FUNK-ELECTRONIC
GMBH
TETRA Radio Modules
Antenna COM DIP
Pwr
Radio Time Com System
Rx Tx Syn Slot RxD I/O OK Pwr
F1 Run Err
TRM-710H/ZZ
C
C 0 1 2 3 4 5 6 7 C C 8 9 10 11 12 13 14 15 C
In In In In 0 1 2 3 4 5 6 7
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Radio Time System
A B Rx Tx Syn Slot I/O OK Pwr
F1 Run Err
RTU-710/DA1
C D RF
0 1 2 3 4 5 6 7 0 1 2 3 0 1 2 3 4 5 6 7
C Out C 0 1 2 3
+ 0 1 2 3 4 5 6 7 - C + - + - + - + - C
TETRA: An ETSI standard for public digital trunked
radio systems.
TETRA (Terrestrial Trunked Radio) is a standard RTU-710T TETRA Radio Slave Stations:
framework for implementation of cellular digital radio On-off inputs: The module's 16 opto-isolated on-off inputs
networks for voice and data, similar in some ways to GSM. can be connected in groups of 4 for +ve or -ve polarity.
TETRA supports circuit and packet switched data services Each input is assigned a 16-bit counter that can be used
(in addition to voice communication), and also direct as a time totalizer or event counter at up to 10 pulses/sec,
communication between field terminals. if and as required.
The TETRA standard was developed by ETSI (European On-off outputs: The on-off outputs are opto-isolated PNP
Telecommunications Standards Institute] initially for the transistors (+ve switching) rated for loads up to 500 mA,
European Community, but has now found acceptance 12-24 VDC.
worldwide. The technology, initially developed for voice
communications, now also supports data, using SDS Analog inputs: These inputs accept 0-20 mA or 4-20 mA
(Short Data Service). The turnaround time for an SDS (0-10 VDC optional) sensor/transmitter signals that are
packet can be 0.3 seconds approximately. digitized at 12-bit resolution.
Piciorgros TETRA Radio Modules are based the TETRA I/O Expansion: RTU-710T modules have an I/O
standard. A master station (MDP-310.200T or TRM- expansion bus interface through which Type PEM I/O
710T/ZZ) can handle up to 240 slave radio RTUs with Expansion Modules can be connected, to increase the
integrated I/O (RTU-710T) or radio modems with serial I/Os available. Every time the RTU module is started up, it
interfaces (TRM-710T). automatically scans this bus interface to check what
Expansion Modules are connected, and their I/O
TRM-710.200T/ZZ TETRA Radio Master Station: At the configurations.
lowest communication layer, the TRM-710.200T/ZZ
operates with 3964R, RK-412 or Timeout protocol. At the
next higher layer, it can handle MoP/MoP2, MODBUS, or
IEC-608870-5-01 protocols. Hardware interfaces available
are RS-232, RS-422/485, or (optionally) Profibus-DP.
Funk-Electronic Piciorgros GmbH · Claudiastr. 5 · 51149 Köln-Porz
Tel.: 02203-911770 · Fax: 02203-913006 ·
[email protected] · www.piciorgros.com
FUNK-ELECTRONIC
GMBH
TRM-710.200T/Z TETRA Master Station Modem
Antenna COM DIP
Pwr
Radio Time Com System
Rx Tx Syn Slot RxD I/O OK Pwr
F1 Run Err
TRM-710/TZ
0 1 2 3 4 5 6 7
T he TRM-710.200T/Z Radio Modem is
intended for use as master station in a
TETRA radio network. Data received by the
while 3964R and Timeout protocols are
supported at the link level (OSI Layer 2).
TRM-710.200T/Z via its serial interface is Operation: Data received by the master station
converted to TETRA frames and transmitted via its serial interface is transmitted using
through the radio packet switching system to a TETRA packet switched SDS (Short Data
TRM-710 (slave radio modem) or RTU-710 Service) to the target radio module. If the data to
(radio RTU with I/Os). The slave TRM-710 be sent exceeds the SDS limit of 120 or 140
reconverts the data into its original format (e.g., characters, it is broken up by the sending station
MODBUS or IEC 60870-5-101) before sending into sub-frames, and reassembled by the
it out via its serial port, while the RTU-710 receiving station into its original composition.
responds by reporting input states and values or
setting outputs as commanded.
Protocol conversion is done by the radio
modems (master and slave) in both directions
(TETRA <-> serial). Serial protocols supported
are: MODBUS-RTU, IEC 60870-5-101, and
user-configurable data-blocks,
Funk-Electronic Piciorgros GmbH · Claudiastr. 5 · 51149 Köln-Porz
Tel.: 02203-911770 · Fax: 02203-913006 ·
[email protected] · www.piciorgros.com
TRM-710.200T/Z
Tetra-Master Station Modem
Function: Master station radio modem for
TETRA networks with serial interface
RF output power Pout: up to 1W
Frequency Range: Tetra Standard
Interfaces: Two independent serial interfaces:
RS-232 or RS-422 / RS-485
Protocols (Link Layer): l
3964R
l
Timeout
Protocols (Application Layer): l
MoP / MoP2
l
Modbus-RTU
l
IEC-60870-5-101
RF field strength indication: LED 8-segment bar-graph display of
received RF signal strength.
Power supply voltage: 12 - 24 VDC nominal
(9.6 - 28.8 VDC operating)
Enclosure: Aluminum pressure die-cast housing,
DIN rail mounting.
Protection class: IP-65
Operating temperature: -20ºC to +70ºC
Mounting: Din-rail 35 mm
Size (w/o connectors): 80 x 162 x 62 mm
FUNK-ELECTRONIC
GMBH
TRM-710.200T - TETRA Slave Radio Modem
Antenna COM DIP
Pwr
Radio Time Com System
Rx Tx Syn Slot RxD I/O OK Pwr
F1 Run Err
TRM-710/T
0 1 2 3 4 5 6 7
T he TRM-710.200T Radio Modem is
intended for use as a slave station in a
TETRA radio network. It is accessed by
Operation: Data received from the master
station over the TETRA network is
transferred to the serial port without further
polling, and transfers data between a handshaking. If an acknowledgement is
central control system linked to a remote received from the terminal connected to its
master station and the serial port of the serial interface, this is passed on to the
slave station. The TRM-710.200T has RS- master station. If no acknowledgement is
232 and RS-422/485 serial interfaces. received from the local terminal, the TRM-
710.200T sends a null data block to the
Protocol conversion is done by the radio master station. This allows the central
modems (master and slave) in both control system to confirm the integrity of the
directions (TETRA <-> serial). Serial TETRA radio network when the slave
protocols supported are: MODBUS-RTU, station terminal fails to respond.
IEC 60870-5-101, and user-configurable
data-blocks, while 3964R and Timeout
protocols are supported at the link level
(OSI Layer 2).
Funk-Electronic Piciorgros GmbH · Claudiastr. 5 · 51149 Köln-Porz
Tel.: 02203-911770 · Fax: 02203-913006 ·
[email protected] · www.piciorgros.com
TRM-710.200T
TETRA Radio Modem with Serial Interface
Function: Slave station radio modem for TETRA
networks
Max. RF transmit power: Pout up to 1W
Frequency range: TETRA standard
Interfaces: Two independent serial interfaces: RS-
232 or RS-422 / RS-485
Protocols supported: Layer 2 (Link Layer):
3964R
Timeout
Layer 7 (Application Layer)
MoP / MoP2
MODBUS-RTU
IEC-60870-5-101
RF field strength indication: LED 8-segment bar-graph display of
received RF signal strength.
Power supply voltage: 12 - 24 VDC nominal (9.6 - 28.8 VDC
operating)
Enclosure: Aluminum pressure die-cast housing, DIN
rail mounting. Protection class: IP-65
Operating temperature: -20ºC to +70ºC
FUNK-ELECTRONIC
GMBH
RTU-710T Slave I/O Module for TETRA Networks
C 0 1 2 3 4 5 6 7 C C 8 9 10 11 12 13 14 15 C
In In In In
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Radio Time System
A B Rx Tx Syn Slot I/O OK Pwr
F1 Run Err
RTU-710T/DA1
C D RF
0 1 2 3 4 5 6 7 0 1 2 3 0 1 2 3 4 5 6 7
C Out C 0 1 2 3
+ 0 1 2 3 4 5 6 7 - C + - + - + - + - C
T he RTU-710T is a slave I/O module with on-off inputs,
analog inputs and on-off outputs that can be directly
operated on TETRA radio networks. Event counting and
RF field strength indication: An 8-segment bar graph
LED display on the front face of the RTU-710 indicates
received radio signal strength. This simplifies commis-
time totalizing functions can be enabled for on-off inputs. sioning and identification of radio communication
An optional PicoLogo Micro-PLC feature allows the RTU- problems. A central control system connected to the
710T to act as an autonomous micro-PLC. All I/Os are master station of the radio network can read field strength
electrically isolated from the module's electronic circuits. values of RTU-710 slave stations by interrogating the
appropriate register.
On-off inputs: The 16 opto-isolated on-off inputs can be
connected to input switching circuits with arbitrary polarity Protocols: RTU-710T Slave I/O Modules can be accessed
in groups of 4. Each on-off input can be enabled with a 16- using the MoP/MoP2, MODBUS-RTU, or IEC-60870-5-101
bit event or time totalizing counter. On-off inputs can switch protocol, in polling mode. Through a TETRA master
at rates up to 10 Hz. station modem (TRM-710.200T/Z), a central control
system can read on-off input states, event/time counter
On-off outputs: The on-off output switching PNP values, and analog input measurements; and set on-off
transistors are also opto-isolated and can switch loads of and analog outputs at a remote RTU station.
up to 500 mA at 12-24 VDC.
Pico-Logo soft-PLC: The RTU-710 is optionally available
Analog inputs: The analog inputs accept 0-20 mA or with the PicoLogo soft-PLC feature that gives it auto-
4-20mA current loop signal, or 0-10 VDC voltage signal, nomous logic control and other micro-PLC capabilities.
converting these to digital values with 12-bit resolution.
Plug-in screw-terminal connections: All I/0 connections
Extension modules: The RTU-710 has a local I/O are made through high quality screw-terminal plug-in block
expansion port via which PEM I/O Extension Modules can connectors. Panel wiring can therefore be done if
be bus-connected to increase the number of I/O's of an necessary before RTU modules are delivered.
RTU-710 station. When an RTU-710 is powered on, it first
checks this I/O expansion port and automatically
determines the number and types of its local I/Os.
Funk-Electronic Piciorgros GmbH · Claudiastr. 5 · 51149 Köln-Porz
Tel.: 02203-911770 · Fax: 02203-913006 ·
[email protected] · www.piciorgros.com
RTU-710T
TETRA RTU Slave Station with On-Off and Analog I/O
Specifications
Function: Slave RTU station for TETRA radio networks,
with on-off and analog inputs, and on-off
outputs.
RF transmit power: Pout 1 W
Frequency range: TETRA standard
On-off inputs: l 16 on-off inputs, potential-free, of which:
l 8 inputs are user-configurable each with a
16-bit time-totalizing counter
l 8 inputs are user-configurable each with a
16-bit event counter
On-off outputs: Standard: 8 solid-state PNP outputs,
potential-free
Optional: 16 solid-state PNP outputs,
potential-free
Analog inputs: 4 analog inputs: 4-20 mA, 0-20 mA,
or 0-10 VDC.
I/O expansion interface: Supports up to 16 daisy-chained Type PEM
I/O Extension Modules
RF field strength indication: LED 8-segment bar-graph display of received
RF signal strength.
Power supply voltage: 12 - 24 VDC nominal (9.6 - 28.8 VDC
operating)
Enclosure: 35mm DIN rail mounting
Dimensions: 80mm x 162mm x 62mm (excluding terminal
blocks)
Operating temperature: -20ºC to +70ºC