KS-ST-DEG-0001 Pipe Rack Design Guide
KS-ST-DEG-0001 Pipe Rack Design Guide
© Copyright 2019 Worley ACN 096 090 158. No part of this document or the information it contains may be reproduced or transmitted in any form or by any
means electronic or mechanical, including photocopying, recording, or by any information storage and retrieval system, without permission in writing from Worley.
worley.com
Table of Contents
1. Introduction ................................................................................................................................... 3
2. General Design Guidelines .............................................................................................................. 3
2.1 Rack Types ..................................................................................................................................... 3
2.2 Layout and Geometry .................................................................................................................... 3
2.3 Design Loads and Combinations .................................................................................................... 6
2.3.1 Dead Loads ................................................................................................................ 6
2.3.2 Snow Loads ............................................................................................................. 12
2.3.3 Live Loads ................................................................................................................ 12
2.3.4 Wind Loads .............................................................................................................. 13
2.3.5 Seismic Loads .......................................................................................................... 14
2.3.6 Upset Condition Loads ............................................................................................ 15
2.3.7 Load Combinations ................................................................................................. 16
2.3.8 Load Factors ............................................................................................................ 17
2.4 Analyzes and Design Considerations ........................................................................................... 17
2.4.1 Design Considerations............................................................................................. 17
2.4.2 Deflection Limits ..................................................................................................... 18
This guideline is prepared to promote consistency across projects and offices for the design of new piping
and electrical rack structures. It includes basic design methodology, layout considerations, basic loads and
combinations, and serviceability limits. The design approach is based on various industrial practices used
across the globe. The following guidelines may be overly conservative when validating the capacity of
existing rack structures.
OSBL Rack:
General Pipe Rack used to connect multiple process and utility units. Contains long sections with consistent
geometry, it does not support equipment, and has minimal platforming.
ISBL Rack:
Pipe rack located within a process or utilities unit. Usually centrally located within the unit, this pipe rack
connects the equipment internal to the unit and may also connect to the OSBL rack system. This pipe rack
has generally consistent layout and may include some small isolated platforms and equipment.
Process Rack:
Pipe rack located within a process or utilities unit. Usually centrally located within the unit, this pipe rack
connects the equipment internal to the unit and may also connect to the OSBL rack system. This pipe rack
supports a significant amount of equipment and may have large platform levels to support operation and
maintenance activities.
Secondary Rack:
Small rack structures connecting OSBL, ISBL, and Process racks to adjacent racks and equipment. They
generally have consistent geometry and may be designed similar to OSBL and ISBL racks.
These frames also provide the lateral stability for resisting wind and seismic loads acting transverse to the
piping run. The typical frame width is about 20 ft. (6m), however the width may be as small as 10 ft. (3m) or
as large as 40 ft. (12m) depending on the function of the pipe rack. Spacing of the frames is determined by
the allowable span of the pipe and tray that is being supported. Frames are typically spaced at 20 ft. (6m)
intervals but may be increased or decreased as necessary to optimize the design when supporting a
significant amount of large, or small diameter piping. Intermediate transverse members may be required
when supporting small bore piping, conduit, or small cable tray that may have a limited span. Coordinate
with the other design disciplines to determine the need for intermediate supports.
Final longitudinal stability “Braced Bays” are provided to transfer the longitudinal forces down to the
foundations. Each pipe rack should have at least one braced bay to provide longitudinal stability. Braced
bays should be located at a maximum spacing of 200 ft. (60m)
The effects of thermal expansion shall be considered for pipe racks over 200 ft. (60m), and when multiple
braced bays are used. Stringer beams in at least one bay may be omitted or slotted connections used to
relieve the accumulated forces due to thermal expansion between braced sections. Slotted connections or
omitting stringers is also preferred at rack intersections to eliminate the transfer of unwanted loads.
Usually, an anchor bay located near the center of a long pipe run. It is important to coordinate with the
Piping engineer early in the design process so that anchor bay locations can be established. Anchor bay and
expansion bay locations shall be considered at the same time.
Definition of Dead Load has no direct relation to the load factors used in some building codes. Refer to
governing building codes for applicable load factors.
Description Load
For the transverse beams of the pipe rack main frames, the total applied operating pipe load (pipe plus
contents) shall be taken as a uniformly distributed load of 20 psf (1.0 kN/m2) to 60 psf (3.0 kN/m2) as
determined by engineering judgment based on the average size and schedule of piping on each level.
For a pipe rack with multiple pipes between 1” and 10”, it is generally recommended to apply a uniformly
distributed load with loading intensity of 40 psf (2.0 kN/m2) which includes full operating load, insulation,
pipe fittings etc. This is equivalent to 8” (200 mm) diameter, schedule 40 bare pipes, full of water, at 14”
(350 mm) c/c spacing.
The weight of the pipe depends upon the schedule of pipe. If not known, standard schedule (schedule 40)
of pipe can be assumed. The empty load will be substantial for schedule 80 (XS) or higher than schedule 40
pipe.
For pipe racks with pipe diameters 12” or more, individual concentrated load shall be calculated and
applied at the pipe locations. The portion of the uniform load at this location may be deleted. The width of
uniform load that is removed should be based on the effective width of the pipe that will be modeled with
a concentrated load. The effective width should be taken as the overall diameter of the pipe including the
insulation plus ½ the standard minimum spacing to the next adjacent pipe on each side.
The stringers are also subjected to the vertical loads in case of pipe turning in or off the rack. Loads on
stringer beams shall include the loads from the intermediate beams if any, plus a uniformly distributed load
or a point load acting in the middle of the beam, whichever is governing. In absence of detailed design
information, a concentrated load of 2000 lbs (10 kN) located at the center of the beam may be used.
Concentrated loads for large pipes on stringers and intermediate transverse beams where pipes are turning
in and out shall be given special consideration. This loading should not normally be added to the design
load for the column or footing if the full pipe weight has already been considered on the transverse beam.
In this case the concentrated load should only be used for the local design of the stringer.
It should be noted that the testing of the pipe is always done one at a time so if the operating load is
considered as a load full of water for all pipes then this load case can be eliminated.
This load case is important when hydrotesting large vapor lines where operating load is almost equal to
empty load and test load with water can be substantially larger than operating. It is also possible that such
large vapor lines can be tested pneumatically. If pneumatic testing is used, this load case can be ignored,
confirm this condition with responsible discipline or project engineer.
The friction forces are generally not given by pipe stress group and will be calculated by structural group
depending upon the pipe operating loads and number of pipes.
The friction will be generated depending upon the materials which are sliding against each other. The
coefficient of static friction is given in the following table for reference.
1 (Teflon) 10% 5%
Under normal loading conditions with multiple pipes, torsional effects (from friction) on the local beam
need not be considered because the pipes supported by the beam limit the rotation of the beam to the
extent that the torsional stresses are minimal. This does not include anchors. Torsional effects from
anchors shall be specifically evaluated.
Anchor loads are generally considered to be permanent, acting on the pipe rack at anchor locations when
the pipe is in operating condition. Pipe anchor load should be treated as dead loads since they are present
throughout the life of the plant while in the operating condition and should be combined in the appropriate
live, wind and seismic load combinations. Anchor loads are generally applied as concentrated loads acting
at either the top flange or on the whole depth of the beam depending on the anchor design.
For straight run piping in racks, anchor loads are generally the reactions resulting from pipe friction and are
to be applied in the opposite direction. Although the anchor load is normally present only for a few lines,
the assumption of 10% friction/anchor loading will generate enough longitudinal loads for the design of
longitudinal frames, vertical bracings and foundations (refer to the Friction Load section above). This
assumption is specifically useful when the design is done for FEED (proposal stage) due to absence of
accurate stress data.
Friction and anchor forces are usually coupled and therefore cannot exist at the same place at the same
time, nor can they be in the same direction. Coupled friction and anchor forces have only an internal effect
on the structural system and do not affect the design of braced bays and foundations. Pipe anchors located
near rack intersections, locations where piping is entering and exiting the rack or cross areas of slotted
connections or discontinuous framing may have more influence on the entire structural system. Special
care should be taken with respect to the direction of application of friction and anchor forces to ensure
that summation and cancelation of forces are in alignment with the expected behavior and effects on
frames, braced bays, and foundations are properly accounted for.
All assumed and preliminary loads should be replaced with the final anchor forces provided by the Piping
Engineering group prior to releasing drawings to construction.
These loads are to be supplied by the pipe stress group either in the form of Stress ISOs or any other agreed
format.
Guide load shall be treated as dead load since these are present throughout the life of the plant in
operating condition. These loads shall form a part of operating load combinations and shall be combined
with live, wind, and seismic loads.
For pipe racks, guide loads are generally considered to have only local effects on beams and should be
provided by the Pipe Stress department. Where significant loads are provided, these are to be considered
when performing the local beam checks only. Guide loads located near rack intersections and at locations
where piping is entering and exiting the rack may have more influence. At these locations care should be
taken to ensure that effects on braced bays and frames are properly accounted for.
For multiple guide loads within one structure, the loads shall be applied with positive and negative values
to establish a net zero effect of forces transferred to the foundations and lateral force resisting system.
Dead loads for cable trays on pipe racks can be estimated as follows unless actual load information is
available:
II Mix of instrumentation and electrical cables with some conduit and/or large main feed
cables
III Instrumentation and electrical cables with large percentage of main feed cables.
Cable Tray Load Category Total Cable Tray Load Empty Load Contents Load
Design engineer should validate the expected cable loading with the Electrical department prior to
finalizing calculations.
For checking uplift due to wind and seismic loads during erection or shut down, the equipment contents
should not be considered.
Definition of Live Load has no direct relation to the load factors used in some building codes. Refer to
governing building codes for applicable load factors.
Unless otherwise specified in the project design criteria, the following live load intensities should be used.
Live Loads
Operating Platforms – with designated laydown and storage 150 psf (7.2 kN/m2)
Shielding effect of equipment, building or structure adjacent to the pipe rack structure shall be ignored.
Ae (Pipe) = (D + 0.1 W)
Where,
For new rack design, all levels are to be assumed as full of cable tray and /or pipe.
Ae (Tray) = (H + 0.1 W)
Where,
For new rack design, all levels are to be assumed as full of cable tray and /or pipe.
If multiple trays are stacked vertically, then the projected area for wind load shall be calculated by
multiplying the number of trays by H.
In absence of customer or local building code requirements the following information should be used when
determining the effective wind forces on the pipe rack and its components.
Guardrails (including toe plate) 2.0 0.8 sq. Ft/ft (0.25 m2/m)
Staircase with Guardrail (side elevation) 2.0 Guardrail area + channel depth
The seismic design loads should be applied in the longitudinal and transverse directions. Seismic design in
the oblique direction shall be considered as required by the governing building code.
Seismic design loads shall not be combined with wind or friction loads.
Seismic analyzes may be performed utilizing the equivalent static load procedure unless a more stringent
analyzes method (dynamic, response spectrum, etc.) is required by the governing building code or
customer requirements.
The slug loads shall be carefully applied with respect to direction, as indicated loads on the stress ISOs may
not act together due to time lag in the application of such loads.
Slug load condition is rare and shall be treated with care while combining with other transient loads like
live, wind and friction loads.
Stress analyzes results shall be used in the design of all structural supporting members for above
mentioned upset condition loads. These loads shall be included only in upset load combinations with the
factor of dead load for only those load combinations. Note that impact factor shall be included in the basic
load application.
a. Empty Condition
b. Operating Condition
c. Upset Condition
Upset condition shall generally follow the same combinations for operating, with the addition of
any special anchor force conditions of “Surge” and “Slug” loads.
d. Test Condition
Dead Test
◼ Load factor of dead load part of piping loads, empty weight of equipment, test fluid weight and cable
trays should be taken equal to the load factor of self-weight of a structure according local code.
◼ Load factor of operating load part of piping loads, operating weight of equipment, piping thermal loads
and upset condition loads shall be taken equal to the load factor of self-weight of a structure according
local code.
While pipe racks may have a simple function and geometry, due to the complex nature of the piping system
and associated friction and anchor loads, developing a detailed analytical model can be extremely tedious
and time consuming. For this reason, the design of pipe racks follows a more prescriptive procedure to
allow for simplified analytical model reducing the design time required.
For pipe racks that contain consistent geometry (OSBL Rack, ISBL Rack, Secondary Rack), it is preferred that
the analyzes be broken into a series of simple analytical models to represent the components of the pipe
rack. One file should be created to analyze and design the frames (“Bent”, “Portal”), and one file should be
created to analyze and design the braced bay. Additional files may be created to analyze and design specific
parts of the pipe rack such as access platforms, anchor locations and special supports.
Pipe racks that support large amounts of equipment, have large integrated platform levels, or inconsistent
geometry (Process Rack), may behave more like a process structure. In this case, the system should be
designed as a process structure where a full 3D analyzes is more appropriate. Special care should be taken
to ensure that piping friction and anchor loads are handled correctly when performing a 3D analyzes.
Pipe racks are normally designed as rigid frame bents with pinned or fixed bases in the transverse direction
and as braced frames in the longitudinal direction. Transverse braced bents shall be avoided unless clear
access ways under the pipe racks are not needed. Pipe rack layout with transverse braced bents shall
require customer's approval.
Transverse Beams
◼ Transverse beams shall be designed as members subject to combined axial and bending stresses.
◼ For flexural loads, the unbraced length shall be taken as the full length of the member.
◼ For axial loads, the unbraced length shall be taken as the full length of the member.
◼ Slenderness ratio for axial compression shall not exceed 200.
◼ For weak direction bending, beams shall be considered pinned ended members.
◼ The local deflection (in the direction of force) of beams supporting pipe anchors shall not exceed 1/4
inch (6mm) due to anchor forces without the concurrence of the pipe stress engineer.
◼ Concrete beams shall be 18 inches (450 mm) square minimum.
Stringers (“Struts”, “Longitudinal Beams”)
◼ Stringer beams shall be designed as members subject to combined axial and bending stresses.
◼ Stringer beams shall be normally pin ended.
◼ For flexural loads, the unbraced length shall be taken as the full length of the member.
◼ For axial loads, the unbraced length shall be taken as the full length of the member.
◼ Slenderness ratio for axial compression shall not exceed 200.
Longitudinal Bracing
◼ Longitudinal Bracing shall be designed as members subject to combined axial and bending stresses.
◼ For “Tee” and “Angle” profiles, member strength design shall account for P-Delta effects resulting from
connection eccentricity.
◼ For flexural loads, the unbraced length shall be taken as the full length of the member.
◼ For axial loads, the unbraced length shall be taken as the full length of the member.
◼ Slenderness ratio for axial compression shall not exceed 200.
◼ Slenderness ratio for axial Tension shall not exceed 400
1 For rack members supporting short piping spans connected to equipment that is located near the rack, stricter deflection criteria
(L/500) may be required. Consult with Piping Engineering group as needed for specific situations.
2 For racks supporting short piping spans connected to equipment that is located near the rack, stricter deflection criteria may be
required. Consult with Piping Engineering group as needed for specific situations.