MCCB NDM5 250V Products Specification

The NDM5-250V series moulded case circuit breakers are designed for AC circuits with a rated insulation voltage of 1000V and provide protection against overload, short circuit, and under-voltage. They come in various rated currents (63A to 250A) and comply with IEC 60947-2 and GB/T 14048.2 standards. The document details specifications, installation modes, accessories, and operational characteristics for effective use and maintenance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
73 views9 pages

MCCB NDM5 250V Products Specification

The NDM5-250V series moulded case circuit breakers are designed for AC circuits with a rated insulation voltage of 1000V and provide protection against overload, short circuit, and under-voltage. They come in various rated currents (63A to 250A) and comply with IEC 60947-2 and GB/T 14048.2 standards. The document details specifications, installation modes, accessories, and operational characteristics for effective use and maintenance.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 9

Document No.

: NDT2930356 Document Version: 3

1 Applicable Scope and Purpose


The NDM5-250V series of moulded case circuit breakers (referred to as circuit breakers) have a rated
insulation voltage of 1000V and apply to circuits with the AC 50Hz/60Hz, the rated working voltage of AC
1000V and rated working current (63A, 80A, 100A, 125A, 160A, 200A, 250A). The circuit breakers are used for
distributing power while protect the overload, short circuit and under-voltage (with a under-voltage release) of
lines and power units as well as the infrequent starting, braking, overload and short circuit of motors.
The circuit breaker has an isolating function with the corresponding symbol of ;
Comply with standards: IEC 60947-2, GB/T 14048.2.

2 Picture of the Product

3P Product
3 Specification and Model Description
ND M 5 – 250 V M □/ 3 / □ /□ □ □ □ □ Order code / Industry code
Accessories: See Table 1
Operation mode: See Note 5
Cabling mode: See Note 4
Installation mode: See Note 3
Release code: See Note 2
Number of poles
Rated current In (A): See Note 1
Breaking level code
High voltage
Frame current Inm (A): 250
Design SN
Moulded case circuit breaker (MCCB)
“Nader”

Page 1/9
Document No.: NDT2930356 Document Version: 3

Note: 1) Rated current In (A): 63, 80, 100, 125, 160, 200, 250
2) Release code:
TMF (power distribution protection-thermal magnet-fixed) [Ir=In, Im=10In];
TMD (power distribution protection-thermal magnet-adjustable)
63A-125A: [thermo-adjustable (0.8-0.9-1.0) In, magnet-fixed];
160A-250A: [thermo-adjustable (0.8-0.9-1.0) In, magnet-adjustable (5-6-7-8-9-10) In]
3) Installation mode: fixed type: no code
4) Cabling mode: front connection: no code
5) Operation mode: direct handle-operated: no code; rotation handle operated: “R”.
Table 1

Installation
Accessory code Accessory name
position

00 None —

08 Alarm contact

10 Shunt release

30 Under-voltage release

21 Single auxiliary contact

61 Two sets of single auxiliary contacts

23 Three sets of single auxiliary contacts

18 Shunt release, alarm contact

38 Under-voltage release, alarm contact

22 Single auxiliary contact, alarm contact


Two sets of single auxiliary contacts, alarm
88
contact
Three sets of single auxiliary contacts, alarm
26
contact
Shunt release, single auxiliary contact, alarm
42
contact
Shunt release, two sets of single auxiliary
44
contacts, alarm contact
Shunt release, three sets of single auxiliary
46
contacts, alarm contact
Under-voltage release, single auxiliary
75
contact, alarm contact
Under-voltage release, two sets of single
77
auxiliary contacts, alarm contact
Under-voltage release, three sets of single
81
auxiliary contacts, alarm contact

41 Shunt release, single auxiliary contact

Shunt release, two sets of single auxiliary


11
contacts

Page 2/9
Document No.: NDT2930356 Document Version: 3

Shunt release, three sets of single auxiliary


12
contacts
71 Under-voltage release, single auxiliary contact
Under-voltage release, two sets of single
72
auxiliary contacts
Under-voltage release, three sets of single
73
auxiliary contacts
Note: Single auxiliary contact; Alarm contact;

Shunt release Under-voltage release


Handle
To be installed in the
To be installed in the
upper right corner
upper left corner

To be installed To be installed in the


in the lower lower right corner
left corner
4 Main Technical Parameters
Frame current Inm(A) 250
Rated current In(A) 63,80,100, 125, 160, 200, 250
Rated voltage Ue (V) AC800, AC1000
Utilization category A
Rated impulse withstand voltage Uimp (V) 8000
Rated insulation voltage Ui (V) 1000
Power frequency withstand voltage (1min) (V) 3500
Rated frequency(Hz) 50/60
Rated Ultimate breaking AC800V 50
capacity Icu (kA) AC1000V 30
Rated Service breaking AC800V 35
capacity Ics (kA) AC1000V 15
Mechanical life 15000
Life(times)
Electrical life 1500

5 Normal Working Environment


2) Ambient air temperature: -40℃~+70℃;
3) Storage environment: -40℃~ +75℃;
4) Altitude: ≤2000m;
5) Class of pollution: 3;
6) Protection class: IP20;
7) Installation category: main circuit and under-voltage release: installation category Ⅲ; auxiliary circuit and
control circuit: installation category Ⅱ;
8) The product can be disposed in places that are free from explosive media, media corrosive to metal, insulation
damaging gas, and conductive dust.

Page 3/9
Document No.: NDT2930356 Document Version: 3

9) The product should be installed free from snow and rain.

Note: The tripping parameters of circuit breakers are set according to the ambient temperature of +50℃; in case
of the ambient temperature within +50℃~+70℃, users need to use the equipment for derating capacity.
See "Derating Factor Table of Product Temperature Change" for the derating factory.

6 Tripping Characteristics
6.1 Tripping characteristics curve under normal environment (ambient air temperature: +50℃)

6.2 Parameter setting and function description of the thermo-magnetic adjustable AC distribution release
Setting gear of the overload long time-delay Ir 0.8In, 0.9In, 1.0In
Setting gear of the 63A-125A 10In (accuracy of ±20%)
instantaneous short-circuit Im 160A-250A 5In, 6In, 7In, 8In, 9In, 10In (accuracy of ±20%)
1.05 In (cold state) doesn't operates within 1 hour,
63A
1.3 In (thermal state) operate within 1 hour
Action time
1.05 In (cold state) doesn't operates within 2 hours,
80A-250A
1.3 In (thermal state) operate within 2 hours
160A-250A features the thermo-magnetic parameter dual-adjustable functions and dual-display functions of
overload and short-circuit fault actions.
6.3 The tripping characteristics should be corrected due to small changes when the ambient air temperature varies
Ambient air temperature Correction factor
40℃ 1.0
45℃ 1.0
50℃ 1.0
55℃ 0.93
60℃ 0.88
65℃ 0.86
70℃ 0.83

Page 4/9
Document No.: NDT2930356 Document Version: 3

Note: 1. The above derating factors are measured at the frame current;
2. When the operating ambient temperature is below ﹢50℃, the product can be used normally, without
requiring the derating capacity.
6.4 The tripping characteristics should be corrected due to small changes by considering the air insulation
characteristics and cooling capacity with the ambient temperature of +50℃ and the altitude above 2,000m.
Altitude (m) 2000 3000 4000 5000
Power frequency withstand voltage (V) 3500 3000 2500 2000
Average insulation class (V) 1Ui 1Ui 1Ui 0.95Ui
Maximum working voltage (V) 1Ue 1Ue 1Ue 0.95Ue
Average working current (A) 1In 0.96In 0.93In 0.9In
7 Product Outline and Installation Dimensions
7.1 External dimensions of products

Insulating
Plate

7.2 Product installation dimensions


7.2.1 Installed on the baseplate

Page 5/9
Document No.: NDT2930356 Document Version: 3

Insulating
Plate

Insulating Plate Dimensions Mounting Hole Dimensions


7.2.2 Safety spacing
See the figure below for the minimum safety distance of the circuit breaker from the top, bottom, side and
adjacent products during installation.

Safety Mounting Spacing between Circuit Breakers

Phase partition

Page 6/9
Document No.: NDT2930356 Document Version: 3

Notes: During use, a terminal cover and phase partition shall be installed respectively on the terminal
side of 1, 3, 5 as well as 2, 4, 6 as shown in the figure. Besides, an insulating plate shall be inserted
between the circuit breaker and the metal mounting plate
8 Installation Mode
The product allowable installation mode is shown as the figure below.

9 Product Power Consumption


Single-phase average
Product model Current specifications (A)
power consumption (W)
63 5
80 8.3
100 10
NDM5-250V 125 7.8
160 12.8
200 20
250 21.8
Note: The above data is the single power consumption of the circuit breaker measured
at an ambient temperature of 40℃ when the rated current is on.
10 Connection Capacity
Rated current (A) 63 80 100 125 160 200 250
Wire cross-section area (mm2) 16 25 35 50 70 95 120
Tightening torque value of the
15
terminal screw M8 (N.m)

11 Operation Instructions for Accessories


11.1 Rated parameters of the auxiliary contact
Accessory name Auxiliary contact
Voltage specifications (V)/conventional AC250V/10A, DC220V/0.2A
Wiring
Off
diagram

Page 7/9
Document No.: NDT2930356 Document Version: 3

On

Internal resistance <30 mΩ


11.2 Rated parameters of the alarm contact
Accessory name Alarm contact
Voltage specifications (V)/conventional AC250V/3A, DC220V/0.2A

On, off
Wiring
diagram
Free tripping

Internal resistance <30 mΩ


11.3 Under-voltage release
When the power voltage drops to the range (35%~70%) of the under-voltage release, the release can break
the circuit breaker reliably; when the power voltage is 35% lower than the rated working voltage of the
under-voltage release, the release can prevent closing of the circuit breaker; when the power voltage is 85%
higher than the rated working voltage of the under-voltage release, the release can guarantee reliable closing of
the circuit breaker
Voltage specifications of the under-voltage release: AC230V/DC250V.
Accessory name Under-voltage release
Voltage
AC230/DC250
specifications (V)
Power
1.0
consumption (W)

11.4 Shunt release


When the external voltage of the shunt release is between 70% and 110% of the rated control power voltage,
the release can break the circuit breaker reliably.
Accessory
Shunt release
name
Voltage
specifications AC24/DC24 AC230/DC250
(V)
Power
consumption 20 19
(W)

Working principle of the shunt release: a single pulse action. If another action is required, the shunt release
can only be operated after being off, reset and energized.

6
Page 8/9
Document No.: NDT2930356 Document Version: 3

Un

U线圈

50ms 200ms t

To make the circuit breaker fail to be closed normally during long-term energization, an auxiliary contact in
series is required.
C1 F4

C2,F1

11.5 The standard wire length of the internal accessories (auxiliary contact, alarm contact, under-voltage release,
shunt release) is 0.7m.
Note: Users must propose to the sales personnel of the special requirements of the accessory wire length.

12 Packaging and Storage


Minimum packaging quantity: 1 piece/box. The packaged products should be stored in a warehouse with the
ambient temperature of -40℃~75℃ and relative humidity below 80% without acidic, alkali or other corrosive gas
in the surrounding air. Under the conditions above, the storage period shall be no more than 36 months since the
manufacturing date.
13 List of accessories and installation

SN Name Specification Quantity

1 Cross small pan-head screw M5×110 4


2 Plain washer 5 4
3 Spring washer 5 4
4 Hexagon nut M5 4
5 Phase partition —— 2
6 Insulating plate —— 1
14 Precautions
1) The performance parameters of this specification are suitable for normal conditions. For special requirements,
put the equipment into use after consulting the company with formal confirmation and re-adjusting parameters
by the company.
2) The circuit breaker, tripping unit or other accessories can only be installed and maintained by the trained or
qualified professionals.
3) Ensure that the power supply is off before installing or removing any device.

Page 9/9