0% found this document useful (0 votes)
4 views1 page

Pages From 6jazn11 Jazn FC Dae PM Spe 0003 B Ifc Technical Specifications Volume 03 of 04 2

The document outlines specifications for various types of fire-resistant LS0H cables, including their construction, ratings, and compliance with relevant standards. It details the use of these cables in fire alarm systems, emergency communication, and firefighting applications, with distinctions based on evacuation times for buildings. Each cable type is identified by an abbreviation and includes requirements for certification and testing to ensure safety and performance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
4 views1 page

Pages From 6jazn11 Jazn FC Dae PM Spe 0003 B Ifc Technical Specifications Volume 03 of 04 2

The document outlines specifications for various types of fire-resistant LS0H cables, including their construction, ratings, and compliance with relevant standards. It details the use of these cables in fire alarm systems, emergency communication, and firefighting applications, with distinctions based on evacuation times for buildings. Each cable type is identified by an abbreviation and includes requirements for certification and testing to ensure safety and performance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 1

8519 including buildings with evacuation time not exceeding 30 minutes unless

otherwise specified under fire alarm section and where shown on the drawings.

M. Fire resistant LS0H Cable (abbreviated as FR4 on the drawings, similar to Prysmian
- Type FP Plus, or approved equal) : Multi core plain annealed copper conductors
to IEC 60228 (in sizes up to 4 mm2), fire resistant insulation, galvanized steel wire
armored, category CWZ to BS 6387, PH 120 classified to BS EN 50200, and
120 minutes rating when tested in accordance with BS 8434-2 and complying with
BS EN 50363, laminated aluminum screen bonded to the sheath and LS0H
composite sheath with tinned earth continuity conductor/drain wire to IEC 61034
and IEC 60754 or BS EN 50267-2-1. Cable shall comply with IEC 60332-1 & 3
(category C) for flame retardant properties. Cable shall be rated 300/500 V,
capable of accepting voltage surges up to 5 kV, operating conductor temperature of
70 deg. C. Cable shall be LPCB and BASEC certified, audited and marked by
embossing on cable sheath. Cable shall be used for fire alarm, voice evacuation
installations, emergency voice communication systems, branch circuits in central
battery system and other loads requiring category 2&3 circuits in accordance with
BS 8519 including buildings with evacuation time higher than 30 minutes, such as
high assembly and high rise buildings unless otherwise specified under fire alarm
section and where shown on the drawings.

N. Fire resistant LS0H Cable 600/1000 V, (abbreviated as FR5 on the drawings,


similar to Prysmian - Type FP-400, or approved equal): Multi core plain copper
stranded circular or shaped conductor (sizes up to 400mm2) complying with
IEC 60228 with fire resistant insulation category CWZ to BS 6387, category F2
to BS 7846, PH60 classified to BS EN 50200 and 30 minutes rating when tested
with additional water spray in accordance with BS EN 50200 Annex E and
complying with BS EN 50363 operating conductor temperature 90ºC, single
galvanized steel wire armour and extruded low smoke zero halogen (LS0H) over
sheath wire to IEC 61034 and IEC 60754 or BS EN 50267-2-1. Cable shall
comply with IEC 60332-1 & 3 (category C) for flame retardant properties. Cable
shall be LPCB and BASEC certified, audited and marked by embossing on cable
sheath. Cable shall be used for feeders of the fire pumps, smoke and pressurizing
fans, fire fighting elevators and other firefighting and life safety loads requiring
category 1 circuits in accordance with BS 8519 including buildings with evacuation
time not exceeding 30 minutes and where shown on the drawings.

O. Fire resistant LS0H Cable 600/1000 V, (abbreviated as FR6 on the drawings,


similar to Prysmian - Type FP-600S, or approved equal): Multi core plain copper
stranded circular or shaped conductor (sizes up to 400 mm2) complying with
IEC 60228 with fire resistant insulation category F120 to BS 7846 and tested in
accordance with BS 8491 and complying with BS EN 50363 operating conductor
temperature 90ºC, single galvanized steel wire armour and extruded low smoke
zero halogen (LS0H) over sheath wire to IEC 61034 and IEC 60754 or BS EN
50267-2-1. Cable shall comply with IEC 60332-1 & 3 (category C) for flame retardant
properties. Cable shall be LPCB and BASEC certified, audited and marked by
embossing on cable sheath . Cable shall be used for feeders of the fire pumps,
smoke and pressurizing fans, fire fighting elevators and other firefighting and life
safety loads requiring category 2&3 circuits in accordance with BS 8519 including
buildings with evacuation time higher than 30 minutes, such as high assembly and
high rise buildings and where shown on the drawings.

P. Fire resistant LS0H Cable (abbreviated as FRE on the drawings, similar to Prysmian
- Type FP 100, or approved equal): Single core stranded plain annealed copper

Seven - KSA 26 05 19 - 6 Low Voltage Electrical Power


Conductors And Cables