The document outlines the technical specifications for a 125KVA diesel generator to be supplied, delivered, installed, commissioned, and tested by a supplier. It includes detailed requirements for the generator's dimensions, engine specifications, electrical systems, safety features, and warranty conditions. Additionally, it specifies the need for an Automatic Transfer Switch with particular features and protections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
27 views3 pages

Diesel Generator 125KVA

The document outlines the technical specifications for a 125KVA diesel generator to be supplied, delivered, installed, commissioned, and tested by a supplier. It includes detailed requirements for the generator's dimensions, engine specifications, electrical systems, safety features, and warranty conditions. Additionally, it specifies the need for an Automatic Transfer Switch with particular features and protections.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 3

Food and Agriculture Organization of the United Nations

FAO Representation Yemen

OFFERED TECHNICAL SPECIFICATIONS


# REQUESTED TECHNICAL SPECIFICATIONS PLEASE FILL IN THE SPACES WITH THE
SPECIFICATIONS OF THE MATERIAL OFFERED
No
. Description
Supplier Technical Offer (SPECS)

Diesel Generator 125KVA

Supply , deliver , install , commission and test A stand-


alone diesel power generating set with engine and
alternator
mounted on its own base frame and protected by an all-
weather, sound proofed
enclosure. Minimum output 125 KVA on site rating.
Maximum output: 145 kVA
Site conditions: Ambient temperature range: 40 to +50
degrees C
Site conditions: Relative Humidity: Typically, 80-100%
Site conditions: Altitude: 1000 m max.
A direct-coupled generator set with electric starting
mounted on a skid unit with integral fuel tank and control
panel.
Encased in an acoustic chamber.
Voltage: 240-380V, 50 Hz, three-phase
Genset rated for continuous running and supplying power
at variable load with no limitation on annual running
hours. (“Prime Power rating”). Minimum 50 Hz rating:
125 KVA
Rated to supply 10% overload power for 1 hour in 12
1 Approximate Length: 2300 mm
dimensions and Width: 1100 mm
weight (including Height: 1500 mm
acoustic chamber): Dry weight: 1800 kg
Fuel tank capacity: 250 litres minimum
Year of manufacturing: 2020 or later
Engine manufacturer from USA, UK or EU
Delivery to be within 10 days from contract signatureIn-
line four-cylinder Perkins diesel engine, CAT or
equivalent
Displacement: 5 litre approximately
Engine power at rated rpm: kWm 125; HP 156.8 – 167
Induction: Turbocharged
Operational engine speed: 1500 rpm (for 50 Hz rating)
Fuel consumption at 100% load: 26 - 29 litres/hour
approximately
Cooling system: Water cooled.
Heavy duty radiator
Filled with anti-freeze/corrosion
inhibitor
Air cleaner Heavy duty dry element type
Restriction indicator
Fuel filter system: Heavy duty filters with water
separator
Lubricating oil filter: Full flow filter with spin on

11
Food and Agriculture Organization of the United Nations
FAO Representation Yemen

OFFERED TECHNICAL SPECIFICATIONS


# REQUESTED TECHNICAL SPECIFICATIONS PLEASE FILL IN THE SPACES WITH THE
SPECIFICATIONS OF THE MATERIAL OFFERED
cartridge
Exhaust system: Totally enclosed for operator
safety
Electrical system: Heavy duty 12-volt system
Battery charging facility with
alternator
180 Amp.h maintenance free
battery
Electronic control panel with English or Arabic display
Control panel installed as an integral part of the acoustic
chamber – vibration isolated from the generator set
Automatic start and shutdown control
High coolant temperature automatic shutdown system
Low lubricating oil pressure automatic shutdown system
Control panel must include the following protections and
take automatic action (shutdown or alarm) in case of:
- Fail to start
- High engine temperature
- Low/High battery voltage
- Underspeed/overspeed
- Loss of engine speed
- Low coolant level
- Low fuel level
- High oil temperature
- Over voltage
Controls to be protected by a fused, DC supply from the
starting battery.
Instrumentation: Voltmeter
Ammeter
Frequency/tachometer
Hours run counter
Coolant temperature gauge
Lube oil pressure gauge
Battery condition voltmeter
Maximum SA sound pressure levels Sound pressure
level at 100% load, 15 metres:
60 dBA
Sound pressure
level at 100% load, 7 metres:
65 dBA
Sound pressure
level at 100% load, 1 metre:
80 dBA
Weatherproof Body made from
galvanized steel coated
sound-attenuated Full length extra
wide lockable doors on each side
enclosure Lube oil and
cooling water drains piped to
incorporating an exterior of
enclosure
internally mounted Control panel viewing window in a
lockable access door
12
Food and Agriculture Organization of the United Nations
FAO Representation Yemen

OFFERED TECHNICAL SPECIFICATIONS


# REQUESTED TECHNICAL SPECIFICATIONS PLEASE FILL IN THE SPACES WITH THE
SPECIFICATIONS OF THE MATERIAL OFFERED
exhaust silencer. Emergency stop button (red)
mounted on enclosure exterior
exhaust silencer. Cooling fan and battery charging
alternator fully guarded
Fuel fill and battery can only be
reached by lockable access
door
Exhaust silencing system totally
enclosed for operation safety
Tested and certified single point
lifting facility
Lifting points on base frame
Alternator/Output
Alternator Marelli, Leroy Somer or equivalent
Insulation class H or better
Main Output: Three pole circuit breakers
Thermal and magnetic overload
Access for outgoing cables
-Basic routine maintenance tool kit supplied for each
generating set.
Circuit wiring diagram
-A list of manufacturer’s recommended spare parts,
sufficient for 2 years of operation (4,000 hours) must
be submitted for each unit. The list must be itemised,
costed and submitted with your bid
-The manufacturer or service agent should give
training to the designed operators in order to ensure
the correct functioning of the unit.
-A full and clear manufacturer’s warranty statement
transferable with the ownership of the equipment
(FAO or end-user) must be submitted with your bid
detailing the terms and conditions that are being
offered. The minimum requirement is for a twelve
month warranty period.
Automatic Transfer Switch
Supply, install, test, and commissioning Automatic
Transfer Switch (ATS) with 2Nos. 250/250A, 50 KA,
4 pole, motorized MCCBs, electrically and
mechanically interlocked with base frame and
controller having selector switch for automatic &
forced operation on normal and emergency sources.
ATS must have monitoring of normal source,
2 automatic changeover, test facility, circuit breaker
status indication (On, Off & Trip), 3 phase Under -
voltage protection and Phase Sequence Protection
inbuilt in the controller or separately provided. The
MCCB's must have Electronic Trip Unit with
adjustable protection against Overload, adjustable
protection against Short Circuit, shunt trip coil,
auxiliary contacts for ON, OFF, TRIP indication etc.
as per drawing and specifications.
13