temperature and voltage sensor [7].
The internal temperature sensor is also used to determine if the solar charger is overheated.
The solar charger uses the Smart Battery Sense measurements for:
• Temperature compensated charging using the actual battery temperature, rather than the solar charger's internal temperature.
An accurate battery temperature measurement will improve charging efficiency and prolong the life of lead-acid batteries.
• Voltage compensation. The charge voltage is increased to compensate in case there is a voltage drop over the battery cables
during high current charging.
The solar charger communicates with the Smart Battery Sense via Bluetooth using a VE.Smart Network. For more detail on the
VE.Smart network see the VE.Smart Networking manual.
Page 7 Features
MPPT solar charger manual
Alternatively, a VE.Smart Network that measures battery temperature and battery voltage, can also be set up between a solar
charger and a BMV-712 Smart or SmartShunt battery monitor that has been equipped with a Temperature sensor for BMV,
without the need for a Smart Battery Sense.
Note that a VE.Smart Network can only be set up if the solar charger is capable of Bluetooth communication,
has Bluetooth enabled or is equipped with a VE.Direct Bluetooth Smart dongle.
There are several ways to turn the solar charger on using the remote terminal(s):
• When the voltage on the H terminal is more than 2.9V (up to the battery voltage) via a switch, relay or other external device,
like a battery BMS.
• When the voltage on the L terminal is pulled to battery minus. (<3.5V) via a switch, relay or other external device, like a battery
BMS.
A virtual remote on/off terminal can be created by using the (optional) VE.Direct non inverting remote on/off cable.
The functionality can be programmed using the VictronConnect App RX port function settings.
• High PV voltage
Page 8 Features
MPPT solar charger manual
• Day detection
• Load output
3.15. WireBox
The optional MPPT WireBox is a plastic cover that can be attached to the bottom of the solar charger. It covers the battery and
solar terminals, preventing accidental or inquisitive contact with the battery and PV terminals. It provides an extra level of safety,
and is particularly useful if the solar charger is installed in a general access area.
For more information and to find the right MPPT WireBox for your solar charger see the MPPT WireBox product page:
• MPPT WireBox-MC4
• MPPT WireBox-Tr
Page 9 Features
MPPT solar charger manual
4. Installation
The DC (PV) input is not isolated from the battery circuit. Therefore the PV, battery and control circuit are
considered hazardous and should not be user accessible.
For proper temperature compensated battery charging the ambient temperature of the solar charger and the
battery must be within 5°C (9°F).
The battery and PV connections must be guarded against inadvertent contact. Install the solar charger in an
enclosure or install the optional WireBox [9].
4.1. Mounting
Mount the solar charger vertically on a non-flammable substrate, with the electrical terminals facing downwards.
The Dimension drawings [70] chapter of this manual contains the dimension drawing of the solar charger, this drawing also
indicates the mounting holes.
Observe a minimum clearance of 10cm under and above the solar charger for optimal cooling.
Mount the solar charger within 3 meters from the battery, but never directly above the battery. This is to prevent damage due to
gassing of the battery.
Avoid ambient temperature differences of more than 5°C between the solar charger and the battery. These
temperature differences can lead to incorrect temperature compensated charging, which can reduce the
battery lifetime.
If large temperature differences or extreme ambient temperature conditions are expected, use a direct battery
temperature sense source like the Smart Battery Sense or a BMV or SmartShunt equipped with a temperature
sensor.
• For solar chargers with screw PV terminal use the MPPT WireBox TR.
• For solar chargers with MC4 PV terminals use the MPPT WireBox MC4.
• Affix the steel WireBox base to the solar charger before the solar charger is mounted into its final position.
• For full mounting instructions, see the MPPT WireBox TR or MPPT WireBox MC4 quick installation guide.
4.2. Battery
The battery supply must be protected by a fuse as per the below table.
Solar charger type Minimum battery fuse rating Maximum battery fuse rating
MPPT 150/70 and 250/70 80A 100A
MPPT 150/85A and 250/85 100A 120A
MPPT 150/100 and 250/100 120A 140A
For Canada the battery fuse must comply with the C22.2 standards.
The battery installation must be done in accordance with the local storage battery rules. For Canada this is the
Canadian Electrical Code, Part I.
Use flexible multi stranded copper cable for the battery connections Also see chapter Wiring safety
precautions [1].
4.3. PV array
The solar charger can be used with a PV configuration that satisfies both these two conditions:
Page 10 Installation
MPPT solar charger manual
• The maximum open circuit PV voltage can not exceed 150 or 250V, depending on the solar charger model.
• The nominal PV voltage should be at least 5V higher than the battery voltage.
The solar panels are connected in series, in parallel or in series/parallel. See below figure for examples of these configurations.
To help calculate the size of the PV array configuration use the MPPT sizing calculator. Alternatively, use one of these PV array
configurations:
• Minimum number of cells in series: 72 (2x 12V panel in series or 1x 24V panel).
• Recommended number of cells for highest controller efficiency: 144 cells (4x 12V panel or 2x 24V panel in series).
• Minimum number of cells in series: 144 (4x 12V panel or 2x 24V panel in series).
• Minimum number of cells in series: 144 (4x 12V panel or 2x 24V panel in series).
• Provide a means to disconnect all current-carrying conductors of a photo-voltaic power source from all other
conductors in a building or other structure.
• Careful: when calculating the number of panels that can be used in series, make sure to take both its Open
circuit voltage (Voc) and its Temperature coefficient into account. At ambient temperatures below 25°C, the
Voc will be higher.
• A switch, circuit breaker, or other device, either AC or DC, shall not be installed in a grounded conductor if
operation of that switch, circuit breaker, or other device leaves the grounded conductor in an un-grounded
state while the system remains energized.
• Do not use solar panels with optimizers. In worst case, the use of optimizers will cause irreparable damage
to the solar charger.
• Use flexible multi stranded copper cable for the screw connections (Tr model). See chapter Wiring safety
precautions [1].
• For MC4 models: several of the solar charger's MC4 pairs may be needed to parallel solar panel strings. Be
aware that the maximum current through a MC4 connection cannot exceed 30A.
Page 11 Installation
MPPT solar charger manual
4.4. Grounding
Battery grounding
Apply a single ground connection, preferably close to the battery, to prevent system issues or ground loops.
PV array grounding
Do not connect the solar charger to a grounded PV array. Only one ground connection is allowed, and this should be near the
battery.
WARNING: The solar charger is not provided with a Ground Fault Detector Interrupter (GFDI) device. This
charge controller must be used with an external GFDI device as required by the Article 690 of the USA
National Electrical Code for the installation location.
The system electrical negative should be bonded through a GFDI to earth ground at one (and only one) location.
WARNING: When a ground fault is indicated, battery terminals and connected circuits may be ungrounded
and hazardous.
TR model.
Page 12 Installation
MPPT solar charger manual
ID Description
A Ground screw connection.
B Rotary switch.
C LEDs.
D VE.Direct socket.
E Battery screw terminals.
F PV screw terminals.
G Relay screw terminals.
H VE.Can sockets.
I Remote on/off terminals.
1. Connect the battery: allow the solar charger to automatically recognise the system voltage (wait 10 seconds).
4. Connect the applicable other connections: such as the remote on/off connector, the programmable relay connector, the
VE.Can port or the VE.Direct port.
The correct connection order is necessary to allow the automatic system voltage detection to setup properly. It is only allowed to
connect PV first when the system voltage is manually set before connecting the battery. Not following the correct procedures can
disable or damage the charger and/or the installation.
See the below figure on how the basic electrical connections are made:
Page 13 Installation
MPPT solar charger manual
ID Description
A Solar charger, on the left the Tr model and on the right the MC4 model.
B Battery or battery bank, lead acid or lithium.
C Solar panel or solar panel array.
D DC loads.
DC fuse.
A maximum of 25 devices can be “daisy-chained” using RJ45 UTP cables (not included).
The first and last devices in the chain require a VE.Can RJ45 terminator (not included).
Right: Multiple chargers connected to a GX device for synchronised charging and monitoring.
The VE.Can +V line is connected to the battery positive and the -V line is connected to the battery minus and the PV minus. This
means that any equipment connected to VE.Can will be a permanent battery load.
The VE.Can bus is not galvanically isolated. For positive grounded systems, a separate CAN isolation module (not provided by
Victron) is necessary.
1. Remove the two screws of the plastic cover. Keep the screws, they are needed again when securing the display.
3. Remove the two plastic plugs on either side of the display plug.
4. Remove the paper backing of the double sided tape on the back of the display.
5. Insert the display into the plug and make sure it has been inserted all the way in.
Page 14 Installation
MPPT solar charger manual
6. Screw the display down by using the two screws that were used for the plastic cover.
The display is hot-swappable, this means that the display can be plugged in or removed while the solar
charger is operating.
The VE.Direct cable is available in a variety of lengths and is not included with the MPPT control display. Note that it is not
possible to extend the VE.Direct cable, the maximum length can not exceed 10 meters.
Page 15 Installation
MPPT solar charger manual
The solar charger settings can be configured so it can be taylored specifically for the system it is used in.
Do not change solar charger settings unless you know what they are and what the effect of changing these
settings is going to be.
Incorrect settings may cause system problems including damage to batteries. When in doubt, seek advice
from an experienced Victron Energy installer, dealer or distributor.
• The VictronConnect app - All settings can be changed and the firmware can be updated.
• The rotary switch - The charge algorithm for a number of pre-set battery types can be selected.
Do not change solar charger settings unless you know what they are and what the effect of changing these
settings can be. Incorrect settings may cause system problems including damage to batteries. When in doubt,
seek advice from an experienced Victron Energy installer, dealer or distributor.
See the VictronConnect app [4] chapter for an overview of the different ways the VictronConnect app can connect to the solar
charger.
This manual only covers the VictronConnect app solar charger-specific items. For more general information on the
VictronConnect app, like how to use it or how to connect, see the VictronConnect manual.
To access the solar charger settings, navigate to the settings page. Do this by clicking on the cog icon at the top right of the
home screen.
The settings page provides access to view and/or to change the solar charger settings.
For information about each setting and how to update firmware see the Updating firmware [32] chapter.
Use a small flathead screwdriver to turn the rotary switch. The arrow indicates which setting number has been selected.
The table below indicates the charge algorithm and charge settings for each rotary switch position.
Turning the rotary switch will override the charge settings including settings that were made with the
VictronConnect app or with the display. Likewise, if charge settings are changed with the VictronConnect
app or the display, this will override the rotary switch setting.
Equalize**
Float Temperature
Switch Suggested Absorption Equalize** nominal
voltage* compensation
position battery type voltage* (V) voltage* (V) current
(V) factor* (mV/°C)
percentage
Gel long life
(OPzV) 14.1 13.8 15.9 -16
0 Gel Exide A600 28.2 27.6 31.8 8% -32
(OPzV) 56.4 55.2 63.6 -64
Gel MK
Gel Victron
deep discharge
Gel Exide A200 14.3 13.8 16.1 -16
1 AGM Victron 28.6 27.6 32.2 8% -32
deep discharge
57.2 55.2 64.4 -64
Stationary
tubular plate
(OPzS)
Default setting
Gel Victron
deep discharge
14.4 13.8 16.2 -16
Gel Exide A200
2 28.8 27.6 32.4 8% -32
AGM Victron
deep discharge 57.6 55.2 64.8 -64
Stationary
tubular plate
(OPzS)
AGM spiral cell
14.7 13.8 16.5 -16
Stationary
3 tubular plate 29.4 27.6 33.0 8% -32
(OPzS) 58.8 55.2 66.0 -64
Rolls AGM
PzS tubular 14.9 13.8 16.7 -16
plate traction
4 29.8 27.6 33.4 25% -32
batteries or
OPzS batteries 59.6 55.2 66.8 -64
* The top value is for 12V systems, the middle for 24V systems and the bottom for 48V systems.
** Equalize is by default disabled. To enable see chapter Battery settings [19]
Equalize**
Float Temperature
Switch Suggested Absorption Equalize** nominal
voltage* compensation
position battery type voltage* (V) voltage* (V) current
(V) factor* (mV/°C)
percentage
PzS tubular 15.1 13.8 16.9 -16
plate traction
5 30.2 27.6 33.8 25% -32
batteries or
OPzS batteries 60.4 55.2 67.6 -64
* The top value is for 12V systems, the middle for 24V systems and the bottom for 48V systems.
** Equalize is by default disabled. To enable see chapter Battery settings [19]
A binary LED code helps determining the position of the rotary switch. After changing the position of the rotary switch, the LEDs
will blink during 4 seconds as indicated in below table. Thereafter, normal indication resumes, as described in the LEDs section.
Switch position Bulk LED Absorption LED Float LED Blinking frequency
0 1 1 1 Fast
1 0 0 1 Slow
2 0 1 0 Slow
3 0 1 1 Slow
4 1 0 0 Slow
5 1 0 1 Slow
6 1 1 0 Slow
7 1 1 1 Slow
Although the MPPT Control can connect to the solar charger, consider using a SmartSolar control display
instead.
Do not change settings unless you know what they are and what the effect of changing these settings will
be. Incorrect settings may cause system problems including damage to batteries. When in doubt, seek advice
from an experienced Victron Energy installer, dealer or distributor.
Battery voltage
The battery voltage is automatically detected at the very first power-up of the solar charger and the battery voltage is set
accordingly. Further automatic detection is disabled. To make sure that a stable measurement is used, the charger first waits 10
seconds, and thereafter takes an averaged measurement. Note that the solar charger will remain off during this time.
In case the solar charger does not measure a battery voltage, it will default to 12V and store that. This will happen if the solar
charger is powered via its PV terminals, while not connected to a battery.
Note that the solar charger will not automatically detect a 36V battery. This will need to be set manually.
After automatic detection has taken place, the battery voltage can be changed and set to 12, 24, 36 or 48V, if so required .
Tip:
If the firmware of the solar charger needs to be updated, while keeping the automatic voltage detection active,
for example before shipping the unit to an end-user, do the following:
• Once the firmware update is complete, go to the settings page in the VictronConnect app.
• On the settings page, click on the three vertical dots in the upper right corner and select "Reset to defaults”
from the drop-down menu.
The next time that the unit is powered up, it will perform the initial automatic voltage detection.
This setting sets the maximum battery charge current. It is by default set to the maximum solar charge current.
Use this setting to reduce the charge current, for example, when a smaller battery bank is used that requires a lower charge
current.
Charger enabled
This setting enables or disables the battery charger. It is by default set to "enabled".
This setting can be used when work needs to be carried out on the installation. When this setting is disabled, the batteries will not
be charged.
Battery preset
This setting sets the battery charge algorithm. It is by default set to "rotary switch".
This setting uses factory pre-defined presets for a large variety of battery types. These pre-defined charge algorithms are suitable
for almost all installations.
It is possible to also create user-defined battery presets. The chapter Customize battery charge algorithm [20] explains how to
do this. These user-defined presets are stored in the VictronConnect app library. This is helpful in case multiple solar chargers
need to be configured, eliminating the need to define the entire charge algorithm each time a new solar charger is configured.
Expert mode
The default charge algorithms work well for almost all installations. Only enable expert settings if your
equipment has special requirements.
For the meaning of these parameters see chapter Battery charge algorithm settings [22].
Equalization
Equalization can cause damage to the battery if the battery is not suitable for an equalization charge. Always
check with the battery manufacturer prior to enabling equalization.
This setting can be used to disable or enable automatic equalization. When enabled, the number of days can be selected when
equalization should repeat.
A manual equalization can be initiated by pressing the "START NOW" button. Use the manual equalize option only during
absorption and float charge stages, and when there is sufficient sunlight. The current and voltage limits are identical to the
automatic equalize function. The manual equalization stage lasts 1 hour and can be stopped at any time by the Stop Equalize.
The equalization setting might not be active, this can be the case if the battery preset does not support an
equalization charge which is the case with lithium batteries.
Only experienced users should configure or edit user defined battery charge algorithms. A wrongly defined
battery charge algorithm can lead to battery damage or create unsafe situations.
• Select a preset battery type that is the best match to your battery type.
• Change one of the basic charge parameters that are listed on the settings screen.
• The basic and additional charge parameters are now listed on the screen.
• Select a preset battery type that is the best match to your battery type.
• Change the charge parameters so they match your battery. This can be done either in normal mode or in expert mode.
• The menu lists all factory preset and custom battery types that were previously added (if any).
• Navigate to the battery you want to modify. It is not possible to modify a factory preset, only custom types can be modified (or
deleted).
• To save the settings press the "SAVE CHANGES" button at the bottom of the page.
Absorption voltage
• When disabled: The length of the absorption stage is the same each day, the length is determined by the "Maximum
absorption time" setting, provided there is enough solar power.
Be aware that this option can potentially result in overcharging your batteries, especially for lead batteries and if only shallow
daily discharges take place. Check with the battery manufacturer for the recommended maximum absorption time.
The only condition that can end the absorption time before the maximum time has been reached, is the "tail current" setting. If
the absorption time always needs to be the same length, then disable the "Tail current" setting. See more information on the tail
current setting further down in this chapter.
• When enabled: The length of the absorption stage is different each day, it adapts itself to the state of charge of the battery in
the morning at the beginning of the charge cycle.
The maximum "adaptive" absorption time for the day is determined by the battery voltage as measured just before the solar
charger begins operation each morning.
This setting sets the absorption time limit. This setting is only available when programming a custom charge profile.
Enter the maximum time in hours and minutes (hh:mm) the solar charger is allowed to spend in the absorption stage. The
maximum time that can be set is 12 hours and 59 minutes.
Float voltage
This setting sets the re-bulk voltage offset. This offset voltage is used to determine when a charge stage stops and the bulk stage
starts again, i.e. the charge cycle resets and starts at the first charge stage again.
The re-bulk voltage is calculated by adding the re-bulk voltage offset to the lowest voltage setting (normally this is the float stage).
An example: If the re-bulk offset is set at 0.1V and the float voltage at 13.8V, the charge cycle will restart once the battery voltage
drops below 13.7V (13.8 minus 0.1) for one minute.
Equalization voltage
This setting sets the percentage of the "maximum charge current" setting that will be used to calculate the equalization charge
current.
For example: If the "maximum charge current" setting is set at 10A and the "Equalization current percentage" setting is set to
10%, the Equalization current will be 1A (10% of 10A).
Automatic equalization
This setting sets the repeat interval when the equalization stage should take place. This can be set between 1 and 250 days.
Setting to 1 means a daily equalization, 2 means every other day and so on.
An equalization stage is typically used to balance the cells and also to prevent stratification of the electrolyte in flooded lead-acid
batteries. If equalization is needed or not depends on the type of battery if (automatic) equalization is needed and under what
conditions. Check with the battery supplier to find out if equalization is needed for the battery.
During the equalization stage, the charge voltage increases up to the set "Equalization voltage". This is maintained as long as the
charge current stays below the "equalization current percentage" setting of the "Maximum current" setting.
• For all VRLA battery presets and for some flooded battery presets, the automatic equalization stage ends when the voltage limit
(maxV) has been reached.
• When an automatic equalization stage has not been completed within one day, it will not resume the next day. The next
equalization surge will take place according to the interval as set in the "Auto Equalization" setting.
• Automatic: Equalization stops if the battery voltage has reached the equalisation voltage.
• Fixed time: Equalization stops when the time has reached the time as set in the "Maximum equalization duration" setting.
This setting sets the maximum time that the equalization stage will last.
Manual equalization
Use this to perform a "once-off" equalization. Once the "start now" button is pressed, a one-hour equalization cycle will be
performed, alternatively, the equalization stage can be stopped manually.
Tail current
This setting sets the current threshold to end the absorption stage before the maximum absorption time has been reached. If the
charge current drops below the set tail current, for one minute, the absorption stage will end and the float stage will start. This
setting can be disabled by setting it to zero.
Temperature compensation
This setting sets the temperature compensation coefficient that is needed for temperature compensated charging.
Many battery types require a lower charge voltage in warm operating conditions and a higher charge voltage in cold operating
conditions. The configured coefficient is in mV per degree Celsius for the whole battery bank, not per cell. The base temperature
for the compensation is 25°C (77°F).
The chart below indicates the absorption and float charge voltage behaviour at different temperatures. The graph displays the
temperature compensation for a 12V system and uses a -16mV/°C temperature compensation coefficient. For a 48V system
multiply by 4.
By default, the solar charger uses its internal temperature for battery temperature compensated charging. An internal temperature
reading is taken in the morning and then again when the e solar charger has been idle for at least one hour, for example when the
charger is not actively charging a battery or supplying a load.
When the solar charger is part of VE.Smart Networking and receives a battery temperature reading from a Battery Sense or a
battery monitor with a temperature sensor, the actual battery temperature will be used for temperature compensated charging
throughout the day.
This setting is used to prevent damage to a lithium battery by disabling charging at low temperatures.
The "Low temperature cut-off" feature is only active when the solar charger is part of a VE.Smart network and
is receiving a battery temperature reading from a Battery Sense or a battery monitor with temperature sensor.
The "low temperature cut-off" setting is by default disabled. When enabled, a low cut off temperature can be set. The default
temperature is 5°C, this is a suitable temperature setting for lithium iron phosphate (LFP) batteries. However, always check with
the lithium battery supplier to find out what this temperature should be set at.
The "low temperature cut-off" mechanism will stop battery charging when the battery temperature has dropped below the low
temperature cut-off setting. Battery charging will resume once the battery temperature has risen 0.5°C above the low temperature
cut-off setting.
Note that setting "low temperature cut-off" is not needed for Victron Lithium Smart batteries or for Victron Super Pack batteries
with serial number HQ2040 and above. This setting is only needed for lithim batteries that are unable to block charging when the
temperature drops too low.
• Conventional algorithm 1:
12V system: OFF when Vbatt < 11.1V, ON when Vbatt > 13.1V.
24V system: OFF when Vbatt < 22.2V, ON when Vbatt > 26.2V.
48V system: OFF when Vbatt < 44.4V, ON when Vbatt > 52.4V.
• Conventional algorithm 2:
12V system: OFF when Vbatt < 11.8V, ON when Vbatt > 14.0V.
24V system: OFF when Vbatt < 23.6V, ON when Vbatt > 28.0V.
48V system: OFF when Vbatt < 47.4V, ON when Vbatt > 56.0V.
• Always off:
The load output is always OFF.
• Always on:
The load output is always ON.
The "always off" and the "always on" modes will respond immediately. The other modes have a 2-minute delay before the load
output changes. This is so that the solar charger does not respond too quickly when, for example, an inrush current briefly lowers
the battery voltage below the threshold.
The load output settings also control the streetlight [27] algorithm. Both work together to protect the battery from being too
deeply drained. The streetlight settings are overridden should the battery voltage falls below the load disconnect voltage. When
the battery voltage increases to the load reconnect voltage, the streetlight function will resume.
• NO (Normally Open)
• C (Common)
• NC (Normally Closed)
The switching conditions must be present for at least 10 seconds before the relay will change position.
Setting Description
Minimum closed Set by default setting to 0 minutes and is customizable. The minimum-time can be set for the ON
time condition to prevail once the relay has been switched ON.
An example where a minimum closed time is usefull, is to set a minimum generator run-time.
When the streetlight function is enabled a timer program can be created whereby Sunset, Sunrise as well as Midnight can be
used as anchor points for the timer program. These anchor points will automatically adjust depending on length of the night as
this changes with the seasons.
Streetlight control
• Via the TX port together with a VE.Direct TX digital output cable. Also see the TX port settings [30] chapter for more details.
• Via the programmable relay. Also see the Programmable relay settings [25] chapter for details.
The streetlight algorithm is always applied in conjunction with the settings as configured in the Load output
menu:
• If the streetlight is disabled, then the (virtual) load output is controlled only by the configuration as made in
the load output menu.
• If streetlight is enabled, then it's an AND function: the load output will be on when both the conditions made
in the Load output menu are satisfied as well as the streetlight settings. Otherwise, it's off.
Make sure that load output setting is set to "Always on" or to "BatteryLife". Do not set it to "Always off" as this
will result in the light being always off.
For more configurable voltage levels to force the light off, the other load output options can also be used.
• Switch off:
Turns the light off at sunrise.
Midnight
The charger has no real time clock, and therefore does not know when it is 12 o'clock at night. All references to midnight refer to
what we call solar midnight, this is the mid-point between sunset and sunrise.
The solar charger needs to have its internal clock synchronised with the solar cycle so it can set the solar midnight and sunrise
anchor points in the timer program.
After the streetlight settings have been programmed and the solar charger is powered up, the solar charger will start
unsynchronised. It will first assume that midnight is 6 hours after sunset, and that the full night last for 12 hours.
Once in operation, the solar charger will check the time between each detected sunrise. After three full day/night cycles, where
the detected time is approximately 24 hours (one hour of deviation is allowed), it will start using its internal clock, instead of the
fixed 6 and 12 hour timing.
A loss of power (no battery power together with no PV power) will cause the solar charger to loose its
synchronisation. It will take 5 days before it is re-synchronised. Note that the streetlight configuration settings
and all other settings will never be lost, they are stored in a non-volatile memory.
The sunset and sunrise detection voltage settings can be used to adjust the detection to match the panel configuration. The
sunrise detection voltage must be 0.5V higher than the sunset detection level. The lowest detectable voltage is 11.4V. Set this
option to 0 to use the built-in defaults, which are:
Use the "Delay" periods to avoid the system making an accidental switch when clouds pass over the panels. The valid range is
between 0 and 60 minutes. The "Delays" are disabled by default (0).
The gradual dimming option can be used to slow down the response of the timer program. This is useful when multiple
streetlights are used in a row. This helps to mask the fact that each timer uses its own detection and will have a transition moment
which will vary from unit to unit.
The dimming settings can be adjusted. You can input the number of seconds required to achieve each percentage-point of
change (x seconds/per 1% of dimming). A number from 0 to 100 can be entered. Two examples:
Make sure that the TX port function is set to "Light dimming" mode (as described in point 1 at the beginning of
this chapter) and connect a VE.Direct TX digital output cable to the PWM dim input of your LED driver.
Mid-point shift
The time of midnight is estimated based on solar activity, and depends on your geographical location. Daylight saving times can
cause a further deviation between the "solar" and the "clock" midnight. The Mid-point shift function will compensate for these
differences. Use 0 to disable the shift (default).
The Mid-point shift setting is only relevant when your streetlight setting program uses "Midnight" as a
switching moment.
Calculation Example:
For calculation we use a day of 1440 minutes, where Sunset is at 19:00 (1140 minutes) and Sunrise is at 6:25 (385 minutes):
• The night duration in minutes is: 1440m(min/day) -1140m(time to sunset) + 385m(time to sunrise) = 685m.
• The degree of shift = time of sunset(minutes) + half the duration of night(minutes) - length of day(minutes) = 1140m + 342m - 1440m =
42 minutes.
Example configuration
The selections which have been made on above screen image results in this program:
• Dim level at end - at the end of one hour the brilliance will be reduced to half (50%).
Also:
• Time before sunrise - at 1h 0m before sunrise, the following adjustment will be made:
• Normal communication:
This is the default setting. Use this function when connecting to a GX device, a VE.Direct Bluetooth Smart dongle, or any other
device that needs to communicate with the solar charger via the VE.Direct port.
**) The TX port is a logic 5V signal. It can drive a maximum of a 22kOhm impedance load, where the output voltage is dropped to
3.3V. Make sure that the connected load is within this specification.
Note that these functionalities (other than the first functionality) do not disable the ability of the unit to communicate. What
happens is that the unit will automatically detect incoming data, and while data is being received, it will resume normal
communication. Once the data reception has been completed, it will automatically return to its configured TX function.
For more in-depth "developer style" information on the VE.Direct port see the Data communication with Victron Energy products
document.
To use the RX port for remote on/off control a VE.Direct non inverting remote on/off cable is needed.
• Remote on/off:
This is the default setting. This functionality will switch the solar charger on or off via the RX pin.
- RX pin to GND will switch the solar charger off.
- RX pin floating or to battery positive will switch the solar charger on.
For more in depth "developer style" information on the VE.Direct port see the Data communication with Victron Energy products
Whitepaper.
The VictronConnect app might ask on the first connection to update the firmware. If this is the case, let it perform a firmware
update.
If it did not automatically update, check if the firmware is already up to date using the following procedure:
• Go to product info.
• Check if you are running the latest firmware and look for the text: “This is the latest version”.
• If the solar charger does not have the most up-to-date firmware, perform a firmware update.
• Connect with the VictronConnect app to the solar charger. Note that if Bluetooth has been disabled, a connection via its built-in
Bluetooth is not possible anymore. In that case use the VE.Direct to USB interface, the VE.Direct Bluetooth Smart dongle or
VRM to connect to the solar charger.
• Navigate to the solar charger settings page by clicking the cog symbol in the top right hand corner.
• Navigate to the product info page by clicking on the 3 dot symbol in the top right hand corner.
• In case of disabling Bluetooth, tick the checkbox confirming you understand that once Bluetooth has been disabled, a Bluetooth
connection with the solar charger is not possible anymore.
VE.Smart Networking allows a variety of products connected to the same network to share data via Bluetooth and is specially
designed for smaller systems that do not have a GX device installed.
When this product is part of a VE.Smart Network, it can receive data or communicate with the following devices:
• A BMV or SmartShunt battery monitor equipped with Bluetooth (or VE.Direct Bluetooth Smart dongle) and an optional BMV
temperature sensor.
For the product compatibility list see the VE.Smart manual located on the VictronConnect app product page.
• Temperature sensing - the measured battery temperature is used by the chargers in the network for temperature compensated
charging and in case of lithium battery for the low temperature cut off.
• Battery voltage sensing - the measured battery voltage is used by the chargers in the network to to compensate the charge
voltage should there be a voltage drop over the battery cables.
• Current sensing - The measured battery current is used by the charger so it knows the exact tail current at which the absorption
stage should end and the float (or equalisation) stage should start. To measure the charge current all charge currents from all
chargers are combined, or if a battery monitor is part of the network the actual battery current will be used.
• Synchronised charging - All chargers in the network will act as they were one large charger. One of the chargers in the network
will assume a master role and the master will dictate the charge algorithm the other chargers will be using. All chargers will
follow the same charge algorithm and charge stages. The master is selected randomly (not user settable) so it is important
that all chargers use the same charge settings. During synchronised charging each charger will charge up to its own maximum
charge current setting (it is not possible to set a maximum current for the whole network). For more information see the
VE.Smart manual located on the VictronConnect app product page.
This video introduces the Smart Battery Sense and some features of VE.Smart Networking:
https://www.youtube.com/embed/v62wCfXaWXY
There can only be one product in the network that transmits battery voltage and/or battery temperature. It is not possible to use a
battery monitor together with a Smart Battery Sense, or multiple of these devices.
For the network to be operational all networked devices must be within Bluetooth transmission distance of each other.
Some older devices might not support VE.Smart Networking. for more information see the Limitations chapter in the VE.Smart
Networking manual.
When setting up the network, first set up the Smart Battery Sense or battery monitor, and then add one or more solar chargers or
AC chargers to the network.
All solar chargers and AC chargers need to have the same charge settings. The easiest way to do this is to use a preset battery
type or a saved used defined battery type. A warning #66 message will be shown if there is a difference between the devices
charge settings.
• Select one of the devices that needs to become part of the new VE.Smart network.
• Click "save".
• Wait for confirmation that the network has been set up and click "OK".
• If more devices need to be added to this network go to next paragraph and join multiple devices to the network.
• Open the VictronConnect app. Select a device that needs to become part of a VE.Direct network.
• Wait for confirmation that the network has been set up and click "OK".
To leave a network:
Once the network has been set up all devices communicate with each other. The active LED on each connected device will now
blink every 4 seconds. This is an indication that the device is actively communicating with the network.
To check if an individual device is communicating with the network, click on the VE.Smart symbol in the main screen next to
the solar dail. A pop-up window will open showing the connection status and the shared parameters.
To check if all devices are actively communicating with the same VE.Smart Networking, navigate to the settings page of one of
the networked devices and click on "VE.Smart Networking". A screen will be shown containing which device parameters of this
device are shared and all the other devices that are connected to the same network are shown.
More information
6. Operation
6.1. Start up
The solar charger will power up as soon as it has been connected to a battery and/or to a solar panel. As soon as the solar
charger has been powered up, it can communicate via the VE.Direct port and Bluetooth. The solar charger's data can be read out
and setting configurations can be made using the VictronConnect or the optional display.
The solar charger will commence battery charging as soon as the PV voltage is 5V higher than the battery voltage. For charging
to continue, the PV voltage must remain at least 1V higher than the battery voltage.
Default method to determine length and end of absorption for Lead-acid batteries
The charging algorithm behaviour of solar chargers differ from AC connected battery chargers. Please read this section of
the manual carefully to understand the solar charging behaviour, and always follow the recommendations of your battery
manufacturer.
The voltage values mentioned in this chapter are for 12V systems, for 24V systems multiply by 2 and for 48V
systems multiply by 4.
By default, the absorption time is determined on idle battery voltage at the start of each day based on the following table:
The default absorption voltage is 14.4V and the default float voltage is 13.8V.
The absorption time counter starts once switched from bulk to absorption.
The MPPT solar chargers will also end absorption and switch to float when the battery current drops below a low current
threshold limit, the "tail current". The default tail current value is 2A.
The default settings (voltages, absorption time multiplier and tail current) can be modified with the VictronConnect app.
• When used in an ESS system; the solar charger algorithm is disabled; and instead it follows the curve as mandated by the
inverter/charger.
• For CAN-bus Lithium batteries, like BYD, the battery tells the system, including the solar charger, what charge voltage to use.
This Charge Voltage Limit (CVL) is for some batteries even dynamic; changes over time; based on for example maximum cell
voltage in the pack and other parameters.
Page 37 Operation
MPPT solar charger manual
the solar charge controller. Be aware this can result in overcharging your batteries. Please see your battery manufacturer for
recommended settings.
The default absorption voltage is to 14.2V (28.4V, 56.8V) and the absorption time is fixed and set to 2 hours. The float voltage
is set at 13.5V (27V, 54V). Equalization is disabled. The tail current is set to 0A, this so that the full absorption time is available
for cell balancing. The temperature compensation is disabled and the low temperature cut off is set to 5. These settings are
the recommended settings for LiFePO4 batteries, but they can be adjusted if the battery manufacturer specifications advise
otherwise.
The default setting for restarting the charge cycle is Vbat < (Vfloat – 0.4 V) for lead-acid, and Vbat (Vfloat – 0.1 V) for LiFePO4
batteries, during 1 minute. These values are for 12 V batteries, multiply by two for 24V and by four for 48V.
Equalization can cause damage to the battery if the battery is not suitable for an equalization charge. Always
check with the battery manufacturer prior to enabling equalization.
Automatic equalization is by default disabled. When enabled, it can be configured with a number between 1 (every day) and 250
(once every 250 days).
When automatic equalization is active, the absorption charge will be followed by a voltage limited constant current period. The
current is by default limited to 8% of the bulk current and can be adjusted between 0% and 100%. The bulk current is set by
default to the maximum charge current the solar charger is capable of, unless a lower charge current has been chosen.
The maximum equalization duration is set by default to 1 hour and can be configured between 0 minutes and 24 hours. The
automatic equalization will end when the voltage limit has been reached or when the set maximum equalization duration has been
reached, whichever comes first.
When automatic equalization has not finished within a day, it will not resume the next day. The next equalization session will take
place as determined by the day interval.
To shut down the solar charger, perform these steps in the prescribed order:
1. Disconnect the PV supply to the solar charger by switching the PV supply off or by removing the external fuse(s) or circuit
breaker(s).
2. Disconnect the battery supply to the solar charger by switching the battery supply off or by removing the exterenal fuse(s) or
circuit breaker(s).
To restart the solar charger after it was shutdown, perform these steps in the prescribed order:
1. Connect the battery supply to the solar charger by switching the battery supply on or by inserting the external fuse(s) or
circuit breaker(s).
Page 38 Operation
MPPT solar charger manual
2. Reconnect the PV supply to the solar charger by switching the PV supply on or by inserting the external fuse(s) or circuit
breakers(s).
Page 39 Operation
MPPT solar charger manual
7. Monitoring
This chapter describes all various monitoring methods and for each method how to access live data, historic data and errors.
Errors are indicated via a combination of LEDs that are on, off, or are blinking. Each LED combination has a meaning, indicating
either a normal operation mode, or indicating an error.
Symbol Meaning
Permanent on
Blinking
Off
Not charging 1
Bulk1
Absorption2
Automatic equalisation2
Float2
1. The bulk LED will blink briefly every 3 seconds when the system is powered but there is insufficient power to start charging.
2. The LED(s) might blink every 4 seconds indicating that the charger is receiving data from another device, this can be a GX
device (ESS) or a VE.Smart Network link via Bluetooth
Charger over-current
For the latest and most up-to-date information about the LED blink codes, refer to the Victron Toolkit app. The app is available for
Apple and Android. The app can be downloaded from the respective app stores or alternatively follow the download links on our
software downloads page.
Page 40 Monitoring
MPPT solar charger manual
For the meaning of blinking LED codes, see the previous chapter or the Victron Toolkit app.
For a full list of error codes and their meaning see the Error code overview chapter.
This chapter explains the solar charger-specific VictronConnect app usage. Refer to the general VictronConnect app manual for
information about the VictronConnect app itself, such as: how to install the app, how to connect to the solar charger, how to
update firmware and more.
To arrive at values for 24V, 36V or 48V batteries, multiply the 12V values by a factor of 2, 3 or 4 respectively.
VE Smart Networking
• The presence of the VE.Smart Networking symbol indicates that the solar charger is configured for VE.Smart Networking
and is receiving battery temperature and/or battery voltage data from the VE.Smart Network.
Solar
• The solar gauge shows the solar output in relation to the maximum output power that the solar charger can generate at the set
battery voltage and displays the dynamic real-time value of the solar array output power.
• The solar voltage measured at the solar terminals of the solar charger.
• The solar current flowing from the PV array into the solar charger.
Battery
Page 41 Monitoring
MPPT solar charger manual
• The battery voltage measured at the battery terminals of the solar charger.
• The current flowing from the solar charger into the battery.
• The battery state indicates the battery charge stage or if external control is active. These are the possible states:
Bulk
During this stage the solar charger delivers as much charge current as possible to rapidly charge the batteries. When the
battery voltage reaches the absorption voltage setting, the solar charger activates the absorption stage.
Absorption
During this stage the solar charger switches to the constant voltage mode, where a pre-set absorption voltage is applied. When
the charge current decreases below 2A or if the pre-set absorption time has elapsed, the battery is fully charged and the solar
charger will enter the Float stage. Note that when an automatic equalisation is being performed this will also be reported as
absorption.
Float
During this stage the float voltage is applied to the battery to maintain a fully-charged state. When the battery voltage drops
below float voltage during at least 1 minute, a new charge cycle will be triggered.
External control
This will be displayed when another device is controlling the charge behaviour of the solar charger, bypassing its normal charge
algorithm. Examples are when the solar charger is controlled by an ESS system or a managed battery.
• In case the charger is not charging a "Why is the charger off?" message will display. When clicking on this message, a new
window will open with more information as to why the solar charger is not charging.
• The state of the virtual load output, being switched on or switched off.
Relay
To switch between portrait or landscape screen presentation click the fragmented square icon, or , at the top left of the
screen.
• Solar Pmax: The maximum power (W) recorded during the day.
• Solar Vmax: The highest voltage (V) from the PV array during the day.
Page 42 Monitoring
MPPT solar charger manual
• Battery max and min: The first figure shows the maximum battery voltage (Vmax) for the day. The figure below is the minimum
battery voltage(Vmin) for the day.
• Errors: This shows the daily number of errors, if any. To get more information about the error(s), click the orange dot. You may
need to slide the display on your device up to see the errors.)
• Lifetime total: This shows the total energy converted by the installation (W and is not re-settable).
• Since reset: This shows how much energy has been converted by the installation since the last reset.
Clicking on any bar (day) in the graph will expand the information. It will show the time and percentage of the total charge time
that the solar charger has spent in each Bulk, Absorption and Float charge stage.
You can use the charge times to see if the PV array is properly sized for your requirements. A system that
never reaches the float stage may need more panels. Or perhaps the load should be reduced?
The history can be exported as a comma-separated file (CSV) by clicking the three connected dots symbol or the save symbol
at the top right of the history screen. The symbol varies, depending on what platform VictronConnect is used.
The history can be reset by clicking the clock with an arrow symbol at the top right of the history screen.
The VictronConnect app also displays historical errors. To see these errors, navigate to the “History” tab and look at the bottom of
each day column. An orange dot will indicate an error on that day.
If the GX device is connected to Victron Remote Monitoring (VRM) portal, the solar charger can be monitored remotely via the
internet.
Page 43 Monitoring
MPPT solar charger manual
All solar charger data, alarms and errors can be accessed via the VRM portal and solar charger settings can be remotely
changed via the VRM portal with the VictronConnect app.
Page 44 Monitoring
MPPT solar charger manual
8. Troubleshooting
Refer to this chapter for addressing any unforeseen behaviour of the solar charger. Start by reviewing the common issues listed
here during troubleshooting.
If the problem persists or requires technical assistance, contact the point of purchase – the Victron Energy dealer or distributor. If
unsure whom to reach or unaware of the point of purchase, visit the Victron Energy Support webpage for guidance.
By conducting this initial visual inspection, you can identify any visible damage that may impact the functionality of the solar
charger:
Visual inspection
Examine the solar charger for any signs of mechanical damage to the housing or electrical terminals. Please be
Step 1
aware that this type of damage is not covered by warranty.
Inspect the electrical terminals of the solar charger for signs of burning or melting. This type of damage is often
caused by loose electrical connections, the use of rigid core cables, or exceeding the MC4 terminal current
Step 2
ratings. Please be aware that this damage is not covered by warranty. Refer to chapter PV connections burned
or melted [59] for more information.
Look for any indications of water damage or corrosion on the solar charger, especially around the electrical
Step 3
connection area. It is important to note that such damage is not covered by warranty.
Conversely, if the solar charger is active, you will notice its LEDs are either illuminated or blinking, and it can successfully
communicate with the VictronConnect app via Bluetooth or the VE.Direct port.
The solar charger should activate as soon it receives power from the battery, the PV supply, or both. Note that the solar charger
does not have an on/off switch.
To troubleshoot, verify that the solar charger is receiving either battery or PV power, using the below procedure.
• Measure the voltage between the positive and negative PV terminals of the solar charger.
Step 2
WARNING: Certain solar charger models may have PV voltages up to 250Vdc. Voltages
exceeding 50V are generally considered dangerous. Only a qualified technician should
handle dangerous voltages.
Page 45 Troubleshooting
MPPT solar charger manual
• Inspect the fuses and circuit breakers in the battery and PV supply cables.
• Verify if the battery voltage is sufficiently high. If not, charge the battery using an auxiliary charger.
• Confirm if the PV voltage is sufficiently high. Check for any issues with the PV array, such as wiring mistakes,
damaged panels, cloudy weather, nighttime conditions, etc.
If, even after confirming sufficient battery or PV voltage, the solar charger remains unresponsive, consider the
Step 4
solar charger to be faulty.
• The settings are being edited on an external display. Refer to the Settings being edited on an external display [47] subchapter.
• The charger is disabled in the settings. Refer to the Disabled in the settings [48] subchapter.
• The charger is disabled by remote or BMS. Refer to the Disabled by remote or BMS [48] subchapter.
• Low lithium battery temperature. Refer to the Low lithium battery temperature [48] subchapter.
To troubleshoot if a low PV voltage is the reason the solar charger is not charging, use the below procedure.
Page 46 Troubleshooting
MPPT solar charger manual
Step 1
If the above step is impossible, use a multimeter in DC mode to measure the battery and PV voltages at the
solar charger terminals.
Step 2
WARNING: Certain solar charger models may have PV voltages up to 250Vdc. Voltages
exceeding 50V are generally considered dangerous. Only a qualified technician should
handle dangerous voltages.
Compare both voltages. Remember that the PV voltage needs to be 5V higher than the battery voltage for
Step 3
charging to commence.
• There is shade from nearby objects. See this shading blog story for more information.
• There are issues with a solar panel or the solar panel wiring:
• There is a mechanical or electrical issue with an individual panel (or multiple panels).
• Wiring problems, like loose wires, loose connections or incorrect crimped MC4 connectors.
• Blown fuses.
• Reverse PV polarity:
• The positive and negative PV wires have been mistakenly swapped when connected to the solar charger. For more
information, see the Reverse battery polarity [51] chapter.
Page 47 Troubleshooting
MPPT solar charger manual
Once the settings menu is closed on the display, charging will resume.
Check the VictronConnect app battery settings page to ensure that the charger has been enabled.
Note that in systems with lithium batteries together with an external BMS, it is typical for the solar charger to be switched on or
off as needed. This happens when the BMS turns off the charger due to full batteries or low temperatures (below ~5°C). Charging
automatically resumes when the batteries are discharged or have warmed up.
If the solar charger has unexpectedly been switched off, check the following:
Verify that the wire loop is making electrical contact with the connector
Step 3
block.
Remote connector with the wire
loop.
Take note of the various methods the solar charger can be activated via the remote terminal:
• ON when the L and H terminals are interconnected via a switch or a relay contact.
Step 4
• ON when the L terminal is pulled to battery minus (VL< 3.5V).
If this protection is triggered unnecessarily, please reach out to your installer to adjust the related settings.
Page 48 Troubleshooting
MPPT solar charger manual
When external control is active, it is visible on both the VictronConnect app and the GX device. This is normal behaviour and is
not a fault.
• Reverse PV polarity. Refer to the Reverse PV polarity [52] subchapter for more details.
• PV voltage is too high. Refer to the PV voltage too high [52] subchapter for more details.
• Reverse battery polarity. Refer to the Reverse battery polarity [51] subchapter for more details.
• The solar charger is disconnected from the battery, possibly due to cable, fuse, or circuit breaker issues. Refer to the Battery
not connected [50] subchapter for more details.
• Incorrect charger configuration, e.g., low charge voltage or current setting. Refer to the Battery settings too low [51]
subchapter for more details.
• The charger is externally controlled (ESS or DVCC), which is normal and not a fault. Refer to the Solar charger externally
controlled chapter for more details.
• The temperature-compensated charging feature is active, and the battery temperature is too high, or the feature is
misconfigured. Refer to the Wrong temperature compensation setting chapter for more details.
Page 49 Troubleshooting
MPPT solar charger manual
To determine the battery's state of charge (SoC), check the battery monitor (if available) or inspect the charge stage indicated by
the solar charger. During the daily charge cycle, the solar cycle progresses through the following stages:
Be aware that the solar charger may detect the battery as fully charged when it's not. This happens if the charge voltages are set
too low, causing the charger to switch from absorption to float stage prematurely. Refer to the Battery settings too low chapter.
Be aware that that if the solar charger operates without a battery, it may seem connected, showing battery voltage and charge
stage in the VictronConnect app, but the charge current will be negligible or zero.
Step 1
Step 2
Page 50 Troubleshooting
MPPT solar charger manual
• Inspect the cable connections for tightness while keeping the maximum torque levels in mind.
Should you come across a blown fuse, make sure to check the correct wiring of the battery
polarity before replacing it. Refer to the Reverse battery polarity [51] chapter.
Be aware that a red or positively labelled cable may not necessarily indicate the cable is positive. A wiring or
labelling mistake during the solar charger installation is possible.
Always double-check the battery polarity before reconnecting the battery wires to the solar charger.
Reverse battery polarity can potentially damage the solar charger, causing its internal fuse to blow for fail-safe protection. This
fuse might blow before the external fuse in the battery cable. However, please note that the internal fuse is situated in a
non-serviceable area, and it cannot be replaced or repaired. If this happens, the solar charger should be considered faulty.
The solar charger is not protected against reverse battery polarity, and any resulting damage is not covered under warranty.
• Setting the ''Absorption voltage" and "Float voltage" parameters too low.
• Setting the "Max charge current" parameter to zero or an excessively low value.
Page 51 Troubleshooting
MPPT solar charger manual
VictronConnect app, showing battery (system) voltage, charge current and charge voltages settings.
Should the PV voltage exceed the maximum rated PV voltage, the solar charger will cease charging, showing an overvoltage
error #33 with rapid blinking of the absorption and float LEDs. Charging resumes only when the PV voltage drops 5V below the
rated maximum voltage.
During investigations into high voltage issues, it's essential to review the VictronConnect app, solar charger display, or GX device
history. Check for the highest PV voltage recorded each day (Vmax) and past overvoltage warnings.
To avoid issues, check the open circuit voltage (Voc) rating of the PV array and ensure it is lower than the solar charger's
maximum rated voltage. Use the MPPT sizing calculator on the solar charger product page. For PV arrays in cold climates or with
night temperatures nearing or below 10°C, it's essential to consider possible increased output (more than its rated Voc). As a rule
of thumb, maintain an additional 10% safety margin.
VictronConnect app error #33 indication on the status screen and history screen.
Page 52 Troubleshooting
MPPT solar charger manual
To verify, use a multimeter to ensure that the positive PV cable is correctly connected to the positive PV terminal and the negative
cable is connected to the negative PV terminal.
WARNING: Certain solar charger models may have PV voltages up to 250Vdc. Voltages exceeding 50V are
generally considered dangerous. Only a qualified technician should handle dangerous voltages.
• Voltage drop in battery cables. Refer to the Battery cable voltage drop [54] subchapter.
• Incorrect temperature compensation setting. Refer to the Temperature compensation setting incorrect [55] subchapter.
• Temperature difference between the solar charger and battery. Refer to the Temperature difference between solar charger and
battery [55] subchapter.
• Battery charge voltages or current settings are too low. Refer to the Battery settings too low [51] chapter.
To investigate, check if the solar charger reaches the float charge stage each day. Utilise the VictronConnect app's history tab,
where a histogram displays the daily charging durations in the Bulk, Absorption, and Float stages for the last 30 days. Clicking on
a histogram column provides a breakdown of the charge stages.
You can use the charge times to assess whether the PV array is appropriately sized for your needs.
Reasons for the solar charger not reaching the float stage include:
• An inadequate number of solar panels.
• Excessive DC load.
Page 53 Troubleshooting
MPPT solar charger manual
• Solar charger is unable to reach full output. Refer to the Solar charger not achieving full output [57] chapter.
Please note that this information does not apply to an ESS system. An ESS system will continuously be in the bulk charge stage
while connected to the grid.
Left: Example of a system that is spending all its time in the bulk stage. Right: Breakdown of the charge stages - The system
spends time in bulk and in the absorption stage.
Battery charging occurs only when the power generated by the PV panels exceeds the power consumed by the system's DC
loads.
• Use a current clamp and compare the current flowing from the solar charger into the battery and the current flowing from the
battery into the DC system.
• A positive sign alongside the current reading indicates current flowing into the battery, whereas a negative sign suggests
current being drawn from the battery.
For more information on cabling issues and voltage drop, refer to the Wiring Unlimited Book.
Page 54 Troubleshooting
MPPT solar charger manual
Step 2
Measure the battery voltage on the terminals of the battery using a multimeter.
Step 3
VE.Smart Networking can assist in mitigating a small cable voltage drop. However, for a substantial voltage drop, there may be
an issue with the wiring between the solar charger and the battery, which requires rectification before proceeding.
In a VE.Smart Network a Smart Battery Sense or battery monitor measures the battery terminal voltage and transmits this via
VE.Smart Networking to the solar charger. If the battery voltage is less than the solar charge voltage, the solar charger will
increase its charge voltage to compensate for (small) voltage losses.
To determine the correct temperature compensation coefficient for your battery, consult the battery documentation. If uncertain,
use the default value of -64.80mV/°C for lead-acid batteries, and for lithium batteries, disable the temperature compensation
setting.
Note that this chapter does not apply if the solar charger is connected to a VE.Smart Network with a battery
temperature measurement or is equipped with a temperature sensor.
At the beginning of the day, as soon as power is generated by the solar array, the solar charger will measure the ambient
temperature and use it to temperature-compensate the charge voltage.
During the float stage, the solar charger will re-measure the ambient temperature and adjust the voltages accordingly.
Large differences in ambient temperature between the solar charger and the battery can lead to improper charging voltages for
the battery.
For instance, if the solar charger is placed near a sunlit window while the batteries are located on a cold concrete floor in the
shade, this temperature discrepancy can affect the charging process.
To ensure optimal performance, always ensure that the ambient conditions are equal for both the solar charger and the battery.
Page 55 Troubleshooting
MPPT solar charger manual
Overcharging batteries can lead to severe battery damage and may be caused by the following factors:
• Incorrect charge voltage settings. Refer to the Battery charge voltage settings too high [56] subchapter.
• Battery voltage setting too high. Refer to the Battery voltage setting too high [56] subchapter.
• Applying equalisation while the battery is not suitable for it. Refer to the Battery unable to deal with equalisation [56]
subchapter.
• The battery is too small, old, has been mistreated in the past or is faulty. Refer to the Battery old, faulty or undersized [56]
subchapter.
The solar charger automatically detects the battery voltage on the first install, and afterwards, the self-detection is disabled.
However, if the solar charger is moved from a 24V system to a 12V system, it may not recognise the system change.
Consequently, it will continue charging with 24V battery charge voltages, while the connected battery is a 12V battery, leading to
overcharging of the 12V battery.
To verify the "battery voltage" setting, use the VictronConnect app or a connected display. If the setting is incorrect, make sure to
adjust it to the correct battery voltage.
Verify that all the battery charge voltages (absorption and float) are correctly configured to match the recommended voltages
specified in the battery manufacturer's documentation.
It's essential to note that not all batteries can handle equalisation voltages. Check with the battery manufacturer to determine if
the battery you are using requires a periodic equalising charge.
In general, sealed batteries and lithium batteries do not require equalisation and should not undergo the equalisation process.
A battery is comprised of multiple cells connected in series. In the case of an old or damaged battery, it's possible that one of
these cells is no longer operational. During charging, the faulty cells will not accept charge, and the remaining cells will receive
the broken cell's charge voltage, resulting in overcharging.
To address this issue, replace the battery. If the system includes multiple batteries, it's recommended to replace the entire battery
bank rather than mixing batteries of different ages in one bank.
Determining the exact history of a battery during its lifetime can be challenging. The solar charger retains 30 days of battery
voltage history. If the system has a battery monitor or is connected to the VRM portal, the battery voltages and cycle history can
be accessed to assess the battery's overall health and whether it is nearing the end of its service life or has been misused.
Similar issues can arise if the battery is too small and charged with a significantly high current. The small battery will not be able
to accept the total charge and will end up being overcharged.
Page 56 Troubleshooting
MPPT solar charger manual
Check if the battery has been charged with a too-high voltage. A very
high charge voltage can damage the battery. Review the maximum
Step 5 battery voltage and the high voltage alarms. Verify that the measured
maximum voltage has not exceeded the battery manufacturer's
recommendations.
VictronConnect app showing
battery monitor history
Reasons for the solar charger not reaching its full output:
• The PV array is too small. If the PV array's power rating is less than the solar charger's nominal power rating, the solar charger
cannot output more power than the connected solar array can provide.
• The PV array is not reaching its maximum power rating. Refer to the PV yield lower than expected [57] subchapter.
• The PV array is a mix of different PV panel types or models. Only use solar panels that are of the same brand, type and model.
• Do not use optimisers. Nearly all optimisers contain an MPPT or other tracking mechanisms, which will interfere with the MPPT
algorithm in the solar charger.
• The PV array is wrongly configured. For a detailed explanation of how to configure PV arrays and properly use MC4 splitters
and MC4 combiners, see the "Solar panel" chapter in the Wiring Unlimited Book.
• The solar charger's maximum PV output power is related to the battery voltage. Refer to the Maximum output power relates to
battery voltage [58] subchapter.
• The solar charger's PV electric connections are burned or melted, or MC4 connectors have been insufficiently crimped. Refer to
the PV connections burned or melted [59] subchapter.
• The solar charger temperature is above 40°C. Refer to the Temperature above 40°C [59] subchapter.
• The batteries are either full or nearly full, causing no further power to flow into them.
• There may be an issue with the battery. Refer to the Batteries are not charged [49] and Batteries are undercharged [53]
chapters.
To determine the potential solar yield per day for a specific PV array size in a particular geographical location, utilise the MPPT
sizing calculator on the solar charger product page.
List of reasons why the PV array may generate less power than expected:
• Low sun angle (morning or evening) or seasonal differences.
Page 57 Troubleshooting
MPPT solar charger manual
• Issues with wiring, fuses, circuit breakers, or there is a cable voltage drop.
For instance:
In a 75/15 solar charger with a 15A output current rating, the power going into the battery will differ for a 12V battery and a 24V
battery.
Thus, even though a 360W panel is connected to the solar charger, the output power into a 12V battery will be less than when
connected to a 24V battery.
Page 58 Troubleshooting
MPPT solar charger manual
For efficient performance, consider the solar charger's mounting arrangement. Mount it vertically with terminals facing downwards
to dissipate heat effectively. In closed enclosures, like cabinets, ensure proper airflow with mounted vents to allow cold air in
and hot air out. In extremely high-temperature environments, mechanical air extraction or air conditioning may be necessary to
maintain optimal performance.
• Using thin cables may result in higher currents when the PV voltage is lower. Refer to the Wiring Unlimited book for more
information.
8.9.1. Bluetooth
Please note that Bluetooth interface issues are highly unlikely. If you encounter problems, they are probably caused by other
factors. Use this chapter to quickly identify common causes of Bluetooth issues.
Bluetooth check
Check if the solar charger is powered up:
• Observe the LEDs: If any LEDs are on, blinking, or pulsing with a few seconds interval, the unit is powered
Step 1 up, and Bluetooth should be functional.
• f all LEDs are off, the unit is not powered up, and Bluetooth is inactive. Refer to the Solar charger is
unresponsive [45] chapter to troubleshoot.
Page 59 Troubleshooting
MPPT solar charger manual
Bluetooth check
Check if Bluetooth is enabled:
• Connect to the solar charger via the VictronConnect app using its VE.Direct port, either through USB using
Step 2 the VE.Direct to USB interface or remotely via the VRM portal.
• In VictronConnect, navigate to the solar charger settings, then to "product info," and re-enable Bluetooth if it
was disabled.
Check that Bluetooth is in range:
Step 3 • Bluetooth's maximum distance in open space is about 20 meters, but it may be lower inside buildings or
vehicles.
The Windows version of the VictronConnect app does not support Bluetooth:
Step 4
• Use an Android, iOS, or macOS device or connect using a VE.Direct to USB interface.
The solar charger is missing from the VictronConnect app device list:
• Press the orange refresh button at the bottom of the device list.
Step 5 • Ensure no other devices are connected to the solar charger simultaneously.
Step 6 • Click on the options symbol (3 dots) next to the solar charger listing.
• Enter the solar charger's unique PUK code as printed on its product information sticker.
• Ensure the connector is inserted properly and fully into the port.
• Inspect the VE.Direct port for bent pins. If found, power the unit off by disconnecting it from the battery and the PV, and
straighten the pins using long-nose pliers.
• If it does not show up in the list, set the TX port function in VictronConnect to "Normal communication."
• Test the RX port's functionality using a VE.Direct non-inverting remote on/off cable.
Page 60 Troubleshooting
MPPT solar charger manual
Also, refrain from using the solar charger as a power supply without batteries connected. Although this operation won't harm the
solar charger, it might not support all types of loads. Some loads may function, while others may not, particularly at low load
power, where the solar charger's response might be too slow to maintain a constant voltage. Please note that support is not
provided for such situations.
• First, thoroughly inspect all the equipment connected to the system and check for any ground faults.
• Next, verify the number of connections to ground in the system. Ideally, there should be only one point in the system connected
to the ground, which should be at the battery.
• For more information on system grounding, see the "System grounding" chapter in the Wiring Unlimited book.
Note that the solar charger is non-isolated and the minus of the PV input is at the same potential as the minus of the battery
output.
• Use the VictronConnect app to verify the relay functionality setting. Refer to the Programmable relay settings [25] chapter.
• Check for continuity between the C and NC terminals when the relay is not energised.
• Check for continuity between the C and NO terminals when the relay is energised.
• Keep in mind that connecting a circuit with excessive current or voltage to the relay can cause damage. For the relay's current
and voltage rating, refer to the Technical specifications [67] chapter. Any damage resulting from exceeding the rating is not
covered by the warranty.
The protection consists of a latching relay, which is mounted across the PV Input. When the firmware detects a short between the
PV inputs and the battery outputs, by monitoring the battery voltage for an over-voltage, it engages the relay and, as such, shorts
the PV Input. See errors 80 to 83 in the Error 80 to 88 - PV Input shutdown [65] chapter.
Applying a higher battery voltage than configured in the solar charger (eg. 48V battery to a 12, 24 or 36V configured charger), and
then connecting the PV array, can cause the protection to “mis-trigger”. Meaning that the charger sees an over-voltage, and as
such assumes that there is an internal fault and then engages the latching protection.
Recovering from such mis-triggers is the purpose of the here documented reset feature.
Page 61 Troubleshooting
MPPT solar charger manual
Follow the below procedure only if (a) the charger is not measuring any PV voltage when it should (i.e. during the day, with
the sun shining, and all connections are ok). (b) the charger no longer charges the battery, and measuring the PV Input with a
multimeter in resistance mode shows a few Ohms or lower. (c ) the charger no longer charges an error 80 to 87 is/was shown.
Step 5 Then click the RESET button. It will gray out for a few
seconds and return blue. A click might be heard.
Note that for the SmartSolar VE.Can MPPT 250/100 with a serial number between HQ2150 and HQ2250, the
reset procedure – unfortunately – often does not work. In this case, contact your dealer for replacing the solar
charger under warranty.
Not necessarily, as described above, the charger takes into account the PV and battery voltages to decide if the reset menu
needs to be shown or not. In case, for example, the charger is connected to a 12V battery and no voltage is detected at the panel
terminals (e.g. during the night), the menu will be shown, even if the charger is not faulty. Pressing the reset button in this case
won't have any effect.
Page 62 Troubleshooting
MPPT solar charger manual
Furthermore, the solar charger utilises specific LED indications to signal particular errors. For an overview of these LED codes,
please refer to the Victron Toolkit app.
This error can also occur if the battery voltage (12, 24, 48V) is set to a lower voltage than the connected battery.
Possible solutions:
• If possible, provide adequate cooling for the unit. A cooler unit can handle more current.
• Charge the battery before using the inverter. At higher battery voltages, the same amount of power requires less current.
If you see this error, update the solar charger to the latest firmware. If, after the update, you still see this error, then perform a
"reset to factory defaults" and then reconfigure the solar charger.
Disconnect all wires and then reconnect all wires to force the solar charger to restart. Also, make sure the minus on the solar
charger (PV negative and battery negative) is not bypassing the solar charger.
If the error remains, please contact your dealer or distributor, as there might be a hardware defect.
Page 63 Troubleshooting
MPPT solar charger manual
Disconnect all wires, and then reconnect all wires. If the error persists, the charger is probably faulty.
Note that this error was introduced in v1.36. So when doing an update, it might look like the firmware update caused this issue;
but it doesn't. The solar charger was then already not performing 100% before the update; updating to v1.36 or later merely made
the issue more visible. The unit needs to be replaced.
This error is an indication that the PV array configuration with regard to open-circuit voltage is critical for this charger. Check
configuration, and if required, re-organise panels.
For more information, refer to the PV voltage too high [52] chapter.
• Another device is connected to the battery, configured to a higher voltage. For example, an inverter/charger is configured to
equalise at 17 Volts, while this is not configured in the solar charger.
Error recovery:
• Error 38: First, disconnect the solar panels and then disconnect the battery. Wait for 3 minutes, then first reconnect the battery
and then the panels.
• Error 39: The charger will automatically resume operation once the battery voltage drops below its maximum voltage setting
(normally Equalisation or Absorption voltages). It can also take a minute to reset the fault.
Make sure all settings are the same and update firmware on all chargers to the latest version.
Solar chargers only show this error when there is solar power available, and thus the device is ready to initiate charging. It does
not show at night. And in case there is a permanent problem, the error will appear in the morning and clear at night, and so forth.
Solution: check the connection between the charger and the BMS.
When removing the solar charger from such a system and reusing it in a system without BMS, that setting needs to be cleared.
Here is how to do that:
Page 64 Troubleshooting
MPPT solar charger manual
• Chargers with LCD display: go into the setup menu, and change setting ‘BMS’ from ‘Y’ to ‘N’ (setup item 31).
• Other chargers: reset the charger to factory defaults with VictronConnect, and then reconfigure it.
This error indicates that the charger detects multiple conflicting network sources, with the same priority, trying to send the
same information to the charger. VE.Can and VE.Direct interfaces have both the same priority level, and BLE (using VE.Smart
Networking) has a lower priority.
Having a higher priority level means that, if the same information (e.g. Battery voltage sense) is being received from both VE.Can
and BLE (using VE.Smart Network) by the charger, the information on VE.Can will be used and the one coming from BLE will be
ignored.
Now, if the same information is being received from two interfaces that have the same priority level (as VE.Can and VE.Direct),
the charger does not know how to prioritize those, causing error 68 to be triggered.
• For the SmartSolar/BlueSolar chargers VE.Can, update the software. If the error persists, it will be because the charger is
connected with both a VE.Direct cable and on VE.Can. That is not supported. Remove one of the two cables. The error will
disappear and the charger will resume normal operation, within a minute.
Prior to any other troubleshooting, make sure to update to the latest firmware version.
• Another device is connected to the battery with a higher charge voltage configuration. For instance, a MultiPlus is configured to
equalise at 17V, while the solar charger has not been configured for equalise charging.
Error recovery:
• Ensure that the solar charger is running the latest firmware.
• Errors 80 to 83: First, disconnect the solar panels, then disconnect the battery and then follow the procedure as described in
the PV Short relay reset procedure [61] chapter.
• Errors 84 to 87: First, disconnect the solar panels and disconnect the battery. Wait for 3 minutes, then first reconnect the battery
and then reconnect the panels.
If the error is only present in the history data and the unit operates normally this error can be ignored safely. Explanation: when
the units power up for the very first time in the factory, it does not have calibration data and an error 116 is logged. Obviously, this
should have been cleared, but in the beginning, units left the factory with this message still in the history data.
SmartSolar models (not the BlueSolar models): upgrading to v1.4x firmware is a one-way trip, you cannot go back to an older
firmware version once you upgrade to v1.4x. Reverting to older firmware gives error 116 (calibration data lost), this can be fixed
by re-installing the v1.4x firmware.
To fix this the update needs to be retried, download the correct firmware for your device from the Victron Professional Portal
When your GX device is connected to VRM, you can do a remote firmware update using this firmware file. You can do this via the
VRM website or using the VRM tab in VictronConnect. VictronConnect can also be used together with the firmware file to update
using a Bluetooth connection.
Page 65 Troubleshooting
MPPT solar charger manual
The procedure to add the file to VictronConnect and start the update is described here: 9. Firmware updates
Error recovery:
• First, restore it to factory defaults. (top right in Victron Connect, click on the three dots).
• Report this to your Victron dealer and ask for it to be escalated to Victron; as this error should never happen. Preferably include
firmware version and any other specifics (VRM URL, VictronConnect screenshots or similar).
Page 66 Troubleshooting
MPPT solar charger manual
9. Technical specifications
35
B 6
R3
B B
12
101 171 182
A R6
DETAIL B
C
SCALE 1 : 1 C
D D
R3
11
E
E
DETAIL A
SCALE 1 : 1
Dimensions in mm
F
F
Rev01
1 2 3 4 5 6 7 8
250
4.7
228 92
5.5
B
35
B R2.75 B
12
C C
A DETAIL B
SCALE 1 : 1
D D
R3
E
E
11
DETAIL A Dimensions in mm
SCALE 1 : 1
F
F
Rev04
1 2 3 4 5 6 7 8
294.6
5 101
268.6
R4
B B
30
A
R4
16
8
13
C
144.1 R8 C
246 8
B DETAIL A DETAIL B
SCALE 1 : 1 SCALE 1 : 1
26
D D
268.6
E
E
Dimensions in mm
F
F
Rev01
1 2 3 4 5 6 7 8
8
30
A R4
16
C C
R8
144.1 213.9
DETAIL A
SCALE 1 : 1
D D
26
B
R4
13
E
E
DETAIL B
SCALE 1 : 1
Dimensions in mm
F
F
Rev02
1 2 3 4 5 6 7 8