The D5FSDA Slim Ductless System offers a range of sizes and features designed for efficient cooling and moisture removal, with specific guidelines for installation and safety. It emphasizes the importance of using trained professionals for installation and maintenance to prevent hazards associated with electrical and refrigerant systems. The system is suitable for various applications, including retrofits and modernization projects, providing flexibility and low sound levels.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
0% found this document useful (0 votes)
61 views50 pages

D5fsda19-01pd 1747151693881

The D5FSDA Slim Ductless System offers a range of sizes and features designed for efficient cooling and moisture removal, with specific guidelines for installation and safety. It emphasizes the importance of using trained professionals for installation and maintenance to prevent hazards associated with electrical and refrigerant systems. The system is suitable for various applications, including retrofits and modernization projects, providing flexibility and low sound levels.
Copyright
© © All Rights Reserved
We take content rights seriously. If you suspect this is your content, claim it here.
Available Formats
Download as PDF, TXT or read online on Scribd
You are on page 1/ 50

D5FSDA

Slim Ductless System


Sizes 6 to 58

Product Data
FAN PERFORMANCES AT VARYING STATIC PRESSURES —
LOW STATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27
. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31
FAN PERFORMANCES AT VARYING STATIC PRESSURES —
HIGH STATIC . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
MOISTURE REMOVAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
PIPING SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 46
REFRIGERANT SYSTEM DIAGRAM . . . . . . . . . . . . . . . . . . . . . 47
WIRING DIAGRAMS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 47
GUIDE SPECIFICATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 50

Fig. 1 – Sizes 06K-18K (Low Static)


SAFETY CONSIDERATIONS
Installing, starting up, and servicing air-conditioning equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roofs, elevated structures, etc.).
Only trained, qualified installers and service mechanics should install,
start- up, and service this equipment.
Untrained personnel can perform basic maintenance functions such as
coil cleaning. All other operations should be performed by trained
service personnel only.
When working on the equipment, observe the precautions in the
Fig. 2 – Sizes 9K-58K (High Static)
literature and on tags, stickers, and labels attached to the equipment.

NOTE: Images are for illustration purposes only. Actual models Follow all safety codes.Wear safety glasses and work gloves. Keep a
may differ slightly. quenching cloth and a fire extinguisher nearby when brazing. Use care in
handling, rigging, and setting bulky equipment.
TABLE OF CONTENTS Read these instructions thoroughly and follow all warnings or cautions
included in the literature and attached to the unit. Consult local building
Page codes and National Electrical Code (NEC) for special requirements.
Recognize safety information.
SAFETY CONSIDERATIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
INDUSTRY LEADING FEATURES / BENEFITS . . . . . . . . . . . . . 3 This is the safety - alert symbol .
MODEL NUMBER NOMENCLATURE . . . . . . . . . . . . . . . . . . . . . 5
STANDARD FEATURES AND ACCESSORIES . . . . . . . . . . . . . . 6 When you see this symbol on the unit and in instructions or manuals, be
DIMENSIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 7 alert to the potential for personal injury. Understand these signal words:
MAINTENANCE CLEARANCES . . . . . . . . . . . . . . . . . . . . . . . . . 11 DANGER, WARNING, and CAUTION. These words are used with the
SPECIFICATIONS (HIGH STATIC) . . . . . . . . . . . . . . . . . . . . . . . 12 safety- alert symbol.
SPECIFICATIONS (low Static) . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
APPLICATION DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 DANGER identifies the most serious hazards which will result in severe
WIRING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15 personal injury or death.
WIRING CONNECTIONS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
ELECTRICAL DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 WARNING signifies hazards which could result in personal injury or
CONTROL SYSTEM. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17 death.
WIRELESS REMOTE CONTROLLER . . . . . . . . . . . . . . . . . . . . . 17
CAUTION is used to identify unsafe practices which may result in
WIRED REMOTE CONTROLLER . . . . . . . . . . . . . . . . . . . . . . . . 17
minor personal injury or product and property damage.
AIR FLOW DATA . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17
SOUND PRESSURE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18 NOTE is used to highlight suggestions which will result in enhanced
FAN AND MOTOR SPECIFICATIONS. . . . . . . . . . . . . . . . . . . . . 18 installation, reliability, or operation.
SOUND PRESSURE TESTING METHOD . . . . . . . . . . . . . . . . . . 18
FAN PERFORMANCES AT VARYING STATIC PRESSURES . 18
D5FSDA: Product Data

! WARNING ! WARNING
ELECTRICAL SHOCK HAZARD EQUIPMENT DAMAGE HAZARD
Failure to follow this warning could result in personal injury or death. Failure to follow this caution may result in equipment damage or
Before installing, modifying, or servicing system, the main electrical improper operation.
disconnect switch must be in the OFF position. There may be more than Do not bury more than 36 in. (914 mm) of refrigerant pipe in the
1 disconnect switch. Lock out and tag switch with a suitable warning ground. If any section of pipe is buried, there must be a 6 in. (152 mm)
label. vertical rise to the valve connections on the outdoor units. If more than
the recommended length is buried, refrigerant may migrate to the
cooler buried section during extended periods of system shutdown.
! WARNING This causes refrigerant slugging and could possibly damage the
compressor at start-up.
EXPLOSION HAZARD
Failure to follow this warning could result in
death, serious personal injury, and/or property
damage.
! WARNING
Never use air or gases containing oxygen for ELECTRICAL SHOCK HAZARD
leak testing or operating refrigerant Failure to follow this warning could result in personal injury, death,
compressors. Pressurized mixtures of air or and/or property damage.
gases containing oxygen can lead to an Turn off the air conditioner and disconnect the power before
explosion. performing any installation or repairing. Failure to do so can cause
electric shock.
Installation must be performed by an authorized dealer or specialist.
! WARNING Defective installation can cause water leakage, electrical shock, or fire.
Installation must be according to the installation instructions.
This appliance is not intended for use by persons (including children) Improper installation can cause water leakage, electrical shock, or fire.
with reduced physical, sensory or mental capabilities, or lack of Contact an authorized service technician for repair or maintenance of
experience and knowledge, unless they have been given supervision or this unit. This appliance shall be installed in accordance with national
instruction concerning use of the appliance by a person responsible for wiring regulations.
their safety. Children should be supervised to ensure that they do not Only use the included accessories, parts, and specified parts for
play with the appliance. installation. Using non-standard parts can cause water leakage,
electrical shock, fire, and can cause the unit to fail.
Install the unit in a firm location that can support the unit’s weight. If
! WARNING the chosen location cannot support the unit’s weight, or the installation
is not done properly, the unit may drop and cause serious injury and
ELECTRICAL SHOCK HAZARD
damage. Install drainage piping according to the instructions in this
Failure to follow this warning could result in personal injury, death, manual. Improper drainage may cause water damage to your home and
and/or property damage. property. For units that have an auxiliary electric heater, do not install
Only use the specified wire. If the wire is damaged, it must be replaced the unit within 3 feet (1 meter) of any combustible materials.
by the manufacturer, its service agent or similarly qualified persons in If combustible gas accumulates around the unit, it may cause fire.
order to avoid a hazard. The product must be properly grounded at the
Do not turn on the power until all work has been completed.
time of installation, or electric shock may occur.
When moving or relocating the air conditioner, consult experienced
For all electrical work, follow all local and national wiring standards,
service technicians for disconnection and re-installation of the unit.
regulations, and the Installation Manual. Connect the cables tightly, and
Read the information for details in “indoor unit installation” and
clamp them securely to prevent external forces from damaging the
“outdoor unit installation” sections.
terminal. Improper electrical connections can overheat and cause fire,
and may also cause shock. All electrical connections must be made
NOTE: The air conditioner’s circuit board (PCB) is designed with a fuse
according to the Electrical Connection Diagram located on the panels
to provide over-current protection. The specifications of the fuse are
of the indoor and outdoor units.
printed on the circuit board, for example: T3.15AL/250VAC,
All wiring must be properly arranged to ensure that the control board T5AL/250VAC, T3.15A/250VAC, T5A/250VAC, T20A/250VAC,
cover can close properly. If the control board cover is not closed T30A/250VAC,etc.
properly, it can lead to corrosion and cause the connection points on the
NOTE: Only a blast-proof ceramic fuse can be used.
terminal to heat up, catch fire, or cause electrical shock.
Disconnection must be incorporated in the fixed wiring in accordance
with NEC, CSA and Local Codes. Do not share the electrical outlet
with other appliances. Improper or insufficient power supply can cause
fire or electric shock.
If connecting power to fixed wiring, an all-pole disconnection device
which has at least 3mm clearances in all poles, and have a leakage
current that may exceed 10mA, the residual current device (RCD)
having a rated residual operating current not exceeding 30mA, and
disconnection must be incorporated in the fixed wiring in accordance
with NEC, CSA and Local Codes.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
2
D5FSDA: Product Data

INDUSTRY LEADING FEATURES /


! WARNING BENEFITS
PERSONAL INJURY AND PROPERTY DAMAGE A PERFECT BALANCE BETWEEN BUDGET
HAZARD LIMITS, ENERGY SAVINGS AND COMFORT
For continued performance, reliability, and safety, the only approved
accessories and replacement parts are those specified by the equipment The D5FSDA series ductless systems are a matched combination
manufacturer. The use of non-manufacturer approved parts and
of an outdoor condensing unit and an indoor fan coil unit
accessories could invalidate the equipment limited warranty and result
connected only by refrigerant tubing and wires.
in a fire risk, equipment malfunction, and failure.
Please review the manufacturer’s instructions and replacement parts
The in-ceiling cassette fan coils are ideal for retrofit or
catalogs available from your equipment supplier.
modernization projects where a false ceiling is available. This
selection of fan coils permits inexpensive and creative solutions
Table 1 – Symbols Displayed on the Indoor or Outdoor Unit
to design problems such as:
This symbol shows that this • Add-ons to current space (an office or family room addition)
appliance used a flammable • Special space requirements
refrigerant. If the • When changes in the load cannot be handled by the existing
WARNING refrigerant is leaked and system
exposed to an external
• Historical renovations or any application where preserving the
ignition source, there is a
look of the original structure is essential.
risk of fire.
This symbol shows that the The ideal complement to your ducted system when it is
CAUTION operation manual should be impractical or prohibitively expensive to use ductwork. These
read carefully. compact indoor fan coil units take up very little space in the room
and do not obstruct windows. The fan coils are attractively styled
CAUTION This symbol shows that a to blend with most room decors. Advanced system components
service personnel should be incorporate innovative technology to provide reliable cooling
handling this equipment performance at low sound levels.
with reference to the
CAUTION installation manual. ECCENTRIC FAN DESIGN
New eccentric fan design improves the airflow at the air outlet, resulting
better performance.
This symbol shows that
information is available SLIM DESIGN
CAUTION such as the operating The industry lowest height is designed to be fitted into tight roof spaces.
manual or installation
manual. FLEXIBLE AIR INTAKE
The frame size of air inlet in rear and bottom is the same. It’s very easy
to switch to match different applications.
! WARNING BUILT-IN DRAIN PUMP(OPTIONAL)
FOR FLAMMABLE REFRIGERANTS The built-in drain pump can lift condensing water up to 29.5" (750mm).
Do not use means to accelerate the defrosting process or to clean, other EASY TO CLEAN
than those recommended by the manufacturer. You can pull out the filter from left, right, or from the bottom for easy
The appliance shall be stored in a room without continuously operating cleaning.
ignition sources (for example: open flames, an operating gas appliance
or an operating electric heater). LOW SOUND LEVELS
Do not pierce or burn. Be aware that refrigerants may not contain an When noise is a concern, the ductless systems are the answer.
odor. The indoor units are whisper quiet. There are no compressors
indoors, either in the conditioned space or directly over it, and
there is none of the noise usually generated by air being forced
Refrigerant through ductwork.
R-454B Safety Group R-454B
SECURE OPERATION
A2L If security is an issue, outdoor and indoor units are connected
WARNING – Risk of Fire due to Flammable Refrigerant only by refrigerant piping and wiring to prevent intruders from
Used. Follow Handling Instructions Carefully in crawling through ductwork. In addition, since outdoor units can
Compliance with National Regulations be installed close to an outside wall, coils are protected from
vandals and severe weather.
NOTE: Risk of Fire. Flammable refrigerant used. To be repaired
only by trained service personnel. Do not puncture
refrigerant tubing.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
3
D5FSDA: Product Data

FAST INSTALLATION FCC


This compact ductless system is simple to install. A mounting bracket is This device complies with part 15 of the FCC Rules. Operation is subject
standard with the indoor units and only wire and piping needs to run to the following two conditions: (1) This device may not cause harmful
between indoor and outdoor units. These units are fast and easy to install interference, and (2) this device must accept any interference received,
ensuring minimal disruption to customers in the home or workplace. including interference that may cause undesired operation.
This makes the ductless systems the equipment of choice, especially in
retrofit situations. FOR CLASS B DIGITAL DEVICE
BUILT-IN RELIABILITY NOTE: This equipment has been tested and found to comply with
the limits for a Class B digital device, pursuant to part 15
Ductless system indoor and outdoor units are designed to provide years of the FCC Rules. These limits are designed to provide
of trouble-free operation. reasonable protection against harmful interference in a
The in-ceiling cassette units include protection against freeze-up and residential installation. This equipment generates, uses and
high evaporator temperatures on heat pumps. can radiate radio frequency energy and, if not installed and
used in accordance with the instructions may cause
The condensing units on heat pumps are protected by a three minute time harmful interference to radio communications. However,
delay before the compressor starts the over-current protection and the there is no guarantee that interference will not occur in a
high temperature protection. particular installation. If this equipment does cause
harmful interference to radio or television reception, which
ECONOMICAL OPERATION can be determined by turning the equipment off and on,
The ductless system design allows individual room heating or cooling the user is encouraged to try t o correct the interference by
when required. There is no need to run large supply-air fans or chilled one or more of the following measures:
water pumps to handle a few spaces with unique load patterns. In • Reorient or relocate the receiving antenna
addition, because air is moved only in the space required, no energy is • Increase the distance between the equipment and the
wasted moving air through ducts. receiver
EASY-TO-USE CONTROLS • Connect the equipment into an outlet on a circuit
different from that to which the receiver is connected.
The in-ceiling cassette has microprocessor-based controls to
provide the ultimate in comfort and efficiency. The user friendly wireless • Consult the dealer or an experienced radio/TV
remote control provides the interface between user and the unit. technician for assistance.

SIMPLE SERVICING AND MAINTENANCE MODIFICATION


Removing the top panel on outdoor units provides immediate access to Any changes or modifications not expressly approved by
the control compartment, providing a service technician access to check the grantee of this device could void the user’s authority
unit operation. In addition, the draw-thru design of the outdoor section to operate this device.
means that dirt accumulates on the outside surface of the coil. Coils can
be cleaned quickly from inside using a pressure hose and detergent.
On all indoor units, service and maintenance expense is reduced due to
easy-to-use cleanable filters. In addition, these cassette systems have
extensive self-diagnostics to assist in troubleshooting.

INDIVIDUAL ROOM COMFORT


Maximum comfort is provided because each space can be
controlled individually based on usage pattern. The air sweep feature
provided permits optimal room air mixing to eliminate hot and cold
spots for occupant comfort. In addition, year-round comfort can be
provided with heat pumps.

FACTORY INSTALLED CONDENSATE LIFT PUMP


Customizing these ductless systems to your application is easily
accomplished. The factory installed condensate lift pump on the cassette
fan coil unit provides installation flexibility.

OPTIONAL WIRED CONTROLLER


AGENCY LISTINGS
All systems are listed with AHRI (Air Conditioning, Heating &
Refrigeration Institute), and ETL.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
4
D5FSDA: Product Data

MODEL NUMBER NOMENCLATURE

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
5
D5FSDA: Product Data

STANDARD FEATURES AND ACCESSORIES


FEATURES HORIZONTAL OR VERTICAL (UP FLOW)
Ease Of Installation INSTALLATION
Designed for maximum installation flexibility. The secondary drain
Mounting Brackets
(built-in) allows the unit to be mounted horizontally (sizes 06K-58K) or
Low Voltage Controls vertically (up flow) (sizes 06K-48K).
Comfort Features
Rear or Bottom Return (Bottom Return only sizes 06K-48K)
Vertical (Up flow) or horizontal installation
(Vertical only sizes 06K-48K)
Microprocessor Controls
Wired Remote Control
(7 Day Programmable KSCAN1401AAA)
Wireless Remote Control
Air Direction Control
Auto Restart Function
Cold Blow Protection On Heat Pumps
Freeze Protection Mode On Heat Pumps
A220735
Turbo Mode Fig. 3 – Unit mounted horizontally
Auto Changeover On Heat Pumps
Follow Me (Sense Temperature at remote)
Energy Saving Features
Outside Air Intake
Sleep Mode
Stop/Start Timer
46°F Heating Mode (Heating Setback)
Safety And Reliability
Indoor Coil Freeze Protection
Indoor Coil High Temp Protection in Heating Mode
Aluminum Golden Hydrophilic pre-coated fins
The unit is equipped with a refrigerant leak detection sensor
Ease Of Service And Maintenance
Cleanable Filters
Diagnostics
Liquid Line Pressure Taps
Application Flexibility
External Condensate Lift Pump shipped with the unit
(sizes 06K-18K)
Built-in Condensate Lift Pump (High Static, sizes 09K-58K) A220736
Fig. 4 – Unit mounted vertically (upflow)

OPTIONAL ACCESSORIES
ORDERING NO. DESCRIPTION FOR MODELS
Wired Controller for basic timer
KSACN1201AAA All Sizes
only operation
24 volt interface for third party
KSAIC0501230 All Sizes
thermostats (GEN 3)
24 volt interface for third party
KSAIC0601230 All Sizes
thermostats (MINI)

17401204010126 T1 Ambient Sensor Extension All Sizes

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
6
D5FSDA: Product Data

DIMENSIONS
Low Static
Table 2 – Low Static
MODEL
UNIT A B C C1 D E F G H I J K L M H1 H2 W1 W2
(KBTU/H)

06 mm 700 200 470 506 450 137 537 30 152 599 186 50 741 360 84 140 84 84
09 inch 27.56 7.87 18.50 19.92 17.72 5.39 21.14 1.18 5.98 23.58 7.32 1.97 29.17 14.17 3.31 5.51 3.31 3.31
mm 880 210 634 674 600 140 706 50 136 782 190 50 920 508 78 148 88 112
18
inch 34.65 8.27 24.96 26.54 23.62 5.51 27.80 1.97 5.35 30.79 7.48 1.97 36.22 20.00 3.07 5.83 3.46 4.41

1 in (25mm)

Fig. 5 – Size 06/09/12K

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
7
D5FSDA: Product Data

3.138 (80)
10.63 (270)

14.2 (360)
29.2 (741)

19.9 (506)
17.7 (450)
7.3 (186)

5.591 (142)
23.6 (599) 8.799 (224)
27.559 (700)

39.8 (1011)

27.6 (700)
21.1 (537)
7.9 (200)

6 (152)

Fig. 6 – Size 06/09/12K with external condensate pump (optional) Low Static

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
8
D5FSDA: Product Data

Fig. 7 – Size 18K with external condensate pump (optional) Low Static

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
9
D5FSDA: Product Data

High Static
Table 3 – Dimensions
FRESH AIR
AIR OUTLET AIR RETURN SIZE OF MOUNTED
MODEL UNIT OUTLINE DIMENSION INTAKE
OPENING SIZE OPENING SIZE LUG
OPENING SIZE
(KBtu/h) A B C D E F G H I J K L
06 mm 700 245 750 795 527 178 592 212 740 640 100 126
09
12 inch 27.6 9.6 29.5 31.3 20.7 7.0 23.3 8.3 29.1 25.2 3.9 5.0

18 mm 1000 245 750 795 827 178 892 212 1040 640 100 126

24 inch 39.4 9.6 29.5 31.3 32.6 7.0 35.1 8.3 40.9 25.2 3.9 5.0

36 mm 1200 300 750 795 1027 233 1092 267 1240 640 125 160
48 inch 47.2 11.8 29.5 31.3 40.4 9.2 43.0 10.5 48.8 25.2 4.9 6.3

mm 1400 380 800 845 1223 320 1272 330 1440 668 125 160
58
inch 55.1 14.9 31.5 33.3 48.1 12.6 50.1 13.0 56.7 26.3 4.9 6.3

Air outlet side view

Electric control box

Top

Bottom
Opposite pipe side view

Bottom Top Top view Pipe side view


Air inlet

4 hanging bracket
Drain connecting
Fresh pipe(for pump)
ai r intake

Drain pipe Test mouth & Test cover

Top Bottom
Liquid side
Gas side
Air outlet

Air inlet side view


Top

Bottom

Fig. 8 – Sizes 9K/12K, 18K, 24K, 36K, 48K, 58K High Static

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
10
D5FSDA: Product Data

MAINTENANCE CLEARANCES
Maintenance clearances provide access for system inspections.
NOTE: Always follow local codes.

Bottom Return
Blower/Motor Service Clearance Unit Width Service access Coil Connection Area
>11.81 in (30cm) Depth of unit Condensate Drain Piping Area
Condensate Pump Service Clearan
Sensor Service Clearance
Unit

B
>4 in (10cm)

7.8 in (20cm)

>11.8in 30cm
Service access
Filter Service Clearance Blower/Motor Service Clearance Access Panel
PCB Board Service Clearance 17.7 in (45cm) x 17.7 in (45cm
A220740
Fig. 9 – Maintenance Clearance
Capacity (Kbtu) B

6K thru 36K 11.81in.(30cm)

48K, 58K 15.75in.(40cm)

NOTE: If installed above a fixed ceiling, utilize a ceiling access panel the length and width of the unit, otherwise the blower components and/or the
entire unit cannot be removed.
If a single access panel is desired, the minimum dimensions should be:
• Single Access Panel Width: The width of the unit plus 2-inches on both sides
• Single Access Panel Length: The length of the unit plus 18-inches on the connection end and 2-inches on the opposite end.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
11
SPECIFICATIONS (HIGH STATIC)

D5FSDA: Product Data


Table 4 – High Static Specifications
Size 9K/12K 18K 24K 36K 48K 58K
Indoor Model Number D5FSDAH06XHK D5FSDAH18XHK D5FSDAH24XHK D5FSDAH36XHK D5FSDAH48XHK D5FSDAH58XHK
Power supply V;Ph;Hz 208/230V;1Ph;60HZ
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Material Galvanized sheet


Type FLBJ-170*130*15-47 FLBJ-170*195*15-47 FLBJ-170*195*15-47 FLBJ-207*233*15-51 FLBJ-207*233*15-51 FLBJ-250*300*15-51
INDOOR FAN inch 6.7 6.7 6.7 8.1 8.1 9.8
Diameter
SPECIFICATIONS mm 170 170 170 207 207 250
inch 5.1 7.7 7.7 9.2 9.2 11.8
Height
mm 130 195 195 233 233 300
Model ZKFN-165-10-1L ZKFN-165-10-1L ZKFN-165-10-1L ZKFN-400-8-1 ZKFN-560-8-4 ZKFN-560-8-4
Type DC DC DC DC DC DC
Input W 185 185 185 302.8 515 515
Max. input W 263 263 263 427.3 665 665
Output W 165 165 165 400 560 560
FLA A 1.5 1.8 2.2 3.2 4 4
INDOOR MOTOR
Rated HP HP 0.22 0.22 0.22 0.54 0.75 0.75
SPECIFICATIONS
Range of current Amps 0.63 ±10% 0.63 ±10% 0.63 ±10% 2.45 ±10% 4 ±10% 4 ±10%
Rated current Amps 0.63 0.63 0.63 2.45 4 4
Speed rev/min 780 / 744 / 708 820 / 760 / 700 920 / 835 / 750 790 / 730 / 670 1000 / 950 / 880 853 / 778 / 702
12

Rated RPM rev/min 780 820 920 790 1000 853


Insulation class B
Safe class IP20
Number of rows Rows 3 3 3 4 4 4
inch 0.197 0.197 0.197 0.276 0.276 0.276
Tube outside dia.
mm Φ5 Φ5 Φ5 Φ7 Φ7 Φ7
Inch
Nominal Tube Wall 0.0079 (0.2) 0.0079 (0.2) 0.0079 (0.2) 0.0091 (0.23) 0.0091 (0.23) 0.0091 (0.23)
(mm)
Tube Enhancement (Yes/No) Yes Yes Yes Yes Yes Yes
Tube Material Copper Copper Copper Copper Copper Copper
INDOOR Tube pitch(a)x row inch 0.77 x 0.46 0.77 x 0.46 0.77 x 0.46 0.83 x 0.53 0.83 x 0.53 0.83 x 0.53
REFRIGERANT pitch(b) mm 19.5 x 11.6 19.5 x 11.6 19.5 x 11.6 21 x 13.37 21 x 13.37 21 x 13.37
COIL
FPI 22 22 22 19 19 20
SPECIFICATIONS Fin Spacing
mm 1.2 1.2 1.2 1.4 1.4 1.3
Fin type Louvered
Fin Material Gold hydrophilic aluminum
Coil length x height x inch 20.67 x 13.82 x 1.37 32.48 x 13.82 x 1.37 32.48 x 13.82 x 1.37 40.35 x 14.88 x 2.11 40.35 x 14.88 x 2.11 48.23 x 18.19 x 2.11
width mm 525*351*34.8 825*351*34.8 825*351*34.8 1025*53.48*378 1025*53.48*378 1225*462*53.48
Face area ft2 1.98 3.12 3.12 4.17 4.17 6.09
Number of circuits # 6 9 9 9 9 11
Table 4 – High Static Specifications (Continued)

D5FSDA: Product Data


Size 9K/12K 18K 24K 36K 48K 58K
Turbo N\A N\A N\A N\A N\A N\A
Hi 32.5 36 40.0 45 51 52
SOUND DATA
Med 30.5 34.0 37.0 40 46 48
Indoor Sound Pressure Level dB(A)
Lo 28.5 32.0 35 34 42 42
Silent 26 28.0 29.5 31 40 41
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.

Turbo 419.08 706.32 853.47 1236.06 1648.08 2001.24


Hi 350.22 618.03 706.32 1059.48 1471.50 1706.94
CFM DATA
Med 256.04 529.74 618.03 941.76 1294.92 1412.64
Indoor air flow data
Lo 216.02 441.45 500.31 765.18 1059.48 1118.34
Silent 135.38 // // // // //
°F 60~90 60~90 60~90 60~90 60~90 60~90
ENVIRONMENTAL SPECIFICATIONS

Cooling Operating Range


Indoor Min - Max DB (°C) (16~32) (16~32) (16~32) (16~32) (16~32) (16~32)
Cooling Operating Range °F 59-84 59-84 59-84 59-84 59-84 59-84
Indoor Min - Max WB (°C) (15-29) (15-29) (15-29) (15-29) (15-29) (15-29)
Heating Operating Range °F 32~86 32~86 32~86 32~86 32~86 32~86
Indoor Min - Max DB (°C) (0~30) (0~30) (0~30) (0~30) (0~30) (0~30)
Non-operating environment °F -189 -189 -189 -189 -189 -189
Storage Temperature range
(DB) (°C) (-45-60) (-45-60) (-45-60) (-45-60) (-45-60) (-45-60)
Operation Humidity % 0-80 0-80 0-80 0-80 0-80 0-80

Ambient Humidity % 0-80 0-80 0-80 0-80 0-80 0-80


13
D5FSDA: Product Data

SPECIFICATIONS (LOW STATIC)


Table 5 – Low Static Specifications
SIZE 6K 09K/12K 18K
INDOOR MODEL NUMBER D5FSDAH06XAK D5FSDAH12XAK D5FSDAH18XAK
POWER SUPPLY V;Ph;Hz 208/230V;1Ph;60HZ 208/230V;1Ph;60HZ 208/230V;1Ph;60HZ
Material PP+GF28 PP+GF28 ABS-GF10
Type LX-143*107*15-41J LX-143*107*15-41J LX-154*158*15-41H
INDOOR FAN inch 5.6 5.6 6.1
Diameter
SPECIFICATIONS mm 143 143 154
inch 4.2 4.2 6.2
Height
mm 107 107 158
Model ZKFN-81-8-1 ZKFN-81-8-1 ZKFN-165-10-1L
Type DC DC DC
Input W 150 150 185
Max. input W 171.5 171.5 263
Output W 81 81 165
FLA A 0.9 0.9 1.2
INDOOR MOTOR
Rated HP HP 0.11 0.11 0.22
SPECIFICATIONS
Range of current Amps 0.35 ±10% 0.35 ±10% 0.63 ±10%
Rated current Amps 0.35 0.35 0.63
Speed rev/min 1070 / 990 / 910 1070 / 990 / 910 1100 / 900 / 700
Rated RPM rev/min 1070 1070 1100
Insulation class B B B
Safe class IP20 IP20 IP20
Number of rows Rows 3 3 3
inch 0.276 0.276 0.276
Tube outside dia.
mm Φ7 Φ7 Φ7
Nominal Tube Inch
0.00945 (0.24) 0.00945 (0.24) 0.00945 (0.24)
Wall (mm)
Tube
(Yes/No) Yes
Enhancement
Tube Material Copper
Tube pitch (a) x inch 0.83 x 0.53 0.83 x 0.53 0.83 x 0.53
INDOOR REFRIGERANT COIL row pitch (b) mm 21 x 13.37 21 x 13.37 21 x 13.37
SPECIFICATIONS
FPI 18 18 18
Fin Spacing
mm 1.4 1.4 1.4
Fin type Louvered Louvered Louvered
Fin Material Gold hydrophilic aluminum
Coil length x inch 20.67 x 8.27 x 1.58 20.67 x 8.27 x 1.58 27.36 x 9.92 x 1.58
height x width mm 525 x 210 x 40.11 525 x 210 x 40.11 695 x 252 x 40.11
Face area ft2 1.19 1.19 1.89
Number of circuits # 3 3 4
Indoor Min - °F 60~90 60~90 60~90
Max DB (°C) (16?32) (16?32) (16?32)
Cooling Operating Indoor Min - °F 59-84 59-84 59-84
Range Max WB (°C) (15-29) (15-29) (15-29)
Outdoor Min - °F -22~122 -22~122 -22~122
Max DB (°C) (-30~50) (-30~50) (-30~50)
ENVIRONMENTAL Indoor Min - °F 32~86 32~86 32~86
SPECIFICATIONS Heating Operating Max DB (°C) (0?30) (0?30) (0?30)
Range Outdoor Min - °F -22~75 -22~75 -22~75
Max DB (°C) (-30~24) (-30~24) (-30~24)
Non-operating environment Storage °F -189 -189 -189
Temperature range (DB) (°C) (-45-60) (-45-60) (-45-60)
Operation Humidity % 0-80 0-80 0-80
Ambient Humidity % 0-80 0-80 0-80

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
14
D5FSDA: Product Data

APPLICATION DATA WIRING


All wires must be sized per NEC (National Electrical Code) or CEC
UNIT SELECTION (Canadian Electrical Code) and local codes. Use the Electrical Data table
Select equipment to either match or handle slightly less than the MCA (minimum circuit amps) and MOCP (maximum over current
anticipated peak load. This provides better humidity control, fewer unit protection) to correctly size the wires and the disconnect fuse or breakers
cycles, and less part-load operation. respectively.
For units used in spaces with high sensible loads, base equipment
selection on the unit sensible load, not on the total anticipated load. SIZES 06-24 RECOMMENDED CONNECTION
Adjust for anticipated room wet bulb temperature to avoid undersizing METHOD FOR POWER AND COMMUNICATION
the equipment. WIRING
Power and Communication Wiring: The main power is supplied to the
UNIT MOUNTING (INDOOR) outdoor unit. The field supplied 14/3 power/ communication wiring,
NOTE: Follow local codes. from the outdoor unit to the indoor unit, consists of four (4) wires and
Refer to unit Installation Instructions for further details. provides the power for the indoor unit. Two wires are high voltage AC
power, one is communication wiring and the other is a ground wire.
Unit leveling - For reliable operation, units should be level in all planes. To minimize communication interference: If installed in a high
Clearance - Provide adequate clearance for airflow (Fig. 9). Electromagnetic field (EMF) area and communication issues arise, a
Unit location - Select a location which provides the best air circulation 14/2 stranded shielded wire can be used to replace L2 and (S) between
for the room. the outdoor and indoor units - landing the shield onto the ground in the
outdoor unit only.
These units should be positioned as accessible as possible above the
ceiling. The unit return and discharge should not be obstructed by Wiring Sizes 06-24
furniture, curtains, or anything which may cause unit short cycling or air
Cable Cable Size Remarks
recirculation.
Connection 3 wire + Ground 1Φ 208/230 V
Duct the unit in the middle of the selected wall (if possible). Duct 14AWG
Cable (Stranded wire is recommended)
towards an outside wall, if available, to make piping easier, and position
the unit so it faces the normal location of room occupants. SIZES 36-58 RECOMMENDED CONNECTION
UNIT MOUNTING (OUTDOOR) METHOD FOR POWER AND COMMUNICATION
Refer to the unit’s Installation Instructions for further details. WIRING
DO NOT install the indoor or outdoor units in a location with special Power and Communication Wiring: The main power is supplied to the
environmental conditions. For those applications, contact your ductless outdoor unit. The field supplied power wiring from the outdoor unit to
representative. the
indoor unit consists of three (3) wires and provides the power for the
MOUNTING TEMPLATE indoor unit. Two wires are high voltage AC power and one is a ground
Refer to the unit’s installation instructions for further details. wire. To minimize voltage drop, the factory recommended wire size is
14/2 stranded with a ground.
SUPPORT Communication Wiring: A separate shielded stranded copper
Adequate support must be provided to support the weight of all fan coils. conductor only, with a 600 volt rating and double insulated copper wire,
Refer to the base unit dimensional drawings which contain the location must be used as the communication wire from the outdoor unit to the
of the mounting brackets. indoor unit.
SYSTEM OPERATING CONDITIONS Please use a separate shielded 16GA stranded control wire.
OPERATING RANGE Wiring Sizes 36-58
Min/Max °F (°C)
Cable Cable Size Remarks
Cooling Heating
Connection
Indoor DB 63 / 90 (17 / 32) 32 / 86 (0 / 30) 14AWG 2 wire + Ground 1Φ 208/230V
Cable
Indoor WB 59 / 84 (15 / 29) -
Communication 2 wire stranded shielded
16AWG
NOTE: Reference the unit’s installation instructions for more Cable control wire
information.

DRAIN CONNECTIONS
Install drains to meet the local sanitation codes. The in-ceiling cassette is
supplied with a condensate lift pump that is capable of lifting the water
29.5in (750mm) above the top of the unit. A downward sloped
condensate drain pipe can be used to dispose of water.

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
15
D5FSDA: Product Data

CONNECTION LABELS - HIGH STATIC


! CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Wires should be sized based on NEC and local codes.

! CAUTION
EQUIPMENT DAMAGE HAZARD
Failure to follow this caution may result in equipment damage or
improper operation.
Be sure to comply with local codes while running wire from the indoor
unit to the outdoor unit.
Fig. 10 – 9K/12K, 18K, 24K Connection Label Every wire must be connected firmly. Loose wiring may cause the
terminal to overheat or result in unit malfunction. A fire hazard may
also exist. Ensure all wiring is tightly connected.
No wire should touch the refrigerant tubing, compressor or any moving
parts.
Disconnecting means must be provided and shall be located within
sight and readily accessible from the air conditioner.
Connecting cable with conduit shall be routed through the hole in the
conduit panel.

Fig. 11 – 36K Connection Label

Fig. 12 – 48K, 60K Connection Label

CONNECTION LABELS - LOW STATIC

Fig. 13 – 6K, 9K/12K, 18K Connection Label

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
16
D5FSDA: Product Data

WIRING CONNECTIONS
System Size 9K/12K 18K 24K 36K 48K 58K

V-Ph-Hz 208/230-1-60

Power Supply 3Wires: includes ground wire (Outdoor); 208/230V-1Ph-60Hz

Interconnection to Indoor Unit Yes

Shielded Wire (Yes/No) Optional Yes

ELECTRICAL DATA
System Size 9K/12K 18K 24K 36K 48K 58K

Power Supply V-Ph-Hz 208/230-1-60

Minimum Circuit Ampacity (MCA) A 3 3 3 3 3 3

Maximum Overcurrent Protection Ampacity (MOPA) A 15 15 15 15 15 15

CONTROL SYSTEM WIRED REMOTE CONTROLLER


The indoor unit is equipped with a microprocessor control to perform P/N KSACN1401AAA (included with the Unit)
two functions: 1. Wired remote controller used for system operation of all ducted
1. Provide safety for the system units.
2. Control the system and provide optimum levels of comfort and 2. Kit includes a wired remote controller but requires 16AWG or
efficiency. 18AWG stranded/shielded cable (field provided) for connecting the
The main microprocessor is located on the control board of the fan coil wired controller to this product. Refer to the KSACN1401AAA
unit (outdoor units have a microprocessor also) with thermistors located installation manual for complete instructions.
in the fan coil air inlet and on the indoor coil. Heat pump units have a 3. Connect the Ha/Hb wire terminals between the remote controller
thermistor on the outdoor coil. These thermistors monitor the system’s and the indoor unit.
operation to keep the unit within acceptable parameters and control the 4. Display in °F or °C and increments every 1°F or every 1°C.
operating mode.

WIRELESS REMOTE CONTROLLER


1. A wireless remote control is supplied for system operation of all
ducted units.
2. Each battery operated wireless (infrared) remote control may be
used to control more than one unit.

Fig. 15 – KSACN1401AAA

24V INTERFACE (OPTIONAL)


Allows the ductless system to be controlled using a third-party
thermostat:
• KSAIC0501230 (GEN 3)
• KSAIC0601230 (MINI)

Boos t Humidity
SMART PHONE CONTROL (OPTIONAL)
A Wi-Fi® Kit used for system operation of all ducted units through a
smart phone is available.

AIR FLOW DATA


Fig. 14 – Wireless Remote Controller Refer to “SPECIFICATIONS (HIGH STATIC)” on page 12 or

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
17
D5FSDA: Product Data

“SPECIFICATIONS (low Static)” on page 14. manually changed to the fan curves 1,2,3,4,5,6,7,8.
a. Press and hold Copy for approximately 3 seconds. The lower
right corner displays P:00, Press OK.
SOUND PRESSURE
b. Press “∧” to scroll through the menu. The lower right corner
Refer to “SPECIFICATIONS (HIGH STATIC)” on page 12 or shows SP, Press ?OK.
“SPECIFICATIONS (low Static)” on page 14.
c. Press “∧” or “∨” to scroll through the menu and select 1-8,
Press OK.
FAN AND MOTOR SPECIFICATIONS d. Press “Back” to exit the test mode.
Refer to “SPECIFICATIONS (HIGH STATIC)” on page 12 or
“SPECIFICATIONS (low Static)” on page 14. To Set Real-Time Constant Air Flow
Use the Automatic Airflow “AF” Adjustment function to realize
SOUND PRESSURE TESTING METHOD Real-time constant airflows.
a. Press and hold Copy for approximately 3 seconds. The lower
right corner shows P:00, Press “OK”.
Unit Outlet b. Press “∧” to scroll through the menu. The lower right corner
shows AF. Press “OK”.
c. Press “Back” to exit the test mode.
Indoor Unit
NOTE: T1, T2, T2b, T3, T4 are sub-menus for thermistors. DO
3.2 ft (1m) NOT select to set the external static pressure.
3.2 ft (1m)
NOTE: Before commissioning, check the power connection of the
machine, turn on the power, and keep the machine not
x working.

Microphone NOTE: If there is no change after airflow adjustment, perform the


Fig. 16 – Sound Pressure Testing Method setting again.

NOTE: Setting Static Pressure or Automatic Airflow need to use the


Wired Remote Controller.
USING THE KSACN1401AAA WIRED
CONTROLLER NOTE: Low static pressure series 06K, 09K, 12K, 18K models, SP
To Set Static Pressure Air Flow options can only be “ 1~4 ”.

The factory default setting is SP1, The external static pressure can be

FAN PERFORMANCES AT VARYING STATIC PRESSURES


The factory default setting is SP1. Airflows and fan curves applicable starting on production of Week 28 Year 2020 (Serial Number 2820V10001). For
previous serial numbers refer to previous revision of this document.

Low Static
Table 6 – 06K/09K
CFM (In.wc) 0 0.04 0.08 0.1 0.12 0.16 0.2 0.24 0.28 0.3 0.32 0.36 0.4
Turbo 446 421 370 331
H 404 373 313 260
SP4
M 358 324 265 214
L 315 278 208 141
Turbo 445 404 361 335
H 381 339 293 270
SP3
M 333 285 242 218
06K/09K

L 271 220 170 148


Turbo 430 412 374 340
H 374 353 311 271
SP2
M 318 297 258 213
L 267 242 204 153
Turbo 402 365 326 307
H 365 326 282 262
SP1
M 330 286 241 214
L 286 238 185 161

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
18
D5FSDA: Product Data

Table 7 – 12K

CFM (In.wc) 0 0.04 0.08 0.1 0.12 0.16 0.2 0.24 0.28 0.3 0.32 0.36 0.4

Turbo 521 489 437 391


H 466 434 376 318
SP4
M 418 378 312 261
L 373 325 249 183
Turbo 544 489 431 397
H 489 431 371 336
SP3
M 450 388 314 268
12K

L 398 331 245 190


Turbo 527 497 447 393
H 460 433 380 330
SP2
M 412 378 324 271
L 358 330 262 181
Turbo 490 461 428 408
H 426 384 343 318
SP1
M 374 327 285 260
L 320 260 202 173

Table 8 – 18K

CFM (In.wc) 0 0.04 0.08 0.1 0.12 0.16 0.2 0.24 0.28 0.3 0.32 0.36 0.4

Turbo 686 669 638 607


H 636 618 586 555
SP4
M 580 565 532 498
L 520 496 462 421
Turbo 678 650 620 612
H 627 591 563 553
SP3
M 571 537 509 500
18K

L 513 480 450 438


Turbo 724 690 642 603
H 662 631 584 556
SP2
M 611 581 536 504
L 554 525 484 452
Turbo 692 647 603 582
H 613 566 523 494
SP1
M 550 514 465 443
L 496 459 418 397

<300 CFM >450 CFM - Airflow below 300 CFM or above 450 cfm/ton

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
19
D5FSDA: Product Data

High Static
Table 9 – 09K

CFM 0 0.04 0.08 0.1 0.12 0.16 0.2 0.24 0.28 0.3 0.32 0.36 0.4 0.44 0.48 0.5 0.52 0.56 0.6 0.64 0.68 0.7 0.72 0.76 0.8
(In.wc)

Turbo 434 403 368 348


H 384 360 331 316
SP8

M 334 305 274 254


L 270 225 178 147
Turbo 460 415 370 346
H 389 354 322 295
SP7

M 325 298 271 244


L 277 237 196 149
Turbo 450 427 391 356
H 398 377 343 305
SP6

M 326 303 262 234


L 283 254 202 153
Turbo 483 437 391 368
H 391 357 324 306
SP5
09K

M 337 288 242 214


L 283 237 190 160
Turbo 478 454 405 361
H 406 385 348 303
SP4

M 361 342 305 256


L 300 278 237 174
Turbo 472 418 361 338
H 404 354 308 287
SP3

M 362 316 273 247


L 300 266 220 172
Turbo 468 448 409 354
H 400 381 343 305
SP2

M 348 330 297 260


L 292 271 234 200
Turbo 441 406 370 353
H 403 366 327 306
SP1

M 377 330 283 265


L 338 290 234 206

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
20
D5FSDA: Product Data

High Static (CONT)


Table 10 – 12K

CFM 0 0.04 0.08 0.1 0.12 0.16 0.2 0.24 0.28 0.3 0.32 0.36 0.4 0.44 0.48 0.5 0.52 0.56 0.6 0.64 0.68 0.7 0.72 0.76 0.8
(In.wc)

Turbo 500 477 445 414


H 459 432 401 374
SP8

M 407 380 353 334


L 353 334 290 242
Turbo 624 541 461 426
H 560 490 418 370
SP7

M 500 436 366 317


L 421 356 285 243
Turbo 607 574 501 447
H 484 465 427 383
SP6

M 401 380 350 327


L 332 307 271 242
Turbo 603 543 483 456
H 549 485 431 394
SP5
12K

M 484 420 356 322


L 407 347 284 248
Turbo 615 584 516 456
H 556 521 456 387
SP4

M 507 472 393 321


L 454 418 337 278
Turbo 647 562 474 427
H 559 483 415 380
SP3

M 504 426 347 303


L 438 376 297 247
Turbo 566 541 489 426
H 531 509 441 371
SP2

M 490 464 396 307


L 438 407 339 250
Turbo 489 457 428 411
H 441 402 360 338
SP1

M 408 356 307 284


L 372 312 248 230

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
21
D5FSDA: Product Data

High Static (CONT)


Table 11 – 18K
CFM 0 0.04 0.08 0.1 0.12 0.16 0.2 0.24 0.28 0.3 0.32 0.36 0.4 0.44 0.48 0.5 0.52 0.56 0.6 0.64 0.68 0.7 0.72 0.76 0.8
(In.wc)
Turbo 910 863 782 700
H 849 808 722 636
SP8

M 763 723 614 486


L 707 657 543 425
Turbo 918 828 725 677
H 823 739 653 610
SP7

M 769 684 590 536


L 669 609 531 463
Turbo 918 881 782 683
H 825 793 707 609
SP6

M 733 700 621 543


L 646 614 545 445
Turbo 918 831 735 692
H 876 768 655 606
SP5

M 813 707 602 534


18K

L 726 634 546 465


Turbo 926 892 810 735
H 877 829 723 619
SP4

M 795 744 637 519


L 696 644 538 424
Turbo 890 842 776 742
H 838 758 677 639
SP3

M 776 680 586 535


L 672 578 491 438
Turbo 856 830 783 718
H 805 778 725 641
SP2

M 738 703 625 534


L 434 414 368 315
Turbo 820 776 737 707
H 711 676 616 577
SP1

M 645 600 537 488


L 574 524 465 426

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
22
D5FSDA: Product Data

High Static (CONT)


Table 12 – 24K
CFM 0 0.04 0.08 0.1 0.12 0.16 0.2 0.24 0.28 0.3 0.32 0.36 0.4 0.44 0.48 0.5 0.52 0.56 0.6 0.64 0.68 0.7 0.72 0.76 0.8
(In.wc)
Turbo 1008 975 904 855
H 866 831 780 716
SP8

M 773 735 673 606


L 680 639 549 486
Turbo 1024 968 902 877
H 889 836 786 759
SP7

M 786 731 678 647


L 657 609 531 463
Turbo 1008 972 908 845
H 890 858 790 735
SP6

M 780 743 686 622


L 682 661 569 510
Turbo 1022 952 882 855
H 935 861 784 729
SP5

M 840 758 678 634


24K

L 749 650 556 519


Turbo 1008 965 904 839
H 916 886 829 753
SP4

M 846 808 724 624


L 766 720 637 522
Turbo 1001 909 846 810
H 898 832 757 731
SP3

M 843 773 691 652


L 719 660 589 527
Turbo 996 951 883 832
H 893 863 801 746
SP2

M 801 776 713 644


L 697 672 593 496
Turbo 998 929 863 827
H 891 811 742 715
SP1

M 762 692 614 588


L 633 572 497 461

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
23
D5FSDA: Product Data

High Static (CONT)


Table 13 – 36K
CFM 0 0.06 0.12 0.148 0.16 0.2 0.22 0.24 0.28 0.3 0.32 0.36 0.4 0.44 0.48 0.5 0.52 0.56 0.6 0.64 0.68 0.7 0.72 0.76 0.8
(In.wc)
Turbo 1699 1621 1493 1370
H 1595 1501 1374 1254
SP8

M 1477 1383 1257 1137


L 1342 1248 1121 1004
Turbo 1642 1524 1410 1333
H 1503 1380 1248 1195
SP7

M 1354 1225 1112 1030


L 1237 1092 926 794
Turbo 1570 1506 1418 1343
H 1442 1388 1298 1226
SP6

M 1295 1236 1151 1074


L 1107 1031 936 854
Turbo 1629 1514 1387 1327
H 1502 1398 1271 1189
SP5

M 1413 1283 1160 1071


36K

L 1277 1165 1018 921


Turbo 1548 1480 1392 1301
H 1413 1366 1268 1185
SP4

M 1260 1201 1112 1031


L 1092 1030 924 856
Turbo 1600 1501 1377 1311
H 1453 1363 1228 1151
SP3

M 1295 1183 1059 992


L 1183 1071 942 873
Turbo 1552 1424 1308 1239
H 1436 1305 1161 1061
SP2

M 1330 1177 999 889


L 1189 1009 809 680
Turbo 1567 1464 1349 1268
H 1304 1192 1046 970
SP1

M 1062 930 798 732


L 898 727 584 515

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
24
D5FSDA: Product Data

High Static (CONT)


Table 14 – 48K
CFM 0 0.06 0.12 0.18 0.2 0.24 0.28 0.3 0.32 0.36 0.4 0.44 0.48 0.5 0.52 0.56 0.6 0.64 0.68 0.7 0.72 0.76 0.8
(In.wc)
Turbo 2279 2161 1972 1779
H 2020 1948 1793 1629
SP8

M 1866 1751 1595 1423


L 1624 1569 1401 1184
Turbo 2226 2102 1913 1722
H 2020 1901 1746 1547
SP7

M 1836 1716 1566 1397


L 1583 1474 1248 1057
Turbo 2126 2061 1919 1745
H 1932 1866 1746 1590
SP6

M 1713 1669 1566 1423


L 1507 1474 1366 1230
Turbo 2067 1978 1825 1710
H 1891 1807 1669 1567
SP5

M 1705 1651 1536 1423


48K

L 1507 1457 1336 1230


Turbo 2032 1978 1856 1728
H 1861 1807 1699 1557
SP4

M 1705 1651 1554 1401


L 1507 1439 1324 1195
Turbo 3332 3120 2934 2828
H 3050 2820 2652 2521
SP3

M 2700 2462 2300 2170


L 2416 2202 2040 1951
Turbo 3410 3275 3110 2925 2862
H 3120 2985 2840 2645 2547
SP2

M 2776 2675 2510 2350 2278


L 2482 2355 2185 2020 1960
Turbo 1960 1881 1783 1675 1637
H 2820 2685 2520 2335 2272
SP1

M 2562 2425 2260 2075 2010


L 2272 2135 1970 1780 1720

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
25
D5FSDA: Product Data

High Static (CONT)


Table 15 – 58K
CFM 0 0.04 0.08 0.12 0.16 0.2 0.24 0.28 0.3 0.32 0.36 0.4 0.44 0.48 0.5 0.52 0.56 0.6 0.64 0.68 0.7 0.72 0.76 0.8
(In.wc)
Turbo 2484 2372 2107 1777
H 2203 2101 1848 1580
SP8

M 1985 1868 1609 1331


L 1784 1682 1420 1134
Turbo 2472 2295 2107 1998
H 2203 2026 1832 1699
SP7

M 2038 1850 1567 1325


L 1848 1599 1264 1024
Turbo 2472 2390 2239 2069
H 2203 2134 1995 1858
SP6

M 2008 1953 1775 1519


L 1848 1710 1447 1279
Turbo 2464 2331 2205 2129
H 2284 2154 2035 1958
SP5

M 2069 1952 1835 1739


58K

L 1894 1743 1546 1325


Turbo 2451 2390 2295 2182
H 2244 2191 2060 1897
SP4

M 2037 1947 1790 1650


L 1735 1655 1471 1203
Turbo 2353 2267 2144 2067
H 2149 2042 1907 1809
SP3

M 1945 1798 1660 1573


L 1696 1543 1360 1188
Turbo 2536 2447 2329 2225 2129 2012
H 2370 2260 2147 2036 1926 1802
SP2

M 2171 2060 1942 1825 1686 1533


L 2014 1891 1773 1630 1480 1324
Turbo 2473 2367 2277 2178 2070 1961
H 2167 2058 1949 1822 1709 1530
SP1

M 2035 1912 1793 1677 1516 1366


L 1899 1772 1648 1507 1338 1138

<300 CFM >450 CFM - Airflow below 300 CFM or above 450 cfm/ton

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
26
D5FSDA: Product Data

FAN PERFORMANCES AT VARYING STATIC PRESSURES — LOW STATIC


96 96
 
9. 9.
. .
 
3 3
2 2
 

 

'OX\UR[SK ),3
'OX\UR[SK ),3

 

 

 

 

 

 

 
              
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.

 .  .

3 3
 
2 2

 
'OX\UR[SK ),3

'OX\UR[SK ),3

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 17 – Low Static Pressure Curves – 6/9k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
27
D5FSDA: Product Data

96 96
 
9. 9.
. .
3 3
 
2 2

 
'OX\UR[SK ),3

'OX\UR[SK ),3
 

 

 

 
              
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.

. .

 3  3

2 2

 
'OX\UR[SK ),3
'OX\UR[SK ),3

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 18 – Low Static Pressure Curves – 12k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
28
D5FSDA: Product Data

96 96
 
9. 9.
. .
 3  3
2 2
 

 

'OX\UR[SK ),3
'OX\UR[SK ),3

 

 

 

 

 
              
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.

. .
 
3 3

2 2
 

 
'OX\UR[SK ),3

'OX\UR[SK ),3

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 19 – Low Static Pressure Curves – 18k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
29
D5FSDA: Product Data

6k/9k


9.
.

 3
2


'OX\UR[SK ),3










          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

12k


9.
.

3
2



'OX\UR[SK ),3












          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 20 – Low Static Pressure Curves – Constant Air Volume

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
30
D5FSDA: Product Data

18k


9.
.
 3
2




'OX\UR[SK ),3










          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 21 – Low Static Pressure Curves – Constant Air Volume

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
31
D5FSDA: Product Data

FAN PERFORMANCES AT VARYING STATIC PRESSURES — HIGH STATIC


9k
96

9.
96

. 9.

3 .

2 3

2



'OX\UR[SK),3



'OX\UR[SK),3














 

 
              
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.

 .  .

3 3
 
2 2

 
'OX\UR[SK),3

'OX\UR[SK),3

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.

 .  .

3 3
 
2 2

 
'OX\UR[SK),3

'OX\UR[SK),3

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 22 – High Static Pressure Curves - 9k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
32
D5FSDA: Product Data

96 96
 
9. 9.

 .  .

3 3
 
2 2

 

'OX\UR[SK),3
'OX\UR[SK),3

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Constant air volume


9.
.
 3
2




'OX\UR[SK),3










          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 23 – High Static Pressure Curves - 9k, Constant Air Volume

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
33
D5FSDA: Product Data

12k
96

9.
96

 . 9.
3  .

2 3

 2




'OX\UR[SK),3



'OX\UR[SK),3














 

 
              
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 
. .
 3  3
 2 2





'OX\UR[SK),3

'OX\UR[SK),3













 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 .  .

 3  3

 2 2


 

 
'OX\UR[SK),3

'OX\UR[SK),3

 

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 24 – High Static Pressure Curves - 12k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
34
D5FSDA: Product Data

96 96
 
9. 9.
 .  .

 3 3

2 2






'OX\UR[SK),3
'OX\UR[SK),3

 

 









 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Constant air volume


9.
.

3
2



'OX\UR[SK),3














          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 25 – High Static Pressure Curves - 12k, Constant Air Volume

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
35
D5FSDA: Product Data

18k
96
 96
9.
 
. 9.
 
3 .
 
2 3
 
2
 




'OX\UR[SK),3



'OX\UR[SK),3
















 
 
 
              
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 
 .  .
 3  3
 
2 2
 
 
 
'OX\UR[SK),3
'OX\UR[SK),3

 
 
 
 
 
 
 
 
 
 
 
 
 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 
 .  .
 3  3
 
2 2
 
 
 
'OX\UR[SK),3

'OX\UR[SK),3

 
 
 
 
 
 
 
 
 
 
 
 
 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 26 – High Static Pressure Curves - 18k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
36
D5FSDA: Product Data

96 96
 
9. 9.
 
 .  .

 3  3
 
2 2
 
 
 

'OX\UR[SK),3
'OX\UR[SK),3

 
 
 
 
 
 
 
 
 
 
 
 
 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Constant air volume


9.
.
 3
2




'OX\UR[SK),3










          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 27 – High Static Pressure Curves - 18k, Constant Air Volume

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
37
D5FSDA: Product Data

24k
96

9.
96

 . 9.
3  .
 2 3
 2



'OX\UR[SK),3



'OX\UR[SK),3















 

 
              
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.

 .  .

3 3
 
2 2
 

 
'OX\UR[SK),3

'OX\UR[SK),3

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.

 .  .

3 3
 
2 2
 

 
'OX\UR[SK),3

'OX\UR[SK),3

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 28 – High Static Pressure Curves - 24k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
38
D5FSDA: Product Data

96 96
 
9. 9.

 .  .

3 3
 
2 2
 

 
'OX\UR[SK),3

'OX\UR[SK),3
 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Constant air volume


9.
.

3
2



'OX\UR[SK),3














          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 29 – High Static Pressure Curves - 24k, Constant Air Volume

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
39
D5FSDA: Product Data

36k
96

9.
96
 
. 9.
 
3 .
 2  3
  2

 

 
'OX\UR[SK),3

 

'OX\UR[SK),3
 

 

 

 

 
 
 
 
 
 
                
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 
. .
 
3 3
 
2 2
 
 
 
'OX\UR[SK),3

'OX\UR[SK),3

 
 
 
 
 
 
 
 
 
 
 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 
. .
 
3 3
 
2 2
 
 
 
'OX\UR[SK),3

'OX\UR[SK),3

 
 
 
 
 
 
 
 
 
 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 30 – High Static Pressure Curves - 36k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
40
D5FSDA: Product Data

96 96
 
9. 9.
 
. .
 
3  3

2  2






'OX\UR[SK),3

'OX\UR[SK),3












 
 
 
 
 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Constant air volume


9.
 .

 3
2





'OX\UR[SK),3


















          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 31 – High Static Pressure Curves - 36k, Constant Air Volume

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
41
D5FSDA: Product Data

48k
96 96
 
9.
 9.

. .
 
 3 3

 2 2

 
 
 
 
'OX\UR[SK),3

'OX\UR[SK),3
 
 
 
 
 
 
 
 
 
 
 
 
 
                   
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 
 .  .
 3  3
 
2 2
 
 
 
 
'OX\UR[SK),3

'OX\UR[SK),3

 
 
 
 
 
 
 
 
 
 
 
 
 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 
 .  .
 
3 3
 
2  2

 
 


'OX\UR[SK),3

'OX\UR[SK),3














 
 
 
 
 
 
 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 32 – High Static Pressure Curves - 48K

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
42
D5FSDA: Product Data

96 96
 
9.  9.

 .  .
 
3  3

 2  2
 
 




'OX\UR[SK),3
'OX\UR[SK),3













 
 
 
 
 
 
 
 
 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Constant air volume


9.

.

3

2




'OX\UR[SK),3












          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 33 – High Static Pressure Curves - 48k, Constant Air Volume

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
43
D5FSDA: Product Data

58k
96 96

9. 
9.
 .
 .
3
 3

2
2






 
'OX\UR[SK),3

'OX\UR[SK),3
 

 

 

 

 

 

 

 
                   
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
 .  .

 3  3

 2 2


 

 
'OX\UR[SK),3
'OX\UR[SK),3

 

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 34 – High Static Pressure Curves - 58k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
44
D5FSDA: Product Data

96 96
 
9. 9.
 .  .
 3  3

 2 2


 

 
'OX\UR[SK),3

'OX\UR[SK),3
 

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

96 96
 
9. 9.
  .
.

 3  3

2  2


 

 
'OX\UR[SK),3
'OX\UR[SK),3

 

 

 

 

 

 

 

 
               
+^ZKXTGRYZGZOIVXKYY[XKOT=) +^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 35 – High Static Pressure Curves - 58k

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
45
D5FSDA: Product Data

Constant air volume


9.

 .
3
 2




'OX\UR[SK),3














          
+^ZKXTGRYZGZOIVXKYY[XKOT=)

Fig. 36 – High Static Pressure Curves - 58k, Constant Air Volume

MOISTURE REMOVAL
Liter/Hour 1.45 2 2.36 4.3 6.13
Moisture Removal
Gal/Day 9.2 12.7 15 27.3 38.9

PIPING SPECIFICATIONS
NAME MODEL LIQUID SIDE GAS SIDE REMARKS

6K, 9K, 12K Ø1/4in (Ø6.35mm) Ø3/8in (Ø9.52mm)


Pipes are not included in the
18K Ø1/4in (Ø6.35mm) Ø1/2in (Ø12.7mm) accessories so you will need to
Connecting Pipe Assembly
purchase them from the local
24K Ø3/8in (Ø9.52mm) Ø5/8in (Ø16mm) dealer.

36K, 48K, 58K Ø3/8in (Ø9.52mm) Ø3/4in (Ø19mm)

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
46
D5FSDA: Product Data

REFRIGERANT SYSTEM DIAGRAM

Fig. 37 – Refrigerant System Diagram

WIRING DIAGRAMS

Fig. 38 – Size 06K

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
47
D5FSDA: Product Data

Fig. 39 – Size 09/12/18/24K

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
48
D5FSDA: Product Data

Fig. 40 – Sizes 36/48/58K

Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
49
D5FSDA: Product Data

GUIDE SPECIFICATIONS
SLIM DUCTLESS SYSTEM
Size Range: 1/2 to 5 Ton Nominal Cooling and Heating Capacity
Model Number: D5FSDA

Part 1 - GENERAL
1.01 System Description The unit has the following functions (at a minimum):
Indoor, in-ceiling cassette, direct-expansion fan coils are matched with a 1. An automatic restart after a power failure at the same operating
heat pump outdoor unit. conditions as at failure.
2. A timer function to provide a minimum 24-hour timer cycle for the
1.02 Agency Listings system’s Auto Start/Stop.
Unit are rated per AHRI Standards 210/240 and listed in the AHRI 3. Temperature-sensing controls sense the return air temperature.
directory as a matched system. 4. Indoor coil freeze protection.
1.03 Delivery, Storage, And Handling 5. Wireless infrared remote control to enter set points and operating
conditions.
Units are stored and handled per manufacturer’s recommendations.
6. Dehumidification mode which provides increased latent removal
1.04 Warranty (For Inclusion By Specifying Engineer) capability by modulating system operation and set point
temperature.
Part 2 - PRODUCTS
7. A fan-only operation to provide room air circulation when no
2.01 Equipment cooling is required.
A. General: 8. Diagnostics to provide continuous checks of the unit operation and
warn of possible malfunctions. Any error messages are displayed at
Indoor, direct-expansion fan coil. Unit is complete with a
the unit.
cooling/heating coil, fan, fan motor, piping connectors,
electrical controls, microprocessor control system, and an 9. The fan speed control is user-selectable: high, medium, low, or
integral temperature sensing. microprocessor controlled automatic operation during all operating
modes.
B. Unit Cabinet:
10. Automatic heating-to-cooling changeover in the heat pump mode.
Unit cabinet is constructed of galvanized steel. The cabinet is
Control includes deadband to prevent rapid mode cycling between
fully insulated for improved thermal and acoustic performance.
heating and cooling.
C. Fans: 11. Indoor coil high temperature protection is provided to detect
The fan is the tangential direct-drive blower type with air intake excessive indoor discharge temperature when unit is in the heat
at the rear or bottom of the unit and discharge at the front. pump mode.
D. Coil: G. Filters:
The coil is a copper tube with aluminum fins and galvanized The unit has a filter track with factory-supplied cleanable filters.
steel tube sheets. Fins are bonded to the tubes by mechanical
expansion and specially golden hydrophilic pre-coated for H. Electrical Requirements:
enhanced wet-ability. A drip pan under the coil has a factory The indoor fan motor operates on 208-230V. Power is supplied
installed condensate lift pump and a drain connection for a hose from the outdoor unit.
attachment to remove condensate. I. Operating Characteristics:
E. Motors: The D5FSDA system has a minimum SEER2 (Seasonal
Motors are open drip-proof, permanently lubricated ball bearing Energy Efficiency Ratio) and HSPF at AHRI conditions, as
with inherent overload protection. Fan motors are 3-speed. listed on the specifications table.
F. Controls: J. Refrigerant Lines:
Controls consist of a microprocessor-based control system All units should have refrigerant lines that can be oriented to
which controls the space temperature, determines the optimum connect from the left, right or back of unit. Both refrigerant lines
fan speed, and runs self diagnostics. The temperature control must be insulated.
range is 62°F to 86°F (17°C to 30°C) in increments of 1°F or K. Refrigerant Leak Detection and Mitigation
1°C, and has a 46°F Heating Mode (Heating Setback). The System comes with a refrigerant leak sensor and mitigation
wireless remote controller, has the ability to act as the system.
temperature sensing location for room comfort.

© 2025 Carrier. All rights reserved. Edition Date: 03/25 Catalog No: D5FSDA19-01PD
A Proud Member of the Carrier Family Replaces: New
Manufacturer reserves the right to change, at any time, specifications and designs without notice and without obligations.
50