CRIO EN Web

The document is a technical catalogue for Euroklimat's R290 air-cooled liquid chillers designed for medium temperature applications, with heating capacities ranging from 7 to 185 kW. It highlights the use of R290 as a natural refrigerant with low environmental impact, energy efficiency features, and safety measures against flammability. The catalogue includes detailed specifications, safety guidelines, and performance tables for various models in the CRIO product range.

Uploaded by

moreds1983
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views92 pages

CRIO EN Web

The document is a technical catalogue for Euroklimat's R290 air-cooled liquid chillers designed for medium temperature applications, with heating capacities ranging from 7 to 185 kW. It highlights the use of R290 as a natural refrigerant with low environmental impact, energy efficiency features, and safety measures against flammability. The catalogue includes detailed specifications, safety guidelines, and performance tables for various models in the CRIO product range.

Uploaded by

moreds1983
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 92

EN

Technical Catalogue

R290 Air-Cooled Liquid Chillers for Medium Temperature applications

Nominal Heating Capacity: 7-185kW | 50Hz


Solutions

Market demands Euroklimat’s responses

Long term refrigerant R290 Natural gas

Energy efficiency NEW High efficiency series now available

Low environmental impact GWP equal to 3


Index
CRIO The natural solution for medium temperature applications 4
Why R290? 6
CRIO Advantage 7
Natural refrigerant Propane & flammavility 8
Safety 9
Maximum allowable R290 charge 10
Technical features 11
Operating limits 13
R290 reciprocating compressor with INVERTER 14
Advanced Electronic Controller 15
Ready for Government incentives 16
R290 Gas detector & Calibration kit 17
Refrigerant Circuit Diagram 18
How to select 19
Heat recovery 20
CRIO/BS 7-1-1 PE 19-1-1 PE 22
CRIO/BS 23-1-1 PE 55-1-1 PE 24
CRIO/BS 38-2-2 PE 95-2-2 PE 26
CRIO/BS 108-2-2 PE 173-2-2 PE 28
CRIO/BS 158-2-2 PV 182-2-2 PV 30
CRIO/HE 10-1-1 PE 24-1-1 PE 32
CRIO/HE 30-1-1 PE 56-1-1 PE 34
CRIO/HE 41-2-2 PE 116-2-2 PE 36
CRIO/HE 130-2-2 PV 185-2-2 PV 38
CRIO/HE+ 10-1-1 PE 56-1-1 PE 40
CRIO/HE+ 41-2-2 PE 116-2-2 PE 42
CRIO/HE+ 130-2-2 PV 185-2-2 PV 44
CRIO/BS Performance tables by model | Cooling 46
CRIO/HE Performance tables by model | Cooling 50
CRIO/HE+ Performance tables by model | Cooling 54
CRIO Standard equipment and Accessories 58
CRIO/BS Standard equipment and Accessories 64
CRIO/HE Standard equipment and Accessories 67
CRIO/HE+ Standard equipment and Accessories 70
CRIO Applications 73
Acoustic configurations 74
Sound levels 75
Dimensions and Operating spaces 76
How it is made 82
Transport of the unit with R290 charge 84
Standard and optional packing 85
WebService2 86
R290 References 88
Some R290 Installations 89
Our plants and quality management 91

www.euroklimat.it 3
SOLID AND LIGHT
STRUCTURE

Structure specifically designed


and built to guarantee total
resistance to atmospheric agents
and corrosion. Base and panels
made of galvanized steel sheet,
oven-painted with polyurethane
powders. Equipped with sturdy
support feets that facilitate the
handling of the unit and allow a
simple and quick installation.

EXTRACTOR FAN

The AC extractor fan, installed


below the electrical panel,
ensures emergency ventilation
in case of R290 leakages and
allows the dilution of propane.
The AC-type extractor fan allows
to convey the air discharge,
ensuring an adequate pressure
head.

CONVEYED SAFETY
VALVE EXPULSION GRID

The safety valve is conveyed


outside the unit and a special
kit is supplied for the final part
of the conveying pipe.
In case of leakages, the dilution
of propane is expulsed by the
extractor fan towards the
expulsion grid.

4 www.euroklimat.it
The Natural solution for
Medium Temperature Applications
ANTI-UV ELECTRICAL
CABLE

The electric cables of the fans,


which are positioned outside, have
a special sheath that protects them
from ultraviolet radiation and can
withstand even at low temperatures.

EC FANS

High efficiency EC fans, electronically


commutated, usefull to reduce
energy power consumption.

ELECTRICAL BOARD

Switchboard made according to


standards IEC 204-1/EN60204-1,
complete with main isolator switch,
door interlock safety device.
Protection index: IP54.
The electrical panel is isolated from
the rest of the unit and installed
in such a way that ensures the
separation from the compressor box.

EXTRACTOR FAN

Thanks to the emergency fan, in


case of leakages air is pushed into
the compressor box, allowing the
dilution of propane.

GAS DETECTOR

ATEX certified gas detector


installed inside the compressor’s
box, ensures the activation of the
adequate safety measures in case
of R290 leakage.
www.euroklimat.it 5
Why R290?
CRIO air-cooled chillers offer you optimized natural solutions combining many advantages in a compact package.

Propane’s refrigerating properties


has been well known since the early
twentieth century.

Its low density and its thermodynamic


characteristics allow a reduction in charge and relatively low working
pressures.
Moreover it offers a very wide range of applications, so it can be used in
refrigeration as well as in conditioning or heating of buildings.
Euroklimat has more than 12 years’ experience with R290 chillers and more
than 500 units installed throughout Europe for all applications

All Models of the CRIO product range


are Eco- Design Ready.
The EU Ecodesign Directive adopted
in 2009 provides rules for improving
the environmental performance of
products by setting out minimum energy efficiency mandatory requirements
for specific product groups.
All CRIO air cooled chillers are conform to REGULATION (EU) No 2015/1095:
the minimum value of SEPR required by this regulation is 2.32 for units with
nominal cooling capacity lower than 300 kW which are using ecological
refrigerants like R290.
The CRIO portfolio is additionally divided between “BUSINESS” and “HIGH
EFFICIENCY” solutions.
CRIO/BS “BUSINESS” models have an average SEPR index of 2.85.
CRIO/HE “HIGH EFFICIENCY” models have an average SEPR index of
3.20.

6 www.euroklimat.it
Advantages

R290 (Propane): Natural and efficient


refrigerant particularly suitable for
Medium Temperature applications.

Hydrocarbons like propane, and


natural refrigerants in general, are particularly suitable for installation in
European countries, where the attention to environmental issues and the
commitment to reduce CO2 emissions are constantly growing.

R290 is a long-term solution: thanks to its very Low GWP (GWP R290 = 3)
it’s suitable to be used up to 2030 without any restriction connected to
F-Gas Regulation.

R290 (propane) is a nontoxic


flammable refrigerant.
To ensure the maximum level of
safety, an Ex-rated Gas detector is
installed as a standard on all units. All
CRIO models are designed and manufactured with the aim to ensure the
containment of propane.

In case of R290 leakage the emergency fan is activated, allowing the dilution
of propane and conveying the air/propane mixture towards the air outlet,
which can be obviously conveyed if necessary. Also the safety valve(s),
when fitted, is (are) conveyed outside the unit. Additionally, the separate
compartment of the electrical panel ensures very high safety levels.

CRIO products range provides an


all-in-one solution thanks to the
integrated hydraulic module (optional)
which contains all the water circuit
components needed for the system to
operate correctly. A wide selection of hydraulic couplings is available to fit
site configuration:
• Single or twin pump with automatic switchover
• Standard or high pressure pump(s)
• Victaulic couplings
The optimized foot-print reduce the use of the surface area for easy
integration into an existing building. Quick, easy and cost-effective
installation and commissioning.

www.euroklimat.it 7
Natural refrigerant Propane
& flammability
Interest and application of hydrocarbon (HC) refrigerants is
The fire triangle
growing, especially now that the global warming impact of
refrigerants is becoming an increasingly important aspect for the
refrigeration and air conditioning industry.

It is widely known that HCs are excellent refrigerants in terms of


performance and because of their negligible environmental impact
aspects. However, it is generally acknowledged that their main
hindrance is related to their flammability.

If you control these components, fire can be avoided.


To achieve this, Euroklimat has considered three general guidelines:

Containment of the substance (propane – R290)

➤➤ CRIO units have leak-tight refrigerant circuits, sufficiently robust throughout the
unit’s lifetime.
➤➤ Pipework is designed to have as few pipe joints as possible.
➤➤ All the materials are fully compatible with the HC refrigerant.

Avoidance of ignition sources

➤➤ All electrically powered components are switched off in case of leakage,


exception made for the gas detector and the emergency fan.
➤➤ Electrical panel is fitted in a separate compartment.
➤➤ Cable glands are at least IP65 and units have a double-barrier.

Use of leak detector & ventilation system

➤➤ Every unit is equipped with a stand-alone gas detection system.


➤➤ The sensor is ATEX Certified and is pre-calibrated at the factory. The sensor
must be calibrated at least once a year, see pag. 22 for more information
➤➤ The fan is automatically activated in case of unlikely leak of propane.

Protection of workers that may come into contact with flammable atmospheres in the workplace.

This may be achieved through leak-tight design, ventilation and appropriate protective systems (for example portable leak
detectors).
Where a flammable atmosphere can arise, people responsible for the positioning and/or installation of the equipment must
ensure that a detailed risk assessment of the installation area has be done.

8 www.euroklimat.it
Safety
Euroklimat Approach
➤➤ In-depth knowledge of the basic principles for the safe use of
Knowledge
flammable HC refrigerants
➤➤ Study of the safe design of refrigeration circuits using flammable
refrigerants
Experience ➤➤ More than 12 years-experience on R290 applications in several
countries

Constant improvement of the risk analysis to:


Risk Analysis ➤➤ Ensure that a detailed safety evaluation has been carried out
➤➤ Enable the identification of ways and means to improve the level
of safety of the systems and equipment, by way of detailed
investigations of all of the factors that affect the risk
Continuos
Improvement
ISO 9001 Quality certification in order to:
➤➤ Ensure the customer a certification path
Certification ➤➤ Run the validation process of the project pre-market

Containment of R290
With the aim of further improving the safety level of the units and ensuring a simpler evaluation of the installation,
Euroklimat developed the new CRIO range with a basic safety principle based on the containment of the
flammable substance.
Containment of the substance is obtained by:
➤➤ Closed box in which all the refrigerant-containing components (with the obvious exception of the condensing
coils) are fitted
➤➤ Gas detector – ATEX certified detection system
➤➤ Extraction fan – EC type
➤➤ Conveyed safety valve(s), made in such a way that in case of valve(s) opening, the extractor fan is activated.

In case of leakage, the above-mentioned components allow the ventilation of the closed box and the dilution of
propane below the Lower Flammable
Limit.
Potential Air/Propane discharge
This system ensures an easier risk Ex-rated area (from emergency fan)
assessment of the unit’s installation
area.
Potential Ex-rated area may be Electrical
panel
generated at the discharge of safety
valve(s) and at the discharge of the R290 discharge
emergency fan (see picture below): from conveyed
safety valve(s)
if necessary, the installer can easily
convey these two elements towards
a safe area. R290 Chiller

www.euroklimat.it 9
Technical features
CRIO/BS: BUSINESS RANGE
Average SEPR: Eco Design EC Inverter
2.85 Ready Fans available

CRIO/BS - Cooling capacity (kW)


182-2-2 PV 181,8
174-2-2 PV 173,9
158-2-2 PV 158,3

173-2-2 PE 172,7
157-2-2 PE 157,5
137-2-2 PE 137,4
126-2-2 PE 125,9
108-2-2 PE 108,3
95-2-2 PE 94,8
79-2-2 PE 79,2
68-2-2 PE 68
58-2-2 PE 58
49-2-2 PE 48,5
38-2-2 PE 38,4

55-1-1 PE 55,3
48-1-1 PE 47,9
39-1-1 PE 39,2
33-1-1 PE 32,7
28-1-1 PE 29,8
23-1-1 PE 23,4
19-1-1 PE 19,4
17-1-1 PE 16,8
12-1-1 PE 12,4
9-1-1 PE 8,9
7-1-1 PE 6,9

0 20 40 60 80 100 120 140 160 180 200

CRIO/BS: BUSINESS RANGE


Cooling capacity 7kW 182kW

Evaporator Condenser
N. of refrigerant circuits Compressors Quantity Fans quantity
type type
Cu/Al
7-1-1 PE ↔ 28-1-1 PE 1 1 1
Cu/Al
33-1-1 PE ↔ 55-1-1 PE 1 1 2
Cu/Al
38-2-2 PE ↔ 68-2-2 PE 2 1 2
Cu/Al
79-2-2 PE ↔ 137-2-2 PE 2 2 3
Cu/Al
157-2-2 PE ↔ 173-2-2 PE 2 2 4
158-2-2 PV ↔ 182-2-2 PV 2 2 4 MCX

Icons legend

Cu/Al MCX
R290

Refrigerant Semi-hermetic Axial fan Brazed plate Single circuit Double circuit Cu/Al Microchannel
R290 | GWP=3 piston compressor heat exchanger condensing colils condensing colils

10 www.euroklimat.it
Technical features
CRIO/HE & HE+: HIGH EFFICIENCY RANGE
Average SEPR: Eco Design EC 10K approach - Inverter
3.20 Ready Fans air side available

CRIO/HE & HE+ - Cooling capacity (kW)


185-2-2 PV 185,1
175-2-2 PV 174,5
161-2-2 PV 161,2
142-2-2 PV 141,8
130-2-2 PV 129,7

116-2-2 PE 116,1
* 99-2-2 PE 99,1
** 97-2-2 PE 97,1
83-2-2 PE 82,5
** 70-2-2 PE 70
** 60-2-2 PE 60,1
48-2-2 PE 47,8
41-2-2 PE 41,4

56-1-1 PE 56,2
** 48-1-1 PE 48
** 41-1-1 PE 41
* 36-1-1 PE 36
** 35-1-1 PE 34,7
30-1-1 PE 29,8
24-1-1 PE 23,9
* 21-1-1 PE 20,7
20-1-1 PE 20,4
17-1-1 PE 17,1
14-1-1 PE 13,6
10-1-1 PE 9,5
0 20 40 60 80 100 120 140 160 180 200

* = only HE+ | ** = only HE

NEW! Special CRIO/HE+ - High Efficiency Plus range available for government incentives
• Fan power max. 21 W per kW condenser capacity
• 10K approach on the condenser coil maintained down to ambient temperature +13°C
More information on page 40-45

CRIO/HE & HE+: HIGH EFFICIENCY RANGE


Cooling capacity 9,5kW 185kW

Compressors Evaporator Condenser


N. of refrigerant circuits Fans quantity
Quantity type type
Cu/Al
10-1-1 PE ↔ 17-1-1 PE 1 1 1
Cu/Al
20-1-1 PE ↔ 48-1-1 PE 1 1 2
Cu/Al
56-1-1 PE 1 1 3
Cu/Al
41-2-2 PE ↔ 97-2-2 PE 2 2 3
Cu/Al
116-2-2 PE 2 2 4
130-2-2 PV ↔ 142-2-2 PV 2 2 4 MCX

161-2-2 PV ↔ 158-2-2 PV 2 2 6 MCX

Icons legend

Cu/Al MCX
R290

Refrigerant Semi-hermetic Axial fan Brazed plate Single circuit Double circuit Cu/Al Microchannel
R290 | GWP=3 piston compressor heat exchanger condensing colils condensing colils

www.euroklimat.it 11
Maximum allowable
R290 charge
Maximum allowable charge of Refrigerating systems and heat pumps should be evaluated according to EN378:2016.
EN378:2016 is a safety and environmental standard published by CEN that provides guidance for Design, Construction,
Installation, Operation and Maintenance of Refrigerating systems and heat pumps.

CRIO Air-cooled chillers


Gas Classification A3 (High Flammability, Low Toxicity)

Application Type
All applications other than Human
Comfort
Equipment Location Machinery room or open air
Maximum allowable
Installation Characteristics 1 Other
charge depends on:
Installation Characteristics 2 Above ground
Installation type Floor location
Device type Fixed system
Access Category General, Supervised, Authorized

Access Category Max. allowable R290 charge CRIO/BS CRIO/HE & HE+

7-1-1 PE 33-1-1 PE 10-1-1 PE 24-1-1 PE


General 5 Kg 38-2-2 PE 79-2-2 PE 41-2-2 PE

7-1-1 PE 55-1-1 PE 10-1-1 PE 48-1-1 PE


Supervised 10 Kg 38-2-2 PE 137-2-2 PE 41-2-2 PE 97-2-2 PE
157-2-2 PV 182-2-2 PV 130-2-2 PV 142-2-2 PV

Authorized NO LIMITS All models All models


.....

12 www.euroklimat.it
Operating limits
CRIO/BS: OPERATING LIMITS - COOLING CRIO/HE & HE+: OPERATING LIMITS - COOLING

Standard operating area Standard operating area


[dT condenser water side: min. 3 max. 7K] [dT condenser water side: min. 3 max. 7K]
T air: Outdoor air temperature [°C] (DB) T air: Outdoor air temperature [°C] (DB)
LWT: Evaporator outlet temperature [°C] LWT: Evaporator outlet temperature [°C]

CRIO/BS: TOTAL HEAT RECOVERY OPERATING LIMITS CRIO/HE & HE+: TOTAL HEAT RECOVERY OPERATING LIMITS

Standard operating area Standard operating area


[dT evaporator water side: min. 3 max. 7K] [dT evaporator water side: min. 3 max. 7K]

T out: Heat Recovery heat exchanger outlet water temperature [°C] (DB) T out: Heat Recovery heat exchanger outlet water temperature [°C] (DB)
T air: Outdoor air temperature [°C] (DB) T air: Outdoor air temperature [°C] (DB)

CRIO/BS: DESUPERHEATER OPERATING LIMITS CRIO/HE & HE+: DESUPERHEATER OPERATING LIMITS

Operating area with Desuperheater Operating area with Desuperheater

T out: Desuperheater heat exchanger outlet water temperature [°C] T out: Desuperheater heat exchanger outlet water temperature [°C]
T air: Outdoor air temperature [°C] (DB) T air: Outdoor air temperature [°C] (DB)

www.euroklimat.it 13
R290 reciprocating
compressor with inverter
Advantages

When comparing with alternative control systems and technologies, a frequency


converter is the optimum energy control system for controlling compressors.

»» Improved system quality by maintaining a constant leaving water temperature

»» Wider range of operation of the heating or cooling power

»» Increased power by increasing the speed of the variable speed compressor

»» Energy saving

»» Longer compressor lifetime

»» Better possibilities of providing monitoring, remote setting and diagnostics

Energy consumption minimized and maximizing comfort levels thanks to CRIO’s INVERTER

Exact capacity match Star/Delta Starter or Soft-starter not Required

Thanks to the advanced P.I.D. control, a last-generation When larger motors are started, it is necessary in many
inverter frequency control system and electronic expansion countries to use equipment that limits the start-up current.
valve management algorithm, the CRIO heat pump is able In more traditional systems, a star/delta starter or soft-
to maintain the constant outlet temperature (LWT) very close starter is widely used. Such motor starters are not required
to the required Set-point, even when the load variations if a frequency converter is used.
required by the system (demand) are very high.

800

700

600
4
500
% Full load currrent

400

300 3

D.O.L.
200
Star - Delta
100 Soft - Starter
1
INVERTER
0
0 12,5 25 37,5 50Hz
Full load & speed

14 www.euroklimat.it
Advanced Electronic Controller
Thanks to a Multitasking Operating System and to the adoption of standard protocols, local and remote connectivity the controller used in CRIO chillers
is the most advanced technology available. Advanced Electronic Controller is available as accessory for CRIO/BS, while is standard for CRIO/HE and
CRIO/HE+ units.

NEW OPERATING SYSTEM

New Multitasking Operating System ensures


optimal system resource usage, extended
datatypes for user application (32bit floating
point numbers) application speed increase
and independent protocol engines.

CONNECTIVITY

CLOUD SERVICE
The controller has two integrated Ethernet
interfaces, three serial interfaces and two
USB ports. Plug & Play solution for tERA platform
A great choice of communication protocols connection. All tERA services are available
is possible (Modbus, Carel, BACNet, LON, just connecting the Ethernet plug to your
Konnex, TCP/IP, HTTP, FTP, DHCP, DNS, NTP, home or office network, without the need
SNMP and many others). for an external connection box.

www.euroklimat.it 15
Ready for Government incentives
CRIO range is specifically designed to meet the requirements of the most
challenging energy efficiency target, with special attention to environmental
issues.
Thanks to their peculiar features, CRIO units allow to have access to
Government incentive systems in different European countries: the
attention to environmental issues can therefore be translated into a
real economic advantage for the customer!

The main configurations and / or characteristics of the units that


can give access* to invariant systems in some European countries
such as France, Netherlands and Germany are:
➤➤ Heat recovery system, which allow the reuse of heat that would
otherwise be “wasted” and rejected in the environment;
➤➤ Inverter driven compressors, which ensure higher efficiency at partial
load and a modulating control
➤➤ Low approaches (∆T) on condensing coils between ambient temperature
and condensing temperature of the refrigerant gas, which ensure higher
efficiency of the compressor and higher global COP of the units
➤➤ Low condensing fans energy consumption: the request of Energy Investment Allowance (EIA) from Netherlands Enterprise
Agency is to have a specific power consumption of the condenser of maximum 21 W per kW condenser power output

Main Features CRIO/BS CRIO/HE CRIO/HE+


Inverter
Desuperheater
Heat recovery
ΔT10K -
21 W/kW - -

standard equipment Available on request - not available

According to the installation Country, please consult the following regulations:

https://english.rvo.nl/subsidies-programmes/energy-investment-allowance-eia

https://certificats-economie-energie.net/

16 www.euroklimat.it
R290 Gas detector & Calibration kit
Gas detector – Main features

PX2 - PolyXeta®2 gas warning device for R290 Propane gas is designed to detect
combustible gases in the hazardous areas of zones 2 according to Directive 2014/34/
EU.

»» ATEX certified
»» Standard Alarm setting: 10% of LFL
»» 4 – 20 mA output signal
»» RS485-Modbus output signal
»» Alarm and fault signal relays
»» Separate power supply 230V-1ph-50Hz

The complete manual of the component is always attached at the end of EK installation
manual.

Calibration kit

At least once a year the component must be checked and calibrated properly to comply with the requirements of
European Regulations and Standards.
Euroklimat can provide the equipment necessary for calibration. The Calibration kit, available as accessory for all
models is made of the following components:

»» Gas application kit:


it must be put on the sensor head to convey test gas/zero gas.
It allows a better and more precise measurement of the substance.

»» Service Tool:
it is necessary for gas detector version without display (our standard) and allows
an easy and simple access to zero and gain calibration.

»» Kit for withdrawal of gas consisting of flow meter and pressure regulator indicators

NOTE: Only a qualified technician must perform the calibration procedure.


Zero gas - Synthetic air (20 % O2, 80 % N, < 10 % RH) and Test gas bottles are not included in the
Calibration kit accessory given by Euroklimat.

www.euroklimat.it 17
Refrigerant Circuit Diagram

High thickness copper tubes State-of-the-art brazing PED test and certification

The copper pipes used for the Our welders are all certified and constantly CRIO Heat Pumps are conform to Directive
construction of the refrigeration circuit are follow training and updating courses on 2014/68 / EU (PED) relating to risk control
of high quality Made in Europe, certified welding techniques. and safety for pressure equipment,
and tested according to the strictest We use a special alloy with silver to obtain provides for compliance with essential
industry standards and offer a greater an extremely safe and reliable seal over safety requirements of all the systems
guarantee of durability thanks to the high time. (assemblies) and of the single equipment
thickness. operating at a maximum allowable
pressure greater than 0.5 relative bar (eg
pressure vessels, pipes and accessories)
placed on the European market.

18 www.euroklimat.it
How to select
The below legend allows you to easily select the proper configuration of CRIO units.

CRIO / BS - B / ST / AS XXX - 1 - 1 P E - 1p3

Series
CRIO = Process MT

Families
BS = Business
HE = High Efficiency
HE+ = High Efficiency Plus
(EIA Compliance)

Configurations
B = Base
I = Integrata (*)

Versions
ST = Standard
LN = Low Noise
SL = Super Low noise

Solutions
AS = Standard
DS = Desuperheater
HR = Total Heat Recovery
SP = Special

Range Cooling capacity


@ nominal conditions

Range Compressor number


1 = One compressor

Range Circuit number


1 = One circuit
2 = Two circuits

Compressor type
P = Semi-hermetics piston
V = Semi-hermetics screw

Structures
E = Vertical coils
V = “V” shaped coils

Only for I (Integrated configuration)


1ps = 1 pump - std pressure (1.5 bar)
2ps = 2 pumps - std pressure (1.5 bar)
1px = 1 pump - pressure “X”
2px = 2 pumps - pressure “X”

All configurable models comply with current European Directives and Regulations
and are accompanied by a declaration of conformity and a CE mark.
www.euroklimat.it 19
Heat recovery
What is Waste Heat? Heatout
Condenser
All air-conditioning and refrigerating systems transfer heat from one location to another
through the use of electrical work.
At the evaporator heat exchanger, heat is drawn into the system to provide indoor cooling
while heat leaves the system in the form of wasted heat at the condenser (see figure Electrical
Expansion Compressor Workin
below). valve
The amount of wasted heat is higher than the cooling that the process creates.conditions
to develop a new algorithm for adjusting the defrost threshold and the time between one
defrost and another.
Evaporator
Heatin

Is it possible to save Energy by recovering waste heat from chillers?

The answer is Yes: this heat, which is otherwise wasted to the environment, can be used for different purposes, such as building/room
heating, sanitary hot water and process heat applications.

Benefits of Heat Recovery

The use of a recovery system to generate hot water can reduce the total energy needs of a building or/and a process and allows a
significant increase of the global efficiency of the system.
The benefits of Heat recovery systems are several:

Increased Efficiency, up to a COP of about 3, due to the possibility to use both chilled and hot water for different purposes. To better
understand this point, we can analyze the COP (Coefficient of Performance) of the unit with and without Heat Recovery. According to its
definition, the COP is the ratio between Q (useful heat) and W (electrical work consumed). For a Heat Recovery system, the equation that
quantifies the combined benefit of hot and cold water can be expressed as:
Heat Heatin
COPCooling = out +
Workin Workin

Reduction of Energy costs: if there are simultaneous heating and cooling loads, it’s possible to recover heat from chillers instead of
rejecting it to the environment. This gives a double benefit: recovered heat reduces the costs of purchased heat and also reduces the
ancillary power necessary to reject the heat (for example cooling towers and/or dry coolers).
A qualitative representation of the cost benefits compared to standard heat generation methods is shown below:

Energy cost comparison (E x 1000 MBH)


35
30 28,43 29,32
25
20
15 14,51

10 8,42
5
0
Heat Recovery Natural Gas Boiler Fuel Oil Boiler Electric Boiler

Reduced Environmental Emissions: energy recovery not only reduce operating costs, but also reduce emissions to the environment.
Heat recovery systems allows the reduction of heat generated by burning fossil fuels (such as natural gas), and consequently the
reduction of site emissions.

Energy codes and Government incentives: considering the benefits of the above-mentioned points, in different countries there are
standards and building codes that require condenser-water heat recovery for service water heating and/or economical incentives for the
installation of recovery systems

20 www.euroklimat.it
Different types of Heat recovery
Option available
DS (DESUPERHEATER)
An additional BPHE (brazed plate heat exchanger) heat exchanger is installed between compressor and air-cooled condenser.
Main Features: • Captures heat from superheated refrigerant, exploiting the hot discharge gas
• Only small quantity of heat is available since only superheat is removed from the refrigerant (depending on
the temperature requirement for hot water is possible to recover up to 20% of the total condensing heat)
• Hot water temperatures up to 55°C can be achieved
By installing a BPHE Desupeheater, the hot water produced can be used for: Room heating, Sanitary hot water, Process hot water.

P
[MPa]

Superheat
Pc

Pe
Refrigeration effect

h [kJ/kg]

HR (TOTAL MODULATING HEAT RECOVERY)


An additional BPHE (brazed plate heat exchanger) is installed, the design of the refrigerant circuit allows to recover the total available
condenser heat. Main Features:
• Captures heat from refrigerant condensing process
• A larger quantity of heat is available compared to desuperheater: if necessary, the full condensing process may be used to produce
hot water
• Hot water temperatures up to 55°C can be achieved

P
[MPa]

Heat recovery
Pc

Pe
Refrigeration effect

h [kJ/kg]

The solution proposed by Euroklimat for Total Heat Recovery is a Modulating solution, based on the concept that the recovery load
may vary during the function of the unit and, as a consequence, there could be:
• A total rejection of the condenser heat to the environment (0% Heat Recovery)
• A partial recovery of the available condenser heat (Variable from 0% to 100%)
• A total recovery of the heat (100% Heat Recovery)
Why choosing Modulating Heat Recovery?
• Innovative solution
• Dedicated software
• Possibility to adapt and modulate the heat production according to requested thermal loads

www.euroklimat.it 21
/BS
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

7-1-1 PE 19-1-1 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 6,9 - 19,4 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54. To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 64-66

22 www.euroklimat.it
Technical data
7-1-1 PE
/BS
19-1-1 PE
CRIO/BS R290 range 7-1-1 PE 9-1-1 PE 12-1-1 PE 17-1-1 PE 19-1-1 PE
COOLING
Cooling capacity (1) [kW] 6,9 8,9 12,4 16,8 19,4
Total power input (1) [kW] 3,6 4,4 6 7,9 9,4
EER - Energy Efficiency Ratio - 1,90 2,03 2,07 2,14 2,06
Saved CO2 equivalent Ton (*) [CO2 Ton] 3,4 5,4 6 10,2 11,3
“Ecodesign’’ compliance for process application (SEPR) - 2,53 2,83 2,64 2,98 2,80
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290
GWP - 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 0,9 1,4 1,6 2,6 2,9
Independent gas circuits [n°] 1 1 1 1 1
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 1 1 1 1 1
Steps of capacity for each compressor (std) - - - - - -
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 1 1 1 1 1
Fans power input (total)
(1)
[kW] 0,3 0,5 0,5 0,8 0,8
Total air flow [m3/h] 4.000 6.300 6.200 11.650 12.000
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 1,7 2,2 3,0 4,1 4,7
Evaporator pressure drop (1) [kPa] 26 20 23 37 24
DESUPERHEATER (option)
Heating capacity (2) [kW] 1,6 1,9 2,5 3,5 4
Water flow [m3/h] 0,28 0,33 0,44 0,60 0,69
Pressure drop (water side) [kPa] 5,1 5,1 5,2 5,2 5,2
HEAT RECOVERY (option)
Heating capacity (2) [kW] 9,9 12,3 17,3 22,9 27,2
Water flow [m3/h] 1,7 2,1 3,0 4,0 4,7
Pressure drop (water side) [kPa] 15,1 10,7 30,7 21,7 21,3
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 7,0 8,7 12,5 14,1 16,6
Locked rotor current – LRA without pump [A] 52,9 64,1 88,3 104,2 119,0
Maximum absorbed current - FLA without pump [A] 12,7 14,8 21,6 23,5 30,6
HYDRONIC KIT (option)
Buffer tank capacity [L] 30 30 30 60 60
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - - - - - -
Pump motor nominal power [kW] 0,37 0,37 0,37 0,55 0,55
Pump motor nominal current [A] 1,4 1,4 1,4 1,9 1,9
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - - - IE3 IE3 IE3
Pump motor nominal power [kW] 0,55 0,55 0,75 0,9 0,9
Pump motor nominal current [A] 2 2 1,9 2,5 2,5
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 1/2" (DN15) 1/2" (DN15) 1" (DN 25) 1" (DN 25) 1" (DN 25)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 82 79 79 82 83
Total sound pressure (ST version) - at 1 m distance [db(A)] 67 63 63 65 66
Total sound pressure (ST version) - at 10 m distance [db(A)] 51 48 48 51 52
Total sound power (LN version) [db(A)] 79 76 76 79 80
Total sound pressure (LN version) - at 1 m distance [db(A)] 64 60 60 62 63
Total sound pressure (LN version) - at 10 m distance [db(A)] 48 45 45 48 49
Total sound power (SL version) [db(A)] 77 74 74 77 78
Total sound pressure (SL version) - at 1 m distance [db(A)] 62 58 58 60 61
Total sound pressure (SL version) - at 10 m distance [db(A)] 46 43 43 46 47
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 1.230 1.380 1.380 1.680 1.680
Width BASE Unit [mm] 685 835 835 1.025 1.025
Weigth BASE unit [kg] 190 300 300 410 420
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 1.730 1.380 1.380 1.680 1.680
Width INTEGRATA Unit [mm] 685 835 835 1.025 1.025
Weigth INTEGRATA unit (shipping weight) [kg] 215 325 325 447 457
Weigth INTEGRATA unit (operating weight) [kg] 245 355 355 507 517

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 23
/BS
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

23-1-1 PE 55-1-1 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 23,4 - 55,3 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54. To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 64-66

24 www.euroklimat.it
Technical data
23-1-1 PE
/BS
55-1-1 PE
CRIO/BS R290 range 23-1-1 PE 28-1-1 PE 33-1-1 PE 39-1-1 PE 48-1-1 PE 55-1-1 PE
COOLING
Cooling capacity (1) [kW] 23,4 28,1 32,7 39,2 47,9 55,3
Total power input (1) [kW] 10 12,6 15,2 18,1 22,1 27,3
EER - Energy Efficiency Ratio - 2,33 2,24 2,14 2,16 1,90 2,03
Saved CO2 equivalent Ton (*) [CO2 Ton] 13,3 14,2 17,7 19,9 25,3 26,1
“Ecodesign’’ compliance for process application (SEPR) - 3,02 2,89 2,99 2,88 3,11 2,93
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290 R290
GWP - 3 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 3,5 3,7 4,6 5,2 6,6 6,8
Independent gas circuits [n°] 1 1 1 1 1 1
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 1 1 1 1 1 1
Steps of capacity for each compressor (std) - - - - - - -
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 1 1 2 2 2 2
Fans power input (total)
(1)
[kW] 0,7 0,9 1,7 1,7 2,9 3,7
Total air flow [m3/h] 10.600 11.150 22.400 22.300 35.200 37.800
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 5,7 6,8 7,9 9,5 11,6 13,4
Evaporator pressure drop (1) [kPa] 40 30 43 22 26 26
DESUPERHEATER (option)
Heating capacity (2) [kW] 4,2 5 5,7 7,3 8,9 11,2
Water flow [m3/h] 0,72 0,87 0,99 1,27 1,54 1,95
Pressure drop (water side) [kPa] 5,2 5,2 5,3 5,3 5,4 5,5
HEAT RECOVERY (option)
Heating capacity (2) [kW] 31,1 38,5 45 53,7 64,2 75,7
Water flow [m3/h] 5,4 6,7 7,8 9,4 11,2 13,2
Pressure drop (water side) [kPa] 17,6 25,7 29,5 25,9 23,9 25,3
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 19,1 21,4 27,5 34,1 42,6 50,2
Locked rotor current – LRA without pump [A] 138,1 204,6 228,2 243,0 282,3 330,7
Maximum absorbed current - FLA without pump [A] 37,8 38,8 47,8 57,7 70,3 83,9
HYDRONIC KIT (option)
Buffer tank capacity [L] 60 60 160 160 290 290
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 0,55 0,9 0,9 0,9 1,1 1,1
Pump motor nominal current [A] 1,9 2,5 2,5 2,5 3,3 3,3
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 1,5 1,5 1,5 1,5 2,2 2,2
Pump motor nominal current [A] 4,1 4,1 4,1 4,1 4,7 4,7
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 1" (DN 25) 1" 1/2 (DN 40) 1" 1/2 (DN 40) 1" 1/2 (DN 40) 1" 1/2 (DN 40) 1" 1/2 (DN 40)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 84 84 87 88 87 87
Total sound pressure (ST version) - at 1 m distance [db(A)] 67 67 70 71 69 69
Total sound pressure (ST version) - at 10 m distance [db(A)] 53 53 56 57 56 56
Total sound power (LN version) [db(A)] 81 81 84 85 84 84
Total sound pressure (LN version) - at 1 m distance [db(A)] 64 64 67 68 66 66
Total sound pressure (LN version) - at 10 m distance [db(A)] 50 50 53 54 53 53
Total sound power (SL version) [db(A)] 79 79 82 83 82 82
Total sound pressure (SL version) - at 1 m distance [db(A)] 62 62 65 66 64 64
Total sound pressure (SL version) - at 10 m distance [db(A)] 48 48 51 52 51 51
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 1.680 1.680 2.330 2.330 2.980 2.980
Width BASE Unit [mm] 1.025 1.025 1.025 1.025 1.025 1.025
Weigth BASE unit [kg] 440 510 660 630 830 840
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 1.680 1.680 2.330 2.330 2.980 2.980
Width INTEGRATA Unit [mm] 1.025 1.025 1.025 1.025 1.025 1.025
Weigth INTEGRATA unit (shipping weight) [Kg] 477 550 711 681 930 940
Weigth INTEGRATA unit (operating weight) [Kg] 537 610 871 841 1.220 1.230

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 25
/BS
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

38-2-2 PE 95-2-2 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 38,4 - 94,8 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54. To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 64-66

26 www.euroklimat.it
Technical data
38-2-2 PE
/BS
95-2-2 PE
CRIO/BS R290 range 38-2-2 PE 49-2-2 PE 58-2-2 PE 68-2-2 PE 79-2-2 PE 95-2-2 PE
COOLING
Cooling capacity (1) [kW] 38,4 48,5 58 68 79,2 94,8
Total power input (1) [kW] 18,5 22,2 27,2 30,4 38,5 44,6
EER - Energy Efficiency Ratio - 2,07 2,18 2,13 2,24 2,06 2,12
Saved CO2 equivalent Ton (*) [CO2 Ton] 20,4 26,3 28,3 36,3 38,1 47,8
“Ecodesign’’ compliance for process application (SEPR) - 2,83 3,26 3,08 3,12 2,98 3,02
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290 R290
GWP - 3 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 5,3 6,8 7,4 9,4 9,9 12,4
Independent gas circuits [n°] 2 2 2 2 2 2
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 2 2 2 2 2 2
Steps of capacity for each compressor (std) - - - - - - -
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 2 2 2 2 3 3
Fans power input (total)
(1)
[kW] 1,7 3,1 4,1 4 5,9 5,6
Total air flow [m3/h] 22.300 35.300 38.500 35.400 56.700 51.000
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 9,3 11,8 14,1 16,5 19,2 23,0
Evaporator pressure drop (1) [kPa] 25 24 23 23 30 32
DESUPERHEATER (option)
Heating capacity (2) [kW] 7,8 8,5 10,1 11,4 14,6 17,7
Water flow [m3/h] 1,37 1,48 1,76 1,99 2,54 3,09
Pressure drop (water side) [kPa] 5,2 5,3 5,2 5,3 5,3 5,4
HEAT RECOVERY (option)
Heating capacity (2) [kW] 53,2 64 77,5 90,6 107,8 128,5
Water flow [m3/h] 9,3 11,1 13,5 15,8 18,8 22,4
Pressure drop (water side) [kPa] 14,9 21 30,5 25 24 24,6
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 33,1 38,6 46,4 56,4 72,6 82,2
Locked rotor current – LRA without pump [A] 149,6 220,0 248,9 277,7 307,1 348,0
Maximum absorbed current - FLA without pump [A] 61,2 69,7 83,1 97,3 121,8 136,0
HYDRONIC KIT (option)
Buffer tank capacity [L] 160 160 160 160 290 290
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 0,9 1,1 1,1 2,2 2,2 2,2
Pump motor nominal current [A] 2,5 3,3 3,3 4,7 4,7 4,7
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 1,5 2,2 2,2 2,2 3 3
Pump motor nominal current [A] 4,1 4,7 4,7 4,7 6,4 6,4
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 1" 1/2 (DN 40) 1" 1/2 (DN 40) 2" (DN 50) 2" (DN 50) 2" (DN 50) 2"1/2 (DN 65)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 87 86 86 88 89 91
Total sound pressure (ST version) - at 1 m distance [db(A)] 70 69 69 70 71 73
Total sound pressure (ST version) - at 10 m distance [db(A)] 56 56 56 57 57 59
Total sound power (LN version) [db(A)] 84 83 83 85 86 88
Total sound pressure (LN version) - at 1 m distance [db(A)] 67 66 66 67 68 70
Total sound pressure (LN version) - at 10 m distance [db(A)] 53 53 53 54 54 56
Total sound power (SL version) [db(A)] 82 81 81 83 84 86
Total sound pressure (SL version) - at 1 m distance [db(A)] 65 64 64 65 66 68
Total sound pressure (SL version) - at 10 m distance [db(A)] 51 51 51 52 52 54
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 2.330 2.980 2.980 2.980 3.920 3.920
Width BASE Unit [mm] 1.025 1.025 1.025 1.025 1.025 1.025
Weigth BASE unit [kg] 700 940 970 1.000 1.200 1.260
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 2.980 2.980 2.980 2.980 3.920 3.920
Width INTEGRATA Unit [mm] 1.025 1.025 1.025 1.025 1.025 1.025
Weigth INTEGRATA unit (shipping weight) [kg] 751 1.008 1.038 1.070 1.302 1.362
Weigth INTEGRATA unit (operating weight) [kg] 911 1.168 1.198 1.230 1.592 1.652

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 27
/BS
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

108-2-2 PE 173-2-2 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 108,3 - 172,7 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54 To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 64-66

28 www.euroklimat.it
Technical data
108-2-2 PE
/BS
173-2-2 PE
CRIO/BS R290 range 108-2-2 PE 126-2-2 PE 137-2-2 PE 157-2-2 PE 173-2-2 PE
COOLING
Cooling capacity (1) [kW] 108,3 125,9 137,4 157,5 172,7
Total power input (1) [kW] 54,5 62,9 69,4 73,7 81,2
EER - Energy Efficiency Ratio - 1,99 2,00 1,98 2,14 2,13
Saved CO2 equivalent Ton (*) [CO2 Ton] 49,6 70,8 73,5 98,2 101,8
“Ecodesign’’ compliance for process application (SEPR) - 2,83 2,54 2,52 2,69 2,67
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290
GWP - 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 12,9 18,4 19,1 25,5 26,5
Independent gas circuits [n°] 2 2 2 2 2
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 2 2 2 2 2
Steps of capacity for each compressor (std) - - - - - -
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 3 3 3 4 4
Fans power input (total)
(1)
[kW] 6,4 5,1 5,6 5,1 5,8
Total air flow [m3/h] 53.200 64.200 66.500 75.000 78.000
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 26,2 30,5 33,3 38,2 41,9
Evaporator pressure drop (1) [kPa] 35 39 40 40 34
DESUPERHEATER (option)
Heating capacity (2) [kW] 22,4 27,8 30,2 34 37,6
Water flow [m3/h] 3,90 4,85 5,27 5,92 6,55
Pressure drop (water side) [kPa] 5,5 5,6 5,7 10,0 11,0
HEAT RECOVERY (option)
Heating capacity (2) [kW] 151,4 176 194,8 215,9 235,1
Water flow [m3/h] 26,4 30,7 33,9 37,6 41,0
Pressure drop (water side) [kPa] 26,7 30,6 36,1 37,9 39,4
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 97,4 92,0 111,2 113,5 119,1
Locked rotor current – LRA without pump [A] 410,0 385,7 468,3 559,0 660,8
Maximum absorbed current - FLA without pump [A] 163,2 161,4 188,6 189,4 207,0
HYDRONIC KIT (option)
Buffer tank capacity [L] 290 500 500 470 470
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 2,2 3 3 3 3
Pump motor nominal current [A] 4,7 6,4 6,4 6,4 6,4
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 4 4 4 5,5 5,5
Pump motor nominal current [A] 8,7 8,7 8,7 10,6 10,6
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 2"1/2 (DN 65) 3" (DN 80) 3" (DN 80) 3" (DN 80) 3" (DN 80)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 91 90 94 95 95
Total sound pressure (ST version) - at 1 m distance [db(A)] 73 71 75 76 76
Total sound pressure (ST version) - at 10 m distance [db(A)] 59 58 62 63 63
Total sound power (LN version) [db(A)] 88 87 91 92 92
Total sound pressure (LN version) - at 1 m distance [db(A)] 70 68 72 73 73
Total sound pressure (LN version) - at 10 m distance [db(A)] 56 55 59 60 60
Total sound power (SL version) [db(A)] 86 85 89 90 90
Total sound pressure (SL version) - at 1 m distance [db(A)] 68 66 70 71 71
Total sound pressure (SL version) - at 10 m distance [db(A)] 54 53 57 58 58
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 3.920 4.200 4.200 5.500 5.500
Width BASE Unit [mm] 1.025 1.185 1.185 1.535 1.535
Weigth BASE unit [kg] 1.280 1.630 1.670 1.700 1.920
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 3.920 5.000 5.000 5.500 5.500
Width INTEGRATA Unit [mm] 1.025 1.185 1.185 1.535 1.535
Weigth INTEGRATA unit (shipping weight) [kg] 1.382 1.769 1.809 1.835 2.055
Weigth INTEGRATA unit (operating weight) [kg] 1.672 2.269 2.309 2.305 2.525

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 29
/BS
MCX
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Microchannel


R290 | GWP=3 heat exchanger piston compressor condensing colils

158-2-2 PV 182-2-2 PV
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 158,3 - 181,8 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Plate-type. Made of AISI 316 steel complete with water differential pressure switch. Shell covered with closed-cell neoprene anti-condensate materia
Shell & tubes. All extremely efficient with low refrigerant charge and very stable operating performance due to excellent refrigerant distribution, thermally
insulated by vapour-proof closed celle.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54 To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 64-66

30 www.euroklimat.it
Technical data
158-2-2 PV
/BS
182-2-2 PV
CRIO/BS R290 range 158-2-2 PV 174-2-2 PV 182-2-2 PV
COOLING
Cooling capacity (1) [kW] 158,3 173,9 181,8
Total power input (1) [kW] 72,8 80,1 84,4
EER - Energy Efficiency Ratio - 2,17 2,17 2,15
Saved CO2 equivalent Ton (*) [CO2 Ton] 64,6 69,5 69,5
“Ecodesign’’ compliance for process application (SEPR) - 2,69 2,68 2,69
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290
GWP - 3 3 3
Charge of refrigerant - Base unit [kg] 16,8 18,1 18,1
Independent gas circuits [n°] 2 2 2
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 2 2 2
Steps of capacity for each compressor (std) - - - -
Condensing coils type - Microchannel Microchannel Microchannel
Fans type - Axial EC
Fans quantity [n°] 4 4 4
Fans power input (total)
(1)
[kW] 4,6 5,1 5,3
Total air flow [m3/h] 75.200 77.900 79.100
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 38,4 42,1 44,1
Evaporator pressure drop (1) [kPa] 40 34 37
DESUPERHEATER (option)
Heating capacity (2) [kW] 34 37,6 39,4
Water flow [m3/h] 5,92 6,55 6,86
Pressure drop (water side) [kPa] 10,0 11,0 11,0
HEAT RECOVERY (option)
Heating capacity (2) [kW] 215,9 235,1 246,8
Water flow [m3/h] 37,6 41,0 43,0
Pressure drop (water side) [kPa] 37,9 39,4 30,5
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 113,5 119,1 127,3
Locked rotor current – LRA without pump [A] 559,0 660,8 704,4
Maximum absorbed current - FLA without pump [A] 189,4 207,0 222,2
HYDRONIC KIT (option)
Buffer tank capacity [L] 290 290 290
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - IE3 IE3 IE3
Pump motor nominal power [kW] 3 3 3
Pump motor nominal current [A] 6,4 6,4 6,4
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3
Pump motor nominal power [kW] 5,5 5,5 5,5
Pump motor nominal current [A] 10,6 10,6 10,6
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 3" (DN 80) 3" (DN 80) 3" (DN 80)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 95 95 97
Total sound pressure (ST version) - at 1 m distance [db(A)] 76 76 78
Total sound pressure (ST version) - at 10 m distance [db(A)] 63 63 65
Total sound power (LN version) [db(A)] 92 92 94
Total sound pressure (LN version) - at 1 m distance [db(A)] 73 73 75
Total sound pressure (LN version) - at 10 m distance [db(A)] 60 60 62
Total sound power (SL version) [db(A)] 90 90 92
Total sound pressure (SL version) - at 1 m distance [db(A)] 71 71 73
Total sound pressure (SL version) - at 10 m distance [db(A)] 58 58 60
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 3.100 3.100 3.100
Width BASE Unit [mm] 2.345 2.345 2.345
Weigth BASE unit [kg] 1.925 1.940 1.945
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 3.100 3.100 3.100
Width INTEGRATA Unit [mm] 2.345 2.345 2.345
Weigth INTEGRATA unit (shipping weight) [kg] 2.035 2.050 2.055
Weigth INTEGRATA unit (operating weight) [kg] 2.325 2.340 2.345

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 31
/HE
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

10-1-1 PE 24-1-1 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 6,9 - 19,4 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54. To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 67-69

32 www.euroklimat.it
Technical data
10-1-1 PE
/HE
24-1-1 PE
CRIO/HE R290 range 10-1-1 PE 14-1-1 PE 17-1-1 PE 20-1-1 PE 24-1-1 PE
COOLING
Cooling capacity (1) [kW] 9,5 13,6 17,1 20,4 23,9
Total power input (1) [kW] 4,0 5,5 7,2 9,8 9,7
EER - Energy Efficiency Ratio - 2,40 2,45 2,38 2,09 2,45
Saved CO2 equivalent Ton (*) [CO2 Ton] 8,3 10,7 11,5 15,5 15,5
“Ecodesign’’ compliance for process application (SEPR) - 3,23 3,07 3,12 3,21 3,28
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290
GWP - 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 2,2 2,8 3,0 4,0 4,0
Independent gas circuits [n°] 1 1 1 1 1
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 1 1 1 1 1
Steps of capacity for each compressor (std) - - - - - -
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 1 1 1 2 2
Fans power input (total)
(1)
[kW] 0,3 0,3 0,5 1,7 0,8
Total air flow [m3/h] 8.100 8.250 9.800 22.100 17.500
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 2,3 3,3 4,1 4,9 5,8
Evaporator pressure drop (1) [kPa] 22 27 27 27 28
DESUPERHEATER (option)
Heating capacity (2) [kW] 1,9 2,5 3,45 3,96 4
Water flow [m3/h] 0,33 0,44 0,60 0,69 0,70
Pressure drop (water side) [kPa] 5,1 5,2 5,2 5,2 5,2
HEAT RECOVERY (option)
Heating capacity (2) [kW] 12,2 17,2 22,7 27,2 30,8
Water flow [m3/h] 2,1 3,0 4,0 4,7 5,4
Pressure drop (water side) [kPa] 11 30,7 21,5 21,3 17,4
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 9,3 13,1 14,1 17,7 20,2
Locked rotor current – LRA without pump [A] 65,0 89,2 104,2 120,9 140,0
Maximum absorbed current - FLA without pump [A] 15,7 22,5 23,5 32,5 39,7
HYDRONIC KIT (option)
Buffer tank capacity [L] 60 60 60 160 160
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - - - - - -
Pump motor nominal power [kW] 0,37 0,37 0,55 0,55 0,55
Pump motor nominal current [A] 1,4 1,4 1,9 1,9 1,9
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - - IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 0,55 0,75 0,9 0,9 1,5
Pump motor nominal current [A] 2 1,9 2,5 2,5 4,1
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 1/2" (DN15) 1" (DN 25) 1" (DN 25) 1" (DN 25) 1" (DN 25)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 73 76 79 82 82
Total sound pressure (ST version) - at 1 m distance [db(A)] 56 59 62 65 65
Total sound pressure (ST version) - at 10 m distance [db(A)] 43 45 48 51 51
Total sound power (LN version) [db(A)] 70 73 76 79 79
Total sound pressure (LN version) - at 1 m distance [db(A)] 53 56 59 62 62
Total sound pressure (LN version) - at 10 m distance [db(A)] 40 42 45 48 48
Total sound power (SL version) [db(A)] 68 71 74 77 77
Total sound pressure (SL version) - at 1 m distance [db(A)] 51 54 57 60 60
Total sound pressure (SL version) - at 10 m distance [db(A)] 38 40 43 46 46
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 1.680 1.680 1.680 2.330 2.330
Width BASE Unit [mm] 1.025 1.025 1.025 1.025 1.025
Weigth BASE unit [kg] 350 360 410 550 560
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 1.680 1.680 1.680 2.330 2.330
Width INTEGRATA Unit [mm] 1.025 1.025 1.025 1.025 1.025
Weigth INTEGRATA unit (shipping weight) [kg] 386 396 447 598 608
Weigth INTEGRATA unit (operating weight) [kg] 446 456 507 758 768

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 33
/HE
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

30-1-1 PE 56-1-1 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 23,4 - 55,3 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54. To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 67-69

34 www.euroklimat.it
Technical data
30-1-1 PE
/HE
56-1-1 PE
CRIO/HE R290 range 30-1-1 PE 35-1-1 PE 41-1-1 PE 48-1-1 PE 56-1-1 PE
COOLING
Cooling capacity (1) [kW] 29,8 34,7 41 48 56,2
Total power input (1) [kW] 11,7 13,9 18,4 21,3 24,1
EER - Energy Efficiency Ratio - 2,56 2,50 2,23 2,26 2,33
Saved CO2 equivalent Ton (*) [CO2 Ton] 20,4 23,5 24,5 29,4 39
“Ecodesign’’ compliance for process application (SEPR) - 3,39 3,35 3,21 3,19 3,12
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290
GWP - 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 5,3 6,1 6,3 7,6 10,1
Independent gas circuits [n°] 1 1 1 1 1
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 1 1 1 1 1
Steps of capacity for each compressor (std) - - - - - -
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 2 2 2 2 3
Fans power input (total)
(1)
[kW] 0,8 1,3 2,8 2,6 1,6
Total air flow [m3/h] 19.700 23.600 34.700 30.900 30.000
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 7,2 8,4 9,9 11,6 13,6
Evaporator pressure drop (1) [kPa] 33 18 20 26 26
DESUPERHEATER (option)
Heating capacity (2) [kW] 5 5,66 7,3 8,86 11,2
Water flow [m3/h] 0,87 0,99 1,27 1,54 1,95
Pressure drop (water side) [kPa] 5,2 5,3 5,3 5,4 5,5
HEAT RECOVERY (option)
Heating capacity (2) [kW] 38,2 45 54,3 64,2 75,7
Water flow [m3/h] 6,7 7,8 9,5 11,2 13,2
Pressure drop (water side) [kPa] 25,5 29,5 26,2 23,9 25,3
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 22,5 27,5 37,8 42,6 47,7
Locked rotor current – LRA without pump [A] 206,5 228,2 248,5 282,3 327,1
Maximum absorbed current - FLA without pump [A] 40,7 47,8 63,2 70,3 80,3
HYDRONIC KIT (option)
Buffer tank capacity [L] 290 290 290 290 290
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 0,9 0,9 0,9 1,1 1,1
Pump motor nominal current [A] 2,5 2,5 2,5 3,3 3,3
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 1,5 1,5 1,5 2,2 2,2
Pump motor nominal current [A] 4,1 4,1 4,1 4,7 4,7
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 1" 1/2 (DN 40) 1" 1/2 (DN 40) 1" 1/2 (DN 40) 1" 1/2 (DN 40) 2" (DN 50)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 81 84 86 87 86
Total sound pressure (ST version) - at 1 m distance [db(A)] 63 66 68 69 68
Total sound pressure (ST version) - at 10 m distance [db(A)] 50 53 55 56 54
Total sound power (LN version) [db(A)] 78 81 83 84 83
Total sound pressure (LN version) - at 1 m distance [db(A)] 60 63 65 66 65
Total sound pressure (LN version) - at 10 m distance [db(A)] 47 50 52 53 51
Total sound power (SL version) [db(A)] 76 79 81 82 81
Total sound pressure (SL version) - at 1 m distance [db(A)] 58 61 63 64 63
Total sound pressure (SL version) - at 10 m distance [db(A)] 45 48 50 51 49
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 2.980 2.980 2.980 2.980 3.920
Width BASE Unit [mm] 1.025 1.025 1.025 1.025 1.025
Weigth BASE unit [kg] 720 740 810 850 960
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 2.980 2.980 2.980 2.980 3.920
Width INTEGRATA Unit [mm] 1.025 1.025 1.025 1.025 1.025
Weigth INTEGRATA unit (shipping weight) [kg] 803 823 893 950 1.060
Weigth INTEGRATA unit (operating weight) [kg] 1.093 1.113 1.183 1.240 1.350

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 35
/HE
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

41-2-2 PE 116-2-2 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 38,4 - 94,8 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54. To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 67-69

36 www.euroklimat.it
Technical data
41-2-2 PE
/HE
116-2-2 PE
CRIO/HE R290 range 41-2-2 PE 48-2-2 PE 60-2-2 PE 70-2-2 PE 83-2-2 PE 97-2-2 PE 116-2-2 PE
COOLING
Cooling capacity (1)
[kW] 41,4 47,8 60,1 70 82,5 97,1 116,1
Total power input (1) [kW] 17,3 18,8 24,6 29,4 33,5 42,2 47,6
EER - Energy Efficiency Ratio - 2,40 2,54 2,44 2,38 2,46 2,30 2,44
Saved CO2 equivalent Ton (*) [CO2 Ton] 32,9 39,4 41,6 45,2 65,5 67,5 87,6
“Ecodesign’’ compliance for process application (SEPR) - 3,28 3,33 3,40 3,39 3,28 3,27 3,32
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290 R290 R290
GWP - 3 3 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 8,5 10,2 10,8 11,7 17,0 17,5 22,8
Independent gas circuits [n°] 2 2 2 2 2 2 2
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 2 2 2 2 2 2 2
Steps of capacity for each compressor (std) - - - - - - - -
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 3 3 3 3 3 3 4
Fans power input (total)
(1)
[kW] 1,2 1,1 2,5 4,3 2,4 4,7 3,3
Total air flow [m3/h] 29.100 26.800 35.100 46.600 50.300 62.500 64.900
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 10,0 11,6 14,6 17,0 20,0 23,5 28,1
Evaporator pressure drop (1) [kPa] 18 24 24 24 25 29 34
DESUPERHEATER (option)
Heating capacity (2) [kW] 7,84 8,5 10,1 11,4 14,6 17,72 22,4
Water flow [m3/h] 1,37 1,48 1,76 1,99 2,54 3,09 3,90
Pressure drop (water side) [kPa] 5,2 5,3 5,2 5,3 5,3 5,4 5,5
HEAT RECOVERY (option)
Heating capacity (2) [kW] 54,4 62 77,7 90,3 108,9 129,8 152,9
Water flow [m3/h] 9,5 10,8 13,5 15,7 19,0 22,6 26,6
Pressure drop (water side) [kPa] 15 20,5 30,5 25 24,2 24,8 26,9
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 34,3 39,3 43,9 59,4 72,6 82,2 100,5
Locked rotor current – LRA without pump [A] 151,5 177,8 245,3 282,4 307,1 348,0 414,6
Maximum absorbed current - FLA without pump [A] 63,1 77,5 79,5 102,0 121,8 136,0 167,8
HYDRONIC KIT (option)
Buffer tank capacity [L] 290 290 290 290 500 500 470
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 1,1 1,1 1,1 2,2 2,2 2,2 2,2
Pump motor nominal current [A] 3,3 3,3 3,3 4,7 4,7 4,7 4,7
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 1,5 2,2 2,2 3 3 4 4
Pump motor nominal current [A] 4,1 4,7 4,7 6,4 6,4 8,7 8,7
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 1" 1/2 (DN 40) 1" 1/2 (DN 40) 2" (DN 50) 2" (DN 50) 2" (DN 50) 2"1/2 (DN 65) 2"1/2 (DN 65)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 83 84 85 88 88 90 89
Total sound pressure (ST version) - at 1 m distance [db(A)] 65 66 67 70 69 71 70
Total sound pressure (ST version) - at 10 m distance [db(A)] 51 52 53 56 56 58 57
Total sound power (LN version) [db(A)] 80 81 82 85 85 87 86
Total sound pressure (LN version) - at 1 m distance [db(A)] 62 63 64 67 66 68 67
Total sound pressure (LN version) - at 10 m distance [db(A)] 48 49 50 53 53 55 54
Total sound power (SL version) [db(A)] 78 79 80 83 83 85 84
Total sound pressure (SL version) - at 1 m distance [db(A)] 60 61 62 65 64 66 65
Total sound pressure (SL version) - at 10 m distance [db(A)] 46 47 48 51 51 53 52
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 3.920 3.920 3.920 3.920 4.200 4.200 5.500
Width BASE Unit [mm] 1.025 1.025 1.025 1.025 1.185 1.185 1.535
Weigth BASE unit [kg] 940 970 1.080 1.150 1.460 1.510 1.710
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 3.920 3.920 3.920 3.920 5.000 5.000 5.500
Width INTEGRATA Unit [mm] 1.025 1.025 1.025 1.025 1.185 1.185 1.535
Weigth INTEGRATA unit (shipping weight) [kg] 1.040 1.070 1.180 1.252 1.592 1.642 1.837
Weigth INTEGRATA unit (operating weight) [kg] 1.330 1.360 1.470 1.542 2.092 2.142 2.307

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 37
/HE
MCX
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Microchannel


R290 | GWP=3 heat exchanger piston compressor condensing colils

130-2-2 PV 185-2-2 PV
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 108,3 - 172,7 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Plate-type. Made of AISI 316 steel complete with water differential pressure switch. Shell covered with closed-cell neoprene anti-condensate materia
Shell & tubes. All extremely efficient with low refrigerant charge and very stable operating performance due to excellent refrigerant distribution, thermally
insulated by vapour-proof closed celle.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54 To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 67-69

38 www.euroklimat.it
Technical data
130-2-2 PV
/HE
185-2-2 PV
CRIO/HE R290 range 130-2-2 PV 142-2-2 PV 161-2-2 PV 175-2-2 PV 185-2-2 PV
COOLING
Cooling capacity (1) [kW] 129,7 141,8 161,2 174,5 185,1
Total power input (1) [kW] 59,5 65,3 70,7 77,2 82,1
EER - Energy Efficiency Ratio - 2,18 2,17 2,28 2,26 2,26
Saved CO2 equivalent Ton (*) [CO2 Ton] 55,8 61,1 77 77,9 81,4
“Ecodesign’’ compliance for process application (SEPR) - 2,71 2,70 2,85 2,81 2,82
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290
GWP - 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 14,5 15,9 20,0 20,2 21,2
Independent gas circuits [n°] 2 2 2 2 2
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 2 2 2 2 2
Steps of capacity for each compressor (std) - - - - - -
Condensing coils type - Microchannel Microchannel Microchannel Microchannel Microchannel
Fans type - Axial EC
Fans quantity [n°] 4 4 6 6 6
Fans power input (1) (total) [kW] 3,5 3,9 4,1 4,5 4,9
Total air flow [m3/h] 68.900 71.400 96.000 99.000 101.200
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 31,4 34,4 39,1 42,3 44,9
Evaporator pressure drop (1) [kPa] 36 33 30 34 33
DESUPERHEATER (option)
Heating capacity (2) [kW] 27,84 30,24 34 37,6 39,4
Water flow [m3/h] 4,85 5,27 5,92 6,55 6,86
Pressure drop (water side) [kPa] 5,6 5,7 10,0 11,0 11,0
HEAT RECOVERY (option)
Heating capacity (2) [kW] 176,45 196,2 218,2 237,6 250,3
Water flow [m3/h] 30,7 34,2 38,0 41,4 43,6
Pressure drop (water side) [kPa] 29,6 36,5 38,2 39,7 30,9
ELECTRICAL DATA
Power supply - 400/3/50 400/3/50 400/3/50 400/3/50 400/3/50
Emergency power supply - 230/1/50 230/1/50 230/1/50 230/1/50 230/1/50
Maximum power input without pump [kW] 95,1 114,3 119,5 125,1 133,3
Locked rotor current – LRA without pump [A] 390,3 472,9 568,3 670,1 713,7
Maximum absorbed current - FLA without pump [A] 166,0 193,2 198,7 216,3 231,5
HYDRONIC KIT (option)
Buffer tank capacity [L] 290 290 290 290 290
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 3 3 3 3 3
Pump motor nominal current [A] 6,4 6,4 6,4 6,4 6,4
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 4 4 5,5 5,5 5,5
Pump motor nominal current [A] 8,7 8,7 10,6 10,6 10,6
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 3" (DN 80) 3" (DN 80) 3" (DN 80) 3" (DN 80) 3" (DN 80)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 90 94 95 95 97
Total sound pressure (ST version) - at 1 m distance [db(A)] 71 75 75 75 77
Total sound pressure (ST version) - at 10 m distance [db(A)] 58 62 63 63 65
Total sound power (LN version) [db(A)] 87 91 92 92 94
Total sound pressure (LN version) - at 1 m distance [db(A)] 68 72 72 72 74
Total sound pressure (LN version) - at 10 m distance [db(A)] 55 59 60 60 62
Total sound power (SL version) [db(A)] 85 89 90 90 92
Total sound pressure (SL version) - at 1 m distance [db(A)] 66 70 70 70 72
Total sound pressure (SL version) - at 10 m distance [db(A)] 53 57 58 58 60
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 3.100 3.100 4.450 4.450 4.450
Width BASE Unit [mm] 2.345 2.345 2.345 2.345 2.345
Weigth BASE unit [kg] 1.855 1.900 2.560 2.575 2.590
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 3.100 3.100 4.450 4.450 4.450
Width INTEGRATA Unit [mm] 2.345 2.345 2.345 2.345 2.345
Weigth INTEGRATA unit (shipping weight) [kg] 1.965 2.010 2.670 2.685 2.700
Weigth INTEGRATA unit (operating weight) [kg] 2.255 2.300 2.960 2.975 2.990

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 39
/HE+
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

10-1-1 PE 56-1-1 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 6,9 - 19,4 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54. To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 70-72

40 www.euroklimat.it
Technical data
10-1-1 PE
/HE+
56-1-1 PE
CRIO/HE+ R290 range 10-1-1 PE 14-1-1 PE 17-1-1 PE 21-1-1 PE 30-1-1 PE 36-1-1 PE 56-1-1 PE
COOLING
Cooling capacity (1) [kW] 9,5 13,6 17,1 20,7 29,8 36 56,2
Total power input (1) [kW] 4,0 5,5 7,2 8,5 11,7 13,5 24,1
EER - Energy Efficiency Ratio - 2,40 2,45 2,38 2,43 2,56 2,66 2,33
Saved CO2 equivalent Ton (*) [CO2 Ton] 8,3 10,7 11,5 15,1 20,4 27,9 39
“Ecodesign’’ compliance for process application (SEPR) - 3,23 3,07 3,12 3,26 3,39 3,42 3,12
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290 R290 R290
GWP - 3 3 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 2,2 2,8 3,0 3,9 5,3 7,2 10,1
Independent gas circuits [n°] 1 1 1 1 1 1 1
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 1 1 1 1 1 1 1
Steps of capacity for each compressor (std) - 1 (75%) 1 (75%) 1 (75%) 1 (75%) 1 (75%) 1 (75%) 1 (83%)
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 1 1 1 2 2 2 3
Fans power input (total)
(1)
[kW] 0,3 0,3 0,5 0,5 0,8 0,8 1,6
Total air flow [m3/h] 8.100 8.250 9.800 15.000 19.700 19.000 30.000
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 2,3 3,3 4,1 5,0 7,2 8,7 13,6
Evaporator pressure drop (1) [kPa] 22 27 27 27 33 19 26
DESUPERHEATER (option)
Heating capacity (2) [kW] 1,9 2,5 3,45 3,96 5 5,66 11,2
Water flow [m3/h] 0,33 0,44 0,60 0,69 0,87 0,99 1,95
Pressure drop (water side) [kPa] 5,1 5,2 5,2 5,2 5,2 5,3 5,5
HEAT RECOVERY (option)
Heating capacity (2) [kW] 12,2 17,2 22,7 27,1 38,2 45 75,7
Water flow [m3/h] 2,1 3,0 4,0 4,7 6,7 7,8 13,2
Pressure drop (water side) [kPa] 11 30,7 21,5 21 25,5 29,5 25,3
ELECTRICAL DATA
Power supply - 400/3/50 400/3/51 400/3/52 400/3/53 400/3/54 400/3/55 400/3/56
Emergency power supply - 230/1/50 230/1/51 230/1/52 230/1/53 230/1/54 230/1/55 230/1/56
Maximum power input without pump [kW] 9,3 13,1 14,1 17,7 22,5 27,5 47,7
Locked rotor current – LRA without pump [A] 65,0 89,2 104,2 120,9 206,5 228,2 327,1
Maximum absorbed current - FLA without pump [A] 15,7 22,5 23,5 32,5 40,7 47,8 80,3
HYDRONIC KIT (option)
Buffer tank capacity [L] 60 60 60 160 290 290 290
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - - - - - IE3 IE3 IE3
Pump motor nominal power [kW] 0,37 0,37 0,55 0,55 0,9 0,9 1,1
Pump motor nominal current [A] 1,4 1,4 1,9 1,9 2,5 2,5 3,3
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - - IE3 IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 0,55 0,75 0,9 0,9 1,5 1,5 2,2
Pump motor nominal current [A] 2 1,9 2,5 2,5 4,1 4,1 4,7
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 1/2" (DN15) 1" (DN 25) 1" (DN 25) 1" (DN 25) 1" 1/2 (DN 40) 1" 1/2 (DN 40) 2" (DN 50)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 73 76 79 80 81 84 86
Total sound pressure (ST version) - at 1 m distance [db(A)] 56 59 62 63 63 66 68
Total sound pressure (ST version) - at 10 m distance [db(A)] 43 45 48 49 50 53 54
Total sound power (LN version) [db(A)] 70 73 76 77 78 81 83
Total sound pressure (LN version) - at 1 m distance [db(A)] 53 56 59 60 60 63 65
Total sound pressure (LN version) - at 10 m distance [db(A)] 40 42 45 46 47 50 51
Total sound power (SL version) [db(A)] 68 71 74 75 76 79 81
Total sound pressure (SL version) - at 1 m distance [db(A)] 51 54 57 58 58 61 63
Total sound pressure (SL version) - at 10 m distance [db(A)] 38 40 43 44 45 48 49
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 1.680 1.680 1.680 2.330 2.980 2.980 3.920
Width BASE Unit [mm] 1.025 1.025 1.025 1.025 1.025 1.025 1.025
Weigth BASE unit [kg] 350 360 410 560 720 760 960
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 1.680 1.680 1.680 2.330 2.980 2.980 3.920
Width INTEGRATA Unit [mm] 1.025 1.025 1.025 1.025 1.025 1.025 1.025
Weigth INTEGRATA unit (shipping weight) [kg] 386 396 447 608 803 843 1.060
Weigth INTEGRATA unit (operating weight) [kg] 446 456 507 768 1.093 1.133 1.350

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 41
/HE+
Cu/Al
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Cu/Al


R290 | GWP=3 heat exchanger piston compressor condensing colils

41-2-2 PE 116-2-2 PE
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 38,4 - 94,8 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Brazed plate-type heat exchanger, stainless steel AISI 316 made, complete with water differential pressure switch, air vent valve and thermally insulated with
closed-cell neoprene anti-condensate material. The heat exchanger design provides high thermal exchange and high-performance results, furthermore it
guarantees small dimensions and easy installation and maintenance.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54. To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 70-72

42 www.euroklimat.it
Technical data
41-2-2 PE
/HE+
116-2-2 PE
CRIO/HE+ R290 range 41-2-2 PE 48-2-2 PE 83-2-2 PE 99-2-2 PE 116-2-2 PE
COOLING
Cooling capacity (1) [kW] 41,4 47,8 82,5 99,1 116,1
Total power input (1) [kW] 17,3 18,8 33,5 38,8 47,6
EER - Energy Efficiency Ratio - 2,40 2,54 2,46 2,56 2,44
Saved CO2 equivalent Ton (*) [CO2 Ton] 32,9 39,4 65,5 85,8 87,6
“Ecodesign’’ compliance for process application (SEPR) - 3,28 3,33 3,28 3,43 3,32
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290
GWP - 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 8,5 10,2 17,0 22,3 22,8
Independent gas circuits [n°] 2 2 2 2 2
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 2 2 2 2 2
Steps of capacity for each compressor (std) - 1 (75%) 1 (75%) 1 (83%) 1 (83%) 1 (83%)
Condensing coils type - Cu/Al Cu/Al Cu/Al Cu/Al Cu/Al
Fans type - Axial EC
Fans quantity [n°] 3 3 3 4 4
Fans power input (total)
(1)
[kW] 1,2 1,1 2,4 2,5 3,3
Total air flow [m3/h] 29.100 26.800 50.300 58.800 64.900
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 10,0 11,6 20,0 24,0 28,1
Evaporator pressure drop (1) [kPa] 18 24 25 30 34
DESUPERHEATER (option)
Heating capacity (2) [kW] 7,84 8,5 14,6 17,72 22,4
Water flow [m3/h] 1,37 1,48 2,54 3,09 3,90
Pressure drop (water side) [kPa] 5,2 5,3 5,3 5,4 5,5
HEAT RECOVERY (option)
Heating capacity (2) [kW] 54,4 62 108,9 129,8 152,9
Water flow [m3/h] 9,5 10,8 19,0 22,6 26,6
Pressure drop (water side) [kPa] 15 20,5 24,2 24,8 26,9
ELECTRICAL DATA
Power supply - 400/3/58 400/3/59 400/3/60 400/3/61 400/3/62
Emergency power supply - 230/1/58 230/1/59 230/1/60 230/1/61 230/1/62
Maximum power input without pump [kW] 34,3 39,3 72,6 85,3 100,5
Locked rotor current – LRA without pump [A] 151,5 177,8 307,1 352,6 414,6
Maximum absorbed current - FLA without pump [A] 63,1 77,5 121,8 140,6 167,8
HYDRONIC KIT (option)
Buffer tank capacity [L] 290 290 500 470 470
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 1,1 1,1 2,2 2,2 2,2
Pump motor nominal current [A] 3,3 3,3 4,7 4,7 4,7
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 1,5 2,2 3 4 4
Pump motor nominal current [A] 4,1 4,7 6,4 8,7 8,7
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 1" 1/2 (DN 40) 1" 1/2 (DN 40) 2" (DN 50) 2"1/2 (DN 65) 2"1/2 (DN 65)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 83 84 88 89 89
Total sound pressure (ST version) - at 1 m distance [db(A)] 65 66 69 70 70
Total sound pressure (ST version) - at 10 m distance [db(A)] 51 52 56 57 57
Total sound power (LN version) [db(A)] 80 81 85 86 86
Total sound pressure (LN version) - at 1 m distance [db(A)] 62 63 66 67 67
Total sound pressure (LN version) - at 10 m distance [db(A)] 48 49 53 54 54
Total sound power (SL version) [db(A)] 78 79 83 84 84
Total sound pressure (SL version) - at 1 m distance [db(A)] 60 61 64 65 65
Total sound pressure (SL version) - at 10 m distance [db(A)] 46 47 51 52 52
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 3.920 3.920 4.200 5.500 5.500
Width BASE Unit [mm] 1.025 1.025 1.185 1.535 1.535
Weigth BASE unit [kg] 940 970 1.460 1.690 1.710
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 3.920 3.920 5.000 5.500 5.500
Width INTEGRATA Unit [mm] 1.025 1.025 1.185 1.535 1.535
Weigth INTEGRATA unit (shipping weight) [kg] 1.040 1.070 1.592 1.817 1.837
Weigth INTEGRATA unit (operating weight) [kg] 1.330 1.360 2.092 2.287 2.307

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 43
/HE+
MCX
R290

Refrigerant Brazed plate Semi-hermetic Axial fan Microchannel


R290 | GWP=3 heat exchanger piston compressor condensing colils

130-2-2 PV 185-2-2 PV
Air-to-Water chillers for medium temperature applications - outdoor installation

Solution
B - Base
I - Integrated

Version
ST - Standard
LN - Low Noise
SL - Super Low Noise

Equipment
AS - Standard equipment
DS - Desuperheater
HR - Total Heat Recovery

Cooling capacity 158,3 - 181,8 kW

Safety system To ensure high-safety-level the unit is equipped with an ATEX certified gas detector and an EC centrifugal extraction fan. The sensor, with external dedicated
power supply and Modbus output signal, has an alarm threshold set at 10% of the lower flammable limit (LFL). The safety devices are managed by the
microprocessor: when a leak is detected, this is signaled on the panel by means of the red LED status indicator and the sensor activates a series of
emergency provisions which ensure the highest possible safety level. The Propane alarm causes the immediate shutdown of the machine and the centrifugal
extraction fan is switched on, which allows the ventilation of the compressor compartment and the dilution of the R290 concentration to values below the
lower flammability limit.
Structure Structure specifically designed and built to guarantee total resistance to atmospheric agents and corrosion. Basement and panels made of galvanized steel
sheet, oven-painted with polyurethane powders. Frame made of anodized aluminium profiles, with aluminium alloy corner joints that guarantee excellent
mechanical resistance and low weight. LN (Low Noise) version: the panels are internally lined with sound-absorbing material. SL (Super Low Noise) version:
the panels are sandwich and insulated with rock wool.
Compressor Reciprocating semi-hermetic type compressor equipped with: electronic control module and protection of the electric motor (installed inside the electrical
panel); oil charge; oil level sight glass and oil crankcase heater; anti-vibration rubber supports; anti-vibration pipes (suction and discharge); suction and
discharge valves. The compressor can be supplied with one or more RSH capacity control heads to guarantee an adaptation of the cooling capacity in case
of thermal load’s reduction: please see the list of accessories for further information.
EC Fan Premium-Axial-Fans with bionic shaped blades and high-efficient EC (Electronically Commutated) external rotor motors, sealed in protection IP54 and
thermal class THCL 155. The motor efficiency class complies with IE4.
Air heat exchanger Finned coil made with copper pipes arranged on staggered rows, mechanically expanded inside a pack of aluminium fins offering a high exchange surface
area.
Water heat exchanger Plate-type. Made of AISI 316 steel complete with water differential pressure switch. Shell covered with closed-cell neoprene anti-condensate materia
Shell & tubes. All extremely efficient with low refrigerant charge and very stable operating performance due to excellent refrigerant distribution, thermally
insulated by vapour-proof closed celle.
Electrical board Each unit is equipped with electric panel, built, wired and fully tested at the factory. Wiring numeration and optimized layout facilitate troubleshooting. The
installed components are identified by nameplates to better identify the application and the type of action. Switchboard is made according to standards IEC
204-1/EN60204-1 and it is complete with the following main components:
- Main isolator switch - Door interlock safety device - Contactor and protection for compressor and fans - Cabinet minimum protection rating IP54 To ensure
higher level of security, the cabinet is outside the machine and positioned on one side of the unit. The propane sensor is equipped with separate power
supply: this power supply must always be guaranteed in order to ensure the monitoring of any leakage.
Control The microprocessor controls the unit capacity by timing the compressors and checks the operating alarms with the possibility to connect to BMS.
Refrigerant circuit Filter drier, moisture-liquid sight glass, electronic expansion valve, high & low pressure gauge, high and low pressure transducers, high pressure switch,
safety high pressure valve (when required by EN 378-2016 standard).
Water circuit Base version: as interface to the plant, includes the water fittings of the evaporator only.
Integrated version: Water storage tank, water pressure gauge, safety valve, water discharge valve, centrifugal pump(s) suitable for glycol solutions up to
40%, manual by-pass valve, manual air venting valve. The pump control equipment is fitted inside the electrical board of the unit and the microprocessor
control manages the pump starting, timing and all the safety devices of the whole system.
MAIN ACCESSORIES ■■ Anti-vibration rubber/spring mounts ■■ Overpressure valve / automatic by-pass
■■ Air heat exchanger protection panel or filter (aluminium mesh) ■■ Double water pump (stand-by) - Standard pressure / High pressure water pump
■■ Air heat exchanger with various coatings treatment ■■ Open expansion tank / Closed expansion vessel with automatic filling unit
- Low pressure switch ■■ RSH Capacity Control head / Inverter driven compressor
- Low pressure safety valve ■■ Advanced control c.pCo
- Double safety valve
➤➤ For the complete list of accessories please see pages 70-72

44 www.euroklimat.it
Technical data
130-2-2 PV
/HE+
185-2-2 PV
CRIO/HE+ R290 range 130-2-2 PV 142-2-2 PV 161-2-2 PV 175-2-2 PV 185-2-2 PV
COOLING
Cooling capacity (1) [kW] 129,7 141,8 161,2 174,5 185,1
Total power input (1) [kW] 59,5 65,3 70,7 77,2 82,1
EER - Energy Efficiency Ratio - 2,18 2,17 2,28 2,26 2,26
Saved CO2 equivalent Ton (*) [CO2 Ton] 55,8 61,1 77 77,9 81,4
“Ecodesign’’ compliance for process application (SEPR) - 2,71 2,70 2,85 2,81 2,82
REFRIGERANT CIRCUIT
Refrigerant - R290 R290 R290 R290 R290
GWP - 3 3 3 3 3
Charge of refrigerant - Base unit [kg] 14,5 15,9 20,0 20,2 21,2
Independent gas circuits [n°] 2 2 2 2 2
Compressors type - Semi-hermetic pistons
Compressors quantity [n°] 2 2 2 2 2
Steps of capacity for each compressor (std) - 1 (87.5%) 1 (87.5%) 1 (87.5%) 1 (87.5%) 1 (87.5%)
Condensing coils type - Microchannel Microchannel Microchannel Microchannel Microchannel
Fans type - Axial EC
Fans quantity [n°] 4 4 6 6 6
Fans power input (total)
(1)
[kW] 3,5 3,9 4,1 4,5 4,9
Total air flow [m3/h] 68.900 71.400 96.000 99.000 101.200
Expansion valve type - Electronic
Evaporator water flow (1) [m3/h] 31,4 34,4 39,1 42,3 44,9
Evaporator pressure drop (1) [kPa] 36 33 30 34 33
DESUPERHEATER (option)
Heating capacity (2) [kW] 27,84 30,24 34 37,6 39,4
Water flow [m3/h] 4,85 5,27 5,92 6,55 6,86
Pressure drop (water side) [kPa] 5,6 5,7 10,0 11,0 11,0
HEAT RECOVERY (option)
Heating capacity (2) [kW] 176,45 196,2 218,2 237,6 250,3
Water flow [m3/h] 30,7 34,2 38,0 41,4 43,6
Pressure drop (water side) [kPa] 29,6 36,5 38,2 39,7 30,9
ELECTRICAL DATA
Power supply - 400/3/64 400/3/65 400/3/66 400/3/67 400/3/68
Emergency power supply - 230/1/64 230/1/65 230/1/66 230/1/67 230/1/68
Maximum power input without pump [kW] 95,1 114,3 119,5 125,1 133,3
Locked rotor current – LRA without pump [A] 390,3 472,9 568,3 670,1 713,7
Maximum absorbed current - FLA without pump [A] 166,0 193,2 198,7 216,3 231,5
HYDRONIC KIT (option)
Buffer tank capacity [L] 290 290 290 290 290
Pump type - Centrifugal
STANDARD PUMP - 150 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 3 3 3 3 3
Pump motor nominal current [A] 6,4 6,4 6,4 6,4 6,4
HIGH PRESSURE PUMP - 250 kPa useful head
Motor Efficiency - IE3 IE3 IE3 IE3 IE3
Pump motor nominal power [kW] 4 4 5,5 5,5 5,5
Pump motor nominal current [A] 8,7 8,7 10,6 10,6 10,6
WATER CONNECTIONS
Dimension (nominal external diameter) [inch/DN] 3" (DN 80) 3" (DN 80) 3" (DN 80) 3" (DN 80) 3" (DN 80)
NOISE LEVELS (3)
Total sound power (ST version) [db(A)] 90 94 95 95 97
Total sound pressure (ST version) - at 1 m distance [db(A)] 71 75 75 75 77
Total sound pressure (ST version) - at 10 m distance [db(A)] 58 62 63 63 65
Total sound power (LN version) [db(A)] 87 91 92 92 94
Total sound pressure (LN version) - at 1 m distance [db(A)] 68 72 72 72 74
Total sound pressure (LN version) - at 10 m distance [db(A)] 55 59 60 60 62
Total sound power (SL version) [db(A)] 85 89 90 90 92
Total sound pressure (SL version) - at 1 m distance [db(A)] 66 70 70 70 72
Total sound pressure (SL version) - at 10 m distance [db(A)] 53 57 58 58 60
DIMENSIONS AND WEIGHT - Base Solution**
Lenght (with eletrical panel) BASE Unit [mm] 3.100 3.100 4.450 4.450 4.450
Width BASE Unit [mm] 2.345 2.345 2.345 2.345 2.345
Weigth BASE unit [kg] 1.855 1.900 2.560 2.575 2.590
DIMENSIONS AND WEIGHT - Integrata Solution**
Lenght (with eletrical panel) INTEGRATA Unit [mm] 3.100 3.100 4.450 4.450 4.450
Width INTEGRATA Unit [mm] 2.345 2.345 2.345 2.345 2.345
Weigth INTEGRATA unit (shipping weight) [kg] 1.965 2.010 2.670 2.685 2.700
Weigth INTEGRATA unit (operating weight) [kg] 2.255 2.300 2.960 2.975 2.990

Compliance with “Eco-Design”


The units comply with the European Directive 2009/125/EC and the Commission Regulation (EU) 2015/1095 and with the Harmonized Directives. The relevant information related to each model
are published on our website www.euroklimat.it

Reference conditions:
(1) Outdoor air temperature = 30°C - Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35%- Condensing coil: Cu/Al or microchannel according to models
(2) Plate heat exchanger water temp. IN/OUT = 40/45°C - Condenser air intake temperature = 35°C -Evaporator water temperature IN/OUT = -4/-8°C - Fluid: ethilene glycol 35% - Condensing coil: Cu/Al or microchannel according to models
(1) - (2) The declared cooling capacity are not taking into account the pump motor power input (where provided).
(3) Sound power level in compliance with ISO 3744 - Sound pressure level (average value), unit in a free field on a reflective surface; non-binding value obtained from the sound power level.
(*) CO2 equivalent tons saved to the Environment compared to the choice of an EUROKLIMAT unit with similar cooling capacity and HFC refrigerant
(**) The indicated dimensions are given for the unit without inverter driven compressor(s). In case of selection of unit with inverter driven compressor(s) please ask additional information to our sales department.

www.euroklimat.it 45
/BS
Performance tables by model | Cooling
CRIO/BS 7-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 8,2 2,6 8,1 2,6 8 2,7 7,8 2,7 7,7 2,7 7,3 2,9 6,8 3,3 6,5 3,6 6,1 3,8 5,7 3,9
-8 8,8 2,7 8,7 2,7 8,6 2,7 8,4 2,8 8,3 2,8 7,9 3 7,3 3,4 6,9 3,6 6,5 3,9 6,1 4,1
-6 9,4 2,7 9,3 2,8 9,1 2,8 9 2,8 8,8 2,9 8,4 3,1 7,8 3,5 7,4 3,8 6,9 4 6,5 4,2 Ethylene
-4 10,1 2,8 9,9 2,8 9,8 2,9 9,6 2,9 9,4 3 8,9 3,2 8,3 3,7 7,9 4 7,4 4,2 6,9 4,3 Glycol 35%
-2 10,8 2,9 10,6 2,9 10,4 2,9 10,3 3 10,1 3,1 9,5 3,3 8,8 3,8 8,4 4,1 7,8 4,3 7,3 4,5
0 11,5 2,9 11,3 3 11,1 3 10,9 3,1 10,7 3,2 10,2 3,4 9,4 4 8,9 4,2 8,3 4,4 7,7 4,6
CRIO/BS 9-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 10,9 3 10,7 3,1 10,6 3,1 10,5 3,2 10,3 3,2 9,6 3,5 8,7 3,9 8,3 4,2 7,7 4,4 7,1 4,5
-8 11,7 3,1 11,6 3,2 11,4 3,2 11,3 3,2 11,1 3,3 10,3 3,6 9,4 4,1 8,9 4,4 8,2 4,6 7,6 4,7
-6 12,7 3,2 12,5 3,2 12,3 3,3 12,1 3,3 11,8 3,4 11,1 3,7 10,1 4,3 9,6 4,5 8,9 4,7 8,2 4,9 Ethylene
-4 13,6 3,2 13,4 3,3 13,2 3,3 13 3,4 12,6 3,5 11,9 3,9 10,8 4,4 10,2 4,7 9,5 4,9 8,8 5,1 Glycol 35%
-2 14,6 3,3 14,3 3,3 14,2 3,4 13,9 3,5 13,5 3,6 12,7 4 11,6 4,6 10,9 4,9 10,1 5,1 9,4 5,3
0 15,6 3,3 15,3 3,4 15,2 3,5 14,8 3,6 14,4 3,8 13,6 4,1 12,4 4,8 11,6 5,1 10,8 5,3 10,1 5,5
CRIO/BS 12-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 14,7 4,5 14,6 4,5 14,4 4,6 14,3 4,7 14 4,8 13,3 5,1 12,2 5,5 11,6 5,8 10,8 5,9 10 6,1
-8 15,9 4,6 15,7 4,7 15,6 4,7 15,3 4,8 15 5 14,3 5,3 13,1 5,7 12,4 6 11,5 6,2 10,7 6,3
-6 17,1 4,7 16,9 4,8 16,8 4,9 16,4 5 16,1 5,1 15,2 5,5 14,1 6 13,2 6,2 12,3 6,4 11,4 6,6 Ethylene
-4 18,4 4,8 18,2 4,9 17,9 5,1 17,6 5,2 17,3 5,3 16,3 5,7 15,1 6,2 14,1 6,5 13,1 6,7 12,2 6,9 Glycol 35%
-2 19,7 4,9 19,5 5,1 19,1 5,2 18,8 5,3 18,4 5,5 17,5 5,9 16 6,5 15 6,7 14 7 13 7,3
0 21,2 5 20,6 5,2 20,5 5,4 20,1 5,5 19,7 5,7 18,6 6,1 17,1 6,7 15,9 7 14,8 7,3 13,7 7,6
CRIO/BS 17-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 18,9 5,1 18,8 5,2 18,7 5,3 18,5 5,4 18,3 5,5 17,5 6 16,3 6,9 15,6 7,5 14,7 7,9 13,7 8,3
-8 20,4 5,3 20,2 5,4 20 5,4 19,9 5,5 19,7 5,7 18,8 6,3 17,5 7,1 16,8 7,9 15,7 8,3 14,7 8,6
-6 21,8 5,4 21,7 5,5 21,5 5,6 21,3 5,7 21,1 5,8 20 6,5 18,9 7,4 17,9 8,1 16,8 8,5 15,8 8,9 Ethylene
-4 23,4 5,5 23,2 5,6 23 5,7 22,8 5,8 22,4 6,1 21,4 6,7 19,9 7,7 19 8,4 17,9 8,8 16,8 9,2 Glycol 35%
-2 25 5,6 24,8 5,7 24,6 5,8 24,4 6 23,9 6,2 22,8 6,9 21,2 8 20,3 8,6 19,1 9,1 17,9 9,5
0 26,8 5,6 26,5 5,8 26,3 5,9 26 6,1 25,5 6,4 24,3 7,1 22,6 8,3 21,5 8,9 20,3 9,4 19 9,8
CRIO/BS 19-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 22,5 6,2 22,3 6,3 22,1 6,4 21,9 6,5 21,6 6,7 20,6 7,4 19,1 8,4 18,2 9,1 17 9,5 15,8 9,9
-8 24,2 6,3 23,9 6,5 23,8 6,6 23,5 6,8 23,1 7,1 22,1 7,7 20,5 8,8 19,4 9,4 18,2 9,9 17 10,3
-6 26 6,5 25,7 6,7 25,5 6,8 25,3 7 24,7 7,3 23,6 8 21,9 9,2 20,8 9,8 19,5 10,2 18,2 10,7 Ethylene
-4 27,9 6,6 27,6 6,8 27,3 7 27,1 7,2 26,5 7,6 25,2 8,3 23,4 9,5 22,2 10,1 20,7 10,6 19,4 11,1 Glycol 35%
-2 29,8 6,7 29,5 7 29,2 7,1 28,7 7,5 28,3 7,8 26,9 8,6 24,9 9,9 23,6 10,5 22,1 11 20,7 11,5
0 32 6,9 31,5 7,1 31,2 7,3 30,6 7,7 30,1 8 28,7 8,9 26,6 10,3 25,1 10,8 23,4 11,4 22,1 11,8
CRIO/BS 23-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 25,7 7 25,5 7,1 25,4 7,2 25,3 7,4 25 7,5 24,1 8,1 22,7 9 21,6 9,6 20,4 10,2 19,1 10,6
-8 27,7 7,2 27,5 7,4 27,4 7,5 27,2 7,6 26,9 7,8 25,9 8,4 24,3 9,4 23,4 10 21,9 10,6 20,5 11
-6 29,8 7,4 29,6 7,6 29,4 7,7 29,2 7,9 28,8 8,1 27,7 8,8 26 9,7 24,9 10,4 23,3 10,9 21,8 11,4 Ethylene
-4 32 7,6 31,7 7,8 31,6 7,9 31,3 8,1 30,8 8,4 29,7 9,1 27,7 10,1 26,5 10,9 24,8 11,4 23,3 11,8 Glycol 35%
-2 34,3 7,7 34 8 33,8 8,1 33,4 8,4 32,9 8,7 31,6 9,4 29,6 10,5 28,2 11,2 26,4 11,8 24,7 12,3
0 36,8 7,9 36,3 8,2 36,1 8,3 35,6 8,6 35,1 8,9 33,7 9,7 31,5 10,9 29,9 11,6 28 12,2 26,2 12,7
CRIO/BS 28-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 32,4 8,6 32,1 8,9 31,9 9,1 31,5 9,3 31 9,6 29,6 10,3 27,7 11,4 26,4 12 24,7 12,5 23,3 12,9
-8 34,9 8,9 34,5 9,2 34,2 9,4 33,7 9,7 33,2 10 31,7 10,8 29,6 11,9 28,1 12,6 26,5 13 24,8 13,4
-6 37,4 9,2 36,9 9,5 36,6 9,7 36,1 10 35,5 10,4 33,9 11,2 31,6 12,4 30 13 28,2 13,5 26,4 13,9 Ethylene
-4 40 9,4 39,5 9,8 39 10,1 38,5 10,4 37,9 10,8 36,2 11,7 33,8 12,9 31,8 13,5 29,9 14 28,2 14,4 Glycol 35%
-2 42,9 9,7 42,1 10,2 41,8 10,5 41,2 10,8 40,4 11,1 38,5 12,1 36 13,5 33,8 14 31,8 14,5 29,9 15
0 45,8 10 45 10,5 44,5 10,8 43,9 11,1 43,1 11,5 41 12,6 38 13,9 35,8 14,5 33,6 15 31,6 15,5

46 www.euroklimat.it
/BS
Performance tables by model | Cooling
CRIO/BS 33-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 37,7 9,9 37,4 10 37,1 10,2 36,8 10,4 36,2 10,7 34,6 11,6 32,4 13,4 30,8 14,6 28,9 15,3 27,1 15,9
-8 40,6 10,1 40,2 10,3 39,9 10,5 39,3 10,8 38,7 11,1 37,1 12,1 34,6 14 32,7 15,2 30,8 15,9 29 16,6
-6 43,5 10,3 43 10,6 42,8 10,7 42,3 11 41,5 11,5 39,7 12,6 37 14,6 35,2 15,7 32,9 16,5 30,7 17,3 Ethylene
-4 46,5 10,6 46,1 10,8 45,7 11 45 11,5 44,5 11,8 42,6 13,1 39,4 15,3 37,2 16,4 35,2 17,1 32,8 17,9 Glycol 35%
-2 49,7 10,8 49,2 11,1 48,8 11,3 48 11,8 47,3 12,2 45,1 13,6 42 15,9 39,7 16,9 37,2 17,8 34,7 18,5
0 53,2 11 52,6 11,3 51,8 11,8 51,3 12,1 50,4 12,6 48,1 14,1 44,5 16,7 42,2 17,5 39,6 18,3 36,8 19,2
CRIO/BS 39-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 44,1 12,2 43,8 12,4 43,5 12,6 43,2 12,8 42,3 13,2 40,6 14,3 38,1 16,1 36,7 17,4 34,8 18,2 33,3 18,9
-8 47,4 12,5 47 12,8 46,7 13 46,3 13,2 45,4 13,7 43,5 14,9 40,8 16,9 39,2 18,1 37,2 19 35,6 19,7
-6 50,9 12,8 50,4 13,1 50 13,3 49,3 13,8 48,6 14,2 46,6 15,5 43,6 17,6 41,9 18,9 39,8 19,7 38 20,4 Ethylene
-4 54,5 13,1 53,9 13,5 53,5 13,7 52,7 14,2 51,9 14,7 49,7 16,1 46,7 18,4 44,6 19,6 42,5 20,5 40,7 21,2 Glycol 35%
-2 58,4 13,4 57,8 13,8 57 14,3 56,4 14,7 55,5 15,2 53 16,7 49,8 19,1 47,5 20,3 45,3 21,2 43,3 22
0 62,4 13,7 61,4 14,3 60,8 14,6 60 15,1 59,1 15,7 56,4 17,3 53 19,9 50,4 21 48,2 22 46,1 22,8
CRIO/BS 48-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 53,4 13,7 52,9 13,9 52,7 14,1 52,2 14,3 51,7 14,6 49,5 16,1 46,6 18,9 44,8 21,1 42,9 23,4 40,5 24,2
-8 57,3 14 56,9 14,3 56,4 14,5 56,1 14,7 55,2 15,3 53,1 16,9 49,9 19,8 47,9 22,1 46 24,2 43,5 25
-6 61,5 14,4 61 14,7 60,6 14,9 60,1 15,2 59,1 15,8 56,9 17,5 53,6 20,7 51,5 23,1 49,2 25,1 46,6 25,9 Ethylene
-4 65,9 14,7 65,4 15 64,9 15,3 64,4 15,6 63,2 16,4 60,8 18,2 57,2 21,6 55,1 24,2 52,5 25,9 49,8 26,8 Glycol 35%
-2 70,6 15 69,9 15,4 69,5 15,7 68,5 16,3 67,6 16,9 64,8 18,9 61,1 22,6 58,9 25,2 56 26,8 53,2 27,7
0 75,4 15,3 74,7 15,7 73,8 16,2 73 16,7 72 17,4 69,2 19,6 65,1 23,5 62,7 26,3 59,7 27,5 56,7 28,5
CRIO/BS 55-1-1 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 63,7 16,8 63,2 17,1 62,8 17,3 61,9 17,8 61 18,4 58,1 20,1 54,1 23,4 51,8 26,1 48,9 27,9 46,2 29,1
-8 68,5 17,2 67,8 17,6 67,3 17,9 66,3 18,4 65,3 19 62,3 21 57,9 24,5 55,3 27,3 52,5 29 49,6 30,2
-6 73,3 17,6 72,6 18 72 18,3 70,9 19 69,8 19,7 66,5 21,9 61,8 25,6 59,3 28,5 56 30,1 53,2 31,3 Ethylene
-4 78,6 18 77,8 18,5 76,6 19,1 75,6 19,6 74,3 20,3 70,9 22,7 66,1 26,8 63,2 29,6 59,8 31,1 56,8 32,4 Glycol 35%
-2 84 18,4 83 18,9 81,8 19,6 80,7 20,2 79,5 21,1 75,6 23,6 70,5 28 67,4 30,6 63,7 32,1 60,6 33,4
0 89,7 18,8 88 19,6 87,1 20,2 86 20,8 84,5 21,7 80,5 24,5 75 29,1 71,6 31,6 67,8 33,2 64,5 34,5
CRIO/BS 38-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 43,9 12,3 43,5 12,5 43,3 12,8 42,9 13 42,2 13,5 40,4 14,7 37,7 16,5 35,9 17,8 33,8 18,7 31,5 19,5
-8 47,3 12,6 46,9 12,9 46,5 13,1 46 13,4 45,2 14 43,3 15,3 40,4 17,2 38,4 18,5 36,1 19,4 33,8 20,2
-6 50,7 12,9 50,3 13,3 49,9 13,5 49,1 14,1 48,4 14,5 46,2 15,9 43,1 18 41 19,3 38,5 20,2 36,1 21 Ethylene
-4 54,3 13,2 53,8 13,6 53,4 13,9 52,5 14,5 51,7 15 49,3 16,5 45,9 18,8 43,7 20 41 20,9 38,5 21,8 Glycol 35%
-2 58,1 13,5 57,5 13,9 56,7 14,5 56 14,9 55,1 15,5 52,6 17,1 49 19,5 46,4 20,7 43,7 21,7 40,9 22,6
0 62,1 13,7 61,5 14,2 60,5 14,9 59,7 15,4 58,7 16 56 17,7 52,2 20,3 49,3 21,5 46,3 22,5 43,5 23,4
CRIO/BS 49-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 55,1 14 54,7 14,2 54,4 14,4 54 14,7 53,1 15,2 50,8 16,6 47,4 19,2 45,4 21,3 42,9 23,3 40,3 24,1
-8 59,3 14,3 58,8 14,6 58,4 14,8 57,9 15,1 56,9 15,7 54,6 17,3 50,8 20,1 48,5 22,2 45,9 24,2 43 24,9
-6 63,6 14,6 63 15 62,6 15,2 61,8 15,7 60,9 16,3 58,3 17,9 54,3 21 52 23,3 49,2 24,9 46 25,7 Ethylene
-4 68,2 15 67,6 15,3 67 15,6 66 16,2 65,1 16,8 62,3 18,6 58,1 21,9 55,6 24,3 52,4 25,7 49,1 26,5 Glycol 35%
-2 73 15,2 72,3 15,7 71,8 16 70,6 16,7 69,6 17,3 66,4 19,3 61,9 22,8 59,3 25,4 55,8 26,5 52,3 27,3
0 78 15,5 77,2 16 76,1 16,6 75,2 17,2 74,1 17,9 70,8 20,1 65,9 23,8 63,1 26,2 59,4 27,2 55,6 28,1
The capacities indicated refer to the maximum capacity of compressor with operation 50 Hz

Notes: Correction Factor - ETHYLENE and PROPYLENE GLYCOL Mixture


Cc = Cooling capacity [kW] Eth. Glycol 35% Prop. Glycol 35%
Pi = Unit total power input [kW] Freezing point -19,9 °C -16,9 °C
LWT = Evaporator Leaving Water Temperature CcCF 1 0,978
* = Leaving temperature, water mixture 35% Eth.Glycol CcCF: Correction factor for cooling capacity

www.euroklimat.it 47
/BS
Performance tables by model | Cooling
CRIO/BS 58-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 66,3 16,7 65,9 17,1 65,5 17,4 64,7 18 63,9 18,6 61,3 20,4 57 23,6 54,3 25,9 50,9 27,2 47,8 28
-8 71,5 17,1 70,9 17,6 70,4 17,9 69,5 18,7 68,5 19,3 65,6 21,3 61 24,7 58 27,2 54,6 28,2 51,2 29
-6 76,7 17,6 76,1 18,1 75,3 18,8 74,5 19,3 73,5 20,1 70,1 22,2 65,1 25,9 61,8 28,2 58,2 29,2 54,5 30 Ethylene
-4 82,2 18 81,2 18,8 80,5 19,3 79,6 20 78,4 20,8 74,9 23,2 69,4 27 66 29,2 61,9 30,1 58 31,1 Glycol 35%
-2 88 18,4 86,7 19,4 86 19,9 85 20,6 83,7 21,5 79,7 24,1 73,9 28,2 70 30,1 65,8 31,1 61,6 32,1
0 94,2 18,8 92,7 19,9 91,8 20,6 90,5 21,3 89,1 22,3 84,7 25,1 78,7 29,5 74,2 31 69,8 32,1 65,5 33,1
CRIO/BS 68-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 76,1 19,9 75,3 20,3 75 20,6 74,2 21,1 73,3 21,6 70,6 23,3 66,4 26,4 63,8 29,1 60,2 30,8 56,4 32,2
-8 81,8 20,5 81 20,9 80,3 21,3 79,6 21,8 78,5 22,3 75,6 24,3 71,1 27,7 68 30,4 64,3 32 60,2 33,4
-6 87,7 20,9 86,9 21,4 86,1 21,9 85,1 22,4 84 23,1 81 25,2 76,1 29 73 31,7 68,6 33,3 64,3 34,7 Ethylene
-4 94,1 21,4 93 22,1 92,2 22,6 91,3 23,1 89,9 23,9 86,1 26,2 81,2 30,2 77,8 32,9 73,1 34,5 68,5 36 Glycol 35%
-2 100,7 21,9 99,4 22,7 98,4 23,2 97,5 23,8 95,9 24,7 92,2 27,2 86,5 31,5 82,7 34 77,7 35,6 72,7 37,3
0 107,5 22,3 105,9 23,2 105 23,8 103,9 24,5 102,4 25,4 98,2 28,2 92,1 32,9 87,6 35,2 82,4 36,9 77 38,5
CRIO/BS 79-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 89 24,1 88,3 24,5 87,9 24,8 86,8 25,4 85,8 26,1 82,3 28,5 77,2 33,1 74,1 36,8 70,4 39 67,1 40,4
-8 95,6 24,7 94,9 25,2 94,4 25,5 93,3 26,3 92,1 27,1 88,2 29,7 82,7 34,7 79,2 38,5 75,4 40,5 72 41,9
-6 102,5 25,3 101,7 25,8 100,8 26,5 99,8 27,1 98,5 28 94,6 30,8 88,3 36,3 84,9 40,2 80,7 41,9 76,9 43,4 Ethylene
-4 109,8 25,8 108,9 26,4 107,7 27,2 106,7 27,9 105,2 28,9 100,8 32,1 94,9 38 90,4 41,6 86,1 43,3 82,3 44,9 Glycol 35%
-2 117,7 26,3 116,6 27 115,3 27,9 113,8 28,7 112,3 29,8 107,3 33,4 100,6 39,6 96,4 42,8 91,7 44,8 87,7 46,4
0 125,6 26,8 123,9 27,9 122,9 28,6 121,4 29,5 119,8 30,7 114,3 34,5 107,3 41,2 102,6 44,3 97,6 46,3 93,2 47,9
CRIO/BS 95-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 106 27,9 104,8 28,5 104,2 29 102,9 29,7 101,4 30,6 97,6 33,4 92 38,7 88,7 42,5 84,5 45,6 80 47,1
-8 113,8 28,7 112,7 29,4 111,9 29,9 110,5 30,8 109 31,8 104,6 34,9 98,6 40,5 94,8 44,6 90,6 47,4 85,7 48,8
-6 122 29,5 120,7 30,3 119,6 31,1 118,3 31,9 116,7 33 112,1 36,4 105,6 42,5 101,9 46,6 96,9 49,1 91,8 50,6 Ethylene
-4 130,6 30,2 129,3 31,1 127,8 32 126,4 32,9 124,7 34,1 119,8 37,9 112,8 44,2 108,7 48,7 103,2 50,8 97,9 52,3 Glycol 35%
-2 140 31 138 32,2 136,8 33 135 34 132,8 35,3 127,7 39,4 120,5 46,2 116 50,3 110 52,5 104,3 54
0 149,5 31,7 147,2 33 145,9 33,9 144,2 35,1 142 36,6 136,4 41 128,4 48,2 123,2 52 116,9 54,2 110,9 55,8
CRIO/BS 108-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 126 34,3 124,4 35,1 123,1 36 121,5 36,9 119,2 37,9 113,8 41,5 106 47,9 101,5 52,3 95,8 55 90,8 57,1
-8 135,3 35,3 133,3 36,5 131,8 37,2 130,1 38,2 128 39,5 122 43,4 113,5 50,1 108,3 54,5 102,7 57,2 97,3 59,3
-6 144,9 36,2 142,5 37,6 141 38,4 139,1 39,5 136,7 40,9 130,3 45,2 121,4 52,4 115,9 56,6 109,7 59,3 104,1 61,6 Ethylene
-4 155,2 37,2 152,5 38,7 150,8 39,7 148,6 40,9 145,8 42,4 138,9 47,1 129,8 54,7 123,4 58,7 117 61,5 111,4 63,9 Glycol 35%
-2 165,4 38,3 162,6 39,8 160,9 40,9 158,5 42,2 155,7 44 147,9 49 138,4 57,1 131,5 60,9 124,6 63,7 118,8 66,1
0 176,3 39,2 173,3 40,9 171,3 42,1 168,7 43,6 165,7 45,5 157,7 51 147,2 59,5 139,6 63 132,8 66 126,5 68,4
CRIO/BS 126-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 133,9 45,9 133,3 46,7 132,8 47,3 132,1 48 131,3 48,8 127,4 52,1 121,4 56,9 117,2 60,2 111,3 62,8 104,6 64,3
-8 144,9 47,3 144,1 48,2 143,5 48,8 142,8 49,6 141,2 51 137,1 54,2 130,5 59,3 125,9 62,9 119,5 65,3 112,5 67,1
-6 156 48,5 155,1 49,5 154,4 50,2 153,5 51,1 151,7 52,8 147,4 56,3 140 61,9 135,3 65,7 128,1 67,9 120,4 69,7 Ethylene
-4 167,7 49,6 166,6 50,8 165,9 51,6 164,8 52,6 162,7 54,5 157,9 58,4 150,1 64,5 144,4 68,1 136,9 70,4 128,9 72,5 Glycol 35%
-2 180,3 50,7 179,1 52 177,9 52,9 175,9 54,6 174,2 56,1 168,8 60,4 160,4 67 154,3 70,5 145,9 72,9 137,5 75,2
0 192,8 51,6 191,6 53,1 190,6 54,1 188,5 56,1 186,5 57,8 180,3 62,4 171,2 69,4 164,1 72,9 155,6 75,5 146,4 77,9
CRIO/BS 137-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 146,7 50,1 145,6 51 144,9 51,6 143,9 52,3 142,2 53,8 138,3 57,1 132,2 62,7 128 66,5 121,9 68,8 114,8 70,5
-8 158,4 51,6 157,1 52,5 156,1 53,2 155,2 54,1 153,2 55,8 148,7 59,5 142,1 65,5 137,4 69,4 130,7 71,7 123,1 73,6
-6 170,2 52,8 168,6 53,9 167,9 54,8 166,5 55,7 164,4 57,7 159,8 61,9 152,3 68,4 147,3 72,2 140,1 74,7 131,8 76,6 Ethylene
-4 182,7 54 181,1 55,3 180,1 56,2 178 58 176,2 59,6 171 64,2 163,2 71,3 157,2 75 149,6 77,6 141,2 79,9 Glycol 35%
-2 196,2 55,1 194,4 56,6 192,8 57,6 190,5 59,6 188,4 61,4 182,8 66,5 174,6 74,3 167,8 77,9 159,4 80,6 150,4 83
0 209,8 56,1 207,9 57,8 205,7 59,7 203,9 61,3 201,6 63,3 195,4 68,9 186,3 77,1 178,5 80,7 170 83,7 160,1 86,1

48 www.euroklimat.it
/BS
Performance tables by model | Cooling
CRIO/BS 157-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 163,6 54,4 162,9 55,2 162,2 55,7 161,4 56,3 160 57,6 156,5 60,7 150,7 66,5 146,4 70,8 141,5 75,9 134,1 78,1
-8 176,9 55,9 175,8 56,7 175,1 57,3 174,2 58 172,6 59,5 168,4 63 162 69,2 157,5 73,7 152,2 78,8 144 81,1
-6 190,2 57,1 189,1 58 188,2 58,7 186,8 60 185,4 61,2 181,1 65,2 173,9 71,9 169,2 76,7 163 81,5 154,5 84,1 Ethylene
-4 204,2 58,2 202,9 59,3 202 60 200,3 61,5 198,7 62,9 194,1 67,2 186,7 74,6 181,6 79,8 174,3 84,2 165,2 87 Glycol 35%
-2 219,4 59,1 217,9 60,4 216,7 61,2 214,5 62,9 212,7 64,5 207,5 69,2 199,5 77,1 194,2 82,6 186,3 87 176,3 89,8
0 234,8 59,9 233,1 61,3 231,3 62,8 229,8 64,2 227,8 66 222,1 71,2 212,9 79,6 207,2 85,5 198,4 89,6 188,1 92,8
CRIO/BS 173-2-2 PE Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 181,2 60,3 180,3 61,2 179,5 61,8 178,4 62,5 176,5 64 172,2 67,4 165,1 73,5 160,5 77,8 154,4 82,5 146 84,8
-8 195,7 62 194,3 62,9 193,4 63,6 191,7 64,9 190,1 66,2 185,2 70 177,7 76,6 172,7 81,2 165,9 85,6 156,8 88
-6 211 63,5 209,4 64,6 208,3 65,4 206 66,8 204,2 68,2 198,9 72,5 190,9 79,6 185,7 84,6 178,1 88,7 168,1 91,3 Ethylene
-4 226,6 64,9 224,9 66,1 223,1 67,5 221,5 68,7 219,4 70,3 213,7 75 204,7 82,6 199,1 87,9 190,4 91,8 179,9 94,5 Glycol 35%
-2 243 66 241 67,5 239 69 237,2 70,4 234,9 72,1 228,7 77,3 219,4 85,5 213 91,1 203,3 94,7 192,4 97,6
0 260,4 67,1 257,2 69,2 255,6 70,4 253,6 72 251,1 73,9 244,3 79,5 234,3 88,4 227,4 94 217,1 97,6 205,1 100,6
CRIO/BS 158-2-2 PV Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 163,3 54,5 162,8 55,3 162,1 55,8 161,3 56,5 160,3 57,4 156,9 60,4 151,5 65,8 147,5 69,9 142,9 75,2 135,3 77,6
-8 176,8 56 175,7 56,8 175 57,4 174,1 58,2 172,9 59,3 168,9 62,5 162,8 68,4 158,3 72,8 153,5 78,1 145,6 80,5
-6 190,2 57,2 189 58,2 188 58,9 187 59,8 185,7 61 181,7 64,6 174,8 71 170,3 75,6 164,7 80,7 156,6 83,4 Ethylene
-4 204,2 58,3 202,7 59,4 201,7 60,2 200,7 61,2 199,2 62,6 194,8 66,6 187,7 73,5 183 78,2 176,4 83,2 167,6 86,2 Glycol 35%
-2 219,3 59,3 217,7 60,6 216,7 61,5 214,9 62,6 213,2 64 208,4 68,5 200,8 75,8 195,8 80,9 188,8 85,8 179 88,9
0 234,6 60,1 232,3 61,5 231,7 62,5 230,2 63,8 228,4 65,4 223,1 70,2 214,4 78,1 209,1 83,5 201,3 88,3 191,3 91,7
CRIO/BS 174-2-2 PV Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 181,5 60,4 180,2 61,3 179,3 61,9 178,3 62,7 176,9 63,8 172,8 67 166,2 72,7 161,5 76,8 155,9 81,8 148 84,1
-8 195,6 62,1 194,2 63,1 193,2 63,8 192 64,7 190,5 65,9 186 69,4 178,9 75,7 173,9 80,1 167,9 84,7 159,1 87,3
-6 210,9 63,6 209,2 64,8 207,9 65,6 206,8 66,6 204,7 67,9 199,8 71,8 192,3 78,4 187,3 83 180,5 87,7 170,8 90,5 Ethylene
-4 226,5 65 224,3 66,3 223,4 67,2 221,9 68,4 220 69,8 214,7 74,1 206,2 81,1 200,8 86,1 193,3 90,6 183,3 93,6 Glycol 35%
-2 242,8 66,2 240,8 67,7 239,4 68,7 237,8 70 235,7 71,6 230 76,3 221,1 83,9 215,1 89,1 206,4 93,5 195,9 96,6
0 260,3 67,3 258,1 68,9 256,1 70 254,3 71,4 252 73,2 245,7 78,3 236,3 86,5 230,3 92 220,5 96,2 209,1 99,5
CRIO/BS 182-2-2 PV Condenser air intake temperature [°C]
LWT* - 20 -10 -5 0 5 15 25 30 35 40
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 190,4 63,5 189,2 64,4 188,3 65,1 187,2 66 185,8 67,1 181,5 70,7 174 76,9 169 81,3 163 86 153,3 88,1
-8 205,7 65,2 204,1 66,3 203,2 67,1 201,7 68,1 200,1 69,4 195,3 73,3 187,4 79,9 181,8 84,4 175 89,1 165 91,3
-6 221,3 66,8 219,6 68,1 218,3 68,9 217,2 70,1 215,5 71,6 210 75,8 201,4 82,9 195,7 87,8 188 92,3 177,2 94,5 Ethylene
-4 237,7 68,2 235,9 69,7 234,7 70,7 233,2 72 231,3 73,6 225,5 78,3 216,5 85,9 210,2 91,1 201,2 95,2 190,4 97,7 Glycol 35%
-2 254,9 69,5 252,9 71,1 251,6 72,3 249,9 73,7 247,7 75,5 241,5 80,7 231,8 88,8 225,4 94,3 215 98,2 203,7 100,8
0 273,4 70,6 271,3 72,5 269,8 73,8 267,9 75,4 265 77,3 258,7 83 247,8 91,7 241,1 97,4 230,1 101,2 217,5 103,7
The capacities indicated refer to the maximum capacity of compressor with operation 50 Hz

Notes: Correction Factor - ETHYLENE and PROPYLENE GLYCOL Mixture


Cc = Cooling capacity [kW] Eth. Glycol 35% Prop. Glycol 35%
Pi = Unit total power input [kW] Freezing point -19,9 °C -16,9 °C
LWT = Evaporator Leaving Water Temperature CcCF 1 0,978
* = Leaving temperature, water mixture 35% Eth.Glycol CcCF: Correction factor for cooling capacity

wEKool
Euroklimat has developed an online software called “wEKool”
that allows you to select the chiller model closest to the project
conditions.
Web Product Selector
For more information, please contact your sales representative.

www.euroklimat.it 49
/HE
Performance tables by model | Cooling
CRIO/HE 10-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 10,9 3 10,9 3 10,7 3 10,6 3,1 10,2 3,2 9,3 3,5 8,8 3,8 8,3 4,1 7,7 4,6 7,1 4,8
-8 11,8 3 11,7 3,1 11,6 3,1 11,4 3,1 11 3,3 10,1 3,6 9,5 4 9 4,3 8,4 4,8 7,7 5
-6 12,7 3,1 12,7 3,1 12,4 3,2 12,3 3,2 11,8 3,4 10,8 3,8 10,3 4,1 9,8 4,5 9 5 8,3 5,1 Ethylene
-4 13,7 3,1 13,6 3,2 13,4 3,2 13,2 3,3 12,7 3,5 11,6 3,9 11 4,2 10,4 4,6 9,7 5,1 9 5,3 Glycol 35%
-2 14,7 3,2 14,6 3,2 14,4 3,3 14,2 3,3 13,6 3,5 12,4 4 11,8 4,4 11,2 4,8 10,4 5,3 9,7 5,5
0 15,8 3,2 15,6 3,2 15,4 3,3 15,2 3,4 14,4 3,7 13,4 4,1 12,6 4,5 12 5 11,2 5,4 10,4 5,7
CRIO/HE 14-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 14,7 4,3 14,7 4,3 14,5 4,4 14,4 4,5 14,1 4,7 13,2 5,1 12,6 5,3 11,9 5,8 11,2 6,2 10,3 6,3
-8 15,9 4,4 15,8 4,5 15,7 4,5 15,6 4,6 15,1 4,8 14,2 5,2 13,6 5,5 12,9 6 12 6,4 11,1 6,6
-6 17,2 4,5 17,1 4,6 16,9 4,7 16,8 4,7 16,3 4,9 15,3 5,4 14,7 5,8 13,9 6,2 12,9 6,6 12 6,8 Ethylene
-4 18,5 4,6 18,4 4,7 18,2 4,8 18 4,8 17,5 5,1 16,4 5,6 15,7 6 14,9 6,5 13,9 6,8 12,8 7,1 Glycol 35%
-2 19,9 4,7 19,8 4,7 19,5 4,9 19,4 4,9 18,7 5,3 17,6 5,8 16,9 6,2 16 6,7 14,9 7 13,8 7,3
0 21,3 4,7 21,2 4,8 20,9 5 20,7 5,1 20 5,4 18,8 6 18 6,4 17,1 7 15,9 7,3 14,7 7,6
CRIO/HE 17-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 18,7 5,1 18,6 5,2 18,4 5,3 18,2 5,4 17,7 5,8 16,7 6,5 16 7 15,2 7,7 14,3 8 13,3 8,4
-8 20,1 5,2 20 5,3 19,7 5,4 19,6 5,6 19 6 17,9 6,7 17,1 7,2 16,3 7,9 15,3 8,3 14,3 8,7
-6 21,6 5,3 21,4 5,4 21,1 5,6 21 5,7 20,3 6,1 19,1 6,9 18,4 7,6 17,5 8,2 16,3 8,6 15,3 9 Ethylene
-4 23,1 5,4 23 5,5 22,7 5,7 22,5 5,8 21,7 6,3 20,4 7,2 19,6 7,8 18,6 8,4 17,4 8,8 16,3 9,3 Glycol 35%
-2 24,8 5,5 24,6 5,6 24,3 5,8 24 6 23,2 6,5 21,8 7,4 21 8,1 19,8 8,7 18,6 9,1 17,4 9,6
0 26,5 5,6 26,2 5,7 25,9 5,9 25,6 6,1 24,7 6,7 23,3 7,7 22,3 8,3 21,1 8,9 19,8 9,4 18,5 9,9
CRIO/HE 20-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 22,4 5,9 22,3 5,9 22,2 6,1 22,1 6,2 21,4 6,7 20,1 8 19,1 9,3 17,9 9,9 16,7 10,3 15,6 10,7
-8 24,2 6 24 6,1 23,7 6,2 23,7 6,4 22,9 7 21,5 8,4 20,4 9,8 19,3 10,3 18 10,7 16,8 11,1
-6 25,9 6,1 25,9 6,2 25,7 6,4 25,5 6,5 24,6 7,2 23,1 8,7 21,9 10,1 20,6 10,6 19,3 11 18 11,5 Ethylene
-4 27,9 6,2 27,7 6,3 27,5 6,5 27,3 6,7 26,4 7,4 24,6 9,1 23,5 10,4 22 10,9 20,6 11,4 19,3 11,8 Glycol 35%
-2 29,9 6,3 29,7 6,4 29,5 6,6 29,2 6,8 28,2 7,7 26,3 9,5 25 10,7 23,5 11,2 22,1 11,7 20,6 12,2
0 32 6,3 31,8 6,5 31,5 6,7 31,3 6,9 30,1 7,9 28,1 9,8 26,7 10,9 25,1 11,5 23,5 12,1 22 12,6
CRIO/HE 24-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 25,5 6,7 25,4 6,8 25,3 7 25,2 7,1 24,6 7,6 23,3 8,6 22,3 9,4 21,1 10,4 19,7 11,1 18,4 11,5
-8 27,5 6,9 27,4 7 27,3 7,2 27,1 7,3 26,4 7,9 25 8,9 23,9 9,7 22,6 10,9 21,2 11,5 19,8 11,9
-6 29,6 7,1 29,6 7,2 29,4 7,4 29,2 7,5 28,3 8,1 26,7 9,3 25,6 10,2 24,3 11,3 22,7 11,9 21,2 12,3 Ethylene
-4 31,9 7,2 31,7 7,3 31,5 7,5 31,3 7,7 30,4 8,4 28,6 9,6 27,4 10,6 26 11,7 24,2 12,2 22,6 12,7 Glycol 35%
-2 34,2 7,3 34 7,5 33,8 7,7 33,5 7,9 32,5 8,7 30,6 10 29,2 10,9 27,7 12,1 25,9 12,6 24,1 13,1
0 36,7 7,4 36,4 7,6 36,1 7,9 35,8 8,1 34,7 8,9 32,6 10,3 31,2 11,3 29,5 12,4 27,5 13 25,7 13,6
CRIO/HE 30-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 32,2 8,1 32,2 8,2 31,9 8,5 31,7 8,6 30,9 9,2 29,1 10,4 27,8 11,3 26,4 12,3 24,7 13 23,1 13,5
-8 34,8 8,3 34,6 8,5 34,3 8,7 34,1 8,9 33,3 9,6 31,2 10,9 29,8 11,7 28,4 12,8 26,6 13,5 24,8 13,9
-6 37,3 8,5 37,2 8,7 36,8 8,9 36,6 9,2 35,5 10 33,4 11,3 32 12,2 30,4 13,3 28,5 13,9 26,6 14,4 Ethylene
-4 40,1 8,7 39,8 8,9 39,5 9,2 39,2 9,4 37,9 10,3 35,7 11,7 34,2 12,6 32,5 13,8 30,4 14,4 28,4 14,9 Glycol 35%
-2 42,9 8,8 42,7 9,1 42,2 9,4 41,9 9,7 40,4 10,7 38,1 12,1 36,5 13,1 34,7 14,3 32,5 14,8 30,4 15,3
0 45,9 9 45,7 9,2 45,2 9,6 44,8 9,9 43,2 11 40,6 12,5 38,9 13,6 37 14,7 34,5 15,3 32,3 15,8

wEKool Web Product Selector

50 www.euroklimat.it
/HE
Performance tables by model | Cooling
CRIO/HE 35-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 37,5 9,7 37,4 9,8 37 10 36,7 10,2 35,6 10,9 33,6 12,2 32,4 13,3 30,8 14,4 28,8 15 26,8 15,7
-8 40,4 9,9 40,1 10,1 39,8 10,3 39,5 10,5 38,2 11,3 36,2 12,7 34,7 13,9 32,9 14,9 30,9 15,6 28,7 16,3
-6 43,4 10,1 43,2 10,3 42,7 10,6 42,3 10,8 40,9 11,7 38,7 13,2 37,2 14,5 35,2 15,4 33 16,2 30,8 16,9 Ethylene
-4 46,6 10,3 46,3 10,5 45,8 10,8 45,4 11,1 43,8 12 41,4 13,7 39,8 15,1 37,6 15,9 35,2 16,8 32,8 17,6 Glycol 35%
-2 49,8 10,5 49,5 10,7 49 11 48,5 11,3 46,8 12,4 44,1 14,3 42,4 15,6 40 16,5 37,5 17,3 35 18,2
0 53,3 10,6 52,9 10,9 52,3 11,3 51,8 11,6 49,9 12,8 47,1 14,8 45,1 16,1 42,6 17 39,9 17,9 37,2 18,8
CRIO/HE 41-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 44,5 11,9 44,4 12 44 12,2 43,7 12,4 42,4 13,4 39,9 15,7 38,3 17,6 36,4 19,9 34,5 20,7 32,9 21,3
-8 47,9 12,1 47,6 12,3 47,3 12,6 47 12,8 45,5 13,9 42,9 16,3 41 18,4 39,2 20,5 37,1 21,4 35,3 22
-6 51,4 12,4 51,3 12,5 50,9 12,9 50,4 13,1 48,7 14,4 45,9 17 44,1 19,3 41,9 21,2 39,8 22 37,9 22,8 Ethylene
-4 55,3 12,6 55 12,8 54,5 13,2 53,9 13,6 52,1 14,9 49,1 17,7 47,2 20,1 44,9 21,8 42,5 22,7 40,5 23,5 Glycol 35%
-2 59,2 12,8 58,9 13 58,3 13,4 57,6 13,9 55,7 15,4 52,4 18,4 50,4 21 47,9 22,5 45,5 23,4 43,3 24,2
0 63,3 13 62,9 13,2 62,3 13,7 61,4 14,3 59,3 15,8 55,9 19,1 53,7 21,8 51 23,1 48,5 24,1 46,2 25
CRIO/HE 48-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 52,4 13,6 52,1 13,8 51,5 14,2 51 14,5 49,2 15,7 46,5 18,2 44,8 20,3 42,9 23,1 40,6 24 38,3 24,7
-8 56,4 14 56 14,2 55,2 14,6 54,8 15 52,9 16,3 49,9 19 48 21,3 46 23,9 43,5 24,8 41,2 25,5
-6 60,5 14,3 60 14,6 59,3 15 58,5 15,5 56,6 16,9 53,5 19,8 51,5 22,2 49,3 24,7 46,8 25,7 44,1 26,3 Ethylene
-4 64,8 14,6 64,3 14,9 63,4 15,5 62,6 16 60,5 17,5 57,2 20,7 55,2 23,1 52,7 25,5 50 26,5 47,2 27,2 Glycol 35%
-2 69,5 14,9 68,8 15,3 67,8 15,8 66,7 16,4 64,6 18,2 61,1 21,5 59 24 56,4 26,2 53,3 27,3 50,4 28
0 74,2 15,2 73,6 15,6 72,3 16,4 71,5 16,9 69 18,8 65,2 22,4 62,8 25,1 59,9 27 56,9 28,1 53,7 28,9
CRIO/HE 56-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 62,6 16,7 62,1 17 61,2 17,4 60,6 17,8 58,3 19,1 54,8 21,4 52,5 23,2 50 25,4 47 26,7 44,4 27,8
-8 67,1 17,1 66,6 17,5 65,7 18 65 18,3 62,6 19,8 58,7 22,2 56,2 24,1 53,7 26,3 50,5 27,7 47,7 28,8
-6 72 17,5 71,3 17,9 70,3 18,5 69,5 18,9 66,9 20,4 62,9 23,1 60,3 25,1 57,4 27,2 54,2 28,7 51,1 29,9 Ethylene
-4 77,1 17,9 76,4 18,3 75,1 18,9 74 19,4 71,4 21,1 67,1 24 64,5 26,1 61,4 28,1 57,9 29,6 54,9 30,9 Glycol 35%
-2 82,4 18,3 81,6 18,7 80,3 19,4 79,4 19,9 76,1 21,8 71,6 24,8 68,9 27 65,5 29,1 61,8 30,6 58,7 32
0 87,9 18,6 87,1 19,1 85,6 19,9 84,6 20,5 81,2 22,5 76,3 25,7 73,5 27,9 69,7 30 66 31,6 62,6 33
CRIO/HE 41-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 45 12 44,8 12,2 44,4 12,5 44,1 12,7 43 13,5 40,3 15,3 38,6 16,6 36,7 18,3 34,4 19,5 32 20,3
-8 48,4 12,2 48,1 12,4 47,8 12,8 47,4 13 46,2 14 43,3 15,9 41,4 17,3 39,5 19 36,9 20,2 34,4 21
-6 52,1 12,5 51,6 12,7 51,2 13,1 50,9 13,4 49,2 14,5 46,5 16,5 44,5 18 42,2 19,8 39,6 20,9 36,9 21,7 Ethylene
-4 55,8 12,7 55,6 12,9 55 13,3 54,5 13,7 52,6 15 49,7 17,1 47,6 18,6 45,2 20,5 42,4 21,5 39,4 22,5 Glycol 35%
-2 59,8 12,8 59,5 13,1 58,9 13,6 58,4 14 56,3 15,4 53 17,6 50,8 19,2 48,3 21,1 45,2 22,2 42,3 23,2
0 64 13 63,6 13,3 62,9 13,9 62,3 14,3 60,1 15,8 56,5 18,2 54,2 19,9 51,5 21,7 48,3 22,9 45,1 23,9
CRIO/HE 48-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 50,8 13,6 50,6 13,8 50,3 14,1 50 14,4 49 15,2 46,5 16,9 44,6 18,2 42,3 19,8 39,7 21,2 37,1 22
-8 54,8 14 54,7 14,2 54,2 14,5 53,9 14,8 52,7 15,7 49,9 17,5 47,8 18,8 45,5 20,6 42,6 21,9 39,8 22,8
-6 58,9 14,3 58,7 14,5 58,3 14,9 57,9 15,2 56,6 16,2 53,4 18,2 51,3 19,6 48,8 21,4 45,7 22,6 42,7 23,6 Ethylene
-4 63,3 14,6 63 14,8 62,5 15,3 62,1 15,6 60,4 16,8 57,3 18,8 54,9 20,3 52,2 22,2 48,9 23,4 45,5 24,3 Glycol 35%
-2 67,8 14,8 67,5 15,1 67 15,6 66,5 16 64,7 17,3 61,1 19,5 58,7 21 55,8 22,9 52,2 24,1 48,6 25,2
0 72,7 15,1 72,4 15,4 71,7 16 71,1 16,4 68,9 17,8 65,1 20,1 62,5 21,7 59,5 23,7 55,4 24,9 51,7 26
The capacities indicated refer to the maximum capacity of compressor with operation 50 Hz

Notes: Correction Factor - ETHYLENE and PROPYLENE GLYCOL Mixture


Cc = Cooling capacity [kW] Eth. Glycol 35% Prop. Glycol 35%
Pi = Unit total power input [kW] Freezing point -19,9 °C -16,9 °C
LWT = Evaporator Leaving Water Temperature CcCF 1 0,978
* = Leaving temperature, water mixture 35% Eth.Glycol CcCF: Correction factor for cooling capacity

www.euroklimat.it 51
/HE
Performance tables by model | Cooling
CRIO/HE 60-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 65,4 16,4 64,8 16,6 64,5 17,1 63,9 17,5 62,3 19 58,8 21,6 56,3 23,7 52,7 24,8 49,3 25,8 46 26,6
-8 70,4 16,8 70 17,1 69,4 17,7 68,8 18,1 66,8 19,6 63 22,5 60,1 24,6 56,4 25,7 52,8 26,7 49,3 27,5
-6 75,5 17,2 75,2 17,5 74,5 18,2 73,9 18,6 71,4 20,4 67,4 23,4 64,3 25,5 60,4 26,6 56,4 27,6 52,8 28,5 Ethylene
-4 81 17,5 80,5 17,9 79,7 18,6 79,1 19,2 76,5 21,1 72 24,4 68,6 26,3 64,4 27,5 60,3 28,6 56,3 29,5 Glycol 35%
-2 86,8 17,8 86,2 18,3 85,2 19,1 84,5 19,7 81,6 21,8 76,9 25,3 73 27,2 68,8 28,5 64,1 29,5 59,9 30,5
0 92,9 18,2 92,2 18,7 91 19,6 89,9 20,4 87,1 22,5 82 26,1 77,6 28 72,8 29,3 68,3 30,5 63,7 31,4
CRIO/HE 70-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 75,6 19,4 75,3 19,7 74,6 20,1 74 20,4 71,8 21,9 67,9 25,2 65,3 28,1 62,2 31,9 58,3 33,2 54,5 34,5
-8 81,3 19,9 80,8 20,1 80 20,6 79,4 21 77 22,7 72,9 26,2 70 29,4 66,7 32,9 62,6 34,3 58,4 35,7
-6 87,2 20,3 86,7 20,6 85,9 21,1 85 21,7 82,5 23,4 78,1 27,3 75,2 30,7 71,4 33,9 67 35,4 62,2 36,8 Ethylene
-4 93,8 20,6 93,2 21 92,1 21,6 91 22,3 88,2 24,2 83,5 28,4 80,4 32 76,2 34,9 71,4 36,5 66,8 38,1 Glycol 35%
-2 100,2 20,9 99,6 21,4 98,5 22,1 97,4 22,8 94,3 25 89,1 29,5 85,8 33,4 81,3 36 76,1 37,6 71,1 39,3
0 107,1 21,2 106,4 21,7 105 22,7 103,9 23,4 100,6 25,8 95,1 30,7 91,4 34,7 86,5 37 81,1 38,7 75,6 40,5
CRIO/HE 83-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 89 24 88,5 24,3 87,7 24,8 87 25,2 84,9 26,6 80 29,8 77 32,2 73,8 35,5 70,1 38,5 66,5 39,9
-8 95,5 24,6 95,1 24,9 94,2 25,5 93,5 25,9 90,8 27,8 86 31 82,5 33,5 79,2 37 75,4 39,8 71,5 41,3
-6 102,7 25,1 102,1 25,5 101 26,1 100,3 26,6 97,1 28,7 92,1 32,2 88,7 34,9 84,9 38,4 80,8 41,1 76,9 42,7 Ethylene
-4 110,1 25,5 109,7 26 108,4 26,8 107,6 27,4 103,9 29,6 98,5 33,4 94,9 36,3 91,1 40 86,5 42,5 82,3 44,1 Glycol 35%
-2 118,2 26 117,3 26,5 116,1 27,3 115 28 111,1 30,5 105,1 34,6 101,4 37,6 97,3 41,5 92,5 43,8 87,9 45,6
0 126,3 26,4 125,4 26,9 123,9 27,9 122,8 28,6 118,5 31,4 112,3 35,8 108,1 39 103,9 43 98,7 45,2 93,9 47
CRIO/HE 97-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 106,1 27,4 104,8 27,8 104,1 28,5 103 29,1 99,5 31,6 94,1 36,4 90,5 40,3 86,3 43,8 81,7 45,6 77 46,9
-8 114,1 28,1 113,2 28,6 111,8 29,4 110,7 30,1 106,8 32,9 101 38,1 97,1 42,2 92,6 45,4 87,7 47,3 82,7 48,5
-6 122,7 28,8 121,8 29,4 120,2 30,3 119 31,1 114,4 34,1 108,2 39,7 104,3 44,1 99,1 47 93,9 49 88,8 50,3 Ethylene
-4 131,4 29,5 130,4 30,1 128,7 31,1 127,4 32 122,6 35,4 115,8 41,3 111,7 46 106,1 48,6 100,4 50,6 94,9 52 Glycol 35%
-2 140,8 30 139,5 30,7 137,6 31,9 136,2 32,9 131 36,7 123,6 43 119,1 47,6 113,2 50,3 107,3 52,4 101,2 53,7
0 150,4 30,6 149,1 31,4 146,9 32,7 144,7 34,2 139,7 37,9 132,1 44,7 126,8 49,1 120,5 51,9 114,3 54 107,9 55,4
CRIO/HE 116-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 127,8 33,3 126,8 33,8 125,4 34,6 124,3 35,2 120,2 37,6 113,3 42,2 108,5 45,9 103,5 50,8 97,9 55,4 92 57,7
-8 137,2 34,1 136,2 34,6 134,5 35,5 133,3 36,2 128,8 38,9 121,4 43,8 116,1 47,6 111,1 52,8 105,1 57,2 99,2 59,8
-6 147,2 34,9 146,2 35,5 144,3 36,4 142,8 37,2 137,7 40,2 129,9 45,4 124,9 49,5 119,4 55 112,7 59 106,5 61,7 Ethylene
-4 157,6 35,6 156,3 36,2 154,3 37,3 152,8 38,2 147,3 41,5 138,8 47 133,5 51,4 127,8 57 120,7 60,9 114,1 63,7 Glycol 35%
-2 168,4 36,2 167 37 164,7 38,2 163,2 39,1 157,1 42,7 148,4 48,7 142,6 53,2 136,6 59 129,2 62,7 122 65,7
0 180 36,8 178,4 37,7 175,7 39 173,3 40,4 167,6 43,9 158,2 50,3 152,4 55 145,8 61,1 137,9 64,6 130,7 67,6
CRIO/HE 130-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 133,1 45,3 132,3 45,9 131,9 46,9 131,3 47,6 129,1 49,8 124,4 54 120,6 57,2 116 61,3 110 64,7 102,8 66,3
-8 143,5 46,5 143,2 47,2 142,3 48,2 141,6 49 139,1 51,6 133,9 56,1 129,7 59,5 125 63,9 118,6 67,1 111,1 68,9
-6 155,2 47,6 154,6 48,4 153,5 49,6 152,4 50,4 149,5 53,2 143,9 58,1 139,7 61,7 134,7 66,5 127,5 69,4 119,6 71,5 Ethylene
-4 166,9 48,6 166,2 49,4 164,9 50,8 164 51,8 160,8 54,9 154,3 60,1 150 63,9 144,6 68,9 137,2 71,8 128,6 74 Glycol 35%
-2 179,1 49,4 178,3 50,4 176,8 51,9 175,8 53 172,2 56,4 165,6 62,1 160,6 66,1 154,9 71,4 146,9 74,1 138 76,5
0 191,9 50,2 190,9 51,3 189 52,9 188 54,2 184,1 57,9 177 63,9 172 68,3 165,7 73,4 157,1 76,3 147,7 78,9

wEKool Web Product Selector

52 www.euroklimat.it
/HE
Performance tables by model | Cooling
CRIO/HE 142-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 146,2 49,5 145,8 50,1 144,5 51,2 143,6 51,9 140,7 54,5 135,4 59,1 131,8 62,7 127,5 67,4 121,5 70,7 113,9 72,4
-8 157,8 50,7 157 51,5 155,6 52,6 154,5 53,5 151,4 56,3 145,9 61,4 141,8 65,3 137,3 70,3 130,8 73,3 122,8 75,4
-6 169,9 51,9 168,8 52,7 167,2 54 166,1 55 162,5 58,1 156,5 63,7 152,7 67,8 147,9 73,2 140,3 76 132,4 78,3 Ethylene
-4 182,7 52,9 181,5 53,8 179,7 55,3 178,4 56,4 174,3 59,9 168 65,9 163,7 70,3 158,6 75,8 150,8 78,6 142,2 81,1 Glycol 35%
-2 195,7 53,7 194,5 54,8 192,5 56,5 191,1 57,7 186,9 61,6 179,8 68 175,4 72,7 169,8 78,1 161,7 81,3 152,4 84
0 209,4 54,4 207,9 55,6 205,7 57,6 204,1 58,9 199,6 63,1 192,5 70,1 187,8 75,1 181,3 80,4 172,8 83,9 163,3 86,9
CRIO/HE 161-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 164,6 53,9 164 54,4 163 55,3 162,1 56 159,2 58,4 153,8 63,7 149,9 68,2 145,3 74,3 139,2 80,5 131 82,6
-8 177,5 55,1 176,6 55,7 175,6 56,7 174,7 57,5 171,6 60,3 165,6 66 161,2 70,7 156,4 77,1 149,7 83,1 141,1 85,5
-6 191,1 56,1 189,8 56,8 188,9 58 187,8 58,9 184,4 62 178,2 68,3 173,8 73,3 168,2 80 161,1 85,8 152,2 88,4 Ethylene
-4 205,5 57 204,4 57,8 202,8 59,2 201,5 60,2 197,8 63,6 191,2 70,4 186,3 75,7 180,8 82,8 172,8 88,4 163,4 91,2 Glycol 35%
-2 220,6 57,7 219,5 58,7 217,7 60,1 216,2 61,3 212,1 65,1 204,7 72,3 199,6 78 193,7 85,4 185,4 90,9 175 93,9
0 235,5 58,2 235 59,3 232,8 61 231,5 62,3 227 66,5 219,2 74,3 213,5 80,3 207,1 88 198,1 93,3 187,4 96,7
CRIO/HE 175-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 179,1 59,2 178,7 59,9 177,3 60,9 176,3 61,7 172,8 64,4 166,7 69,9 162 74,4 156,8 80,5 150 86,3 141 88,5
-8 193,8 60,8 192,3 61,4 191,1 62,6 189,9 63,5 186,1 66,5 179,5 72,5 174,5 77,2 169 83,8 161,6 89,2 152,2 91,7
-6 208,7 62,1 207,8 62,9 205,8 64,2 204,5 65,2 200 68,5 192,9 75 187,8 80,1 182,1 87 173,8 92,1 163,8 94,8 Ethylene
-4 224,2 63,3 223,1 64,2 221,1 65,7 219,5 66,8 215 70,5 206,9 77,4 201,7 82,8 195,5 90 186,9 95 176 97,8 Glycol 35%
-2 240,6 64,2 239,1 65,3 236,9 66,9 235,2 68,2 230,3 72,3 222,1 79,8 216,1 85,4 209,4 92,9 200,2 97,6 188,9 100,8
0 257,4 65 256 66,2 253 68 251,6 69,5 246,2 73,9 237,2 81,9 231,5 88 224,6 95,8 214 100,2 202,5 103,4
CRIO/HE 185-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 190,9 62,6 190,2 63,2 188,9 64,4 187,8 65,2 183,9 68,2 177,1 74,2 172,1 79,1 166,3 85,6 158 90,9 148,1 92,8
-8 206,1 64 204,6 64,8 203,5 66,1 202,3 67,1 198,4 70,5 190,8 77 185,1 82,1 179,3 88,9 170,8 94 160 96,1
-6 221,4 65,3 220,7 66,3 218,9 67,7 217,5 68,9 213,3 72,6 205,5 79,7 199,9 85,2 192,9 92,2 183,7 97 172,6 99,2 Ethylene
-4 237,9 66,5 237,2 67,5 235,1 69,2 233,6 70,5 228,9 74,7 220,6 82,3 214,7 88,1 207,7 95,6 197,4 99,9 185,7 102,3 Glycol 35%
-2 256,4 67,5 254,9 68,7 252,6 70,6 250,9 72 245,3 76,6 236,4 84,8 230,2 90,9 222,7 98,7 211,9 102,7 200 105,3
0 274,3 68,3 272,9 69,6 270,4 71,8 268,5 73,4 262,9 78,4 252,9 87,2 246,3 93,6 238,5 101,7 227,2 105,4 214 108
The capacities indicated refer to the maximum capacity of compressor with operation 50 Hz

Notes: Correction Factor - ETHYLENE and PROPYLENE GLYCOL Mixture


Cc = Cooling capacity [kW] Eth. Glycol 35% Prop. Glycol 35%
Pi = Unit total power input [kW] Freezing point -19,9 °C -16,9 °C
LWT = Evaporator Leaving Water Temperature CcCF 1 0,978
* = Leaving temperature, water mixture 35% Eth.Glycol CcCF: Correction factor for cooling capacity

wEKool
Euroklimat has developed an online software called “wEKool”
that allows you to select the chiller model closest to the project
conditions.
Web Product Selector
For more information, please contact your sales representative.

www.euroklimat.it 53
/HE+
Performance tables by model | Cooling
CRIO/HE+ 10-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 10,9 3 10,9 3 10,7 3 10,6 3,1 10,2 3,2 9,3 3,5 8,8 3,8 8,3 4,1 7,7 4,6 7,1 4,8
-8 11,8 3 11,7 3,1 11,6 3,1 11,4 3,1 11 3,3 10,1 3,6 9,5 4 9 4,3 8,4 4,8 7,7 5
-6 12,7 3,1 12,7 3,1 12,4 3,2 12,3 3,2 11,8 3,4 10,8 3,8 10,3 4,1 9,8 4,5 9 5 8,3 5,1 Ethylene
-4 13,7 3,1 13,6 3,2 13,4 3,2 13,2 3,3 12,7 3,5 11,6 3,9 11 4,2 10,4 4,6 9,7 5,1 9 5,3 Glycol 35%
-2 14,7 3,2 14,6 3,2 14,4 3,3 14,2 3,3 13,6 3,5 12,4 4 11,8 4,4 11,2 4,8 10,4 5,3 9,7 5,5
0 15,8 3,2 15,6 3,2 15,4 3,3 15,2 3,4 14,4 3,7 13,4 4,1 12,6 4,5 12 5 11,2 5,4 10,4 5,7
CRIO/HE+ 14-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 14,7 4,3 14,7 4,3 14,5 4,4 14,4 4,5 14,1 4,7 13,2 5,1 12,6 5,3 11,9 5,8 11,2 6,2 10,3 6,3
-8 15,9 4,4 15,8 4,5 15,7 4,5 15,6 4,6 15,1 4,8 14,2 5,2 13,6 5,5 12,9 6 12 6,4 11,1 6,6
-6 17,2 4,5 17,1 4,6 16,9 4,7 16,8 4,7 16,3 4,9 15,3 5,4 14,7 5,8 13,9 6,2 12,9 6,6 12 6,8 Ethylene
-4 18,5 4,6 18,4 4,7 18,2 4,8 18 4,8 17,5 5,1 16,4 5,6 15,7 6 14,9 6,5 13,9 6,8 12,8 7,1 Glycol 35%
-2 19,9 4,7 19,8 4,7 19,5 4,9 19,4 4,9 18,7 5,3 17,6 5,8 16,9 6,2 16 6,7 14,9 7 13,8 7,3
0 21,3 4,7 21,2 4,8 20,9 5 20,7 5,1 20 5,4 18,8 6 18 6,4 17,1 7 15,9 7,3 14,7 7,6
CRIO/HE+ 17-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 18,7 5,1 18,6 5,2 18,4 5,3 18,2 5,4 17,7 5,8 16,7 6,5 16 7 15,2 7,7 14,3 8 13,3 8,4
-8 20,1 5,2 20 5,3 19,7 5,4 19,6 5,6 19 6 17,9 6,7 17,1 7,2 16,3 7,9 15,3 8,3 14,3 8,7
-6 21,6 5,3 21,4 5,4 21,1 5,6 21 5,7 20,3 6,1 19,1 6,9 18,4 7,6 17,5 8,2 16,3 8,6 15,3 9 Ethylene
-4 23,1 5,4 23 5,5 22,7 5,7 22,5 5,8 21,7 6,3 20,4 7,2 19,6 7,8 18,6 8,4 17,4 8,8 16,3 9,3 Glycol 35%
-2 24,8 5,5 24,6 5,6 24,3 5,8 24 6 23,2 6,5 21,8 7,4 21 8,1 19,8 8,7 18,6 9,1 17,4 9,6
0 26,5 5,6 26,2 5,7 25,9 5,9 25,6 6,1 24,7 6,7 23,3 7,7 22,3 8,3 21,1 8,9 19,8 9,4 18,5 9,9
CRIO/HE+ 21-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 22,3 5,9 22,2 6 22,1 6,2 21,9 6,3 21,4 6,7 20,2 7,6 19,3 8,2 18,3 9 17,3 10 16,1 10,5
-8 24,1 6,1 23,9 6,2 23,7 6,3 23,5 6,5 23 6,9 21,6 7,8 20,7 8,5 19,7 9,3 18,6 10,4 17,4 10,9
-6 25,8 6,2 25,7 6,3 25,5 6,5 25,4 6,6 24,7 7,1 23,2 8,1 22,2 8,8 21,2 9,7 19,9 10,8 18,6 11,2 Ethylene
-4 27,8 6,3 27,6 6,4 27,4 6,6 27,2 6,8 26,3 7,4 24,8 8,4 23,8 9,1 22,7 10,1 21,4 11,1 20 11,6 Glycol 35%
-2 29,8 6,4 29,6 6,5 29,3 6,7 29,1 6,9 28,1 7,6 26,5 8,7 25,5 9,4 24,2 10,4 22,9 11,4 21,4 11,9
0 31,8 6,4 31,7 6,6 31,3 6,9 31,1 7 30 7,8 28,2 8,9 27,2 9,8 25,9 10,8 24,4 11,8 22,9 12,3

54 www.euroklimat.it
/HE+
Performance tables by model | Cooling
CRIO/HE+ 30-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 32,2 8,1 32,2 8,2 31,9 8,5 31,7 8,6 30,9 9,2 29,1 10,4 27,8 11,3 26,4 12,3 24,7 13 23,1 13,5
-8 34,8 8,3 34,6 8,5 34,3 8,7 34,1 8,9 33,3 9,6 31,2 10,9 29,8 11,7 28,4 12,8 26,6 13,5 24,8 13,9
-6 37,3 8,5 37,2 8,7 36,8 8,9 36,6 9,2 35,5 10 33,4 11,3 32 12,2 30,4 13,3 28,5 13,9 26,6 14,4 Ethylene
-4 40,1 8,7 39,8 8,9 39,5 9,2 39,2 9,4 37,9 10,3 35,7 11,7 34,2 12,6 32,5 13,8 30,4 14,4 28,4 14,9 Glycol 35%
-2 42,9 8,8 42,7 9,1 42,2 9,4 41,9 9,7 40,4 10,7 38,1 12,1 36,5 13,1 34,7 14,3 32,5 14,8 30,4 15,3
0 45,9 9 45,7 9,2 45,2 9,6 44,8 9,9 43,2 11 40,6 12,5 38,9 13,6 37 14,7 34,5 15,3 32,3 15,8
CRIO/HE+ 36-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 38,7 9,9 38,5 10 38,1 10,2 37,7 10,4 36,8 11 34,9 12,2 33,5 13,1 32 14,2 30,2 15,2 28,1 15,9
-8 41,6 10,1 41,3 10,3 40,9 10,5 40,6 10,7 39,5 11,3 37,4 12,6 36 13,5 34,4 14,8 32,4 15,7 30,2 16,4
-6 44,7 10,3 44,5 10,5 43,9 10,8 43,6 11 42,2 11,8 40 13,1 38,6 14,1 37 15,4 34,7 16,3 32,3 17 Ethylene
-4 48 10,5 47,7 10,7 47,1 11 46,7 11,3 45,2 12,2 42,8 13,6 41,3 14,6 39,5 16 37 16,8 34,5 17,6 Glycol 35%
-2 51,2 10,7 51 10,9 50,3 11,3 49,9 11,6 48,3 12,5 45,8 14,1 44 15,2 42,1 16,5 39,5 17,4 36,8 18,2
0 54,9 10,8 54,5 11,1 53,8 11,5 53,3 11,8 51,5 12,9 48,8 14,5 47,1 15,7 44,8 17 42,1 17,9 39,3 18,8
CRIO/HE+ 56-1-1 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 62,6 16,7 62,1 17 61,2 17,4 60,6 17,8 58,3 19,1 54,8 21,4 52,5 23,2 50 25,4 47 26,7 44,4 27,8
-8 67,1 17,1 66,6 17,5 65,7 18 65 18,3 62,6 19,8 58,7 22,2 56,2 24,1 53,7 26,3 50,5 27,7 47,7 28,8
-6 72 17,5 71,3 17,9 70,3 18,5 69,5 18,9 66,9 20,4 62,9 23,1 60,3 25,1 57,4 27,2 54,2 28,7 51,1 29,9 Ethylene
-4 77,1 17,9 76,4 18,3 75,1 18,9 74 19,4 71,4 21,1 67,1 24 64,5 26,1 61,4 28,1 57,9 29,6 54,9 30,9 Glycol 35%
-2 82,4 18,3 81,6 18,7 80,3 19,4 79,4 19,9 76,1 21,8 71,6 24,8 68,9 27 65,5 29,1 61,8 30,6 58,7 32
0 87,9 18,6 87,1 19,1 85,6 19,9 84,6 20,5 81,2 22,5 76,3 25,7 73,5 27,9 69,7 30 66 31,6 62,6 33
CRIO/HE+ 41-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 45 12 44,8 12,2 44,4 12,5 44,1 12,7 43 13,5 40,3 15,3 38,6 16,6 36,7 18,3 34,4 19,5 32 20,3
-8 48,4 12,2 48,1 12,4 47,8 12,8 47,4 13 46,2 14 43,3 15,9 41,4 17,3 39,5 19 36,9 20,2 34,4 21
-6 52,1 12,5 51,6 12,7 51,2 13,1 50,9 13,4 49,2 14,5 46,5 16,5 44,5 18 42,2 19,8 39,6 20,9 36,9 21,7 Ethylene
-4 55,8 12,7 55,6 12,9 55 13,3 54,5 13,7 52,6 15 49,7 17,1 47,6 18,6 45,2 20,5 42,4 21,5 39,4 22,5 Glycol 35%
-2 59,8 12,8 59,5 13,1 58,9 13,6 58,4 14 56,3 15,4 53 17,6 50,8 19,2 48,3 21,1 45,2 22,2 42,3 23,2
0 64 13 63,6 13,3 62,9 13,9 62,3 14,3 60,1 15,8 56,5 18,2 54,2 19,9 51,5 21,7 48,3 22,9 45,1 23,9
The capacities indicated refer to the maximum capacity of compressor with operation 50 Hz

Notes: Correction Factor - ETHYLENE and PROPYLENE GLYCOL Mixture


Cc = Cooling capacity [kW] Eth. Glycol 35% Prop. Glycol 35%
Pi = Unit total power input [kW] Freezing point -19,9 °C -16,9 °C
LWT = Evaporator Leaving Water Temperature CcCF 1 0,978
* = Leaving temperature, water mixture 35% Eth.Glycol CcCF: Correction factor for cooling capacity

wEKool
Euroklimat has developed an online software called “wEKool”
that allows you to select the chiller model closest to the project
conditions.
Web Product Selector
For more information, please contact your sales representative.

www.euroklimat.it 55
/HE+
Performance tables by model | Cooling
CRIO/HE+ 48-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 50,8 13,6 50,6 13,8 50,3 14,1 50 14,4 49 15,2 46,5 16,9 44,6 18,2 42,3 19,8 39,7 21,2 37,1 22
-8 54,8 14 54,7 14,2 54,2 14,5 53,9 14,8 52,7 15,7 49,9 17,5 47,8 18,8 45,5 20,6 42,6 21,9 39,8 22,8
-6 58,9 14,3 58,7 14,5 58,3 14,9 57,9 15,2 56,6 16,2 53,4 18,2 51,3 19,6 48,8 21,4 45,7 22,6 42,7 23,6 Ethylene
-4 63,3 14,6 63 14,8 62,5 15,3 62,1 15,6 60,4 16,8 57,3 18,8 54,9 20,3 52,2 22,2 48,9 23,4 45,5 24,3 Glycol 35%
-2 67,8 14,8 67,5 15,1 67 15,6 66,5 16 64,7 17,3 61,1 19,5 58,7 21 55,8 22,9 52,2 24,1 48,6 25,2
0 72,7 15,1 72,4 15,4 71,7 16 71,1 16,4 68,9 17,8 65,1 20,1 62,5 21,7 59,5 23,7 55,4 24,9 51,7 26
CRIO/HE+ 82-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 89 24 88,5 24,3 87,7 24,8 87 25,2 84,9 26,6 80 29,8 77 32,2 73,8 35,5 70,1 38,5 66,5 39,9
-8 95,5 24,6 95,1 24,9 94,2 25,5 93,5 25,9 90,8 27,8 86 31 82,5 33,5 79,2 37 75,4 39,8 71,5 41,3
-6 102,7 25,1 102,1 25,5 101 26,1 100,3 26,6 97,1 28,7 92,1 32,2 88,7 34,9 84,9 38,4 80,8 41,1 76,9 42,7 Ethylene
-4 110,1 25,5 109,7 26 108,4 26,8 107,6 27,4 103,9 29,6 98,5 33,4 94,9 36,3 91,1 40 86,5 42,5 82,3 44,1 Glycol 35%
-2 118,2 26 117,3 26,5 116,1 27,3 115 28 111,1 30,5 105,1 34,6 101,4 37,6 97,3 41,5 92,5 43,8 87,9 45,6
0 126,3 26,4 125,4 26,9 123,9 27,9 122,8 28,6 118,5 31,4 112,3 35,8 108,1 39 103,9 43 98,7 45,2 93,9 47
CRIO/HE+ 99-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 106,2 27,2 105,6 27,6 104,5 28,1 103,7 28,6 100,8 30,5 95,8 34,2 92,3 37,3 88,6 41,4 84,6 46,5 80
-8 114,1 27,9 113,6 28,3 112,2 29 111,3 29,5 108,2 31,6 102,9 35,6 99,1 38,8 95,3 43 91 48 86
-6 122,8 28,6 121,9 29 120,5 29,8 119,7 30,3 115,9 32,6 110,3 36,9 106,6 40,3 102,5 44,8 97,7 49,5 92,4 Ethylene
-4 131,6 29,2 130,7 29,7 129,2 30,5 128 31,1 124,4 33,7 118 38,3 114,1 41,8 109,8 46,5 104,8 51,1 99 Glycol 35%
-2 140,8 29,7 139,8 30,3 138,2 31,2 137 31,9 132,8 34,8 126,4 39,6 122 43,3 117,4 48,1 112,1 52,6 106,1
0 150,6 30,2 149,3 30,8 147,4 31,8 146,3 32,6 141,7 35,8 134,9 41 130,6 44,9 125,5 49,8 119,7 54,1 113,4
CRIO/HE+ 116-2-2 PE Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 127,8 33,3 126,8 33,8 125,4 34,6 124,3 35,2 120,2 37,6 113,3 42,2 108,5 45,9 103,5 50,8 97,9 55,4 92 57,7
-8 137,2 34,1 136,2 34,6 134,5 35,5 133,3 36,2 128,8 38,9 121,4 43,8 116,1 47,6 111,1 52,8 105,1 57,2 99,2 59,8
-6 147,2 34,9 146,2 35,5 144,3 36,4 142,8 37,2 137,7 40,2 129,9 45,4 124,9 49,5 119,4 55 112,7 59 106,5 61,7 Ethylene
-4 157,6 35,6 156,3 36,2 154,3 37,3 152,8 38,2 147,3 41,5 138,8 47 133,5 51,4 127,8 57 120,7 60,9 114,1 63,7 Glycol 35%
-2 168,4 36,2 167 37 164,7 38,2 163,2 39,1 157,1 42,7 148,4 48,7 142,6 53,2 136,6 59 129,2 62,7 122 65,7
0 180 36,8 178,4 37,7 175,7 39 173,3 40,4 167,6 43,9 158,2 50,3 152,4 55 145,8 61,1 137,9 64,6 130,7 67,6
CRIO/HE+ 130-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 133,1 45,3 132,3 45,9 131,9 46,9 131,3 47,6 129,1 49,8 124,4 54 120,6 57,2 116 61,3 110 64,7 102,8 66,3
-8 143,5 46,5 143,2 47,2 142,3 48,2 141,6 49 139,1 51,6 133,9 56,1 129,7 59,5 125 63,9 118,6 67,1 111,1 68,9
-6 155,2 47,6 154,6 48,4 153,5 49,6 152,4 50,4 149,5 53,2 143,9 58,1 139,7 61,7 134,7 66,5 127,5 69,4 119,6 71,5 Ethylene
-4 166,9 48,6 166,2 49,4 164,9 50,8 164 51,8 160,8 54,9 154,3 60,1 150 63,9 144,6 68,9 137,2 71,8 128,6 74 Glycol 35%
-2 179,1 49,4 178,3 50,4 176,8 51,9 175,8 53 172,2 56,4 165,6 62,1 160,6 66,1 154,9 71,4 146,9 74,1 138 76,5
0 191,9 50,2 190,9 51,3 189 52,9 188 54,2 184,1 57,9 177 63,9 172 68,3 165,7 73,4 157,1 76,3 147,7 78,9

56 www.euroklimat.it
/HE+
Performance tables by model | Cooling
CRIO/HE+ 142-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 146,2 49,5 145,8 50,1 144,5 51,2 143,6 51,9 140,7 54,5 135,4 59,1 131,8 62,7 127,5 67,4 121,5 70,7 113,9 72,4
-8 157,8 50,7 157 51,5 155,6 52,6 154,5 53,5 151,4 56,3 145,9 61,4 141,8 65,3 137,3 70,3 130,8 73,3 122,8 75,4
-6 169,9 51,9 168,8 52,7 167,2 54 166,1 55 162,5 58,1 156,5 63,7 152,7 67,8 147,9 73,2 140,3 76 132,4 78,3 Ethylene
-4 182,7 52,9 181,5 53,8 179,7 55,3 178,4 56,4 174,3 59,9 168 65,9 163,7 70,3 158,6 75,8 150,8 78,6 142,2 81,1 Glycol 35%
-2 195,7 53,7 194,5 54,8 192,5 56,5 191,1 57,7 186,9 61,6 179,8 68 175,4 72,7 169,8 78,1 161,7 81,3 152,4 84
0 209,4 54,4 207,9 55,6 205,7 57,6 204,1 58,9 199,6 63,1 192,5 70,1 187,8 75,1 181,3 80,4 172,8 83,9 163,3 86,9
CRIO/HE+ 161-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 164,6 53,9 164 54,4 163 55,3 162,1 56 159,2 58,4 153,8 63,7 149,9 68,2 145,3 74,3 139,2 80,5 131 82,6
-8 177,5 55,1 176,6 55,7 175,6 56,7 174,7 57,5 171,6 60,3 165,6 66 161,2 70,7 156,4 77,1 149,7 83,1 141,1 85,5
-6 191,1 56,1 189,8 56,8 188,9 58 187,8 58,9 184,4 62 178,2 68,3 173,8 73,3 168,2 80 161,1 85,8 152,2 88,4 Ethylene
-4 205,5 57 204,4 57,8 202,8 59,2 201,5 60,2 197,8 63,6 191,2 70,4 186,3 75,7 180,8 82,8 172,8 88,4 163,4 91,2 Glycol 35%
-2 220,6 57,7 219,5 58,7 217,7 60,1 216,2 61,3 212,1 65,1 204,7 72,3 199,6 78 193,7 85,4 185,4 90,9 175 93,9
0 235,5 58,2 235 59,3 232,8 61 231,5 62,3 227 66,5 219,2 74,3 213,5 80,3 207,1 88 198,1 93,3 187,4 96,7
CRIO/HE+ 175-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 179,1 59,2 178,7 59,9 177,3 60,9 176,3 61,7 172,8 64,4 166,7 69,9 162 74,4 156,8 80,5 150 86,3 141 88,5
-8 193,8 60,8 192,3 61,4 191,1 62,6 189,9 63,5 186,1 66,5 179,5 72,5 174,5 77,2 169 83,8 161,6 89,2 152,2 91,7
-6 208,7 62,1 207,8 62,9 205,8 64,2 204,5 65,2 200 68,5 192,9 75 187,8 80,1 182,1 87 173,8 92,1 163,8 94,8 Ethylene
-4 224,2 63,3 223,1 64,2 221,1 65,7 219,5 66,8 215 70,5 206,9 77,4 201,7 82,8 195,5 90 186,9 95 176 97,8 Glycol 35%
-2 240,6 64,2 239,1 65,3 236,9 66,9 235,2 68,2 230,3 72,3 222,1 79,8 216,1 85,4 209,4 92,9 200,2 97,6 188,9 100,8
0 257,4 65 256 66,2 253 68 251,6 69,5 246,2 73,9 237,2 81,9 231,5 88 224,6 95,8 214 100,2 202,5 103,4
CRIO/HE+ 185-2-2 PV Condenser air intake temperature [°C]
LWT* -20 -10 0 5 15 25 30 35 40 45
°C Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi Cc Pi
-10 190,9 62,6 190,2 63,2 188,9 64,4 187,8 65,2 183,9 68,2 177,1 74,2 172,1 79,1 166,3 85,6 158 90,9 148,1 92,8
-8 206,1 64 204,6 64,8 203,5 66,1 202,3 67,1 198,4 70,5 190,8 77 185,1 82,1 179,3 88,9 170,8 94 160 96,1
-6 221,4 65,3 220,7 66,3 218,9 67,7 217,5 68,9 213,3 72,6 205,5 79,7 199,9 85,2 192,9 92,2 183,7 97 172,6 99,2 Ethylene
-4 237,9 66,5 237,2 67,5 235,1 69,2 233,6 70,5 228,9 74,7 220,6 82,3 214,7 88,1 207,7 95,6 197,4 99,9 185,7 102,3 Glycol 35%
-2 256,4 67,5 254,9 68,7 252,6 70,6 250,9 72 245,3 76,6 236,4 84,8 230,2 90,9 222,7 98,7 211,9 102,7 200 105,3
0 274,3 68,3 272,9 69,6 270,4 71,8 268,5 73,4 262,9 78,4 252,9 87,2 246,3 93,6 238,5 101,7 227,2 105,4 214 108
The capacities indicated refer to the maximum capacity of compressor with operation 50 Hz

Notes: Correction Factor - ETHYLENE and PROPYLENE GLYCOL Mixture


Cc = Cooling capacity [kW] Eth. Glycol 35% Prop. Glycol 35%
Pi = Unit total power input [kW] Freezing point -19,9 °C -16,9 °C
LWT = Evaporator Leaving Water Temperature CcCF 1 0,978
* = Leaving temperature, water mixture 35% Eth.Glycol CcCF: Correction factor for cooling capacity

wEKool
Euroklimat has developed an online software called “wEKool”
that allows you to select the chiller model closest to the project
conditions.
Web Product Selector
For more information, please contact your sales representative.

www.euroklimat.it 57
Standard equipment and Accessories
General
Optional accessories
Anti-vibration rubber mounts (supplied separately) Anti-vibration spring mounts (supplied separately)

Rubber vibration isolation mounting (Kit). The system prevent the Spring vibration isolation mounting (Kit). The system prevent the
transmission of vibrations to the structure where the unit is located. transmission of vibrations to the structure where the unit is located.

Anti-vibration seismic spring mounts (supplied separately) Condensing coil protection panel

Seismic vibration isolation mounting (Kit). The system prevent the Metal protection panel for condensing coil against accidental
transmission of vibrations to the structure where the unit is located. impacts. Available for “PE” models only.

Condensing coil protection panel Metallic filters for condensing coils

Metallic filters specially designed for condensing coils applications on


Metal protection anti-intrusion grid for condensing coil against
immagine industrial chillers, made of an aluminum sheet frame and microextruded
accidental impacts. Available for “PE” and “PV” models. The picture
mancante aluminum mesh. These filters ensure very low pressure drops and their
on the left refers to “V” shaped coils.
design allow to cover large suction surfaces.

Aluminum panels (fan panel not included) Stainless steel panels (AISI 304) - (fan panel not included)

Aluminium-based panels, with the exception of fan(s) bellmouth,


Stainless steel-based (AISI 304) panels, with the exception of fan(s)
allow to reduce the weight of tje unit and ensure higher wethering
bellmouth, allow higher rusting resitance.
resistance.

Panels insulated with polyurethane foam sheets Sandwich soundproofing galvanized sheet panels

Painted galvanized sheet panels, insulated with polyurethane foam Sandwich soundproofing galvanized sheet panels, painted outside and
sheets, polyester based, anthracite colour, selfextinguishing non isolated with high- density rock wool (100 Kg/m3).
dripping. Standard for LN version. Standard for SL version

58 www.euroklimat.it
Standard equipment and Accessories
Condensing section
Optional accessories
Condensing coil with ElectroFin® treatment Condensing coil with AiAX Coatings treatment
The AiAX Coatings treatment protects the exchangers from the
hostile conditions of the most aggressive environments. The
ElectroFin® treatment delivers corrosion durability protection for treatment is specially designed to resist thermal contractions and
fins and tubes, increasing efficiency and length of service. expansions, UV rays, it is dirt repellent, mechanically resistant and
with very limited heat transfer losses. It has practically no effects
on air side pressure drop.
Condensing coil with Blygold® treatment Condensing coil with Heresite P413 treatment
The Heresite P413 treatment is a thin film, high performance coating
used for protecting heat exchangers. It is the first HVAC-R coil
The Blygold® treatment provides a long-lasting corrosion
coating to meet the ISO 20340 Standard for severe offshore marine
protection to heat exchangers, without affecting heat transfer and
environments. The corrosion resistance of Heresite P413 coatings
pressure drop. The heat conductive pigmentation in the coating
significantly extends the service life of heat exchangers. In addition
is oriented in such a way that it creates a very high chemical
to marine and salt air environments, the P413 coatings will withstand
resistance at a low layer thickness.
exposure to an extensive variety of high and low pH corrosive and
chemical fumes and condensate.
Condensing coil with Thermoguard treatment Cu/Cu condensing coil
The Thermoguard treatment is a polyurethane-based anticorrosive
coating with high flexibility that protects the exchangers from the
hostile conditions of corrosive environments, ensuring longer life
Condensing coil with copper tubes and copper fins, solution provided to
of the unit. The product includes aluminum pigments that improve
increase heat exchange efficiency. Available for “PE” models only.
its thermal conductivity and resistance to UV rays. The purpose
of the product is to provide protection and prevention against the
chemical and galvanic corrosion of the heat exchangers.

www.euroklimat.it 59
Standard equipment and Accessories
Refrigerant circuit section
Standard accessories
High & Low pressure manometers Compressor crankcase oil heater

Crankcase oil heater directly installed on the compressor in


Gauges for the control of low and high refrigerant pressures,
order to increase compressor reliability and ensure adequate oil
embedded in glycerine.
temperature.

Suction and discharge compressor’s valves Electronic expansion valve


Electronic expansion valve for the accurate and timely control of
Intercepting valves on compressor’s suction and discharge sides to
the superheater level, after evaporation and many others operative
facilitate maintenance activities.
functions.

Pressure switch-HP side Safety valve – HP side


Safety valve(s) installed on HP side according to EN- 378:2016 standard
to protect the circuit against highpressure risk. The safety valve(s) is (are)
Pressure switch installed on HP side according to EN-378:2016
standard for some models only, according to EN-378:2016 requirements.
standard to protect the circuit against high-pressure risk.
See accessories Table for more details. All safety valves are conveyed
outside the unit.

Optional accessories
Pressure switch - LP side Safety valve – LP side

Pressure switch installed on LP side to prevent risks related to Safety valve(s) installed on LP side to protect refrigeraton circuit against
excessively low evaporating temperatures. highpressure risk. All safety vals are conveyed outside the unit.

Double Safety valve with changeover valve Gauges

Double safety vale with changeover valve installed to ensure easy


maintenance. This solution is available both for HP and LP side. All Gauges for the control of oil pressure, embedded in glycerine.
safety valves are conveyed outside the unit.

60 www.euroklimat.it
Standard equipment and Accessories
Electrical cabinet section
Standard accessories
Electrical panel installed outside the unit Double- barrier
To ensure higher security level, the cabinet is mounted outside the
machine.
The cable entry plates consist of a robust hard frame made of
Standard power supply: 400V/3ph/50hz.
plastic which ensure the tightness of the electrical panel.
The propane sensor is equipped with separate power supply.
Emergency power supply: 230V/1ph/50hz
Optional accessories
Phase monitoring sequence relay Min./Max. voltage relay

Min and max power supply relays mounted directly inside


Sequence phases relay mounted directly inside the
the electrical box and with the function of stopping the unit
electrical box and with the function of stopping the unit in
in case the power supply voltage is outside the tolerance
the case where the phase sequence is not correct.
range.

Anti-condensation heater with thermostat Power factor correction capacitors for compressors

System ables to ensure, inside the enclosure, temperature Power factor compressor capacitor to keep the value of the
value properely above the dew point. cosφ higher than 0,9.

Emergency power electronic expansion valve (Ultracap module) Device for measuring the electric energy consumed (Energy meter)

Ultracap is a emergency power supply device for systems Measuring instrument dedicated to the detection of the
that use electronic expansion valves: this device ensures main electrical parameters and the consumption of the
complete closing of the valves even when there are sudden connected loads.Energy meter records consumption and
mains power failures. allows for a complete and detailed analysis.

Compressors’ capacity steps – RSH Heads Inverter

The innovative RSH technology limits overheating and avoid Inverter driven compressor allows to increase drastically the
the compressor to work unbalanced, ensuring optimized efficiency at part loads.
operation at partial loads even for long operation periods. NOTE: The technical data shown in this catalogue refer to
One RSH head is standard for HE+ models. the unit without VFD accessory.

Control section
Optional accessories
Remote control panel Connectivity

Remote user terminal can be used to get all the readings Most of the common
and duplicate commands on a second display located at communication protocol
a distance and in more accessible site compared to the are available for integration
microprocessor on board the machine. with the BMS.

www.euroklimat.it 61
Standard equipment and Accessories
Water circuit section
Standard accessories
Differential pressure switch Electromechanical water flow switch (supplied separately)

Differential pressure switch with function to control the failure Electromechanical flow switch with function to control the
or reduced water flow. failure or reduced water flow.

Air vent valve (manual) Increased thermal insulation – 19 mm

Closed-cell thermal insulation with special thickness of 19


mm, which ensures an adequate protection against moisture
Manual air vent valve for discharging air from water circuit.
from condensation. For Integrated version adequate insulation
is provided also for the pump.

Optional accessories
Pressure relief valve (4,5 bar setting) Electronic water flow switch (supplied separately)

Pressure relief valve for hydraulic circuit. Electronic flow switch with function to control the failure or
Default setting: 4.5 Bar reduced water flow.

Automatic overpressure by-pass valve Air vent valve (automatic)

Water circuit automatic overpressure by-pass valve. Automatic air vent valve for discharging air from water circuit.

Sacrificial anode installed inside the unit Non-ferrous water circuit

Sacrificial anode installed inside the unit prevents the


Water circuit made entirely from non-ferrous material.
evaporator corrosion by means cathodic protection.

High pressure water pump (increased pump pressure) Double water pump (stand-by) - Standard pressure

Pumping group consisting of high head centrifugal electric Pumping group consisting of two centrifugal electric pumps,
pump (peripheral for models 21 and 31), suitable for water one in stand-by (peripheral for model 21), with standard
circuits with high pressure drops. pressure drops.

Open expansion tank Closed expansion tank with automatic filling valve

Closed expansion vessel for the containment of pressure


Open expansion vessel for the containment of pressure
variations in the water circuit. The fluid is separated from
variations in the water circuit. The fluid is in direct contact
the gas chamber by a diaphragm and the tank is equipped
with the atmosphere.
with an automatic filling valve.

Flanged connections Victoulic couplings

Flanged couplings for water connections. Available


Victoulic couplings for water connections, which
materials: carbon steel and AISI 304L steel (only for non-
ensure easy start-up operations.
ferrous circuits).

62 www.euroklimat.it
Standard equipment and Accessories
Safety section
Standard accessories
ATEX certified Gas detector EC emergency fan

The unit is equipped with a stand-alone gas detection The centrifugal EC fan, managed by the microprocessor, is
activated in case of R290 leakage and the ventilation lasts until the
system. The sensor is ATEX certified and is pre-calibrated
dilution of the refrigerant gas is completed. Additional accessories
at the factory. The standard setting is set at 10% of LFL are available to convey the air discharge. Power supply: 230V-1ph-
(Low Flammability Limit). 50Hz
Optional accessories
Double gas detector Flanged connection for emergency fan air outlet

The redundancy of the ATEX certified gas detector allows a Flange to convey the air discharge in rectangularsection
higher level of security to be achieved. air ducts. The flange is supplied separately.

Calibration kit Emergency stop button


The R290 leak detector requires periodic maintenance: the
calibration must be carried out according to the indications
of the manual. The calibration kit, which allows calibration Safety switch for emergency stop installed on the electrical
to be carried out quickly and easily, consists of:
- adapter; panel.
- pressure regulator and pressure gauge;
- service tool
Sound alarm

The sound alarm, installed on the electrical panel, is


activated in case of R290 leakage.

www.euroklimat.it 63
/BS
Standard equipment and Accessories
7-1-1 PE 17-1-1 PE 48-1-1 PE 49-2-2 PE 79-2-2 PE 126-2-2 PE 158-2-2 PV
CRIO/BS <-> <-> 39-1-1 PE <-> 38-2-2 PE <-> <-> <-> <->
12-1-1 PE 33-1-1 PE 55-1-1 PE 68-2-2 PE 108-2-2 PE 173-2-2 PE 182-2-2 PV

General
Anti-vibration rubber mounts - - - - -
Anti-vibration spring mounts - - - -
Anti-vibration seismic spring mounts - - - -
Condensing coil protection panel - -
Condensing coil protection grid - - - - - - - -
Anti-intrusion grills - upper part - - - - - - - -
Anti-intrusion grills - lower part - - - - - - - -
Condensing coil filter in micro-stretched aluminum mesh
Aluminum panels (fan panel not included) - -
Stainless steel (AISI 304) panels (fan panel not included) - -
Closed compressor(s) box(es) - - - - - - - -
Wooden cage packing without base - -
Standard packing with wooden base - - - - - - - -
Sound insulating panels compressor(s) box(es) [LN version]
Sandwich insulating panels compressor(s) box(es) [SL version]
System of blocks for long-distance transport - - - - - - - -
Condensing section
Condensing coil in copper and turbulent aluminum fins -
Microchannel condensing coil made of aluminum - - - - - - - -
Condensing coil with ElectroFin® treatment (*****)
Condensing coil with AiAX Coatings treatment
Condensing coil with Blygold® treatment
Condensing coil with Heresite P413 treatment
Condensing coil with Thermoguard treatment
Condensing coil in copper/copper -
EC Fans (brushless motor)
EC Fans (brushless motor) with diffuser kit - - - - - - - -
Refrigerant circuit section
Compliance with PED Directive (2014/68/EU)
Low pressure transducer
High pressure transducer
Low pressure safety switch
High pressure safety switch
High & Low pressure gauges
Compressor crankcase oil heater
Compressor suction and discharge valve
Electronic expansion valve
Safety valve low pressure side (LP) (*) -
Double Safety valve with changeover valve low pressure side (LP) (*)
Safety valve low pressure side (HP) (*)
Double Safety valve with changeover valve low pressure side (HP) (*)
Oil pressure gauge
Oil charge
Unit charged with Nitrogen
Unit charged with R290 (ADR transport, if required, managed by customer)

(*) conveyed discharge


(*****) For 158 --> 182 2-2 PV consider E-Coating® treatment
standard equipment optional - not available
64 www.euroklimat.it
/BS
Standard equipment and Accessories
7-1-1 PE 17-1-1 PE 48-1-1 PE 49-2-2 PE 79-2-2 PE 126-2-2 PE 158-2-2 PV
CRIO/BS <-> <-> 39-1-1 PE <-> 38-2-2 PE <-> <-> <-> <->
12-1-1 PE 33-1-1 PE 55-1-1 PE 68-2-2 PE 108-2-2 PE 173-2-2 PE 182-2-2 PV

Water circuit section


Differential pressure switch
Electromechanical water flow switch
Electronic water flow switch
Pressure relief valve [Only for Integrated Version]
Air vent valve (manual)
Air vent valve (automatic)
Manual by-pass valve
Overpressure valve / automatic by-pass
Increased thermal insulation - thickness 19 mm & pump insulation
Water filter (supplied separately)
Flange for water fittings (carbon steel A105)
Flange for water fittings (AISI 304L)(**)
Flange and counterflange for water fittings (carbon steel A105)
Flange and counterflange for water fittings (AISI 304L)(**)
Victaulic® type water connections
Sacrificial anode
Non-ferrous water circuit
Water pump - Standard pressure (1,5 bar) [Only for Integrated Version]
High pressure water pump (3 bar)
Double water pump (stand-by) - Standard pressure
Double water pump (stand-by) - Increased pressure
Pump suction and discharge valve [Only for Integrated Version]
Water tank [Only for Integrated Version]
Open expansion tank
Closed expansion vessel with automatic filling unit
Water pipes/evaporator with trace heating
Electric cabinet section
Electrical panel installed outside the unit
Electrical panel weather protection cover
Power supply without neutral
Separate power supply for propane safety devices 230V/1ph/50Hz
Device locking doors windproof cabinet
Phase monitoring sequence relay (***)
Min./max. voltage relay
Anti-condensation heater with thermostat
Power factor correction capacitors for compressors (***)
Part winding compressors (PWS) -
Emergency power electronic expansion valve (Ultracap module)
Device for measuring the electric energy consumed (Energy Meter)
Service socket 230VAC - max. 150 Watt
LED cabinet lighting
N°1 compressors' capacity step (RSH Head)
N°2 compressors' capacity steps (RSH Heads)
N°3 compressors' capacity steps (RSH Heads) - - - -
N°4 compressors' capacity steps (RSH Heads) - - - - - - -
Inverter driven compressor(s)
Integratd Electronic Security module installed inside the electrical panel

(**) only for non ferrous water circuit


(***) not available with inverter
standard equipment optional - not available
www.euroklimat.it 65
/BS
Standard equipment and Accessories
7-1-1 PE 17-1-1 PE 48-1-1 PE 49-2-2 PE 79-2-2 PE 126-2-2 PE 158-2-2 PV
CRIO/BS <-> <-> 39-1-1 PE <-> 38-2-2 PE <-> <-> <-> <->
12-1-1 PE 33-1-1 PE 55-1-1 PE 68-2-2 PE 108-2-2 PE 173-2-2 PE 182-2-2 PV

Control section
Display with 3 digits and digital point
Remote control panel
Operating hour meter (Compressor, water pump)
Clock board and alarm history up to 20 events (data logger function)
Advanced electronic controller (c.pCO)
Second set-point from digital input
Remote On/Off digital input
Set point compensation by outside temperature
ModBus® interface RS 485 (*)
LonWorks® interface (***)
BACnet® MS/TP interface (**)
BACnet® TCP/IP interface (**)
Software updates via USB key (***)
Update with transferring files via FTP (**)
tERA cloud service - UMTS/3G (**)
tERA cloud service - Ethernet (**)
Floating HP (****)
Safety section
Gas detector with separate electrical supply
EC extraction fan activated in case of R290 leakage
Double gas detector with separate electrical supply
Flange for extraction line discharge (supplied separately)
HP Safety valve(s) with conveyed discharge (if requested by EN 378:2016)
Calibration kit for refrigerant leak detector
Emergency stop button
Sound alarm activated in case of R290 leakage

(*) standard on c.pCO machines, for machines with Microchiller2 contact EK


(**) Available only with c.pCO, not available with Microchiller2
standard equipment optional - not available
(***) Available only with c.pCO
(****) Standard equipment with c.pCO, for other versions contact EK

66 www.euroklimat.it
/HE
Standard equipment and Accessories
10-1-1 PE 17-1-1 PE 30-1-1 PE 41-1-1 PE 41-2-2 PE 83-2-2 PE 130-2-2 PV
CRIO/HE <-> <-> <-> <-> <-> <-> <->
14-1-1 PE 24-1-1 PE 35-1-1 PE 56-1-1 PE 70-2-2 PE 116-2-2 PE 185-2-2 PV

General
Anti-vibration rubber mounts - - - - -
Anti-vibration spring mounts - -
Anti-vibration seismic spring mounts - -
Condensing coil protection panel - -
Condensing coil protection grid - - - - - - -
Anti-intrusion grills - upper part - - - - - -
Anti-intrusion grills - lower part - - - - - -
Condensing coil filter in micro-stretched aluminum mesh -
Aluminum panels (fan panel not included) - -
Stainless steel (AISI 304) panels (fan panel not included) - -
Closed compressor(s) box(es) - - - - - -
Wooden cage packing without base - -
Standard packing with wooden base - - - - - - -
Sound insulating panels compressor(s) box(es) [LN version]
Sandwich insulating panels compressor(s) box(es) [SL version]
System of blocks for long-distance transport - - - - - -
Condensing section
Condensing coil in copper and turbulent aluminum fins -
Microchannel condensing coil made of aluminum - - - - - -
Condensing coil with ElectroFin® treatment (*****)
Condensing coil with AiAX Coatings treatment
Condensing coil with Blygold® treatment
Condensing coil with Heresite P413 treatment
Condensing coil with Thermoguard treatment
Condensing coil in copper/copper -
EC Fans (brushless motor)
EC Fans (brushless motor) with diffuser kit - - - - - -
Refrigerant circuit section
Compliance with PED Directive (2014/68/EU)
Low pressure transducer
High pressure transducer
Low pressure safety switch
High pressure safety switch
High & Low pressure gauges
Compressor crankcase oil heater
Compressor suction and discharge valve
Electronic expansion valve
Safety valve low pressure side (LP) (*)
Double Safety valve with changeover valve low pressure side (LP) (*)
Safety valve low pressure side (HP) (*) -
Double Safety valve with changeover valve low pressure side (HP) (*)
Oil pressure gauge
Oil charge
Unit charged with Nitrogen
Unit charged with R290 (ADR transport, if required, managed by customer)

(*) conveyed discharge


(*****) For 158 --> 182 2-2 PV consider E-Coating® treatment
standard equipment optional - not available
www.euroklimat.it 67
/HE
Standard equipment and Accessories
10-1-1 PE 17-1-1 PE 30-1-1 PE 41-1-1 PE 41-2-2 PE 83-2-2 PE 130-2-2 PV
CRIO/HE <-> <-> <-> <-> <-> <-> <->
14-1-1 PE 24-1-1 PE 35-1-1 PE 56-1-1 PE 70-2-2 PE 116-2-2 PE 185-2-2 PV

Water circuit section


Differential pressure switch
Electromechanical water flow switch
Electronic water flow switch
Pressure relief valve [Only for Integrated Version]
Air vent valve (manual)
Air vent valve (automatic)
Manual by-pass valve
Overpressure valve / automatic by-pass
Increased thermal insulation - thickness 19 mm & pump insulation
Water filter (supplied separately)
Flange for water fittings (carbon steel A105)
Flange for water fittings (AISI 304L)(**)
Flange and counterflange for water fittings (carbon steel A105)
Flange and counterflange for water fittings (AISI 304L)(**)
Victaulic® type water connections
Sacrificial anode
Non-ferrous water circuit
Water pump - Standard pressure (1,5 bar) [Only for Integrated Version]
High pressure water pump (3 bar)
Double water pump (stand-by) - Standard pressure
Double water pump (stand-by) - Increased pressure
Pump suction and discharge valve [Only for Integrated Version]
Water tank [Only for Integrated Version]
Open expansion tank
Closed expansion vessel with automatic filling unit
Water pipes/evaporator with trace heating
Electric cabinet section
Electrical panel installed outside the unit
Electrical panel weather protection cover
Power supply without neutral
Separate power supply for propane safety devices 230V/1ph/50Hz
Device locking doors windproof cabinet
Phase monitoring sequence relay (***)
Min./max. voltage relay
Anti-condensation heater with thermostat
Power factor correction capacitors for compressors (***)
Part winding compressors (PWS) -
Emergency power electronic expansion valve (Ultracap module)
Device for measuring the electric energy consumed (Energy Meter)
Service socket 230VAC - max. 150 Watt
LED cabinet lighting
N°1 compressors' capacity step (RSH Head)
N°2 compressors' capacity steps (RSH Heads) -
N°3 compressors' capacity steps (RSH Heads) - - - -
N°4 compressors' capacity steps (RSH Heads) - - - - - -
Inverter driven compressor(s)
Integratd Electronic Security module installed inside the electrical panel

(**) only for non ferrous water circuit


(***) not available with inverter
standard equipment optional - not available
68 www.euroklimat.it
/HE
Standard equipment and Accessories
10-1-1 PE 17-1-1 PE 30-1-1 PE 41-1-1 PE 41-2-2 PE 83-2-2 PE 130-2-2 PV
CRIO/HE <-> <-> <-> <-> <-> <-> <->
14-1-1 PE 24-1-1 PE 35-1-1 PE 56-1-1 PE 70-2-2 PE 116-2-2 PE 185-2-2 PV

Control section
Display with 3 digits and digital point
Remote control panel
Operating hour meter (Compressor, water pump)
Clock board and alarm history up to 20 events (data logger function)
Advanced electronic controller (c.pCO)
Second set-point from digital input
Remote On/Off digital input
Set point compensation by outside temperature
ModBus® interface RS 485 (*)
LonWorks® interface (***)
BACnet® MS/TP interface (**)
BACnet® TCP/IP interface (**)
Software updates via USB key (***)
Update with transferring files via FTP (**)
tERA cloud service - UMTS/3G (**)
tERA cloud service - Ethernet (**)
Floating HP (****)
Safety section
Gas detector with separate electrical supply
EC extraction fan activated in case of R290 leakage
Double gas detector with separate electrical supply
Flange for extraction line discharge (supplied separately)
HP Safety valve(s) with conveyed discharge
Calibration kit for refrigerant leak detector
Emergency stop button
Sound alarm activated in case of R290 leakage

(*) standard on c.pCO machines, for machines with Microchiller2 contact EK


(**) Available only with c.pCO, not available with Microchiller2
standard equipment optional - not available
(***) Available only with c.pCO
(****) Standard equipment with c.pCO, for other versions contact EK

www.euroklimat.it 69
/HE+
Standard equipment and Accessories
10-1-1 PE 17-1-1 PE 30-1-1 PE 41-2-2 PE 83-2-2 PE 130-2-2 PV
CRIO/HE+ <-> <-> <-> 56-1-1 PE <-> <-> <->
14-1-1 PE 21-1-1 PE 36-1-1 PE 48-2-2 PE 116-2-2 PE 185-2-2 PV

General
Anti-vibration rubber mounts - - - - -
Anti-vibration spring mounts - -
Anti-vibration seismic spring mounts - -
Condensing coil protection panel - -
Condensing coil protection grid - - - - - -
Anti-intrusion grills - upper part - - - - - -
Anti-intrusion grills - lower part - - - - - -
Condensing coil filter in micro-stretched aluminum mesh
Aluminum panels (fan panel not included) - -
Stainless steel (AISI 304) panels (fan panel not included) - -
Closed compressor(s) box(es) - - - - - -
Wooden cage packing without base - -
Standard packing with wooden base - - - - - - -
Sound insulating panels compressor(s) box(es) [LN version]
Sandwich insulating panels compressor(s) box(es) [SL version]
System of blocks for long-distance transport - - - - - -
Condensing section
Condensing coil in copper and turbulent aluminum fins -
Microchannel condensing coil made of aluminum - - - - - -
Condensing coil with ElectroFin® treatment (*****)
Condensing coil with AiAX Coatings treatment
Condensing coil with Blygold® treatment
Condensing coil with Heresite P413 treatment
Condensing coil with Thermoguard treatment
Condensing coil in copper/copper -
EC Fans (brushless motor)
EC Fans (brushless motor) with diffuser kit - - - - - -
Refrigerant circuit section
Compliance with PED Directive (2014/68/EU)
Low pressure transducer
High pressure transducer
Low pressure safety switch
High pressure safety switch
High & Low pressure gauges
Compressor crankcase oil heater
Compressor suction and discharge valve
Electronic expansion valve
Safety valve low pressure side (LP) (*)
Double Safety valve with changeover valve low pressure side (LP) (*)
Safety valve low pressure side (HP) (*) -
Double Safety valve with changeover valve low pressure side (HP) (*)
Oil pressure gauge
Oil charge
Unit charged with Nitrogen
Unit charged with R290 (ADR transport, if required, managed by customer)

(*) conveyed discharge


(*****) For 158 --> 182 2-2 PV consider E-Coating® treatment
standard equipment optional - not available
70 www.euroklimat.it
/HE+
Standard equipment and Accessories
10-1-1 PE 17-1-1 PE 30-1-1 PE 41-2-2 PE 83-2-2 PE 130-2-2 PV
CRIO/HE+ <-> <-> <-> 56-1-1 PE <-> <-> <->
14-1-1 PE 21-1-1 PE 36-1-1 PE 48-2-2 PE 116-2-2 PE 185-2-2 PV

Water circuit section


Differential pressure switch
Electromechanical water flow switch
Electronic water flow switch
Pressure relief valve [Only for Integrated Version]
Air vent valve (manual)
Air vent valve (automatic)
Manual by-pass valve
Overpressure valve / automatic by-pass
Increased thermal insulation - thickness 19 mm & pump insulation
Water filter (supplied separately)
Flange for water fittings (carbon steel A105)
Flange for water fittings (AISI 304L)(**)
Flange and counterflange for water fittings (carbon steel A105)
Flange and counterflange for water fittings (AISI 304L)(**)
Victaulic® type water connections
Sacrificial anode
Non-ferrous water circuit
Water pump - Standard pressure (1,5 bar) [Only for Integrated Version]
High pressure water pump (3 bar)
Double water pump (stand-by) - Standard pressure
Double water pump (stand-by) - Increased pressure
Pump suction and discharge valve [Only for Integrated Version]
Water tank [Only for Integrated Version]
Open expansion tank
Closed expansion vessel with automatic filling unit
Water pipes/evaporator with trace heating
Electric cabinet section
Electrical panel installed outside the unit
Electrical panel weather protection cover
Power supply without neutral
Separate power supply for propane safety devices 230V/1ph/50Hz
Device locking doors windproof cabinet
Phase monitoring sequence relay (***)
Min./max. voltage relay
Anti-condensation heater with thermostat
Power factor correction capacitors for compressors (***)
Part winding compressors (PWS) -
Emergency power electronic expansion valve (Ultracap module)
Device for measuring the electric energy consumed (Energy Meter)
Service socket 230VAC - max. 150 Watt
LED cabinet lighting
N°1 compressors' capacity step (RSH Head)
N°2 compressors' capacity steps (RSH Heads) -
N°3 compressors' capacity steps (RSH Heads) - - - -
N°4 compressors' capacity steps (RSH Heads) - - - - - -
Inverter driven compressor(s)
Integratd Electronic Security module installed inside the electrical panel

(**) only for non ferrous water circuit


(***) not available with inverter
standard equipment optional - not available
www.euroklimat.it 71
/HE+
Standard equipment and Accessories
10-1-1 PE 17-1-1 PE 30-1-1 PE 41-2-2 PE 83-2-2 PE 130-2-2 PV
CRIO/HE+ <-> <-> <-> 56-1-1 PE <-> <-> <->
14-1-1 PE 21-1-1 PE 36-1-1 PE 48-2-2 PE 116-2-2 PE 185-2-2 PV

Control section
Display with 3 digits and digital point
Remote control panel
Operating hour meter (Compressor, water pump)
Clock board and alarm history up to 20 events (data logger function)
Advanced electronic controller (c.pCO)
Second set-point from digital input
Remote On/Off digital input
Set point compensation by outside temperature
ModBus® interface RS 485 (*)
LonWorks® interface (***)
BACnet® MS/TP interface (**)
BACnet® TCP/IP interface (**)
Software updates via USB key (***)
Update with transferring files via FTP (**)
tERA cloud service - UMTS/3G (**)
tERA cloud service - Ethernet (**)
Floating HP (****)
Safety section
Gas detector with separate electrical supply
EC extraction fan activated in case of R290 leakage
Double gas detector with separate electrical supply
Flange for extraction line discharge (supplied separately)
HP Safety valve(s) with conveyed discharge
Calibration kit for refrigerant leak detector
Emergency stop button
Sound alarm activated in case of R290 leakage

(*) standard on c.pCO machines, for machines with Microchiller2 contact EK


(**) Available only with c.pCO, not available with Microchiller2
standard equipment optional - not available
(***) Available only with c.pCO
(****) Standard equipment with c.pCO, for other versions contact EK

72 www.euroklimat.it
Applications

Food
The food industry requires various types of cooling, ranging from
Cooling request for production processes to the storage of semi-
finished food products.
CRIO units are the right solution for all these applications.

Pharma
Euroklimat’s liquid chillers used in the pharmaceutical chemical
industry work reliably and economically, ensuring process continuity
at all times and perfect temperature control.

Shopping Centres
The basic main advantages are the efficiency of CRIO solutions and
the ability to provide heating and cooling at the same time, using the
DS (Desuperheater) or HR (Total heat recovery) option.

Industries
Chemical, Textile, Winery, Plastic: thanks to their efficiency and
reliability, CRIO chillers keep energy costs as low as possible which
is the most important thing for any industry

www.euroklimat.it 73
Acoustic configurations
ST - Standard

This solution is suitable


for installations where
no particular silence is
required.

Painted galvanized sheet panels

LN - Low Noise

It represents a good
compromise between
price and performance in
terms of reducing noise
levels.
Painted galvanized sheet panels, insulated
with polyurethane foam sheets, polyester
based, anthracite colour, self-extinguishing
non dripping.

SL - Super Low Noise

This configuration is ideal


for all applications where
the noise of the machine is
an essential aspect.

Sandwich soundproofing galvanized sheet


panels, painted outside and isolated with high-
density rock wool (100 Kg/m3)

74 www.euroklimat.it
Sound levels
Sound levels are obtained by means of theoretical calculations that could deviate from the real conditions of the place of installation of
the unit.

Sound Power: this is the acoustic emission of the unit when operating. It is dependent on operating conditions.
Sound power level in compliance with ISO 3744.

Sound Pressure: this is the measurement of the effect of the acoustic emission generated by the unit at a certain distance and in the
acoustic environment (reflection, absorption, directivity) in which it operates. The value will depend on the sound
power of the unit, the directivity of the source and the reflectivity of the surroundings. Sound pressure level (average
value), calculated for unit in a free field on a reflective surface; non-binding value obtained from the sound power
level.

It is assumed that sound power and sound pressure are linked together by defining the space and conditions as follows:

■■ the source is omnidirectional, i.e. the acoustic emission is the same in all directions
■■ the conditions are free field, i.e. at 1 meter from the source there is no effect from acoustic wave reflections with the
exception of the support plane

The power is therefore distributed over an imaginary sphere around the unit and the following relationship applies:

■■ sound pressure at 1 m = sound power - 11 dB (A)

www.euroklimat.it 75
Dimensions and Operating spaces
Frame 1
CRIO/BS CRIO/HE CRIO/HE+
7-1-1 PE

Overall dimensions - Base unit Integrated unit


D mm 680 680
L mm 1.130 1.630
H mm 1.405 1.405

Frame 2
CRIO/BS CRIO/HE CRIO/HE+
9-1-1 PE 12-1-1 PE

Overall dimensions - Base unit Integrated unit


D mm 830 830
L mm 1.280 1.280
H mm 1.820 1.820

76 www.euroklimat.it
Dimensions and Operating spaces
Frame 3
CRIO/BS CRIO/HE CRIO/HE+
17-1-1 PE 28-1-1 PE 10-1-1 PE 17-1-1 PE 10-1-1 PE 17-1-1 PE

Overall dimensions - Base unit Integrated unit


D mm 1.025 1.025
L mm 1.580 1.580
H mm 2.090 2.090

Frame 4
CRIO/BS CRIO/HE CRIO/HE+
33-1-1 PE 39-1-1 PE 20-1-1 PE 24-1-1 PE 21-1-1 PE
38-2-2 PE

Overall dimensions - Base unit Integrated unit


D mm 1.025 1.025
L mm 2.230 2.230
H mm 2.190 2.190

www.euroklimat.it 77
Dimensions and Operating spaces
Frame 5
CRIO/BS CRIO/HE CRIO/HE+
30-1-1 PE 35-1-1 PE 30-1-1 PE 36-1-1 PE

Overall dimensions - Base unit Integrated unit


D mm 1.025 1.025
L mm 2.880 2.880
H mm 2.190 2.190

Frame 6
CRIO/BS CRIO/HE CRIO/HE+
48-1-1 PE 55-1-1 PE 41-1-1 PE 48-1-1 PE
49-2-2 PE 68-2-2 PE

Overall dimensions - Base unit Integrated unit


D mm 1.025 1.025
L mm 2.880 2.880
H mm 2.288 2.288

78 www.euroklimat.it
Dimensions and Operating spaces
Frame 7
CRIO/BS CRIO/HE CRIO/HE+
- 56-1-1 PE 56-1-1 PE
41-2-2 PE 60-2-2 PE 41-2-2 PE 48-2-2 PE

Overall dimensions - Base unit Integrated unit


D mm 1.025 1.025
L mm 3.820 3.820
H mm 2.250 2.250

Frame 8
CRIO/BS CRIO/HE CRIO/HE+
79-2-2 PE 108-2-2 PE 70-2-2 PE -

Overall dimensions - Base unit Integrated unit


D mm 1.025 1.025
L mm 3.820 3.820
H mm 2.328 2.328

www.euroklimat.it 79
Dimensions and Operating spaces
Frame 9
CRIO/BS CRIO/HE CRIO/HE+
126-2-2 PE 137-2-2 PE 83-2-2 PE 97-2-2 PE 83-2-2 PE

Overall dimensions - Base unit Integrated unit


D mm 1.185 1.185
L mm 4.250 4.900
H mm 2.135 2.135

Frame 10
CRIO/BS CRIO/HE CRIO/HE+
158-2-2 PE 173-2-2 PE 116-2-2 PE 99-2-2 PE 116-2-2 PE

Overall dimensions - Base unit Integrated unit


D mm 1.535 1.535
L mm 5.450 5.450
H mm 2.300 2.300

80 www.euroklimat.it
Dimensions and Operating spaces
Frame 11
CRIO/BS CRIO/HE CRIO/HE+
158-2-2 PV 182-2-2 PV 130-2-2 PV 142-2-2 PV 130-2-2 PV 142-2-2 PV

Overall dimensions - Base unit Integrated unit


D mm 2.345 2.345
L mm 2.950 2.950
H mm 2.465 2.465

Frame 12
CRIO/BS CRIO/HE CRIO/HE+
- 161-2-2 PV 185-2-2 PV 161-2-2 PV 185-2-2 PV

Overall dimensions - Base unit Integrated unit


D mm 2.345 2.345
L mm 4.300 4.300
H mm 2.465 2.465

www.euroklimat.it 81
Euroklimat firmly believes that Customer Satisfaction is an indispensable factor for success. A priority objective to achieve this result is the
constant improvement of our products, services and the relative production processes.
For this reason, we work every day to create reliable products that can help our customers in their business.
To achieve this goal, for every single unit we produce there is a lot of work. Therefore, we are pleased to tell you how Euroklimat’s CRIO
Medium Temperature Chillers are made.

1 Products design and development 2 Supply chain

Starting from market’s needs we draft a concept which is The materials procurement process is the result of a
then transformed into a product. The design involves many constant partnership with all our suppliers and a careful
people of the company and results in the production of management of the timing. To do this we use modern
all the necessary documentation such as installation and manufacturing techniques such as MRP (Material
operating manual, P&ID diagrams, wiring diagrams, 3D Requirements Planning), trend analysis, which are some
drawings and much more. of the tools that feed the issuance of orders.
Euroklimat’s supply chain ends with the reception of the
materials and their quality check.

3 Mechanical assembly 4 Water circuit

The production of the units starts at the mechanical Then the production continues at the water circuit
assembly station. Here the structures are assembled and assembly station where all the components of this circuit
the main components such as compressors and heat are mounted.
exchangers are positioned and fixed.

82 www.euroklimat.it
How it is made
The whole production cycle is subjected to Euroklimat’s Quality Management System, that complies with the international standard UNI EN ISO 9001:2015, ensuring
quality and long-term reliability.

5 Refrigerant circuit 6 Electrical wiring

The next stop is at refrigerant circuit assembly station. Once completed the refrigeration and water circuit, we
Here the pipes of the circuit are assembled and brazed perform the electrical wiring and the connection between
welded, which will connect the various elements of the electric board and compressor, fan, pump, etc. .Each unit
unit, such as compressor(s), condenser(s), evaporator(s), is equipped with electric panel, built, wired and fully tested
etc. The refrigerant circuit is specifically designed in order at the factory. Wiring numeration and optimized layout
to minimize load losses and to avoid capacity reduction. facilitate troubleshooting. The installed components are
The circuit is entirely made of copper tube brazed with identified by nameplates to better identify the application
silver alloy and it is isolated on the suction part, in order to and the type of action.
avoid condensation.

7 Running test area 8 Final inspection and packaging area

The production cycle draws to a close at the running test The last phase of the production cycle concerns the
station. Here all models are individually tested in order to finishing of the units and the packaging for shipping. Here
check correct operation, refrigerant charge and settings of all the units are subjected to a final check and prepared for
microprocessor. the shipping. If a special packaging has not been requested
Once all the checks and inspections are completed and the standard one is realized with heat-shrinkable plastic
successfully passed, the units are disconnected from the film that cover the whole unit and protect it from dust,
testing station and moved to the last station: the shipping water and other atmospheric agents. Polystyrol corners
area. are also foreseen in order to protect the unit from potential
damages caused during transports. The units are then
ready for transportation and final installation.

www.euroklimat.it 83
Transport of the unit with R290 charge
The units are normally supplied with a nitrogen preload, at a pressure between 1 and 2 bar.
The installer must take care of the vacuum and circuit loading operations according to the
indications provided in the use and maintenance manual.

On request, the units can be supplied with R290 gas charge.

CRIO Chillers have United Nations number designation UN 3358.

Observance to national and international regulations is necessary if refrigeration equipment containing a charge of HC
refrigerant is to be transported. Particular requirements are generally determined by the equipment charge size. In general,
the applicable regulations require adequate packaging and marking.
Transport companies should also be consulted when transporting equipment containing HC refrigerants.

Transport by road Transport by sea Transport by air

Transport by road and rail within Europe is The International Maritime Dangerous Goods The International Civil Aviation Organisation/
covered by the Articles Dangereuses par Code, 2008 (IMDG) prescribes requirements International Air Transport Association,
Routier, 2009 (ADR). for transport of equipment by sea. 2009 (IATA) prescribes the regulations for
transport by air.
Equipment containing less than 12 kg of flammable Refrigerating machines containing less than This forbids transport of equipment containing
refrigerant is exempt from regulations for carriage 100g of flammable refrigerant are not subject to more than 0.1 kg in either passenger or cargo
provided it is protected by design (i.e. conforms the regulations. Otherwise packaging requires planes. If transport by air is necessary, the
to the appropriate safety standards). Where the special marking. Refrigerating machines may be regulations do permit up to 150 kg of flammable
charge is above 12 kg, the equipment is subject carried unpacked in crates or other appropriate refrigerant to be carried by cylinder, so systems
to the provisions for any receptacle containing over-packs, provided that the equipment has been can be charged on-site.
flammable gases. pressure tested and designed so as to prevent the
release of refrigerant during transport conditions.
However, if the charge is less than 12 kg then
these requirements do not apply.

ALL MODELS
NITROGEN CHARGE
ONLY
CRIO/BS 7-1-1 CRIO/BS 79-1-1 CRIO/BS 7-1-1 CRIO/BS 79-1-1
CRIO/HE 10-1-1 CRIO/HE 60-2-2 CRIO/HE 10-1-1 CRIO/HE 60-2-2
CRIO/HE+ 10-1-1 CRIO/HE+ 48-2-2 CRIO/HE+ 10-1-1 CRIO/HE+ 48-2-2

ALL OTHER MODELS ALL OTHER MODELS

84 www.euroklimat.it
Standard and optional packing
The standard packing foreseen for CRIO range consists of heat-shrinkable plastic film that cover the whole unit and protect it from
dust, water and other atmospheric agents. Polystyrol corner are also foreseen in order to protect the unit from potential damages caused
during transports.

Heat-shrinkable plastic film

Polystyrol corners

17-1-1 PE 55-1-1 PE
CRIO/BS 7-1-1 PE 12-1-1 PE 126-2-2 PE 182-2-2 PV
38-2-2 PE 108-2-2 PE
CRIO/HE - 10-1-1 PE 70-2-2 PE 83-2-2 PE 185-2-2 PV
CRIO/HE+ - 10-1-1 PE 48-2-2 PE 83-2-2 PE 185-2-2 PV

Standard packing
Standard packing with wooden base - -
Wooden cage packing without base -

standard equipment optional - not available

www.euroklimat.it 85
WebService2
What do I receive with my order?
When you order an Euroklimat product, after the order confirmation, you get your user ID and password to
access to WebService2.
With the advent of information technology, there are several possibilities for communication and transmission of
information in real-time.
Euroklimat wanted to exploit these instruments creating a website, which provides an important support to all
customers: WebService2.

WebService2 - web portal 24/7


The simple and intuitive interface of the site allows you to “browse”
WebService2 quickly and easily reach the information you need. Planned and
designed for the specific competences, “webservice”is a web
portal that enables customers or support centres to access the
detailed documentation for each single machine:
»» order confirmation, waybill and invoice
»» declaration of conformity
»» instructions manual
»» electric diagram
»» construction drawing
»» complete list of spare parts
»» ... and much much more.

86 www.euroklimat.it
WebService2
The information is consequently always available and up-to-date,
also when you are physically at the site of installation.

Thanks to the new features of WebService2, it is now possible


to check in real time the availability of spare parts for each serial
number, simply by accessing the service with your own web
credentials.

The “mission” of Euroklimat is always to improve the service


offered to customers.

www.euroklimat.it 87
R290 References
Customers who have chosen us

Nestlè Metro Roche Diagnostic

Coop Waitrose Danish Technological Institute

E.ON Kernkraft Carrefour Del Monte Foods

Colruyt STEF Clauger

John Lewis Birmingham Cityringen Copenhagen The Coca Cola Company

88 www.euroklimat.it
Some R290
Installations

www.euroklimat.it 89
www.euroklimat.it
Our plants
and quality management
Over 50 years of business
Since we set up business in 1963, the company’s head offices have always been
in Italy, near Milan. Today, our aim is to be a market leader in chillers with natural
refrigerant (propane): by doing this, we are helping the industry to become more
efficient, preserving natural resources and protecting the environment.

Organization in Italy
At our Italian plant spread over an area of 6,000 square metres, with a work force
of 60 people, Euroklimat designs and produces refrigeration units, heat pumps
and precision air conditioners that can be used both in industrial processes and
traditional comfort applications.

Infinite quality
Euroklimat firmly believes that Customer Satisfaction is an indispensable factor for
success. A priority objective to achieve this result is the constant improvement of
our products, services and the relative production processes.
This objective means involving all of the company’s resources with planned,
systematic activities for Quality; for this reason, our system complies with the
international standard UNI EN ISO 9001:2015.

Organization in China
Our plant covers a surface of approximately 100,000 square metres, with
over 1,000 people and includes a large test chamber and a sophisticated R&D
laboratory, in addition to real production departments, where the performance of
the units is measured before being placed on the market.

COMPANY
WITH QUALITY SYSTEM
CERTIFIED BY DNV GL
= ISO 9001 =

Factory Italy • Siziano Factory China • Huangjiang, Dongguan, Guangdong

www.euroklimat.it 91
The data are indicative and not binding. Euroklimat reserves the right to make changes at any time without notice
99992065 CATALOGO “CRIO” “CRIO_01_20_rev0_ENG”

EUROKLIMAT SpA Euroklimat Co., Ltd EUROKLIMAT FZCO

Factory Italy Factory China Office Dubai

Via Liguria, 8 Euroklimat Industrial Park, High Bay Office 24, Dubai Silicon Oasis,UAE
27010 Siziano (PV) Italy Huangjiang, Dongguan, Guangdong, China PO Box 28178, Dubai, UAE

T: +39 038 2610282 T +86 0769 8366 0888 ext. 8260 T + 971 4 3423152
E: [email protected] E: [email protected] E: [email protected]

www.euroklimat.it www.euroklimat.com.cn www.euroklimatme.com



You might also like